Regin CORRIGO L10 User Manual

Manual C ORRIGO L10 2002-11
CORRIGO L10 for use with air handling systems comes with or without LON communication option.
L10 Temperature controller for up to three sequences L10-LON Same as L10 bus also has LON Works communication.
COORIGO L10 is a new controller which has been designed to be easy to use and operate. It has been designed for use in less complex air-handling systems. The controller has a display and built in indicator on the front for alarm and is operated by means of clearly defined buttons. The controller has been designed for mounting on a DIN rail, in norm housing or on the front of a cabinet. The required functions are selected with the help of questions in normal script or by means of a code under the configuration menu depending on the type of application. The controller has a year-base clock and automatic summer/winter time changeover. The menu system works with different user-levels to show settings and to allow settings to be altered. This means that non-technical staff can feel secure while using the system since it is impossible, on the lower user-levels, to programme incorrect settings when checking operating status, parameter values, alarms etc. During normal operation, without pressing any buttons, the display also shows the most important operating statuses such as setpoint/current value, sequence-output control and time/date/version etc. We hope you will be satisfied with your CORRIGO and that it will provide you with simpler and more economic running of your control systems.
Models
Contents
Page 4 Technical data
5 Overview of in- and outputs
6 Installation and wiring 10 Handling and menu system 14 Configuration of functions 22 Description of inputs/outputs 24 Scheduler 25 Settings 27 Overview of alarm functions 28 Commissioning protocol 30 Configuration guide 31 Index
Manual C ORRIGO L10 2002-11
Technical data
Supply voltage 24 V AC +/- 15% Power consumption 3 VA Ambient temperature 0...50°C Storage temperature -40...+50°C Ambient humidity Max 90%RH Size (l x h x d) 105 x 110 (incl terminals) x 59 mm Protection class IP20, panel mount IP40 Mounting On DIN-rail in cabinet
On panel front with assembly kit FMC or FMK
Terminals Detachable screw terminal blocks, 2,5 mm
2
Sensor inputs PT1000. Digital inputs Potential free, closing to common feedpoint Analogue outputs 0...10 V DC, 5mA, short circuit protected Digital outputs 2 Triac controlled 24 V AC 0,5 A (max 1A pulse)
3 Relay controlled 230V AC 5A
Memory Flash (all settings are saved in case of power
failiure).
Real-Time Clock has 24H backup power. Display Backlit, LCD, 2 rows of 16 characters Alarm output Flashing/Constant lit light emitting diode (LED) and
relay output capable of switching 230V AC / 5A.
The alarm output can be set to filter low priority
alarms at certain times of the week.
This product conforms with the requirements of
European EMC standards CENELEC EN50081-1
and EN50082-1 and carries the CE mark.
Front panel assembly kit
When mounting CORRIGO L10 in a cabinet front use the FMK1 kit for easier mounting. The kit contains a front frame with see-through lid and an integrated mounting-rail. Protection class IP65. Reversable screw terminals can be ordered (article id: PLTL).
When mounting 2 CORRIGOs or one CORRIGO plus a relay unit next to each other in the cabinet front use the FMK2 mounting kit. It contains the same items as FMK1 above but in different dimensions.
Manual C ORRIGO L10 2002-11
Analogue outputs - 0...10 V
AO1 Y1 - Heat or cooling AO2 Y2 - Plate-exchg. or rotating,
damper, cooling or not used
AO3 Y3 - Cooling or not used
Digital outputs
DO1 DX-cooling stage 1 DO2 DX-cooling stage 2 or
Frostprotection interlock DO3 Control fans DO4 Control pump or electric heater
interlock DO5 Alarm output
Application example. A typical airhandling unit that the CORRIGO L10 can manage and control.
Overview
4 analogue sensor inputs for Pt1000 type sensor 4 digital inputs 3 analogue outputs 0...10 V 5 digital outputs L10 has temperature control with up to 3 sequences, optional DX cooling
CORRIGO - L10
Analogue inputs - temperature
AI1 Outdoor temp. Alt. external setpoint AI2 Room temp. AI3 Supply air temp. AI4 Frostguard temp. When heater is water
type or
Overheat sensor When electric heater
is used
Digital inputs - status and alarms
DI1 Fan alarm or Fan status DI2 Water heater pump status DI3 Extended runtime (timer/pushbutton),
(presence det.), smokealarm or external alarm
DI4 Cooler alarm, Exchg. alarm or external alarm
Manual C ORRIGO L10 2002-11
Installation
Corrigo L10 can be mounted on a DIN-rail in a panel or in a panel front. Panel front assembly kit (See page 2)
When CORRIGO L10 is mounted in a panel front the procedure is made easier by using the assembly kit FMC. This kit includes front frame in aluminium, support rail, nuts and bolts. Reversable screw terminals can be ordered (article id: PLTL). Alternatively FMK1 front mounting kit can be used. It has a transparent cover and meets the IP54 protection class.
If two CORRIGO L10 are placed adjacent to each other, use the FMCR assembly kit which is wider. It essentially contains the same things as the FMC kit. Alternatively, use the FMK2 front mounting kit (has the same properties as FMK1, only wider).
Supply voltage
The L10 is supplied with 24 V AC.
Inputs
The analogue sensor inputs (AI1-4) have a common reference point that is signal ground. The digital inputs (DI1 - 4) have a common reference point that is not the same signal as neutral (terminal 19) and must therefore not be tied together.
The signal neutral for analogue inputs and analogue outputs and the system neutral (terminal 25) are internally connected.
Outputs
Analogue outputs (0...10V) have signal neutral as common reference point, terminal
23. Digital outputs are divided into two categories: Outputs DO1 and DO2 are of triac type and have a common 24 V AC feed point at terminal 8. Outputs DO3...DO5 are of relay type and have a common pole at terminal 11.
Wiring
Connects sensors using a shielded twisted-pair wire. The shield should be connected to the earthrail in the cabinet and left unconnected at the sensor end.
AI1...AI4 analogue inputs AO1... AO3 analogue outputs Supply voltage 24 V AC
LON Service pin and LED (Model L10-LON) DI1...DI4 digital inputs DO1...DO5 digital outputs
Important!
LON network connector (Model L10-LON)
Manual C ORRIGO L10 2002-11
Wiring diagram L10
1 2
24V AC / 0.5A
24V AC
Supply Voltage
Terminals 19, 23 and 25 are internally connected
230V AC
5 A
AO1 Y1 0..10V DC AO2 Y2 0..10V DC AO3 Y3 0..10V DC M Signal neutral
3 4 5 6 7
8 9 10
11 12 13 14
15 16 17 18 19
20 21 22 23
24 25 26
Net A (L10-LON only) Net B(L10-LON only)
DI4 Alarms cooler/Exchg./Smoke/Ext. DI3 Ext.runtime/Smokealarm/Ext. alarm DI2 Pump monitor DI1 Fan malfuct.alarm/Fan indicator DI+ Common DI1..DI4
C1/2 24V AC Common DO1 and DO2 DO2 DX cool stage 2 / Fan interl. DO1 DX cool stage 1
24V AC Supply N 24V AC System neutral Protective earth
AI1 Outdoor temp./External setpoint AI2 Room temperature AI3 Supply air temperature AI4 Frost prot./Overheat prot. M Signal neutral
DO3..5 Common relay pole DO5 Alarm output DO4 Control pump /Electr. heating interlock DO3 Control fans
Manual C ORRIGO L10 2002-11
Digital inputs DI
CORRIGO L10 has 4 digital inputs, DI1...DI4 in order to to activate certain functions and to monitor alarms. These inputs must only be connected to potential free closing switches. These inputs should only be closed against the common point DI+ on terminal 7. Terminal 7 is NOT signal neutral; do not wire together.
DI1 Fan malfunction alarm or Fan status indicator.
- Fan alarm: Intended for use with, for example an overcurrent protection device. Activates the fan alarm after 2 seconds and stops the system.
- Fan status: Connect to a pressure switch or free contact in the fan motor relay. In order to activate the controlling outputs on the L10, the DI1 input must be activated within preset delay time. If this does not occur the system stops and alarm is activated. To check status for more than one fan, connect the status circuit breakers in series to DI1.
DI2 Water heater pump status.
Must be connected when water heater is used. Stopped pump interlocks the system.
DI3 Input for status monitoring or alarms. Following functions can be set:
- Extended runtime using timer or pushbutton. Can also be used with presence detectors.
- Alarm from smoke detectors
- External alarms
DI4 Input for various alarms. Following alarm types can be set:
- Cooler alarm
- Heat exchanger alarm
- Smoke alarm
- External alarm
AI Analogue inputs
CORRIGO L10 has 4 analogue inputs, AI1...AI4. These inputs are for use with temperature sensors of type Pt1000.
Exception: The AI4 input is used as a digital input when the unit is configured with overheat protection on an electric heater. In that case, connect this input to a poten­tial free closing contact.
Wire AI-inputs with sensor between respective input and common signal neutral (terminal 19).
AI1 Outdoor sensor
For example, type TG-R6/Pt1000.
AI2 Room sensor
For example, Ex type TG-R5/Pt1000.
AI3 Supply air sensor
For example, type TG-KH1/Pt1000.
AI4 Frost protection sensor when used with water heater, for example,
type TG-A1/Pt1000 or overheat protection thermostat when used with electric heater.
Connect this input to a potential free closing switch if configured as overheat protection input.
Wiring
Manual C ORRIGO L10 2002-11
Digital outputs DO
Corrigo has 5 digital outputs DO1...DO5. Outputs DO3...DO5 are potential free closing relay contacts, 230V AC, 5A. Outputs DO1...DO2 are of triac type for use with 24 V AC, 0.5A (1A short duration). The triac outputs have a common 24V supply pole (see picture in margin). For use with higher voltages and currents, use external relays.
DO1 Control DX-Cooling stage 1
DO2 Control DX-Cooling stage 2 or external fan control interlock for frost protection.
When used in systems with external fan control and frost protection it is advisable to interlock fans over this output to ensure that the fans are stopped in the event of a frost alarm.
DO3 Control fans
DO4 Control pump or electric heater interlock
When the system is configured with electric heater, DO4 is used to interlock the heater. For example: when a steprelay is used for heating control the heat will be activated during the cool-off sequence. To prevent this, interlock the heater via this output (DO4) to ensure that the heater is disconnected from power during the cool-off period.
When using electric heater the DO4 output is active, except when the system is idle and during the cool-off period.
DO5 Alarm output.
Analogue outputs AO
CORRIGO L10 has 3 analogue outputs, AO1...AO3. Outpul levels are 0...10 V DC, 5 mA. Short circuit protected. Reference point is terminal 23, signal neutral which is internally connected to
terminal 25, system neutral. The outputs AO1...AO3 make up the temperature controlling sequence. Function for
each output is determined by configuration setting but the order is always Y3 ? Y2 ? Y1 on increasing heat demand.
AO1 Y1 - Heating or cooling AO2 Y2 - Cooling, damper, Plate exchanger or rotating exchanger AO3 Y3 - Cooling
Wiring
8 9
10
DO2 DO1
C1/2
Manual C ORRIGO L10 2002-11
Up arrow - scrolls upwards in menu selections. In “Edit-mode“ this key is used to INCREASE the selected value. If the key is held in depressed position it will repeat.
Down arrow - scrolls downwards in menu selections. In “Edit-mode“ this key is used to DECREASE the selected value. If the key is held in depressed position it will repeat.
Used to cancel current operation or take a step one level up in the menu structure. The ESC key is also used to step backward in editable fields when in ”Edit-Mode” and menu contains multiple fields. Switch back and forth between editable fields with the OK and Esc keys.
(Enter) - Used to confirm selections in menus. When used in ”Edit-Mode” this key confirms set value and/or proceed to next editable field. Helpmenus: By pressing and holding down the OK key the controller will show context sensitive menu helptexts. This is not done if the controller is in ”Edit-Mode”.
Alarms - opens the alarm queue. Pressing this button will show active and unconfirmed alarms. The alarm indicator light emitting diode (LED) located above the key will light when there are alarms in the queue. If there is more than one alarm, use the ? and ? keys to scroll between them. Confirm alarms with the OK key. To cancel, press the Esc key.
Edit mode - Enters ”Edit-Mode” . If you have entered a menu and wish to change a value, for example: a setpoint, press this key. The controller will remain in the edit mode until operation is confirmed with the OK key or cancelled with the Esc key. The controller will abandon edit mode after approximately 1 minute of keyboard inactivity.
Change language
CORRIGO L10 has English as factory setting. Other languages can also be set. Activate the language select function by pressing and holding down the ? key while applying power to the controller. Menu for language selection is shown:
To change, press the ? key once. A cursor is lit at the current language selection. Change setting with the ? or ? keys. Confirm the new setting with the OK key.
When the language setting is changed or to continue operation without changing the setting, press the OK key and the controller will revert to its normal menu system.
?
Language/Språk English
Operating buttons
?
?
OK
Esc
?
?
Manual C ORRIGO L10 2002-11
Information series - scrolling display
During normal running when the buttons are not in use a series of menu pages is shown.The display alternates between a general display with product description and clock, setpoint/actual temperature and output status for the control outputs Y1,Y2 and Y3. The initial display shows the product name, date and time.
Setpoint/actual temperature display shows the current values as well as the control status for the output signals Y1,Y2,Y3.
NOTE: When the system is stopped, the setpoint value is displayed as --- , meaning the control function is disabled.
Program version number: By pressing and holding down the Esc key when the scrolling display is active, an info frame containing the current program version and LON neuron ID is shown.
The scrolling info is started when leaving the main menu with the Esc key or if the keyboard is left idle for more than 10 minutes. The sequence always starts by showing the first frame for 10 seconds and then continues with the next one pausing 3 seconds between each.
If not logged in, the menu system will jump to the login page as described above.
Main menu
Press the OK button.The scrolling information series will stop and the main menu will open immediately.
The main menu consists of a number of menu headings and what can be seen and done is governed by the log-in level of the user, as described below.
When the main menu is opened INPUTS is always displayed at the top of the dis­play.
The arrow ”>” pointing at INPUTS means that this heading is marked and pressing the OK button opens this menu and shows its submenus.
Arrows at the right of the display indicate that there are headings above and below the text that is currently being displayed. Move by using the arrow buttons.
The main menu has the following headings: Login
Configuration Shown only in level 3 Inputs Outputs Scheduler Settings Shown in level 2 & 3
* CORRIGO L10 * TU 14:10 AUT:ON
Setpoint/Actual 20,0°C / 20,0°C
Y1 / Y2 / Y3 0% / 45% / 0%
>Inputs ? Outputs ?
Manual C ORRIGO L10 2002-11
Alarms
When alarms are activated they are displayed in the alarm queue and also as a flashing red light on the display panel on the front of the controller in the event of an
alarm.
Alarm queue
To check the alarm queue press the alarm button ?. The display will then show active alarms, the date and time when the alarm became active and the alarm status.
Alarm status Flashing ”AL” indicates that the alarm is active and has not been
acknowledged. Steady ”AL” indicates that the alarm is active but has been acknowledged. Flashing ”OK” indicates that the alarm has aborted but has not been acknowledged.
Acknowledging an alarm
Alarms are acknowledged by means of the OK button which will remove the alarm from the alarm list. If the alarms are still active they will remain in the alarm list but the flashing will be replaced by a steady ”AL” and a steady red light on the alarm
signals.
Arrows on the right-hand side show when there are more alarms in the queue.
Login
CORRIGO has four different login levels to prevent the user from inadvertently changing any settings.
0 Without logging in all of the most important parameters can be viewed such as
input and output status, alarms in the alarm queue, setpoints etc. Alarms can also be acknowledged.
1 Main setpoint, time and date can be set. Outputs can be manually set and the
running mode can be set to manually on or off. Other parameters can be read off but not changed.
2 Gives access to most setpoints and running parameters such as outdoor
compensation, control alarm deviations, time delays etc.
3 The highest user level giving total access. Used by the commissioning engineer for
system configuration.
Menu information
If the user attempts to make changes that cannot be made or which lie outside his user level the controller will display the following information:
Unauthorized Make new logon
No changes in this menu
Alarm Chiller AL 980925 14:20
Manual C ORRIGO L10 2002-11
To log in to another user level press up/down arrow keys until the cursor arrow points at Login. Press OK, the login menu will be displayed.
To log in press the ? key and a marker will be shown on the first digit. Press the up/down arrow keys to change the value.
Press OK to move to the next digit. To return to the previous digit press Esc. After the last digit the code is evaluated. The operation can be aborted by means of Esc.
If an incorrect code is given an error message is displayed:
The correct code will result in an acknowledging message showing the login level.
After 2 seconds the system automatically returns to the main menu.
Factory preset codes
The codes for the three user levels are factory set as follows User level 1 1111 User level 2 2222 User level 3 3333
Changing login codes
The codes for the three user levels can easily be changed in user level 3. Enter the login menu:
The arrow means that there are menus below, press the arrow until the code for level 1, 2 or 3 is displayed.
Change the code using the ??key. The cursor will start on the first digit. Change using the arrow keys. To move to the next digit press the OK key. To return to the previous digit press Esc.
By pressing OK after the last digit the code will be registered. To abort use Esc. DO NOT FORGET TO MEMORIZE THE NEW CODES or to write them down. This is
especially important for user level 3. Should the code for level three be lost the sys­tem can only be opened by means of a code number which can be obtained from REGIN. This code number is time limited.
Important!
Set your code 0000 Level:0
Incorrect code Try again
Login OK Level: X
Set your code 0000 Level:3 ?
Code level 1 ? 1111 ?
Code level 2 ? 2222 ?
Code level 3 ? 3333
Login
Manual C ORRIGO L10 2002-11
Configuration
CORRIGO-L10 is adapted to the system at hand by selecting functions individually. All configuration options are set using explanatory menu texts.
Configuration codes
There is also the option of setting parameters by means of two configuration codes. This function is particularly useful and timesaving when a number of controllers are to be configured in the same way.
The first thing to be shown when the configuration menu is opened is the setting of the control function. Using the arrow up button the configuration code will be dis­played, and the arrow down button will give the parameters of the other configurations in plain text.
The code digits in the configuration code correspond to the script parameters below in numerical sequence. This means that the first digit in CONFIG CODE determines which control function the controller is to work with. The second digit refers to sequence etc.
In front of the corresponding selection in the script parameters there is a digit which corresponds to the code number in the configuration code. See the details below.
Guide for configuration code
There is also a special table to facilitate the choice of configuration code. This is always supplied together with the CORRIGO L10 instruction sheet.
In the table all the configuration parameters are shown as well as the selections that can be made. Basic selections are marked in bold type.
By going through the parameters and filling in the appropriate figure for each selection the configuration code can be obtained without difficulty. This can also act as a protocol of settings for CORRIGO L10.
Automatic restart after changing
When one or more parameters have been changed the controller will restart when the user leaves the configuration menu.
Example of a configuration guide.
Control funct. ? 0 Suppl.air cnt?
Config Code
0501.0000.010 ?
CONFIGURATION-Corrigo L10 A B C D . E F G H . I J K Config Code . .
A Control function
0. Supply air control 0
1. Supply air control with outdoortemp. compensation 1
2. Room control with cascaded supply air 2
3. Room control with min/max limitited supply air temperature 3
4. Room control with no supply air sensor 4
5. Supply air control/Room control. Outdoor temperature dependent 5
B Output sequence Y1, Y2, Y3 (AO1, AO2, AO3)
0. Heat / - / - 0
1. Heat / Cool / - 1
2. Heat / Damper / - 2
3. Heat / Damper / Cool 3
4. Heat / Plate exchg. / - 4
5. Heat / Plate exchg. / Cool 5
6. Heat / Rotating exchg. / - 6
7. Heat / Rotating exchg. / Cool 7
8. Cool / - / - 8
C Heater type
0. Water heater 0
1. Electric heater 1
D Frostguard (Only if Waterheater is selected)
0. Not activated 0
1. Y1 1
2. Y1 Automatic reset 2
E Shut-down mode (Only if Waterheater is selected)
0. No 0
1. Yes 1
F Pumpstop (Only if Waterheater is selected)
0. No 0
1. Yes 1
G Function for AI1
0. Outdoor temperature sensor 0
1. External setpoint 1
H Function for DI1
0. Fan malfunction alarm 0
1. Fan status 1
I Function for DI3
0. Not used 0
1. Timer for extended run (presence detector) 1
2. Pushbutton 2
3. Smoke detector alarm 3
4. External alarm 4
J Function for DI4
0. Not used 0
1. Frost build-up guard 1
2. Alarm rotating exchanger 2
3. Alarm chiller/cooler 3
4. Smoke detector alarm 4
5. External alarm 5
K Function for DO1, DO2
0. -- / -- 0
1. DX1 / -- 1
2. -- / Frostguard interlock 2
3. DX1 / Frostguard interlock 3
4. DX1 / DX2 4
5. DX Binary 5
Manual C ORRIGO L10 2002-11
A. Control function.
To change the parameter press the ??key, the marker appears by the digit. Press up or down arrow keys to change to another control function. The various functions are described below. When the correct function has been selected, press OK to store.
Application examples – flow diagrams
In all the examples below for the various control situations, a water heater has been depicted with frost protection sensor. All examples are drawn with rotating heat exchanger and water cooling. When configuring, the three output control sequences in CORRIGO L10 are set individually to suit the appropriate application .
Supply air temperature control
The temperature sensor Supply Air (AI3) controls the sequences to reach setpoint.
0. Supply air control
Configuration settings
A. CONTROL FUNCTION B. SEQUENCE Y1,Y2, Y3 C. HEATER TYPE D. FROST PROTECTION E. SHUT-DOWN MODE F. PUMPSTOP G. FUNCTION AI1 H. FUNCTION DI1 I. FUNCTION DI3 J. FUNCTION DI4 K. FUNCTION DO1/DO2 L. FACTORY SETTINGS. Used for resetting unit to factory settings (Not part of
the configuration code).
Control funct. ? 0 Suppl.air cnt?
Configuration
Frost protection sensor
Supply air sensor
Manual C ORRIGO L10 2002-11
Supply air control with outdoor temperature compensation
The temperature sensor Supply Air (AI3) controls the sequences to reach setpoint. The setpoint is compensated with respect to the temperature at outdoor temperature sensor (AI1). Parameters are set in the menu ”Settings” where menus for outdoor compensation will become accessible when this selection is made. Outdoor temperature compensation can be set with two breakpoints and two end positions, see the section ”Settings”.
Frost protection
sensor
Supply air
sensor
Outdoor
sensor
1. Supply air control with outdoor temperature compensation.
Frost protection
sensor
Room sensor
Supply air sensor
Room temperature control with cascade control of the supply air temperature
The temperature sensor Supply air (AI3) controls the sequence so that the setpoint is reached in the same way as with supply air control. The setpoint for the supply air temperature is determined by Room sensor (AI2) which, when heating is required, raises the setpoint for supply air according to the parameters set or, when cooling is required, lowers the setpoint.
The cascade factor (by how much the setpoint should be changed on a one-degree deviation from the set room-temperature) is set under ”Settings”, see the appropriate section.
NOTE: Cascade control is a PI-control with settable I-time (Factory setting 10 minu­tes) and works with setpoints between set minimum and maximum limitation. (Current setpoint for supply air temperature is shown in the menu for cascade factor).
Configuration
2. Room control with cascaded supply air.
Manual C ORRIGO L10 2002-11
Frost protection
sensor
Room sensor
Supply air sensor
Frost protection
sensor
Room sensor
Frost protection
sensor
Room sensor
Supply air sensor
Outdoor sensor
Supply air temperature control with outdoor temperature compensation or room control with min/max limiting. Outdoor temperature dependent switch­over
The outdoor temperature sensor controls the change-over between supply air control (winter) and room control (summer).
1) The supply air sensor (AI3) controls the sequences to reach setpoint. The setpoint is outdoor temperature compensated by means of the outdoor temperature sensor (AI1). Parameters are set under the menu ”Settings”.
2) The room sensor (AI2) controls the sequences to reach setpoint. The supply air temperature (AI3)can be min/max limited. Parameters are set under ”Settings”.
Room temperature control without supply air sensor
The temperature sensor Room (AI2) controls the sequences so that the setpoint is reached.
Room temperature control with minimum-maximum limitation of supply air temperature
The temperature sensor Room (AI2) controls the sequences so that the setpoint is reached. The temperature at the Supply air sensor (AI3) is kept within the minimum and maximum limits set.
3. Room control with min/max limiting of supply air temperature.
4. Room control with no supply air sensing
5. Supply air/ Room control. Outdoor temperature dependent.
Configuration
Manual C ORRIGO L10 2002-11
B. Sequence Y1/Y2/Y3
0. AO1 - Heating, AO2 - Not used (--), AO3 - Not used (--)
1. AO1 - Heating, AO2 - Cooling, AO3 - Not used (--)
2. AO1 - Heating, AO2 - Damper, AO3 - Not used (--)
3. AO1 - Heating, AO2 - Damper, AO3 - Cooling
4. AO1 - Heating, AO2 - Plate exchanger., AO3 - Not used (--)
5. AO1 - Heating, AO2 - Plate exchanger., AO3 - Cooling
6. AO1 - Heating, AO2 - Rotating exchanger., AO3 - Not used (--)
7. AO1 - Heating, AO2 - Rotating exchanger., AO3 - Cooling
8. AO1 - Cooling, AO2 - Not used (--), AO3 - Not used (--)
Output seq. ? 5 Heat/Plt/Coo ?
C. Heater type
0. Water heating
1. Electric heating type 1 (Cool-down period even at high temperature alarm)
2. Electric heating type 2 (No cool-down period at high temperature alarm) When electric heating has been selected input AI4 is set for closing contact
from high temperature limit. The configuration parameters applicable to water heated circuits: frost protection sensor, shutdown mode, pump stop, are not shown when electric heating is selected. The alarm output terminal on the electric heater overheat thermostat should always interlock the helper relay or the main heater relay (hardware interlock).
Heater type ?
0 Water heatin?
Overheat thermostat
Helper relay
Control
Control
18 19
CORRIGO L10 AI4
Suggested wiring for overheat thermostat. Circuit breakers drawn in idle state.
Main relay heat
Y1 Y2 Y3
Output level
Temperature
Setpoint
Output sequence Y1, Y2, Y3
The function of the outputs can be set individually. The sequence or­der, however, is always the same: At increasing heat requirement Y3 is always activated first, then Y2 and finally Y1.
Configuration
Manual C ORRIGO L10 2002-11
Controlling plate heat exchanger
Plate heat exchanger means that the output controls e.g. a damper actuator to vary the capacity of the heat exchanger.
Defrosting plate heat exchanger
Ice-build up sensor (pressure switch) is connected to DI4. On ice build-up the defrosting function is activated. The heat exchanger capacity is set to zero and the heating sequence, Y1 is used when heating is required. If this is not sufficient to maintain the setpoint the heat exchanger is permitted to go in with up to 30% of capacity.
The fans continue to operate. Defrosting will continue until the ice build-up sensor returns to normal, with a
switch-off delay of 10 minutes.
Controlling rotating heat exchanger
Alarm from a rotation sentinel can be connected to input DI4. CORRIGO L10 can be set to stop the fans on rotation sentinel alarm. Set under ”Settings”.
D. Frostprotection
0. No
1. Y1
2. Y1 Automatic reset (Reset is performed when the temperature rises to alarm point plus 5K, with a time delay of 10 minutes)
The alarm limit for the frost protection sentinel is set under ”Settings”. (Factory setting is 7°C.) The system begins to override the output signal to the valve when the temperature is 5K higher than the alarm limit. This means that the temperature when the output begins to be affected is 12°C for the factory alarm setting of 7°C.
E. Shutdown mode
Controls the heating valve to maintain a preset temperature at the frost protection sensor when the system is shut down. Shutdown temperature is set under ”Settings”. (Factory setting, 25°C). This function is only activated when the pump output (DO3) is active. It means that when the pumpstop function has been selected, as described in the paragraph below, the shutdown mode will be deactivated when the pump is stopped due to warm weather.
0. No
1. Yes
F. Pumpstop
This function requires an outdoor temperature sensor. The circulation pump is stopped when there is no heating demand (Y1 is less than 1%) and the outdoor temperature is above a preset temperature. The basic setting is +6°C. Stop delayed 15 minutes. Can be set under settings. Stopped pump is exercised 5 minutes every day at 12:00.
0. No
1. Yes
Frostprotection? 1 Y1 ?
Shutdown mode ? 0 No ?
Pumpstop ? 0 No ?
Configuration
Manual C ORRIGO L10 2002-11
DI3 ? 0 Not used ?
DI4 ? 0 Not used ?
AI1 ? 1 Outdoor ?
G. Function AI1
Normally AI1 is used as input for outdoor temperature sensor. If external set­point is desired, change setting and connect a setpoint adjust unit to AI1. When set to external setpoint, no other functions requiring outdoor temperature sensing can be used.
0. Not active
1. Outdoor sensor
2. External setpoint
H. Function DI1
Connect DI1 to thermal or overload guard(s), or, status indicator(s) circuit breakers located on relays or similar.
Fan alarm: Use this setting when connecting this input to a filter guard or similar. Activates fan alarm after preset time delay (2 seconds).
Fan status indicator: In order to start the control sequence and activate the analogue outputs DI1 has to be closed. When the fan control output (DO3) is activated, Corrigo L10 awaits a status running signal at DI1. If no status running signal is present at DI1 after a preset delay time, a fan alarm is activated and the system stops.
0. Fan alarm
1. Fan status
I. Function DI3
Input for use with various functions.
0.Input is not used
1.Timer for extended runtime. Presence detectors can also be used with this setting.
2.Pushbutton. System runs preset extended time when input temporarily closed.
3.Smoke alarm - closed contacts. Fans are stopped when the alarm is activated.
4.Smoke alarm - open contacts. Fans are stopped when the alarm is activated.
5.External alarm - closed contacts. Shown as ”Extern. alarm” in the alarm queue.
6.External alarm - open contacts. Shown as ”Extern. alarm” in the alarm queue.
J. Function DI4
Input can be used for variuos functions. To be able to use the plate exchanger defrosting function, the mode selector must be set to 1 (Heat exchanger frost detection).
0.Input is not used
1.Heat exchanger frost build-up detector
2.Alarm rotating exchanger - closing contacts
3.Alarm rotating exchanger - open contacts
4.Alarm cooling unit - closing contacts
5.Alarm cooling unit - open contacts
6.Smoke alarm - closing contacts. Fans are stopped when the alarm is activated.
7.Smoke alarm - open contacts. Fans are stopped when the alarm is activated.
8.External alarm - closed contacts. Shown as ”Extern. alarm” in the alarm queue.
9.External alarm - open contacts. Shown as ”Extern. alarm” in the alarm queue.
DI1 ? 0 Fan alarm ?
Configuration
Manual C ORRIGO L10 2002-11
K. Function DO1/DO2
When DX cooling is selected, at least one of the outputs Y2 or Y3 must be configured as cooling control output. In applications with supply air minimum limiting the minimum limit will be lowered by a preset amount when the DX-cooling is activated. See under ”Settings”.
DX Binary means that the two outputs are controlled in a binary sequence: 1, 2, 1+2.
If an outdoor sensor has been configured on AI1, DX-cooling will be blocked for outdoor temperatures lower than +12°C (fixed value).
When an external fan control switch is used in systems with frost protection, it is recommended that this breaker is routed via this interlock output. This is to prevent forced (manual) fan run when the frost alarm is activated.
0. -- / --
1. DX1 / --
2. -- / Frost interlock
3. DX1 / Frost interlock
4. DX1 / DX2
5. DX Binary stepping
DO 1 & 2 ? 0 -- / --????
L. Factory settings
Use this option to return Corrigo L10 to factory setting. Press the ? key, choose ”Yes” and confirm choice with the OK key. If you enter the ? -mode and change your mind, you can leave the edit
mode by pressing the Esc key and nothing will be changed. User login level will be reset to 0.
All of the configuration settings and values will be reset to their default values if this command is executed. Use with caution. Only authorized personnel may do this.
Basic setting ? No ?
Configuration
Manual C ORRIGO L10 2002-11
Inputs
This menu is used to inspect current values/states for the AI and DI inputs.
AI1 Outdoor temperature or external setpoint AI2 Room temperature AI3 Supply air temperature AI4 Frost protection sensor When frostprotection is selected with water heater
or Overheat protection When electric heater is used
DI1 Fan malfunction or fan status indicator. DI2 Pump status or electric heater interlock DI3 Input for extended runtime, smoke detector alarm or external alarm DI4 Input for alarm from chiller/cooler, exchanger, smoke detector alarm or external
alarm
Adjustment of analogue inputs
The analogue inputs are intended for use with Pt1000 type sensors. You can also inspect min and max values since last value reset. Refer to menu
branch ”Settings”. The presented value for inputs AI1...AI4 can be trimmed by ± 2 K when needed. Make a login at level 3, enter the appropriate input menu for AI1...AI4, press the ?
key and adjust the readout with the up/down arrow keys. When done, press OK. A filter factor can be applied if values appear unstable. Refer to menu branch
”Settings”. NOTE: CORRIGO L10 is always factory calibrated with respect to analogue inputs.
Adjustments are therefore normally not necessary. There is a rare possibility that f.ex. long wires cause erroneous readout. When in
doubt, measure the controlling value at the sensor with an accurate and calibrated instrument under stable conditions to eliminate any faulty sensor.
Min/Max viewing of temperature values
The four analogue inputs for temperature can keep track of the min/max temperature since the last reset was made. The ”Settings” section have a menu for activation of this option ”SHOW MIN/MAX”. To reset the min/max values, press the ? button and then the OK button. The min­and maxvalue will be set to the current measured value.
Filtering - analogue inputs
The analogue inputs are factory set with a filter factor of 1. This feature is used to suppress noise and hum that is introduced into the sensor circuits. The filter factor can be increased, but use caution so that the factor for the controlling sensor is not set too high so that it may jeopardize the control function.
Manual C ORRIGO L10 2002-11
Outputs
Shows present values for AO1...AO3 and DO1...DO5. Outputs can be set manually. This requires user level 1. If output is not set back to AUTO-mode within 15 seconds, an ”Output in manual” alarm is activated.
AO1 Y1 - Heat or Cooling AO2 Y2 - Damper, plate exchanger, rotating exchanger or cooling AO3 Y3 - Cooling
DO1 Control DX-Cooling stage 1 DO2 Control DX-Cooling stage 2 or frostprotection interlock DO3 Control fans DO4 Control pump DO5 Alarm output
Outputs AO2 and AO3 can also be shown as - ( 0 ), which means they are not used.
Manual override of outputs
Both analogue and digital outputs can be temporarily set to manual override mode for configuration and system set-up purposes.
1. Analogue outputs To enter manual override mode press the ? key and change to MAN with
the up/down arrow keys. Press the OK key to confirm, then use the up/down arrow keys again
to set the output level. Confirm setting with the OK. To go back to auto, press the ? key again and change to AUTO using the
up/down arrow keys. Confirm with the OK key. If the output is set to manual override mode for more than 15 seconds,
a manual override alarm is activated.
2. Digital outputs To enter manual override mode press the ? key and change to ON or OFF
with the up/down arrow keys. Then press the OK key to confirm setting. To go back to auto, press the ? key again and change to AUTO using the
up/down arrow keys. Confirm with the OK key. If the output is set to manual override mode for more than 15 seconds,
a manual override alarm is activated.
AO1 Heater Auto / 50% /5V ?
DO3 Fan ctrl ? Auto ON ?
Manual C ORRIGO L10 2002-11
Scheduler
CORRIGO L10 has a scheduler based on a one-week period. This means that the days of the week can be individually selected or deselected in the period. The scheduler can handle power losses for at least 24 hours without loss of data.
1. Clock. Change requires user level 1. The first menu manages current date, time and weekday.
3. Period 1, 2, 3 Change requires user level 2. CORRIGO L10 has 3 period settings for the weekly program. To change. press the ? key. By pressing the up/down arrow keys the
weekday at the cursor is toggled in and out of the period program. When day has been selected/deselected, press the OK key to confirm setting for this day and advance the cursor to the next day. Repeat this procedure for the remaining days in the period.
The time-of-day entries determine start and stop times. The one at the upper row is start time and the one at the lower row is stop time.
If other times of day for start and stop than those for period 1 iare required for some weekdays, set this using period 2 and 3 if needed.
If 24 hours continous run is desired, set both start and stop times to 00:00. Example: The system should run Mo - Fri 07:00-17:00 and Sat 08:00-13:00 Solution: Set period 1 to: and period 2 to:
External scheduler
If an external scheduler is used, disable all weekday entries in all periods such as described in the menu frame below.
3. Daylight saving time toggling
The scheduler normally works with automatic daylight saving time (DST) adjustment i the spring and in the autumn in accordance with the European DST rules. Spring: Current time is advanced 1 hour at 02:00 last Sunday in March. Autumn: Current time is set back 1 hour at 03:00 last Sunday in October. If automatic DST adjustment is not required set this configuration option to: ”0 No”.
0. No
1. Yes
Clock Th 980925 14:24?
Period 1 08:00? MTOTF___ -17:00?
Period 1 07:00? MTWTF___ -17:00?
Period 2 08:00? _____S__ -13:00?
Period 1 00:00? ________ -10:00?
Daylight saving? 1 Yes ?
Manual C ORRIGO L10 2002-11
Settings
All parameter settings have been gathered under this menu. Which parameters are shown or hidden depends on which control function has been
selected.
1. Running mode Also shown in the scrolling info series default menu. Shows time and
current run mode. when in AUTO mode, the controller decides what mode it is inbased on the scheduler or signal at DI3 which controls extended runtime.
Explanation of displayed run modes: AUT/HU Automatic/Startup. The unit is controlled by the internal, or by an
external clock. The system is in startup mode.
AUT/ON Automatic/On. The unit is controlled by the internal, or by an
external clock. The system is in normal running mode.
AUT/OFF Automatic/Off. The unit is controlled by the internal, or by an
external clock. The system is in off mode.
AUT/DEF Automatic/Defrost. The unit is controlled by the internal, or by an
external clock. Defrosting of the Plate-heatexchanger is proceeding.
AUT/CD Automatic/Cooldown. The unit is controlled by the internal, or by
an external clock. Cool-down of electric heater is proceeding.
When set to manual control AUTO is replaced by ON or OFF depending on the set mode.
Manual override for the run mode can be changed in this menu. The current mode is shown to the left. The actual status is shown to the right as explained above.
Run modes AUTO / ON / OFF can be set. To change, press the ? key. Then scroll to the desired modes with the up/down arrow keys. Press the OK key to confirm new setting.
When system is set to manual run mode for more than 15 seconds, alarm ”Manual run.mode” is activated.
2. Setpoint/Actual. Control function 0, 2, 3, 4.
3. Calculated setpoint/Actual. Control function 1, 5.
4. Setpoint Supply air. Control function 2, 3.
5. Setpoint Supply air / Compensation. Control function 1, 5.
6. Setpoint cascade. Control function 2.
7. Setpoint Room / Outdoor temperature. Control function 5.
Outdoor temp setting is the switchover point between supply air/Room control automatic selection.
8. Min/Max limits. Control function 2, 3, 5.
9. P-band/I.time/ Neutralzone. All control functions.
10. P-Band for sequence 2 and 3.
11. Room P-Band / I factor. Control function 5.
These factors control the P/I behaviour for room control in control function 5. The final parameter values for P and I are obtained by multiplying the factors above with the numbers set in paragraph 9.
12.Cascade factor/I-time room. Control function 2.
Explanation of control funktions
0. Supply air control
1. Supply air control with outdoortemp. compensation
2. Room control with cascaded supply air
3. Room control with min/max limited supply air temperature
4. Room control with no supply air sensor
5. Supply air control/ Room control. Outdoor temperature dependent
Manual C ORRIGO L10 2002-11
17.Setpoint frost protection Factory setting 7°C Adjustable 0...50°C
18.Setpoint shutdown mode Factory setting 25°C Adjustable 0...50°C
19.Pumpstop. Outdoor temperature when the circulation pump is allowed to stop if there is no demand for heat (i.e. heater output is less than 1%). Stop delay time can also be adjusted. Factory setting 6°C and 15 minutes Adjustable 0...20°C and 0...60 min
20.Cool-off run when electric heater is used Factory setting 120 seconds Adjustable 0...180 sec
21.Extended runtime when pushbutton is configured for DI3. Enter desired extended runtime. Factory setting 0 min Adjustable 0...180 min
22.Min amount of fresh air in supply when damper/mixer configured at Y2 Factory setting 0 % Adjustable 0...100 %
23.DX-Cooling. Start and stop delay times Factory setting 5 min and 5 min Adjustable 0...90 and och 0...90 min
24.Lowered minimum limit when using DX-cooling Factory setting 5K Adjustable 0...15K
25.Show Min/Max-temperatures for AI1...AI4. This function is disabled in the factory setting but can be enabled in this menu. Factory setting No Adjustable Yes / No
26.Filter factor for AI1...AI4. Factory set to 1. Adjustable 0...30
27.Alarm delay. Control deviation too large Adjustable 0...10K and 0...10 min
28.Deviation alarm. Outdoor temperature interval for which the control deviation alarm is enabled. Adjustable -40°C...40°C
29.Fan alarm delay time The alarm signal from the fans is delayed this amount of time prevent a
malfunction status while pressure is being built up during startup.
Settings - continued
Outdoor compensation
Values for compensation can be freely set but the breakpoints should be ordered with the highest (highest outdoor temp) at 4 and lowest (lowest outdoor temp) at 1. See diagram to the left. Set the outdoor temp for each breakpoint and the compensation in °C (+/-). The breakpoints have preset values which can easily be changed if needed.
For outdoor temperatures lower than BP1 or higher than BP4 the compensation is constant and equal to the values for BP1 and BP4 respectivly.
13.Outdoor compensation, breakpoint 1. Control function 1, 5.
14.Outdoor compensation, breakpoint 1. Control function 1, 5.
15.Outdoor compensation, breakpoint 1. Control function 1, 5.
16.Outdoor compensation, breakpoint 1. Control function 1, 5.
Manual C ORRIGO L10 2002-11
Overview - alarms
Fan malfunction DI1 Pump malfunction DI2 (Water heater only) Frost hazard AI4 (Water heater only) Overheat alarm AI4 (Electric heater only) Fire/smoke alarm DI3/DI4 (See configuration for each input) External alarm DI3/DI4 (See configuration for each input) Rotation alarm (exchg.) DI4 Cooler/chiller DI4 Output in manual override mode Control deviation too high Sensor error AI1 Sensor error AI2 Sensor error AI3 Sensor error AI4
Alarm out 08:00? MTOTF___ -17:00?
Exch.alarm stop? No
30.Blocking conditions for alarm output The alarm output can be blocked during certain times of day/week so that alarms
are not forwarded during these periods (for example: night time and weekends). Important alarms however, such as frostprotection, overheat protection and smoke alarms always activates the alarm output and will not be affected by this setting.
Time period and days for which to allow all alarms to be forwarded is set in this menu.
Example: Alarms are only allowed to activate the alarm output Monday to Friday between 08:00 - 17:00. The setting would be as follows:
NOTE: Even if the alarm output is being blocked the alarm is registered and placed in alarm queue and the indicator on the front will flash as normal.
31.Stop system on malfunctioning rotating exchanger If a rotating heat exchanger malfunctions and causes alarm, the system can be
stopped to prevent running with too low temperature. A malfunctioning exchanger can cause increasing heating costs which can be avoided by stopping the system when DI4 is activated.
Set to ”Yes” to stop system to stop the fans when alarm from exchanger is present.
This function is only relevant when rotating exchanger is configured.
Manual C ORRIGO L10 2002-11
Commissioning protocol
No value written means default value
Configuration Default setting Actual setting
Config code 0501.0000.000 ____._____._____ A. CONTROL FUNC. 0 Supply air ctrl _______________
B. SEQUENCE Y1/Y2/Y3 5 Heat/P-exchg./Cool _______________ C. HEATER TYPE 0 Water heater _______________ D. FROST PROTECTION 1 Y1 _______________ E. SHUT-DOWN MODE 0 No _______________ F. PUMPSTOP 0 No _______________ G. FUNCTION AI1 0 Not active _______________ H. FUNCTION DI1 0 Fan alarm _______________ I. FUNCTION DI3 0 Not used _______________ J. FUNCTION DI4 0 Not used _______________ K. FUNCTION DO1, DO2 0 -- / -- _______________
SET DEFAULT VALUES No Sets controller to default config
Settings
Setpoint / Actual 20.0 _______________ Min/Max limits 10.0°C / 30.0°C ________ / _____ PBand / I-time / Neutral zone 20K / 60s / 2K _____/_____/____ Room P/I Factors 0.5 / 2.0 _______________ Cascade factor / I-time 2.0 / --- _______________ Setpoint room / outdoor temp 22.0 / 12.0 _______________ Compensation breakpoint 1 -20°C / 0.0°C _______________ Compensation breakpoint 2 20°C / 0.0°C _______________ Compensation breakpoint 3 25°C / 0.0°C _______________ Compensation breakpoint 4 30°C / 0.0°C _______________
Site System Date Commissioned by:
Pg 1
Manual C ORRIGO L10 2002-11
Commissioning protocol
No value written means default value
Scheduler Default setting Actual setting
Period 1 MTWTF 08:00-17:00 _______________ Period 2 _______________ Period 3 _______________
more settings
1 Setpoint frost guard 7°C _______________ 2 Setpoint shut-down mode 25°C _______________ 3 Pumpstop. Outdoor temp - start 6°C _______________
stop delay 15 min _______________ 4 Cool-off runtime (electr. heater) 120 sec _______________ 5 Extended runtime, pushbutton 0 min _______________ 6 P-band Y2,Y3. 0,5 / 0,5 _______________ 7 Min fresh air using damper at Y2 0 % _______________ 8 DX-Cooling. start/stop min times 5 min and 5 min _______________ 9 Lowered min-limit using DX-cooling 5 K _______________ 10 Filter factor AI1...AI4. 1 _______________ 11 Control deviation limit 5K and 5 min _______________ 12 Deviation alarm, outdoor
temperature limits -20°C to 20°C _______________ 13 Show Min/Max-temp AI1...AI4 No _______________ 14 Alarm delay, exhaust fan status 30 sec _______________ 15 Alarm output allowed at times: Mo-su 00:00 - 24:00 _______________ 16 Stop system when rotating heat
exchanger fails No _______________
Site System Date Commissioned by
Pg 2
CONFIGURATION - Corrigo L10 A B C D . E F GH . I J K
Configuration code . .
A Control function
0. Supply air control 0
1. Supply air control with outdoor temperature compensation 1
2. Room control with cascaded supply air temperature control 2
3. Room control with min/max limiting of supply air temp. 3
4. Room control, single sensor 4
5. Supply air control/Room control. Outdoor temp dependent 5
B Output sequences Y1, Y2, Y3
0. Heating / - / - 0
1. Heating / Cooling / - 1
2. Heating / Dampers / - 2
3. Heating / Dampers / Cooling 3
4. Heating / Plate exchanger / - 4
5. Heating / Plate exchanger / Cooling 5
6. Heating / Rotating exchanger / - 6
7. Heating / Rotating exchanger / Cooling 7
8. Cooling 8
C Heater type
0. Water heater 0
1. Electric heater Type 1 1
2. Electric heater Type 2 2
D Frost protection
0. Not active 0
1. Active on Y1 1
2. Active on Y1 with automatic alarm reset 2
E Shutdown mode
0. No 0
1. Yes 1
F Pump stop
0. No 0
1. Yes 1
G Function AI1
0. Not activated 0
1. Outdoor temperature sensor 1
2. External setpoint device 2
H Function DI1
0. Fan alarm 0
1. Fan indication 1
I Function DI3
0.Not active 0
1. Timer 1
2. Pushbutton 2
3. Alarm, smoke detector, contact closes 3
4. Alarm, smokedetector, contact opens 4
5. External alarm, contact closes 5
6. External alarm, contact opens 6
J Function DI4
0. Not active 0
1. Freeze-up protection plate-exchanger 1
2. Alarm, rotating exchanger, contact closes 2
3. Alarm, rotating exchanger, contact opens 3
4. Alarm, chiller, contact closes 4
5. Alarm chiller, contact opens 5
6. Alarm, smoke detector, contact closes 6
7. Alarm smoke detector, contact opens 7
8. External alarm, contact closes 8
9. external alarm, contact opens 9
K Function DO1, DO2
0. -- / -- 0
1. DX1 / -- 1
2. -- / Frost interlock 2
3. DX1 / Frost interlock 3
4. DX1 / DX2 in sequence 4
5. DX1 / DX2 binary 5
Numbers in bold indicate factory settings
Index
A
Adjustment of analogue inputs 22 AI Analogue inputs 8 Alarms 12 Analogue outputs AO 9
C
Change language 10 Change setpoint 11 Changing login codes 13 Clock 24 Commissioning protocol 28 Configuration 14 Configuration settings 15 Control function 15
D
Daylight saving time toggling 24 Digital inputs DI 8 Digital outputs DO 9
E
Extended runtime 20 External scheduler 24
F
Factory preset codes 13 Factory settings 21 Front panel assembly kit 4 Frostprotection 19 Function DI1 20 Function AI1 20 Function DI3 20 Function DI4 20 Function DO1/DO2 21
H
Heater type 18
I
Information series - scrolling display 11 Inputs 22 Installation 6 Introduction 3
L
Login 12
M
Main menu 11 Manual override of outputs 23 Menu information 12
O
Operating buttons 10 Outputs 23 Overview 5 Overview - alarms 27
P
Period 1, 2, 3 24 Program version number 11 Pumpstop 19
R
Room temperature control with cascade
control of t 16
Room temperature control with minimum-
maximum limi 17
Room temperature control without supply
air sensor 17
Running mode 25
S
Scheduler 24 Sequence Y1/Y2/Y3 18 Settings 25 Shutdown mode 19 Supply air control with outdoor tempera-
ture compen 16 Supply air temperature control 15 Supply air temperature control with
outdoor temper 17 Supply voltage 6
T
Table for configuration code 14 Technical data 4
V
Wiring 6 Wiring diagram L10 7
Loading...