Manual C ORRIGO L10 2002-11
Settings
All parameter settings have been gathered under this menu.
Which parameters are shown or hidden depends on which control function has been
selected.
1. Running mode
Also shown in the scrolling info series default menu. Shows time and
current run mode. when in AUTO mode, the controller decides what mode
it is inbased on the scheduler or signal at DI3 which controls extended
runtime.
Explanation of displayed run modes:
AUT/HU Automatic/Startup. The unit is controlled by the internal, or by an
external clock. The system is in startup mode.
AUT/ON Automatic/On. The unit is controlled by the internal, or by an
external clock. The system is in normal running mode.
AUT/OFF Automatic/Off. The unit is controlled by the internal, or by an
external clock. The system is in off mode.
AUT/DEF Automatic/Defrost. The unit is controlled by the internal, or by an
external clock. Defrosting of the Plate-heatexchanger is
proceeding.
AUT/CD Automatic/Cooldown. The unit is controlled by the internal, or by
an external clock. Cool-down of electric heater is proceeding.
When set to manual control AUTO is replaced by ON or OFF depending on
the set mode.
Manual override for the run mode can be changed in this menu. The current
mode is shown to the left. The actual status is shown to the right as explained
above.
Run modes AUTO / ON / OFF can be set. To change, press the ? key.
Then scroll to the desired modes with the up/down arrow keys.
Press the OK key to confirm new setting.
When system is set to manual run mode for more than 15 seconds, alarm
”Manual run.mode” is activated.
2. Setpoint/Actual. Control function 0, 2, 3, 4.
3. Calculated setpoint/Actual. Control function 1, 5.
4. Setpoint Supply air. Control function 2, 3.
5. Setpoint Supply air / Compensation. Control function 1, 5.
6. Setpoint cascade. Control function 2.
7. Setpoint Room / Outdoor temperature. Control function 5.
Outdoor temp setting is the switchover point between supply air/Room control
automatic selection.
8. Min/Max limits. Control function 2, 3, 5.
9. P-band/I.time/ Neutralzone. All control functions.
10. P-Band for sequence 2 and 3.
11. Room P-Band / I factor. Control function 5.
These factors control the P/I behaviour for room control in control function 5.
The final parameter values for P and I are obtained by multiplying the factors
above with the numbers set in paragraph 9.
12.Cascade factor/I-time room. Control function 2.
Explanation of control
funktions
0. Supply air control
1. Supply air control with
outdoortemp.
compensation
2. Room control with
cascaded supply air
3. Room control with
min/max limited supply
air temperature
4. Room control with no
supply air sensor
5. Supply air control/
Room control. Outdoor
temperature dependent