Regin Corrigo E User Manual

Corrigo E
Corrigo E
Pre-programmed with all applications and languages
Ventilation, heating or boiler control
• Model for expansion units
• Model with integrated web server
• Android application for mobile control
Corrigo E is a range of digital controllers for ventilation, heating or boiler control. The controllers can be used stand-alone or as part of a network.
Corrigo E is easy to install and adjust according to your needs. The controller fits on a standard DIN rail or into a standard housing.
Corrigo E is available with or without display. Models without display can be mounted in a cabinet and be controlled via the external display unit E-DSP, which functions as a remote control.
Corrigo E - The easy way to perfect control
Corrigo E makes every step from installation to operation and maintenance easier than ever before. Just connect the controller, adjust the pre-installed applications if needed and start up.
The model program has a logical order, which is helpful when you choose a model for you application. It will also be easier to get the right functionality at the right price.
Communication
Corrigo E is easy to integrate with existing products. All models have a port for communication with a PC. Other standards are available. Read more in the section Corrigo E with communication on page 3.
Model with web server and TCP/IP
Corrigo E for ventilation and heating applications is also available in a web version with integrated web server and TCP/IP communication. Read more about the possibilities in the section Corrigo E with communication on page 3.
Android application, Regin Building Access
Web models from version 3.0-1-06 have an integrated android application for control from e.g. a mobile phone. The application can be used for ventilation and heating.
Model for expansion units (ventilation and heating)
Corrigo E models from version 3.0 and up are available with two communication ports. Port 1 is used in the same way as before, i.e. for connection to SCADA systems and E tool. Port 2 is used for expansion units. Read more in the section Corrigo E with communication on page 3.
Applications
• Ventilation control
For control of air handling units with temperature control (up to 4 sequences), 1- or 2-speed operation, or alternatively, pressure or air flow control of supply air fan and extract air fan, humidity control and other functions within ventilation.
• Heating control
For control of up to three heating systems and one or two hot water circuits. Pump control, pressure control of pump, hot water preparation, inputs for water and energy meter.
• Boiler control
For control of boilers with up to four boilers in sequence, where each boiler can have single or double burners. Also for control of up to three outdoor temperature controlled heating systems and one domestic hot water system, with the same functions as for application heating above.
E tool
E tool is a PC-based software which makes it possible to configure and supervise an installation via a graphical interface. Read more in the section To use Corrigo E on page 2.
Display
The display is backlit and has 4 rows of 20 characters. The illumination is normally off, but is activated as soon as a button is pressed. It is turned off after a certain period of inactivity.
revision
02 2013
Version 3.1 (ventilation), 3.1 (heating),
1.1 (boiler).
Controllers for heating, boiler and ventilation applications in buildings.
2
Corrigo E
To use Corrigo E
Each model of Corrigo E is loaded with all applications (ventilation, heating and boiler control). At the first start-up, you choose application and language. Thereafter, the unit should be configured. Inputs and outputs must be assigned and all relevant parameters must be set to adapt the application to the current operation mode.
Configuration
Corrigo E can be configured in different ways:
Via the display
Directly on the controller panel in “step-by-step menus”. Operation status, alarms and values are shown in the backlit display.
E tool
Corrigo E tool is a PC-based configuration software with graphical user interface. The program gives you a very good overview of the settings, which will save time.
Using E tool, all settings can be done on the computer and then be downloaded to the Corrigo. An infinite number of configurations can be stored in the computer memory for later use.
When E tool is used for configuration, a file is saved which documents the settings. This can easily be distributed when needed via for example e-mail.
E-DSP
The external display E-DSP can be ordered with 3 or 10 m cable length. To handle greater distances than 10 m, E-DSP can also be used together with the repeaters E0-R and E0-R230K, for distances up to 1000 m (RS485).
Front panel
Corrigo E has a clear and functional front panel for simple operation of the controller. All information is shown in the backlit display.
LEDs
There are two LEDs on the front:
The alarm LED is marked with a symbol
The "write enable" LED is marked with a symbol
Buttons
All functions can be configured by using the display information and buttons on the controller.
OK
C
Access rights
Corrigo E has four different log on levels.
• Admin – gives full read/write access to all settings and parameters in all menus.
• Service – gives access to all menus except the submenus "Configuration"/"In- and Outputs" and "Configuration"/"System".
• Operator – gives read-only access to all settings and parameters and write access to all settings and parameters in all menus except Configuration.
• Basic level – gives read-only access to all settings and parameters.
Scheduler
Corrigo has a year-based clock function. This means that a week-schedule with holiday periods for a full year can be set. The clock has automatic summertime/wintertime change-over.
The controllers have individual schedules for each weekday plus a separate holiday schedule.
Holiday period
Up to 24 individual holiday periods can be configured. Holiday schedules take precedence over other schedules.
Running periods
Each day has up to two individual running periods. For two-speed fans and pressure controlled fans, there are daily individual schedules for normal speed and reduced speed, each with up to two running periods.
Manual control (Manual / Auto position)
Corrigo E and all the configured outputs can be manually controlled, as well as a number of control functions.
This is a very handy feature which simplifies the checking of individual functions in the Corrigo. The supply air controller's output signal can be manually set (Manual/Auto) to any value between 0 and 100%. The temperature output signals will change accordingly if they are in Auto mode.
It is also possible to manually control each of the temperature output signals individually. All the configured digital outputs can be set to On, Off or Auto.
Alarm handling
If an alarm condition occurs, the alarm LED on the front panel on units with display will start flashing. The LED will continue to flash as long as there are unacknowledged alarms. Alarms are logged in the alarm list. The list shows type of alarm, date and time for the alarm and the alarm class (A, B or C alarm).
Alarm classification
Class A and B alarms will activate alarm output(s) if these have been configured.
Class C alarms do not activate the alarm output(s). These alarms are removed from the alarm list when the alarm input resets, even if the alarm has not been acknowledged.
Alarm log
For the ventilation and heating applications, the latest 40 alarm events are listed under ”Alarm events” in the display.
3
Corrigo E
Menu information
With E tool connected to Corrigo E you can add free text in the first line of the start-up screen. As an example, you can give the controller an identity. There are also five different menu alternatives for other information. Corrigo E also has an information screen where all 4 rows can be used. You can for example display contact information etc.
Corrigo E with communication
The basic version of Corrigo E is equipped with an RS485 port for connection via EXOline or Modbus. As an option, the controllers can be delivered with ports for TCP/IP or LON communication. This makes it possible to use Corrigo E in existing networks, and to supervise the application via the Internet, a mobile unit, or a local computer.
Connection via LAN/Internet gives excellent possibilities for adjusting set points, storing settings and supervising the functionality of the installation.
Connection of expansion units
In order to expand the number of I/Os on a controller, up to two Corrigo E units can be connected to models with two ports. The maximum number of inputs/ outputs is 3*28 = 84 I/Os. Port 2 can also be used for communication with two Vacon NXL, Lenze, Omron V1000 or Emerson Commander frequency converters. A frequency converter and an expansion controller can be connected to the same port. Control and sending of alarms from the frequency converters takes place via Modbus communication.
Corrigo E models with two ports are available in models with port 1 as RS485 (E...2-S) or TCP/IP (E...2-S-WEB). They have 15 or 28 I/Os. See the model overview on page
11. Any Corrigo E controller can be used as expansion unit.
However, units without display are normally utilised since no information is shown in the display of the expansion unit.
Modbus communication
The basic version of Corrigo E can be changed to communicate with Modbus RTU via the RS485 port.
When Modbus has been activated, Corrigo E automatically senses if communication is taking place via Modbus or EXOline (with E tool).
Models with LON communication
Models with LON use LonWorks, adjusted according to the LonMark-guidelines. See separate network variable list LON.
LON communicates via the LON port on Corrigo E. The configuration takes place in the display of the controller or via E tool on a PC connected via the RS485 port on Corrigo E. Corrigo E should be installed in the LON network with the help of LonMaker or a corresponding computer program.
LON communication is not yet available for boiler application.
LON can also be used in combination with expansion units. In this case, expansion unit 1 should be a Corrigo E-LON.
Which LON files are to be used for the controller is shown in the display.
Corrigo Web (with TCP/IP port)
E...-WEB models communicate via TCP/IP and use the TCP/IP port instead of the RS485 port on Corrigo E. This communicates with EXOline via TCP/IP.
To connect Corrigo E to a PC and the configuration tool E tool, a special network cable, E-CABLE-TCP/IP, should be used. This is a crossover network cable.
4
Corrigo E
Corrigo Web
The E...-WEB models has an integrated web server, which is easy to commission and configure using E tool.
The web server automatically puts required information and values on the website, depending on the configuration of the application in Corrigo E (which functions are used, inputs and outputs etc.). There are also real-time diagrams available on the website for 3.0 versions and up.
Corrigo E with integrated web server can be used in internal intranet solutions as well as externally towards the Internet. If you want to connect the controller to the Internet, you need broadband Internet access. The ventilation and heating applications have this web server function. However, Corrigo Web for application boiler control is not yet available.
Below are examples of what the website looks like for Corrigo Web.
Regin Building Access
Regin Building Access is a general application for the operating system Android which makes it possible to access a Regin controller with TCP/IP communication via e.g. a mobile network or a Wi-Fi network. Once connected, you can view parameters, alarms, documentation, etc. from the controller in the form of lists.
The application is intended to be run on a mobile phone, however can also be used on an Internet tablet. Regin Building Access can be downloaded free of charge from Android Market.
User interface similar to that of the website
5
Corrigo E
Digital temperature control
• Heating / DX-cooling
As alternative or complement to the above mentioned analogue control, heating and cooling can be activated in steps. The internal signal is then used to activate digital outputs for control of the heaters/chillers. Up to four heating outputs and three cooling outputs can be configured.
The outputs can be set to sequential or binary control. At binary control, the analogue heating and cooling outputs can be set to 0...100 % between every step for equalization purposes.
Outdoor temperature dependent, individual blocking of DX cooling steps is possible.
The fan speed can be overridden to normal speed when using DX cooling.
When using aftercooling in units with an electric heating coil, the heat exchanger will continue to run.
Digital time-switch
Up to 5 digital outputs can be used as timer controlled outputs. Each timer channel has a separate scheduler with two periods per weekday. These outputs can be used to control lighting, doorlocks etc.
Support control
When running room temperature control or extract air control (with a room sensor connected), “Support control Heating” or “Support control Cooling” will run.
• Support control heating
• Support control cooling
• Recirculation damper
• Stopped extract fan can be selected
Free cooling
This function is used during the summer to cool the building during the night using cool outdoor air.
Temperature control
The temperature controller is based on a supply air PI-controller for heating control with a pre-programmed set of control modes. The controller uses data from sensors etc. to control a number of different control functions, as well as various input and output functions. The user can choose which functions are to be used, the only restriction is the physical number of inputs and outputs of the different models.
Corrigo E has achoice of the following control modes:
1. Supply air control
2. Outdoor temperature compensated supply air control
3. Cascaded room temperature control
4. Cascade connected extract air temperature control
5. Outdoor temperature dependent switching between room control and supply air control
6. Outdoor temperature dependent switching between extract air control and supply air control
Applications Heating - Cooling - VVX - Dampers
Output functions which can be controlled by Corrigo E.
Analogue temperature control
• Water heating
• Electric heating
• Heat exchanger output Plate exchanger
Rotating exchanger Liquid connected exchanger Mixing dampers
• Water cooling
• Extra sequence
For Corrigo E 3.0, and up, there is an additional extra sequence which gives a fourth stand-alone sequence for temperature control.
• Split
It is also possible to split the heating, VVX or coo­ling signal to gain two outputs in sequence.
Control and functionality: Ventilation control
Example of ventilation control
6
Corrigo E
Free heating
This function is useful in Southern Europe where the reverse function of free cooling is desired. The function can be used to heat a building in the morning if the outdoor temperature increases faster than the indoor temperature and heating is required.
Cooling recovery
If the extract air temperature is lower than the outdoor temperature, cooling recovery can be activated.
Enthalpy control Override the signal for mixing dampers if the outdoor enthalpy is higher than the indoor enthalpy for increasing re-circulated air.
Heat exchanger efficiency monitoring
Gives an alarm when the efficiency falls below set value.
External setpoint
For connection of an external setpoint device.
Humidity control
Humidity control can be configured as:
• Humidification
• Dehumidification
• Humidification/Dehumidification Two humidity sensors can be connected, a room sensor for control and a duct sensor for maximum limiting.
The humidity sensors must give 0…10 V for 0…100% RH.
Fan control
Fans can be 1-speed, 2-speed or frequency controlled. For frequency controlled fans there are a number of options:
1. Constant pressure: The pressure signal from a
pressure transmitter is kept constant by frequency controlling the fan.
2. Constant flow: The flow m3/h is calculated using
a signal from the pressure transmitter. The flow is kept constant by frequency controlling the fan. The supply and extract air fans have individual conversion parameters for calculation of their respective flow.
3. Manual output to fixed values: Pressure signals are
not used. Instead, the output signal for the frequency converter is set to a fixed value.
4. External control signal: Direct control of both SAF
and EAF with external 0...10 V control signals for integration with VAV systems.
5. Frequency control SAF with EAF slave: Frequency
and pressure controlled supply air fan with frequency controlled extract air fan. The EAF output follows the SAF output.
6. Frequency control SAF with flow controlled EAF:
Frequency and pressure controlled supply air fan. The extract air fan flow is controlled by the flow in the supply air fan.
Air flow compensation for frequency controlled fans
Compensation can be set for both the supply air fan and the extract air fan, or the supply air fan only. Air flow compensation can be based on the supply air, extract air or room temperature.
Cont. Control and functionality: Ventilation control
Blocking of automatic restart at power-up
Restart at power-up can be blocked. However, as default the unit is set to start automatically.
Demand controlled ventilation
In applications with varying occupancy, the fan speeds or mixing dampers can be controlled by the air quality, which is measured with a CO2/VOC-sensor.
Pump control
Digital inputs and outputs can be configured for pump control.
• Heating circuit
• Exchanger circuit, liquid connected exchangers
• Cooling circuit
Damper control
Control possibilities:
• Close-off dampers
• Return air damper
• Extract air damper control
• Fire dampers
• Fire damper exercising
The close-off damper can be controlled individually or together with Return air damper / Extract air damper.
Extended running
Digital inputs can be used to force the unit to start although the timer says the running mode should be “Off”. These input signals have higher priority than the internal timer channels.
Recirculation function
Function for distributing the air in the room using the supply air fan, with or without temperature control.
Alarms
Alarm log in the display which shows the 40 latest alarm events.
Change-over
”Change-over” function for switching between heating and cooling control in 2-pipe systems. A new analogue output signal which is set to either heating or cooling. A digital input signal is used for switching between heating or cooling function.
User settings
Factory settings and user settings can be handled directly in the display. It is possible to save a configuration as user setting in the controller. A configuration can also be reset to factory settings or to a previously made user setting. Using E tool, a configuration can be saved as factory setting in the controller.
External control circuit
Separate, external control circuit with a sensor input as well as an analogue and a digital output signal for control of for example a post-treatment unit.
7
Corrigo E
Extra sensors for temperature and flow
There are four extra sensors for temperature measurement. If these sensors are configured, their values will be shown in the display and in E tool. The plain text description of the extra sensors can be adjusted via E tool. Only ”sensor error” alarms are shown for the sensors.
Two extra sensors for air flow, one for supply air and one for extract air can be configured. They must be supplemented with K- and X-constants for the fans.
Pretreatment (type "Puit Canadien")
Damper and pump control for preheating or precooling of the outdoor air via an underground intake channel.
Cont. Control and functionality: Ventilation control
8
Corrigo E
Wind compensation
To compensate for wind chilling, it is possible to connect a wind sensor and generate a setpoint displacement.
Building inertia
The building inertia, i.e. the building heat storage capacity, is settable to one of three levels. The set inertia dictates the influence of outdoor temperature.
Power limitation
Power limitation of HS1 can be set.
Night set-back
Set in room temperature degrees. The Corrigo has individual schedules for each heating system with two comfort-temperature periods per day.
Power limitation
Using a digital input the power to the heating systems can be temporarily restricted.
Domestic hot water
Can be configured for one or two domestic hot water systems, HW1 and HW2. These have constant supply­temperature control.
Controllers
The heating system controllers are PID-controllers with settable P-band, I-time and D-time.
Night set-back
Corrigo E has individual schedules for each hot water system with two normal temperature periods per day.
Pump control (HW1 only)
Corrigo E has a digital output signal which can be used to control the hot-water circulation pump in HW1.
Periodic overheating (HW1 only)
Once daily, the temperature setpoint can be increased to 62°C to prevent growth of Legionella bacteria.
Storage tank
A storage tank function can be enabled. The storage tank
In this case, Corrigo E uses PI controllers for heating control and PID for domestic hot water control. The controller uses data from sensors etc. to control a number of control functions, as well as various input and output functions. The user can choose which functions are to be used. The only restriction is the physical number of inputs and outputs of the different models.
Menu system
From version 3.0 of Corrigo E heating, the menu system is upgraded so that only parameters for which the controller is configured are displayed. This simplifies navigation in the menu system.
Heating circuits
Corrigo E with heating control can be configured for 1 to 3 heating systems.
Controllers
The heating system controllers are PI-controllers with settable P-band and I-time.
Control curves
The controllers have individual outdoor temperature / supply temperature control curves.
Adaption of curves
Room sensors can be used to correct the control curves. The average room temperature error over 24 h is calculated.
Pump control
Each system can have single or double pumps. Double pumps are run one at a time with automatic, weekly change-over and automatic start of the backup pump on malfunction of the active pump. Outdoor temperature dependent pump stop can be configured.
Frost protection
If a controller is set to Off or Man(ual control) and the outdoor temperature is below a settable value, a minimum settable supply temperature will be maintained and the pump will run.
Control and functionality: Heating control
Example of heating control
9
Corrigo E
load pump, P1-HP1, is started depending on the storage tank supply water and return water temperatures.
Pressure control
Corrigo E can, using an analogue output signal, control a variable speed pump to maintain a constant settable pressure.
Boiler control
A simple boiler control can be enabled. Two-step control using two start temperatures and one stop temperature.
Start signal for water chillers
A digital output for start of a water chiller can be configured.
Cooling circuit
Corrigo E heating version 3.0 and later have a controller for a cooling circuit, CS1. It can also be used for dew point control, see below.
Dew point control
The heating application has dew point control for a brine circuit. The function is based on a room temperature sensor and a room humidity sensor. Combined temperature and humidity transmitters are available from Regin.
Cold water monitoring
Monitoring of the cold water usage.
The following values are calculated:
• 24 hour usage in litres, today
• 24 hour usage in litres, yesterday
• 24 hour usage in litres, day before yesterday
• Lowest hourly usage in litres, today
• Lowest hourly usage in litres, yesterday
• Usage total in m3. The value can be reset.
• Water-flow (litres/min)
Alarm types
• Pulse error / High usage / Leakage control
Energy monitoring
One digital pulse function can be configured for heating energy monitoring. The pulse constant is settable.
The following usage values are calculated:
• 24 hour usage in kWh, today
• 24 hour usage in kWh, yesterday
• 24 hour usage in kWh, day before yesterday
• Total usage in kWh/MWh. The value can be reset.
Power values
Heating power is calculated by measuring the time between the energy pulses. The following power values are calculated:
• Instantaneous value for a certain time or after a certain number of pulses
• Average of the above instantaneous value.
• Maximum value for the above instantaneous value.
Leakage monitoring
Once a week, the control valves will be closed and the energy usage measured for a preset time. An alarm is generated if the energy leakage is larger than a settable
Cont. Control and functionality: Heating control
value.
Electricity meter
One digital pulse function can be configured for heating energy monitoring. The pulse constant is settable.
Usage values
Total usage in MWh. The value can be reset.
Timer channel outputs
Up to 5 digital outputs can be used as timer controlled outputs. Each timer has its own scheduler with two activation periods for each day of the week and a year-based holiday calendar.
M-Bus
A sensor that communicates via M-Bus can be connected to Port 2 on the controller. The connection requires the converter X1176, which can be ordered from Regin.
Extra temperature sensors
There are five extra temperature sensors. If these sensors are configured, their values will be shown in the display and in E tool. The plain text description of the extra sensors can be adjusted via E tool. Only ”sensor error” alarms are shown for the sensors.
10
Corrigo E
Control and functionality: Boiler control
Example of boiler control
In this application, Corrigo E can be used for boiler control as well as heating and domestic hot water control. The controller uses data from sensors etc. to control a number of control functions, as well as various input and output functions. The user can choose which functions are to be used. The only restriction is the physical number of inputs and outputs of the different models.
Boiler control
One boiler control circuit (one main sensor) with 1...4 boiler vessels, each with single or double burners (on/off).
Boiler 1 can have analogue control (0...10 V). Two control modes: modulating PI-control or thermostat
control (fixed starting and stopping points for each vessel).
The boiler circuit setpoint can be a fixed temperature, an outdoor temperature dependent setpoint (curve) or a heating circuit temperature dependent setpoint.
The boiler control has automatic malfunction take-over, with multiple boilers the starting order can be fixed, run-time controlled or alternating.
Common boiler pump or individual pumps for each boiler vessel, with start/stop and settable automatic pump exercising.
The boiler return temperature can be limited to eliminate the risk of condensation as a result of low temperature.
Heating circuits
Can be configured for 1 to 3 heating systems, which are controlled by PI-controllers with settable P-band and I-time.
Control curves/Outdoor compensation
The controllers have individual outdoor temperature / supply temperature control curves.
Adaption of curves
Room sensors can be used to correct the control curves. The average room temperature error over 24 h is calculated.
Pump control
Each system can have single or double pumps. Double pumps are run one at a time with automatic, weekly change-over and automatic start of the backup pump on malfunction of the active pump. Outdoor temperature dependent pump stop can be configured.
Frost protection
If a controller is set to Off or Man(ual control) and the outdoor temperature is below a settable value, a minimum settable supply temperature will be maintained and the pump will run.
Wind compensation
To compensate for wind chilling, it is possible to connect a wind sensor and generate a setpoint displacement.
Building inertia
The building inertia, i.e. the building heat storage capacity, is settable to one of three levels. The set inertia dictates the influence of outdoor temperature.
Night set-back
Set in room temperature degrees. The Corrigo has individual schedules for each heating system with two comfort-temperature periods per day.
Start time optimizer
Function for automatically calculating when the night set-back should stop in order to reach a pre-set temperature at the time set for start of comfort time in the internal scheduler. Autodidact function. A room sensor is required when this function is used.
Power limitation
Using a digital input the power to the heating systems can be temporarily restricted.
Domestic hot water
Can be configured for one domestic hot water circuit, HW1, which has constant supply-temperature control and is controlled by PID-controllers with settable P-band, I-time and D-time.
11
Corrigo E
Night set-back
Individual schedules for the hot water system with two normal temperature periods per day.
Pump control
Corrigo E has a digital output signal which can be used to control the hot-water circulation pump in HW1.
Periodic overheating
Once daily, the temperature setpoint can be increased to 62°C to prevent growth of Legionella bacteria.
Storage tank
A storage tank function can be enabled. The storage tank load pump, P1-HP1, is started depending on the storage tank supply water and return water temperatures.
Pressure control
Corrigo E can , using an analogue output signal, control a variable speed pump to maintain a constant settable pressure.
Cold water monitoring
Monitoring of the cold water usage. The following values are calculated:
• 24 hour usage in litres, today
• 24 hour usage in litres, yesterday
• 24 hour usage in litres, day before yesterday
• Lowest hourly usage in litres, today
• Lowest hourly usage in litres, yesterday
• Usage total in m3. The value can be reset.
• Water-flow (litres/min)
Alarm types
• Pulse error / High usage / Leakage control
Energy monitoring
One digital pulse function can be configured for heating energy monitoring. The pulse constant is settable.
The following usage values are calculated:
• 24 hour usage in kWh, today
• 24 hour usage in kWh, yesterday
• 24 hour usage in kWh, day before yesterday
• Total usage in kWh/MWh. The value can be reset.
Power values
Heating power is calculated by measuring the time between the energy pulses. The following power values are calculated:
• Instantaneous value for a certain time or after a certain number of pulses
• Average of the above instantaneous value.
• Maximum value for the above instantaneous value.
Leakage monitoring
Once a week, the control valves will be closed and the energy usage measured for a preset time. An alarm is generated if the energy leakage is larger than a settable value.
Electricity meter
One digital pulse function can be configured for heating energy monitoring. The pulse constant is settable.
Usage values
Total usage in MWh. The value can be reset.
Timer channel outputs
Up to 5 digital outputs can be used as timer controlled outputs. Each timer has its own scheduler with two activation periods for each day of the week and a year-based holiday calendar.
Cont. Control and functionality: Boiler control
12
Corrigo E
Models
Number of inputs and outputs (I/Os)* Models with 8 I/Os Models with 15 I/Os Models with 28 I/Os
2 AI, 3 DI, 1 AO, 2 DO 4 AI, 4 DI, 3 AO, 4 DO 4 AI, 4 UI, 8 DI, 5 AO, 7 DO
Basic model
E8-S E15-S E28-S
Basic model with display
E8D-S E15D-S E28D-S
Model with LON port
E15-S-LON E28-S-LON
Model with LON port and display
E8D-S-LON E15D-S-LON E28D-S-LON
Model with TCP/IP port
E8-S-WEB E15-S-WEB E28-S-WEB
Model with TCP/IP port and display
E8D-S-WEB E15D-S-WEB E28D-S-WEB
Model with two RS485 ports
E152-S E282-S
Model with two RS485 ports and display
E152D-S E152D-S
Model with one RS485 port and one TCP/IP port
E152-S-WEB E282-S-WEB
Model with one RS485 port, one TCP/IP port and display
E152D-S-WEB E282D-S-WEB
* AI=analogue inputs, DI=digital inputs, AO=analogue outputs, DO=digital outputs, UI=universal inputs (can be configured to function as either analogue input or digital input)
Accessories
External display unit
Including 3 m cable
E-DSP-3
Including 10 m cable
E-DSP-10
Display repeater for E-DSP
Supply voltage 24 V AC
E0-R
Supply voltage 230 V AC
E0-R230K
External display unit
Including 3 m cable
ED9100-3
Including 10 m cable
ED9100-10
Front mounting kit
Room for one Corrigo
FMCE
Cabinets
Cabinet intended for any Corrigo E15...D... model
CAB-STD1
Cabinet intended for any Corrigo E15...D... model
CAB-STD2
Cabinet intended for any Corrigo E28...D... model
CAB-STD3
Plug-in terminals
Set of plug-in terminals for E8 models
PLT-E8
Set of plug-in terminals for E15 models
PLT-E15
Set of plug-in terminals for E28 models
PLT-E28
GSM modem
GSM Fargo EXOcompact/Corrigo E kit
GSM100L-CORRIGO
Relay module
Relay unit
RM6-24/D
Relay unit with manual/auto-switches
RM6H-24/D
Panel PC
Panel PC with operating system in English
DP89
Panel PC with operating system in Swedish
DP156
Sensors
PT1000 sensors from Regin
TG-.../PT1000
Head Office Sweden
Phone: +46 31 720 02 00 Web: www.regin.se Mail: info@regin.se
Sales Offices
France: +33 1 41 71 00 34 Germany: +49 30 77 99 40 Spain: +34 91 473 27 65
Hong Kong: +852 24 07 02 81 Singapore: +65 67 47 82 33
Corrigo E
Technical data
Supply voltage 24 V AC ±15%, 50…60 Hz or 21…36 V DC Power consumption 8 VA, 4 W (DC), model WEB: 12 VA, 6 W (DC) Ambient temperature 0...50°C Storage temperature -40...+50°C Ambient humidity Max 90% RH Protection class IP20 (E-DSP IP44) Connection Disconnectable terminal strips, 4 mm2 Memory backup Long life battery. All settings are stored in the event of power failure. Display Backlit, LCD, four rows of 20 characters This product conforms with the requirements of European EMC standards CENELEC EN 61000-6-1:2001 and 61000-6-3:2001 and carries the CE-mark
Inputs
Analogue inputs For Pt1000-sensors (accuracy +/- 0.4°C) or 0...10 V DC (accuracy +/- 0.15% of full output signal). 12 bit resolution in the AO conversion. Digital inputs For potential free contacts
Outputs
Analogue outputs 0...10 V DC, 1 mA, short-circuit proof Digital outputs Mosfet outputs, 24 V AC or DC, 2 A continuous. Totally max 8 A.
Indicators
Operation indication Supply voltage is indicated with green LED Alarm indication Clear script and blinking red LED Sum alarm The output can be configured
E tool
System requirements Computer with operating system MS Windows 7, 2000, XP or Vista
Options
LON FT3150, gives a second communication port WEB / Android application (TCP/IP port) Replaces RS485 for EXOline (Port 1) communication 2 ports Two RS485 ports 2 ports WEB One RS485 port and one TCP/IP port
Dimensions
Product documentation
Document Type
Manual Corrigo E ventilation application
Manuals for the different applications
Manual Corrigo E heating application Manual Corrigo E boiler application Manual E tool and Corrigo Web
Manual for the configuration software E tool and Corrigo Web
Product sheet and instruction E-DSP
Information about accessories for Corrigo E
Product sheet and instruction E0-R/E0-R230K Product sheet ED9100 Instruction FMCE Instruction RM6-24/D and RM6H-24/D
The product documentation is available at www.regin.se.
Loading...