These gas appliances have been tested in
accordance with AS4553-2000, NZS 5262
and have been certifi ed by the Australian
Gas Association for installation and
operation as described in these Installation
and Operating Instructions.
Your unit should be serviced annually
by an authorised service person.
PLEASE KEEP THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING:
Improper installation, adjustment, alteration,
service or maintenance can cause injury or
property damage. Refer to this manual. For
assistance or additional information consult
an authorised installer, service agency or
the gas supplier.
FOR YOUR SAFETY
Do not store or use gasoline or other
fl ammable vapours and liquids in the vicinity
of this or any other appliance.
Installation and service must be performed
by an authorised installer, service agency or
the gas supplier.
918-538b
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any
appliance
Do not touch any electrical
switch: do not use any
phone in your building.
Immediately call your gas
supplier from a neighbour's
phone. Follow the gas
supplier's instructions.
If you cannot reach your
gas supplier, call the fi re
department.
08/16/07
Page 2
TO THE NEW OWNER:
Congratulations!
You are the owner of a state-of-the-art Gas Log Fireplace by FPI FIREPLACE PRODUCTS INTERNATIONAL.
The P36 has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick
of a switch. The model P36 has been approved by the Australian Gas Association for both safety and
effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for
many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions
and the many features of your Regency® Fireplace.
2
Regency® P36-4 Gas Log Fireplace
Page 3
TABLE OF CONTENTS
DATA BADGE
Data Badge ...................................................................4
INSTALLATION
Important Message ........................................................5
Before You Start ............................................................5
General Safety Information ...........................................5
This is a copy of the label that accompanies
each P36 Zero Clearance Room Sealed Gas
Fireplace. We have printed a copy of the contents
here for your review.
The label is located on the front inside base of the
unit, visible when the bottom louvre is open.
DATA BADGE NOTE: Regency® units are
constantly being improved. Check the label on
the unit and if there is a difference, the label on
the unit is the correct one.
(Australia Only)
4
Regency® P36-4 Gas Log Fireplace
Page 5
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE INSTRUCTIONS
The P36-NG or P36-LPG Room Sealed Fireplace
must be installed in accordance with AS56012004 and NZS 5261 5261 and these instructions.
Carefully read all the instructions in this manual
fi rst. Consult the "authority having jurisdiction"
to determine the need for a permit prior to
starting the installation. It is the responsibility of
the installer to ensure this fi replace is installed
in compliance with manufacturer's instructions
and all applicable codes.
BEFORE YOU START
NOTE: NOT INTENDED AS A FIREPLACE
INSERT.
INSTALLATION AND REPAIR SHOULD
BE DONE BY A AUTHORISED SERVICE
PERSON. THE APPLIANCE SHOULD BE
INSPECTED BEFORE USE AND AT LEAST
ANNUALLY BY AN AUTHORISED SERVICE
PERSON. MORE FREQUENT CLEANING
MAY BE REQUIRED DUE TO EXCESSIVE
LINT FROM CARPETING, BEDDING
MATERIAL, ETC. IT IS IMPERATIVE THAT
CONTROL COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS
OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE
APPLIANCE SHOULD BE LOCATED OUT
OF TRAFFIC AND AWAY FROM FURNITURE
AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS
APPLIANCE CORRECTLY WILL VOID YOUR
WARRANTY AND MAY CAUSE A SERIOUS
HOUSE FIRE.
CHILDREN AND ADULTS SHOULD BE
ALERTED TO THE HAZARDS OF HIGH
SURFACE TEMPERATURES, ESPECIALLY
THE FIREPLACE GLASS, AND SHOULD
STAY AWAY TO AVOID BURNS OR
CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN THEY
ARE IN THE SAME ROOM AS THE
APPLIANCE.
CLOTHING OR OTHER FLAMMABLE
MATERIAL SHOULD NOT BE PLACED ON
OR NEAR THE APPLIANCE. DO NOT USE
AEROSOLS IN THE VICINITY OF THIS
APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance shall be installed in
accordance with the manufacturer's
installation instructions,local gas fi tting
regulations, municipal building codes,
water supply regulations, electrical wiring
regulations, with AS5601-2004 (AGA
gas installation code) NZS 5261 (New
Zealand)
2) Installation and repair should be done
ONLY by an authorised person.
3) THIS APPLIANCE IS NOT INTENDED AS A
FIREPLACE INSERT. DO NOT CONNECT
TO MASONARY FLUE.
4) This appliance must be connected to
the specifi ed fl ue and termination cap
to the outside of the building envelope.
Never fl ue to another room or inside a
building. Make sure that the fl ue is fi tted
as per Flueing instructions.
5) Inspect the fl ueing system annually for
blockage and any signs of deterioration.
6) Flueing terminals shall not be recessed into
a wall or siding.
7) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
9) Wear gloves and safety glasses for protection
while doing required maintenance.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
11) Under no circumstances should this
appliance be modifi ed. Parts that have to be
removed for servicing should be replaced
prior to operating this appliance.
12) Installation and any repairs to this appliance
should be done by an authorised service
person. An authorised service person should
be called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
13) Do not slam shut or strike the glass door.
INSTALLATION
CHECKLIST
1) Locate appliance
a) Locate Your Gas Fireplace
b) Clearances
c) Combustible Mantels
d) Framing & Finishing
2) Assemble Top Standoffs and Top Facing
Support and Side Nailing Strips, refer to
section "Unit Assembly Prior to Installation".
(NOTE: must be done before installing unit
into fi replace.)
3) Install fl ue (Refer to section "Simpson Dura-
vent Flueing").
4) Make gas and electrical connections. Test
the pilot. Must be as per diagram. Refer to
section "Pilot Adjustment."
5) Install standard and optional features. Refer
to the following sections:
a. Brick Panels
b. Log Set
c. Flush Door
d. Premium Flush Front
e. Bay Door
f. Hampton® Cast Faceplate
g. Hampton® Cast Grills
h. Wall Switch
i. Remote Control
j. Wall Thermostat
k. Fan
6) Final check.
Before leaving this unit with the customer,
the installer must ensure that the appliance is
fi ring correctly and operation fully explained
to customer.
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label 30,000 Btu/h)
after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
15) The appliance area must be kept clear and
free of combustible materials, (gases and
other fl ammable vapours and liquids).
Regency® P36-4 Gas Log Fireplace5
Page 6
INSTALLATION
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your stove,
ensure that the clearances outlined on this
page are met.
2) Provide adequate clearances for
servicing.
3) The appliance must be installed on a fl at,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the fl oor, or raised up
on a platform to enhance its visual impact.
If the appliance is going to be installed
on carpeting, combustible linoleum tile or
other combustible material other than wood
fl ooring, the appliance must be installed on
a metal or wood panel extending the full
width and depth of the appliance.
4) The P36 Co Axial Flue Gas Fireplace can
be installed in a recessed position or framed
out into the room as in A, B, C, D. See
Diagram 1.
Diagram 1
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8 ground
lug provided. See section "Wiring."
CLEARANCES
The clearances listed below are Minimum
distances unless otherwise stated:
A major cause of chimney related fi res is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fi replace and
fl ue system be installed only in accordance
with these instructions.
Clearance to Combustibles from:
Back 0" (0mm)
Side 0" (0mm)
Floor 0" (0mm)
NOTE: The minimum fl oor clearance must
be maintained from the top surface of the
carpeting, tile, etc.
Minimum Clearance from Top of Unit to:
Mantel* Minimum 7" (177mm)
Ceiling from top of unit. 32" (1016mm)
Side Wall Clearance
Bay or Flush Front 6" (152mm)
Horizontal Flue Clearances
Top 2" (51mm)
Side 1-1/2" (38mm)
Bottom 1-1/2" (38mm)
Vertical Flue Clearances 1-1/4" (32mm)
Alcove Clearances**:
Max. Depth 36" (914mm)
Min. Width 48" 1219mm)
Min. Height 72" 1829mm)
* see mantle clearance instructions
(Refer to section "Combustible Mantels" &
"Mantel Leg Clearances."
if these clearances
are not adhered to.
WARNING
Fire hazard is an
extreme risk
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into Wall/Alcove
D) Corner
5) This appliance is Listed for bedroom
installations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The P36 Co Axial Flue Gas Fireplace is
approved for alcove installations, which
meet the clearances listed on this page.
7) We recommend that you plan your installation
on paper using exact measurements for
clearances and floor protection before
actually installing this appliance. Have an
authorized inspector, dealer, or installer
review your plans before installation.
Note: For fl ue terminations see section
"Exterior Flue Termination
Locations."
Clearances for Bay or Flush Front
6
Regency® P36-4 Gas Log Fireplace
Page 7
INSTALLATION
is made of metal studs covered with a non-combustible board.
Note: A non-combustible mantel may be installed at a lower height if the framing
COMBUSTIBLE MANTELS
Diagram 1 Diagram 2
These drawings are to scale at 1:6 (one inch = 6 inches)
Mantel can be installed anywhere in shaded area or higher using the above scale.
Because of the extreme heat this fi replace emits, the mantel clearances are critical.
Combustible mantel clearances from top of unit are shown in Diagrams 1 & 2.
Regency® P36-4 Gas Log Fireplace7
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.
Page 8
INSTALLATION
MANTEL LEG
CLEARANCES
Combustible mantel leg clearances as per
diagram below:
P36
Fire p lace
Maximum
38mm
projection
at 51mm
minimum
clearance.
152m m Side Wall
Mantel leg
51m m
127m m
Allow able m antel leg
projection.
Mantel leg
38m m
76m m
FRAMING AND
FINISHING
1) Determine the total thickness of facing
material (e.g. drywall plus ceramic tiles) to
allow the fi nished surface to be fl ush with
the front of the unit. Total facing thickness
can vary from 1/2" (13mm) to 1-1/4" (32mm)
thick.
2) Frame in the enclosure for the unit with
framing material.
Standard Framing Dimensions
A B C D
36-1/4" 36-1/4" 12-3/4" 46"*
921mm 921mm 324mm 1126mm*
Framing Dimensions with
Premium Flush Front Option
A B C D
37-1/4" 37-1/4" 17-3/8" 46-1/2"*
944mm 946mm 432mm 1182mm*
* 'D' is Minimum height to combustible mate-
rials including the Minimum 2" (51mm) Top
clearance to the Horizontal Flue, see fl ue
clearances in section "Clearances."
Note: 40-1/2" (1029mm) is the minimum
height for both fl ex termination or
Simpson Dura-Vent fl ueing.
Note: The unit does not have to be
completely enclosed in a chase. The
clearance on top of the unit is 0" to
the standoffs so combustible building
materials can be laid directly on top
of the standoffs. You must maintain
1-1/2" (38mm) clearance from the
fl ue to combustible materials for fl ex
(1-1/4" for Simpson Dura-Vent ).
5) Use steel studs for framing where the
1-1/2" (38mm) clearance from the fl ue to
combustible material cannot be maintained,
e.g. front top header.
Install Side Nailing Strips, Top Facing
Support, and Top Standoffs before
unit is slipped into position. See "Unit
Assembly Prior to Installation" section
for assembly details.
NOTE:
When using the Premium Flush Front
option, a fi nishing trim (962mm cover)
needs to be installed to cover the
spacers.
Maintain a physical gap between lining
and spacers 2-5mm. (5mm clearance to
framing each side).
8
Premium Flush Front Framing
Do not use combustible material as lining (eg.
timber) around the fi replace as shown in the
shaded area in the diagram below.
3) For exterior walls, insulate the enclosure to
the same degree as the rest of the house,
apply vapour barrier and drywall, as per
local installation codes. (Do not insulate
the fi replace itself.)
4) The top of the unit must not be closer than
32" (813mm) to the ceiling.
Regency® P36-4 Gas Log Fireplace
Page 9
INSTALLATION
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The Top Facing Support, the Side Nailing Strips
and the 2 Top Standoffs must be correctly
positioned and attached to the top before unit
is slipped into position.
Top Standoff Assembly
The top standoffs are shipped in a fl at position
and must be folded into shape and attached.
1) Remove the standoffs from the fi replace
top.
2) Take each standoff and bend into the correct
shape. Bend up at the bend lines until the
screw holes in the standoff and the prepunched screw holes on the fi replace top
line up.
3) Attach the standoff securely to the top with 2
screws per standoff (on opposite corners).
1) Mount Top Facing Support using the 3
supplied screws into the three pre-punched
screw holes on the top front of the unit. Use
hole positions A, B, or C depending on your
facing depth.
Premium Flush Front
Spacer Installation
Before the unit is slid into position, install the
provided spacers to the side of the fi replace
as follows;
1) Align the screw locations on spacer with
screw locations on the side of the fi rebox
and secure in place using 3 screws.
2) Repeat for other side.
NOTE: The side nailing strips are to be in-
stalled to the spacer after the spacer
is attached to the unit.
Top Facing Support and
Side Nailing Strips
Determine the total thickness of facing material
(e.g. drywall plus ceramic tiles) to allow the
fi nished surface to be fl ush with the front of the
unit. Total facing thickness can vary from 1/2"
(13mm) to 1-1/4" (32mm) thick.
The Top Facing Support & Side Nailing Strips can
be mounted in 3 different positions depending
on the thickness of the facing material.
Screw Facing Material
Position Depth
A 1/2" / 13mm
B 7/8" / 22mm
C* 1-1/4" / 32mm
* For "C" screw position the top facing support
is reversed.
"C" Screw Position:
For a facing material depth of 1-1/4"
(32mm), the top facing support must be
reversed.
2) Use the same screw hole position for the
Side Nailing Strips as was used for the Top
Facing Support. Attach each side nailing
strip using 3 screws.
Spacer
Left Side Shown
FLUEING
INTRODUCTION
The P36 uses the "balanced fl ue" technology
Co Axial system. The inner liner fl ues products
of combustion to the outside while the outer
liner draws outside combustion air into the
combustion chamber thereby eliminating the
need to use heated room air for combustion and
losing warm room air up the chimney.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and fl ue system must be
fl ued directly to the outside of the building,
and never be attached to a chimney serving a
separate solid fuel or gas burning appliance.
Each Co Axial Flue gas appliance must use
it's own separate fl ue system. Common fl ue
systems are prohibited.
Regency® P36-4 Gas Log Fireplace9
Page 10
INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced fl ue terminals or
according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand)
the fl ue terminals of outdoor appliances
Minimum
Clearance (mm)
a Below eaves, balconies or other projections:
- Appliances up to 50 MJ/h input 300
- Appliances over 50 MJ/h input 500
b From the ground or above a balcony 300
c From a return wall or external corner 500
d From a gas meter (M) 1000
e From an electricity meter or fuse box (P) 500
f From a drain or soil pipe 150
g Horizontal from any building structure (unless appliance is approved
for closer installation) or obstruction facing a terminal 500
h From any other fl ue terminal, cowl or combustion air intake 500
j Horizontally from an openable window, door, or non-mechanical air inlet, or
any other opening into a building, with the exception of sub-fl oor ventilation
(see also Note (I)):
- Appliances up to 150 MJ/h input 500
- Appliances over 150 MJ/h input 1500
k Vertically below an openable window, door, or non-mechanical air inlet,
or any other opening into a building, with the exception of sub-fl oor ventilation
(see also Note (I)): see table below
Clearance 'k' in mm
Space Heaters All Other Appliances
Up to 50 MJ/h Up to 50 MJ/h input Over 50 MJ/h input Over 150 MJ/h input
input to 150 MJ/h input
150 500 1000 1500
NOTES:
(I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases.
(II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest par to of the terminal.
(III) Prohibited area below electricity meter or fuse box extends to ground level.
(IV) A fl ue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on at least two sides and a free fl ow
of air at the appliance is achieved.
10
Regency® P36-4 Gas Log Fireplace
Page 11
INSTALLATION
FLUEING
Regency® Direct Vent System (Flex)
Horizontal Terminations Only
These fl ueing systems, in combination with the P36 Room Sealed Gas Fireplace, have been tested and listed as a Direct Vent type fl ue system
by the Australian Gas Association. The location of the termination cap must conform to the requirements in the Flue Terminal Locations diagram in
section "Exterior Flue Termination Locations."
Regency® Direct Vent (Flex) System Termination Kit (Part # 946-515) includes all the parts needed to install the P36 with a maximum run
of 1200mm.
1) 175mm dia. fl exible liner (1200mm length)
2) 100mm dia. fl exible liner (1200mm length)
3) spring spacers (4)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
If longer runs are needed, the Regency
Vent system (Flex) # 946-516 includes all the
parts needed to install the P36 with a maximum
3.0m run.
1) 175mm dia. fl exible liner (3.0m length)
2) 100mm dia. fl exible liner (3.0m length)
3) spring spacers (7)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" Drill Point, Stainless
Steel (4)
®
Direct
4" (102mm)
dia. flue pipe
6-7/8"
(173mm)
dia. Flue pipe
Wall Thimble
AstroCap
Termination Cap
(Part# 946-578/P)
(patented)
spring spacer
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency
3) If you are installing the P36 into a Regency
to include the mantel base in your calculations and to maintain the 32mm clearance (38mm with Flex) to the underside of the mantel
top.
Regency® P36-4 Gas Log Fireplace11
®
may be used for Flex installations.
®
Mantel Kit, use the minimum horizontal vent height (centre-line of 1029mm). Remember
Page 12
INSTALLATION
SIMPSON DURA-VENT FLUEING
Horizontal or Vertical Terminations
The Simpson Dura-Vent Co Axial Flue System offers a complete line of component parts for installation of both horizontal and vertical installations.
Many items are offered in decorative black, as well as galvanized fi nish. We recommend using the galvanized fi nish for installation with the P36.
The minimum components required for a basic
horizontal termination are:
1 Horizontal Termination Cap
1 90
1 Flue Adaptor
1 Wall Thimble
1 Length of pipe to suit wall thickness
(see chart)
o
Elbow
Flat Wall Installation
Wall Thickness
(inches)
4" - 5-1/2"6"
7" - 8-1/2"9"
10" - 1-1/2" 12"
9" - 14-1/2"11" - 14-5/8" Adj. Pipe
15" - 23-1/2"17" - 24" Adj.
Corner Installation
Wall Thickness
(inches)
3-1/4" - 6-3/4"11" - 14-5/8" Adj. Pipe
7-3/4" - 16-1/4"17" - 24" Adj. Pipe
7-1/4" - 8-3/4"6" + 12"
4-1/4" - 5-3/4"6" + 9"
Vent Length Required
(inches)
Vent Length Required
(inches)
9" + 9"
Wall thickness is measured from the back
standoffs to the inside mounting surface of
termination cap. For siding other than vinyl furring
strips may be used, instead of the vinyl siding
standoff, to create a level surface to mount the
fl ue terminal. The Terminal must not be recessed
into siding. Measure the wall thickness including
furring strips.
If a Vinyl Siding Standoff is required (it must
be used with vinyl siding), measure to outside
surface of wall without siding and add 2
inches.
Simpson Dura-Vent
Co-Axial Flue GS
SIMPSON DURA-VENT FLUEING COMPONENTS LIST
All Simpson Dura-Vent components are available directly from Regency®.
Part # Description Part # Description Part # Description
971 Horiz. Termination Kit includes: 90
black elbow, wall thimble cover, horiz. square
termination cap, 24" black pipe, and 11" -14"
5/8" adjustable black pipe.
970 Basic Horiz. Termination. Kit includes:
90o black elbow, wall thimble cover, horiz.
• Maintain clearances to combustibles as listed in section "Clearances."
• Horizontal fl ue must be supported every 3 feet (0.9 meters).
• Firestops are required at each fl oor level and whenever passing through a wall.
A fl ue guard should be used whenever
the termination is lower than the
specifi ed minimum or as per local
codes.
Note: Regency® Co Axial Flue System
(Flex) is only approved for
horizontal terminations.
Regency® P36-4 Gas Log Fireplace13
Page 14
INSTALLATION
FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT FLUE GS SYSTEM and
REGENCY® CO AXIAL FLUE SYSTEM (FLEX)
(LPG & NG)
The diagram below shows examples of horizontal termination arrangements using two 90o elbows (two 45o elbows equal one 90o elbow).
Note: 1) A maximum of two 90o elbows are permitted.
2) A minimum of 6 ft. (1.8m) vertical from base of unit is required if two 90o elbows are used.
3) Minimum distance between elbows is 2 ft. (0.6m).
4) Determine the permitted range of horizontal termination arrangements by using chart in section "Simpson Dura-vent
Flueing." and deducting 3 ft. (0.9m) from the maximum horizontal distance for the second 90o elbow.
If length "B" is increased, length "A" must be
decreased by a corresponding amount.
A fl ue guard should be used whenever the
termination is lower than the specifi ed minimum
or as per local codes.
• Maintain clearances to combustibles as listed in section "Clearances."
• Horizontal fl ue must be supported every 3 feet (0.9 meters).
• Firestops are required at each fl oor level and whenever passing through a wall.
14
Regency® P36-4 Gas Log Fireplace
Page 15
FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS
SIMPSON DURA-VENT CO AXIAL FLUE GS SYSTEM (LPG & NG)
The P36 is approved for a 23 ft. (7.0m) vertical, with a maximum 12 ft. (3.7m) horizontal offset
using two 90o elbows (two 45o elbows equal one 90o elbow) with Simpson Dura-Vent Co Axial Flue GS fl ue systems for LPG and NG, as per diagram 1.
The P36 is approved for a 37 ft. (11.3m) straight vertical, including a 20" (0.5m) horizontal offset
using two 90o elbow (two 45o elbows equal one 90o elbow) with Simpson Dura-Vent Co Axial
Flue GS fl ue systems for LPG and NG, as per the diagram 2.
• Flue must be supported at offsets
• Maintain clearances to combustibles as listed in section "Clearances."
Note: Must use optional fl ue adapter when using Simpson Dura-Vent pipe
(Part # 510-994).
Note: Regen cy® Co Axial Flue System (Flex) is only approved for horizontal
terminations.
INSTALLATION
Diagram 1
Regency® P36-4 Gas Log Fireplace15
Diagram 2
Page 16
INSTALLATION
The P36 is approved for a 37 ft. (11.3m) straight vertical, with Simpson
Dura-Vent Co Axial Flue GS fl ue systems for LPG and NG, as per the
diagram 3.
The shaded area in the diagram 3 shows all allowable combinations of
straight vertical and offset to vertical terminations with Simpson Dura-Vent Co Axial Flue GS fl ue systems for LPG and NG. Maximum two
o
elbows allowed.
45
• Flue must be supported at offsets
• Firestops are required at each fl oor level and whenever passing
through a wall.
• Maintain clearances to combustibles as listed in section
"Clearances."
16
Diagram 3
Regency® P36-4 Gas Log Fireplace
Page 17
INSTALLATION
HORIZONTAL
TERMINATIONS
Install the fl ue system according to the
manufacturer's instructions included with
the components.
1) Set the unit in its desired location. Check
to determine if wall studs or roof rafters
are in the way when the fl ueing system is
attached. If this is the case, you may want
to adjust the location of the unit. Rough in
the gas preferably on the right side of the
unit and the electrical (junction block is on
the left side) on the left.
2) Co Axial Flue pipe and fi ttings are designed
with special twist-lock connections to
connect the fl ueing system to the appliance
fl ue outlet. A twist-lock appliance adaptor
is an available option that must be used in
conjunction with the Simpson Dura-Vent Co
Axial Flue GS system.
3) Put a bead of silicone inside the outer
section of the adapter and a bead of Stove
Mate on the inner collar. Slip the adapter
over the existing inner and outer fl ue collar
and fasten to the outer collar only with the
3 supplied screws (drilling pilot holes will
make this easier). Level the fi replace and
fasten it to the framing using nails or screws
through the nailing strips.
4) Assemble the desired combination of pipe
and elbows to the appliance adaptor and
twist-lock for a solid connection.
Note:
a) Twist-lock procedure: Four indentations,
located on the female ends of pipes and
fi ttings, are designed to slide straight
onto the male ends of adjacent pipes
and fi ttings, by orienting the four pipe
indentations so they match and slide
in to the four entry slots on the male
ends, Diagram 1. Push the pipe sections
completely together, then twist-lock
one section clockwise approximately
one-quarter turn, until the two sections
are fully locked. The female locking lugs
will not be visible from the outside, on
the Black Pipe or fi ttings. They may be
located by examining the inside of the
female ends.
b) Horizontal runs of fl ue must be supported
every three feet. Wall straps are available
for this purpose.
5) Mark the wall for a 10" x 10" square hole. The
center of the square hole should line up with
the centerline of the horizontal pipe. Cut and
frame the 10 inch square hole in the exterior
wall where the fl ue will be terminated. If the
wall being penetrated is constructed of noncombustible material, i.e. masonry block or
concrete, a 7"(178mm) dia. (7-1/2"(191mm)
dia. for fl ex) hole is acceptable.
Note: With
Dura-Vent,
the minimum
height is
achieved by
installing a
o
elbow
90
directly to the
fl ue adaptor.
Diagram 2
Note:
a) The horizontal run of fl ue must be level,
or have a 1/4 inch rise for every 1 foot
of run towards the termination. Never
allow the fl ue to run downward. This
could cause high temperatures and may
present the possibility of a fi re.
b) The location of the horizontal flue
termination on an exterior wall must meet
all local and national building codes,
and must not be blocked or obstructed.
For External Flue Terminal Locations,
see diagram in section "Exterior Flue
Termination Locations."
6) The arrow on the flue cap should
be pointing up. Insure that the 1-1/2"
clearances to combustible materials are
maintained. Install the termination cap,
diagram 5.
The four wood screws provided should
be replaced with appropriate fasteners for
stucco, brick, concrete, or other types of
sidings.
Diagram 3
8) Slide the appliance and fl ue assembly
towards the wall carefully inserting the
fl ue pipe into the fl ue cap assembly. It is
important that the fl ue pipe extends into
the fl ue cap suffi cient distance so as to
result in a minimum pipe overlap of 1-1/4
inches. Secure the connection between the
fl ue pipe and the fl ue cap by attaching the
two sheet metal strips extending from the
fl ue cap assembly into the outer wall of the
fl ue pipe. Use the two sheet metal screws
provided to connect the strips to the pipe
section. See Diagram 4.
9) Install wall thimble in the center of the
10" square and attach with wood screws
(Diagram 5).
Diagram 4
Note: If installing termination on a siding
covered wall, a vinyl siding standoff
or furring strips must be used to
ensure that the termination is not
Diagram 1
Note: Apply sealant "Mill-Pac" to inner pipe
and high temperature silicone sealant
to outer pipe on every
twist-lock joint.
Regency® P36-4 Gas Log Fireplace17
recessed into the siding.
7) Before connecting the horizontal run of
fl ue pipe to the fl ue termination, slide the
Wall Thimble (Part # 620-926) over the fl ue
pipe.
Diagram 5
Page 18
INSTALLATION
VERTICAL
TERMINATIONS
1) Maintain the 1-1/4"
clearances (air spaces)
to combustibles when
passing through ceilings,
walls, roofs, enclosures,
attic rafter, or other nearby
combustible surfaces.
Do not pack air spaces
with insulation. Check
section "Simpson Duravent Flueing" for the
maximum vertical rise of
the fl ueing system and the
maximum horizontal offset
limitations.
Diagram 1
2) Set the gas appliance in its desired location.
Drop a plumb bob down from the ceiling to the
position of the appliance fl ue exit, and mark
the location where the fl ue will penetrate
the ceiling. Drill
a small hole at
his point. Next,
drop a plumb
bob from the
roof to the hole
previously drilled
in the ceiling,
and mark the
spot where
the flue will
penetrate the
roof. Determine
if ceiling joists,
roof rafters or
other framing
will obstruct the fl ueing system. You
may wish to relocate the appliance or to
offset, as shown in Diagram 2 to avoid cutting
load bearing members.
Diagram 2
Diagram 3
4) Assemble the desired lengths of pipe and
elbows. Ensure that all pipes and elbow
connections are in the fully twist-locked
position and sealed.
5) Cut a hole in the roof centered on the small
drilled hole placed in the roof in Step 2. The
hole should be of suffi cient size to meet
the minimum requirements for clearance
to combustibles of 1-1/2". Slip the fl ashing
under the shingles (shingles should overlap
half the fl ashing) as per Diagram 4.
Diagram 4: The upper half of the fl ashing is
installed under the roofi ng material and not
nailed down until the chimney is installed.
This allows for small adjustments.
6) Continue to assemble pipe lengths.
Roof Pitch Minimum Flue Height
Feet Meters
fl at to 7/12 2 0.61
over 7/12 to 8/12 2 0.61
over 8/12 to 9/12 2 0.61
over 9/12 to 10/12 2.5 0.76
over 10/12 to 11/12 3.25 0.99
over 11/12 to 12/12 4 1.22
over 12/12 to 14/12 5 1.52
over 14/12 to 16/12 6 1.83
over 16/12 to 18/12 7 2.13
over 18/12 to 20/12 7.5 2.29
over 20/12 to 21/12 8 2.44
Galvanized pipe is desirable above the roofl ine
due to its higher corrosion resistance. Continue
to add pipe sections through the fl ashing until
the height of the fl ue cap meets the minimum
height requirements specifi ed in Diagram 5 or
local codes. Note that for steep roof pitches,
the vertical height must be increased. A poor
draft, or down drafting can result from high
wind conditions near big trees or adjoining
roof lines, in these cases, increasing the fl ue
height may solve the problem.
7) Ensure fl ue is vertical and secure the base
of the fl ashing to the roof with roofi ng rails,
slide storm collar over the pipe section and
seal with a mastic.
8) Install the vertical termination cap by twist-
locking it.
Note: Any closets or storage spaces, which
the fl ue passes through must be
enclosed.
Offset Chart
Note: Apply sealant "Mill-Pac" to inner
pipe and high temperature silicone
sealant to outer pipe on every twistlock joint.
3) A Firestop spacer must be installed in the
fl oor or ceiling of every level. To install the
Firestop spacer in a fl at ceiling or wall,
cut a 10 inch square hole. Frame the hole
as shown in Diagram 3 and install the
fi restop.
18
Note: If an offset is necessary in the attic
to avoid obstructions, it is important
to support the fl ue pipe every 3 feet,
to avoid excessive stress on the
elbows, and possible separation.
Wall straps are available for this
purpose (Diagram 2).
Diagram 5
Regency® P36-4 Gas Log Fireplace
Page 19
INSTALLATION
Conversion Kit #513-968 from NG to LPG
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !!
Conversion Kit Contains:
Qty. Part # Description
1 910-037 LPG Injector
(Pilot Orifi ce)
1 904-390 Burner Orifi ce #52
1 918-590 Decal "Converted
to LPG"
1 908-528 Red "LPG" label
1 904-529 5/32" Allen Key
1 918-546 Instruction Sheet
1) Shut off the gas supply.
2) Remove the louvers (and bay door if it is
installed).
3) Open the fl ush door and remove the door.
4) Remove the logs and embers (if used).
5) Remove the 2 screws holding the Burner
Assembly to the fi rebox base. Push the
Burner Assembly to the left and lift out.
8) Remove burner orifi ce with a 1/2" wrench.
Use another wrench to hold on to the elbow
behind the orifi ce. Discard orifi ce.
Burner Orifi ce
9) Reinstall new burner orifi ce LPG stamped
#52 and tighten.
10) Turn control knob to the “OFF” position.
11) Remove the black
protection cap by hand
from the hi-low knob
(Fig.1).
WARNING!
Do not over tighten the screw.
Recommended to
grip the wrench by the short side.
16) Verify that if the conversion is from NG to
LPG, the screw must be re-assembled with
the red o-ring visible (Fig. 5).
Red o-ring visible
LPG Configuration
Fig.5
17) Re-assemble the
black protection cap
(Fig. 6).
18) Reverse step 2).
Remove the 2 screws, push Burner Assembly
to the left and lift out.
6) Pull off the pilot cap to expose the pilot
orifi ce.
7) Unscrew the pilot orifi ce with the allen key;
then replace with the LPG pilot orifi ce and
the pilot cap, provided in the kit.
12) Insert a 5/32” or 4mm Allen
wrench into the hexagonal
key-way of the screw
(Fig. 2), rotate it counterclockwise until it is free and
extract it.
Fig.2
13) Check that the screw is
clean and if necessary
remove dirt.
14) Flip the screw (Fig. 3).
Fig.3
15) Using the Allen wrench as
shown in Fig.4, rotate the
screw clockwise until snug,
do not overtighten.
Fig. 1
Fig. 6
WARNING!
Also check that the pilot and main
burner injectors are appropriate for
the gas type.
19) Attach clear label "This unit has been
converted to LPG" near or on the serial
# decal.
20) Replace yellow "NG" label with red "LPG"
label.
21) Check for gas leaks.
22) Check inlet and outlet pressures.
23) Check operation of fl ame control.
24) Check for proper fl ame appearance and
glow on logs.
Fig.4
Regency® P36-4 Gas Log Fireplace19
Page 20
INSTALLATION
P36-NG System Data
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes: #37( 2.65mm)
Max. Input Rating 33 mj
Min. Input Rating 20 mj
Supply Pressure min.1.25 kPa
Manifold Pressure
(High) 0.9 kPa
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fi bre, 7 per set.
Flue System: Simpson Dura-Vent Direct
Flue System or Regency
Flue System (Flex)
®
Direct
P36-LPG System Data
For 0 to 2000 feet altitude
Burner Inlet Orifi ce Sizes: #52 (1.6 mm)
Max. Input Rating 31 mj
Min. Input Rating 18 mj
For 0 to 4500 feet Altitude:
Supply Pressure min 2.75 kPa
GAS LINE
INSTALLATION
The gas line can be brought through either the
right or the left side of the appliance. The gas
valve is situated on the right hand side of the
unit and the gas inlet is on the right hand side
of the valve.
Note: If the gas line is being installed from
the left side, be sure to leave room to
accommodate servicing of the fan.
The gas line connection may be made of
rigid pipe, copper pipe or an approved fl ex
connector. (If you are using rigid pipe, ensure
that the valve can be removed for servicing.)
Since some municipalities have additional local
codes it is always best to consult with your local
authorities and the AS5601-2004 or NZS 5261
installation code.
When using copper or fl ex connectors use only
approved fi ttings. Always provide a union so
that gas lines can be easily disconnected for
servicing. Flare nuts for copper lines and fl ex
connectors are usually considered to meet this
requirement.
Important: Always check for gas leaks with a
soap and water solution or gas leak detector.
Do not use open fl ame for leak testing.
PILOT ADJUSTMENT
Periodically check the pilot fl ames. Correct
fl ame pattern has three strong blue fl ames:
1 fl owing around the thermopile, 1 around
the thermocouple and 1 fl owing across the
burner (it does not have to be touching the
burner).
Note: If you have an incorrect fl ame pattern,
contact your Regency® dealer for
further instructions.
Incorrect fl ame pattern will have small,
probably yellow fl ames, not coming into
proper contact with the rear burner or
thermopile or thermocouple.
Manifold Pressure
(High) 2.7 kPa
Electrical: 240 V A.C. System.
Circulation Fan: variable speed 130 CFM.
Log Set: Ceramic fi bre, 7 per set.
Flue System: Simpson Dura-Vent Co Axial
Flue System
AERATION
ADJUSTMENT
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is accessed
through the bottom louvre opening. Open the air
shutter for a blue fl ame or close for a yellower
fl ame. The burner aeration is factory set but
may need adjusting due to either the local gas
supply or altitude. This adjustment is performed
by the gas fi tter.
Minimum Air Shutter Opening:
8 mm NG
Full Open LPG
CAUTION: Carbon will be produced if air shutter
is closed too much.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
Closed - Tall yellow
Open - Short Blue
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 3.45 kPa.
The manifold pressure is controlled by a
regulator built into the gas control, and should
be checked at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a
1/8" wide fl at screwdriver.
20
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
Regency® P36-4 Gas Log Fireplace
Page 21
INSTALLATION
4) Light the pilot and turn the valve to "ON"
position.
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specifi ed on the safety
label.
6) When fi nished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" fl at
screwdriver. Note: Screw should be snug,
but do not over tighten.
S.I.T. VALVE DESCRIPTION
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection Point
OPTIONAL
BRICK PANELS
1) Undo the bottom 2 door latches and open
and remove glass door. Remove logs.
Note: The logs must not be in the unit.
2) Insert the back brick panel fi rst by carefully
slipping it between the back wall of the
fi rebox and the rear log bracket.
3) Put the side panels in next. Slide them in
from the front and push them fl at up against
the wall. Be very careful not to scratch them
on the fi rebox hardware.
LOG SET
INSTALLATION
Read the instructions below carefully and
refer to the diagrams. If logs are broken
do not use the unit until they are replaced.
Broken logs can interfere with the pilot
operation.
The gas log kit (Part # 512-930) contains the
following pieces:
a) 02-49 Rear Log
b) 02-55 Middle Left Log
c) 02-50 Front Left Log
d) 02-53 Center Left Log
e) 02-51 Front Bottom Log
f) 02-54 Center Right Log
g) 02-52 Middle Right Log
h) Embers 902-156
i) Vermiculite 902-179
4) Install the 2 brick retaining clips, one on
each side.
The "02" refer numbers (i.e. 02-49) are
molded into the rear of each log.
NOTE: If you will be installing the optional
Brick Panels, install the Brick Panels
prior to installing the logs.
1) Carefully remove the logs from the box and
unwrap them. The logs are fragile, handle
with care - do not force into position.
2) Sprinkle the vermiculite around the fi rebox
base.
Vermiculite
3) Place the Log 02-49 on the rear log support
pins with the fl at side to the back.
Vermiculite
Vermiculite
Regency® P36-4 Gas Log Fireplace21
Page 22
INSTALLATION
02-49
02-49
8) Position Log 02-54 across the cutouts in
Logs 02-51 and 02-53. The notch in the
bottom right end fi tting against the 5th grate
tab.
4) Place Log 02-51 on the front right side of
the burner. Push the back of the log against
the 2 brackets with the notch on the bottom
right side of the log fi tting into the right side
of the grate.
02-51
02-53
6) Place the bottom left front edge of Log
02-55 against the rear bracket on the burner
tray and rest the log on the cutout on
Log 02-53.
02-49
02-55
02-53
Rear Bracket
7) Sit Log 02-50 on the front left side of the
burner. Push the back of the log against the
2 front brackets with the notch on the bottom
of the log fi tting into the fi rst grate tab.
02-51
02-51
02-54
02-53
02-55
02-50
02
9) Place Log 02-52 between Logs 02-51 and
02-49 and on the indentation on Log 02-54.
The bottom right end sits behind the rear
grate tab.
02-51
5th Grate Tab
02-49
53
-
02-51
02-54
Bracket
5) Position Log 02-53 across the cutouts in
Logs 02-49 and 02-51 with the notch on the
left side of the log fi tting into the 2nd grate
tab.
2nd Grate Tab
02-49
Bracket
Notch
02-51
02-53
02-49
02-51
Cutouts
02-50
02-50
Front Brackets
Notch
02-55
02-55
02-53
02-53
02-52
02-51
Log indentation
02-52
02-54
Photo shows rear grate tab.
Log 02-51 was removed to show
the positioning of Log 02-52.
02-54
Grate
02-49
Rear
Tab
22
Regency® P36-4 Gas Log Fireplace
Page 23
10) Place the embers on the front of the burner
tray in the places shown on the photo.
INSTALLATION
02-49
Place embers in these 3 locations
on the burner tray.
Embers
The standard fl ush door comes with a black
frame. To install the frame, simply hook the top
door fl ange onto the top of the unit and swing
the door towards the unit, diagram 1.
02-55
02-50
53
-
02
11) Test fi re to ensure proper light off (make sure fl ame fl ows smoothly from one end of burner
to the other). If there is any fl ame hesitation, check that area for any blockage of the burner
ports.
02-51
02-52
02-54
STANDARD FLUSH DOOR
Use the hook to pull the spring out until you
can put the hook into the slot on the bottom
door bracket. Repeat for 2nd spring. See
diagram 3.
1) Install the top louvre by sliding the two
bracket clips into the brackets located
underneath the top of the fi rebox.
2) The bottom louvre has a hinge that is
attached (2 screws per hinge) to the lip on
bottom of the unit.
Flush Louvres
Diagram 3
Diagram 1
To remove the fl ush door, reverse the above
steps.
Optional
Flush Trim
Attach the round
magnets to the
back of the top trim
piece and to the
Be careful that the glass gasket does not roll up;
there must be a gap between the gasket and
the door lip to ensure that the door sits securely
on the unit. Diagram 2.
Diagram 2
Regency® P36-4 Gas Log Fireplace23
bottom trim piece,
then attach trim to
the top and bottom
of Flush door.
Note: Top and bottom louvres are
different.
Page 24
INSTALLATION
PREMIUM FLUSH FRONT INSTALLATION
1) Unplug the power source.
2) Remove the top louver (if fi tted) by carefully pulling it out.
3) Install the premium fl ush front top louver in place by sliding the louver
tabs into the louver brackets on the inside top of the fi rebox.
Louver Tab
6) Remove the manual control switch bracket by undoing the 2
screws.
7) Remove the burner ON/OFF switch from the bracket using a pair
of pliers and remove the 2 screws that secure the 2 wires on the
valve.
Burner ON/OFF
Switch
Premium Flush Front Top Louver in place.
4) Open the bottom louver.
5) Remove the bottom louver (if fi tted) by undoing the 2 screws which
secure the louver to the hinges on the left and right side.
24
Valve
8) Install the new ON/OFF switch to the manual control switch
bracket.
Regency® P36-4 Gas Log Fireplace
Page 25
INSTALLATION
9) Connect the female connecter on the white wire to the TH terminal
of the valve.
10) Remove the thermodisc cover from the thermodisc plate by undoing
the 2 screws and then remove the wire grommet.
Thermodisc Plate
12) Place the wire grommet back into the thermodisc cover with the 2
female ends of the wires inside the cover as shown.
13) Connect the female ends of the red and white wires to the thermo-
disc.
Thermodisc Cover
Grommet
11) Take the white wire from the kit and the red wire from the burner
ON/OFF switch and place the grommet thru the wires.
14) Reattach the thermodisc plate to the thermodisc cover using the 2
screws removed in step 10.
Regency® P36-4 Gas Log Fireplace25
Page 26
INSTALLATION
15) Connect the thermodisc wire harness to the new valve/module wire harness. Refer to the wiring diagram on next page for details.
16) Mount the thermodisc bracket to the adjustable bracket using 2 screws.
Important: Thermodisc location is crucial, check the data badge to
identify unit and secure to screw location accordingly.
17) Remove the left side bottom hinge bracket by undoing the 2
screws.
22) Install the wire cover by fi tting the 3 clips onto the fl ange at the front
of the fi rebox. See note below for P36 units.
Wire Cover
Firebox Flange
18) Install the supplied hinge to the hinge bracket using 2 screws.
19) Slide the adjustable bracket to the bottom left corner and secure in
place using the 2 screw holes on the fi rebox fl ange.
20) Secure loose wires using wire clips to the base of the fi rebox as far
back as possible.
21) Place the manual control bracket back into it's original location and
secure using 2 screws.
One clip shown in place
on fi rebox fl ange.
NOTE - P36 UNITS ONLY:
For the wire cover to fi t in place on the P36 the top half of the wire
cover will need to be broken off by bending back and forth.
Bend Here
23) Align the bottom louver mounting tab with hinges on the left and right
side and secure using 2 screws on each side.
24) Plug in power source.
25) Close the bottom louver.
26
NOTE:
The fan must run at minimum speed to prevent the unit from overheating
which will cause automatic shutdown via the thermodisc safety switch.
Regency® P36-4 Gas Log Fireplace
Page 27
INSTALLATION
Option 1:
WALL SWITCH
1) Run supplied 15' of wire through the right
or left side gas inlet opening. Be careful not
to damage wire.
Note: We recommend a maximum of 15'
of wire but if you wish to go with a
longer run, use the Thermostat Wire
Table.
2) Connect wire to supplied wall switch and
install into the receptacle box.
CAUTION
Do not connect millivolt
wall switch wires for gas
appliance to a 240V power supply.
Option 2:
REMOTE CONTROL
Use the Regency® Remote Control Kit approved
for this unit. Use of other systems may void
your warranty.
The remote control kit comes with a hand held
transmitter, a receiver and a wall mounting
plate.
1) Choose a convenient location on the wall
to install the receiver and the receptacle
box (protection from extreme heat is very
important). Run wires from the fi replace to
that location. Use Thermostat Wire Table.
2) Connect the two wires to the gas valve. See
diagram below.
CAUTION
Do not connect millivolt
remote control wires for
gas appliance to a
240V power supply.
3) Install a 9V alkaline battery in both the
receiver and the transmitter. Install the
receiver and its cover in the wall. Switch the
hand held remote transmitter to "remote"
mode. The remote control is now ready for
operation.
Option 3:
WALL THERMOSTAT
A wall thermostat may be installed if desired,
connect the wires as per the wiring diagram.
Use chart below to determine the maximum
wire length.
Note: Pr ef er ab le if the thermo st at is
installed on an interior wall.
Regency® offers a programmable thermostat
but any CSA, UCL or UL approved millivolt
thermostat, 250-750 millivolt rated nonanticipator type thermostat may be used.
CAUTION
Do not connect millivolt
wall thermostat wires for
gas appliance to a
240V power supply.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size Max. Length
14 GA.
16 GA.
18 GA.
20 GA.
22 GA.
15.24 m
9.75 m
6.10 m
3.66 m
2.71 m
Regency® P36-4 Gas Log Fireplace27
Page 28
INSTALLATION
WIRING
This heater does not require a 240V A.C. supply
for the gas control to operate. A 240V A.C. power
supply is needed for the fan/blower operation.
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
STANDARD WIRING
CAUTION: Label all wires prior
to disconnection when servicing
controls. Wiring errors can
cause improper and dangerous
operation.
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged (grounding) plug for your
protection against shock hazard and should be plugged directly into a properly
grounded three-prong receptacle. Do not cut or remove the grounding prong
from this plug.
28
Regency® P36-4 Gas Log Fireplace
Page 29
INSTALLATION
WIRING WITH PREMIUM FLUSH FRONT OPTION
Regency® P36-4 Gas Log Fireplace29
Page 30
OPERATING INSTRUCTIONS
OPTIONAL
FAN
240 Volt AC power is needed for the fan switch
and blower. The fan can be hard wired if desired.
A terminal block is provided on the left hand side
of the unit. A three wire power cord can also be
used and plugged into a suitable receptacle.
Unit must be grounded at all times. Do
not cut the ground terminal off under any
circumstances.
1) Shut the power off.
2) Open the bottom louvre door.
3) Remove the terminal block cover.
4) Slide the fan in towards the rear of the unit
and slip it over the two mounting studs.
Ensure that the fan blades do not rub
against the valve tubing.
7) Slide the thermodisc into the bracket clip
on the underside of the fi rebox.
8) Connect black wire from fan to the
thermodisc.
9) Connect fan ground cable to ground lug.
Refer to wiring diagram.
10) Attach the ground wire to the stove (ground
lug provided).
11) Attach black wire from thermodisc to terminal
block.
12) Hard wire into terminal block and to fan
speed controller. Wires not supplied.
Note: A 240 Volt AC power cord can be
installed at rough-in stage so that
the power is available. A three wire
power cord can be used.
OPERATING
INSTRUCTIONS
1) Read and understand these instructions
before operating this appliance.
2) Check to see that all wiring is correct and
enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the door frame is
properly positioned. Never operate the
appliance with the glass removed.
5) Verify that the flueing and cap are
unobstructed.
6) Ensure that the brick panels are installed.
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have
been incorrectly positioned.
8) The unit should never be turned off, and on
again without a minimum of a 60 second
wait.
Optional: If you require extra space to slide
the fan to the back, the left spring can be
unhooked from the bracket.
5) Wire the fan to the terminal block as shown
in the wiring diagram below.
6) Connect white wire from fan to neutral of
terminal block.
13) Attach the terminal block cover. If the left
spring was unhooked in step 4), hook it back
into the bracket.
To Remove the Fan
1) Shut the power off.
2) Reverse the above instructions.
Note: The bearings are lubricated for life.
Do not lubricate them. Make sure
you vacuum the fan area on a regular
basis.
IMPORTANT:
These fans collect a lot of dust from within
your home. Ensure you maintain these fan
motors on a regular basis by vacuuming
out the fan blades and housing using a soft
brush nozzle.
30
Regency® P36-4 Gas Log Fireplace
Page 31
OPERATING INSTRUCTIONS
LIGHTING
PROCEDURE
1) Push in gas control knob slightly and turn to
“PILOT” position.
2) Push in control knob all the way and hold in
until the pilot lights up. Continue to hold the
control knob in for about 20 seconds after the
pilot is lit. Release knob.
3) Push in gas control knob slightly and
turn to "ON" position.
4) Turn ON the fl ame switch.
Gas Inlet
SHUTDOWN
PROCEDURE
1) Turn OFF the fl ame switch.
2) Push in gas control knob slightly and turn to
"OFF" position.
FIRST FIRE
The fi rst fi re in your stove is part of the paint
curing process. To ensure that the paint is
properly cured, it is recommended that you burn
your fi replace for at least four (4) hours the fi rst
time you use it with the fan on.
When fi rst operated, the unit will release an odour
caused by the curing of the paint, the burning
off of any oils remaining from manufacturing.
Smoke detectors in the house may go off at
this time. Open a few windows to ventilate the
room for a couple of hours.
The glass panel may require cleaning after the
unit has cooled down.
DO NOT ATTEMPT TO CLEAN THE
GLASS WHILE IT IS HOT.
Note: When the glass is cold and the
appliance is lit, it may cause
condensation and fog the glass.
This condensation is normal and
will disappear in a few minutes as
the glass heats up.
DO NOT BURN THE APPLIANCE
WITHOUT THE GLASS FRONT IN
PLACE.
During the fi rst few fi res, a white fi lm
may develop on the glass front as part
of the curing process. The glass should
be cleaned or the fi lm will bake on and
become very diffi cult to remove. Use a
non-abrasive cleaner and NEVER clean
the glass while it is hot.
NORMAL OPERATING
SOUNDS OF GAS
APPLIANCES
It is possible that you will hear some sounds
from your gas appliance. This is perfectly normal
due to the fact that there are various gauges
and types of steel used within your appliance.
Listed below are some examples. All are normal operating sounds and should not be considered
as defects in your appliance.
Blower:
Regency® gas appliances use high tech blowers
to push heated air farther into the room. It is not
unusual for the fan to make a "whirring" sound
when ON. This sound will increase or decrease
in volume depending on the speed setting of
your fan speed control.
Burner Tray:
The burner tray is positioned directly under the
burner tube(s) and logs and is made of a different
gauge material from the rest of the fi rebox and
body. Therefore, the varying thicknesses of steel
will expand and contract at slightly different
rates which can cause "ticking" and "cracking"
sounds. You should also be aware that as there
are temperature changes within the unit these
sounds will likely re-occur. Again, this is normal
for steel fi reboxes.
Blower Thermodisc:
When this thermally activated switch turns ON
it will create a small "clicking" sound. This is the
switch contacts closing and is normal.
Pilot Flame:
While the pilot fl ame is on it can make a very
slight "whisper" sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a
dull clicking sound may be audible, this is normal
operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will
expand and contract at different rates resulting
in some "cracking" and "ticking" sounds will be
heard throughout the cycling process.
Regency® P36-4 Gas Log Fireplace31
Page 32
OPERATING INSTRUCTIONS
COPY OF THE LIGHTING PLATE INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
This appliance must be installed in accordance with local codes, if any; if not, follow the
current CAN1-B149/ANSI Z 223.1 (Australia: AS5601-2004, New Zealand: NZS 5261)
WARNING: If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal injury or loss
of life. Improper installation, adjustment, alteration, service or maintenance
can cause injury or property damage. Refer to the owners information
manual provided with this appliance. For assistance or additional
information consult a qualified installer, service agency or gas supplier.
A)This appliance has a pilot which
must be lighted by hand. When
lighting the pilot, follow these
instructions exactly.
B)BEFORE LIGHTING smell all around
the appliance area for gas. Be sure
to smell next to the floor because
some gas is heavier than air and
will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electric switch, do
not use any phone in your building
- Immediately call your gas supplier
from a neighbours phone. Follow
the gas suppliers instructions.
- If you cannot reach your gas
supplier, call the fire department.
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due
to high surface temperatures keep children, clothing and furniture, gasoline
and other liquids having fammable vapors away. Keep burner and control
compartment clean. See installation and operating instructions
accompanying appliance.
LIGHTING INSTRUCTIONS
STOP! Read the safety information above on this label.
1) Push in gas control knob slightly and turn to PILOT position.
2) Push in control knob all the way and hold in until the pilot lights up. Continue
to hold the control knob in for about 20 seconds after the pilot is lit. Release
knob.
3) Push in gas control knob slightly and
turn to "ON" position.
4) Turn ON the flame switch.
TO TURN OFF GAS APPLIANCE
You may shut off the pilot during prolonged non use periods to conserve fuel.
1) Turn OFF the flame switch.
2) Push in gas control knob slightly and turn to "OFF" position.
DO NOT REMOVE THIS INSTRUCTION PLATE
C)Use only your hand to push in or turn
the gas control knob. Never use tools.
If the knob will not push in or turn by
hand, dont try to repair it, call a
qualified service technician. Force or
attempted repair may result in a fire
or explosion.
D)Do not use this appliance if any part
has been under water. Immediately
call a qualified service technician to
inspect the appliance and to replace
any part of the control system and any
gas control which has been under
water.
This appliance needs fresh air for safe
operation and must be installed so there
are provisions for adequate combustion
and ventilation air.
Gas Inlet
918-253a
MAINTENANCE
INSTRUCTIONS
1) Always turn off the gas valve before cleaning.
For relighting, refer to lighting instructions.
Keep the burner and control compartment
clean by brushing and vacuuming at least
once a year. When cleaning the logs, use a
soft clean paint brush as the logs are fragile
and easily damaged.
2) Clean appliance and door with a damp
cloth (never when unit is hot). Never use
an abrasive cleaner. The glass should be
cleaned with a gas fi replace glass cleaner.
The glass should be cleaned when it
starts looking cloudy.
3) The heater is fi nished in a heat resistant
paint and should only be refi nished with heat
resistant paint. Regency® uses StoveBright
Paint - Metallic Black #6309.
4) Make a periodic check of burner for proper
position and condition. Visually check the
fl ame of the burner periodically, making sure
the fl ames are steady; not lifting or fl oating.
If there is a problem, call an authorized
service person.
5) The appliance and fl ueing system must be
inspected before use, and at least annually,
by an authorized fi eld service person, to
ensure that the fl ow of combustion and
ventilation air is not obstructed.
Note: Never operate the appliance without
the glass properly secured in
place.
6) Do not use this appliance if any part has been
under water. Immediately call an authorized
service technician to inspect the appliance
and to replace nay part of the control system
and any gas control which has been under
water.
7) Verify operation after servicing.
General Flue Maintenance
Conduct an inspection of the fl ueing system
semi-annually. Recommended areas to inspect
as follows:
1) Check the Flueing System for corrosion in
areas that are exposed to the elements.
These will appear as rust spots or
streaks, and in extreme cases, holes.
These components should be replaced
immediately.
2) Remove the Cap, and shine a fl ashlight
down the Flue. Remove any bird nests, or
other foreign material.
32
Regency® P36-4 Gas Log Fireplace
Page 33
MAINTENANCE
3) Check for evidences of excessive
condensation, such as water droplets forming
in the inner liner, and subsequently dripping
out the joints, Continuous condensation can
cause corrosion of caps, pipe, and fi ttings.
It may be caused by having excessive
lateral runs, too many elbows, and exterior
portions of the system being exposed to
cold weather.
4) Inspect joints, to verify that no pipe
sections or fi ttings have been disturbed,
and consequently loosened. Also check
mechanical supports such as Wall Straps,
or plumbers' tape for rigidity.
GOLD-PLATED &
BRASS
LOUVRES OR TRIM
The 24 carat gold plated or brass fi nish on the
trim requires little maintenance, and need only
be cleaned with a damp cloth. DO NOT use
abrasive materials or chemical cleaners, as
they may harm the fi nish and void the warranty.
Clean any fi ngerprints off before turning the
unit on. If the top louvres start to discolour,
check the door gasket seal and replace if
necessary.
LOG REPLACEMENT
The unit should never be used with broken logs.
Turn off the gas valve and allow the unit to cool
before opening door and carefully remove the
logs. (The pilot light generates enough heat to
burn someone.) If for any reason a log should
need replacement, you must use the proper
replacement log. The position of these logs
must be as shown in the diagrams under Log
Installation.
Note: Improper positioning of logs may
create carbon build-up and will
severely alter the unit's performance
which is not covered under
warranty.
THERMOPILE /
THERMOCOUPLE
1) Open the bottom louvres.
2) Loosen the thermocouple or thermopile with
a 7/16" spanner.
3) Disconnect thermocouple by loosening
nut from the valve with a 9mm spanner.
Disconnect thermopile by loosening 2
screws marked TP on the valve.
4) Drop the thermocouple or thermopile down
from the bracket and pull it out of the unit.
5) Reinstall the new ones in reverse order.
GLASS GASKET
If the glass gasket requires replacement use
5/8" fl at glass gasket for the Bay Front (Part
# 936-243) and a tadpole glass gasket for the
Flush Front (Part # 936-155).
DOOR GLASS
Your Regency® fi replace is supplied with high
temperature, 5 mm Neoceram ceramic glass that
will withstand the highest heat that your unit will
produce. If your glass requires cleaning, we
recommend using an approved glass cleaner
available at all authorized dealers. Do not use
abrasive materials. Do not clean the glass
when hot.
In the event that you break your glass by impact,
purchase your replacement from an authorized
Regency® dealer only, and follow our step-bystep instructions for replacement.
WARNING: Do not operate the
appliance with the glass panels
removed, cracked or broken.
Replacement of the glass panels
should be done by a licensed or
qualifi ed service person.
Flush Glass Replacement
Remove the fl ush door front (as per instructions
in section "Standard Flush Door"). Remove
the 4 glass clips from each corner. Slide in the
new replacement glass. Push the 4 glass clips
back onto the frame. The glass must have
gasketing around it.
Bay Glass Replacement
1) Remove the door from the unit and place
on a soft surface to prevent scratching.
2) Remove the nuts holding the glass clips in
place and remove.
3) Replace the glass. The glass must have
gasketing around it.
5) Reverse the previous steps, replace the glass
clips and fasten with the nuts but do not over
tighten, as this can break the glass.
6) Replace door on the stove and check the
seal.
Caution: Wear gloves when
removing damaged or broken
glass.
Regency® P36-4 Gas Log Fireplace33
Page 34
MAINTENANCE
REMOVING VALVE
1) Shut off the gas supply.
2) Remove the louvres (and bay door if it is
on).
3) Open the fl ush door and remove the door.
4) Remove the logs.
5) Remove the burner/grate assembly by
removing the two Phillips head screws and
then lift the burner assembly out.
10) Undo the pilot tube from the valve with a
7/16" spanner.
11) Undo the quick drop out thermocouple nut
on the valve with a 9mm (metric) spanner.
12) Remove the Piezo igniter wire and push
button assembly.
13) Undo the "gas out" fl are nut with a 13/16"
spanner.
Undo the "gas out" fl are fi tting with an 11/16"
14)
spanner.
15) Remove the 4 Phillips head screws from
the sides of the valve bracket and remove
valve.
INSTALLING VALVE
1) Attach the valve to the valve bracket with
the 4 (m5x8 metric) screws provided.
2) Reconnect the "gas out" fl are fi tting with an
11/16" spanner.
3) Reconnect the "gas out" fl are nut with a
13/16" spanner.
4) Install piezo ignitor push button assembly
and reconnect wire.
5) Reconnect the quick drop out thermocouple
nut with a 9mm spanner.
6) Reconnect the pilot tube nut with a 7/16"
spanner.
7) Scrape off the old gasket from the fl oor of the
fi rebox and from the valve tray assembly.
8) Install a new gasket and reinstall the valve
tray assembly.
Note: Failure to install a new gasket
may severely affect the appliance
performance.
Diagram 1: Remove the left and right screws
and then lift out the burner/grate assembly.
6) Remove the rear log stand by removing the
2 screws.
Rear Log Standscrews
screwsValve Tray Assembly
Diagram 2: Rear Log Stand and
Valve Tray Assembly
7) Disconnect the inlet gas line. See diagram
2.
Hint: If you are using black pipe, ensure
that there is a union by the valve,
otherwise removal will be almost
impossible.
9) Reinstall the 10 hold down screws.
10) Hook up the 2 TP and 2 TH wires to the
appropriate connections on the valve.
11) Reinstall the front log stand.
12) Install Burner/grate assembly
13) Hook up the gas line and check for gas
leaks with a soap and water solution or a
gas leak detector. (Do not use open fl ame
for leak testing.)
14) Fire up the unit temporarily
15) Check the manifold pressure.
16) Reinstall the logs and brick panels as
needed.
17) Close the door and replace the louvres.
18) Fire up the unit again and check for proper
fl ame appearance and glow on logs.
8) Disconnect the 2 TP wires and the 2 TH
wires from the valve.
9) Remove the 10 Phillips head screws securing
the valve tray assembly in place (diagram 2)
and then lift the entire assembly out diagram
3).
34
Regency® P36-4 Gas Log Fireplace
Page 35
Part # Description
1) 910-142 Thermodisc-Fan Auto ON/OFF
2) * Thermodisc Bracket
3) 948-045 Chain
4) 948-025 Spring
6) 510-125 Terminal Block Housing
7) 910-006 Terminal Block
8) 510-126 Terminal Block Cover
9) 910-140 Fan Switch HIGH/OFF/LOW
10) 910-246 Burner Switch ON/OFF
12) 910-169/P Fan Motor
910-520 Wire Harness
910-714 Power Cord (240 V)
14) 510-026 Hinge Bracket - Left/Right
15) 948-253 Door Handle
17) * Wire Holder Clip
20) 510-033 Top Nailing Strip
21) 510-064 Side Nailing Strip
22) 510-153 Baffl e Plate
23) 510-011 Standoff - Top
24) 511-044 Standoff - Side/Back
27) * Outer Flue Collar
28) * Inner Flue Collar Assembly
30) * Gasket for Flue Collar
31) * Flue Mounting Plate
513-901 Brick Panel Set - Standard Brown
513-902 Brick Panel Set - Standard Red
513-903 Brick Panel Set - Herringbone Brown
513-904 Brick Panel Set - Herringbone Red
33) * Brick Panel - Back
34) * Brick Panel - Left
35) * Brick Panel - Right
36) 910-073 Spark Generator Battery Holder
37) 910-074 Spark Generator Switch c/w Wire
MAIN ASSEMBLY
20
22
23
PARTS LIST
31
30
28
30
27
23
24
511-031 Brick Clip (each)
918-538 Manual
513-968 Conversion Kit - NG to LPG
17
21
14
6
7
33
4
8
3
15
1
2
14
24
21
37
34
BRICK PANEL SET
35
Regency® P36-4 Gas Log Fireplace35
DOORS & LOU VERS PLEASE
REFER SEPARATE SECTION
10
9
36
Page 36
PARTS LIST
BURNER ASSEMBLY & LOG SET
Part # Description
513-560/P Valve Assy - NG
513-562/P Valve Assy - LPG
52) * Valve Tray -NG
53) 430-055 Gasket - Valve Access Plate
54) 910-421 Pilot ON/OFF 3" Extension Knob
55) 910-422 HI/LOW 3" Extension Knob
57) 910-478 S.I.T. Valve - NG/LPG
58) * Valve Bracket
59) * Firebox Base
65) * Pilot Bracket
66) 910-038 Pilot Assy-NG 3 way fl ame-S.I.T.
910-039 Pilot Assy-LPG 3 way fl ame-S.I.T.
904-240 Orifi ce #37 - NG (Burner)
904-390 Orifi ce #52 - LPG (Burner)
910-036 Pilot Orifi ce - NG
910-037 Pilot Orifi ce - LPG
936-170 Orifi ce Gasket
67) * Pilot Holder
68) W840470 Pilot Assembly Gasket
79) 512-525 Burner Assy - NG
82) 511-030 Burner Grate Assy
84) * Rear Log Support Assy
85) 512-930 Log Set
86) 910-386 Thermocouple
87) 910-341 Thermopile
88) 910-096 Pilot Hood (3-way)
95
94
92
93
98
97
96
92) * Rear Log
93) * Middle Right Log
94) * Front Left Log
95) * Center Left Log
96) * Center Right Log
97) * Front Bottom Log
98) * Middle Left Log
*Not available as a replacement part.
36
Regency® P36-4 Gas Log Fireplace
Page 37
PARTS LIST
BAY FRONT ASSEMBLY
Part # Description Part # Description 780-931 Bay Front Complete
103) 940-092/P Side Glass
107) 936-243 Glass Gasket - Soft Fibre Black
108) 940-094/P Center Glass
111) 780-905 Brick Panel Inlay - Rustic Brown Bay
780-906 Brick Panel Inlay - Old Town Red Bay
780-938 Bay Front Trim - Brass
780-936 Bay Front Trim - Steel
112) * Bay Front Trim -Top/Bottom
780-934 Bay Door Trim - Gold
113) * Bay Door Trim-Gold-Bottom
114) * Bay Door Trim-Gold-Top
510-988 Bay Louvres - Black
510-990 Bay Louvres - Gold/Black
510-992 Bay Louvres - Brass/Black
510-993 Bay Louvres - Steel/Black
Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully
inspects each unit thoroughly before it leaves our door. FPI is pleased to extend this limited lifetime warranty to the original purchaser
of a Regency
The Warranty: Lifetime
Covered under the agreement are the following components: Combustion chamber, heat exchanger, burner tubes, logs, embers, glass (thermal
breakage) and all gold plating against defective manufacture.
NOTE: Gold Plated Barcelona Front - slight imperfections in the gold plating are due to the plating process and are not considered defects.
The above will be covered for parts and labour for the fi rst fi ve years and parts only thereafter.
Electrical components such as blowers, switches, wiring, thermodiscs, remote control, thermopiles, thermocouples and gas valves are covered for
one year from the date of purchase.
The warranty on brass parts is for one year, no labour. The brass is not warranted against tarnishing.
Conditions:
All installations must be performed by a qualifi ed gas fi tter and installed according to all applicable local and national codes. Also, all service
work must be carried out by a qualifi ed gas service person provided by the selling dealer. It is the responsibility of the installer to ensure that
the appliance is fi ring as per rating plate. Any part or parts of this unit which in our judgement show evidence of such defect will be repaired or
replaced at Regency®'s option, through an accredited distributor or agent provided that the defective part be returned to the distributor or agent
Transportation Prepaid, if requested. In areas where there is not an approved service agent or the closest approved service agent is situated
more than twenty-fi ve (25) kilometres from the installation, Australian Heating Distributors are not obliged to arrange warranty repairs and travel
and/or additional labour charges will apply.
®
Product.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim. It does not cover installation and operational
related problems such as over-fi ring, downdrafts or spillage caused by environmental conditions, nearby trees, buildings, hilltops, mountains,
inadequate fl ueing or ventilation, excessive offsets, negative air pressures caused by insuffi cient make up air, mechanical systems such as furnaces,
fans, clothes dryers etc.
The warranty does not extend to any part or parts which show evidence of misuse or abuse, neglect, accident, lack of maintenance, or improper
installation.
Products made by other manufacturers and used in conjunction with the operation of this appliance without authorization from Regency®, may
nullify your warranty on this product.
FPI Ltd., shall in no event be liable for any special, indirect consequential damages of any nature whatsoever which are in excess of the original
purchase price of the product. Any alteration to the unit which causes sooting or carboning that results in damage to the exterior facia is not the
responsibility of FPI.
General:
It is essential that all submitted claims provide all of the necessary information including purchase date, serial #, type of unit and part or parts
requested.
SUBJECT TO CHANGE.
DISTRIBUTORS: Western Australia Eastern Australia
AUSTRALIAN HEATING DISTRIBUTORS FIREPLACE PRODUCTS AUSTRALIA PTY. LTD.
SERVICE AGENTS:
HEARTH HOUSE SERVICE
31 CLUNE STREET
BAYSWATER, WA 6053
31 CLUNE STREET 21-23 SOUTH LINK BLVD. BAYSWATER, WA 6053 DANDENONG, VIC 3175
NOTE: PLEASE RETAIN YOUR INVOICE AS PROOF OF PURCHASE FOR WARRANTY VERIFICATION
INCORRECT INSTALLATION OR GAS PRESSURE SETTINGS ARE NOT COVERED BY WARRANTY
A SERVICE OR CALLOUT FEE WILL BE CHARGED IN THESE CIRCUMSTANCES.