WARNING:
If the information in these instructions are not followed exactly,
a fi re or explosion may result causing property damage,
personal injury or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other fl ammable vapors and
liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed
installer, service agency or the gas supplier.
Tested by:
918-262a
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
FOR YOUR SAFETY
What to do if you smell gas:
Do not try to light any applianceDo not touch any electrical switch:
do not use any phone in your
building.
Immediately call your gas supplier
from a neighbour's phone. Follow
the gas supplier's instructions.
If you cannot reach your gas
supplier, call the fi re department.
01/04/06
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Gas Stove by FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. The
P33-3 has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch.
The P33-3 has been approved by Warnock Hersey for both safety and effi ciency. As it also bears our own mark,
it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a
moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace.
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency product has been tested and listed by Warnock Hersey as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2002/CSA 2.33-2002 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN/CGA-2.17-M91.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations,
Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow
the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA
B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
Ensure that structural members are not cut or weakened during installation.
This Regency Mobile/Manufactured Home Listed
appliance comes factory equipped with a means
to secure the unit.
This Regency Mobile/Manufactured Home listed
appliance comes equipped with a dedicated #8
ground lug to which an 18 gauge copper wire from
the steel chassis ground must be attached.
This appliance may be installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless
a certifi ed kit is used.
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
SAFETY LABEL
This is a copy of the label that accompanies each
P33-3 Zero Clearance Direct Vent Gas Fireplace.
We have printed a copy of the contents here for
your review. The safety label is located on the
front inside base of the unit, visible when the
bottom louver is open.
NOTE: Regency units are constantly being
improved. Check the label on the unit and if
there is a difference, the label on the unit is the
correct one.
For the State of Massachusetts, installation
and repair must be done by a plumber or
gasfi tter licensed in the Commonwealth of
Massachusetts.
For the State of Massachusetts, fl exible
connectors shall not exceed 36 inches in
length.
For the State of Massachusetts, the appliances individual manual shut-off must be a
t-handle type valve.
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
IMPORTANT:
SAVE THESE
INSTRUCTIONS
The P33-NG3 or P33-LP3 Direct Vent Fireplace
must be installed in accordance with these instructions. Carefully read all the instructions in
this manual fi rst. Consult the "authority having
jurisdiction" to determine the need for a permit
prior to starting the installation. It is the responsibility of the installer to ensure this fi replace
is installed in compliance with manufacturer's
instructions and all applicable codes.
BEFORE YOU START
Safe installation and operation of this appliance requires common sense, however, we
are required by the Canadian Safety Standards
and ANSI Standards to make you aware of the
INSTALLATION AND REPAIR
SHOULD BE DONE BY A QUALIFIED SERVICE PERSON. THE
APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT
LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE
FREQUENT CLEANING MAY
BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING,
BEDDING MATERIAL, ETC. IT IS
IMPERATIVE THAT CONTROL
COMPARTMENTS, BURNERS
AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE
BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES,
THE APPLIANCE SHOULD BE
LOCATED OUT OF TRAFFIC AND
AWAY FROM FURNITURE AND
DRAPERIES.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN
THEY ARE IN THE SAME ROOM
AS THE APPLIANCE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT
BE PLACED ON OR NEAR THE
APPLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local codes or, in the absence of local codes,
with the current Canadian or National
Gas Codes, CAN1-B149 or ANSI Z223.1
Installation Codes.
2) The appliance when installed, must be
electrically grounded in accordance with
local codes, or in the absence of local codes
with the current National Electrical Code,
ANSI/NFPA 70 or CSA C22.1 Canadian
Electrical Code.
3) See general construction and assembly
instructions. The appliance and vent should
be enclosed.
4) This appliance must be connected to the
specifi ed vent and termination cap to the
outside of the building envelope. Never vent
to another room or inside a building. Make
sure that the vent is fi tted as per Venting
instructions.
5) Inspect the venting system annually for
blockage and any signs of deterioration.
6) Venting terminals shall not be recessed into a
wall or siding.
10) Be aware of electrical wiring locations in
walls and ceilings when cutting holes for
termination.
11) Under no circumstances should this ap-
pliance be modifi ed. Parts that have to be
removed for servicing should be replaced
prior to operating this appliance.
12) Installation and any repairs to this appliance
should be done by a qualifi ed service person. A professional service person should
be called to inspect this appliance annually.
Make it a practice to have all of your gas
appliances checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid
fuels (wood, paper, cardboard, coal, etc.)
be used in this appliance.
15) The appliance area must be kept clear and
free of combustible materials, (gases and
other fl ammable vapours and liquids).
Emissions from burning wood or gas could
contain chemicals known to the State of California to cause cancer, birth defects or other
reproductive harm.
MANUFACTURED
MOBILE HOME
ADDITIONAL
REQUIREMENTS
1) Ensure that structural members are not cut
or weakened during installation.
2) Ensure proper grounding using the #8
ground lug provided. See page 34.
WARNING: FAILURE TO INSTALL
THIS APPLIANCE CORRECTLY
WILL VOID YOUR WARRANTY
7) Any safety glass removed for servicing
must be replaced prior to operating the
appliance.
AND MAY CAUSE A SERIOUS
HOUSE FIRE.
CHILDREN AND ADULTS SHOULD
8) To prevent injury, do not allow anyone who
is unfamiliar with the operation to use the
fi replace.
BE ALERTED TO THE HAZARDS
OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIRE-
9) Wear gloves and safety glasses for protec-
tion while doing required maintenance.
PLACE GLASS, AND SHOULD
STAY AWAY TO AVOID BURNS OR
CLOTHING IGNITION.
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
INSTALLATION
CHECKLIST
1) Locate appliance
a) Room location, page 6
b) Clearances to Combustibles, page 7
c) Mantle Clearances, page 7
d) Framing & Finishing Requirements,
page 8
e) Venting Requirements, pages 10 to
15.
2) Assemble Top Facing Support and Side
Nailing Strips, page 9. (NOTE: must be
done before installing unit into fi replace.)
3) Install vent, pages 10 to 24.
4) Make gas and electrical connections. Test
the pilot. Must be as per diagram. Page 25.
Convert to Propane if desired, page 26.
5) Install brick panels (optional), page 27.
6) Install logs and embers and rockwool where
indicated on page 27.
7) Install Flush Door Front (Standard) and
optional Flush Gold Trim, page 28.
UNIT DIMENSIONS
4) The P33-3 can be installed in a recessed
position or framed out into the room as in
A, B, C, D. See Diagram 1.
5) This appliance is Listed for bedroom instal-
lations when used with a Listed Millivolt
Thermostat. Some areas may have further
requirements, check local codes before
installation.
6) The P33-3 Direct Vent Gas Fireplace is ap-
proved for alcove installations, which meet
the clearances listed on this page.
7) We recommend that you plan your instal-
lation on paper using exact measurements
for clearances and fl oor protection before
actually installing this appliance. Have a
qualifi ed inspector, dealer, or installer review
your plans before installation.
Note: For vent terminations see page 10.
8) Install optional Double Screen Door, page
29.
9) Install Optional Bay Front and optional Bay
Gold Trim, page 29.
10) Install Louvers (Flush or Bay), pages 28
and 29.
11) Install optional Wall Switch, Remote Control,
or Wall Thermostat, page 33.
11) Install Optional Fan, page 35.
13) Final check.
Before leaving this unit with the customer, the
installer must ensure that the appliance is fi ring correctly and operation fully explained
to customer.
This includes:
1) Clocking the appliance to ensure the correct
fi ring rate (rate noted on label) after burning
appliance for 15 minutes.
2) If required, adjusting the primary air to ensure
that the fl ame does not carbon. First allow
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that
causes sooting or carboning that results
in damage is not the responsibility of the
manufacturer.
LOCATING YOUR
GAS STOVE
1) When selecting a location for your stove,
ensure that the clearances outlined on this
page are met.
2) Provide adequate clearances for servic-
ing.
3) The appliance must be installed on a fl at,
solid, continuous surface (e.g. wood, metal,
concrete). This may be the fl oor, or raised up
on a platform to enhance its visual impact.
If the appliance is going to be installed on
carpeting, combustible linoleum tile or other
combustible material other than wood fl ooring, the appliance must be installed on a
metal or wood panel extending the full width
and depth of the appliance.
Diagram 1
A) Flat on Wall
B) Flat on Wall Corner
C) Recessed into Wall/Alcove
DUCT SYSTEM
OPTION
KIT #946-556
The HeatWave Air Duct Kit increases the effectiveness of your fi replace by dispersing warm
air from the fi replace to remote locations in the
same room or other rooms in your home.
Up to two kits may be installed on the fi replace.
Please Note: Only 1 HeatWave kit may be
operated at one time. This includes the internal
blower option as well.
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is
failure to maintain required clearances (air
space) to combustible materials. It is of the
greatest importance that this fi replace and
vent system be installed only in accordance
with these instructions.
Clearance to Combustibles from:
Back 0" (0mm)
Side 0" (0mm)
Floor 0" (0mm)
NOTE: The minimum fl oor clearance must be
maintained from the top surface of the carpeting, tile, etc.
Alcove Clearances:
Max. Depth 36" (914mm)
Min. Width 48" (1219mm)
Min. Height 59" (1499mm)
* see mantel clearance instructions.
WARNING
Fire hazard is an extreme risk if these
clearances are not adhered to.
Because of the extreme heat this fi replace emits, the mantel clearances are critical. Com-
bustible mantel clearances from top of unit are shown in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made
of metal studs covered with a non-combustible board.
This drawing is to scale at 1:6 (one inch = 6 inches). Mantel can be installed anywhere in shaded
area or higher using the above scale.
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the
COMBUSTIBLE MANTELS
paint may discolour.
MANTEL LEG CLEARANCES
Combustible mantel leg clearances as per diagram below:
Clearances for Bay or Flush Front
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
Maximum
1-1/2" projection at 2"
minimum clearance.
The HeatWave Duct Kit has different clear-
ance and framing requirements, check the
HeatWave manual for details.
INSTALLATION
FRAMING AND FINISHING
1) Determine the total thickness of facing
material (e.g. drywall plus ceramic tiles) to
allow the fi nished surface to be fl ush with
the front of the unit. Total facing thickness
can vary from 1/2" (13mm) to 1-1/4" (32mm)
thick.
Install Side Nailing Strips, and Top Facing
Support before unit is slipped into position.
See page 9 for assembly details.
2) Frame in the enclosure for the unit with
framing material.
Vertical Termination or
Vertical Rise with Horizontal
Termination
For Both Simpson & Flex
NOTE: If this is an outside corner, the
minimum distance between the vent and the
outside corner is 6" (15cm) with AstroCap
termination cap or 12" (30cm) with Dura-Vent
termination cap.
Rear Termination
Simpson Dura-Vent Piping
Flex Piping
For Both Simpson & Flex
NOTE: If this is an outside corner, the minimum
distance between the vent and the outside corner
is 6" (15cm) with AstroCap termination cap or 12"
(30cm) with Dura-Vent termination cap.
3) For exterior walls, insulate the enclosure to
the same degree as the rest of the house,
apply vapour barrier and drywall, as per local installation codes. (Do not insulate the
fi replace itself.)
4) The top of the unit must not be closer than
30" (762mm) to the ceiling.
5) Combustible material may be brought up to
the top and sides of the unit and be covered
with ceramic tiles, bricks, rock or other suitable combustible fi nishing materials.
Note: The unit does not have to be complete-
ly enclosed in a chase. The clearance
on top of the unit is 0" to the standoffs
so combustible building materials can
be laid directly on top of the standoffs.
You must maintain clearance from the
vent to combustible materials for fl ex
for Simpson Dura-Vent, see page 7.
Simpson Dura-Vent
Minimum Clearances
Top Header
1/2"
(13mm)
Drywall
1-1/2"
(38mm)
(102mm)
Opening for gas
4"
(76mm)
connection
3"
10" (254mm)
dia. Hole through
wall for Dura-Vent
30”
(762mm)
16-1/2”
(419mm)
Minimum
Flex Pipe
Minimum Clearances
Top Header
1/2"
(13mm)
Drywall
1-1/2"
(38mm)
4"
(102mm)
Opening for gas
6) Use steel studs for framing where the
1-1/2" (38mm) clearance from the vent
to combustible material cannot be maintained.
The HeatWave Duct Kit has different clear-
ance and framing requirements, check the
HeatWave manual for details.
3"
(76mm)
connection
10" (254mm)
dia. Hole through
wall for Flex
26”
(660mm)
12-3/4”
(324mm)
Minimum
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
UNIT ASSEMBLY
PRIOR TO INSTALLATION
INSTALLATION
The Top Facing Support, the Side Nailing Strips
and the 2 Top Standoffs must be correctly positioned and attached to the top before the unit
is put into position.
Top Standoff Assembly
The top standoffs are shipped in a fl at position
and must be pulled up and bent into the correct shape.
1) Remove the standoffs from on top of the
fi rebox by undoing the screws.
2) Take each standoff and bend into the cor-
rect shape. Bend up at the bend lines until
the screw holes in the standoff and the
pre-punched screw holes on the fi rebox top
line-up.
3) Attach the standoffs securely to the top with
4 screws per standoff.
Note: Secure the standoffs to the holes
closest to the edge of the fi rebox top.
Top Facing Support &
Side Nailing Strips
Determine the total thickness of facing material (e.g. drywall plus ceramic tiles) to allow the
fi nished surface to be fl ush with the front of the
unit. Total facing thickness can vary from 1/2"
(13mm) to 1-1/4" (32mm) thick.
The Top Facing Support & Side Nailing Strips
can be mounted in various positions depending
on the thickness of the facing material.
1) Mount Top Facing Support using the 3
supplied screws into the three pre-punched
screw holes on the top front of the unit. Adjust
support to desired facing material depth.
2) Mount Side Nailing Strip using the 3 sup-
plied screws into the three pre-punched
screw holes at the front sides of the unit.
Adjust support to desired facing material
thickness.
For a facing material depth of
1-1/4"(32mm), the top facing
support must be reversed.
VENTING INTRODUCTION
The P33-3 uses the "balanced fl ue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer
liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing
warm room air up the chimney.
There are 2 vent systems approved for use with the P33-3: the Regency Direct Vent System (Flex) for Horizontal Terminations only (see pages
11-12), and the Simpson Dura-Vent Systems for Horizontal and Vertical Terminations (see pages 13-24).
Note: These fl ue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid
fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
NOTE: Ensure compliance with the outside vent terminal location before cutting hole as both dimensions must be met.
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
EXTERIOR VENT TERMINATION LOCATIONS
18"
24"
Vertical
Termination
A
L
V
N
j
H
V
B
A
B
Closed
K
Fixed
V
V
Openable
B
V
B
A
Area where terminal is not permited
from the centerline of the regulator.
any other appliance *(12"/30cm) #(9"/23cm)
H= Not to be installed above a meter/regulator assembly within (3'/90cm) horizontally
J= Clearance to service regulator vent outlet *(min. 36"/90cm)
K= Clearance to non-mechanical air supply inlet to building or the combustion air inlet to
*(min. 84"/2.1m)
L= Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
#3' (91cm) above if within 10' (3m) horizontally.
M= Clearance above paved sidewalk or a paved driveway located on public property
N= Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)
Inside
corner detail
V
G
Vertical
Termination
Air supply outlet
A
Openable
Fixed
Closed
C
A
V
.
B
24"
E
V
D
M
V
B
V
F
Vent terminal
V
Dura-Vent Termination Cap (12"/30cm)
distance of (24"/60cm) from the centerline of the terminal (min. 18"/46cm) check with
B= Clearance to window or door that may be opened *(12"/30cm) #(9"/23cm)
C= Clearance to permanently closed window *(min. 12"/30cm)
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
E= Clearance to unventilated soffi t (min. 15"/38cm)
D= Vertical clearance to ventilated soffi t located above the terminal within a horizontal
Vent Termination Cap (12"/30cm)
G= Clearance to inside corner: with AstroCap Termination Cap (min. 6"/15cm), with Dura-
F= Clearance to outside corner: with AstroCap Termination Cap (min. 6"/15cm), with
Note:
- A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.
- Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
- If the vent termination is accessible, a certifi ed guard shall be installed.
* As specifi ed in CGA B149 Installation Code. Note: Local codes or regulations may require different clearances.
# In accordance with the current ANSI Z223.1/NFPA 54, Natioinal Fuel Gas Code.
INSTALLATION
REGENCY DIRECT VENT SYSTEM (FLEX)
HORIZONTAL TERMINATIONS ONLY
This venting system, in combination with the P33-3 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock
Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram on page 10.
Regency Direct Vent (Flex) System Termination Kit (Part # 946-513) includes all the parts needed to install the P33-3 with a maximum
run of 2 feet. If installing the P33 with a continuous vent length of more than 2 ft (.6m) to a maximum of 10 ft. (3.0m) using Kit # 946-515 (4 ft) or
946-516 (10 ft) or see page 13 for alternate venting arrangements.
1) 6-7/8" dia. fl exible liner (2 ft. length)
2) 4" dia. fl exible liner (2 ft. length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" drill point, stainless steel (4)
Notes:
1) Liner sections should be continuous without any
joints or seams.
2) Only Flex pipe purchased from Regency may be
used for Flex installations.
4" (102mm)
dia. flue pipe
Wall Thimble (2 pc)
(required in
Canada only)
spring
spacer
AstroCap
Termination Cap
(Part# 946-523/P)
See also
Figure 1 below.
TM
Important
If using any Cabinet Mantels with Part
# 510956, 510958, 510962, 510964
and 510834 the wall thimble must
be secured fi rst and venting must be
attached to unit before sliding into
fi nal position.
Also Simpson Dura-Vent venting cannot be used with any of the mantels
noted above.
Minimum
Simpson Dura-Vent Center-Line
6-7/8"
(173mm)
dia. Flue pipe
Minimum Flex Kit Center-Line
Alternate Hori-
zontal Termi-
nation Caps
Figure 1
Wherever necessary due to
external location of cap, the
AstroCap can be replaced with
the FPI Riser Vent Termination
Cap or the Dura-Vent Snorkel
Termination Cap.
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
INSTALLATION PROCEDURES
for Regency Direct Vent System (Flex)
1) Locate the unit in the framing, rough in the
gas (preferably on the right side of the unit)
and the electrical (Junction block is on the
left side) on the left. Locate the centerline of
the termination and mark wall accordingly.
Cut a 10"(254mm) hole in the wall (inside
dimension).
Note: To make the installation more aes-
thetically pleasing, we recommend
framing out a square to mount the
terminal to.
Note: A 2-1/2" (64mm) horizontal top and
1-1/2" (38mm) horizontal sides &
bottom clearance around the liner
must be maintained except that only
a 1" (25mm) clearance is needed at
the termination end. We recommend
framing a 10"(254mm) x 10"(254mm)
(inside dimensions) hole to give
structural rigidity for mounting the
termination.
Note: If installing termination on a siding
covered wall, furring strips must be
used to ensure that the termination
is not recessed into the siding.
2) Level the fi replace and fasten it to the fram-
ing using nails or screws through the nailing
strips.
3) Assemble the vent assembly by applying
Mill Pac to the 4"(100mm) inner collar of the
termination and slipping the 4"(100mm) liner
over it at least 1-3/8" (35mm). Fasten with
the 3 screws (drilling pilot holes will make this
easier). Apply Mill Pac or high temperature
silicone to the 6-7/8"(175mm) fl ex pipe and
slip it over the 6-7/8" outer collar of the vent
terminal at least 1-3/8"(35mm) and fasten
with the 3 screws.
4) Separate the 2 halves of the wall thimble and
securely fasten the one with the tabs to the
outside wall making sure that the tabs are
on top and bottom. Fasten the other thimble
half to the inside wall. The thimble halves
slip inside each other and can be adjusted
for 2 x 4 or 2 x 6 walls. The liners must slip
over the collars a minimum of 1-3/8".
*If this is an outside corner, the minimum distance between the vent and the outside
corner is 6" (15cm) with AstroCap termination cap or 12" (30cm) with Dura-Vent
termination cap. See "F" on the diagram on page 10.
Minimum and Maximum Vent Clearances
5) Slip the assembled liner and termination
assembly through the thimble making sure
the termination cap faces up (there are
markings on the cap that show which way
is up). This will position the termination cap
with proper down slope for draining water.
Fasten the cap to the outer wall with the 4
supplied screws.
6) Pull the centre 4"(100mm) liner and outer
6-7/8"(175mm) liner out enough to slip over
the fl ue collars of the fi replace.
7) Apply Mill Pac over the fi replace inner collar
and slip the 4"(100mm) liner down over it
and attach with 3 supplied screws.
8) Do the same with the 6-7/8"(175mm) liner.
4" (102mm)
dia. flue pipe
with spring spacer
Screws
(3 per
connection)
6-7/8"
(175mm)
dia. air intake
Wall Thimble 2 pieces
(10" (254mm) Outer Diameter)
9) Apply a bead of silicone between the thimble
and termination and around the outer edge
of the terminal at the wall in order to keep
the water out.
IMPORTANT: Do not locate termination
hood where excessive snow or ice
buildup may occur. Be sure to check
vent termination area after snow falls,
and clear to prevent accidental blockage of venting system. When using
snow blowers, make sure snow is
not directed towards vent termination
area.
2”x4”or2”x6”
(21mm x 102mm
or 21mm x 152mm)
Termination Cap
Screws
(4 per connection)
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
INSTALLATION
The minimum components required for a basic
horizontal termination are:
1 AstroCap Horizontal Termination Cap
1 45o Elbow
1 Rigid Pipe Adaptor
1 Wall Thimble
1 Length of pipe to suit wall thickness
(see chart)
For siding other than vinyl furring strips may be
used, instead of the vinyl siding standoff, to create
a level surface to mount the vent terminal. The
Terminal must not be recessed into siding.
If a Vinyl Siding Standoff is required (it must be
used with vinyl siding), measure to outside surface
of wall without siding and add 2 inches.
Alternate Hori-
zontal Termi-
nation Caps
Vertical
Terminal
Storm Collar
Flashing
Ceiling Firestop
Pipe Length
o
90 Elbow
24" (610mm)
Pipe Length
o
45 Elbow
Vinyl Siding
Standoff (Optional)
Adj.Pipe Length
11" - 14-5/8"
(279mm - 372mm)
Wall Thimble
Adj.Pipe Length
11" - 14-5/8"
(279mm - 372mm)
Horizontal
Termination
Cap
Wall Thimble
Horizontal
Termination Cap
Vinyl Siding
Standoff (Optional)
Rigid Pipe Adaptor
WARNING:
Do not combine venting components from
different venting systems.
However use of the the AstroCapTM and FPI
Riser is acceptable with all systems.
This product has been evaluated by Intertek for
using a Dura-Vent Flue Adaptor in conjunction
Flat Wall Installation
Max. Wall Vent Length
Thickness (inches) Required (inches)
7-1/4" 6"
with Selkirk Direct-Temp and Ameri Vent Direct
venting systems. Use of these systems with the
Direct Vent GS starting collar is deemed acceptable and does not affect the Intertek WHI listing
of components.
The FPI AstroCap
American Metal Products, Ameri Vent Direct vent and Selkirk Direct-Temp. FPITM, and FPI AstroCapTM are the proprietary trademarks of FPI Fireplace
Products International Ltd. Dura-Vent® and Direct Vent GS are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
TM
and FPI Riser Vent terminal is certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent®, Direct Vent GS,
When using piping other than Simpson
Dura-Vent, 3 screws must be used to
secure rigid pipe to adaptor.
Regency P33-3 Zero Clearance Direct Vent Gas Fireplace
INSTALLATION
RIGID PIPE VENTING COMPONENTS LIST
All Simpson Dura-Vent components are available directly from FPI.
Description Simpson Dura-Vent Selkirk AmeriventR
Direct VentGS
Ceiling Support 949 - n/a from FPI 4DT-CS 4DFSP
Cathedral Support Box 941 4DT-CSS 4DRSB
Wall Support/Band 988 4DT-WS/B 4DWS
Offset Support 989 - n/a from FPI 4DT-OS N/A
Wall Thimble, Black 942 4DT-WT 4DWT
Wall Thimble Support Box/Ceiling Support 940 N/A N/A
Firestop Spacer 963 4DT-FS 4DFSP
Trim Plate, Black N/A 4DT-TP 4DFPB
Brass Trim for Wall Thimble/Ceiling Support 3951 N/A N/A