Regency P121-NG, P121LC-NG, P121RC-NG, P131-NG User Manual

Owners & Installation
Zero Clearance Room
Sealed Gas Fireplace
Manual
LISTINGS AND CODE APPROVALS
These gas appliances have been tested in accordance with AS4553-2000, NZS 5262 and have been certified by the Australian Gas Association for installation and operation as described in these Installation and Operating Instructions.
Your unit should be serviced annually by an authorised service person.
STYLE MODEL See Thru P121-NG P121-LPG Left Corner P121LC-NG P121LC-LPG Right Corner P121RC-NG P121RC-LPG Pier P131-NG P131-LPG
PLEASE KEEP THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING: Improper installation, adjustment, altera­tion, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional infor­mation consult an authorized installer, serv­ice agency or the gas supplier.
FOR YOUR SAFETY Do not store or use gasoline or other flamma­ble vapours and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by an authorized installer, service agency or the gas supplier.
FOR YOUR SAFETY What to do if you smell gas:
918-179a
02/16/06
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Gas Fireplace by REGENCY. The P121/P121LC/P121RC/ P131 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The model P121/P121LC/P121RC/P131 has been approved by the Australian Gas Association for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace.
IMPORTANT:
If the unit is to be installed into a bathroom, optional Neo ceramic glass Part# 360-946 Front or Part# 360-948 Side must be purchased and installed in place of the tempered glass supplied with the unit.
2
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
TABLE OF CONTENTS
Safety Label
Safety Label ............................................................... 4
Installation
Important Message .................................................... 5
Before You Start ........................................................ 5
General Safety Information ......................................... 5
Installation Checklist .................................................. 5
Specifications ............................................................ 6
Locating Your Fireplace ............................................. 8
Clearances ................................................................. 9
Combustible Mantel Clearances ................................. 9
Framing and Finishing ...............................................10
Facing and Finishing Requirements .......................... 11
Unit Assembly Prior to Installation
Top Standoff Assembly ....................................... 11
Flueing Introduction ...................................................11
Exterior Flue Termination Locations .......................... 12
Flueing: Direct Vent System (Flex) ........................... 13
Flueing: Simpson Dura-Vent Direct Vent GS .............14
Flueing: Simpson Dura-Vent Components List .......... 14
Flueing Arrangements
Horizontal Terminations ...................................... 15
Vertical Terminations ..........................................17
Flueing - Dura-Vent Horizontal Installations ...............19
Flueing - Dura-Vent Vertical Termination ................... 20
Flueing - Installation Procedures for Direct Vent
System (Flex) ..................................................... 21
Converion to LPG ......................................................22
System Data ............................................................. 23
Gas Line Installation..................................................23
Pilot Adjustment ....................................................... 23
Gas Pipe Pressure Test ............................................ 23
S.I.T. Valve Description .............................................23
Log Set Installation ................................................... 24
Glass Door Removal..................................................26
Finishing Trim ........................................................... 26
Louvers and Grills......................................................26
Remote Control (optional) .......................................... 27
Remote Wall Switch (optional) .................................. 27
Wall Thermostat (optional) ........................................27
Wiring Diagram ......................................................... 28
Operating Instructions
Operating Instructions ............................................... 29
Lighting Procedure .................................................... 29
Shutdown Procedure .................................................29
First Fire ...................................................................29
Normal Operating Sounds of
Gas Appliances .................................................. 29
Aeration Adjustment..................................................29
Lighting Plate Instructions ......................................... 30
Maintenance
Maintenance Instructions .......................................... 30
General Flue Maintenance ........................................30
Log Replacement ...................................................... 31
Thermopile/Thermocouple ......................................... 31
Glass Gasket ............................................................ 31
Door Glass ................................................................ 31
Gold-Plated Accessories ...........................................31
Removing Valve .........................................................31
Installing Valve .......................................................... 32
Parts List
Replacement/Spare Parts List ................................... 33
Warranty
Warranty ...................................................................39
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 3
SAFETY LABEL
This is a copy of the label that accompanies each REGENCY P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open.
NOTE: Regency units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
4
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
INSTALLATION
IMPORTANT:
SAVE THESE
INSTRUCTIONS
The Regency P121/P121LC/P121RC/P131-NG or P121/P121LC/P121RC/P131-LPG Room Sealed Gas Fireplace must be installed in ac­cordance AG601 and NZS 5261 and with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the respon­sibility of the installer to ensure this fireplace is installed in compliance with manufacturer's instructions and all applicable codes.
BEFORE YOU START
Safe installation and operation of this appliance requires common sense, however, we are required to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY A AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A AUTHORIZED SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPER­ATIVE THAT CONTROL COMPART­MENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLI­ANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNI­TURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CLOTHING OR OTHER FLAMMABLE MA­TERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIAL­LY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE AP­PLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance shall be installed in accord­ance with the manufacturer's installation instructions, local gas fitting regulations, municipal building codes, water supply reg­ulations, electrical wiring regulations, with AS5601-2004 (AGA gas installation code) NZS 5261 (New Zealand)
2) See general construction and assembly instructions. The appliance and flue should be enclosed.
3) This appliance must be connected to the specified flue and termination cap to the outside of the building envelope. Never flue to another room or inside a building. Make sure that the flue is fitted as per Flueing instructions.
4) Inspect the flueing system annually for blockage and any signs of deterioration.
5) Flueing terminals shall not be recessed into a wall or siding.
6) Any safety glass removed for servicing must be replaced prior to operating the appliance.
7) To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.
8) Wear gloves and safety glasses for pro­tection while doing required maintenance.
9) Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
10) Under no circumstances should this appli­ance be modified. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
11) Installation and any repairs to this appliance should be done by a authorized service person. A authorized service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
12) Do not slam shut or strike the glass door.
13) Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
14) The appliance area must be kept clear and free of combustible materials, (gases and other flammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INSTALLATION
CHECKLIST
Note: These units are
non-load bearing.
1) Locate appliance a) Room location, page 8. b) Clearances to Combustibles,
page 9. c) Mantle Clearances, page 9. d) Framing & Finishing Requirements,
page 10. e) Flueing Requirements, pages 11-19.
2) Assemble Top Standoffs, page (NOTE: page 11 must be done before installing unit into fireplace.)
3) Install flue, pages 19-21.
4) Make gas connections. Test the pilot. Must be as per diagram. Page 22.
5) Install log set where indicated on page 24-25.
6) Glass Door Removal (page 26), Louvers or Grills (page 26), and Finishing Trim (page 26).
7) Install optional Wall Switch, Remote Con­trol, or Wall Thermostat, page 27.
8) Final check.
Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to cus­tomer.
This includes:
1) Clocking the appliance to ensure the cor­rect firing rate (rate noted on label 40,000 Btu/h NG, and 39,000 Btu/h LPG) after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsi­bility of the manufacturer.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 5
INSTALLATION
SPECIFICATIONS
P121 - See Thru
Note: These units are non-load bearing.
P131 - Pier
6
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
P121LC - Left Corner Unit
INSTALLATION
Note: These units are non-load bearing.
P121RC - Right Corner Unit
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 7
INSTALLATION
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your stove, ensure that the clearances are met as outlined on page 9.
2) Provide adequate clearances for servic­ing.
3) The appliance must be installed on a flat, solid, continuous surface (e.g. wood, met­al, concrete). This may be the floor, or raised up on a platform to enhance its visual impact. If the appliance is going to be in­stalled on carpeting, combustible linoleum tile or other combustible material other than wood flooring, the appliance must be in­stalled on a metal or wood panel extending the full width and depth of the appliance.
4) The Room Sealed Gas Fireplace can be installed as follows:
A) P121 - See Thru
Model # Position A ) P121: See Thru B) P131: Pier C) P121LC: Left Corner D) P121RC: Right Corner
5) This appliance is Listed for bedroom instal­lations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
6) The P121/P121LC/P121RC/P131 Room Sealed Gas Fireplace is approved for al­cove installations, which meet the clear­ances listed on this page.
7) We recommend that you plan your installa­tion on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have a authorized inspector, dealer, or installer review your plans before installation.
Note: For Exterior Flue Termination
Locations see page 12.
.
B) P131 - Pier
C) P121LC - Left Corner
D) P121RC - Right Corner
8
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams on page 8):
Clearance to Combustibles from:
Back 0" (0mm) Side 0" (0mm) Floor 0" (0mm)
CAUTION REQUIREMENTS: The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoffs may NOT be recessed into combus­tible construction.
Determine the total thickness of the finished floor (eg. tile, carpet, slate) to allow the finished surface to be flush with the base of the unit.
Ceiling Height from Floor 72" (1828mm)
Fire hazard is an extreme risk
if these clearances (air space)
to combustible materials are
not adhered to. It is of greatest
importance that this fireplace
and flue system be installed
only in accordance with these
INSTALLATION
WARNING:
instructions.
Mantel Height from Base of Unit:
39" min. (991mm)
Horizontal Flue Clearances:
Top 2-1/2"(64mm) Side 1-1/2"(38mm) Bottom 1-1/2"(38mm)
Vertical Flue Clearances 1-1/4" (32mm)
COMBUSTIBLE MANTELS
Because of the extreme heat this fireplace emits, the mantel clearanc­es are critical. Combustible mantel clearances from top of unit are shown in
Diagram to the right.
Note: A non-combustible mantel may be installed at a lower height if
the framing is made of metal studs covered with a non­combustible board.
This drawing is to scale at 1:6 (one inch = 6 inches) Mantel can be installed anywhere in shaded area or higher using this scale.
Caution: Ensure the paint that is used on the mantel and the facing is
"heat resistant" or the paint may discolour.
Mantel Clearances
* If the 3" (76mm) metal extension trim is removed it must be replaced with a 8" (203mm) non-combustible material.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 9
B
C
A
INSTALLATION
FRAMING AND FINISHING
1) For ease of installation, frame your fireplace after it is positioned and the flue system is installed. Remember to install the top standoffs. See page 11 for assembly. Use 2x4's and frame to local building codes.
CAUTION: Verify your fireplace dimensions, framing methods and finished wall facing details before framing. Determine the total thickness of facing material - drywall plus ceramic tiles, slate, etc. Allow the finish surface to be flush with the front or side of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.
2) When locating your appliance on an exterior wall or in a chase, apply a vapour barrier and drywall, as per local building codes. DO NOT
INSULATE THE FIREPLACE ITSELF.
CAUTION: The unit does not have to be completely enclosed in a chase. The clearance on top of the unit is 0" to the standoffs so combustible building materials can be laid directly on top of the standoffs. You must maintain clearance from the flue to combustible materials for both rigid and flex, see Flue Clear­ances, page 9.
P121 - See Thru
Framing Dimensions
P121 (See Thru) P131 (Pier) P121LC / P121RC
(Corner Unit)
A 25"(635mm) 25"(635mm) 26-13/13"(660mm)
minus two times minus two times minus two times the finishing the finishing the finishing material thickness* material thickness* material thickness*
B 42-1/2"(1080mm) 42-1/2"(1080mm) 42-1/2"(1080mm)
C 46-3/4"(1187mm) 45" (1143mm) 45"(1143mm)
minus one time minus one time the finishing the finishing material thickness* material thickness*
* Finish material thickness includes: drywall, ceramic tile, slate, etc.
P121LC - Corner Unit
P131 - Pier
Note: These units are non-load bearing.
10
P121RC - Corner Unit
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
INSTALLATION
FACING & FINISHING REQUIREMENTS
This fireplace is supplied with a 3" metal extension trim above the fireplace. The extension trim may be replaced if the framing is faced with a non­combustible material placed flush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position.
Top Standoff Assembly
The top standoffs are shipped in a flat position and must be folded into shape and attached.
1) Remove the standoffs from the fireplace top.
2) Take each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the pre-punched screw holes on the fireplace top line up.
3) Attach the standoff securely to the top with 4 screws per standoff (on opposite cor­ners).
FLUEING
INTRODUCTION
The P121/P121LC/P121RC/P131 uses the "balanced flue" technology Co Axial system. The inner liner flue products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be con-
nected to any other appliance.
The gas appliance and flue system must be flueed directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct flue gas appliance must use it's own separate flue system. Common flue sys­tems are prohibited.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 11
INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced flue terminals or
the flue terminals of outdoor appliances
according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand)
Minimum
a Below eaves, balconies or other projections:
- Appliances up to 50 MJ/h input 300
- Appliances over 50 MJ/h input 500 b From the ground or above a balcony 300 c From a return wall or external corner 500 d From a gas meter (M) 1000 e From an electricity meter or fuse box (P) 500 f From a drain or soil pipe 150 g Horizontal from any building structure (unless appliance is approved
for closer installation) or obstruction facing a terminal 500 h From any other flue terminal, cowl or combustion air intake 500 j Horizontally from an openable window, door, or non-mechanical air inlet, or
any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)):
- Appliances up to 150 MJ/h input 500
- Appliances over 150 MJ/h input 1500
k Vertically below an openable window, door, or non-mechanical air inlet,
or any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)): see table below
Clearance (mm)
Clearance 'k' in mm
Space Heaters All Other Appliances Up to 50 MJ/h Up to 50 MJ/h input Over 50 MJ/h input Over 150 MJ/h input
input to 150 MJ/h input
12
150 500 1000 1500
NOTES: (I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases. (II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest
par to of the terminal. (III) Prohibited area below electricity meter or fuse box extends to ground level. (IV)A flue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on
at least two sides and a free flow of air at the appliance is achieved.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
INSTALLATION
FLUEING ARRANGEMENT - HORIZONTAL TERMINATIONS
Regency Direct Vent System (Flex) Horizontal Terminations Only
These flueing systems, in combination with the P121/P121LC/P121RC/P131 Direct Vent Gas Fireplace, have been tested and listed as a direct flue heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram on page 12.
Regency Direct Vent (Flex) System Termination Kit (Part# 946-513) includes all the parts needed to install the P121/P121LC/P121RC/ P131 with a maximum run of 2 feet.
1) 6-7/8" dia. flexible liner (2 ft. length)
2) 4" dia. flexible liner (2 ft. length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" drill point, stainless steel (4)
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex installations.
3) Regency Direct Vent System (Flex) is only approved for horizontal terminations.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 13
INSTALLATION
SIMPSON DURA-VENT FLUEING
Horizontal or Vertical Terminations
The Simpson Dura-Vent Direct Vent System offers a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized finish. We recommend using the galvanized finish for installation with the P121/ P121LC/P121RC/P131.
The minimum components required for a basic horizontal termination are:
1 Simpson Duravent Adaptor 1 Horizontal Termination Cap 145o Elbow 1 Flue Adaptor 1 Wall Thimble 1 Length of pipe to suit wall thickness
(see chart)
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl furring strips may be used, instead of the
Flat Wall Installation
vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Meas­ure the wall thickness in­cluding furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.
Wall Thickness Vent Length
(inches) Required (inches)
4" - 5-1/2" 6" 7" - 8-1/2" 9"
10" - 11-1/2" 12"
9" - 14-1/2" 11" - 14-5/8" Adj. Pipe
15" - 23-1/2" 17" - 24" Adj. Pipe
The Regency AstroCap venting systems as well as Simpson Dura-Vent® and Direct Vent GS.
TM
is certified for installations using FPI
RegencyTM, and Regency AstroCapTM are the proprietary trade­marks of FPI Fireplace Products International Ltd.
Dura-Vent® and Direct Vent GS are registered and/or propri­etary trademarks of Simpson Dura-Vent Co. Inc.
Simpson Dura-Vent Direct Vent GS
SIMPSON DURA-VENT FLUEING COMPONENTS LIST
All Simpson Dura-Vent components are available directly from Regency.
Part # Description Part # Description Part # Description
971 Horiz. Termination Kit includes: 90o black elbow, wall thimble cover, horiz. square termination cap, 24" black pipe, and 11"
-14" 5/8" adjustable black pipe 970 Basic Horiz. Termination. Kit includes:
90o black elbow, wall thimble cover, horiz. square termination cap
978 Vert. Termination Kit includes 0/12 -
6/12 pitch adjustable flashing, storm
collar, low profile term. cap 908B 6" Pipe Length - Black 907B 9" Pipe Length - Black 906 12" Pipe Length - Galv. 906B 12" Pipe Length - Black 904 24" Pipe Length - Galv. 904B 24" Pipe Length - Black 903 36" Pipe Length - Galv. 903B 36" Pipe Length - Black
14
902 48" Pipe Length - Galv. 902B 48" Pipe Length - Black 911B 11"-14 5/8" Adjustable Pipe Length -
Black 917B 17"- 24" Adjustable Length - Black 945 45O Elbow - Galv. 945B 45O Elbow - Black 945G 45O Elbow - Swivel - Galv. 945BG 45O Elbow - Swivel - Black 990 90O Elbow - Galv. 990B 90O Elbow - Black 990G 90O Elbow - Swivel - Galv. 990BG 90O Elbow - Swivel - Black 991 High Wind Termination Cap (Vertical) 980 Vertical Termination Cap 984 Horizontal Square Termination Cap 985 Horiz. Square High Wind Termination
Cap
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
982 Snorkel - 14" Rise Termination Cap 981 Snorkel - 36" Rise Termination Cap 940 Wall Thimble - Support/Box 941 Cathedral/Ceiling - Support/Box 3951 Brass Trim for Wall Thimble/Ceiling Sup. 963 Firestop Spacer 943 Flashing 0/12-6/12 943S Flashing 7/12-12/12 953 Storm Collar 950 Vinyl Siding Standoff 988 Wall Strap 942 Wall Thimble
Parts not supplied by Dura-Vent
946-506/P Vent Guard (Optional) 510-994 Dura-Vent Flue Adaptor 640-530/P Riser Vent Terminal 946-205 Vinyl Siding Shield for Riser
946-206 AstroCap Standoff
Vent Terminal
INSTALLATION
FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (LPG & NG)
The diagram below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90 elbow).
Note:
1) A maximum of three 90o elbows are permitted.
2) Minimum distance between elbows is 1 ft. (305mm).
Maintain clearances to combustibles as listed on page 9.  Horizontal flue must be supported every 3 feet.  Firestops are required at each floor level and whenever passing through a wall.  Must use optional flue adapter (Part# 510-994) when using Simpson Dura-Vent pipe.  A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes.
Straight Out Horizontal Flueing
Horizontal Flueing with One (1) 90o Elbow
Simpson Dura-Vent 4" inner diameter 6-5/8" outer diameter
Option V H
A) 1' (305mm) Minimum 3' (914mm) Maximum B) 2' (610mm) Minimum 6' (1.86m) Maximum C) 3' (914mm) Minimum 9' (2.7m) Maximum D) 4' (1.22m) Minimum 12' (3.6m) Maximum E) 5' (1.5m) Minimum 15' (4.5m) Maximum F) 6' (1.86m) Minimum 17' (5.1m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
o
Diagram 1
Diagram 2
Please note the minimum centerline for basic install shown above.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 15
INSTALLATION
Horizontal Flueing with Two (2) 90o Elbows
Option V H + H1
A) 1' (305mm) Minimum 2' (610mm) Maximum B) 2' (610mm) Minimum 5' (1.5m) Maximum C) 3' (914mm) Minimum 8' (2.4m) Maximum D) 4' (1.22m) Minimum 11' (3.35m) Maximum E) 5' (1.5m) Minimum 14' (4.27m) Maximum F) 6' (1.86m) Minimum 15' (4.5m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 15 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Horizontal Flueing with Three (3) 90o Elbows
Option V H H + H1 + H2
A) 2' (610mm) Min. 1' (305mm) Max. 3' (914mm) Max. B) 3' (914mm) Min. 3' (914mm) Max. 6' (1.86m) Max. C) 4' (1.22mm) Min. 5' (1.5m) Max. 9' (2.7m) Max. D) 5' (1.5m) Min. 7' (2.13m) Max. 12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 5
Diagram 3
Horizontal Flueing with Two (2) 90o Elbows
Option V H H + H1
A) 1' (305mm) Min. 1' (305mm) Max. 3' (914mm) Max. B) 2' (610mm) Min. 3' (0.91m) Max. 6' (1.86m) Max. C) 3' (914mm) Min. 5' (1.5m) Max. 9' (2.7m) Max. D) 5' (1.5m) Min. 8' (2.4m) Max. 12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Horizontal Flueing with Three (3) 90o Elbows
Option V + V1 H + H1
A) 2' (610mm) Minimum 3' (914mm) Maximum B) 3' (914mm) Minimum 6' (1.86m) Maximum C) 4' (1.22m) Minimum 9' (2.7m) Maximum D) 5' (1.5m) Minimum 12' (3.6m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
16
Diagram 4 Diagram 6
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
INSTALLATION
FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS
SIMPSON DURA-VENT DIRECT VENT GS SYSTEM (LPG & NG)
Flue must be supported at offsets Maintain clearances to combustibles as listed on page 9. Firestops are required at each floor level and whenever passing through a wall.
Must use optional flue adapter when using Simpson Dura-Vent pipe (Part# 510-994).
The P121/P121LC/P121RC/P131 is approved for a maximum 35 ft. (10.7m) straight vertical, with Simpson Dura-Vent Direct Vent GS flue systems for LPG and NG, as per diagram 7 below.
Straight Up Vertical Flueing
Vertical Flueing with One (1) 90o Elbow
Option V H
A) 1' (305mm) Minimum 2' (610mm) Maximum B) 2' (610mm) Minimum 4' (1.22m) Maximum C) 3' (914mm) Minimum 6' (1.86m) Maximum D) 4' (1.22m) Minimum 8' (2.4m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 7
Diagram 8
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 17
INSTALLATION
Vertical Flueing with Two (2) 90o Elbows
Option V H
A) 1' (305mm) Minimum 4' (1.22m) Maximum B) 2' (610mm) Minimum 6' (1.86m) Maximum C) 3' (914mm) Minimum 9' (2.7m) Maximum D) 4' (1.22m) Minimum 12' (3.6m) Maximum E) 5' (1.5m) Minimum 15' (4.5m) Maximum F) 6' (1.86m) Minimum 17' (5.1m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Vertical Flueing with Two (2) 90o Elbows
Option V H + H1
A) 1' (305mm) Minimum 2' (610mm) Maximum B) 2' (610mm) Minimum 4' (1.22m) Maximum C) 3' (914mm) Minimum 6' (1.86m) Maximum D) 4' (1.22m) Minimum 8' (2.4m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 9
Diagram 10
Vertical Flueing with Three (3) 90o Elbows
Option V + V1 H H + H1
A) 2' (610mm) Min. 1' (305mm) Max. 2' (610mm) Max. B) 3' (914mm) Min. 4' (1.22m) Max. 5' (1.5m) Max. C) 4' (1.22mm) Min. 6' (1.86m) Max. 8' (2.4m) Max. D) 5' (1.5m) Min. 8' (2.4m) Max. 12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
18
Diagram 11
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
Vertical Flueing with Three (3) 90o Elbows
Option V + V1 H + H1
A) 2' (610mm) Minimum 3' (914mm) Maximum B) 3' (914mm) Minimum 6' (1.86m) Maximum C) 4' (1.22m) Minimum 9' (2.7m) Maximum D) 5' (1.5m) Minimum 12' (3.6m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 12
INSTALLATION
HORIZONTAL
INSTALLATIONS
Install the flue system according to the manufacturer's instructions included with the components.
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in the way when the flueing system is at­tached. If this is the case, you may want to adjust the location of the unit. Rough in the gas.
2) Direct Flue pipe and fittings are designed with special twist-lock connections to con­nect the flueing system to the appliance flue outlet. A twist-lock appliance adaptor is an available option that must be used in con­junction with the Simpson Dura-Vent Direct Vent GS system.
3) Put a bead of silicone inside the outer section of the adapter and a bead of Mill Pac on the inner collar. Slip the adapter over the exist­ing inner and outer flue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fireplace and fasten it to the framing using nails or screws through the nailing strips.
4) Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.
Note:
a) Twist-lock procedure: Four indentations,
located on the female ends of pipes and fittings, are designed to slide straight onto the male ends of adjacent pipes and fittings, by orienting the four pipe inden­tations so they match and slide in to the four entry slots on the male ends, Dia-
gram 1. Push the pipe sections com­pletely together, then twist-lock one section clockwise approximately one­quarter turn, until the two sections are fully locked. The female locking lugs will not be visible from the outside, on the Black Pipe or fittings. They may be located by examining the inside of the female ends.
Diagram 1
Note: Apply sealant "Mill-Pac" to inner
pipe and high temperature sili­cone sealant to outer pipe on eve­ry twist-lock joint.
b) Horizontal runs of flue must be sup-
ported every three feet. Wall straps are available for this purpose.
5) Mark the wall for a 10" x 10" square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the flue will be termi­nated. If the wall being penetrated is con­structed of non-combustible material, i.e. masonry block or concrete, a 7"(178mm) dia. (7-1/2"(191mm) dia. for flex) hole is acceptable.
Note: With Dura-Vent, the minimum height is achieved by installing a 45o elbow di­rectly to the flue adaptor.
Diagram 2
Note:
a) The horizontal run of flue must be level,
or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the flue to run downward. This could cause high temperatures and may present the possibility of a fire.
b) The location of the horizontal flue termi-
nation on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Flue Terminal Locations, see diagram on page 12.
6) The arrow on the flue cap should be pointing up. Insure that the 1-1/2" clear-
ances to combustible materials are main­tained (Diagram 3 on page 16). Install the termination cap.
The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
Note: If installing termination on a siding
covered wall, a vinyl siding stand­off or furring strips must be used
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 19
INSTALLATION
Diagram 3
to ensure that the termination is not recessed into the siding.
7) Before connecting the horizontal run of flue
pipe to the flue termination, slide the Wall Thimble (Part # 942) over the flue pipe.
8) Slide the appliance and flue assembly to­wards the wall carefully inserting the flue pipe into the flue cap assembly. It is impor­tant that the flue pipe extends into the flue cap sufficient distance so as to result in a minimum pipe overlap of 1-1/4 inches. Se­cure the connection between the flue pipe and the flue cap by attaching the two sheet metal strips extending from the flue cap assembly into the outer wall of the flue pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 4.
9) Install wall thimble in the center of the 10" square and attach with wood screws (Di­agram 5).
VERTICAL
TERMINATION
1) Maintain the 1-1/4" clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfac­es. Do not pack air spaces with insulation. Check pages 17-19 for the maximum vertical rise of the flueing system and the maximum horizontal offset limitations.
2) Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance flue exit, and mark the location where the flue will pene-
trate the ceiling. Drill a small hole at his point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the flue will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will obstruct the flueing system. You may wish to relocate the appliance or to offset, as shown in Dia­gram 2 to avoid cutting load bearing mem­bers.
Diagram 1
Diagram 2
4) Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.
5) Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to com­bustibles of 1-1/4". Slip the flashing under the shingles (shingles should overlap half the flashing) as per Diagram 4.
Diagram 4: The upper half of the flashing is
installed under the roofing material and not
nailed down until the chimney is installed.
This allows for small adjustments.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic
to avoid obstructions, it is impor­tant to support the flue pipe every 3 feet, to avoid excessive stress on the elbows, and possible sep­aration. Wall straps are available for this purpose (Diagram 2).
Galvanized pipe is desirable above the roof­line due to its higher corrosion resistance. Continue to add pipe sections through the flashing until the height of the flue cap meets the minimum height requirements specified in Diagram 5 or local codes. Note that for steep
20
Diagram 4
Diagram 5
Note: Apply sealant "Mill-Pac" to inner
pipe and high temperature sili­cone sealant to outer pipe on eve­ry twist-lock joint.
3) A Firestop spacer must be installed in the
floor or ceiling of every level. To install the Firestop spacer in a flat ceiling or wall, cut a 10 inch square hole. Frame the hole as shown in Diagram 3 and install the firestop.
Diagram 3
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
Diagram 5
Roof Pitch Minimum Vent Height
Feet Meters
flat to 7/12 2 0.61
over 7/12 to 8/12 2 0.61
over 8/12 to 9/12 2 0.61
over 9/12 to 10/12 2.5 0.76
over 10/12 to 11/12 3.25 0.99
over 11/12 to 12/12 4 1.22
over 12/12 to 14/12 5 1.52
over 14/12 to 16/12 6 1.83
over 16/12 to 18/12 7 2.13
over 18/12 to 20/12 7.5 2.29
over 20/12 to 21/12 8 2.44
INSTALLATION
roof pitches, the vertical height must be increased. A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the flue height may solve the problem.
7) Ensure flue is vertical and secure the base of the flashing to the roof with roofing rails, slide storm collar over the pipe section and seal with a mastic.
8) Install the vertical termination cap by twist­locking it.
Note: Any closets or storage spaces,
which the flue passes through must be enclosed.
Offset Chart
Note: To make the installation more aesthetically pleas­ing, we recom­mend framing out a square to mount the terminal to.
be used to ensure that the termi­nation is not recessed into the siding.
2) Level the fireplace and fasten it to the
framing using nails or screws through the nailing strips.
3) Assemble the flue assembly by applying Mill Pac to the 4"(100mm) inner collar of the termination and slipping the 4"(100mm) liner over it at least 1-3/8" (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Apply Mill Pac or high temper­ature silicone to the 6-7/8"(175mm) flex pipe and slip it over the 6-7/8" outer collar of the flue terminal at least 1-3/8"(35mm) and fas­ten with the 3 screws.
NOTE: Horizontal sections must be sup-
ported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).
4) Separate the 2 halves of the wall thimble and
securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip
inside each other and can be adjusted for 2 x 4 or 2 x 6 walls. The liners must slip
over the collars a minimum of 1-3/8".
5) Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.
6) Pull the centre 4"(100mm) liner and outer 6-7/8"(175mm) liner out enough to slip over the flue collars of the fireplace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than 45o.
7) Apply Mill Pac over the fireplace inner collar and slip the 4"(100mm) liner down over it and attach with 3 supplied screws.
8) Do the same with the 6-7/8"(175mm) liner.
9) Apply a bead of silicone between the thim-
ble and termination and around the outer edge of the terminal at the wall in order to keep the water out.
IMPORTANT: Do not locate termination hood where excessive snow or ice build­up may occur. Be sure to check flue termi­nation area after snow falls, and clear to prevent accidental blockage of flueing system. When using snow blowers, make sure snow is not directed towards flue termination area.
INSTALLATION
PROCEDURES
for Regency AstroCapTM Direct
Flue System (Flex)
1) Locate the unit in the framing, rough in the gas. Locate the centerline of the termina­tion and mark wall accordingly. Cut a 10"(254mm) hole in the wall (inside dimen­sion).
Note: A 1-1/2"(38mm) clearance around
the liner must be maintained ex­cept that only a 1" (25mm) clear­ance is needed at the termination end. We recommend framing a 10"(254mm) x 10"(254mm) (inside dimensions) hole to give struc­tural rigidity for mounting the ter­mination.
Note: If installing termination on a siding
covered wall, furring strips must
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 21
INSTALLATION
CONVERSION KIT FROM NG TO LPG MODEL #730-969
FOR P121/P121LC/P121RC/P131 USING SIT 820 NOVA GAS VALVE
THIS CONVERSION MUST BE DONE BY A AUTHORIZED GAS FITTER
IF IN DOUBT DO NOT DO THIS CONVERSION !!
Conversion Kit Contains:
Qty. Part # Description 1 910-018 SIT Conversion Kit-50%
Turndown LPG 1 910-037 LPG Injector (Pilot Orifice) 1 * Burner Orifice #50 1 908-255 Decal "Converted to LPG" 1 908-529 5/32" Allen Key 1 918-032 Instruction Sheet
1) Remove the louvers and trim kit. Remove the
front door.
2) Remove the logs, embers.
3) Remove the grate by lifting straight up.
Remove the side brick panels (if installed). The brick panel is very fragile - handle
with care.
4) Remove the burner assembly by removing
the 4 Phillips head screws and then slide the burner assembly away from the orifice and lift out.
5) Remove pilot inner box by removing the 2 screws.
6) Pull off the pilot cap to expose the pilot orifice.
7) Unscrew the pilot orifice with the allen key and replace with the LPG pilot orifice in the kit and replace pilot cap.
8) Re-install pilot inner box using 2 screws.
9) Remove burner orifice with a 1/2" spanner
and discard. Use another spanner to hold on to the elbow behind the orifice.
Diagram 1: Remove the left and right screws and then slide the burner assembly away from the orifice and lift out.
22
Burner Orifice
10) Reinstall new burner orifice LPG stamped #50 and tighten.
11) Remove and discard the 3 pressure regu­lator mounting screws (A), pressure regu­lator tower (B) and diaphragm (C).
12) Insure that the rubber gasket (D) is properly positioned and install the new HI/LO pres­sure regulator assembly to the valve using the new screws (E) supplied with the kit. Tighten screws securely.
13) Reverse steps 4) to 1).
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
14) Attach clear label "This unit has been con­verted to LPG" near or on the serial # decal. Attach white label "This valve has been converted from NG to LPG using SIT con­version Kit Code 0.907.202" onto the valve.
15) Replace yellow "NG" label with red "LPG" label
16) Check for gas leaks.
17) Check inlet and outlet pressures.
18) Check operation of flame control.
19) Check for proper flame appearance and
glow on logs.
INSTALLATION
P121/P121LC/P121RC/P131-NG
System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #31 Pilot Orifice NG
Max. Input Rating 42 mj. Min. Input Rating 22 mj.
Supply Pressure min. 1.13 kPa
Manifold Pressure
(High) 1.00 kPa
Log Set: Ceramic fibre, 8 per set. Flue System: Regency AstrocapTM, Re-
gency Direct Vent System (Flex) and Simp­son Dura-Vent Direct Flue System
P121/P121LC/P121RC/P131-LPG
System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #50 Pilot Orifice LPG
Max. Input Rating 41 mj. Min. Input Rating 22 mj.
Supply Pressure min. 3.00 kPa
Manifold Pressure
(High) 2.65 kPa
Log Set: Ceramic fibre, 8 per set. Flue System: Regency AstrocapTM, Re-
gency Direct Vent System (Flex) and Simp­son Dura-Vent Direct Flue System
Important: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.
PILOT ADJUSTMENT
Periodically check the pilot flames. Cor­rect flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).
Note: If you have an incorrect flame pat-
tern, contact your Regency dealer for further instructions.
Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.
Note: To properly check gas pressure,
both inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a 1/8" wide flat screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with the unit burning and the setting should be within the limits specified on the safety label.
6) When finished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" flat screwdriver.
snug, but do not over tighten.
Note: Screw should be
S.I.T. VALVE DESCRIPTION
1) Gas cock knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection
Point
GAS LINE
INSTALLATION
The gas line can be brought through either the right, the left side or the bottom of the appliance. The gas valve is situated on the bottom of the unit.
The gas line connection may be made of rigid pipe, copper pipe or an approved flex connec­tor. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and AS5601-2004 (Australian Installation Code) NZS 5261(New Zealand Installation Standard).
When using copper or flex connectors use only approved fittings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and flex connectors are usually considered to meet this requirement.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 23
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 3.45 kPa. Disconnect piping from valve at pressures over
3.45 kPa.
The manifold pressure is controlled by a regu­lator built into the gas control, and should be checked at the pressure test point.
INSTALLATION
LOG INSTALLATION
Read the instructions below carefully and refer to the dia­grams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation.
Log Kit # 360-930 contains the following pieces:
a) 326 Front Right Log 902-326 b) 327 Front Left Log 902-327 c) 328 Middle Right Log 902-328 d) 329 Middle Left Log 902-329 e) Embers 902-154
Please note that there are 2 of each log. This log set is mirrored front and back.
327
326
1) Carefully remove the logs from the box and unwrap them. The logs are fragile, handle with care - do not force into position.
2) Place Log 326 on the front right side of the burner. Ensure that the
notches on the far right side of the log fit into the grate posts. Push back side of the left end of the log up against the tab on the burner.
326
Push back side of the left end of the log up
against the tab on the burner.
Repeat step 2 on the opposite side of the burner.
329
The 3-digit numbers (ie. 327) are
molded into the rear of each log.
The image below shows all of the logs in place.
326 329328
328
327
326
326
3) Place Log 327 on the front left side of the burner. Position the right end of the log in between the two tabs and the left end of the log into the grate post.
327
24
328327 329 326
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
Grate Post
Tab on Burner
INSTALLATION
Repeat step 3 on the opposite side of the burner.
327
327
4) Embers should be placed in front of Log 326 and Log 327 and also
down the middle between the logs as shown in the image below.
Repeat step 5 on the opposite side of the burner.
329
329
6) Place Log 328 on the middle right side of the burner. Ensure that the log fits over the 2nd grate post from the right.
Caution: Do NOT cover burner ports.
5) Place Log 329 on the middle left side of the burner. Rest the bottom
of the Log onto the second grate post from the left. Ensure that the log fits into a pin that is on Log 326.
329
326
328
Grate Post
Repeat step 6 on the opposite side of the burner.
328
328
Grate Post
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 25
Place Log 329 onto pin.
INSTALLATION
GLASS DOOR
REMOVAL
1) Remove the 8 screws that secure the glass door.
2) Pull the door slightly out on an angle and
then lift up and pull completely out.
FINISHING TRIM
1) Slide the Side Finishing Trim up into the slot in the top flange of the fireplace. Push tight against the magnet at the base of the unit.
Slide Trim into
slot.
Push trim tight
against magnet.
LOUVERS & GRILLS
1) Attach the screws provided to the top left and right corners.
NOTE: Do not tighten the screw entirely, ensure that some room is left to be able to hang the grill or louver over the screw.
2) Hang the Top Louver or Grill onto the 2 screws in the top fireplace opening.
3) Attach the Bottom Louver or Grill to the hinges on the bottom flange of the fireplace.
3) P131 & P121LC/P121RC Corner Model: Remove the 6 screws that secure the glass door and repeat step 2.
2) Slide the Corner Finishing Trim up into the slot in the top flange of the fireplace. Push tight against the magnet at the base of the unit.
Slide Trim into
slot.
Push trim tight
against magnet.
P121 & P131 Corner Models
4) Attach the screws provided to the top and bottom, left and right corners similar to step
1.
5) Hang the top and bottom louver or grill onto the screws in the top and bottom, left and right sides of the fireplace opening.
The Top and Bottom Side Louver or Grill is
installed the same way.
26
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
INSTALLATION
Option 1:
REMOTE CONTROL
Can be used with Option 2 or 3
but not both.
Use the Regency Remote Control Kit approved for this unit. Use of other systems may void your warranty.
The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.
1) Choose a convenient location on the wall to install the receiver and the receptacle box (protection from extreme heat is very im­portant). Run wires from the fireplace to that location. Use the Thermostat Wire Ta­ble.
2) Connect the two wires to the gas valve. See diagram below.
CAUTION
Do not connect millivolt remote
control wires to a 240V wire.
3) Install 3 AAA alkaline batteries in transmitter and 4 AA alkaline batteries in the receiver. Install the receiver and its cover in the wall. Switch the remote receiver to "remote" mode. The remote control is now ready for operation.
Option 2:
WALL SWITCH
Can be used with Option 1 or 3
but not both.
1) Run the supplied 4.5m of wire through the back gas inlet opening. Be careful not to damage wire.
Note: We recommend a maximum of
4.5m of wire but if you wish to go with a longer run, use the Thermo­stat Wire Table.
2) Connect the wire to the supplied wall switch
and install into the receptacle box.
CAUTION
Do not connect millivolt
wall switch wire to a 240V wire.
Option 3:
WALL THERMOSTAT
Can be used with Option 1 or 2
but not both.
A wall thermostat may be installed if desired, connect the wires as per the wiring diagram. Use the table below to determine the maximum wire length.
Note: Preferable if the thermostat is in­stalled on an interior wall.
Regency offers an optional programmable ther­mostat but any 250-750 millivolt rated non­anticipator type thermostat that is CSA, ULC or UL approved may be used.
CAUTION
Do not connect millivolt
wall thermostat wires
to a 240V wire.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size Max. Length
14 GA. 16 GA. 18 GA. 20 GA. 22 GA.
15.0 M.
10.0 M.
6.0 M.
3.6 M.
2.7 M.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 27
INSTALLATION
FROM
POWER LIVE
POWER NEUTRAL
WHITE
TERMINAL
BLOCK
FAN 1
1
2
FAN 2
~
BLACK
GROUND
(WIRE SUPPLY & INSTALL BY OTHERS)
910-802 BLACK
CONVECTION AIR TEMPERATURE SWITCH
(THERMO DISC - NORMALLY OPEN)
~
ON-OFF SWITCH (910-138) BLACK
910-610 BLACK
Lockwasher
Nut
#8 Ground Lug
(for mobile home)
Star washer
Ground Wire
Grounding Lug Detail
Yellow
Orange
Burner
ON OFF
DC Spark
Box
Ground
To Thermocouple IN
Pilot
Assembly
H
I
L
O
O
F
F
O
N
P I
L
O
T
Gas Pilot
Thermopile
Thermocouple
Electrode
Remote Transmitter
(Optional)
ON OFF
Regency
Remote Receiver
or Thermostat
(Millivolt) (Optional)
Brown
White
"S.I.T" Valve
(To THTP)
(To TH)
Gas In
WIRING DIAGRAM
No electrical power supply is required for the gas control to operate.
(Do not cut the ground terminal off under any circumstances.)
Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring er­rors can cause improper and dangerous operation.
Terminal Block Location
access Terminal
Remove cover to
Block
Terminal Block
28
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
OPERATING INSTRUCTIONS
OPERATING
INSTRUCTIONS
1) Read and understand these instructions before operating this appliance.
2) Check to see that all wiring is correct and enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the door frame is
properly positioned. Never operate the ap­pliance with the glass removed.
5) Verify that the flueing and cap are unob­structed.
6) Ensure that the brick panels are installed.
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have been incorrectly positioned.
8) The unit should never be turned off, and on again without a minimum of a 60 second wait.
LIGHTING
PROCEDURE
1)
Push in gas control knob slightly and turn to PILOT position.
2)
Push in control knob all the way and hold in until the pilot lights up. Continue to hold the control knob in for about 20 seconds after the pilot is lit. Release knob.
3)
Push in gas control knob slightly and turn to "ON" position.
4)
Turn ON the flame switch.
SHUTDOWN
PROCEDURE
1) Turn OFF the flame switch.
2) Push in gas control knob slightly and turn to "OFF"
position.
FIRST FIRE
DO NOT BURN THE APPLIANCE WITHOUT THE GLASS FRONT IN PLACE.
The first fire in your stove is part of the paint curing process. To ensure that the paint is properly cured, it is recommended that you burn your fireplace for at least four (4) hours the first time before you use it with the fan on.
When first operated, the unit will release an odour caused by the curing of the paint, the burning off of any oils remaining from manufac­turing. Smoke detectors in the house may go off at this time. Open a few windows to ventilate the room for a couple of hours.
Note: When the glass is cold and the
appliance is lit, it may cause con­densation and fog the glass. This condensation is normal and will disappear in a few minutes as the glass heats up.
During the first few fires, a white film may develop on the glass front as part of the curing process. The glass should be cleaned after the unit has cooled down or the film will bake on and become very difficult to remove. Use a non-abrasive cleaner and DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS HOT.
NORMAL OPERATING
SOUNDS OF GAS
APPLIANCES
It is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various gauges and types of steel used within your appliance. Listed below are some examples. All are normal operating sounds and should not be considered as defects in your appliance.
Blower:
Regency gas appliances use high tech blow­ers to push heated air farther into the room. It is not unusual for the fan to make a "whirring" sound when ON. This sound will increase or decrease in volume depending on the speed setting of your fan speed control.
Burner Tray:
The burner tray is positioned directly under the burner tube(s) and logs and is made of a different gauge material from the rest of the firebox and body. Therefore, the varying thick­nesses of steel will expand and contract at slightly different rates which can cause "tick­ing" and "cracking" sounds. You should also be aware that as there are temperature changes within the unit these sounds will likely re-occur. Again, this is normal for steel fireboxes.
Blower Thermodisc:
When this thermally activated switch turns ON it will create a small "clicking" sound. This is the switch contacts closing and is normal.
Pilot Flame:
While the pilot flame is on it can make a very slight "whisper" sound.
Gas Control Valve:
As the gas control valve turns ON and OFF, a dull clicking sound may be audible, this is normal operation of a gas regulator or valve.
Unit Body/Firebox:
Different types and thicknesses of steel will expand and contract at different rates resulting in some "cracking" and "ticking" sounds will be heard throughout the cycling process.
AERATION
ADJUSTMENT
The burner aeration is factory set. Adjustment may be needed due to the local gas supply or altitude. As a general rule if the flame is too yellow open up the air shutter, if it is too blue close the air shutter.
Gas Inlet
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 29
NG 10mm open LPG 10mm open
NOTE: This adjustment is only to be made by an authorised person.
OPERATING INSTRUCTIONS
TO TURN OFF GAS APPLIANCE
FOR YOUR SAFETY READ BEFORE LIGHTING
This appliance must be installed in accordance with local codes, if any; if not, follow the
current CAN1-B149/ANSI Z 223.1 (Australia: AS5601-2004, New Zealand: NZS 5261)
1) Turn OFF the flame switch.
2) Push in gas control knob slightly and turn to "OFF" position.
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due to high surface temperatures keep children, clothing and furniture, gasoline and other liquids having fammable vapors away. Keep burner and control compartment clean. See installation and operating instructions
accompanying appliance.
LIGHTING INSTRUCTIONS
A)This appliance has a pilot which
must be lighted by hand. When lighting the pilot, follow these instructions exactly.
B)BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electric switch, do not use any phone in your building
- Immediately call your gas supplier from a neighbours phone. Follow the gas suppliers instructions.
- If you cannot reach your gas supplier, call the fire department.
C)Use only your hand to push in or turn
the gas control knob. Never use tools. If the knob will not push in or turn by hand, dont try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D)Do not use this appliance if any part
has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
DO NOT REMOVE THIS INSTRUCTION PLATE
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owners information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency or gas supplier.
918-253a
You may shut off the pilot during prolonged non use periods to conserve fuel.
STOP! Read the safety information above on this label.
1) Push in gas control knob slightly and turn to PILOT position.
2) Push in control knob all the way and hold in until the pilot lights up. Continue to hold the control knob in for about 20 seconds after the pilot is lit. Release knob.
3) Push in gas control knob slightly and turn to "ON" position.
4) Turn ON the flame switch.
COPY OF THE LIGHTING PLATE INSTRUCTIONS
Gas Inlet
MAINTENANCE
INSTRUCTIONS
1) Always turn off the gas valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacu­uming at least once a year. When cleaning the logs, use a soft clean paint brush as the logs are fragile and easily damaged.
2) Clean appliance and door with a damp cloth (never when unit is hot). Never use an abrasive cleaner. The glass should be cleaned with a gas fireplace glass cleaner.
The glass should be cleaned when it starts looking cloudy.
3) The heater is finished in a heat resistant paint and should only be refinished with heat resistant paint. Regency uses Stove­Bright Paint - Metallic Black #6309.
4) Make a periodic check of burner for proper position and condition. Visually check the flame of the burner periodically, making sure the flames are steady; not lifting or floating. If there is a problem, call a author­ized service person.
5) The appliance and flueing system must be inspected before use, and at least annual­ly, by a authorized field service person, to ensure that the flow of combustion and ventilation air is not obstructed.
Note: Never operate the appliance with-
out the glass properly secured in place.
6) Do not use this appliance if any part has
been under water. Immediately call a au­thorized service technician to inspect the appliance and to replace nay part of the control system and any gas control which has been under water.
7) In the event this appliance has been serv­iced check that the flue-air system has been properly resealed & reinstalled in accordance with the manufacturer's in­structions.
8) Verify operation after servicing.
30
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
General Flue Maintenance
Conduct an inspection of the flueing system semi-annually. Recommended areas to inspect as follows:
1) Check the Flueing System for corrosion in areas that are exposed to the elements. These will appear as rust spots or streaks, and in extreme cases, holes. These com­ponents should be replaced immediately.
MAINTENANCE
2) Remove the Cap, and shine a flashlight down the Flue. Remove any bird nests, or other foreign material.
3) Check for evidences of excessive con­densation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fittings. It may be caused by having exces­sive lateral runs, too many elbows, and exterior portions of the system being ex­posed to cold weather.
4) Inspect joints, to verify that no pipe sections or fittings have been disturbed, and conse­quently loosened. Also check mechanical supports such as Wall Straps, or plumbers' tape for rigidity.
LOG REPLACEMENT
The unit should never be used with broken logs. Turn off the gas valve and allow the unit to cool before opening door and carefully remove the logs. (The pilot light generates enough heat to burn someone.) If for any reason a log should need replacement, you must use the proper replacement log. The position of these logs must be as shown in the diagrams under Log Installation.
GLASS GASKET
If the glass gasket requires replacement use a tadpole glass gasket (Part # 936-155).
DOOR GLASS
Your Regency fireplace is supplied with high temperature 5mm-Tempered glass & 5mm-Ce­ramic glass. If your glass requires cleaning, we recommend using an approved glass cleaner available at all authorized dealers. Do not use abrasive materials.
CAUTION & WARNINGS:
* Do not clean when the glass is hot. * The use of substitute glass will void all product warranties. * Care must be taken to avoid breakage of the glass. * Do not strike or abuse the glass. * Do not operate this fireplace without the glass front or with a cracked or broken glass front. * Wear gloves when removing damaged or broken glass. * Replacement of the glass panels should be done by a licensed or authorized service per son.
REMOVING VALVE
1) Shut off the gas supply.
2) Remove the louvers and trim kit. Remove the front door.
3) Remove the logs, embers.
4) Remove the grate by lifting straight up.
5) Remove the side brick clip in the top of the firebox and then slide the Side Brick Panel out. The brick panels are very fragile
- handle with care.
Note: Improper positioning of logs may
create carbon build-up and will severely alter the unit's perform­ance which is not covered under warranty.
THERMOPILE/
THERMOCOUPLE
1) Open the Bottom Louvers or Grills. Remove the Top Louver or Grill.
2) Remove the Trim Kit, Glass Door, Log Set, Grate and Burner Assembly (see page 26).
3) Disconnect thermocouple by loosening nut from the valve with a 9mm spanner. Dis­connect thermopile by loosening 2 screws marked TP on the valve.
4) Remove 2 screws from the pilot assembly and pull up far enough to be able to loosen the thermocouple or thermopile with a 7/16" spanner. NOTE: the pilot line is very fragile, use caution when pulling it up.
5) Drop the thermocouple or thermopile down through the extrusion and pull it out of the unit.
GLASS REPLACEMENT
In the event that you break your glass by impact, purchase your replacement from an authorized Regency dealer only. Replacement glass is shipped already installed into the door frame. Reinstall as per Glass Door Installation on page
22.
REPLACEMENT PARTS:
Front Door - Tempered (Part# 360-528) Side Door - Tempered (Part# 360-529) Front Door - Ceramic (Part# 360-538) Side Door - Ceramic (Part# 360-539)
GOLD-PLATED ACCESSORIES
The 24 carat gold-plated finish requires little maintenance, and need only be cleaned with a damp cloth. DO NOT use abrasive materials or chemical cleaners, as they may harm the finish and void the warranty. Clean any finger-
prints off before turning the unit on.
6) Remove the burner by removing the 4 screws.
7) Slide the burner assembly away from the orifice and lift out.
6) Reinstall the new ones in reverse order.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 31
MAINTENANCE
8) Remove the Side Base Brick Panels and finally the Long Base Brick Panels.
Remove Left & Right Side Base
Brick Panels
Remove the 2 Long Base Brick Panels
9) Disconnect the inlet gas line.
10) Disconnect the 2 TP wires and the 2 TH wires from the valve.
11) Remove the 16 Phillips head screws secur­ing the valve tray.
13) Undo the pilot tube from the valve with a 7/16" spanner.
14) Undo the quick drop out thermocouple nut on the valve with a 9mm (metric) spanner.
15) Remove the Piezo igniter wire and push button assembly.
16) Undo the "gas out" flare nut with a 13/16" spanner.
Undo the "gas out" flare fitting with an
17) 11/16" spanner.
18) Remove the 6 Phillips head screws from the sides of the valve bracket and remove valve.
Hint: If you are using black pipe, ensure
that there is a union by the valve, otherwise removal will be almost impossible.
INSTALLING VALVE
1) Attach the valve to the valve bracket with the 6 (m5x8 metric) screws provided.
2) Reconnect the "gas out" flare fitting with an 11/16" spanner.
3) Reconnect the "gas out" flare nut with a 13/ 16" spanner.
4) Install piezo ignitor push button assembly and reconnect wire.
5) Reconnect the quick drop out thermocouple nut with a 9mm spanner.
6) Reconnect the pilot tube nut with a 7/16" spanner.
7) Scrape off the old gasket from the floor of the firebox and from the valve tray assem­bly.
8) Install a new gasket and reinstall the valve tray assembly.
Note: Failure to install a new gasket may severely affect the appliance perform­ance.
9) Reinstall the 16 hold down screws.
10) Hook up the 2 TP and 2 TH wires to the
appropriate connections on the valve.
11) Reinstall the Burner Assembly.
13) Hook up the gas line and check for gas leaks
with a soap and water solution or a gas leak detector. (Do not use open flame for leak testing.)
12) Lift the entire assembly out.
32
14) Fire up the unit temporarily
15) Check the manifold pressure.
16) Reinstall the logs, grate and brick panels as
needed.
17) Reinstall the glass doors.
18) Fire up the unit again and check for proper
flame appearance.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
PARTS LIST
P121 (SEE THRU) MAIN ASSEMBLY
Part # Description Part # Description Part # Description
1) 360-528 Door Assy Front - Tempered 360-538 Door Assy Front - Ceramic
(Optional)
2) 360-529 Door Assy Side - Tempered 360-539 Door Assy Side - Ceramic
(Optional)
135) 360-069 Heat Shield - Side
146) 360-035 Finishing Trim
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
168) 360-068 Door Cover Assembly - Side
181) * Extension Trim - See Thru
204) 360-940 Dec. Grill Front - Black (set)
205) 948-216 Regency Logo Plate
206) 910-172 Fan Axial 240V
207) 910-142 Thermodisc
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
17) 360-086 Gasket - Relief Door
24) * Relief Door Assembly
32) 902-296 Brick Panel - Base - Front
33) 902-297 Brick Panel - Base - Side
34) 902-298 Brick Panel - Side
171) 360-920 Louver Front - Black (set) 360-922 Louver Front - Black/Gold (set) 360-924 Louver Front - Black/Steel (set) 360-926 Louver Front - Black/Brass (set)
918-179 Manual
*Not available as a replacement part.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 33
PARTS LIST
P131 (PIER) MAIN ASSEMBLY
Part # Description Part # Description Part # Description
1) 360-528 Door Assy Front - Tempered 360-946 Door Assy Front - Ceramic
(Optional)
2) 360-529 Door Assy Side - Tempered 360-948 Door Assy Side- Ceramic
(Optional)
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
17) 360-086 Gasket - Relief Door
24) * Relief Door Assembly
32) 902-296 Brick Panel - Base - Side
33) 902-297 Brick Panel - Base - Front
34) 902-298 Brick Panel - Side
141) 360-031 Column Finishing Trim
146) 360-035 Finishing Trim
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
171) 360-920 Louver Front - Black (set) 360-922 Louver Front - Black/Gold (set) 360-924 Louver Front - Black/Steel (set) 360-926 Louver Front - Black/Brass (set)
173) 360-932 Louver Side - Black (set) 360-934 Louver Side - Black/Gold (set) 360-936 Louver Side - Black/Steel (set) 360-938 Louver Side - Black/Brass (set)
181) * Extension Trim - Pier
204) 360-940 Dec. Grill Front - Black (set)
206) 910-172 Fan Axial 240V
224) 360-942 Dec. Grill Side - Black (set)
225) 948-216 Regency Logo Plate
226) 910-142 Thermodisc
918-179 Manual
*Not available as a replacement part.
34
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
PARTS LIST
P121RC (RIGHT CORNER) MAIN ASSEMBLY
Part # Description Part # Description Part # Description
1) 360-528 Door Assy Front - Tempered 360-538 Door Assy Front - Ceramic
(Optional)
2) 360-529 Door Assy Side - Tempered 360-539 Door Assy Side - Ceramic
(Optional)
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top 780-013 Standoff - Rear
17) 360-086 Gasket - Relief Door
24) * Relief Door Assembly
32) 902-296 Brick Panel - Base - Side
33) 902-297 Brick Panel - Base - Front
34) 902-298 Brick Panel - Side
35) 902-300 Brick Panel - Front
138) 360-063 Heat Shield - Front
141) 360-031 Column Finishing Trim
146) 360-035 Finishing Trim - Left Side
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
158) 360-060 Door Cover Assembly-Front
171) 360-920 Louver Front - Black (set) 360-922 Louver Front - Black/Gold (set) 360-924 Louver Front - Black/Steel (set) 360-926 Louver Front - Black/Brass (set)
173) 360-932 Louver Side - Black (set) 360-934 Louver Side - Black/Gold (set) 360-936 Louver Side - Black/Steel (set) 360-938 Louver Side - Black/Brass (set)
181) * Extension Trim
204) 360-940 Dec. Grill Front - Black (set)
206) 910-172 Fan Axial 240V
224) 360-942 Dec. Grill Side - Black (set)
225) 948-216 Regency Logo Plate
226) 910-142 Thermodisc
918-179 Manual
*Not available as a replacement part.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 35
PARTS LIST
P121LC (LEFT CORNER) MAIN ASSEMBLY
Part # Description Part # Description Part # Description
1) 360-528 Door Assy Front - Tempered 360-538 Door Assy Front - Ceramic
(Optional)
2) 360-529 Door Assy Side - Tempered 360-539 Door Assy Side - Ceramic
(Optional)
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
17) 360-086 Gasket - Relief Door
24) * Relief Door Assembly
32) 902-296 Brick Panel - Base - Side
33) 902-297 Brick Panel - Base - Front
34) 902-298 Brick Panel - Side
35) 902-300 Brick Panel - Front
138) 360-069 Heat Shield - Front
141) 360-031 Column Finishing Trim
146) 360-035 Finishing Trim
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
158) 360-062 Door Cover Assembly-Front
171) 360-920 Louver Front - Black (set) 360-922 Louver Front - Black/Gold (set) 360-924 Louver Front - Black/Steel (set) 360-926 Louver Front - Black/Brass (set)
173) 360-932 Louver Side - Black (set) 360-934 Louver Side - Black/Gold (set) 360-936 Louver Side - Black/Steel (set) 360-938 Louver Side - Black/Brass (set)
204) 360-940 Dec. Grill Front - Black (set)
206) 910-172 Fan Axial 240V
224) 360-942 Dec. Grill Side - Black (set)
225) 948-216 Regency Logo Plate
226) 910-142 Thermodisc
918-179 Manual
*Not available as a replacement part.
36
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
P121/P121LC/P121RC/P131 BURNER ASSEMBLY & LOG SET
Part # Description
360-930 Log Set
41) 904-326 Front Right Log
42) 904-327 Front Left Log
43) 904-328 Middle Left Log
44) 904-329 Middle Right Log
360-574/P Valve Assembly
56) 360-378/P Valve S.I.T. - NG
57) 360-090 Gasket - Valve Tray
58) * Valve Tray
66) 910-038 Pilot Assembly - NG
67) * Pilot Holder
68) W840470 Pilot Assembly Gasket
69) 910-190 Piezo Ignitor and Nut
79) 360-525 Burner Assembly
82) 360-027 Grate Assembly 904-690 Orifice #31 - NG 936-170 Orifice Gasket
PARTS LIST
83) 910-073 Spark Generator Battery Holder
84) 910-074 Spark Generator Switch c/w Wire
90) 910-386 Thermocouple
91) 910-341 Thermopile
*Not available as a replacement part.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 37
NOTES
_____________________________________________________________________________________
____________________________________________________________
__________________________________________________________
____________________________________________________________
_______________________________________________________
_____________________________________________________
__________________________________________________________
_________________________________________________________
_________________________________________________________
______________________________________________________
______________________________________________________
_______________________________________________________________
___________________________________________________________
__________________________________________________________
____________________________________________________________
____________________________________________________________
____________________________________________________________
_____________________________________________________________
__________________________________________________________
__________________________________________________________
_____________________________________________________
________________________________________________________
_________________________________________________________
_________________________________________________________
38
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
WARRANTY
Regency Fireplace Products are designed with relia­bility and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our door. Regency Indus­tries Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a Regency Prod­uct.
The Warranty: Lifetime
Covered under the agreement are the following components: Combustion chamber, heat exchanger, burner tubes, logs, embers, glass (thermal breakage) and all gold plating (against defective manufacture). The above will be covered for parts and labour for the first five years and parts only thereafter. Electrical components such as fans, switches, wiring, thermodiscs, remote control, thermopiles, thermocouples and gas valves are covered for one year from the date of purchase.
Conditions:
All installations must be performed by an authorised gas fitter and installed according to all applicable local and national codes. Also, all service work must be carried out by an authorised gas service person. It is the responsibility of the installer to ensure that the appliance is firing as per rating plate. Any part or parts of this unit which in our judgement show evidence of such defect will be repaired or replaced at Regency's option, through an accredited distributor or agent provided that the defective part be returned to the distributor or agent Transportation Prepaid, if requested. In areas where there is not an approved service agent or the closest approved service agent is situated more than twenty-five (25) kilometres from the installation, Australian Heating Distrib­utors are not obliged to arrange warranty repairs and travel and/or additional labour charges will apply.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim. It does not cover installation and operational related problems such as over­firing, downdrafts or spillage caused by environmental con­ditions, nearby trees, buildings, hilltops, mountains, inade­quate flueing or ventilation, excessive offsets, negative air pressures caused by insufficient make up air, mechanical systems such as furnaces, fans, clothes dryers etc. The warranty does not extend to any part or parts which show evidence of misuse or abuse, neglect, accident or lack of maintenance. Products made by other manufacturers and used in con­junction with the operation of this appliance without author­ization from Regency, may nullify your warranty on this product. Regency Industries Ltd., shall in no event be liable for any special, indirect consequential damages of any nature whatsoever which are in excess of the original purchase price of the product. Any alteration to the unit which causes sooting or carbonning that results in damage to the exterior facia is not the responsibility of Regency Industries Ltd.
General:
It is essential that all submitted claims provide all of the necessary information including purchase date, serial #, type of unit and part or parts requested.
DISTRIBUTORS: Western Australia Eastern Australia
SERVICE AGENTS:
NOTE: PLEASE RETAIN YOUR INVOICE AS PROOF OF PURCHASE FOR WARRANTY VERIFICATION
INCORRECT INSTALLATION OR GAS PRESSURE SETTINGS ARE NOT COVERED BY WARRANTY
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 39
AUSTRALIAN HEATING DISTRIBUTORS FIREPLACE PRODUCTS AUSTRALIA PTY. LTD. 31 CLUNE STREET 21-23 SOUTH LINK BLVD. BAYSWATER, WA 6053 DANDENONG, VIC 3175
HEARTH HOUSE SERVICE 31 CLUNE STREET BAYSWATER, WA 6053
A SERVICE OR CALLOUT FEE WILL BE CHARGED IN THESE CIRCUMSTANCES.
© Copyright 2006, FPI Fireplace Products International Ltd. All rights reserved.
Printed in Canada