Regency P121-NG2, P121, P121LC, P121RC, P131 Owners & Installation Manual

...
Page 1
P121 / P121LC / P121RC / P131
Zero Clearance Direct Vent Gas Fireplace
Owners &
Installation Manual
STYLE MODEL See Thru P121-NG2 Natural Gas P121-LP2 Propane Left Corner P121LC-NG2 Natural Gas P121LC-LP2 Propane Right Corner P121RC-NG2 Natural Gas P121RC-LP2 Propane Pier P131-NG2 Natural Gas P131-LP2 Propane
WARNING: If the information in these instructions are not followed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other fl ammable vapours and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
Tested by:
Installer: Please complete the details on the back cover
and leave this manual with the homeowner.
Homeowner: Please keep these instructions for future reference.
918-519b
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4
www.regency-fi re.com
FOR YOUR SAFETY What to do if you smell gas: Do not try to light any appliance Do not touch any electrical switch: do not use any
phone in your building.
Immediately call your gas supplier from a neighbour's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fi re
06/15/10
Page 2
To the New Owner:
Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The P121 / P121LC / P121RC / P131 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model P121 / P121LC / P121RC / P131 has been approved by Intertek for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency® Fireplace.
IMPORT ANT: If the unit is to be installed into a bathroom, optional Neo ceramic glass Part# 360-946 Front or Part# 360-948 Side must be purchased and installed in place of the tempered glass supplied with the unit.
2
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 3
MANUFACTURED MOBILE HOME REQUIREMENTS
INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Intertek as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88a-2007/CSA 2.33a-2007 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN/ CGA 2.17-M91.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This Regency® mobile/manufactured home listed appliance comes factory equipped with four 1/4" diameter holes located near each corner of the base. Fasten the fi replace in place using screw, inserted through the holes.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes. See the "Wiring Diagram" section.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes.
This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other cases, unless a certifi ed kit is used.
Ensure that structural members are not cut or weakened during installation.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
3
Page 4
TABLE OF CONTENTS
SAFETY LABEL
Copy of the Safety Label ...............................................5
DIMENSION
Unit Dimensions ............................................................7
INSTALLATION
General Safety.............................................................10
Information...................................................................10
Installation Checklist ....................................................10
Locating Your Gas Fireplace .......................................11
Clearances ..................................................................12
Combustible Mantels ..................................................12
Framing And Finishing .................................................13
Unit Assembly Prior To Installation ..............................14
Venting Introduction .....................................................14
Exterior Vent Termination Locations ............................15
4” x 6-5/8” Rigid Pipe Cross Reference Chart .............16
Venting Arrangement - Horizontal Terminations ..........18
Rigid Pipe Venting Systems ........................................19
Horizontal or Vertical Terminations ..............................19
Rigid Pipe Venting Arrangements ................................20
Horizontal Terminations .......................................20
Horizontal terminations ................................................24
Vertical Terminations ...................................................25
Installation Procedures ................................................26
Conversion From NG To LP ........................................27
High Elevation .............................................................30
Gas Line Installation ....................................................30
Pilot Adjustment ...........................................................30
Gas Pipe Pressure Testing ..........................................30
Log Set Installation ......................................................31
Glass Door Removal ...................................................33
Finishing Trim ..............................................................33
Louvers & Grills ...........................................................33
Option 1: Remote Control ............................................34
Option 2: Wall Switch ..................................................34
Option 3: Wall Thermostat ..........................................34
Wiring Diagrams ..........................................................35
OPERATING INSTRUCTIONS
Operating Instructions .................................................37
Lighting Procedure ......................................................37
Shutdown Procedure ...................................................37
First Fire ......................................................................37
Aeration Adjustment ....................................................37
Copy of The Lighting Plate Instructions .......................38
Normal Operating Sounds Of Gas Appliances ............38
Maintenance Instructions.............................................39
Log Replacement ........................................................39
Thermopile / Thermocouple .........................................39
Door Glass...................................................................39
Gold-plated Accessories ..............................................39
MAINTENANCE
Removing Valve ...........................................................40
Installing Valve .............................................................41
Fan Replacement ........................................................41
PARTS LIST
P121-2 (See Thru) Main Assembly ..............................42
P131-2 (Pier) Main Assembly ......................................43
P121rc-2 (Right Corner) Main Assembly .....................44
P121lc-2 (Left Corner) Main Assembly ........................45
P121/p121lc/p121rc/p131-2 Burner Assembly & Log Set 46
WARRANTY
Warranty ......................................................................47
4
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 5
This is a copy of the label that accompanies
APPAREIL FONCTIONNANT AU GAZ PROPANE
CONCU POUR ETRE POELE:
Pression d'allimentation minimum
Pression à la tubulure d' chappement lev e
Pression à la tubulure d' chappement basse
Grandeur de l'injecteur
D bit minimum selon
D bit maximum selon
Calorifique
Calorifique
l'altitude
ééé
é
é
é
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
304
NATURAL GAS:
Minimum supply pressure
Manifold pressure high
Manifold pressure low
Orifice size
Minimum input
Maximum input
Altitude
L
PROPANE:
DOOR SEAL:Please check that the door is properly sealed
Minimum Clearances to Combustibles / Degagement Minimum De Materiaux Combustibles
Top, bottom, sides & rear of unit
Min. 39" (991mm)
" (0mm)
0" Clearance to combustibles from:
Mantel Height from Base of Unit:
Side Wall Clearance from Side Facing 0
Horizontal Top 2-1/2" (64mm)
Horizontal Side 1-1/2" (38mm)
Horizontal Bottom 1-1/2" (38mm)
Minimum Vent Clearances:
Serial No./ No de serie
918-497a
5" WC (1.25 kPa)
3.8" WC (0.95 kPa)
1.1" WC (0.27 kPa)
# 31 DMS
20,500 Btu/h (6.01 kW)
0-4500 ft/pi (0-1372 m)
40,000 Btu/h (11.72 kW)
12" WC (3.00 kPa)
11" WC (2.74 kPa)
2.9" WC (0.72 kPa)
# 50 DMS
20,600 Btu/h (6.04 kW)
39,000 Btu/h (11.43 kW)
0-4500 ft/pi (0-1372 m)
APPAREIL FONCTIONNANT AU NATURAL GAZ
CONCU POUR ETRE POELE:
Pression d'allimentation minimum
Pression à la tubulure d' chappement lev e
Pression à la tubulure d' chappement basse
Grandeur de l'injecteur
D bit minimum selon
D bit maximum selon
l'altitude
Calorifique
Calorifique
ééé
é
é
é
Listed:
Certified for/Certifi e pour:
Tested to:
VENTED GAS FIREPLACE HEATER/
CANADA and U.S.A.
Gas-Fired Appliances For Use At High Altitudes
FOYER AU GAZ À ÉVACUATION
é
WN# 16474
CAN/CGA-2.17-M91,
Vented Gas Fireplace Heaters ANSI Z21.88a-2007/CSA 2.33a-2007
Made in Canada/ Fabrique au Canada
Duplicate S/N
(See Instruction Manual for Detailed Instructions)
P121LC-NG2 P121LC-LP2P121RC-NG2 P121RC-LP2P121-NG2
P121-LP2
Model:
Modele:
P131-NG2
P131-LP2
304
Model/Modele: P121-LP2, P131-LP2,
P121LC-LP2, P121RC-LP2
Model/Modele: P121-NG2, P131-NG2,
P121LC-NG2, P121RC-NG2
Minimum supply pressure
Manifold pressure high
Manifold pressure low
Orifice size
Minimum input
Maximum input
Altitude
This appliance must be installed in accordance with local codes, if any; if
none, follow the National Fuel Gas Code, ANSI Z223.1, or Natural Gas
and Propane Installation Code, CSA B149.1.
This appliance mustbeinstalled in accordance withtheStandard CAN/CSA
Z240 MH, Mobile Housing, in Canada, or with the Manufactured Home
Construction and Safety Standard, Title 24 CFR, Part 3280, in the United
States, or when such a standard is not applicable, ANSI/NCSBCS
A225.1/NFPA 501A, Manufactured Home Installations Standard or ANSI
A119.2ou NFPA501C Standardfor RecreationalVehicles
This applianceis only foruse with thetype ofgasindicated on therating plate
and may be installed inan aftermarket, permanently located, manufactured
(mobile) home wherenotprohibitedbylocal codes. See owner's manualfor
details.
Installer l'appareilselon les codesou règlements locaux,ou, en l'absencede
tels règlements, selon les codes d'installation ANSI Z223.1, National Fuel
Gas Codeou CSA-B149.1en vigueur.
Installer l'appareil selon la norme CAN/CSA-Z240, Série MM, Maison
mobiles ouCAN/CSA-Z240 VC, Véhiculesdecamping, ou lanorme24 CFR
Part 3280, Manufactured Home Construction and Safety Standard. Si ces
normes ne sont pas pertinentes, utilisez la norme ANSI/NCSBCS
A225.1/NFPA 501A, Manufactured Home Installations Standard, ou ANSI
A119.2ou NFPA501C Standardfor RecreationalVehicles.
For usewith glassdoors certified withthe applianceonly.
This ventedgas fireplaceheater is notfor usewith air filters.
Ne pasutiliser defiltre à airavec cefoyer au gazà évacuation.
Cet appareil doit être utilize uniquement avec le type de gaz indiqué sur la
plaque signalétique. Cet appareil peut être installé dans une maison
préfabriquée ou mobile (É.-U. seulement) installée à demeure si les
règlements locaux le permettent. Voir la notice de l'utilisateur pour plus de
renseignements. Cetappareilne peut pas êtreutilisé avec d'autres gazsauf
si unetrousse deconversion certifiée estfournie.
Pour utilisation uniquement avec les portes en verre certifiées avec
l'appareil.
Electrical supply/ Électrique115VAC,1.13A, 60Hz.
VENTED GAS FIREPLACE HEATER - NOT FOR USE WITH SOLID FUELS. /
NE PAS UTILISER AVEC DU COMBUSTIBLE SOLIDE.
FOYER
AU GAZ À ÉVACUATION -
each P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open.
®
NOTE: Regency
units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
SAFETY LABEL
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible connectors shall not exceed 36 inches in length.
Copy of Safety Decal for P121/P121LC/P121RC/P131
For the State of Massachusetts, the appli­ances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
5
Page 6
REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
MA Code - CO Detector
(for the State of Massachusetts only)
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
6
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 7
SPECIFICATIONS
P121-2 See Thru
DIMENSIONS
Note: These units are
non-load bearing.
P131-2 Pier
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
7
Page 8
DIMENSIONS
P121LC-2 Left Corner Unit
Note: These units are
non-load bearing.
P121RC-2 Right Corner Unit
8
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 9
INSTALLATION
IMPORTANT MESSAGE
SAVE THESE
INSTRUCTIONS
The Panorama P121/P121LC/P121RC/P131­NG1 or P121/P121LC/P121RC/P131-LP1 Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturer's instructions and all applicable codes.
BEFORE YOU ST ART
Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE­CIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE CARE­FULLY SUPERVISED WHEN THEY ARE IN THE SAME AREA AS THE APPLI­ANCE. TODDLERS, YOUNG CHILDREN AND OTHERS MAY BE SUSCEPTIBLE TO ACCIDENTAL CONTACT BURNS. A PHYSICAL BARRIERS IS RECOMMEND­ED IF THERE ARE AT RISK INDIVIDUAL IN THE HOUSE. TO RESTRICT ACCESS TO A FIREPLACE OR STOVE, INSTALL AN ADJUSTABLE SAFETY GATE TO KEEP TODDLERS, YOUNG CHILDREN AND OTHER AT RISK INDIVIDUALS OUT OF THE ROOM AND AWAY FROM HOT SURFACES.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
9
Page 10
INSTALLATION
GENERAL SAFETY
INFORMATION
1) The appliance installation must conform with
local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 or ANSI Z223.1 Installation Codes.
2) See general construction and assembly
instructions. The appliance and vent should be enclosed.
3) This appliance must be connected to the
specifi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.
4) Inspect the venting system annually for blockage
and any signs of deterioration.
5) Venting terminals shall not be recessed into a
wall or siding.
6) Any safety glass removed for servicing must
be replaced prior to operating the appliance.
7) To prevent injury, do not allow anyone who is
unfamiliar with the operation to use the fi replace.
8) Wear gloves and safety glasses for protection
while doing required maintenance.
9) Be aware of electrical wiring locations in walls
and ceilings when cutting holes for termination.
10) Under no circumstances should this appliance
be modifi ed. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
11) Installation and any repairs to this appliance
should be done by a qualifi ed service person. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
12) Do not slam shut or strike the glass door.
13) Under no circumstances should any solid fuels
(wood, paper, cardboard, coal, etc.) be used in this appliance.
14) The appliance area must be kept clear and
free of combustible materials, (gases and other ammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INSTALLATION
CHECKLIST
Note: These units are
non-load bearing.
1) Locate appliance. Refer to the following sections:
a) Locating Your Fireplace b) Clearances c) Combustible Mantel Clearances d) Framing & Finishing e) Venting. See the "Venting Introduction"
to "Venting Arrangements" sections.
2) Assemble Top Standoffs. Refer to the "Unit
Assembly Prior to Installation" section. (NOTE: must be done before installing unit into fi replace.)
3) Install vent. See the "Horizontal
Installations" to "Installation Procedures" sections
4) Make gas connections. Test the pilot. Must be as per diagram. Refer to the "Gas Line Installation" & "Pilot Adjustment" sections.
5) Install standard and optional features. Refer to the following sections where applicable:
a. Log Set b. Glass Door c. Finishing Trim d. Louvers & Grills e. Remote Control f. Wall Switch g. Wall Thermostat
6) Final check.
Before leaving this unit with the customer, the installer must ensure that the appliance is ring correctly and operation fully explained to customer.
This includes:
1) Clocking the appliance to ensure the correct ring rate (rate noted on label 40,000 Btu/h NG, and 39,000 Btu/h LP) after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.
10
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 11
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your fi replace, ensure that the clearances are met as outlined in the "Clearances" section.
2) Provide adequate clearances for servicing.
3) The appliance must be installed on a fl at, solid, continuous surface (e.g. wood, metal, concrete). This may be the fl oor, or raised up on a platform to enhance its visual impact. If the appliance is going to be installed on carpeting, combustible linoleum tile or other combustible material other than wood fl ooring, the appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
4) The Direct Vent Gas Fireplace can be installed as follows:
Model # Position A) P121-2: See Thru B) P131-2: Pier C) P121LC-2: Left Corner D) P121RC-2: Right Corner
INSTALLATION
A) P121-2 See Thru
B) P131-2 Pier
5) This appliance is Listed for bedroom installations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
6) The P121-2/P121LC-2/P121RC-2/P131-2 Direct Vent Gas Fireplace is approved for alcove installations, which meet the clearances listed on this page.
7) We recommend that you plan your installation on paper using exact measurements for clearances and fl oor protection before actually installing this appliance. Have a qualifi ed inspector, dealer , or installer review your plans before installation.
Note: For Exterior Vent Termination Locations see section "Exterior Vent
Termination Locations."
C) P121LC-2 Left Corner
D) P121RC-2 Right Corner
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
11
Page 12
INSTALLATION
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams in the "Locating Your Fireplace" section):
Clearance to Combustibles from: Back 0" (0mm) Side 0" (0mm) Floor 0" (0mm)
CAUTION REQUIREMENTS: The top, back and sides of the fi replace are defi ned by standoffs. The metal ends of the standoffs may NOT be recessed into combustible construction.
Determine the total thickness of the fi nished fl oor (eg. tile, carpet, slate) to allow the fi nished surface to be fl ush with the base of the unit.
Ceiling Height from Floor 72" (1828mm)
Mantel Height from Base of Unit:
39" min. (991mm)
Horizontal Vent Clearances:
Top 2-1/2" (64mm) Side 1-1/2" (38mm) Bottom 1-1/2" (38mm)
Vertical Vent Clearances 1-1/4" (32mm)
COMBUSTIBLE MANTELS
Mantel Clearances
Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible
mantel clearances from top of unit are shown in Diagram to the right.
Note: A non-combustible mantel may be
installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
WARNING:
Fire hazard is an extreme risk
if these clearances (air space)
to combustible materials are
not adhered to. It is of greatest
importance that this fi replace
and vent system be installed
only in accordance with these
instructions.
This drawing is to scale at 1:6 (one inch = 6 inches) Mantel can be installed anywhere in shaded area or higher using this scale.
Caution: Ensure the paint that is used on the
mantel and the facing is "heat resistant" or the paint may discolour.
* If the 3" (76mm) metal extension trim is removed it must be replaced with a 8" (203mm) non­combustible material.
12
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 13
FRAMING AND FINISHING
INSTALLATION
1) For ease of installation, frame your fi replace after it is positioned and the vent system is installed. Remember to install the top standoffs. See the "Unit Assembly Prior to Installation" section. Use 2x4's and frame to local building codes.
CAUTION: Verify your replace dimensions, framing methods and nished wall facing details before framing. Determine the total
thickness of facing material - drywall plus ceramic tiles, slate, etc. Allow the fi nish surface to be fl ush with the front or side of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.
2) When locating your appliance on an exterior wall or in a chase, apply a vapour barrier and drywall, as per local building codes. DO NOT
INSULATE THE FIREPLACE ITSELF.
CAUTION: The unit does not have to be completely enclosed in a chase. The clearance on top of the unit is 0" to the standoffs so combustible building materials can be laid directly on top of the standoffs. You must maintain clearance from the vent to combustible materials for both rigid and fl ex, see Vent Clearances in the "Clearances" section.
P121-2 - See Thru
Framing Dimensions
P121-2 (See Thru) P131-2 (Pier) P121LC-2 / P121RC-2 (Corner Unit)
A 25"(635mm) 25"(635mm) 26-13/16"
minus two times minus two times minus one time the fi nishing the fi nishing the fi nishing material thickness* material thickness* material thickness*
B 42-1/2"(1080mm) 42-1/2"(1080mm) 42-1/2"(1080mm)
C 46-3/4"(1187mm) 45" (1143mm) 45"(1143mm)
minus one time minus one time the fi nishing the fi nishing
* Finish material thickness includes: drywall, ceramic tile, slate, etc.
P121LC-2 - Corner Unit
P131-2 - Pier
C
A
B
Note: These units are
non-load bearing.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
P121RC-2 - Corner Unit
13
Page 14
INSTALLATION
Facing & Finishing Requirements
This fi replace is supplied with a 3" metal extension trim above the fi replace. The extension trim may be replaced if the framing is faced with a non- combustible material placed fl ush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position.
Top Standoff Assembly
The top standoffs are shipped in a fl at position and must be folded into shape and attached.
1) Remove the standoffs from the fi replace top.
2) Take each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the pre­punched screw holes on the fi replace top line up.
3) Attach the standoff securely to the top with 4 screws per standoff (on opposite corners).
VENTING
INTRODUCTION
The P121-2/P121LC-2/P121RC-2/P131-2 uses the "balanced fl ue" technology Co -Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be
connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited. (See "Rigid Pipe Venting Systems" for more details and exceptions).
14
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 15
EXTERIOR VENT TERMINATION LOCATIONS
INSTALLATION
1
Minimum Clearance Requirements
A Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm)
B Clearance to window or door that may be opened 12"(30cm) 9" (23cm)
C Clearance to permanently closed window **
D Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm) 18"(46cm) 18"(46cm)
E Clearance to unventilated soffi t 20"(51cm) 20"(51cm)
F Clearance to outside corner: with AstroCap Termination Cap. 6"(15cm) 6"(15cm)
Clearance to outside corner: with all other approved Termination Caps. 14"(36cm) 14"(36cm)
G Clearance to inside corner: with AstroCap Termination Cap 6"(15cm) 6"(12cm)
Clearance to inside corner: with all other approved Termination Caps. 12"(30cm) 12"(30cm)
H Clearance to each side of center line extended above meter/regulator assembly 36"(90cm)
J Clearance to service regulator vent outlet 36"(90cm) *
K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance 12"(30cm) 9" (23cm)
L Clearance to a mechanical air supply inlet 72"(1.8m) 36"(90cm)
M Clearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)
N Clearance under veranda, porch, deck, or balcony 12"(30cm)
1
In accordance with current CSA B149.1, Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
Clearance in accordance with local installation codes and the requirements of the gas supplier
*
a
3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly
b
3 feet (91cm) above - if within 10 feet (3m) horizontally
Canada
a
USA
*
*
*
2
b
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
15
Page 16
INSTALLATION
4” X 6-5/8” RIGID PIPE CROSS REFERENCE CHART
Components from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Description
6” Pipe Length-Galvanized 46DVA-06 4DT-6 N/A 4D6 SV4L6 TC-4DL6
6” Pipe Length-Black 46DVA-06B 4DT-6B N/A 4D6B SV4LB6 TC-4DL6B
7” Pipe Length-Galvanized N/A N/A 4D7 N/A N/A N/A
7” Pipe Length-Black N/A N/A 4D7B N/A N/A N/A
9” Pipe Length-Galvanized 46DVA-09 4DT-9 N/A N/A N/A N/A
9” Pipe Length-Black 46DVA-09B 4DT-9B N/A N/A N/A N/A
12” Pipe Length-Galvanized 46DVA-12 4DT-12 4D12 4D12 SV4L12 TC-4DL1
12” Pipe Length-Black 46DVA-12B 4DT-12B 4D12B 4D12B SV4LB12 TC-4DL1B
18” Pipe Length-Galvanized 46DVA-18 4DT-18 4D18 4D18 SV4LA TC-4DL18
18” Pipe Length-Black 46DVA-18B 4DT-18B 4D18B 4D18B SV4LA TC-4DL18B
24” Pipe Length-Galvanized 46DVA-24 4DT-24 4D24 4D24 SV4L24 TC-4DL2
24” Pipe Length-Black 46DVA-24B 4DT-24B 4D24B 4D24B SV4LB24 TC-4DL2B
36” Pipe Length-Galvanized 46DVA-36 4DT-36 4D36 4D36 SV4L36 TC-4DL3
36” Pipe Length-Black 46DVA-36B 4DT-36B 4D36B 4D36B SV4LB36 TC-4DL3B
48” Pipe Length-Galvanized 46DVA-48 4DT-48 4D48 4D48 SV4L48 TC-4DL4
48” Pipe Length-Black 46DVA-48B 4DT-48B 4D48B 4D48B SV4LB48 TC-4DL4B
60” Pipe Length-Galvanized 46DVA-60 4DT-60 N/A N/A N/A N/A
60” Pipe Length-Black 46DVA-60B 4DT-60B N/A N/A N/A N/A
Adjustable Length 3”-10”-Galvanized N/A N/A N/A 4DAL N/A TC-4DLT
Adjustable Length 3”-10”-Black N/A N/A N/A 4DALB N/A TC-4DLTB
Adjustable Length 7”-Galvanized N/A N/A 4D7A N/A N/A N/A
Adjustable Length 7”-Black N/A N/A 4D7AB N/A N/A N/A
Extension Pipe 8-1/2”-Galvanized 46DVA-08A N/A N/A N/A N/A N/A
Extension Pipe 8-1/2”-Black 46DVA-08AB N/A N/A N/A N/A N/A
Adjustable Length 12”-Galvanized N/A N/A 4D12A N/A SV4LA12 N/A
Adjustable Length 12”-Black N/A N/A 4D12A N/A SV4LBA12 N/A
Extension Pipe 16”-Galvanized 46DVA-16A N/A N/A N/A N/A N/A
Extension Pipe 16”-Black 46DVA-16AB N/A N/A N/A N/A N/A
Simpson
Direct Vent Pro
®
Selkirk
Direct Temp™
American Metal
Products®
Amerivent Direct
Metal-Fab™
Sure Seal
Security
Secure- Vent®
ICC Excel
Direct
45º Elbow-Galvanized 46DVA-E45 4DT-EL45 4D45L N/A N/A TE-4DE45
45º Elbow-Black 46DVA-E45B 4DT-EL45B 4DT-EL45B N/A N/A TE-4DE45B
45º Elbow Swivel-Galvanized See 46DVA-E45 N/A N/A 4D45L SV4E45 N/A
45º Elbow Swivel-Black See 46DVA-E45B N/A N/A 4D45LB SV4EB45 N/A
90º Elbow-Galvanized 46DVA-E90 4DT-EL90S 4DT-EL90S N/A N/A TE-4DE90
90º Elbow-Black 46DVA-E90B 4DT-EL90SB 4DT-EL90SB N/A SV4EBR90-1 TE-4DE90B
90º Elbow, Swivel-Galvanized See 46DVA-E90 N/A N/A 4D90L SV4E90-1 N/A
90º Elbow, Swivel-Black See 46DVA-E90B N/A N/A 4D90LB SV4EB90-1 N/A
90º Starter Elbow, Swivel-Galvanized N/A N/A N/A 4D90A N/A N/A
Adaptor* N/A N/A N/A 4D90L N/A N/A
Ceiling Support N/A 4DT-CS 4DFSP 4DSP SV4SD TE-4DE45
Cathedral Support Box 46DVA-CS 4DT-CSS 4DRSB 4DRS SV4CSB TE-4DE45B
Wall Support/Band 46DVA-WS 4DT-WS/B 4DWS 4DWS SV4BM N/A
Offset Support
Wall Thimble-Black 46DVA-WT 4DT-WT 4DWT 4DWT SV4RSM TE-4DE90
Wall Thimble Support/Ceiling Support 46DVA-DC N/A N/A N/A SV4PF TE-4DE90B
Firestop Spacer 46DVA-FS 4DT-FS 4DFSP 4DFS SV4BF N/A
Trim Plate-Black N/A 4DT-TP 4DFPB 4DCP SV4LA N/A
46DVA-ES (N/A - FPI)
16
4DT-OS N/A N/A SV4SU N/A
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 17
INSTALLATION
Description
Attic Insulation Shield 12” 46DVA-IS N/A@ FPI N/A 4DAIS12 N/A SV4RSA N/A
Attic Insulation Shield -
Basic Horizontal Ter mination Kit (A) Disc. 4DT-HKA 4DHTK2 4DHTKA SV-SHK N/A
Horizontal Ter mination Kit (B) 46DVA-KHA
Vertical Termination Kit Disc. 4DT-VKC 4DHTK 4DHTK SV-FK N/A
High Wind Vertical Cap 46DVA-VCH N/A N/A N/A N/A TM-4VT
High Wind Horizontal Cap 46DVA-HC N/A N/A N/A N/A TM-4DHT
Horizontal Square Ter mination Cap See
Vertical Termination Cap N/A 4DT-HVC 4DVC 4DVT SV4CGV-1 TM-4VT
Storm Collar 46DVA-08A 4DT-SC 4DSC 4DSC SV4FC TM-SC
Adjustable Flashing 0/12-6/12 N/A 4DT-ST14 4D12S 4DST14 SV4STC14 TF-4FA
Adjustable Flashing 6/12-12/12 N/A 4DT-ST36 4D36S 4DST36 SV4STC36 TF-4FB
Vinyl Siding Standoff 46DVA-VSS 4DT-VS N/A 4DVS SV4VS TM-VSS
Vinyl Siding Shield Plate N/A 4DT-VSP N/A N/A SV4VS N/A
Snorkel Termination 14” 46DVA-VCH N/A N/A N/A N/A TM-4ST14
Snorkel Termination 36” 46DVA-HC N/A N/A N/A N/A TM-4ST36
Restrictor Disk 46DVA-RD N/A N/A N/A N/A TM-4DS
Extended Vertical Termination Cap 46DVA-VCE N/A N/A N/A N/A N/A
Chimney Conversion Kit A (USA only) 46DVA-KCA N/A N/A N/A N/A TM-4CA6
Chimney Conversion Kit B (USA only) 46DVA-KCB N/A N/A N/A N/A TM-4CA7
Chimney Conversion Kit C (USA only) 46DVA-KCC N/A N/A N/A N/A TM-4CA8
Chimney Conversion Kit Masonry (USA only)
Wall Firestop 46DVA-WFS N/A N/A N/A N/A TM-4TR
Colinear Flex Connectors 46DVA-ADF N/A N/A N/A N/A N/A
Cold Climates 36” N/A N/A 4DAIS12 N/A N/A TM-4AS
Simpson
Direct Vent Pro
(Changed Components)
46DVA-HC 4DT-HHC 4DHC 4DHT SV4CHC-1 TM-4HT
46DVA-KMC N/A N/A N/A N/A N/A
®
Selkirk
Direct Temp™
4DT-HKB 4DHTK1 4DHTKB SV-HK N/A
American Metal
Products®
Amerivent Direct
Metal-Fab™
Sure Seal
Security
Secure- Vent®
ICC Excel
Direct
FPI
946-506/P Vent Guard (Optional) for AstroCap 946-205 Vinyl Siding Shield for Riser Vent Terminal
510-994 Rigid Pipe Adaptor (Must use with all rigid piping) 946-208/P Vent Guard (Optional) for Riser Vent Terminal
640-530/P Riser Vent Terminal 946-523/P AstroCap Horizontal Cap
946-605 Starter Collar Increaser 4” x 6-5/8” to 5” x 8” 946-206 Vinyl Siding Standoff for AstroCap
Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length
(L)
0” (0mm) 4-7/8” (124mm) 13-7/8” (340mm) Simpson Direct Vent Pro: www.duravent.com
6” (152mm) 8” (203mm) 16-1/2” (419mm) Selkir k Direct-Temp: www.selkirkcorp.com
9” (229mm) 10-1/8” (257mm) 18-5/8” (473mm) American Metal Products: www.americanmetalproducts.com
12” (305mm) 12-1/4” (311mm) 20-3/4” (527mm) Metal-Fab Sure Seal: www.mtlfab.com
24” (610mm) 20-5/8” (524mm) 29-1/8” (740mm) Security Secure Vent: www.securitychimneys.com
36” (914mm) 29” (737mm) 37-1/2” (953mm) Industrial Chimney Company: www.icc-rsf.com
48” (1219mm) 37-7/16” (951mm) 45-15/16” (1167mm)
Note: Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination. Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.
4” x 6-5/8” Venting For specifi c instructions on venting components - visit the
Run (X) Rise (Y)
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
manufacturers website listed below.
17
Page 18
INSTALLATION
VENTING ARRANGEMENT - HORIZONTAL TERMINATIONS
Regency® Direct Vent System (Flex) Horizontal Terminations Only
These venting systems, in combination with the P121-2/P121LC-2/P121RC-2/P131-2 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in the "Exterior Vent Termination Locations" section.
Regency® Direct Vent (Flex) System Termination Kit (Part# 946-513) includes all the parts needed to install the P121-2/P121LC-2/P121RC­2/P131-2 with a maximum run of 2 feet. If installing the P121-2/P121LC-2/P121RC-2/P131-2 with a continous vent length of more than 2 ft. (.6m)
to a maximum of 10 ft. (3.0m) use Kit # 946-515 (4 ft.) or 946-516 (10 ft.)
1) 6-7/8" dia. exible liner (2 ft. length)
2) 4" dia. exible liner (2 ft. length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) screws #8 x 1-1/2" drill point, stainless steel (4)
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency
3) Regency
18
®
Direct Vent System (Flex) is only approved for horizontal terminations.
®
may be used for Flex installations.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 19
RIGID PIPE VENTING SYSTEMS
Horizontal or Vertical Terminations
The minimum components required for a basic horizontal termination are:
1 Simpson Duravent Adaptor 1 Horizontal Termination Cap 1 45o Elbow 1 Rigid Pipe Adaptor 1 Wall Thimble 1 Length of pipe to suit wall thickness (see chart)
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl furring strips may be used, instead of the vinyl siding standoff, to create a level surface to mount the vent terminal. The T erminal must not be recessed into siding. Measure the wall thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.
INSTALLATION
Flat Wall Installation
Wall Thickness Vent Length (inches) Required (inches)
4" - 5-1/2" 6" 7" - 8-1/2" 9" 10" - 11-1/2" 12" 9" - 14-1/2" 11" - 14-5/8" Adj. Pipe 15" - 23-1/2" 17" - 24" Adj. Pipe
WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCapTM and FPI Riser is acceptable with all systems.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Duravent Direct-Vent , Selkirk Direct-T emp, Ameri Vent Direct venting and Security Secure Vent systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of components.
When using Rigid Vent other than
Simpson Dura-Vent, 3 screws must be
used to secure rigid pipe to adaptor.
The FPI AstroCap can Metal Products Ameri Vent Direct Vent, Security Secure Vent®, Selkirk Direct-Temp. AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
TM
and FPI Riser Vent terminal are certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent, Ameri-
19
Page 20
INSTALLATION
RIGID PIPE VENTING ARRANGEMENTS
HORIZONTAL TERMINATIONS
REGENCY DIRECT VENT SYSTEM (FLEX) (Propane & Natural Gas)
The diagram below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o elbow).
Note:
1) A maximum of three 90o elbows are permitted.
2) Minimum distance between elbows is 1 ft. (305mm).
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part# 510-994) when using rigid pipe vent systems.
• A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.
Straight Out Horizontal Venting
Horizontal Venting with One (1) 90o Elbow
All Rigid Pipe Systems 4" inner diameter 6-5/8" outer diameter
Option V H A) 1' (305mm) Minimum 3' (914mm) Maximum B) 2' (610mm) Minimum 6' (1.86m) Maximum C) 3' (914mm) Minimum 9' (2.7m) Maximum D) 4' (1.22m) Minimum 12' (3.6m) Maximum E) 5' (1.5m) Minimum 15' (4.5m) Maximum F) 6' (1.86m) Minimum 17' (5.1m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 1
Please note the minimum centerline for basic install shown above.
Diagram 2
20
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 21
INSTALLATION
INSTALLATION
Horizontal Venting with Two (2) 90o Elbows
Option V H + H1
A) 1' (305mm) Minimum 2' (610mm) Maximum B) 2' (610mm) Minimum 5' (1.5m) Maximum C) 3' (914mm) Minimum 8' (2.4m) Maximum D) 4' (1.22m) Minimum 11' (3.35m) Maximum E) 5' (1.5m) Minimum 14' (4.27m) Maximum F) 6' (1.86m) Minimum 15' (4.5m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 15 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Option V H H + H1 + H2 A) 2' (610mm) Min. 1' (305mm) Max. 3'(914mm) Max. B) 3' (914mm) Min. 3' (914mm) Max. 6' (1.86m) Max. C) 4' (1.22mm) Min. 5' (1.5m) Max. 9' (2.7m) Max. D) 5' (1.5m) Min. 7' (2.13m) Max. 12' (3.6m) Max.
Horizontal Venting with Three (3) 90
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 5
o
Elbows
Diagram 3
Horizontal Venting with Two (2) 90o Elbows
Option V H H + H1
A) 1' (305mm) Min. 1' (305mm) Max. 3'(914mm) Max. B) 2' (610mm) Min. 3' (0.91m) Max. 6' (1.86m) Max. C) 3' (914mm) Min. 5' (1.5m) Max. 9' (2.7m) Max. D) 5' (1.5m) Min. 8' (2.4m) Max. 12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90
o
elbows is required.
Horizontal Venting with Three (3) 90o Elbows
Option V + V1 H + H1
A) 2' (610mm) Minimum 3' (914mm) Maximum B) 3' (914mm) Minimum 6' (1.86m) Maximum C) 4' (1.22m) Minimum 9' (2.7m) Maximum D) 5' (1.5m) Minimum 12' (3.6m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 4 Diagram 6
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
21
Page 22
INSTALLATION
Rigid Pipe
Adapter
1-1/2” (38mm)
45 Elbow
o
RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
(Propane & Natural Gas)
Vent must be supported at offsets
Maintain clearances to combustibles as listed in the "Clearances" section.
Firestops are required at each oor level and whenever passing through a wall.
Must use optional rigid pipe adaptor when using rigid pipe vent systems (Part# 510-994).
The P121-2/P121LC-2/P121RC-2/P131-2 is approved for a maximum 35 ft. (10.7m) straight vertical, with rigid pipe vent systems for Propane and Natural Gas, as per diagram 7 below.
Straight Up Vertical Venting
Minimum 6' 6”(2.0m)
Maximum 35'(10.7m)
45° Elbow
Rigid Pipe Adapter
Part # 510-994
Vertical Venting with One (1) 90o Elbow
Option V H
A) 1' (305mm) Minimum 2' (610mm) Maximum B) 2' (610mm) Minimum 4' (1.22m) Maximum C) 3' (914mm) Minimum 6' (1.86m) Maximum D) 4' (1.22m) Minimum 8' (2.4m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 7
22
Diagram 8
IMPORTANT
When installing this unit vertically, the 45o elbow when installed in conjunction with the Rigid Pipe Adaptor will pertrude past the unit 1-1/2" (38mm) when measured from the rear standoffs.
Note: A 1-1/4" (32mm) clearance from the elbow must also be maintained.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 23
INSTALLATION
Vertical Venting with Two (2) 90o Elbows
Option V + V1 H A) 1' (305mm) Minimum 4' (1.22m) Maximum B) 2' (610mm) Minimum 6' (1.86m) Maximum C) 3' (914mm) Minimum 9' (2.7m) Maximum D) 4' (1.22m) Minimum 12' (3.6m) Maximum E) 5' (1.5m) Minimum 15' (4.5m) Maximum F) 6' (1.86m) Minimum 17' (5.1m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 17 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Vertical Venting with Two (2) 90o Elbows
Option V H + H1 A) 1' (305mm) Minimum 2' (610mm) Maximum B) 2' (610mm) Minimum 4' (1.22m) Maximum C) 3' (914mm) Minimum 6' (1.86m) Maximum D) 4' (1.22m) Minimum 8' (2.4m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 4 feet total vertical and maximum 8 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
Diagram 9
Vertical Venting with Three (3) 90o Elbows
Option V + V1 H H + H1 A) 2' (610mm) Min. 1' (305mm) Max. 2' (610mm) Max. B) 3' (914mm) Min. 4' (1.22m) Max. 5' (1.5m) Max. C) 4' (1.22mm) Min. 6' (1.86m) Max. 8' (2.4m) Max. D) 5' (1.5m) Min. 8' (2.4m) Max. 12' (3.6m) Max.
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90
Diagram 11
Diagram 10
o
elbows is required.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
23
Page 24
INSTALLATION
Diagram 12
Vertical Venting with Three (3) 90o Elbows
Option V + V1 H + H1 A) 2' (610mm) Minimum 3' (914mm) Maximum B) 3' (914mm) Minimum 6' (1.86m) Maximum C) 4' (1.22m) Minimum 9' (2.7m) Maximum D) 5' (1.5m) Minimum 12' (3.6m) Maximum
With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90o elbows is required.
HORIZONTAL
TERMINATIONS
Install the vent system according to the manufacturer's instructions included with the components.
1) Set the unit in its desired location. Check
to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas.
2) Direct Vent pipe and fi ttings are designed with special twist-lock connections to connect the venting system to the appliance ue outlet. A twist-lock appliance adaptor is an available option that must be used in conjunction with the Simpson Dura-Vent Direct Vent system.
3) Put a bead of silicone inside the outer section of the adapter and a bead of Mill Pac on the inner collar. Slip the adapter over the existing inner and outer fl ue collar and fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier). Level the fi replace and fasten it to the framing using nails or screws through the nailing strips.
4) Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.
Note:
a) Twist-lock procedure: Four indentations,
located on the female ends of pipes and ttings, are designed to slide straight onto the male ends of adjacent pipes and fi ttings, by orienting the four pipe indentations so they match and slide in to the four entry slots on the male ends, Diagram 1. Push the pipe sections
completely together, then twist-lock one section clockwise approximately one-quarter turn, until the two sections are fully locked. The female locking lugs will not be visible from the outside, on the Black Pipe or fi ttings. They may be located by examining the inside of the female ends.
Diagram 1
NOTE: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every in­ner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.
b) Horizontal runs of vent must be
supported every three feet. Wall straps are available for this purpose.
5) Mark the wall for a 10" x 10" square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, a 7"(178mm) dia. (7-1/2"(191mm) dia. for fl ex) hole is acceptable.
Note: With Dura-Vent, the minimum height is achieved by installing a 45o elbow directly to the rigid pipe adaptor.
Diagram 2
Note:
a) The horizontal run of vent must be level,
or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.
b) The location of the horizontal vent
termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Vent Terminal Locations, see diagram in the "Exterior Vent Termination Locations" section.
6) The arrow on the vent cap should be pointing up. Insure that the 1-1/2"
clearances to combustible materials are maintained (Diagram 3 in the "Venting Arrangement - Horizontal Terminations" section) Install the termination cap.
The four wood screws provided should
be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
Note: If installing termination on a siding
covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.
24
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 25
INSTALLATION
Diagram 3
7) Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble (Part # 942) over the vent pipe.
8) Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap suffi cient distance so as to result in a minimum pipe overlap of 1-1/4 inches. Secure the connection between the vent pipe and the vent cap by attaching the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe. Use the two sheet metal screws provided to connect the strips to the pipe section. See Diagram 4.
9) Install wall thimble in the center of the 10" square and attach with wood screws (Diagram 5).
VERTICAL
TERMINATIONS
1) Maintain the 1-1/4" clearances
(air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces. Do not pack air spaces with insulation. Check the "Venting Arrangement" section for the maximum vertical rise of the venting system and the maximum horizontal offset limitations.
2) Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance fl ue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at his point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will obstruct the venting system. You may wish to relocate the appliance or to offset, as shown in Diagram 2 to avoid cutting load bearing members.
Diagram 2
4) Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.
5) Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of suffi cient size to meet the minimum requirements for clearance to combustibles of 1-1/4". Slip the fl ashing under the shingles (shingles should overlap half the fl ashing) as per Diagram 4.
Diagram 4: The upper half of the fl ashing is installed under the roofi ng material and not
nailed down until the chimney is installed.
This allows for small adjustments.
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic
to avoid obstructions, it is important to support the vent pipe every 3 feet, to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose (Diagram 2).
Galvanized pipe is desirable above the roofl ine
due to its higher corrosion resistance. Continue to add pipe sections through the fl ashing until the height of the vent cap meets the minimum height requirements specifi ed in Diagram 5 or
NOTE: For best results and optimum perform­ance with each approved venting system, it is highly recommended to apply “Mill-Pac” seal­ant (supplied) to every inner pipe connection. Failure to do so may result in drafting or per­formance issues not covered under warranty. Silicone (red RTV) is optional.
3) A Firestop spacer must be installed in the
oor or ceiling of every level. To install the
Diagram 4
Diagram 5
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Firestop spacer in a fl at ceiling or wall, cut a 10 inch square hole. Frame the hole as shown in Diagram 3 and install the restop.
Diagram 3
Diagram 5
Roof Pitch Minimum Vent Height Feet Meters at to 7/12 2 0.61 over 7/12 to 8/12 2 0.61 over 8/12 to 9/12 2 0.61 over 9/12 to 10/12 2.5 0.76 over 10/12 to 11/12 3.25 0.99 over 11/12 to 12/12 4 1.22 over 12/12 to 14/12 5 1.52 over 14/12 to 16/12 6 1.83 over 16/12 to 18/12 7 2.13 over 18/12 to 20/12 7.5 2.29 over 20/12 to 21/12 8 2.44
25
Page 26
INSTALLATION
local codes. Note that for steep roof pitches, the vertical height must be increased. A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.
7) Ensure vent is vertical and secure the base of the fl ashing to the roof with roofi ng rails, slide storm collar over the pipe section and seal with a mastic.
8) Install the vertical termination cap by twist­locking it.
Note: Any closets or storage spaces, which
the vent passes through must be enclosed.
Offset Chart
Note: To make the installation more aesthetically pleasing, we recommend framing out a square to mount the terminal to.
2) Level the replace and fasten it to the framing
using nails or screws through the nailing strips.
3) Assemble the vent assembly by applying Mill Pac to the 4"(100mm) inner collar of the termination and slipping the 4"(100mm) liner over it at least 1-3/8" (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Apply Mill Pac or high temperature silicone to the 6-7/8"(175mm) fl ex pipe and slip it over the 6-7/8" outer collar of the vent terminal at least 1-3/8"(35mm) and fasten with the 3 screws.
NOTE: Horizontal sections must be
supported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).
4) Separate the 2 halves of the wall thimble and
securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls. The liners must slip
over the collars a minimum of 1-3/8".
5) Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.
6) Pull the centre 4"(100mm) liner and outer
6-7/8"(175mm) liner out enough to slip over
the fl ue collars of the fi replace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than
o
.
45
7) Apply Mill Pac over the fi replace inner collar and slip the 4"(100mm) liner down over it and attach with 3 supplied screws.
8) Do the same with the 6-7/8"(175mm) liner.
9) Apply a bead of silicone between the thimble
and termination and around the outer edge of the terminal at the wall in order to keep the water out.
IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
INSTALLATION
PROCEDURES
for Regency® AstroCapTM Direct
Vent System (Flex)
1) Locate the unit in the framing, rough in the
gas. Locate the centerline of the termination and mark wall accordingly. Cut a 10"(254mm) hole in the wall (inside dimension).
Note: A 1-1/2"(38mm) clearance around
the liner must be maintained except that only a 1" (25mm) clearance is needed at the termination end. We recommend framing a 10"(254mm) x 10"(254mm) (inside dimensions) hole to give structural rigidity for mounting the termination.
Note: If installing termination on a siding
covered wall, furring strips must be used to ensure that the termination is not recessed into the siding.
26
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 27
INSTALLATION
CONVERSION KIT #731-969 FROM NG TO LP
FOR P121-2/P121LC-2/P121RC-2/P131-2 USING SIT 820 NOVA GAS VALVE
THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER
IF IN DOUBT DO NOT DO THIS CONVERSION !!
Each Kit contains one LPG Conversion Kit and one DC Sparker Kit.
LPG Conversion Kit Contains: Qty. Part # Description
1 904-529 5/32" Allen Key 1 904-641 Burner Orifi ce #50 1 918-590 Decal "Converted to
LPG" 1 908-528 Red "LPG" label 1 910-037 LPG Injector
(Pilot Orifi ce) 1 918-485 Instruction Sheet
DC Sparker Kit Contains: Qty. Part # Description
1 820-475 Bracket DC Sparker 1 820-476 Bracket DC Sparker 1 904-153 Washer #8 External Star 1 904-330 Nut 8-32 Hex 2 904-531 Bushing Split Plastic
0.500 in. 1 904-543 Screw 8-32 x 3/4 Pan Head 2 904-553 Screw #8 x 1/2 Type "B",
Black Oxide
1 910-073 Spark Generator
Battery Holder
1 910-074 Spark Generator Switch
C/W Wire 1 910-078 Battery Size AA Energizer En91 2 910-199 Clip Wire Holder 1 910-903 Wire Fan To Power Cord
Ground 30 in. 904-781 Velcro Hook, Black 904-782 Velcro Hook, Black
3) Remove the grate by lifting straight up.
Remove the side brick panels (if
installed). The brick panel is very
fragile - handle with care.
4) Remove the burner assembly by remov-
ing the 4 Phillips head screws and then slide the burner assembly away from the orifi ce and lift out.
Diagram 1
Diagram 1 and 2: Remove the left and right screws and then slide the burner assembly away from the orifi ce and lift out.
6) Unscrew the pilot orifi ce with the allen key
and replace with the LPG pilot orifi ce in the kit and replace pilot cap.
7) Remove burner orifi ce with a 1/2" wrench
to hold onto the elbow behind the orifi ce and discard the orifi ce.
Burner Orifi ce
8) Reinstall new burner orifi ce LPG stamped
#50 and tighten.
9) Turn control knob to the “OFF” position.
10) Remove the black protection cap by hand
from the high-low knob (Fig.1).
Installation of LPG Conversion Kit:
1) Remove the louvers and trim kit. Remove
the front door.
2) Remove the logs, embers.
5) Pull off the pilot
cap to expose the pilot orifi ce.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Diagram 2
Fig. 1
27
Page 28
INSTALLATION
11) Insert a 5/32” or 4mm Allen wrench into
the hexagonal key-way of the screw (Fig. 2), rotate it counter-clockwise until it is free and extract it.
Fig.2
12) Check that the screw is clean and if
necessary remove dirt.
13) Flip the screw (Fig. 3).
15) Verify that if the conversion is from NG
to LPG, the screw must be re-assembled with the red o-ring visible (Fig. 5).
Red o-ring visible
LPG Configuration
Fig.5
16) Re-assemble the black protection cap
(Fig. 6).
Installation of the DC Sparker:
20) Locate the Piezo Ignitor situated at the
side of valve.
Piezo
Ignitor
21) Remove the Piezo Ignitor by unscrewing
the nut at the back of the mounting bracket.
Ignitor
Wire
Piezo
Ignitor
Fig.3
14) Using the Allen wrench as shown in Fig.4,
rotate the screw clockwise until snug, do not overtighten.
Fig.4
ig. 6
WARNING!
Also check that the pilot and
main burner injectors are
appropriate for the gas type.
17) Reverse steps 4) to 1).
18) Attach the label "This unit has been
converted to LPG" near or on top of the serial # decal.
19) Replace yellow "NG" label with red "LPG"
label.
22) Disconnect the ignitor wire from the Piezo
Ignitor and connect it to the D.C. Sparker.
DC
Sparker
Ignitor
Wire
23) Connect the DC spark generator wires
to the SIT Valve with the screw, which is provided in the kit.
WARNING!
Do not over tighten the screw.
Recommended to
grip the wrench by the short side.
28
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 29
INSTALLATION
24) Locate the ground lug at the receptical
box, left of the unit.
25) Connect one end of the supplied green
ground wire to the lug with the nut and washer from the kit.
Ground
wire from
kit
28) Plug the DC spark generator wires to the
DC Sparker.
29) Connect the ground wire to the DC
Sparker mounting bracket.
32) Find a location which is not too hot and is
easy to reach for changing the battery.
33) Tie up the loose wire with the wire clip.
34) Check for gas leaks.
35) Check inlet and outlet pressures.
36) Check operation of fl ame control.
37) Check for proper fl ame appearance and
glow on logs.
26) Install the 1/2" bushing to the heat shield.
27) Run the other end of the ground wire and
DC spark generator wires through the bushing on the heat shield.
Heat Shield
Installer Notice:
These instructions must be left
with the appliance.
30) Install the supplied battery into the DC Sparker
Box by opening the battery compartment.
NOTE: The battery in the DC Sparker Box
will need to be replaced annually.
Battery
Compartment
31) Mount the heat shield to the DC Sparker.
Secure into place with the velcro, which is provided in the kit.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
29
Page 30
INSTALLATION
P121/P121LC/P121RC/P131-NG1
System Data
For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes: #31 Max. Input Rating 40,000 Btu/h
Min. Input Rating 20,500 Btu/h Supply Pressure min.5.0" w.c.
Manifold Pressure (High) 3.8"+/- 0.2"w.c.
Log Set: Ceramic bre, 8 per set. Vent System: Regency® AstrocapTM,
Regency® Direct Vent System (Flex) and Simpson Dura-Vent Direct Vent System
P121/P121LC/P121RC/P131-LP1
System Data
Conversion Kit# 730-969 For 0 to 4500 feet altitude
Burner Inlet Orifi ce Sizes: #50 Max. Input Rating 39,000 Btu/h Min. Input Rating 20,600 Btu/h
When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.
Important: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open fl ame for leak testing.
PILOT ADJUSTMENT
Periodically check the pilot fl ames. Correct ame pattern has three strong blue fl ames: 1 fl owing around the thermopile, 1 around the thermocouple and 1 fl owing across the burner (it does not have to be touching the burner).
Note: To properly check gas pressure, both
inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1) Make sure the valve is in the "OFF"
position.
2) Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a
1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Note: Screw should be snug,
but do not over tighten.
S.I.T. VALVE DESCRIPTION
Supply Pressure min.12.0" w.c.
Manifold Pressure (High) 11"+/- 0.2" w.c.
Log Set: Ceramic bre, 8 per set. Vent System: Regency® AstrocapTM,
Regency® Direct Vent System (Flex) and Simpson Dura-Vent Direct Vent System
HIGH ELEVATION
This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1 2.17-M91).
GAS LINE
INSTALLATION
The gas line can be brought through either the right, the left side or the bottom of the appliance. The gas valve is situated on the bottom of the unit.
The gas line connection may be made of rigid pipe, copper pipe or an approved fl ex connector . (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.
For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.
Note: If you have an incorrect fl ame pattern,
contact your Regency® dealer for further instructions.
Incorrect fl ame pattern will have small, probably yellow fl ames, not coming into proper contact with the rear burner or thermopile or thermocouple.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
1) Gas on/off knob
2) Manual high/low adjustment
3) Pilot Adjustment
4) Thermocouple Connection - option
5) Outlet Pressure Tap
6) Inlet Pressure Tap
7) Pilot Outlet
8) Main Gas Outlet
9) Alternative TC Connection
Point
30
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 31
LOG SET INSTALLATION
Read the instructions below carefully and refer to the diagrams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation.
Log Kit # 360-930 contains the following pieces: a) 326 Front Right Log b) 327 Front Left Log c) 328 Middle Right Log d) 329 Middle Left Log e) Embers (902-154) f) Platinum Embers (946-669) -
aged manual
Please note that there are 2 of each log. This log set is mirrored front and back.
supplied with pack-
INSTALLATION
INSTALLATION
3) Place Log 326 on the front right side of the burner.
Ensure that the notches on the far right side of the log fi t into the grate posts. Push back side of the left end of the log up against the tab on the burner.
326
327
326
329
The 3-digit numbers (ie. 327) are molded into the rear of each log.
328
1) Carefully remove the logs from the box and unwrap them. The logs are fragile, handle with care - do not force into position.
2) Place embers on the burner as shown below.
Separate platinum embers and place on the burner
over top of and around embers. Platinum embers can cover burner ports. Avoid stacking platinum embers.
Push back side of the left end of the log up
against the tab on the burner.
Repeat step 3 on the opposite side of the burner.
326
326
4) Place Log 327 on the front left side of the burner. Po-
sition the right end of the log in between the two tabs and the left end of the log into the grate post.
IMPORTANT
When placing Embers, do not block burner ports
as this can cause an incorrect fl ame pattern,
carbon deposits and delayed ignition.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
327
Grate Post
Tab on Burner
31
Page 32
INSTALLATION
INSTALLATION
Repeat step 4 on the opposite side of the burner.
327
327
5) Place Log 329 on the middle left side of the burner.
Rest the bottom of the Log onto the second grate post from the left. Ensure that the log fi ts into a pin that is on Log 326.
6) Place Log 328 on the middle right side of the burner.
Ensure that the log fi ts over the 2nd grate post from the right.
328
Grate Post
Repeat step 6 on the opposite side of the burner.
328
329
Grate Post
Repeat step 5 on the opposite side of the burner.
329
326
Pin
329
Completed Log Set Installation:
326 329328
328
327
32
328327 329 326
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 33
INSTALLATION
INSTALLATION
GLASS DOOR
REMOVAL
1) Remove the 8 screws that secure the glass
door.
2) Pull the door slightly out on an angle and
then lift up and pull completely out.
FINISHING TRIM
1) Slide the Side Finishing Trim up into the slot in the top fl ange of the fi replace. Push tight against the magnet at the base of the unit.
Slide Trim into
slot.
Push trim tight
against magnet.
LOUVERS & GRILLS
1) Attach the screws provided to the top left and right corners.
NOTE: Do not tighten the screw entirely, ensure that some room is left to be able to hang the grill or louver over the screw.
2) Hang the Top Louver or Grill onto the 2 screws in the top fi replace opening.
3) Attach the Bottom Louver or Grill to the hinges on the bottom fl ange of the replace.
3) P131 & P121LC/P121RC Corner Model: Remove the 6 screws that secure the glass door and repeat step 2.
2) Slide the Corner Finishing T rim up into the slot in the top fl ange of the fi replace. Push tight against the magnet at the base of the unit.
Slide Trim into
slot.
Push trim tight
against magnet.
P121-2 & P131-2 Corner Models
4) Attach the screws provided to the top and bottom, left and right corners similar to step 1.
5) Hang the top and bottom louver or grill onto the screws in the top and bottom, left and right sides of the fi replace opening.
The Top and Bottom Side Louver or Grill is
installed the same way.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
33
Page 34
INSTALLATION
Option 1:
REMOTE CONTROL
Can be used with Option 2 or 3 but
not both.
Use the Regency® Remote Control Kit approved for this unit. Use of other systems may void your warranty.
The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.
1) Choose a convenient location on the wall to install the receiver and the receptacle box (protection from extreme heat is very important). Run wires from the fi replace to that location. Use the Thermostat Wire Table.
2) Connect the two wires to the gas valve. See diagram below.
Option 2:
WALL SWITCH
Can be used with Option 1 or 3
but not both.
1) Run the supplied 15' of wire through the back gas inlet opening. Be careful not to damage wire.
Note: We recommend a maximum of 15' of
wire but if you wish to go with a longer run, use the Thermostat Wire Table.
2) Connect the wire to the supplied wall switch
and install into the receptacle box.
CAUTION
Do not connect millivolt all
switch wire to a 120V wire.
Option 3:
WALL THERMOSTAT
Can be used with Option 1 or 2 but
not both.
A wall thermostat may be installed if desired, connect the wires as per the wiring diagram. Use the table below to determine the maximum wire length.
Note: Preferable if the thermostat is installed on an interior wall.
Regency® offers an optional programmable thermostat but any 250-750 millivolt rated non­anticipator type thermostat that is CSA, ULC or UL approved may be used.
CAUTION
Do not connect millivolt
wall thermostat wires
to a 120V wire.
CAUTION
Do not connect millivolt
remote control wires to a
120V wire.
3) Install 3 AAA alkaline batteries in transmitter
and 4 AA alkaline batteries in the receiver. Install the receiver and its cover in the wall. Switch the remote receiver to "remote" mode. The remote control is now ready for operation.
Thermostat Wire Table
Recommended Maximum Lead Length
(Two-Wire) When Using Wall
Thermostat (CP-2 System)
Wire Size Max. Length
14 GA. 50 Ft. 16 GA. 32 Ft. 18 GA. 20 Ft. 20 GA. 12 Ft. 22 GA. 9 Ft.
34
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 35
WIRING DIAGRAMS
INSTALLATION
No electrical power supply is required for the gas control to operate. 120 Volt AC power is needed for the fan switch and blower. The fan can be hard wired if desired. A terminal block is provided on the left hand side of the unit.
For NATURAL GAS Units and Units NOT Equipped with DC Spark Boxes
Lockwasher
Star washer
Ground Wire
Grounding Lug Detail
#8 Ground Lug
(for mobile home)
Pilot
Assembly
Nut
A three wire power cord can also be used and plugged into a suitable receptacle.
(Do not cut the ground terminal off under any circumstances.)
Green (Ground) White (Neutral) Black (Live)
(*by others)
White
ON
Thermopile
Gas Pilot
Electrode
120 VAC
60HZ
(*by others)
Thermocouple
Black
(*Supplied by others - install
according to local code)
Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges.
White
OFF
FAN 1
(*by others)
Black
Thermodisc
FAN 2
Black
To Burner ON / OFF
Switch
Piezo
Ignitor
Red
Black
(To THTP)
(To TH)
ON OFF
Remote Receiver
or Thermostat
(Millivolt) (Optional)
To Thermocouple IN
Regency
Remote Transmitter
(Optional)
Brown
White
O
L
H
I
"S.I.T" Valve
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
O
F
F
P I
L
O
T
N
O
Gas In
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
35
Page 36
INSTALLATION
For PROPANE Units and Units Equipped with DC Spark Boxes*
*For installation of the DC Spark Box refer to the LP Conversion instructions in this manual.
Lockwasher
Star washer
(for mobile home)
Nut
Ground Wire
Grounding Lug Detail
To Burner ON / OFF
Switch
#8 Ground Lug
Red
Black
Pilot
Assembly
(To THTP)
(To TH)
ON OFF
Remote Receiver
or Thermostat
(Millivolt) (Optional)
Thermopile
Gas Pilot
Electrode
Remote Transmitter
(Optional)
120 VAC
60HZ
(*by others)
Thermocouple
White
Black
(*Supplied by others - install
according to local code)
DC Spark
Ground
Box
To Thermocouple IN
Regency
Green (Ground) White (Neutral) Black (Live)
(*by others)
OFF
ON
Black
Brown
White
(*by others)
Thermodisc
O
L
O
F
F
P I
H
L
I
O
T
N
O
"S.I.T" Valve
FAN 1
White
FAN 2
Black
Gas In
36
Terminal Block Location
Terminal Block
Remove cover to
access Terminal
Block
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 37
OPERATING INSTRUCTIONS
OPERATING
INSTRUCTIONS
1) Read and understand these instructions
before operating this appliance.
2) Check to see that all wiring is correct and enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the door frame is
properly positioned. Never operate the appliance with the glass removed.
5) Verify that the venting and cap are unobstructed.
6) Ensure that the brick panels are installed.
7) Verify log placement. If the pilot cannot be
seen when lighting the unit, the logs have been incorrectly positioned.
8) The unit should never be turned off, and on again without a minimum of a 60 second wait.
3) Turn gas control knob counterclockwise so indicator points to the "PILOT" position. Depress the gas control knob fully. Depress the igniter button several times until the pilot lights. After approximately one minute, release the gas control knob. The pilot fl ame should continue to burn. If the pilot does not remain lit, repeat operation allowing a longer period before releasing gas control knob.
4) When the pilot stays lit, turn the gas knob further counterclockwise to the "ON" position.
5) Use the wall switch, thermostat or remote control to turn on the unit.
6) Rotate the fl ame height regulator to adjust the fl ame height higher or lower.
SHUTDOWN
PROCEDURE
1) Use the wall switch, thermostat or remote
control to turn off the main burner.
2) Turn the main gas control clockwise to the "OFF" position to turn off the pilot.
AERATION
ADJUSTMENT
The air shutter can be adjusted by moving the adjusting wire up or down. The wire is accessed through the bottom louver opening. Open the air shutter for a blue fl ame or close for a yellower ame. The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude.
Minimum Air Shutter Opening: 3/16" Natural Gas 3/8" Propane
CAUTION: Carbon will be produced if air shutter is closed too much.
Note: Any damage due to carboning
resulting from improperly setting the aeration controls is NOT covered under warranty.
FIRST FIRE
DO NOT BURN THE APPLIANCE WITHOUT THE GLASS FRONT IN PLACE.
LIGHTING
PROCEDURE
IMPORTANT
To ignite or reignite the pilot,
remove one glass panel/door.
NOTE: For all propane units and units
equipped with electric spark boxes, see "Copy of Lighting Plate Instruc­tions" section for more details.
Only when the pilot holds, without pressure being applied to the control knob, resecure the glass panel to the unit. The unit must not be
operated with the glass removed.
IMPORTANT Gas on/off knob cannot be turned from "PILOT" to "OFF" unless it is partially depressed.
1) Turn burner OFF using "ON/OFF" switch.
2) Turn gas control knob so indicator points
to "OFF" position and allow 5 minutes for any gas in the combustion chamber to escape.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
The fi rst fi re in your fi replace is part of the paint curing process. To ensure that the paint is properly cured, it is recommended that you burn your fi replace for at least four (4) hours the fi rst time before you use it with the fan on.
When fi rst operated, the unit will release an odour caused by the curing of the paint, the burning off of any oils remaining from manufacturing. Smoke detectors in the house may go off at this time. Open a few windows to ventilate the room for a couple of hours.
Note: When the glass is cold and the
appliance is lit, it may cause condensation and fog the glass. This condensation is normal and will disappear in a few minutes as the glass heats up.
During the fi rst few fi res, a white fi lm may develop on the glass front as part of the curing process. The glass should be cleaned after the unit has cooled down or the fi lm will bake on and become very diffi cult to remove. Use a non-abrasive cleaner and DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS HOT.
Adjustment Wire - Push to close or
pull to open aeration cap.
Closed - Tall yellow
Open - Short Blue
Note: Aeration Adjustment should only be
performed by an authorized Regency® Installer at the time of installation or service.
37
Page 38
OPERATING INSTRUCTIONS
COPY OF THE LIGHTING PLATE INSTRUCTIONSNORMAL OPERATING
SOUNDS OF GAS
APPLIANCES
It is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various gauges and types of steel used within your appliance. Listed below are some examples. All are normal operating sounds and should not be considered as defects in your appliance.
Blower:
Regency® gas appliances use high tech blowers to push heated air farther into the room. It is not unusual for the fan to make a "whirring" sound when ON.
Burner Tray:
The burner tray is positioned directly under the burner tube(s) and logs and is made of a different gauge material from the rest of the fi rebox and body. Therefore, the varying thicknesses of steel will expand and contract at slightly different rates which can cause "ticking" and "cracking" sounds. Y ou should also be aware that as there are temperature changes within the unit these sounds will likely re-occur. Again, this is normal for steel fi reboxes.
Blower Thermodisc:
When this thermally activated switch turns ON it will create a small "clicking" sound. This is the switch contacts closing and is normal. Pilot Flame: While the pilot fl ame is on it can make a very slight "whisper" sound.
Gas Control Valve: As the gas control valve turns ON and OFF, a dull clicking sound may be audible, this is normal operation of a gas regulator or valve.
Unit Body/Firebox: Different types and thicknesses of steel will expand and contract at different rates resulting in some "cracking" and "ticking" sounds will be heard throughout the cycling process.
OFF
38
38
a
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 39
OPERATING INSTRUCTIONS
MAINTENANCE
INSTRUCTIONS
1) Always turn off the gas valve before cleaning.
For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year. When cleaning the logs, use a soft clean paint brush as the logs are fragile and easily damaged.
2) Clean appliance and door with a damp cloth (never when unit is hot). Never use an abrasive cleaner. The glass should be cleaned with a gas fi replace glass cleaner.
The glass should be cleaned when it starts looking cloudy.
3) The heater is fi nished in a heat resistant paint and should only be refi nished with heat resistant paint. Regency® uses StoveBright Paint - Metallic Black #6309.
4) Make a periodic check of burner for proper position and condition. Visually check the ame of the burner periodically, making sure the fl ames are steady; not lifting or fl oating. If there is a problem, call a qualifi ed service person.
5) The appliance and venting system must be inspected before use, and at least annually, by a qualifi ed fi eld service person, to ensure that the fl ow of combustion and ventilation air is not obstructed.
Note: Never operate the appliance without
the glass properly secured in place.
6) Do not use this appliance if any part has been
under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace nay part of the control system and any gas control which has been under water.
7) In the event this appliance has been serviced check that the vent-air system has been properly resealed & reinstalled in accordance with the manufacturer's instructions.
8) Verify operation after servicing.
General Vent Maintenance
Conduct an inspection of the venting system semi-annually. Recommended areas to inspect as follows:
1) Check the Venting System for corrosion in areas that are exposed to the elements. These will appear as rust spots or streaks, and in extreme cases, holes. These components should be replaced immediately.
2) Remove the Cap, and shine a fl ashlight down the Vent. Remove any bird nests, or other foreign material.
3) Check for evidences of excessive condensation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fi ttings. It may be caused by having excessive lateral runs, too many elbows, and exterior portions of the system being exposed to cold weather.
4) Inspect joints, to verify that no pipe sections or fi ttings have been disturbed, and consequently loosened. Also check mechanical supports such as Wall Straps, or plumbers' tape for rigidity.
LOG REPLACEMENT
The unit should never be used with broken logs. Turn off the gas valve and allow the unit to cool before opening door and carefully remove the logs. (The pilot light generates enough heat to burn someone.) If for any reason a log should need replacement, you must use the proper replacement log. The position of these logs must be as shown in the diagrams under Log Installation.
Note: Improper positioning of logs may
create carbon build-up and will severely alter the unit's performance which is not covered under warranty.
THERMOPILE /
THERMOCOUPLE
1) Open the Bottom Louvers or Grills. Remove the Top Louver or Grill.
2) Remove the Trim Kit, Glass Door, Log Set, Grate and Burner Assembly (see the "Log Installation" & "Glass Door Removal" sections).
3) Disconnect thermocouple by loosening nut from the valve with a 9mm wrench. Disconnect thermopile by loosening 2 screws marked TP on the valve.
4) Remove 2 screws from the pilot assembly and pull up far enough to be able to loosen the thermocouple or thermopile with a 7/16" wrench. NOTE: the pilot line is very fragile, use caution when pulling it up.
5) Drop the thermocouple or thermopile down through the extrusion and pull it out of the unit.
6) Reinstall the new ones in reverse order.
GLASS GASKET
If the glass gasket requires replacement use a tadpole glass gasket (Part # 936-155).
DOOR GLASS
Your Regency® fi replace is supplied with high temperature 5mm-Tempered glass & 5mm­Ceramic glass. If your glass requires cleaning, we recommend using an approved glass cleaner available at all authorized dealers. Do not use abrasive materials.
CAUTION & WARNINGS:
* Do not clean when the glass is hot. * The use of substitute glass will void all product warranties. * Care must be taken to avoid breakage of the glass. * Do not strike or abuse the glass. * Do not operate this fi replace without the glass front or with a cracked or broken glass front. * Wear gloves when removing damaged or broken glass. * Replacement of the glass panels should be done by a licensed or qualifi ed service per son.
GLASS REPLACEMENT
In the event that you break your glass by impact, purchase your replacement from an authorized Regency dealer only. Replacement glass is shipped already installed into the door frame. Reinstall as per Glass Door Installation in the "Glass Door Removal" section.
REPLACEMENT PARTS:
Front Door - Tempered (Part# 360-528) Side Door - Tempered (Part# 360-529) Front Door - Ceramic (Part# 360-538) Side Door - Ceramic (Part# 360-539)
GOLD-PLATED
Accessories
The 24 carat gold-plated fi nish requires little maintenance, and need only be cleaned with a damp cloth. DO NOT use abrasive materials or chemical cleaners, as they may harm the fi nish and void the warranty. Clean any ngerprints
off before turning the unit on.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
39
Page 40
MAINTENANCE
REMOVING VALVE
1) Shut off the gas supply.
2) Remove the louvers and trim kit. Remove the front door.
3) Remove the logs, embers.
4) Remove the grate by lifting straight up.
5) Remove the side brick clip in the top of the rebox and then slide the Side Brick Panel out. The brick panels are very fragile
- handle with care.
8) Remove the Side Base Brick Panels and nally the Long Base Brick Panels.
Remove Left & Right Side Base
Brick Panels
13) Undo the pilot tube from the valve with a 7/16" wrench.
14) Undo the quick drop out thermocouple nut on the valve with a 9mm (metric) wrench.
15) Remove the Piezo igniter wire and push button assembly.
16) Undo the "gas out" fl are nut with a 13/16" wrench.
Undo the "gas out" fl are fi tting with an
17)
11/16" wrench.
18) Remove the 6 Phillips head screws from the sides of the valve bracket and remove valve.
Hint: If you are using black pipe, ensure
that there is a union by the valve, otherwise removal will be almost impossible.
6) Remove the burner by removing the 4 screws.
7) Slide the burner assembly away from the orifi ce and lift out.
Remove the 2 Long Base Brick Panels
9) Disconnect the inlet gas line.
10) Disconnect the 2 TP wires and the 2 TH wires from the valve.
11) Remove the 16 Phillips head screws securing the valve tray.
12) Lift the entire assembly out.
40
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 41
MAINTENANCE
MAINTENANCE
INSTALLING VALVE
1) Attach the valve to the valve bracket with
the 6 (m5x8 metric) screws provided.
2) Reconnect the "gas out" fl are fi tting with an 11/16" wrench.
3) Reconnect the "gas out" fl are nut with a 13/16" wrench.
4) Install piezo ignitor push button assembly and reconnect wire.
5) Reconnect the quick drop out thermocouple nut with a 9mm wrench.
6) Reconnect the pilot tube nut with a 7/16" wrench.
7) Scrape off the old gasket from the fl oor of the rebox and from the valve tray assembly.
8) Install a new gasket and reinstall the valve tray assembly.
Note: Failure to install a new gasket may severely affect the appliance performance.
9) Reinstall the 16 hold down screws.
FAN REPLACEMENT
1) Shut off power.
2) Remove top louvers.
3) Unplug power wires.
4) Remove 4 screws securing fan to mounting
bracket.
5) Remove 2 connector wires.
6) Replace fan.
7) Repeat for opposite side/corner.
8) Reverse steps 1 - 5 for installation.
9) T o remove the thermodisc, located at the back
center of the unit, slide the thermodisc/cover assembly away from the bracket clip on the under side of the fi rebox. Reverse for installation. Ensure that no wires will touch hot surfaces.
10) Hook up the 2 TP and 2 TH wires to the appropriate connections on the valve.
11) Reinstall the Burner Assembly.
13) Hook up the gas line and check for gas
leaks with a soap and water solution or a gas leak detector. (Do not use open fl ame for leak testing.)
14) Fire up the unit temporarily
15) Check the manifold pressure.
16) Reinstall the logs, grate and brick panels
as needed.
17) Reinstall the glass doors.
18) Fire up the unit again and check for proper
ame appearance.
Connector wires
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
41
Page 42
PARTS LIST
100
99
98
181
181
34
11
3434
32
BRICK PA NELS
9
146
146
168
146
172
1
135
204
204
172
17
206
24
10
206
146
207
150
151
204
171
1
171
204
205
205
P121-2 (SEE THRU) MAIN ASSEMBLY
Part # Description Part # Description Part # Description
1) 360-528 Door Assy Front - Tempered 360-538 Door Assy Front - Ceramic (Optional)
2) 360-529 Door Assy Side - Tempered 360-539 Door Assy Side - Ceramic (Optional)
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
17) 360-086 Gasket - Relief Door
24) * Relief Door Assembly
32) 362-528 Brick Panel Base (Set of 6)
34) 902-603 Brick Panel - Std. Red (Side)
98) 910-366 Switch Cover Plate
99) 910-363 Wall Switch
100) 910-367 Switch Receptacle Plastic Box 910-882 Wire - Valve to Burner Switch
135) 360-069 Heat Shield - Side
146) 360-033 Left Side Door Trim 360-034 Right Side Door Trim
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
168) 360-068 Door Cover Assembly - Side
171) 360-920 Louver Front - Black (set) 360-922 Louver Front - Black/Gold (set) 360-924 Louver Front - Black/Steel (set)
181) * Extension Trim - See Thru
204) 360-940 Dec. Grill Front - Black (set)
205) 948-216 Regency
206) 910-171 Fan Axial 115V
207) 910-142 Thermodisc 918-519 Manual *Not available as a replacement part.
®
Logo Plate
42
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 43
PARTS LIST
2
99
98
224
224
204
204
171
171
1
149
17
24
173
173
11
100
141
10
206
181
3434
151
171
225
225
32
171
141
204
204
9
150
151
146
146
1
206
226
P131-2 (PIER) MAIN ASSEMBLY
Part # Description Part # Description Part # Description
1) 360-528 Door Assy Front - Tempered
360-946 Door Assy Front - Ceramic (Optional)
2) 360-529 Door Assy Side - Tempered
360-948 Door Assy Side- Ceramic (Optional)
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
98) 910-366 Switch Cover Plate
99) 910-363 Wall Switch
100) 910-367 Switch Receptacle Plastic Box 910-882 Wire - Valve to Burner Switch
141) 360-031 Column Finishing Trim
146) 360-035 Finishing Trim
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
173) 360-932 Louver Side - Black (set) 360-934 Louver Side - Black/Gold (set) 360-936 Louver Side - Black/Steel (set)
181) * Extension Trim - Pier
204) 360-940 Dec. Grill Front - Black (set)
206) 910-171 Fan Axial 115V
224) 360-942 Dec. Grill Side - Black (set)
225) 948-216 Regency
®
Logo Plate
226) 910-412 Thermodisc
17) 360-086 Gasket - Relief Door
24) * Relief Door Assembly
32) 362-528 Brick Panel Base (Set of 6)
34) 902-603 Brick Panel - Side Std. Red
171) 360-920 Louver Front - Black (set) 360-922 Louver Front - Black/Gold (set) 360-924 Louver Front - Black/Steel (set)
918-519 Manual *Not available as a replacement part.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
43
Page 44
PARTS LIST
P121RC-2 (RIGHT CORNER) MAIN ASSEMBLY
Part # Description Part # Description Part # Description
1) 360-528 Door Assy Front - Tempered 360-538 Door Assy Front - Ceramic (Optional)
2) 360-529 Door Assy Side - Tempered 360-539 Door Assy Side - Ceramic (Optional)
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top 780-013 Standoff - Rear
17) 360-086 Gasket - Relief Door
24) * Relief Door Assembly
32) 362-528 Brick Panel Base (Set of 6)
34) 902-603 Brick Panel - Side Std. Red
35) 902-604 Brick Panel - Front Std. Red
98) 910-366 Switch Cover Plate
99) 910-363 Wall Switch
100) 910-367 Switch Receptacle Plastic Box 910-882 Wire - Valve to Burner Switch
138) 360-063 Heat Shield - Front
141) 360-031 Column Finishing Trim
146) 360-035 Finishing Trim - Left Side
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
158) 360-060 Door Cover Assembly-Front
171) 360-920 Louver Front - Black (set) 360-922 Louver Front - Black/Gold (set) 360-924 Louver Front - Black/Steel (set)
173) 360-932 Louver Side - Black (set) 360-934 Louver Side - Black/Gold (set) 360-936 Louver Side - Black/Steel (set)
181) * Extension Trim
204) 360-940 Dec. Grill Front - Black (set)
206) 910-171 Fan Axial 115V
224) 360-942 Dec. Grill Side - Black (set)
225) 948-216 Regency
226) 910-142 Thermodisc 918-519 Manual *Not available as a replacement part.
®
Logo Plate
204
204
225
224
224
34
171
35
1
99
100
181
98
32
24
11
146
BRICK PA N ELS
225
10
9
17
171
141
206
158
173
146
206
151
150
138
226
149
2
151
44
173
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 45
PARTS LIST
181
100
10
2
98
99
173
146
173
17
138
158
24
11
206
206
151
150
226
224
224
149
151
204
34
35
9
32
BRICK PA NELS
146
141
204
171
171
1
225
225
P121LC-2 (LEFT CORNER) MAIN ASSEMBLY
Part # Description Part # Description Part # Description
1) 360-528 Door Assy Front - Tempered
360-538 Door Assy Front - Ceramic (Optional)
2) 360-529 Door Assy Side - Tempered
360-539 Door Assy Side - Ceramic (Optional)
9) 360-046 Nailing Strip - Top - Front
10) 360-047 Nailing Strip - Top - Side
11) 430-001 Standoff - Top
17) 360-086 Gasket - Relief Door
24) * Relief Door Assembly
32) 362-528 Brick Panel Base (Set of 6)
34) 902-603 Brick Panel - Side Std. Red
35) 902-604 Brick Panel - Front Std. Red
98) 910-366 Switch Cover Plate
99) 910-363 Wall Switch
100) 910-367 Switch Receptacle Plastic Box 910-882 Wire - Valve to Burner Switch
138) 360-069 Heat Shield - Front
141) 360-031 Column Finishing Trim
146) 360-035 Finishing Trim
149) 360-122 Magnet Bracket - Corner
150) 360-123 Magnet Bracket - Front
151) 904-258 Magnet
158) 360-062 Door Cover Assembly-Front
171) 360-920 Louver Front - Black (set) 360-922 Louver Front - Black/Gold (set) 360-924 Louver Front - Black/Steel (set)
173) 360-932 Louver Side - Black (set) 360-934 Louver Side - Black/Gold (set) 360-936 Louver Side - Black/Steel (set)
204) 360-940 Dec. Grill Front - Black (set)
206) 910-171 Fan Axial 115V
224) 360-942 Dec. Grill Side - Black (set)
®
225) 948-216 Regency
226) 910-142 Thermodisc 918-519 Manual *Not available as a replacement part.
Logo Plate
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
45
Page 46
PARTS LIST
P121/P121LC/P121RC/P131-2 BURNER ASSEMBLY & LOG SET
Part # Description 360-930 Log Set
41) * Front Right Log
42) * Front Left Log
43) * Middle Left Log
44) * Middle Right Log 360-574/P Valve Assembly
56) 910-478 Valve S.I.T. - NG/LPG
57) 360-090 Gasket - Valve Tray
58) * Valve T ray
66) 910-038 Pilot Assembly - NG 910-039 Pilot Assembly - LPG
67) * Pilot Holder
68) W840470 Pilot Assembly Gasket
69) 910-190 Piezo Ignitor and Nut
79) 360-525 Burner Assembly
82) 360-027 Grate Assembly 904-690 Orifi ce #31 - NG 936-170 Orifi ce Gasket
*Not available as a replacement part.
46
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
Page 47
WARRANTY
Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a Excalibur Product. This warranty is not transferable.
The Warranty: Limited Lifetime
The combustion chamber, heat exchanger, burner tubes/pans, logs, brick panels and gold plating (against defective manufacture only) are covered under the Limited Lifetime Warranty for fi ve (5) years for parts and subsidized labour* and parts only thereafter.
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for fi ve (5) years and parts only thereafter from date of purchase.
External casting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and subsidized labour* for three (3) years from the date of purchase and parts only thereafter.
Special Finishes - One year on brushed nickel and antique copper full screens and doors. You can expect some changes in color as the product "ages" with constant heating and cooling. FPI warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty does not cover changing colors and marks, ie. fi nger prints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
Electrical and mechanical components such as blowers, switches, wiring, thermodiscs, FPI remote controls, spill switches, thermopiles, thermocouples, pilot assembly components, and gas valves are covered for two years parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered repairs and continue as if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacement.
FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.
Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
Repair/replacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any item shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.
Conditions:
Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent provided that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
Porcelain/Enamel - Absolute perfection is either guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three days of installation. Reported damage after this time will be subject to rejection.
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect.
The authorized selling dealer is responsible for all in-fi eld service work carried out on your Regency product. FPI will not be liable for results or costs of workmanship from unauthorized service persons or dealers.
At all times FPI reserves the right to inspect product in the fi eld which is claimed to be defective.
All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name, purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:
This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.
At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured. ie. as products evolve, fi eld modifi cations or upgrades will not be performed.
FPI will not be liable for travel costs for service work.
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers, rockwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical systems such as furnaces, fans, clothes dryer, etc.
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.
FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your warranty on this product.
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.
Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace
47
Page 48
Regency® fi replace products are designed
with reliability and simplicity in mind. In
addition, our internal Quality Assurance
Team carefully inspects each unit
thoroughly before it leaves our door .
Fireplace Products International
Ltd. is pleased to extend this
Limited Lifetime Warranty to the
original purchaser of a Regency®
Product.
See the inside back cover for details.
Register your Regency® online at
http://www.regency-fi re.com
Installer: Please complete the following information
Dealer Name & Address: ______________________________________________ ___________________________________________________________________ Installer: ___________________________________________________________ Phone #: ___________________________________________________________ Date Installed: ______________________________________________________ Serial No.: __________________________________________________________
Regency and Panorama are trademarks of FPI Fireplace Products International Ltd.
© Copyright 2010, FPI Fireplace Products International Ltd. All rights reserved.
Printed in Canada