Regency P121-NG, P121LC-NG, P121RC-NG, P131-NG User Manual

Owners & Installation
Zero Clearance Room
Sealed Gas Fireplace
Manual
LISTINGS AND CODE APPROVALS
These gas appliances have been tested in accordance with AS4553-2000, NZS 5262 and have been certified by the Australian Gas Association for installation and operation as described in these Installation and Operating Instructions.
Your unit should be serviced annually by an authorised service person.
STYLE MODEL See Thru P121-NG P121-LPG Left Corner P121LC-NG P121LC-LPG Right Corner P121RC-NG P121RC-LPG Pier P131-NG P131-LPG
PLEASE KEEP THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING: Improper installation, adjustment, altera­tion, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional infor­mation consult an authorized installer, serv­ice agency or the gas supplier.
FOR YOUR SAFETY Do not store or use gasoline or other flamma­ble vapours and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by an authorized installer, service agency or the gas supplier.
FOR YOUR SAFETY What to do if you smell gas:
918-179a
02/16/06
To the New Owner:
Congratulations!
You are the owner of a state-of-the-art Gas Fireplace by REGENCY. The P121/P121LC/P121RC/ P131 is a hand crafted appliance and has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The model P121/P121LC/P121RC/P131 has been approved by the Australian Gas Association for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency Fireplace.
IMPORTANT:
If the unit is to be installed into a bathroom, optional Neo ceramic glass Part# 360-946 Front or Part# 360-948 Side must be purchased and installed in place of the tempered glass supplied with the unit.
2
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
TABLE OF CONTENTS
Safety Label
Safety Label ............................................................... 4
Installation
Important Message .................................................... 5
Before You Start ........................................................ 5
General Safety Information ......................................... 5
Installation Checklist .................................................. 5
Specifications ............................................................ 6
Locating Your Fireplace ............................................. 8
Clearances ................................................................. 9
Combustible Mantel Clearances ................................. 9
Framing and Finishing ...............................................10
Facing and Finishing Requirements .......................... 11
Unit Assembly Prior to Installation
Top Standoff Assembly ....................................... 11
Flueing Introduction ...................................................11
Exterior Flue Termination Locations .......................... 12
Flueing: Direct Vent System (Flex) ........................... 13
Flueing: Simpson Dura-Vent Direct Vent GS .............14
Flueing: Simpson Dura-Vent Components List .......... 14
Flueing Arrangements
Horizontal Terminations ...................................... 15
Vertical Terminations ..........................................17
Flueing - Dura-Vent Horizontal Installations ...............19
Flueing - Dura-Vent Vertical Termination ................... 20
Flueing - Installation Procedures for Direct Vent
System (Flex) ..................................................... 21
Converion to LPG ......................................................22
System Data ............................................................. 23
Gas Line Installation..................................................23
Pilot Adjustment ....................................................... 23
Gas Pipe Pressure Test ............................................ 23
S.I.T. Valve Description .............................................23
Log Set Installation ................................................... 24
Glass Door Removal..................................................26
Finishing Trim ........................................................... 26
Louvers and Grills......................................................26
Remote Control (optional) .......................................... 27
Remote Wall Switch (optional) .................................. 27
Wall Thermostat (optional) ........................................27
Wiring Diagram ......................................................... 28
Operating Instructions
Operating Instructions ............................................... 29
Lighting Procedure .................................................... 29
Shutdown Procedure .................................................29
First Fire ...................................................................29
Normal Operating Sounds of
Gas Appliances .................................................. 29
Aeration Adjustment..................................................29
Lighting Plate Instructions ......................................... 30
Maintenance
Maintenance Instructions .......................................... 30
General Flue Maintenance ........................................30
Log Replacement ...................................................... 31
Thermopile/Thermocouple ......................................... 31
Glass Gasket ............................................................ 31
Door Glass ................................................................ 31
Gold-Plated Accessories ...........................................31
Removing Valve .........................................................31
Installing Valve .......................................................... 32
Parts List
Replacement/Spare Parts List ................................... 33
Warranty
Warranty ...................................................................39
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 3
SAFETY LABEL
This is a copy of the label that accompanies each REGENCY P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open.
NOTE: Regency units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
4
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
INSTALLATION
IMPORTANT:
SAVE THESE
INSTRUCTIONS
The Regency P121/P121LC/P121RC/P131-NG or P121/P121LC/P121RC/P131-LPG Room Sealed Gas Fireplace must be installed in ac­cordance AG601 and NZS 5261 and with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the respon­sibility of the installer to ensure this fireplace is installed in compliance with manufacturer's instructions and all applicable codes.
BEFORE YOU START
Safe installation and operation of this appliance requires common sense, however, we are required to make you aware of the following:
INSTALLATION AND REPAIR SHOULD BE DONE BY A AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A AUTHORIZED SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPER­ATIVE THAT CONTROL COMPART­MENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLI­ANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNI­TURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CLOTHING OR OTHER FLAMMABLE MA­TERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIAL­LY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
YOUNG CHILDREN SHOULD BE
CAREFULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE AP­PLIANCE.
GENERAL SAFETY
INFORMATION
1) The appliance shall be installed in accord­ance with the manufacturer's installation instructions, local gas fitting regulations, municipal building codes, water supply reg­ulations, electrical wiring regulations, with AS5601-2004 (AGA gas installation code) NZS 5261 (New Zealand)
2) See general construction and assembly instructions. The appliance and flue should be enclosed.
3) This appliance must be connected to the specified flue and termination cap to the outside of the building envelope. Never flue to another room or inside a building. Make sure that the flue is fitted as per Flueing instructions.
4) Inspect the flueing system annually for blockage and any signs of deterioration.
5) Flueing terminals shall not be recessed into a wall or siding.
6) Any safety glass removed for servicing must be replaced prior to operating the appliance.
7) To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace.
8) Wear gloves and safety glasses for pro­tection while doing required maintenance.
9) Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
10) Under no circumstances should this appli­ance be modified. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
11) Installation and any repairs to this appliance should be done by a authorized service person. A authorized service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
12) Do not slam shut or strike the glass door.
13) Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
14) The appliance area must be kept clear and free of combustible materials, (gases and other flammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
INSTALLATION
CHECKLIST
Note: These units are
non-load bearing.
1) Locate appliance a) Room location, page 8. b) Clearances to Combustibles,
page 9. c) Mantle Clearances, page 9. d) Framing & Finishing Requirements,
page 10. e) Flueing Requirements, pages 11-19.
2) Assemble Top Standoffs, page (NOTE: page 11 must be done before installing unit into fireplace.)
3) Install flue, pages 19-21.
4) Make gas connections. Test the pilot. Must be as per diagram. Page 22.
5) Install log set where indicated on page 24-25.
6) Glass Door Removal (page 26), Louvers or Grills (page 26), and Finishing Trim (page 26).
7) Install optional Wall Switch, Remote Con­trol, or Wall Thermostat, page 27.
8) Final check.
Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to cus­tomer.
This includes:
1) Clocking the appliance to ensure the cor­rect firing rate (rate noted on label 40,000 Btu/h NG, and 39,000 Btu/h LPG) after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsi­bility of the manufacturer.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 5
INSTALLATION
SPECIFICATIONS
P121 - See Thru
Note: These units are non-load bearing.
P131 - Pier
6
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
P121LC - Left Corner Unit
INSTALLATION
Note: These units are non-load bearing.
P121RC - Right Corner Unit
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 7
INSTALLATION
LOCATING YOUR
GAS FIREPLACE
1) When selecting a location for your stove, ensure that the clearances are met as outlined on page 9.
2) Provide adequate clearances for servic­ing.
3) The appliance must be installed on a flat, solid, continuous surface (e.g. wood, met­al, concrete). This may be the floor, or raised up on a platform to enhance its visual impact. If the appliance is going to be in­stalled on carpeting, combustible linoleum tile or other combustible material other than wood flooring, the appliance must be in­stalled on a metal or wood panel extending the full width and depth of the appliance.
4) The Room Sealed Gas Fireplace can be installed as follows:
A) P121 - See Thru
Model # Position A ) P121: See Thru B) P131: Pier C) P121LC: Left Corner D) P121RC: Right Corner
5) This appliance is Listed for bedroom instal­lations when used with a Listed Millivolt Thermostat. Some areas may have further requirements, check local codes before installation.
6) The P121/P121LC/P121RC/P131 Room Sealed Gas Fireplace is approved for al­cove installations, which meet the clear­ances listed on this page.
7) We recommend that you plan your installa­tion on paper using exact measurements for clearances and floor protection before actually installing this appliance. Have a authorized inspector, dealer, or installer review your plans before installation.
Note: For Exterior Flue Termination
Locations see page 12.
.
B) P131 - Pier
C) P121LC - Left Corner
D) P121RC - Right Corner
8
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams on page 8):
Clearance to Combustibles from:
Back 0" (0mm) Side 0" (0mm) Floor 0" (0mm)
CAUTION REQUIREMENTS: The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoffs may NOT be recessed into combus­tible construction.
Determine the total thickness of the finished floor (eg. tile, carpet, slate) to allow the finished surface to be flush with the base of the unit.
Ceiling Height from Floor 72" (1828mm)
Fire hazard is an extreme risk
if these clearances (air space)
to combustible materials are
not adhered to. It is of greatest
importance that this fireplace
and flue system be installed
only in accordance with these
INSTALLATION
WARNING:
instructions.
Mantel Height from Base of Unit:
39" min. (991mm)
Horizontal Flue Clearances:
Top 2-1/2"(64mm) Side 1-1/2"(38mm) Bottom 1-1/2"(38mm)
Vertical Flue Clearances 1-1/4" (32mm)
COMBUSTIBLE MANTELS
Because of the extreme heat this fireplace emits, the mantel clearanc­es are critical. Combustible mantel clearances from top of unit are shown in
Diagram to the right.
Note: A non-combustible mantel may be installed at a lower height if
the framing is made of metal studs covered with a non­combustible board.
This drawing is to scale at 1:6 (one inch = 6 inches) Mantel can be installed anywhere in shaded area or higher using this scale.
Caution: Ensure the paint that is used on the mantel and the facing is
"heat resistant" or the paint may discolour.
Mantel Clearances
* If the 3" (76mm) metal extension trim is removed it must be replaced with a 8" (203mm) non-combustible material.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 9
B
C
A
INSTALLATION
FRAMING AND FINISHING
1) For ease of installation, frame your fireplace after it is positioned and the flue system is installed. Remember to install the top standoffs. See page 11 for assembly. Use 2x4's and frame to local building codes.
CAUTION: Verify your fireplace dimensions, framing methods and finished wall facing details before framing. Determine the total thickness of facing material - drywall plus ceramic tiles, slate, etc. Allow the finish surface to be flush with the front or side of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.
2) When locating your appliance on an exterior wall or in a chase, apply a vapour barrier and drywall, as per local building codes. DO NOT
INSULATE THE FIREPLACE ITSELF.
CAUTION: The unit does not have to be completely enclosed in a chase. The clearance on top of the unit is 0" to the standoffs so combustible building materials can be laid directly on top of the standoffs. You must maintain clearance from the flue to combustible materials for both rigid and flex, see Flue Clear­ances, page 9.
P121 - See Thru
Framing Dimensions
P121 (See Thru) P131 (Pier) P121LC / P121RC
(Corner Unit)
A 25"(635mm) 25"(635mm) 26-13/13"(660mm)
minus two times minus two times minus two times the finishing the finishing the finishing material thickness* material thickness* material thickness*
B 42-1/2"(1080mm) 42-1/2"(1080mm) 42-1/2"(1080mm)
C 46-3/4"(1187mm) 45" (1143mm) 45"(1143mm)
minus one time minus one time the finishing the finishing material thickness* material thickness*
* Finish material thickness includes: drywall, ceramic tile, slate, etc.
P121LC - Corner Unit
P131 - Pier
Note: These units are non-load bearing.
10
P121RC - Corner Unit
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace
INSTALLATION
FACING & FINISHING REQUIREMENTS
This fireplace is supplied with a 3" metal extension trim above the fireplace. The extension trim may be replaced if the framing is faced with a non­combustible material placed flush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.)
UNIT ASSEMBLY
PRIOR TO
INSTALLATION
The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position.
Top Standoff Assembly
The top standoffs are shipped in a flat position and must be folded into shape and attached.
1) Remove the standoffs from the fireplace top.
2) Take each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the pre-punched screw holes on the fireplace top line up.
3) Attach the standoff securely to the top with 4 screws per standoff (on opposite cor­ners).
FLUEING
INTRODUCTION
The P121/P121LC/P121RC/P131 uses the "balanced flue" technology Co Axial system. The inner liner flue products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be con-
nected to any other appliance.
The gas appliance and flue system must be flueed directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct flue gas appliance must use it's own separate flue system. Common flue sys­tems are prohibited.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace 11
INSTALLATION
EXTERIOR FLUE TERMINATION LOCATIONS
Minimum clearances required for balanced flue terminals or
the flue terminals of outdoor appliances
according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand)
Minimum
a Below eaves, balconies or other projections:
- Appliances up to 50 MJ/h input 300
- Appliances over 50 MJ/h input 500 b From the ground or above a balcony 300 c From a return wall or external corner 500 d From a gas meter (M) 1000 e From an electricity meter or fuse box (P) 500 f From a drain or soil pipe 150 g Horizontal from any building structure (unless appliance is approved
for closer installation) or obstruction facing a terminal 500 h From any other flue terminal, cowl or combustion air intake 500 j Horizontally from an openable window, door, or non-mechanical air inlet, or
any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)):
- Appliances up to 150 MJ/h input 500
- Appliances over 150 MJ/h input 1500
k Vertically below an openable window, door, or non-mechanical air inlet,
or any other opening into a building, with the exception of sub-floor ventilation
(see also Note (I)): see table below
Clearance (mm)
Clearance 'k' in mm
Space Heaters All Other Appliances Up to 50 MJ/h Up to 50 MJ/h input Over 50 MJ/h input Over 150 MJ/h input
input to 150 MJ/h input
12
150 500 1000 1500
NOTES: (I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases. (II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest
par to of the terminal. (III) Prohibited area below electricity meter or fuse box extends to ground level. (IV)A flue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on
at least two sides and a free flow of air at the appliance is achieved.
Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace