Combustible
Material
3”
Extension
Trim
Non-Combustible
Material *
Top of
Unit
8”
Greyed out framing will not apply to all units.
Please refer to the manual.
L
Gas Fireplaces
P121-P131 Gas Fireplace
P121 - P121LC/RC - P131 Zero Clearance Direct Vent Gas Fireplace
Model P121/P131-NG2 P121/P131-LP2
Fuel Type Natural Gas Propane
Minimum Supply Pressure 5” W.C. (1.25 kPa) 12” W.C. (3.00 kPa)
Manifold Pressure - High 3.8” W.C. (0.95 kPa) 11” W.C. (2.74 kPa)
Manifold Pressure - Low 1.1” W.C. (0.27 kPa) 2.9” W.C. (0.72 kPa)
Orifi ce Size #31 DMS #50 DMS
Minimum Input 20,500 BTU/h (6.01 kW) 20,600 BTU/h (6.04 kW)
Maximum Input 40,000 BTU/h (11.72 kW) 39,000 BTU/h (11.43 kW)
Vent Sizing 4” Inner / 6-5/8” Outer 4” Inner / 6-5/8” Outer
Approved Venting Systems
Flex Vent Systems: FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems: Simpson Dura-Vent® Direct Vent GS
M
N
Electrical
Inlet
BACK
P
Gas Line
Inlet
O
B
American Metal Products Ameri Vent
Security Secure Vent®
Selkirk Direct-Temp.
P121 See Thru P131 Pier
P121RC Right Corner P121LC Left Corner
G
F
Gas Fireplaces
D
C
41-1/2”
(1054mm)
44-1/2”
(1130mm)
26-13/16”
(681mm)
21-1/8”
(537mm)
4-3/4”
(121mm)
E
A
Unit Dimensions Description P121 P121LC/RC P131
A Front Face Width
B Total Firebox Width
C Front Face Height 36” (914mm) 36” (914mm) 36” (914mm)
D Height w/ Standoff 42” (1067mm) 42” (1067mm) 42” (1067mm)
E Unit Depth 25” (635mm)
F Top Offset Depth
G Inset to Standoff
If the provided 3” extension trim is not installed the P121(LC/RC)/
P131 must be installed with non-combustible facing up to 8” above
the fi replace. Otherwise combustible facing may be used above the
43-1/2”
(1105mm)
46-1/4”
(1175mm)
21-1/8”
(537mm)
4-3/4”
(121mm)
extension trim.
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
41-1/2”
(1054mm)
44-1/2”
(1130mm)
25” (635mm)
21-1/8”
(537mm)
3” (76mm)
Framing Dimensions Description P121 P121LC/RC P131
H Framing Width
I** Framing Height **
J
** Framing Depth** 25” (635mm)**
K Vent Centerline Height 42-13/16” (1072mm)
L Framed Chase Ceiling 48-1/4” (1226mm)
M Electrical Inlet Height 2” (51mm) 2” (51mm) 2” (51mm)
N Electrical Inlet Inset
O Gas Connection Height
P Gas Connection Inset
46-3/4”
(1187mm)
42-1/2”
(1080mm)
11-3/8”
(289mm)
1-11/16”
(43mm)
11-1/2”
(292mm)
45”
(1143mm)**
42-1/2”
(1080mm)
26-13/16”
(681mm)
13-5/16”
(338mm)
1-11/16”
(43mm)
11-1/2”
(292mm)
45”
(1143mm)**
42-1/2”
(1080mm)
25” (635mm)
11-3/8”
(289mm)
1-5/8” (41mm)
11-1/2”
(292mm)
**
** Refer to the manual for variations effected by fi nishing material
thickness.
69June 2007 Regency Product Specifi cations Book
P121-P131 Gas Fireplace
Framing and Finishing
Gas Fireplaces
Parallel Wall Clearances
1) Determine the total thickness of facing material (e.g. drywall plus
ceramic tiles) to allow the fi nished surface to be fl ush with the front
of the unit. Total facing thickness can vary from 1/2” (13mm) to 1-¼”
(32mm) thick.
2) Frame in the enclosure for the unit with framing material.
Gas Fireplaces
3) For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local
installation codes. (Do not insulate the fi replace itself.)
4) The top of the unit must not be closer than 36” (990mm) to the
ceiling.
5) Combustible material may be brought up to the top and
sides of the unit and be covered with ceramic tiles, bricks,
rock or other suitable combustible finishing materials.
Note: The unit does not have to be completely enclosed in a
chase. The clearance on top of the unit is 0” to the standoffs
so combustible building materials can be laid directly on top
of the standoffs. You must maintain proper clearances from
the vent to combustible materials (See Below).
6) Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.
Clearance Requirements
D
C
Unless otherwise stated the clearances listed below are Minimum
distances to combustible materials. Unit pictured is a P131
Parallel Wall Clearances P121(LC/RC)/131
Min distance from glass to a parallel wall 36” (914mm)
36"min.
(914mm)
36"min. (914mm)
36"min.
(914mm)
Vent Clearances Clearance Dimension
Horizontal - Top 2-1/2” (64mm)
Horizontal - Side 1-1/2” (38mm)
Horizontal - Bottom 1-1/2” (38mm)
Vertical 1-1/4” (32mm)
WARNING
Failure to maintain required clearances is a major cause of
chimney related fi res. Installation of this fi replace must comply
with these clearances.
Combustible Mantels
A
F
B
B
E
Clearance: Dimension Measured From:
A: Mantel Height 3” (76mm) Minimum (Additional on this page)
B: Sidewall 0” (0mm) Side of installed front
3” (76mm) On P121-2 See-Thru
3” clearance opposite vent.
C: Ceiling 36” (914mm) Top of installed unit
D: Mantel Depth 12” (305mm) Maximum (Additional on this page)
E: Alcove Width See Parallel Wall Clearances.
F: Alcove Depth 36” (914mm) Front to back wall (Maximum)
Top of Hearth must not be higher than the base of the fi rebox.
Because of the extreme heat this fi replace emits, the mantel
clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.
Mantel Clearances
12
64810
12" (305mm)
Note: If the fi replace is installed
without the 3” Extension Trim,
the facing material must be
B
non combustible up to 8”
above the unit.
0
A
Mantel Clearances
Front 36” (914mm) 7” (178mm) 3” (76mm)
ABC
3 ½" (89mm)
Top of
Unit
0
2
Drywall
Header
Standoff
3” Extension Trim
C
Side View
Note: If desired a non-combustible mantel may be installed at a
lower height.
Note: Ensure the paint that is used on the mantel and the facing
is “heat resistant” or the paint may discolour.
70 June 2007 Regency Product Specifi cations Book
Gas Fireplaces
Regency Direct Vent System (Flex)
Horizontal Terminations Only
These venting systems, in combination with the P121/P131 Direct Vent
Gas Fireplace, have been tested and listed as a direct vent heater system
by Warnock Hersey. The location of the termination cap must conform
to the requirements in the Vent Terminal Locations diagram.
FPI Direct Vent (Flex) System Termination Kits include all the parts
needed to install the P42 using a fl exible vent.
FPI Kit # Length Contains:
#946-513 2 Feet 1) 6-5/8” fl exible liner (Kit length)
#946-515 4 Feet
#946-516 10 Feet
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex
installations.
3) Horizontal sections must be supported every 3 feet.
2) 4” fl exible liner (Kit length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) S.S. screws #8 x 1-1/2” drill point, (4)
P121-P131 Gas Fireplace
Snorkel Terminations
Snorkel Terminations:
For installations requiring a vertical rise on the exterior of the building,
14-inch and 36-inch tall Snorkel Terminations and the Riser Vent are
available. Follow the same installation procedures as used for standard
Horizontal Termination. NEVER install the snorkel upside down.
Riser Vent
Termination
Dura-Vent
Snorkel
Min. 12"*
(305mm)
Below Grade Snorkel Installation (Dura-Vent Only)
If the Snorkel Termination must be installed below grade, i.e. basement
application, proper drainage must be provided to prevent water from
entering the Snorkel Termination. Refer to Rigid Pipe Installation
instructions for details. Do not attempt to enclose the Snorkel within the
wall, or any other type of enclosure.
Min. 6-1/4"*
(159mm)
Gas Fireplaces
Alternate Horizontal
Termination Caps
Alternate:
Horizontal
Riser Vent
Terminal
Part# 640-530/P
Dura-Vent
Snorkel
Adequate
drainage
Gravel
(305mm)
Min. 12"*
Window
Well