Regency P121, P131-NG2, P131-LP2 User Manual

Page 1
H
I
J
K
Combustible
Material
3”
Extension
Trim
Non-Combustible
Material *
Top of
Unit
8”
Greyed out framing will not apply to all units.
Please refer to the manual.
L
Gas Fireplaces
P121-P131 Gas Fireplace
P121 - P121LC/RC - P131 Zero Clearance Direct Vent Gas Fireplace
Model P121/P131-NG2 P121/P131-LP2
Fuel Type Natural Gas Propane
Minimum Supply Pressure 5” W.C. (1.25 kPa) 12” W.C. (3.00 kPa)
Manifold Pressure - High 3.8” W.C. (0.95 kPa) 11” W.C. (2.74 kPa)
Manifold Pressure - Low 1.1” W.C. (0.27 kPa) 2.9” W.C. (0.72 kPa)
Orifi ce Size #31 DMS #50 DMS
Minimum Input 20,500 BTU/h (6.01 kW) 20,600 BTU/h (6.04 kW)
Vent Sizing 4” Inner / 6-5/8” Outer 4” Inner / 6-5/8” Outer
Approved Venting Systems
Flex Vent Systems: FPI AstroCap™ Flex Vent
Rigid Pipe Vent Systems: Simpson Dura-Vent® Direct Vent GS
M
N
Electrical
Inlet
BACK
P
Gas Line
Inlet
O
B
American Metal Products Ameri Vent Security Secure Vent® Selkirk Direct-Temp.
P121 See Thru P131 Pier
P121RC Right Corner P121LC Left Corner
G
F
Gas Fireplaces
D
C
41-1/2”
(1054mm)
44-1/2”
(1130mm)
26-13/16”
(681mm)
21-1/8”
(537mm)
4-3/4”
(121mm)
E
A
Unit Dimensions Description P121 P121LC/RC P131
A Front Face Width
B Total Firebox Width
C Front Face Height 36” (914mm) 36” (914mm) 36” (914mm)
D Height w/ Standoff 42” (1067mm) 42” (1067mm) 42” (1067mm)
E Unit Depth 25” (635mm)
F Top Offset Depth
G Inset to Standoff
If the provided 3” extension trim is not installed the P121(LC/RC)/ P131 must be installed with non-combustible facing up to 8” above the fi replace. Otherwise combustible facing may be used above the
43-1/2”
(1105mm)
46-1/4”
(1175mm)
21-1/8”
(537mm)
4-3/4”
(121mm)
extension trim.
Please refer to Page 11 (Exterior Vent Terminations)
for additional guidelines on vent locations.
41-1/2”
(1054mm)
44-1/2”
(1130mm)
25” (635mm)
21-1/8”
(537mm)
3” (76mm)
Framing Dimensions Description P121 P121LC/RC P131
H Framing Width
I** Framing Height **
J
** Framing Depth** 25” (635mm)**
K Vent Centerline Height 42-13/16” (1072mm)
L Framed Chase Ceiling 48-1/4” (1226mm)
M Electrical Inlet Height 2” (51mm) 2” (51mm) 2” (51mm)
N Electrical Inlet Inset
O Gas Connection Height
P Gas Connection Inset
46-3/4”
(1187mm)
42-1/2”
(1080mm)
11-3/8”
(289mm)
1-11/16” (43mm)
11-1/2”
(292mm)
45”
(1143mm)**
42-1/2”
(1080mm)
26-13/16”
(681mm)
13-5/16”
(338mm)
1-11/16”
(43mm)
11-1/2”
(292mm)
45”
(1143mm)**
42-1/2”
(1080mm)
25” (635mm)
11-3/8”
(289mm)
1-5/8” (41mm)
11-1/2”
(292mm)
**
** Refer to the manual for variations effected by fi nishing material
thickness.
69June 2007 Regency Product Specifi cations Book
Page 2
P121-P131 Gas Fireplace
Framing and Finishing
Gas Fireplaces
Parallel Wall Clearances
1) Determine the total thickness of facing material (e.g. drywall plus ceramic tiles) to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2” (13mm) to 1-¼” (32mm) thick.
2) Frame in the enclosure for the unit with framing material.
Gas Fireplaces
3) For exterior walls, insulate the enclosure to the same degree as the rest of the house, apply vapor barrier and drywall, as per local installation codes. (Do not insulate the fi replace itself.)
4) The top of the unit must not be closer than 36” (990mm) to the ceiling.
5) Combustible material may be brought up to the top and sides of the unit and be covered with ceramic tiles, bricks, rock or other suitable combustible finishing materials.
Note: The unit does not have to be completely enclosed in a chase. The clearance on top of the unit is 0” to the standoffs so combustible building materials can be laid directly on top of the standoffs. You must maintain proper clearances from the vent to combustible materials (See Below).
6) Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.
Clearance Requirements
D
C
Unless otherwise stated the clearances listed below are Minimum distances to combustible materials. Unit pictured is a P131
Parallel Wall Clearances P121(LC/RC)/131
Min distance from glass to a parallel wall 36” (914mm)
36"min.
(914mm)
36"min. (914mm)
36"min.
(914mm)
Vent Clearances Clearance Dimension
Horizontal - Top 2-1/2” (64mm)
Horizontal - Side 1-1/2” (38mm)
Horizontal - Bottom 1-1/2” (38mm)
Vertical 1-1/4” (32mm)
WARNING
Failure to maintain required clearances is a major cause of chimney related fi res. Installation of this fi replace must comply with these clearances.
Combustible Mantels
A
F
B
B
E
Clearance: Dimension Measured From:
A: Mantel Height 3” (76mm) Minimum (Additional on this page)
B: Sidewall 0” (0mm) Side of installed front
3” (76mm) On P121-2 See-Thru
3” clearance opposite vent.
C: Ceiling 36” (914mm) Top of installed unit
D: Mantel Depth 12” (305mm) Maximum (Additional on this page)
E: Alcove Width See Parallel Wall Clearances.
F: Alcove Depth 36” (914mm) Front to back wall (Maximum)
Top of Hearth must not be higher than the base of the fi rebox.
Because of the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed anywhere in the shaded area or higher.
Mantel Clearances
12
64810
12" (305mm)
Note: If the fi replace is installed without the 3” Extension Trim, the facing material must be
B
non combustible up to 8” above the unit.
0
A
Mantel Clearances
Front 36” (914mm) 7” (178mm) 3” (76mm)
ABC
3 ½" (89mm)
Top of Unit
0
2
Drywall
Header
Standoff
3” Extension Trim
C
Side View
Note: If desired a non-combustible mantel may be installed at a
lower height.
Note: Ensure the paint that is used on the mantel and the facing
is “heat resistant” or the paint may discolour.
70 June 2007 Regency Product Specifi cations Book
Page 3
Gas Fireplaces
Regency Direct Vent System (Flex)
Horizontal Terminations Only
These venting systems, in combination with the P121/P131 Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram.
FPI Direct Vent (Flex) System Termination Kits include all the parts needed to install the P42 using a fl exible vent.
FPI Kit # Length Contains:
#946-513 2 Feet 1) 6-5/8” fl exible liner (Kit length)
#946-515 4 Feet
#946-516 10 Feet
Notes:
1) Liner sections should be continuous without any joints or seams.
2) Only Flex pipe purchased from Regency may be used for Flex installations.
3) Horizontal sections must be supported every 3 feet.
2) 4” fl exible liner (Kit length)
3) spring spacers (3)
4) thimble (2)
5) AstroCap termination cap (1)
6) screws (12)
7) tube of Mill Pac (1)
8) plated screws (8)
9) S.S. screws #8 x 1-1/2” drill point, (4)
P121-P131 Gas Fireplace
Snorkel Terminations
Snorkel Terminations:
For installations requiring a vertical rise on the exterior of the building, 14-inch and 36-inch tall Snorkel Terminations and the Riser Vent are available. Follow the same installation procedures as used for standard Horizontal Termination. NEVER install the snorkel upside down.
Riser Vent
Termination
Dura-Vent
Snorkel
Min. 12"* (305mm)
Below Grade Snorkel Installation (Dura-Vent Only)
If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Rigid Pipe Installation instructions for details. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure.
Min. 6-1/4"*
(159mm)
Gas Fireplaces
Alternate Horizontal
Termination Caps
Alternate: Horizontal Riser Vent Terminal Part# 640-530/P
Dura-Vent
Snorkel
Adequate
drainage
Gravel
(305mm)
Min. 12"*
Window
Well
71June 2007 Regency Product Specifi cations Book
Page 4
P121-P131 Gas Fireplace
Rigid Pipe Venting
Horizontal or Vertical Terminations
Storm Collar
Gas Fireplaces
Flashing
943 or 943S
Ceiling Firestop
(Part # 963)
Vertical
Terminal
Part # 953
Pipe Length
Adj.Pipe Length
o
90 Elbow
Pipe
Length
o
45 Elbow
Rigid Pipe Adapter
(Part #510-994)
Vinyl Siding
Standoff (Optional)
(Part #950)
11" - 14-5/8"
Horizontal Termination Cap Part# 946-523/P
Wall Thimble
(Part # 942)
(Required in
Canada)
Alternate Horizontal
Termination Caps
Alternate: Horizontal Riser Vent Terminal Part# 640-530/P
Gas Fireplaces
Vertical Venting with One (1) 90° Elbow
Two 45° elbows = One 90° elbow
Option V H Maximum total pipe: length, of
A) 1’ Min. 2’ Max.
B) 2’ Min. 4’ Max.
C) 3’ Min. 6’ Max.
D) 4’ Min. 8’ Max.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 8 feet.
Minimum of 1 foot between 90° elbows is required.
Venting Arrangements - Vertical Terminations
Rigid Pipe System
(Propane & Natural Gas)
The P121 /131 is approved for a maximum 35 ft. straight vertical, with
Rigid Pipe vent systems for Propane and Natural Gas.
Vent must be supported at offsets.
Horizontal sections must be supported every 3 feet.
• Firestops are required at each floor level and whenever passing through a wall.
Maintain clearances to combustible materials.
Minimum of 1’ pipe section between elbows.
Note: Must use optional fl ue adapter when using Rigid Pipe (Part
# 510-994).
Minimum 6' 6”(2.0m)
Maximum 35'(10.7m)
When installing this unit vertically, the 45˚ elbow when installed in conjunction with the Rigid Pipe Adapter will protrude past the unit 1-½” (38mm) when measured from the rear standoffs.
Note: A 1-¼” (32mm) clearance from the elbow must also be maintained.
o
45 Elbow
Rigid Pipe
Adapter
1-1/2” (38mm)
IMPORTANT
45° Elbow
Rigid Pipe Adapter
Part # 510-994
72 June 2007 Regency Product Specifi cations Book
Page 5
Gas Fireplaces
Vertical Venting with Two (2) 90° Elbows
- Initial vertical section.
Two 45° elbows = One 90° elbow
P121-P131 Gas Fireplace
Vertical Venting with Three (3) 90° Elbows - Initial vertical section.
Two 45° elbows = One 90° elbow
Gas Fireplaces
Option V+ V1 H Maximum total pipe: length, of
A) 1’ Min. 4’ Max.
B) 2’ Min. 6’ Max.
C) 3’ Min. 9’ Max.
D) 4’ Min. 12’ Max.
E) 5’ Min. 15’ Max.
E) 6’ Min. 17’ Max.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 17 feet.
Minimum of 1 foot between 90° elbows is required.
Vertical Venting with Two (2) 90° Elbows
- Initial horizontal section.
Two 45° elbows = One 90° elbow
Option H + H1 V Maximum total pipe: length, of
A) 2’ Max. 1’ Min.
B) 4’ Max. 2’ Min.
C) 6’ Max. 3’ Min.
D) 8’ Max. 4’ Min.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 8 feet.
Minimum of 1 foot between 90° elbows is required.
Option V+ V1 H + H1 Maximum total pipe: length, of
A) 2’ Min. 3’ Max.
B) 3’ Min. 6’ Max.
C) 4’ Min. 9’ Max.
D) 5’ Min. 12’ Max.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 12 feet.
Minimum of 1 foot between 90° elbows is required.
Vertical Venting with Three (3) 90° Elbows - Initial horizontal section.
Two 45° elbows = One 90° elbow
Option V+ V1 H H + H1 Maximum total pipe: length, of
A) 2’ Min. 1’ Max. 2’ Max.
B) 3’ Min. 4’ Max. 5’ Max.
C) 4’ Min. 6’ Max. 8’ Max.
D) 5’ Min. 8’ Max. 12’ Max.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 12 feet.
Minimum of 1 foot between 90° elbows is required.
73June 2007 Regency Product Specifi cations Book
Page 6
P121-P131 Gas Fireplace
Venting Arrangements - Horizontal
Terminations
This diagram shows allowable venting confi gurations using one 45°.
Note: Must use optional fl ue adapter (Part # 770-994) when using
Gas Fireplaces
Rigid Pipe.
Maintain clearances to combustibles.
Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
A vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes.
Note: FPI Direct Vent System (Flex) is only approved for horizontal
terminations.
Gas Fireplaces
Horizontal Venting with One (1) 90° Elbow
Two 45° elbows = One 90° elbow
Option V H Maximum total pipe: length, of
A) 1’ Min. 3’ Max.
B) 2’ Min. 6’ Max.
C) 3’ Min. 9’ Max.
D) 4’ Min. 12’ Max.
E) 5’ Min. 15’ Max.
F) 6’ Min. 17’ Max.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 17 feet.
Minimum of 1 foot between 90° elbows is required.
74 June 2007 Regency Product Specifi cations Book
Page 7
Gas Fireplaces
Horizontal Venting with Two (2) 90° Elbows - Initial vertical section.
Two 45° elbows = One 90° elbow
P121-P131 Gas Fireplace
Horizontal Venting with Three (3) 90° Elbows - Initial vertical section.
Two 45° elbows = One 90° elbow
Gas Fireplaces
Option V H+ H1 Maximum total pipe: length, of
A) 1’ Min. 2’ Max.
B) 2’ Min. 5’ Max.
C) 3’ Min. 8’ Max.
D) 4’ Min. 11’ Max.
E) 5’ Min. 14’ Max.
F) 6’ Min. 15’ Max.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 15 feet.
Minimum of 1 foot between 90° elbows is required.
Option V+ V1 H + H1 Maximum total pipe: length,
A) 2’ Min. 3’ Max.
B) 3’ Min. 6’ Max.
C) 4’ Min. 9’ Max.
D) 5’ Min. 12’ Max.
of all sections, must not exceed 37 feet. Total horizontal sections must not exceed 12 feet.
Minimum of 1 foot between 90° elbows is required.
Horizontal Venting with Two (2) 90° Elbows - Initial horizontal section.
Two 45° elbows = One 90° elbow
Option H V H + H1 Maximum total pipe: length, of
A) 1’ Max. 1’ Min. 3’ Max.
B) 3’ Max. 2’ Min. 6’ Max.
C) 5’ Max. 3’ Min. 9’ Max.
D) 8’ Max. 5’ Min. 12’ Max.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 12 feet.
Minimum of 1 foot between 90° elbows is required.
Horizontal Venting with Three (3) 90° Elbows - Initial horizontal section.
Two 45° elbows = One 90° elbow
Option H V H + H1 + H2 Maximum total pipe: length, of
A) 1’ Max. 2’ Min. 3’ Max.
B) 3’ Max. 3’ Min. 6’ Max.
C) 5’ Max. 4’ Min. 9’ Max.
F) 7’ Max. 5’ Min. 12’ Max.
all sections, must not exceed 37 feet. Total horizontal sections must not exceed 12 feet.
Minimum of 1 foot between 90° elbows is required.
75June 2007 Regency Product Specifi cations Book