Regal ECS401, ECS402 Instruction Bulletin

REGAL
INSTRUCTION BULLETIN ECS 401/402
1044 SE Dixie Cutoff Road, Stuart, Florida 34994 USA
Phone: (772) 288-4854 Fax: (772) 287-3238
www.regalchlorinators.com Email: regal@regalchlorinators.com
ELECTRONIC CYLINDER SCALES
Models ECS401 Single Cylinder Scales
and ECS402 Dual Cylinder Scales
INTRODUCTION
REGAL Series ECS400 single and dual cylinder electronic scales are designed for use in multiple water treatment applications to monitor the chemical weight of Chlorine, Sulfur Dioxide and Ammonia supplied in 150 lb. cylinders. The scales are an
IMPORTANT NOTES
1. All software including design, appearance, algorithms, and source codes are copyrighted and owned by Chlorinators Incorporated.
2. The entire contents of this manual MUST be read and under­stood prior to installing and operating this equipment.
3. DO NOT discard this instruction manual upon completion of the installa tion as this manual contains information essential to the safe handling, operation, and maintenance of this equipment.
WARNINGS
1. This equipment is suitable for use only with the gases specified.
DO NOT USE THIS EQUIPMENT WITH OTHER GASES. Such use can result in failures having hazardous consequences.
2. This equipment is designed FOR VACUUM SERVICE ONLY.
3. To insure proper and safe operation of this equipment, use only
REGAL parts. The use of non-REGAL parts can result in equip­ment failures having hazardous consequences and voids the REGAL warranty and insurance coverage.
4. Maintenance should be performed by competent personnel
familiar with this type of equipment, such as Chlorinators Incorporated themselves.
5. It is essential that all external wiring be done exactly as shown
on the wiring diagrams depicted in this manual. Incorrect wiring or improper grounding of this equipment WILL cause improper operation and presents a safety hazard.
6. Field wiring MUST conform to national and local electrical codes.
essential part of all REGAL Gas Feed Systems, providing the user with instantaneous Gross and Net weight readings. The two models available are the ECS401 for single cylinder applications and the ECS402 for dual cylinders.
4. Additional instruction manuals are available at nominal cost from Chlorinators Incorporated.
5. Plastic pipe or tubing connector fittings may be broken or damaged if tightened excessively. HAND TIGHTEN ONLY.
6. For optimum operation, the installation should be indoors so that the minimum and maximum temperature limitations as listed in the “TECHNICAL SPECIFICATIONS” section of this manual are not exceeded.
7. DISC ONNECT POW ER BEFORE removin g the cover or servicing this equipment.
8. ALWAYS make sure that the cover is in place and securely fastened to prevent the entry of moisture, water, or corrosive gases and also to eliminate the potential for electric shock.
9. Any equipment powered by AC line voltage presents a potential shock hazard. Installation and servicing of this equipment should only be attempted by qualified electronics technicians.
10. This non-metallic enclosure DOES NOT automatically provide grounding between the conduit connections. Grounding MUST be provided as part of the installation.
11. Damage to the circuit boards or internal components incurred by drilling the enclosure for field wiring or connecting power lines to low voltage signal terminals voids the warranty.
12. Changing parameter settings and selections WILL affect the operation of this equipment. If unsure, consult Chlorinators Incorporated BEFORE changing parameters or selections.
CHLORINATORS INCORPORATED ONE (1)
YEAR LIMITED WARRANTY
Chlorinators Incorporated (hereinafter called “C.I.”) sets forth the follow ing warranties with respect to its REGAL Model ECS Electronic Cylinder Scales. This war ranty does not apply to the purchase of spare parts or other services performed by C.I. or its authorized dealers. This represents the entire agreement between C.I. and Buyer (also referred to as “end-user”) and shall apply unless modified in writing and signed by a C.I. Officer, and this warranty and its intended terms shall supersede any prior negoti­ations, correspondence, understand ings, or agreements, written or oral. The Buyer agrees to and accepts all terms of this warranty by its contracting for or acceptance of C.I.’s prod ucts, and forms or other documents or statements issued by Buyer or any other person shall not modify or otherwise affect any of the following terms. Buyer should be aware that reseller must rely entirely upon Chlo rinators Incorporated’s warranties, or assume their own responsibility.
The following states C.I.’s entire warranty and represents Buyer’s exclu sive remedy with respect to its product. Such warranties are expressly given in lieu of any other warranty, expressed or implied, including but not limited to those of merchantability and fitness for a particular purpose. This expressed warranty or any other warranty implied by law shall not cover defects due to accident, improper use, or non-compliance with C.I.’s operating and main tenance, assembly, installation manual and instructions.
Recommendations and advice as to specifications, capabilities, design, in stallation, engineering, application, and use of products are provided as an accommodation and are intended only as suggestions. C.I. assumes no lia bility for such recommendations and advice and they are not to be con strued as constituting any warranty, expressed or implied.
Not withstanding the foregoing, C.I. shall not be liable to Buyer for damages, including personal injury or death to any person or persons, or claims of any kind by a third party or property damage, loss of business or profits. In no event shall C.I. be liable to Buyer for consequential or acciden­tal damages of any kind, even if C.I. was aware of the possibility of such damages. There are no remedies except those set forth. Further, that there are no other authorized warranty repair facilities other than those at the Chlorinators Incorporated factory in Stuart, Florida.
EXCLUSIONS
The following are considered external environmental factors beyond the control of C.I., and which may cause damage and/or need for service which will be specifically excluded from this warranty (i.e., not a material defect in components and workmanship occurring in the course of manufacture).
1. Damage by extraneous causes such as fire, water, lightning, chemical or galvanic attack, etc.
2. Damage to the circuit boards or internal components incurred by drilling the enclosure for field wiring.
3. Damage due to the connection of power lines to low voltage signal terminals.
4. Physical damage due to force, dropping, misuse or other abuse.
5. Use other tha n that as describ ed i n this Instruct io n Manual (misapplication).
6. Repair by someone other than Chlorinators Incorporated.
7. Improperly installed.
8. This warranty DOES NOT cover wear items subject to periodic replacement such as o-rings, gaskets, seals and packing.
The exclusions listed above are provided for purposes of clarification, and are not intended to, in any way, limit or eliminate other possible exclu sions.
TERMS OF WARRANTY
C.I. warrants its REGAL Model ECS Scales for a period of one (1) year from date of shipment from C.I. Date of shipment from the factory shall be determined solely on the basis of the serial code sticker inside the monitor enclosure. The serial number contains a date code. All serial numbers are also registered by Chlorinators Incorporated as to date of shipment, model number and billing name. If the serial number is missing, defaced, changed, or in any way ren dered un readable, Chlorinators Incorporated shall, at its option, have the right to declare the warranty void. If the serial number does not match the regis tered model number as to, but not limited to, such items as maximum chlorine feed rate, the same option shall be applicable.
The warranty shall apply against material defects in components and work manship occurring in the course of manufacture. Buyer’s sole remedy for breach of said warranty shall be, at C.I.’s option, either repair or replace ment of any unit which is received by C.I. at its plant in Stuart, Florida (shipping charges prepaid by buyer), within the time period set forth above and which is found by C.I. to be defective by reason of manufacture.
NO OTHER WARRANTIES
Unless otherwise explicitly agreed in writing, and signed by a C.I. officer, it is understood that this is the only written warranty given by C.I. for the systems and components stated.
The dealers or representatives of C.I. may not make verbal representations that add, modify or change the written warranties contained herein or change the extent and nature of C.I.’s liability. In no event shall C.I. be liable for direct, consequential, special, incidental or punitive damages of any kind with respect to the product, including but not limited to those which may allegedly arise out of breach of warran ty, breach of contract, negligence, strict liability, or any other law, gov ernmental regulation, or court decision, except as provided herein.
2
GENERAL INFORMATION
SPECIFICATIONS
The REGAL Single Cylinder (ECS401) and Dual Cylinder (ECS402) Electronic Scales come equipped with the following standard features:
• Easy to read LCD digital display(s).
• LED indicators for low and empty weight conditions.
• Auto Zero feature with back-up pushbutton.
• 4-20 milliamp analog output circuits for data recording and SCADA interface.
• Stainless steel electronic strain gage load cells.
• Low profile base(s) for easy changing of cylinders.
• Solid PVC platforms and stainless steel hardware.
• Cylinder Stop(s) for proper positioning of cylinders.
• Accommodates Chlorine, Sulfur Dioxide and Ammonia cylinders.
• Wall mount brackets with cylinder restraining chains.
• Low weight alarm relay circuits.
• Displays "Gross" or "Net" cylinder weight with the push of a button.
Capacity: 300 lbs./base
ylinder Size: 14" Dia. Max.
C
verload Capacity: 150%
O
emperature Rating: 32° to 122° F
T
esolution: 0.2 lbs.
R
ccuracy: ±1% Full Scale
A
ushbuttons: 3 or 4 tactile-dome
P
pdates/second: Four
U
Display
Indicators: LED (three per channel)
Digital Display: LCD
Auto Zero Maintenance: ±4 Graduations
Load Cell Excitation: 5 VDC
Power: 115V/230V AC
Power Consumption: 10 Watts
Milliamp Output: 4-20mA (500 Ohms)
Fuse: 1/4 Amp (115V), 1/8 Amp (230V)
Low Level Alarm Relays (5 Amp or Better)
Form: C (N/O & N/C)
Function: Low Weight Alarm
3