RefPlus LSA 0400-1, LSA 0540-1, LSA 0650-1, LSA 0900-1, LSA 1100-1 Installation, Operation & Maintenance Instructions Manual

...
1
1
1
WALK-IN COOLERS
SERIES LS-LP-LA-LV
& MAINTENANCE INSTRUCTIONS
INSTALLATION, OPERATION
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
2
INTRODUCTION . . . . . . . . . . . . . . . . . . . 3
INSTALLATION S
TEP 1 – COMPLETE
PRE-I
NSTALLATION CHECKS. . . 3
S
TEP 2 – LOCATION
. . . . . . . . . . . . . . . . . . 3
S
TEP 3 – MOUNTING
. . . . . . . . . . . . . . . . . . 3
S
TEP 4 – CONNECT
DRAIN L
INE . . . . . . . . . . . 3
S
TEP 5 – REFRIGERANT
CONNECTIONS . . . . . . . . 4
S
TEP 6 – EXPANSION
VALVE
CONNECTION . . . . . . 4
S
TEP 7 – WIRING
. . . . . . . . . . . . . . . . . . . 4
START-UP L
EAK TESTING AND EVACUATION . . . . . . . . . . . . 4
F
AN MOTOR . . . . . . . . . . . . . . . . . . . . . . . 4
F
AN DELAY DEFROST TERMINATION CONTROL . . . . . 4
F
AN DELAY DRAIN PAN CONTROL . . . . . . . . . . . 4
C
HECK SUPERHEAT. . . . . . . . . . . . . . . . . . . . 4
D
EFROST SYSTEM . . . . . . . . . . . . . . . . . . . . 5
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . 5
I
NSPECTION. . . . . . . . . . . . . . . . . . . . . . . . 5
C
LEANING. . . . . . . . . . . . . . . . . . . . . . . . . 5
UNIT SPECIFICATIONS . . . . . . . . . . . . . . . 6
T
ECHNICAL
DATA. . . . . . . . . . . . . . . . . . . . . 7
T
ECHNICAL
DATA (CONT
D) . . . . . . . . . . . . . . . 8
R
EFRIGERATION
SYSTEM
START
-UP CHECK LIST
. . . . . . . . . . . . . . . . . 10
WARRANTIES . . . . . . . . . . . . . . . . . . . . 11
1 = 120/1/60 2 = 240/1/60 5 = 208-240/3/60 8 = 600/3/60 9 = 480/3/60
Product Generation
Unit Capacity @ 10
o
F T.D. 22,400 Btu/hr
NOMENCLATURE
CONTENTS
L = Low
S = Silhouette P = Profile A=Air
A = Air Defrost E = Electric Defrost G = Reverse Cycle Hot Gas Defrost
W/Electric Heated Drain Pan
H = Three Pipe Hot Gas Defrost
W/Electric Heated Drain Pan R = Reverse Cycle Hot Gas Defrost T = Three Pipe Hot Gas Defrost
L S A 224 1 — 1
INSTALLATION
STEP 1 ­COMPLETE PRE-INSTALLATION CHECKS
Examine for damage incurred during shipment. File a claim immediately with transit company if damage is found.Verify that the nameplate electrical requirements match the available power supply. Check the shipment for completeness.
STEP 2 - LOCATION
All unit coolers should be installed flush against the ceiling. The unit cooler must be level in all directions to ensure proper drainage of condensate. Be sure there is sufficient clearance between the ceiling and unit cooler to allow for cleaning the unit cooler top.
When deciding on the location of the unit cooler, consider the following:
• Location of aisle racks
• Location relative to compressor for minimum pipe runs
• Location of condensate drains for minimum run
• The air pattern must cover the entire room
• Never locate unit coolers over doors or door openings
• Allow sufficient space between rear of unit cooler and wall to permit free return of air
SAFETY CONSIDERATIONS
Installing, star ting up, and servicing equipment can be hazardous due to system pressures, electrical components and equipment location (roofs, elevated structures, etc.). Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
When working on the equipment, obser ve precautions in the literature and on the tags, stickers, and labels attached to the equipment.
Follow all safety codes.Wear safety glasses and work gloves. Keep quenching cloths and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
INTRODUCTION
These instructions describe installation, start-up, and service for the RefPlus refrigeration unit coolers.
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
3
WARNING
Before installation, always check to be sure main power to systems is OFF. Electrical shock can cause personal injury or death.
NOTE
Avoid placement of the unit cooler directly above doors and door openings where low temperature is being maintained. Position the unit cooler so the discharge air blows above the doors. Install a baffle if door extends above the blower level.
NOTE
Unit coolers with electric defrost require a 20 in. clearance at the left end when facing the fans to allow removal of defrost heaters.
NOTICE
The unit cooler must be mounted level for proper condensate draining. Adequate support must be provided to hold the weight of the unit cooler.
Note: The area above the unit must be sealed and accessible to facilitate hand cleaning without the use of tools in order to comply with National Sanitation Foundation (NSF) Standard 7.
S
TEP 3 - MOUNTING
Most unit coolers can be mounted with either bolts or rod hangers. Use 5/16 in. bolts and washers for unit coolers weighing up to 250 pounds. Use 3/8 in. bolts and washers for unit coolers weighing from 250 to 500 pounds. For unit coolers over 500 pounds, use 5/8 in. bolts and washers .
STEP 4 - CONNECT DRAIN LINE
For all unit coolers, a drain line union is recommend­ed for ease of installation and future servicing and should be located in close proximity to the drain pan.
LS, LP & LA UNIT COOLERS – A 7/8 in. ID removable drain fitting is supplied with each unit. Follow steps 1 through 4 above for connecting the drain line.
FOR ALL UNIT COOLERS, connect the drain line as follows:
1. Replace the rubber gasket to prevent
condensate leakage.
2. Locate the union as close to the drain pan
as possible.
3. Using two wrenches, tighten the drain fitting.
The use of two wrenches prevents the drain fitting from twisting and damaging the unit cooler.
4. Sharply pitch the drain line and exit it through
the cooler with a short run.
5. Insulate and seal the drain line where it
passes through the wall.
6. Locate the drain traps in warm ambient air
temperature to prevent freeze up.
NOTE
If the cooler temperature is below 32ºF, a field supplied drain line heater (15 W per foot) may be required.When installing the heater, be sure to avoid overlapping.
LS UNIT COOLERS – These unit coolers should be located in a position where the air discharge is toward the door. The coil face on the unit cooler should be least 7 in. away from the wall.
LP & LA UNIT COOLERS – These unit coolers should be located in the center of the cooler with air discharge toward the back or side wall.
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
4
FAN DELAY DEFROST TERMINATION CONTROL
This control located on the coil plate senses the coil temperature. To provide fan delay, the defrost thermostat must be turned off.
1. Set thermostat between 20ºF and 30ºF
or above.
2. Adjust defrost timer up to maximum
of 45 minutes.
3. Set the thermostat between 55 to 60ºF
to defrost unit coolers operating between –40 to –20ºF. To defrost unit coolers operating between –10 to 10ºF, set the thermostat between 60 to 65ºF.
F
AN DELAY DRAIN PAN CONTROL
The fan delay drain pan control senses the general coil temperature.
• With temperature rise, the fan delay thermostat de-energizes the fan and energizes the electric pan heaters.
• After defrost cycle, the coil temperature drops and the fan delay thermostat energizes the motor and de-energizes the heaters.
• Defrost timer must be set long enough to completely melt the ice in the unit cooler. Set the thermostat at 20 to 25ºF and the differential at minimum.
CHECK SUPERHEAT
After the temperature has reached the desired temperature, the unit cooler superheat should be checked and adjustments made if necessary. Generally, systems with a design temperature difference (TD) of 10ºF should have a superheat value of 6 to 10ºF for maximum efficiency. For systems operating at higher TD, the superheat can be adjusted to 12 to 15ºF as required.
IMPORTANT
After correcting a faulty defrost cycle, it is essential that the coil, drain pan and unit cooler be free and clear of ice before placing the unit cooler back on automatic operation.
To ensure unit cooler performance, the expansion valve must be set at the proper superheat and at the lowest temperature in which the system is expected to operate.
STEP 7 - WIRING
All systems wiring must be in compliance with all applicable local and national codes.
All internal wiring of fan motors, tubular heaters and combination defrost termination fan delay control have been factory connected. All wiring connections terminate on a single terminal block in the wiring compartment and are clearly labeled.
START-UP
L
EAK TESTING AND EVACUATION
Leak testing and evacuation must be done in accordance with local and national codes.
Once all refrigerant connections are made, leak test all joints before charging the system with refrigerant. After leak testing, all moisture and non-condensable gas must be evacuated from the system. Attach high vacuum line pump and gauge on both high and low pressure sides of the system. A minimum vacuum level of 100 microns is required to effectively remove moisture.
Be sure all valves such as compressor, hot gas , receiver, and liquid solenoid valves are open. Break the vacuum in the system with the refrigerant to be used. Always charge the refrigerant into the system through a new 16 cu. in drier (field supplied) in the charging manifold line.
F
AN MOTOR
The fan motor may restart on automatic thermal protection if the coils are frozen. The fan motor may cycle if the coil is blocked. Check the supply voltage at the motor leads if motor is inoperable.
CAUTION
Before starting unit cooler, be sure wire fan guards are secured in place over each fan.
IMPORTANT
The use of a calibrated pressure gauge and regulator must always be used with nitrogen gas cylinders.
Drain traps on low temperature unit coolers must be outside of refrigerated enclosures. In the instance where traps are subject to freezing temperatures, wrap the traps with heat tape and insulation. Always trap drain lines individually to prevent vapor migration.
S
TEP 5 - REFRIGERANT CONNECTIONS
All refrigerant system components must be installed in accordance with applicable local and national codes using proper engineering practices.
Use top quality refrigeration tubing that is internally free of dirt, humidity or other contaminants. Unsealed tubing should not be used. Long radius elbows are recommended.
Dry nitrogen must be swept through the lines while joints are brazed to avoid oxidation and carbon deposits.
All external piping must be well supported. The unit cooler will not support external piping or valves.
If the condition arises where the suction line must be raised to a point higher than the suction connection on the unit cooler, a suction line trap must be installed on the unit cooler.
Horizontal suction lines should slope away from the evaporator toward the compressor. Leak check and evacuate the system using a two-stage deep vacuum pump.
S
TEP 6 - EXPANSION VALVE CONNECTION
All unit coolers are supplied with a 1/2 in. OD sweat expansion valve connection. Expansion valves are field supplied.
LS, LP & LA unit coolers require the use of an externally equalized expansion valve and are provided with a 1/4 in. OD equalizer line.
Check the operation of the expansion valve after the system has reached the desired cooler temperature. If the coil is not receiving enough refrigerant, reduce the superheat setting on the expansion valve.
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
DEFROST SYSTEM
AIR DEFROST UNIT COOLERS: Fan motors run
continuously and a defrost time clock or low-pressure setting stops the compressor when defrost is required.
E
LECTRIC DEFROST UNIT COOLER
: A time clock
starts the defrost process by stopping the fan and energizing the heaters.When the defrost thermostat resets the time clock, it de-energizes the heaters and re-starts the fan motors.
R
EVERSE CYCLE HOT GAS DEFROST UNIT
C
OOLERS: Reverse cycle defrost systems introduce
compressor discharge gas through the suction line during defrost. The amount of gas introduced is controlled by a solenoid bypass valve and a gas defrost time clock.
Condensed refrigerant is relieved through a check valve. The check valve bypasses the expansion valve leading to the liquid line which has reduced pressure. The drain pan is warmed by the entering hot gas to avoid freezing. Defrost is initiated and terminated by the time clock.
NOTE
Minimum compressor suction superheat of 20ºF may override these recommendations on some systems with short line runs.
NOTE
The unit cooler must not be in operation more than 16 hours per day.
NOTE
Using a suction to liquid heat exchanger is recommended.
IMPORTANT
Do not use alkaline or acidic solutions; they will damage the coils. Remove the fan guard to clean the inner face of the fan coil.
NOTE
A field-installed pressure regulating valve may be required on low temperature systems to control compressor crankcase pressure.
NOTE
This method will yield accurate results as long as the pressure drop through the unit cooler coil is low.
WARNING
If the condensing unit does not have flooded condenser head pressure control, then the condensing unit must have discharge pressure above the equivalent 105ºF condensing pressure.
T
HREE PIPE HOT GAS DEFROST UNIT
COOLERS: During defrost, compressor discharge
gas is introduced in a separate hot gas line. The amount of gas introduced is controlled by a solenoid bypass valve and a gas defrost time clock. To avoid excessive accumulation of liquid in the suction accumulator, a heat exchanger is recommend­ed. The drain pan is warmed by the entering hot gas to avoid freezing. The time clock cycles fan motors, liquid and hot gas solenoids.
SERVICE
INSPECTION
After one day of operation, check for any vibration in the unit cooler. All unit coolers should be checked at least once a month for proper defrosting. It may be necessary to periodically change the number of defrost cycles or adjust the duration of defrost.
Under normal usage conditions, proper unit cooler maintenance should be done every six months to include the following:
1. Check all wiring and insulators.
2. Check and tighten all electrical connections.
3. Inspect contactors for proper operation and
for worn contact points.
4. Check all fan motors. Tighten motor mount
bolts/nuts and tighten fan set screws.
5. Clean condenser coil surface.
6. Check refrigerant and oil level in the system.
7. Check operation of the control system ensuring
all safety controls are operating properly.
8. Check all defrost controls are functioning
properly.
9. Clean the unit cooler coil surface.
10. Clean the drain pan and check the drain pan
drain line for proper drainage.
11. Check drain line heater for proper operation,
cuts and abrasions.
12. Check and tighten all flare connections .
See troubleshooting chart for troubleshooting information.
To properly determine the superheat of the unit cooler, follow the steps below:
1. Measure the temperature of the suction line
at the point where the bulb is secured.
2. Determine the suction pressure in the suction
line at the bulb location by using one of the following methods :
A
)
Placing a gauge in the external equalized line.
B) Placing a gauge directly in the suction line
near the unit cooler or directly in the suction header of the unit cooler.
3. Convert the pressure reading to saturated unit
cooler temperature by using a temperature pressure table. See table # 1.
4. Subtract the saturated temperature from the
actual suction line temperature reading. The difference is superheat.
An alternate method to determine superheat of the unit cooler can be used :
1. Measure the temperature of the suction line at
the point where the bulb is secured (outlet).
2. Measure the temperature of one of the distrib-
utor tubes close to the unit cooler coil (inlet).
3. Subtract the inlet temperature from the outlet
temperature. The difference is superheat.
C
LEANING
The unit cooler should be checked periodically for dirt accumulation. Grease and dust should be removed from the fan, fan guards, and drain pan.
Occasional cleaning of finned surfaces can be done by dusting the fins and then cleaning with a mild detergent and warm water spray.Always pressure clean in reverse of the air flow.
UNIT SPECIFICATIONS
F
OR ALL UNITS:
- For R-134a or R-22 refrigerant charge, multiply R-404 by 1.09.
- Operating charge is based on 30% liquid and 70% vapor at 25ºF suction.
LS S
ERIES
:
- Use LSR model for hot gas reverse cycle defrosts.
- Use LST model for hot gas three pipe defrost with gas drain pan.
- Air throw for LS Series:25 to 35 feet.
LP S
ERIES:
- Use LPG model for hot gas reverse cycle defrost with electric drain pan.
- Use LPH model for hot gas three pipe defrost with electrical drain pan.
- Air throw for LP Series:12 to 18 feet on each side.
LA SERIES:
- Use LAG model for hot gas reverse cycle defrost with electric drain pan.
- Use LAH model for hot gas three pipe defrost with electric drain pan.
- Air throw for LA Series:10 to 15 feet on each side.
TROUBLESHOOTING CHART
SYMPTOMS POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS
Fan(s) will not operate 1. Main switch open 1. Close switch
2. Blown fuses 2. Replace fuses . Check for short circuits
3. Defective motor or overload conditions.
4. Defective timer or defrost thermostat 3. Replace motor
5. Unit in defrost cycle 4. Replace defective component
6. Coil does not get cold enough to reset thermostat 5. Wait for completion of cycle
6. Adjust fan delay setting of thermostat
Room temperature too high 1. Room thermostat set too high 1. Adjust thermostat
2. Superheat too high 2. Adjust thermal expansion valve
3. System low on refrigerant 3. Add refrigerant
4. Coil iced-up 4. Manually defrost coil and check defrost controls for malfunctions
Ice accumulating on ceiling 1. Defrost duration is too long 1. Adjust defrost termination thermostat around evaporator and/or on 2. Fan delay not delaying fans after defrost period 2. Defective defrost thermostat or not adjusted proper ly fan guards, venturi, or blades 3. Defective defrost thermostat or timer 3. Replace defective components
4. Too many defrosts 4. Reduce number of defrost
Coil not clearing of frost 1. Coil temperature not getting above 1. Check heater operation during defrost cycle freezing point during defrost 2. Adjust timer for more defrost cycles
2. Not enough defrost cycles per day 3. Adjust defrost thermostat or timer for longer cycle
3. Defrost cycle too short 4. Replace defective component
4. Defective timer or defrost thermostat
Ice accumulating in drain pan 1. Defective heater 1. Replace heater
2. Unit not pitched properly 2. Check pitch and adjust if necessary
3. Drain line plugged 3. Clean drain line
4. Defective drain line heater 4. Replace heater
5. Defective timer or thermostat 5. Replace defective component
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
6
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
7
DRAIN FITTING KIT
All Models
DFK-2
DEFROST CONTROL
All Models R&T G&H E
TERMINAL BLOCK
All Models
REM 0004
WIRING HARNESS
All Models
Note: All electric defrost units (E) use 4 coil heaters and 2 drain pan heaters All gas defrost units (G)(H) use 2 drain pan heaters
ELECTRIC DEFROST HEATER
MODEL
SUFFIX 1, 2 & 5 SUFFIX 8 & 9
LSE LPE(G) (H) LAE(G) (H)
0500 0600
REH 0010 N/A
0600 0700 0800 0950 0650
REH 0020 N/A
1000 1200 0760 1200 1400 0900 REH 0030 REH 0080
1200 1500 1800 1500 REH 0040 REH 0085 1800 2100
1800
REH 0050 REH 0090
2400 2800
2700
REH 0060 REH 0097
3000 3500 3800 3600 3000
REH 0070 REH 0100
4200 4500
REW 0020 REW 0030 REW 0040
COMMERCIAL WALK-IN COOLERS LS, LP, LA LOW SILHOUETTE
MOTOR
All Models
SUFFIX-1 120/1/60
RMT 0004
SUFFIX-2 240/1/60
RMT 0005
Note: Motors are mounted in sheet metal base.
Motors include RHW 1999 (4)
1
Standard plastic guard
2
Optional steel wire guard
FAN BLADE
LS LP, LA
RFN 0023 RFN 0022
FAN GUARD
ALL MODELS
RGR 0085
1
RGR 0084
2
DEFROSTTERMINATION RTH0002
RTH0003
N/A N/A
(LS) RTH0002
1
(LP, LA) RTH0009
RTH0002
RTH0002
FANDELAY
PANHEATERSAFETY
Note:
1
RTH 0009 for optional LS Medium & Low Temperature
Note: DFK-2 includes RHW 4007, RHW 2011 & RFT 5135
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
8
TECHNICAL DATA (LS SERIES)
TECHNICAL DATA (LP SERIES)
Model R404A, R507 Operating Charge (lb.) Shipping Weight (lb.)
LSA 0400-1 0.9 36 LSA 0540-1 1.4 41 LSA 0650-1 1.8 45 LSA 0900-1 2.1 58 LSA 1100-1 2.8 64 LSA 1300-1 3.4 77 LSA 1700-1 3.8 96 LSA 2000-1 5.1 106 LSA 2600-1 6.7 140 LSA 3250-1 8.3 172 LSA 3900-1 10.0 203
LSE 0500-2 1.9 44 LSE 0600-2 2.6 48 LSE 0800-2 2.9 62 LSE 1000-2 3.9 68 LSE 1200-2 4.8 82 LSE 1500-2 5.3 108 LSE 1800-2 7.1 116 LSE 2400-2 9.4 150 LSE 3000-2 11.6 185 LSE 3600-2 13.9 219
LS(R)(T) 0500-1 1.4 42 LS(R)(T) 0600-1 1.8 46 LS(R)(T) 0800-1 2.1 60 LS(R)(T) 1000-1 2.8 66 LS(R)(T) 1200-1 3.4 79 LS(R)(T) 1500-1 3.8 100 LS(R)(T) 1800-1 5.1 112 LS(R)(T) 2400-1 6.7 145 LS(R)(T) 3000-1 8.3 178 LS(R)(T) 3600-1 10.0 211
Model R404A, R507 Operating Charge (lb.) Shipping Weight (lb.)
LPA 0600-1 1.5 74 LPA 0700-1 1.9 81 LPA 0950-1 2.2 102 LPA 1200-1 3.0 113 LPA 1400-1 3.7 135 LPA 1800-1 4.1 169 LPA 2100-1 5.4 189 LPA 2800-1 7.1 243 LPA 3500-1 8.9 297 LPA 4200-1 10.6 351
LPE 0600-1 2.6 79 LPE 0700-1 3.5 87 LPE 0950-1 4.0 110 LPE 1200-1 5.3 124 LPE 1400-1 6.6 148 LPE 1800-1 7.3 185 LPE 2100-1 9.7 209 LPE 2800-1 12.8 269 LPE 3500-1 15.9 330 LPE 4200-1 19.0 391
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
9
TECHNICAL DATA (LP SERIES)
Model R404A, R507 Operating Charge (lb.) Shipping Weight (lb.)
LP(G)(H) 0600-1 1.5 75 LP(G)(H) 0700-1 1.9 82 LP(G)(H) 0950-1 2.2 105 LP(G)(H) 1200-1 3.0 115 LP(G)(H) 1400-1 3.7 137 LP(G)(H) 1800-1 4.1 173 LP(G)(H) 2100-1 5.4 193 LP(G)(H) 2800-1 7.1 248 LP(G)(H) 3500-1 8.9 304 LP(G)(H) 4200-1 10.6 359
TECHNICAL DATA (LA SERIES)
Model R404A, R507 Operating Charge (lb.) Shipping Weight (lb.)
LAA 0650-1 2.2 100 LAA 0760-1 3.0 108 LAA 0900-1 3.7 131 LAA 1200-1 4.1 174 LAA 1500-1 5.4 190 LAA 1800-1 7.1 235 LAA 2700-1 8.9 272 LAA 3000-1 10.6 345 LAA 3800-1 13.3 438 LAA 4500-1 15.9 517
LAE 0650-2 4.0 107 LAE 0760-2 5.3 123 LAE 0900-2 6.6 141 LAE 1200-2 7.3 187 LAE 1500-2 9.7 219 LAE 1800-2 12.8 256 LAE 2700-2 15.9 315 LAE 3000-2 19.0 412 LAE 3800-2 24.3 508 LAE 4500-2 29.1 605
LA(G)(H) 0650-1 2.2 103 LA(G)(H) 0750-1 3.0 112 LA(G)(H) 0900-1 3.7 133 LA(G)(H) 1200-1 4.1 180 LA(G)(H) 1500-1 5.4 198 LA(G)(H) 1800-1 7.1 240 LA(G)(H) 2700-1 8.9 284 LA(G)(H) 3000-1 10.6 370 LA(G)(H) 3800-1 13.3 455 LA(G)(H) 4500-1 15.9 541
Note: • Operating charges are based on 30% liquid, 70% vapor at 25ºF suction
• Fan motor heat is not included in rating, add 342 BTUH (100W) per fan motor to room load
• Use suffix 1 for 120/1/60, suffix 2 for 240/1/60
• For 200-240/1/50 use suffix 2 and multiply capacity by 0.92
• For R134a or R-22 refrigerant charge, multiply R-404A by 1.09.
• Air throw for LS Series is 25 to 35 feet
• Air throw for LP Series is 12 to 18 feet
• Air throw for LA Series is 10 to 15 feet
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
10
1. PRELIMINARY INFORMATION
UNIT COOLER MODEL No.: UNIT COOLER MODEL No.: CONDENSING UNIT MODEL No.: COMPRESSOR MODEL No.: COMPRESSOR MODEL No.: DATE:
SERIALNo.: SERIALNo.: SERIALNo.: SERIALNo.: SERIALNo.: TECHNICIAN:
2. PRE-START-UP (Check each item when completed)
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS VERIFY REFRIGERANT CHARGE USING CHARGING CHART LABEL ON CONDENSING UNIT CHECK REFRIGERANT AND OIL LEVEL IN SYSTEM VERIFY THAT ALL DEFROST CONTROLS ARE FUNCTIONING PROPERLY
CHECK ALL FAN MOTORS AND MOTOR MOUNTS FOR TIGHTNESS CHECK DRAIN LINES AND DRAIN PAN FOR PROPER DRAINAGE CHECK DRAIN LINE HEATER FOR PROPER OPERATION CHECK ALL FLARE CONNECTIONS FOR TIGHTNESS
4. CONTROLS
THERMOSTAT SETTING F
DEFROSTSETTING /DAY
/DAY
5. FIELD INSTALLED EXPANSION VALVE
MANUFACTURER MODEL
F
MINUTES FAIL-SAFE MINUTES FAIL-SAFE
PRESSURES (in cooling mode)
REFRIGERANT SUCTION PSIG REFRIGERANT DISCHARGE PSIG EVACUATION: NUMBER TIMES
TEMP AT COMPRESSOR TEMP AT COMPRESSOR FINAL MICRON
3. START-UP
ELECTRICAL
COMPRESSOR VOLTAGE COMPRESSOR AMPS COMPRESSOR UNITCOOLER
L1 - L2 L1 VOLTS VOLTS
L2 - L3 L2 PHASE PHASE
L3 - L1 L3 HERTZ HERTZ
TEMPERATURE
AMBIENT TEMPERATURE DESIGN BOX TEMPERATURE OPERATING BOX TEMPERATURE OPERATING BOX TEMPERATURE SUPERHEAT AT COMPRESSOR SUCTION LINE TEMP. AT UNIT COOLER SUPERHEAT AT UNIT COOLER
START-UP
F F F F F F F
AFTER 24 HOURS OF OPERATION
F F F F F F F
UNIT COOLER DRAIN LINE TRAPPED OUTSIDE OF BOX: YES OR NO
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
11
REFPLUS SHALL NOT BE LIABLE:
WARRANTIES
RefPlus warrants the labeled (Serial No.) new RefPlus equipment and all parts thereof, to be free from defects in workmanship and material at the time of purchase. Applies to original purchaser only (nontransferable).
Under this warranty RefPlus shall be limited to repairing or exchanging any parts, without charge FOB factory or nearest authorized parts wholesalers , which may prove defective to the satisfaction of RefPlus, within one year from date of start-up, not to exceed eighteen (18) months from date of shipment from the factory.
The warranties to repair or replace as recited, are the only warranties , express, implied, or statutor y, made by RefPlus. No express or implied warranties as to merchantability or fitness for a particular purpose or use. RefPlus neither assumes, nor authorizes any person to assume for it, any other obligation or liability in connection with the sale of said equipment or any part thereof.
1 - For any repairs or replacement by buyer without the written consent of
RefPlus, or when the equipment is installed or operated in a manner con­trary to the instructions covering installation and service which accompanied such equipment.
2 - For any damages, delays, or losses, direct or consequential, caused by
defects, nor for damages caused by short or reduced supply of materials, fire, flood, strikes, acts of God, or circumstances beyond its control.
3 - When the failure or defect of any part or parts is incidental to
ordinary wear, accident, abuse or misuse; or when the serial number of
the equipment has been removed, defaced, altered, or tampered with. 4 - When this equipment is operated on low or improper voltages. 5 - For payment of any removal or installation charges of parts or units. 6 - When this equipment is moved to a different location other than the
original installation.
EXCLUSIONS
THIS WARRANTY SHALL NOT APPLY TO LOSS OF FOOD OR REFRIGERANT DUE TO FAILURE FOR ANY REASON.
RefPlus reserves the right to make any changes in the design or specifications of any product at any time without notice.
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
WI/O&M-04-04-R0-3K Printed in Canada.
USA & CANADA 1-888-816-2665
1385 De Coulomb,Boucherville , Quebec Canada J4B 7L8 Tel.:(450) 641-2665 Fax: (450) 641-4554
www.refplus.com
Loading...