This handbook describes how to use the MOSAIC programmable safety module and its
expansion units ("SLAVES");
it includes:
• a description of the system
• method of installation
• connections
• signals
• troubleshooting
• use of the configuration SW
Important safety instructions
This safety alert symbol indicates a potential personal safety hazard. Failure to
comply with instructions bearing this symbol could pose a very serious risk to
personnel.
This symbol indicates an important instruction.
The MOSAIC is built to the following safety levels: SIL 3, SILCL 3, PL e, Cat. 4, Type 4
in accordance with the applicable standards. However, the definitive SIL and PL of the
application will depend on the number of safety components, their parameters and
the connections that are made, as per the risk analysis.
Read the "Applicable Standards" section carefully.
Perform an in-depth risk analysis to determine the appropriate safety level for your
specific application, on the basis of all the applicable standards.
Programming/configuration of the Mosaic is the sole responsibility of the installer or
user.
The device must be programmed/configured in accordance with the application-
specific risk analysis and all the applicable standards.
Once you have programmed/configured and installed the Mosaic and all the relative
devices, run a complete application safety test (see "TESTING the system", page 80).
Always test the complete system whenever new safety components are added (see
the "TESTING the system" section, page 80).
ReeR is not responsible for these operations or any risks in connection therewith.
Reference should be made to the handbooks and the relative product and/or
application standards to ensure correct use of devices connected to the Mosaic within
the specific application.
The ambient temperature in the place where the system is installed must be
compatible with the operating temperature parameters stated on the product label
and in the specifications.
For all matters concerning safety, if necessary, contact your country's competent
safety authorities or the competent trade association.
8540780 • 23/03/2017 • Rev.317
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
CEI EN 61131-2
Programmable controllers, part 2:
Equipment requirements and tests
EN ISO 13489-1
Safety of machinery:
Safety related parts of control systems. General principles for design
EN 61496-1
Safety of machinery: Electro-sensitive protective equipment. Part 1: General
requirements and tests.
IEC 61508-1
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: General requirements.
IEC 61508-2
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: Requirements for electrical/electronic/programmable
electronic safety-related systems.
IEC 61508-3
Functional safety of electrical/electronic/programmable electronic safetyrelated systems: Software requirements.
IEC 61508-4
Functional safety of electrical/electronic programmable electronic safety
related systems: Definitions and abbreviations.
IEC 61784-3
Digital data communication for measurement and control: Functional safety
fieldbuses.
IEC 62061
Safety of machinery. Functional safety of safety-related electrical, electronic
and programmable electronic control systems
Abbreviations and symbols
MCM = MOSAIC Configuration Memory: memorychip for MOSAIC M1 (accessory)
MSC = MOSAIC Safety Communication: proprietary bus for expansion units
MSD = MOSAIC Safety Designer: MOSAIC configuration SW running in Windows
OSSD = Output Signal Switching Device: solid state safety output
MTTFd = Mean Time to Dangerous Failure
PL = Performance Level
PFHd = Probability of a dangerous failure per Hour
SIL = Safety Integrity Level
SILCL = Safety Integrity Level Claim Limit
SW = Software
Applicable standards
MOSAIC complies with the following European Directives:
MOSAIC is a modular safety controller. It consists of a master unit (M1), which can
be configured using the MSD graphic interface, and a number of expansion units
connected to the M1 via the proprietary MSC bus.
The M1 can also be used as a stand-alone device. It has 8 safety inputs and 2
independent programmable dual channel outputs.
The following expansions are available: I/O expansions (MI8O2), input only
expansions (MI8, MI12T8, MI16, MV0, MV1 and MV2), output only expansions
(MO2, MO4 and MO4LHCS8), signaling only expansions (MOS8 and MOS16),
guided contact safety relay output modules (MR2, MR4, MOR4 and MOR4S8) and
diagnostic connections to the main fieldbuses: MBP (PROFIBUS), MBC (CanOpen),
MOSAIC is capable of monitoring the following safety sensors and commands:
optoelectronic sensors (safety light curtains, scanners, safety photocells),
mechanical switches, safety mats, emergency stops, two-hand controls, all
managed by a single flexible and expandable device.
The system must consist of just one Master M1 and a number of electronic
expansions that can range from 0 to a maximum of 14, not more than 4 of which
of the same type. There is no limit to the number of relay modules that can be
installed.
With 14 expansions, the system can have up to 128 inputs, 16 dual channel safety
outputs and 16 status outputs. The MASTER and its SLAVE units communicate via
the 5-way MSC bus (ReeR proprietary bus), physically arranged on the rear panel
of each unit.
Furthermore 8 inputs and 16 outputs probe controllable (by Fieldbus) are
available.
With the MI8, MI16 and MI12T8 Mosaic expansion units, the number of inputs in
the system can be increased to allow more external devices to be connected. The
MI12T8 also provides 8 OUT_TEST outputs.
The MO2 and MO4 Mosaic expansion units provide the system, respectively, with
2 and 4 OSSD (Output Signal Switching Device) pairs for controlling devices
connected downstream of the MOSAIC.
The MO4LHCS8 is a safety module with 4 High Current Safety Outputs and 4
relative inputs for external feedback contacts (EDM).
The module provides 8 programmable signal outputs.
The MI802 has 8 inputs and 2 OSSD outputs.
The MR2 and MR4 Mosaic expansion units provide the system with 2 and 4 N.O.
guided contact safety relay outputs, respectively, with the related external relay
feedback (N.C. contact).
8540780 • 23/03/2017 • Rev.319
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
The expansion units in the MB series permit connection to the most commonly
used industrial fieldbus systems for diagnostics and data transmission.
The MBEI, MBEI2B,MBEP, MBEM and MBEC also have an ethernet connection. The
MBU permits connection to devices with a USB port.
The MCT1 and MCT2 Mosaic units are used to connect the M1 to other slave
units installed at a distance (< 50 m). Two MCT units installed at the required
distance can be connected using a shielded cable (ReeR MC25, MC50 or other
cable with the characteristics set out in the cable data sheet).
The MV0, MV1 and MV2 Mosaic expansion units can be used to control the
following (up to PLe):
Zero speed, Max. speed, Speed range;
Direction of movement, rotation/translation;
Up to 4 speed thresholds can be set for each logic output (axis).
Each unit incorporates two logic outputs that can be configured using the MSD
software and is thus capable of controlling up to two independent axes.
The MOR4 and MOR4S8 are safety units provided with 4 independent safety relay
outputs and the corresponding 4 inputs for the external feedback contacts (EDM).
There are two possible output settings (configured using the MSD configuration
software).
Two pairs of connection contacts (2 N.O. contacts per output with 2
corresponding feedback inputs).
Four independent single connection contacts (1 N.O. contact per output
with 1 corresponding feedback input).
Only the MOR4S8 unit has 8 programmable signal outputs.
The MOS8 and MOS16 have 8 and 16 programmable signal outputs.
The MSD software is capable of creating complex logics, using logical operators
and safety functions such as muting, timer, counters, etc.
All this is performed through an easy and intuitive graphic interface.
The configuration performed on the PC is sent to the M1 via USB connection; the
file resides in the M1 and can also be saved on the proprietary MCM memory chip
(accessory). The configuration can therefore quickly be copied to another M1 unit.
The MOSAIC system is certified to the maximum safety level envisaged by the
• CD-ROM containing the free MSD SW, this PDF multi-language handbook and
other product literature.
• Multi-language installation sheet.
NB: the rear panel MSC connector and MCM memory can be ordered separately as
accessories.
The expansion units are supplied with:
• Multilingual Installation sheet.
• Rear panel MSC connector (not present in the MR2 and MR4 which are
connected via terminal blocks only).
NB: to install an expansion unit (excluding relays) you will need the MSC connector
supplied with the unit plus another MSC for the connection to the M1. This can be
ordered separately as an accessory.
8540780 • 23/03/2017 • Rev.3111
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
INSTALLATION
Mechanical fastening
Fix the MOSAIC system units to a 35mm DIN rail as follows:
1. Connect the same number of "MSC" 5-pole rear panel connectors as the
number of units to be installed.
2. Fix the train of connectors thus obtained to the Omega DIN 35mm
(EN 5022) rail (hooking them at the top first).
3. Fasten the units to the rail, arranging the contacts on the base of the unit
on the respective connector. Press the unit gently until you feel it snap into
place.
4. To remove a unit, use a screwdriver to pull down the locking latch on the
back of the unit; then lift the unit upwards and pull.
1 2a
2b 3 4
Figure 1
12 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
1
The MOSAIC system units are provided with terminal
blocks for the electrical connections. Each unit can
have 8, 16 or 24 terminals.
Each unit also has a rear panel plug-in connector
(for communication with the master and with the
other expansion units).
The MR2 and MR4 are connected via terminal blocks
only.
Calculation of safety distance of an ESPE connected to MOSAIC
Any Electro-sensitive Protective Equipment device connected to MOSAIC, must be
positioned at a distance equal to or greater than the minimum safety distance S so that
the dangerous point can be reached only after stopping the dangerous movement of the
machine.
The european standard:
- ISO 13855:2010- (EN 999:2008) Safety of machinery - Positioning of safeguards with
respect to the approach speeds of parts of the human body.
provides the elements to calculate the proper safety distance.
Carefully read the installation manual of each device for specific information on the
correct positioning.
Remember that the total response time depends on:
MOSAIC response time + ESPE response time + response time of the machine (i.e. the
time taken by the machine to stop the dangerous movement from the moment in
which the stop signal is transmitted).
Electrical connections
Install safety units in an enclosure with a protection class of at least IP54.
Connect the module when it is not powered.
The supply voltage to the units must be 24Vdc 20% (PELV, in compliance with the
standard EN 60204-1 (Chapter 6.4)).
Do not use the MOSAIC to supply external devices.
The same ground connection (0VDC) must be used for all system components.
"Describe the methods that designers can use to calculate the minimum safety distance from a specific dangerous point
for the safety devices, particularly Electro-sensitive devices (eg. light curtains), safety-mats or pressure sensitive floors and
bimanual control. It contains a rule to determine the placement of safety devices based on approach speed and the
stopping time of the machine, which can reasonably be extrapolated so that it also includes the interlocking guards without
guard locking."
We recommend the use of separate power supplies for the safety module and for
other electrical power equipment (electric motors, inverters, frequency converters)
or other sources of disturbance.
Cables used for connections of longer than 50m must have a cross-section of at
least 1mm2 (AWG16).
Connections of each single MOSAIC system unit are listed in the table below:
Module Master M1
14 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
USB input
The MOSAIC master M1 includes a
USB 2.0 connector for connection to
a Personal Computer where
the MSD (MOSAIC Safety Designer)
configuration SW resides.
A USB cable of the correct size is
available as an accessory (CSU).
Figure 2 - USB 2.0 front panel connector
TECHNICAL DATA LABEL
MCM LABEL
Figure 3 - MCM
MOSAIC Configuration Memory (MCM)
A backup memory, called MCM (optional)
can be installed in the MOSAIC master M1
and used to save the SW configuration
parameters.
The MCM is written each time a new
project is sent from the PC to the M1.
Always switch the M1 off before
logging on to/logging off from the
MCM.
Insert the card in the slot in the rear panel of the M1 (in the direction shown
in Figure 3 - MCM).
MULTIPLE LOAD function
To perform the configuration of several
M1 modules without using a PC and the
USB connector, you can save the desired
configuration on a single MCM and then
use it to download data on the modules
M1 to be configured.
If the file contained in the MCM is not identical to the one contained in M1, an overwrite
operation that will permanently delete the configuration data contained in M1 will be
performed.
WARNING: ALL DATA PREVIOUSLY CONTAINED IN M1 WILL BE LOST.
RESTORE function
If the M1 unit is damaged, you can replace it with a new one; having already saved all the
configurations on the MCM, all you need to do is insert the MCM in the new M1 and
8540780 • 23/03/2017 • Rev.3115
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2 )
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2 )
4
0VDC
-
0VDC power supply
-
5
OSSD1_A
Output
Static output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback/Restart 1
Input according to EN 61131-2
8
OUT_STATUS1
Output
Programmable signal output
PNP active high
9
OSSD2_A
Output
Static output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback/Restart 2
Input according to EN 61131-2
12
OUT_STATUS2
Output
Programmable signal output
PNP active high
13
OUT_TEST1
Output
Short circuit detected output
PNP active high
14
OUT_TEST2
Output
Short circuit detected output
PNP active high
15
OUT_TEST3
Output
Short circuit detected output
PNP active high
16
OUT_TEST4
Output
Short circuit detected output
PNP active high
17
INPUT1
Input
Digital input 1
Input according to EN 61131-2
18
INPUT2
Input
Digital input 2
Input according to EN 61131-2
19
INPUT3
Input
Digital input 3
Input according to EN 61131-2
20
INPUT4
Input
Digital input 4
Input according to EN 61131-2
21
INPUT5
Input
Digital input 5
Input according to EN 61131-2
22
INPUT6
Input
Digital input 6
Input according to EN 61131-2
23
INPUT7
Input
Digital input 7
Input according to EN 61131-2
24
INPUT8
Input
Digital input 8
Input according to EN 61131-2
switch on the MOSAIC system, that will immediately load the backup configuration. In this
way, the work interruptions will be minimized.
The LOAD and RESTORE functions can be disabled via SW. (see Figure 42)
In order to be used, the expansion units must be addressed at the time of
installation (see the NODE SEL section).
Each time MCM is used, carefully check that the chosen configuration is the one that
was planned for that particular system. Try again a fully functional test of the system
composed of Mosaic plus all devices connected to it (see the TESTING the system
section).
Module MI8O2
16 8540780 • 23/03/2017 • Rev.31
Table 2
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2 )
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2 )
4
0VDC
-
0VDC power supply
-
5
INPUT1
Input
Digital input 1
Input according to EN 61131-2
6
INPUT2
Input
Digital input 2
Input according to EN 61131-2
7
INPUT3
Input
Digital input 3
Input according to EN 61131-2
8
INPUT4
Input
Digital input 4
Input according to EN 61131-2
9
OUT_TEST1
Output
Short circuit detected output
PNP active high
10
OUT_TEST2
Output
Short circuit detected output
PNP active high
11
OUT_TEST3
Output
Short circuit detected output
PNP active high
12
OUT_TEST4
Output
Short circuit detected output
PNP active high
13
INPUT5
Input
Digital input 5
Input according to EN 61131-2
14
INPUT6
Input
Digital input 6
Input according to EN 61131-2
15
INPUT7
Input
Digital input 7
Input according to EN 61131-2
16
INPUT8
Input
Digital input 8
Input according to EN 61131-2
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2 )
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2 )
4
0VDC
-
0VDC power supply
-
5
INPUT1
Input
Digital input 1
Input according to EN 61131-2
6
INPUT2
Input
Digital input 2
Input according to EN 61131-2
7
INPUT3
Input
Digital input 3
Input according to EN 61131-2
8
INPUT4
Input
Digital input 4
Input according to EN 61131-2
9
OUT_TEST1
Output
Short circuit detected output
PNP active high
10
OUT_TEST2
Output
Short circuit detected output
PNP active high
11
OUT_TEST3
Output
Short circuit detected output
PNP active high
12
OUT_TEST4
Output
Short circuit detected output
PNP active high
13
INPUT5
Input
Digital input 5
Input according to EN 61131-2
14
INPUT6
Input
Digital input 6
Input according to EN 61131-2
15
INPUT7
Input
Digital input 7
Input according to EN 61131-2
16
INPUT8
Input
Digital input 8
Input according to EN 61131-2
17
OUT_TEST5
Output
Short circuit detected output
PNP active high
18
OUT_TEST6
Output
Short circuit detected output
PNP active high
19
OUT_TEST7
Output
Short circuit detected output
PNP active high
20
OUT_TEST8
Output
Short circuit detected output
PNP active high
21
INPUT9
Input
Digital input 9
Input according to EN 61131-2
22
INPUT10
Input
Digital input 10
Input according to EN 61131-2
23
INPUT11
Input
Digital input 11
Input according to EN 61131-2
24
INPUT12
Input
Digital input 12
Input according to EN 61131-2
Module MI8
Table 3
Module MI12T8
8540780 • 23/03/2017 • Rev.3117
Table 4
English
Module MI16
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2 )
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2 )
4
0VDC
-
0VDC power supply
-
5
INPUT1
Input
Digital input 1
Input according to EN 61131-2
6
INPUT2
Input
Digital input 2
Input according to EN 61131-2
7
INPUT3
Input
Digital input 3
Input according to EN 61131-2
8
INPUT4
Input
Digital input 4
Input according to EN 61131-2
9
OUT_TEST1
Output
Short circuit detected output
PNP active high
10
OUT_TEST2
Output
Short circuit detected output
PNP active high
11
OUT_TEST3
Output
Short circuit detected output
PNP active high
12
OUT_TEST4
Output
Short circuit detected output
PNP active high
13
INPUT5
Input
Digital input 5
Input according to EN 61131-2
14
INPUT6
Input
Digital input 6
Input according to EN 61131-2
15
INPUT7
Input
Digital input 7
Input according to EN 61131-2
16
INPUT8
Input
Digital input 8
Input according to EN 61131-2
17
INPUT9
Input
Digital input 9
Input according to EN 61131-2
18
INPUT10
Input
Digital input 10
Input according to EN 61131-2
19
INPUT11
Input
Digital input 11
Input according to EN 61131-2
20
INPUT12
Input
Digital input 12
Input according to EN 61131-2
21
INPUT13
Input
Digital input 13
Input according to EN 61131-2
22
INPUT14
Input
Digital input 14
Input according to EN 61131-2
23
INPUT15
Input
Digital input 15
Input according to EN 61131-2
24
INPUT16
Input
Digital input 16
Input according to EN 61131-2
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2 )
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2 )
4
0VDC
-
0VDC power supply
-
5
OSSD1_A
Output
Static output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback/Restart 1
Input according to EN 61131-2
8
OUT_STATUS1
Output
Programmable signal output
PNP active high
9
OSSD2_A
Output
Static output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback/Restart 2
Input according to EN 61131-2
12
OUT_STATUS2
Output
Programmable signal output
PNP active high
13
24VDC
-
24VDC power supply
24VDC outputs power supply *
14
24VDC
-
24VDC power supply
-
15
0VDC
-
0VDC power supply
0VDC outputs *
16
0VDC
-
0VDC power supply
-
17
OSSD4_A
Output
Static output 4
PNP active high
18
OSSD4_B
Output
PNP active high
19
RESTART_FBK4
Input
Feedback/Restart 4
Input according to EN 61131-2
20
OUT_STATUS4
Output
Programmable signal output
PNP active high
21
OSSD3_A
Output
Static output 3
PNP active high
22
OSSD3_B
Output
PNP active high
23
RESTART_FBK3
Input
Feedback/Restart 3
Input according to EN 61131-2
24
OUT_STATUS3
Output
Programmable signal output
PNP active high
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
Module MO4
Table 5
18 8540780 • 23/03/2017 • Rev.31
Table 6
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2 )
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2 )
4
0VDC
-
0VDC power supply
-
5
OSSD1_A
Output
Static output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback/Restart 1
Input according to EN 61131-2
8
OUT_STATUS1
Output
Programmable signal output
PNP active high
9
OSSD2_A
Output
Static output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback/Restart 2
Input according to EN 61131-2
12
OUT_STATUS2
Output
Programmable signal output
PNP active high
13
24VDC
-
24VDC power supply
24VDC output power supply *
14
n.c. - -
-
15
0VDC
-
0VDC power supply
0VDC output *
16
n.c. - -
-
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
- 4 0VDC
-
0VDC power supply
-
5
OSSD1_A
Input
Control ZONE 1
PNP active high
6
OSSD1_B
Input
7
FBK_K1_K2_1
Output
Feedback K1K2 ZONE 1
9 A_NC1
Output
NC contact ZONE 1
10
B_NC1
Output
13
A_NO11
Output
NO1 contact ZONE 1
14
B_NO11
Output
15
A_NO12
Output
NO2 contact ZONE 1
16
B_NO12
Output
11
A_NC2
Output
NC contact ZONE 2
12
B_NC2
Output
17
OSSD2_A
Input
Control ZONE 2
PNP active high
18
OSSD2_B
Input
19
FBK_K1_K2_2
Output
Feedback K1K2 ZONE 2
21
A_NO21
Output
NO1 contact ZONE 2
22
B_NO21
Output
23
A_NO22
Output
NO2 contact ZONE 2
24
B_NO22
Output
Module MO2
Table 7
* This terminal must be connected to the power supply for the unit to work
properly.
Module MR4
Table 8
8540780 • 23/03/2017 • Rev.3119
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
- 4 0VDC
-
0VDC power supply
-
5
OSSD1_A
Input
Control ZONE 1
PNP active high
6
OSSD1_B
Input
7
FBK_K1_K2_1
Output
Feedback K1K2 ZONE 1
9 A_NC1
Output
NC contact ZONE 1
10
B_NC1
Output
13
A_NO11
Output
NO1 contact ZONE 1
14
B_NO11
Output
15
A_NO12
Output
NO2 contact ZONE 1
16
B_NO12
Output
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to
EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" according to
EN 61131-2)
4
0VDC
-
0VDC power supply
-
5
PROXI1_24V
Output
PROXIMITY 1
connections
PROXIMITY INPUT FOR SPEED
CONTROLLER MV2 -> 27)
Power supply 24VDC to
PROXI1
6
PROXI1_REF
Output
Power supply 0VDC to PROXI1
7
PROXI1 IN1 (3 WIRES)
Input
PROXI1 NO input
8
PROXI1 IN2 (4 WIRES)
Input
PROXI1 NC input
9
PROXI2_24V
Output
PROXIMITY 2
connections
-> 27)
Power supply 24VDC to
PROXI2
10
PROXI2_REF
Output
Power supply 0VDC to PROXI2
11
PROXI2 IN1 (3 WIRES)
Input
PROXI2 NO input
12
PROXI2 IN2 (4 WIRES)
Input
PROXI2 NC input
13
N.C.
-
Not connected
-
14
N.C. - -
15
N.C. - -
16
N.C. - -
Module MR2
Modules MV0 - MV1 - MV2
Table 9
20 8540780 • 23/03/2017 • Rev.31
Table 10
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
PIN
MVT
MVTB
MVH
MVS
TWISTED *
1
INPUT
5VDC
N.C.
N.C.
N.C. 2 EXT_0V
EXT_0V
EXT_0V
EXT_0V 3
N.C.
N.C.
N.C.
N.C.
TWISTED *
4
A A A A 5
ĀĀĀĀ
6
N.C.
N.C.
N.C.
N.C.
TWISTED *
7
B B B
B
8
B B B
B
POWER SUPPLY
5VDCEXT_0V
ENCODER TTL - M12 8 POLES CONNECTOR
EXT_0V
+5VDC
A
A
B
B
5
6
1
3
4
2
GREY
PINK
YELLOW
GREEN
BROWN
WHITE
MV MODULE - RJ45 CONNECTOR
8
7
6
5
4
3
2
1
B
B
A
A
+5VDC
EXT_0V
ENCODER TTL
B
6
B
5
8
B
7
B
A
4
A
3
1
24VDC
2
6
5
A
4
A
3
2
1
EXT_0V
24VDC
POWER SUPPLY
5
B
B
6
A
A
4
3
7
8
B
B
6
5
A
A
4
3
ENCODER SIN/COS
1
2
2
1
POWER SUPPLY
EXT_0V
24VDC
5VDC/24VDC
ENCODER HTL - M12 8 POLES CONNECTOR
MV MODULE - RJ45 CONNECTOR
ENCODER SIN/COS - M12 8 POLES CONNECTOR
MV MODULE - RJ45 CONNECTOR
N.C.
N.C.
7
8
PINK
GREY
GREEN
YELLOW
WHITE
BROWN
7
N.C.
8
N.C.
PINK
GREY
GREEN
YELLOW
WHITE
BROWN
7
N.C.
8
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
5VDC/
ENCODER HTL
EXT_0V
EXT_0V
EXT_0V
EXT_0V
5
B
B
6
A
A
4
3
7
8
B
B
6
5
A
A
4
3
1
2
2
1
POWER SUPPLY
EXT_0V24VDC
5VDC/24VDC
ENCODER TTLB - M12 8 POLES CONNECTOR
MV MODULE - RJ45 CONNECTOR
PINK
GREY
GREEN
YELLOW
WHITE
BROWN
7
N.C.
8
N.C.
N.C.
N.C.
5VDC/
EXT_0V
EXT_0V
ENCODER TTLB
ENCODER CONNECTIONS WITH RJ45 CONNECTOR (MV1, MV2)
* IN CASE OF UTILIZATION OF TWISTED CABLE
8540780 • 23/03/2017 • Rev.3121
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2)
4
0VDC
-
0VDC power supply
-
5
REST_FBK1
Input
Feedback/Restart 1
Input (according EN 61131-2)
6
REST_FBK2
Input
Feedback/Restart 2
Input (according EN 61131-2)
7
REST_FBK3
Input
Feedback/Restart 3
Input (according EN 61131-2)
8
REST_FBK4
Input
Feedback/Restart 4
Input (according EN 61131-2)
9
A_NO1
Output
N.O. contact Channel 1
10
B_NO1
Output
11
A_NO2
Output
N.O. contact Channel 2
12
B_NO2
Output
13
A_NO3
Output
N.O. contact Channel 3
14
B_NO3
Output
15
A_NO4
Output
N.O. contact Channel 4
16
B_NO4
Output
TERMINAL
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to
EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" according to
EN 61131-2)
4
0VDC - 0VDC power supply
-
5
REST_FBK1
Input
Feedback/Restart 1
Input (according EN 61131-2)
6
REST_FBK2
Input
Feedback/Restart 2
Input (according EN 61131-2)
7
REST_FBK3
Input
Feedback/Restart 3
Input (according EN 61131-2)
8
REST_FBK4
Input
Feedback/Restart 4
Input (according EN 61131-2)
9
A_NO1
Output
N.O. contact Channel 1
10
B_NO1
Output
11
A_NO2
Output
N.O. contact Channel 2
12
B_NO2
Output
13
A_NO3
Output
N.O. contact Channel 3
14
B_NO3
Output
15
A_NO4
Output
N.O. contact Channel 4
16
B_NO4
Output 17
OUT_STATUS1
Output
Programmable signal output 1
PNP active high
18
OUT_STATUS2
Output
Programmable signal output 2
PNP active high
19
OUT_STATUS3
Output
Programmable signal output 3
PNP active high
20
OUT_STATUS4
Output
Programmable signal output 4
PNP active high
21
OUT_STATUS5
Output
Programmable signal output 5
PNP active high
22
OUT_STATUS6
Output
Programmable signal output 6
PNP active high
23
OUT_STATUS7
Output
Programmable signal output 7
PNP active high
24
OUT_STATUS8
Output
Programmable signal output 8
PNP active high
Module MOR4
Table 11
Module MOR4S8
22 8540780 • 23/03/2017 • Rev.31
Table 12
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
PIN
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2)
4
0VDC - 0VDC power supply
-
5
24VDC
STATUS 1-8
-
24VDC power supply
OUTPUT STATUS 1-8
-
6 - -
-
-
7 - -
-
-
8 - -
-
-
9
OUT_STATUS1
Output
Programmable signal output 1
PNP active high
10
OUT_STATUS2
Output
Programmable signal output 2
PNP active high
11
OUT_STATUS3
Output
Programmable signal output 3
PNP active high
12
OUT_STATUS4
Output
Programmable signal output 4
PNP active high
13
OUT_STATUS5
Output
Programmable signal output 5
PNP active high
14
OUT_STATUS6
Output
Programmable signal output 6
PNP active high
15
OUT_STATUS7
Output
Programmable signal output 7
PNP active high
16
OUT_STATUS8
Output
Programmable signal output 8
PNP active high
PIN
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2 )
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2 )
4
0VDC
-
0VDC power supply
-
5
24VDC
STATUS 1-8
-
24VDC power supply OUTPUT
STATUS 1-8
-
6
24VDC
STATUS 9-16
-
24VDC power supply OUTPUT
STATUS 9-16
-
7 - -
-
-
8 - -
-
-
9
OUT_STATUS1
Output
Programmable signal output 1
PNP active high
10
OUT_STATUS2
Output
Programmable signal output 2
PNP active high
11
OUT_STATUS3
Output
Programmable signal output 3
PNP active high
12
OUT_STATUS4
Output
Programmable signal output 4
PNP active high
13
OUT_STATUS5
Output
Programmable signal output 5
PNP active high
14
OUT_STATUS6
Output
Programmable signal output 6
PNP active high
15
OUT_STATUS7
Output
Programmable signal output 7
PNP active high
16
OUT_STATUS8
Output
Programmable signal output 8
PNP active high
17
OUT_STATUS9
Output
Programmable signal output 9
PNP active high
18
OUT_STATUS10
Output
Programmable signal output 10
PNP active high
19
OUT_STATUS11
Output
Programmable signal output 11
PNP active high
20
OUT_STATUS12
Output
Programmable signal output 12
PNP active high
21
OUT_STATUS13
Output
Programmable signal output 13
PNP active high
22
OUT_STATUS14
Output
Programmable signal output 14
PNP active high
23
OUT_STATUS15
Output
Programmable signal output 15
PNP active high
24
OUT_STATUS16
Output
Programmable signal output 16
PNP active high
Module MOS8
Module MOS16
Table 13
8540780 • 23/03/2017 • Rev.3123
Table 14
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
PIN
SIGNAL
TYPE
DESCRIPTION
OPERATION
1
24VDC
-
24VDC power supply
-
2
NODE_SEL0
Input
Node selection
Input ("type B" according to EN 61131-2)
3
NODE_SEL1
Input
Input ("type B" according to EN 61131-2)
4
0VDC
0VDC power supply
5
REST_FBK1
Input
Feedback/Restart 1
Input (according EN 61131-2)
6
REST_FBK2
Input
Feedback/Restart 2
Input (according EN 61131-2)
7
REST_FBK3
Input
Feedback/Restart 3
Input (according EN 61131-2)
8
REST_FBK4
Input
Feedback/Restart 4
Input (according EN 61131-2)
9
OSSD1
Output
Safety Output 1
PNP active high
4 single channels (or 2 dual channels)
10
OSSD2
Output
Safety Output 2
11
OSSD3
Output
Safety Output 3
12
OSSD4
Output
Safety Output 4
13 -
-
-
14
24 VDC
24VDC power supply
-
15 -
-
-
16 -
-
-
17
OUT_STATUS1
Output
Programmable signal output 1
PNP active high
18
OUT_STATUS2
Output
Programmable signal output 2
PNP active high
19
OUT_STATUS3
Output
Programmable signal output 3
PNP active high
20
OUT_STATUS4
Output
Programmable signal output 4
PNP active high
21
OUT_STATUS5
Output
Programmable signal output 5
PNP active high
22
OUT_STATUS6
Output
Programmable signal output 6
PNP active high
23
OUT_STATUS7
Output
Programmable signal output 7
PNP active high
24
OUT_STATUS8
Output
Programmable signal output 8
PNP active high
Module MO4LHCS8
Example of connection of Mosaic to the machine control system
Figure 4
CHECKLIST AFTER INSTALLATION
The MOSAIC system is able to detect the faults that occurs in each own module.
Anyway to have the system perfect operation perform the following checks at start up
and at least every one year:
1. Operate a complete system TEST (see "TESTING the system")
2. Verify that all the cables are correctly inserted and the terminal blocks well screwed.
3. Verify that all the leds (indicators) light on correctly.
4. Verify the positioning of all the sensors connected to MOSAIC.
5. Verify the correct fixing of MOSAIC to the Omega rail.
6. Verify that all the external indicators (lamps) work properly.
After installation, maintenance and after any eventual configuration change perform
a System TEST as described in the paragraph "TESTING the system" at page 80.
24 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Mechanical fastening
Electrical connections
between the Mosaic
modules and with the
external sensors
Designing the diagram
Validation
sw OK ?
NO
YES
Downloading the
diagram to M1
Configuration check
(including complete
system TEST at page 54)
on M1 OK?
NO
YES
End of connection
via USB
System
startup
Connection
via USB with PSW
OPERATING DIAGRAM
8540780 • 23/03/2017 • Rev.3125
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
NODE_SEL1 (Terminal 3)
NODE_SEL0 (Terminal 2)
NODE 0
0 (or not connected)
0 (or not connected)
NODE 1
0 (or not connected)
24VDC
NODE 2
24VDC
0 (or not connected)
NODE 3
24VDC
24VDC
SIGNALS
INPUTS
MASTER ENABLE
The MOSAIC M1 master has two inputs: MASTER_ENABLE1 and MASTER_ENABLE2.
These signals must both be permanently set to logic level 1 (24VDC) for the MOSAIC
to operate. If the user needs to disable the MOSAIC simply lower these inputs to
logic level 0 (0VDC).
NODE SEL
The NODE_SEL0 and NODE_SEL1 inputs (on the SLAVE units) are used to attribute a
physical address to the slave units with the connections shown in Table 15:
Table 15
It is not allowed to use the same physical address on two units of the same type.
26 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
PROXIMITY INPUT FOR SPEED CONTROLLER MV
Configuration With Interleaved Proximity (Figure 5)
When an axis of the MV modules is configured for a measurement with two proximity
switches, these can be configured in interleaved mode. Under the conditions listed below
the system reaches a Performance Level = PLe:
Proximity switches must be fitted such that the recorded signals overlap.
Proximity switches must be fitted such that at least one is always activated.
Figure 5
In addition:
The proximity switches must be PNP type.
The proximity switches must be NO type (Output ON when detecting metal).
With the above conditions fulfilled, the DC value is equal to 90%.
The two proximity switches must be of the same model, with MTTF > 70 years.
8540780 • 23/03/2017 • Rev.3127
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MODE OF
OPERATION
EDM
RESTART_FBK
AUTOMATIC
With K1_K2
control
K2
K1
24V
ext_Restart_fbk
Without
K1_K2
control
24V
ext_Restart_fbk
MANUAL
With K1_K2
control
K2
K1
24V
ext_Restart_fbk
Without
K1_K2
control
24V
ext_Restart_fbk
RESTART_FBK
The RESTART_FBK signal input allows the MOSAIC to verify an EDM (External Device
Monitoring) feedback signal (series of contacts) from the external contactors, and to
monitor Manual/Automatic operation (See the list of possible connections in Table 16).
If the application requires it, the response time of the external contactors must be
verified by an additional device.
The RESTART command must be installed outside the danger area in a position where
the danger area and the entire work area concerned are clearly visible.
It must not be possible to reach the control from inside the danger area.
Table 16
28 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Automatic
The output is activated according to le configurations set by the MSD SW only if the
corresponding RESTART_FBK input is conected to 24VDC.
Manual
The output is activated according to le configurations set by the MSD SW only if corresponding
RESTART_FBK input FOLLOWS A LOGIC TRANSITION OF 0-->1.
Monitored
The output is activated according to le configurations set by the MSD SW only if the
corresponding RESTART_FBK input FOLLOWS A LOGIC TRANSITION OF 0-->1-->0.
OUTPUTS
OUT STATUS
The OUT STATUS signal is a Programmable signal output that can indicate the status of:
•An input.
•An output.
•A node of the logic diagram designed using the MSD.
OUT TEST
The OUT TEST signals must be used to monitor the presence of short-circuits or
overloads on the inputs (Figure 6).
The maximum number of controllable inputs for each output
The OSSD (static semiconductor safety outputs) are short circuit protected, cross circuit
monitored and supply:
•In the ON condition: Uv-0,75V ÷ Uv (where Uv is 24V ± 20%)
•In the OFF condition: 0V ÷ 2V r.m.s.
The maximum load of 400mA@24V corresponds to a minimum resistive load of 60.
The maximum capacitive load is 0.82F. The maximum inductive load is 2 mH.
OSSD (MO2, MO4)
The OSSD (static semiconductor safety outputs) are short circuit protected, cross circuit
monitored and supply:
•In the ON condition: Uv-0,75V ÷ Uv (where Uv is 24V ± 20%)
•In the OFF condition: 0V ÷ 2V r.m.s.
The maximum load of 400mA@24V corresponds to a minimum resistive load of 60.
The maximum capacitive load is 0.82F. The maximum inductive load is 2 mH.
It is not allowed the connection of external devices to the outputs, except as
expected in the configuration performed with the MSD software.
Each OSSD output can be configured as shown in Table 17:
Table 17
8540780 • 23/03/2017 • Rev.3129
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
t = 250ms
250ms < t1< 5s
t2 = 250ms
Configuration with 2 dual channel
outputs (safety category 4)
Configuration with 4 single outputs
(safety category 4)
OSSD (MO4LHCS8)
MO4LHCS8 provides 4 High Current Safety Outputs (2A max per channel).
Two different output configurations (configurable with MSD configuration software)
can be set:
• Four single channels (1 Safety Output per channel with its relative feedback input).
• Two dual channels (2 Safety Outputs per channel with their relative feedback input).
Using MO4LHCS8 with current output >500mA, separate it from adjacent modules
by interposing an MSC connector.
30 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Excitation voltage
17...31 VDC
Minimum switchable voltage
10 VDC
Minimum switchable current
20 mA
Maximum switchable voltage (DC)
250VDC
Maximum switchable voltage (AC)
400VAC
Maximum switchable current
6A
Response time
12ms
Mechanical life of contacts
> 20 x 106
SAFETY RELAYS (MR2, MR4, MOR4, MOR4S8)
Characteristics of the output circuit.
The MR2/MR4 units use guided contact safety relays, each of which provides two N.O.
contacts and one N.C contact in addition to the N.C. feedback contact.
The MR2 unit uses two safety relays and the MR4 uses four.
The MOR4/MOR4S8 units use four guided-contact safety relays. Each relay provides one
NO contact monitored by the module logic through internal FBK contact.
Refer to the "RELAY" section to check the possible MOR4/MOR4S8 operation modes
configurable with MSD software.
Table 18
To guarantee correct isolation and avoid the risk of premature ageing of or damage
to the relays, each output line must be protected using a fast acting 4A fuse and the
load characteristics must be consistent with those specified in Table 12.
See the "MR2/MR4" section (for further details on these relays).
MR2/MR4 internal contacts diagram
8540780 • 23/03/2017 • Rev.3131
Figure 7
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
2
Example of MR2 module connection with static OSSD outputs of a module M12
Switching operation timing diagram.
Figure 8
Figure 9
If a relay module is connected, the response time of the OSSD linked, must be increased of 12ms.
32 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Parameter
Value
Standard
PFHd
See the technical data tables for each module
IEC 61508:2010
SIL 3 SFF
99,8%
HFT 1 Safety standard
Type B
SILCL
3
IEC 62061:2005
Type
4
EN 61496-1:2013
PL
e
EN ISO 13849-1:2008
EN 62061:2005
Dc
avg
High
MTTFd (years)
30 ÷ 100
Category
4
Device lifetime
20 years
Pollution degree
2
Max number of inputs
128
Max number of outputs
16
Max number of slave units
(excluding MR2-MR4)
14
Max number of slave units of the same type
(excluding MR2-MR4)
4
Rated voltage
24VDC 20% / Supply from class II (LVLE)
Over voltage category
II
Digital INPUTS
PNP active high (EN 61131-2) Max. applicable resistance 1,2kΩ
Encoder input signals electrically
insulated in accordance with
EN 61800-5
-
Rated insulation voltage 250V
Overvoltage category II
Rated impulse withstand voltage 4.00 kV
Max number of encoders
-
1
2
Max encoder frequency
-
500KHz (HTL: 300KHz)
Encoder adjustable
threshold range
-
1Hz ÷ 450KHz
Proximity type
PNP/NPN - 3/4 wires
Proximity connections
Terminal blocks
Proximity adjustable threshold range
1Hz ÷ 4KHz
Max number of proximity
2
Max proximity frequency
5KHz
Max number of axes
2
Stand-still/overspeed frequency gap
>10Hz
Min. gap between tresholds
(with tresholds >1)
> 5%
M1 connections
via MSC 5-way ReeR proprietary bus
MO4LHCS8 module
Using MO4LHCS8 with current output >500mA, separate it from adjacent modules by
interposing an MSC connector.
MV0 - MV1 - MV2 modules
8540780 • 23/03/2017 • Rev.3137
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
114.5 mm
108 mm
22.5 mm99 mm
MECHANICAL DIMENSIONS
Figure 10
38 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
COM
ENA
IN1÷8
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
BLUE
YELLOW
RED/GREEN
YELLOW
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
ON
Red
ON
ON
MCM recognised
OFF
OFF
OFF
ON
(max 1s)
ON
(max 1s)
OFF
Red
OFF
OFF
Writing/loading/ diagram
to/from MCM card
OFF
OFF
OFF
5
flashes
5
flashes
OFF
Red
OFF
OFF
MSD requesting connection:
internal configuration not present
OFF
OFF
OFF
Flashes slowly
OFF
OFF
Red
OFF
OFF
MSD requesting connection:
(slave module or node number
not correct) (ref. System composition)
OFF
OFF
OFF
Flashes quickly
OFF
OFF
Red
OFF
OFF
MSD requesting connection:
(slave module missing or not ready)
(ref. System composition)
Flashes quickly
OFF
OFF
Flashes quickly
OFF
OFF
Red
OFF
OFF
MSD connected M1 stopped
OFF
OFF
OFF
ON
OFF
OFF
Red
OFF
OFF
MEANING
LED
RUN
IN FAIL
EXT FAIL
COM
IN1÷8
ENA
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
BLUE
RED/GREEN
YELLOW
YELLOW
NORMAL
OPERATION
ON
OFF
OFF
op. OK
ON = M1
connected to
PC
OFF=otherwise
INPUT condition
ON
MASTER_ENABLE1
and MASTER_ENABLE2
active
OFF
otherwise
RED with
output OFF
GREEN with
output ON
ON
waiting for
RESTART
Flashing
NO feedback
OUTPUT
condition
EXTERNAL
FAULT
DETECTED
ON
OFF
ON
incorrect
external
connection
detected
ON = M1
connected to
PC
OFF=otherwise
only the number
of the INPUT with
the incorrect
connection
flashes
RUN
ON
INEXT
ENACOM
FAIL
IN
STATUS
CLEAR
OSSD
21
21
21
8
7
65
43
21
Figure 11 - M1
SIGNALS
Master M1 (Figure 11)
39 8540780 • 23/03/2017 • Rev.31
Table 19 - Opening Screen
Table 20 - Dynamic Screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1÷8
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
RED/GREEN
YELLOW
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
Red
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
IN1÷8
SEL
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
YELLOW
ORANGE
RED/GREEN
YELLOW
YELLOW
NORMAL
OPERATION
OFF
if the unit is waiting for
the first communication
from the MASTER
OFF
OFF
INPUT condition
Shows the
NODE_SEL0/1
signal table
RED
with output
OFF
GREEN
with output
ON
ON
waiting for
RESTART
Flashes
NO feedback
OUTPUT
condition
FLASHES
if no INPUT or OUTPUT
requested by the
configuration
ON
incorrect
external
connection
detected
only the number of the
INPUT with the
incorrect connection
flashes
ON
if INPUT or OUTPUT
requested by the
configuration
SEL
1
EXT
0
IN
RUNON
FAIL
IN
STATUS
CLEAR
OSSD
21
21
2
1
8
7
6
5
43
2
1
Figure 12 - MI8O2
MI8O2 (Figure 12)
Table 21 - Opening Screen
40 8540780 • 23/03/2017 • Rev.31
Table 22 - Dynamic Screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1÷8
GREEN
RED
RED
ORANGE
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1÷8
GREEN
RED
RED
ORANGE
YELLOW
NORMAL
OPERATION
OFF
if the unit is waiting for the first
communication from the MASTER
OFF
OFF
Shows the
NODE_SEL0/1 signal
table
INPUT condition
FLASHES
if no INPUT or OUTPUT requested by the
configuration
ON
incorrect external
connection detected
only the number of the INPUT
with the incorrect connection
flashes
ON
if INPUT or OUTPUT requested by the
configuration
IN
8
7
6
5
4
3
2
1
SEL
1
EXT
0
IN
RUN
ON
FAIL
Figure 13 - MI8
MI8 (Figure 13)
Table 23 - Opening Screen
8540780 • 23/03/2017 • Rev.3141
Table 24 - Dynamic Screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1÷12
GREEN
RED
RED
ORANGE
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1÷12
GREEN
RED
RED
ORANGE
YELLOW
NORMAL
OPERATION
OFF
if the unit is waiting for the first
communication from the MASTER
OFF
OFF
Shows the
NODE_SEL0/1 signal
table
INPUT condition
FLASHES
if no INPUT or OUTPUT requested by the
configuration
ON
incorrect external
connection detected
only the number of the INPUT
with the incorrect connection
flashes
ON
if INPUT or OUTPUT requested by the
configuration
Figure 14
MI12T8
MI12T8 (Figure 15)
Table 25 - Opening Screen
Table 26 - Dynamic Screen
42 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1÷16
GREEN
RED
RED
ORANGE
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
IN1÷16
GREEN
RED
RED
ORANGE
YELLOW
NORMAL
OPERATION
OFF
if the unit is waiting for the first
communication from the MASTER
OFF
OFF
Shows the
NODE_SEL0/1 signal
table
INPUT condition
FLASHES
if no INPUT or OUTPUT requested by the
configuration
ON
incorrect external
connection detected
only the number of the INPUT
with the incorrect connection
flashes
ON
if INPUT or OUTPUT requested by the
configuration
1615
14
13
12
11
109
IN
8
7
6
5
4
3
21
SEL
1
EXT
0
IN
RUN
ON
FAIL
Figure 15 - MI16
MI16 (Figure 15)
Table 27 - Opening Screen
8540780 • 23/03/2017 • Rev.3143
Table 28 - Dynamic Screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
OSDD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
Power on - initial TEST
ON
ON
ON
ON
Red
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
NORMAL
OPERATION
OFF
if the unit is waiting for the first
communication from the MASTER
OFF
op. OK
OFF
op. OK
Shows the
NODE_SEL0/1 signal
table
RED
with output
OFF
ON
waiting for
RESTART
OUTPUT
condition
FLASHES
if no INPUT or OUTPUT requested by
the configuration
GREEN
with output
ON
Flashes
NO feedback
ON
if INPUT or OUTPUT requested by the
configuration
STATUS
CLEAR
OSSD
21
2
1
2
1
SEL
1
EXT
0
IN
RUN
ON
FAIL
Figure 16 - MO2
MO2 (Figure 16)
Table 29 - Opening screen
44 8540780 • 23/03/2017 • Rev.31
Table 30 - Dynamic screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
OSDD1/4
CLEAR1/4
STATUS1/4
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
Power on - initial TEST
ON
ON
ON
ON
Red
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
OSDD1/4
CLEAR1/4
STATUS1/4
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
NORMAL
OPERATION
OFF
if the unit is waiting for the first
communication from the MASTER
OFF
op. OK
OFF
op. OK
Shows the
NODE_SEL0/1 signal
table
RED
with output
OFF
ON
waiting for
RESTART
OUTPUT
condition
FLASHES
if no INPUT or OUTPUT requested by
the configuration
GREEN
with output
ON
Flashes
NO feedback
ON
if INPUT or OUTPUT requested by the
configuration
STATUS
CLEAR
OSSD
21
21
2
1
STATUS
CLEAR
OSSD
4
3
43
43
SEL
1
EXT
0
IN
RUN
ON
FAIL
Figure 17 - MO4
MO4 (Figure 17)
Table 31 - Opening screen
8540780 • 23/03/2017 • Rev.3145
Table 32 - Dynamic screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL 0/1
RELAY 1/4
CLEAR1/4
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
Power on - initial TEST
ON
ON
ON
ON
Red
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL 0/1
RELAY 1/4
CLEAR1/4
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
NORMAL OPERATION
OFF
if the unit is waiting
for the first
communication from
the MASTER
FLASHES
if no INPUT or
OUTPUT requested by
the configuration
ON
if INPUT or OUTPUT
requested by the
configuration
OFF
operation OK
OFF
operation OK
Shows the
NODE_SEL0/1
signal table
RED
with contact
opened
ON
waiting for
RESTART
GREEN
with contact closed
FLASHES
External contactors
feedback error
Figure 18 - MOR4
MOR4 (Figure 18)
Table 33 - Opening screen
46 8540780 • 23/03/2017 • Rev.31
Table 34 - Dynamic screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL 0/1
RELAY 1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
Power on - initial
TEST
ON
ON
ON
ON
Red
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL 0/1
RELAY 1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
NORMAL OPERATION
OFF
if the unit is
waiting for the
first
communication
from the MASTER
FLASHES
if no INPUT or
OUTPUT requested
by the
configuration
ON
if INPUT or
OUTPUT requested
by the
configuration
OFF
operation OK
OFF
operation OK
Shows the
NODE_SEL0/1
signal table
RED
with contact opened
ON
waiting for
RESTART
OUTPUT
condition
GREEN
with contact closed
FLASHES
wrong feedback
external
contactors
Figure 19 - MOR4S8
MOR4S8 (Figure 19)
Table 35 - Opening screen
8540780 • 23/03/2017 • Rev.3147
Table 36 - Dynamic screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
LED
MEANING
RUN
IN FAIL
EXT FAIL
SEL 0/1
STATUS1/8
GREEN
RED
RED
ORANGE
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
LED
MEANING
RUN
IN FAIL
EXT FAIL
SEL 0/1
STATUS1/8
GREEN
RED
RED
ORANGE
YELLOW
NORMAL OPERATION
OFF
if the unit is waiting
for the first
communication from
the MASTER
FLASHES
if no INPUT or OUTPUT
requested by the
configuration
ON
if INPUT or OUTPUT
requested by the
configuration
OFF
operation OK
OFF
operation OK
Shows the
NODE_SEL0/1 signal
table
OUTPUT
condition
Figure 20 - MOS8
MOS8 (Figure 20)
Table 37 - Opening screen
48 8540780 • 23/03/2017 • Rev.31
Table 38 - Dynamic screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
LED
MEANING
RUN
IN FAIL
EXT FAIL
SEL 0/1
STATUS1/16
GREEN
RED
RED
ORANGE
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
LED
MEANING
RUN
IN FAIL
EXT FAIL
SEL 0/1
STATUS1/16
GREEN
RED
RED
ORANGE
YELLOW
NORMAL OPERATION
OFF
if the unit is waiting
for the first
communication from
the MASTER
FLASHES
if no INPUT or OUTPUT
requested by the
configuration
ON
if INPUT or OUTPUT
requested by the
configuration
OFF
operation OK
OFF
operation OK
Shows the
NODE_SEL0/1 signal
table
OUTPUT
condition
Figure 21 – MOS16
MOS16 (Figure 21)
Table 39 - Opening screen
8540780 • 23/03/2017 • Rev.3149
Table 40 - Dynamic screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
Power on - initial TEST
ON
ON
ON
ON
ON
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
NORMAL OPERATION
OFF
if the unit is waiting
for the first
communication
from the MASTER
FLASHES
if no INPUT or
OUTPUT requested
by the
configuration
ON
if INPUT or OUTPUT
requested by the
configuration
OFF
operation OK
OFF
operation OK
Shows the
NODE_SEL0/1
signal table
ON
Encoder
connected and
operative
ON
Proximity
connected and
operative
OFF
Axis in normal
speed range
ON
Axis in stand
still
BLINKING
Axis in
overspeed
Figure 22 - MV1, MV2
MV1, MV2 (Figure 22)
Table 41 - Opening screen
50 8540780 • 23/03/2017 • Rev.31
Table 42 - Dynamic screen
* NOT PRESENT ON MV0 MODULE
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
OSSD1
GREEN
NORMAL OPERATION
ON with output activated
MEANING
LED
OSSD1
OSSD2
GREEN
GREEN
NORMAL OPERATION
ON with output activated
OSSD
1
Figure 23 - MR2
OSSD
12
Figure 24 - MR4
MR2 (Figure 23) / MR4 (Figure 24)
Table 43 - MR2 - Dynamic screen
Table 44 - MR4 - Dynamic screen
8540780 • 23/03/2017 • Rev.3151
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL 0/1
OSSD 1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
Power on - initial
TEST
ON
ON
ON
ON
Red
ON
ON
MEANING
LED
RUN
IN FAIL
EXT FAIL
SEL 0/1
OSSD 1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
NORMAL OPERATION
OFF
if the unit is waiting
for the first
communication
from the MASTER
FLASHES
if no INPUT or
OUTPUT requested
by the configuration
ON
if INPUT or OUTPUT
requested by the
configuration
OFF
operation
OK
OFF
operation
OK
Shows the
NODE_SEL0/1
signal table
RED
with output OFF
ON
waiting for
RESTART
ON
The associated
SYSTEM STATUS
output is active
GREEN
with output ON
FLASHES
wrong feedback
external
contactors
OFF
The associated
SYSTEM STATUS
output is NOT
active
Figure 25 -
MO4LHCS8
MO4LHCS8 (Figure 25)
Table 45 - Opening screen
52 8540780 • 23/03/2017 • Rev.31
Table 46 - Dynamic screen
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
COM
IN1÷8
ENA
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
BLUE
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
OFF
OFF
OFF
Red
OFF
OFF
Return the unit to
ReeR to be
repaired
OSSD output
error
OFF
4
flashes
OFF
OFF
OFF
OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF
OFF
• Check the
OSSD1/2
connections
• If the problem
persists return
the M1 to ReeR to
be repaired
Error in
communication
with slave
OFF
5
flashes
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• Restart the
system.
• If the problem
persists return
the M1 to ReeR to
be repaired
Slave unit
error
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
• Restart the
system
• Check which unit
is in FAIL mode
MCM error
OFF
6
flashes
OFF
6
flashes
OFF
OFF
OFF
OFF
OFF
Replace the MCM
RUN
ON
INEXT
ENACOM
FAIL
IN
STATUS
CLEAR
OSSD
21
21
21
8
7
65
43
21
Figure 26 - M1
TROUBLESHOOTING
Master M1 (Figure 26)
8540780 • 23/03/2017 • Rev.3153
Table 47 - Troubleshooting M1
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL
IN1÷8
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address of the
unit
OFF
Red
OFF
OFF
• Return the unit to
ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5 flashes
5
flashes
5
flashes
5
flashes
• Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
OSSD output error
OFF
4
flashes
OFF
OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF
OFF
• Check OSSD1/2
connections
• If the problem
persists, return the
unit to ReeR to be
repaired
Error in
communication with
master
OFF
5
flashes
OFF
OFF
OFF
OFF
OFF
• Restart the system
• If the problem
persists, return the
MI8O2 to ReeR to be
repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
OFF
OFF
OFF
• Restart the system
• Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
OFF
• Change the unit's
address (see NODE
SEL)
Node detection
circuit error
OFF
3
flashes
OFF
3
flashes
OFF
OFF
OFF
OFF
• Return the unit to
ReeR to be repaired
SEL
1
EXT
0
IN
RUNON
FAIL
IN
STATUS
CLEAR
OSSD
21
21
2
1
8
7
6
5
43
2
1
Figure 27 - MI8O2
MI8O2 (Figure 27)
54 8540780 • 23/03/2017 • Rev.31
Table 48 - Troubleshooting MI8O2
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL
IN1÷8
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address of
the unit
OFF
• Return the unit to ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
• Firmware version not compatible with M1,
return to ReeR for FW upgrade.
Error in communication with
master
OFF
5
flashes
OFF
OFF
• Restart the system
• If the problem persists, return the unit to ReeR
to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
• Restart the system
• Check which unit is in FAIL mode
Same type of slave with same
address detected
OFF
5
flashes
5
flashes
OFF
• Change the unit's address (see NODE SEL)
Node detection circuit error
OFF
3
flashes
OFF
3
flashes
OFF
• Return the unit to ReeR to be repaired
IN
8
7
6
5
4
3
2
1
SEL
1
EXT
0
IN
RUN
ON
FAIL
Figure 28 - MI8
MI8 (Figure 28)
8540780 • 23/03/2017 • Rev.3155
Table 49 - Troubleshooting MI8
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
LED
MEANING
RUN
IN FAIL
EXT FAIL
SEL
IN1÷12
REMEDY
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
2 or 3 flashes
OFF
Shows the physical
address of the unit
OFF
Return the unit to ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
• Firmware version not compatible with M1,
return to ReeR for FW upgrade.
Error in communication with
master
OFF
5
flashes
OFF
OFF
• Restart the system
• If the problem persists, return the unit to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
• Restart the system
• Check which unit is in FAIL mode
Same type of slave with
same address detected
OFF
5
flashes
5
flashes
OFF
• Change the unit's address (see NODE SEL)
Node detection circuit error
OFF
3
flashes
OFF
3
flashes
OFF
• Return the unit to ReeR to be repaired
Figure 29 -
MI12T8
MI12T8 (Figure 29)
56 8540780 • 23/03/2017 • Rev.31
Table 50 - Troubleshooting MI12T8
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL
IN1÷16
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
2 or 3 flashes
OFF
Shows the
physical
address of the
unit
OFF
• Return the unit to ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
• Firmware version not compatible with M1,
return to ReeR for FW upgrade.
Error in communication with
master
OFF
5
flashes
OFF
OFF
• Restart the system
• If the problem persists, return the unit to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
• Restart the system
• Check which unit is in FAIL mode
Same type of slave with same
address detected
OFF
5
flashes
5
flashes
OFF
• Change the unit's address (see NODE SEL)
Node detection circuit error
OFF
3
flashes
OFF
3
flashes
OFF
• Return the unit to ReeR to be repaired
1615
14
13
12
11
109
IN
8
7
6
5
4
3
21
SEL
1
EXT
0
IN
RUN
ON
FAIL
Figure 30 - MI16
MI16 (Figure 30 - MI16)
8540780 • 23/03/2017 • Rev.3157
Table 51 - Troubleshooting MI16
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL
OSSD1/4
CLEAR1/4
STATUS1/4
GREEN
RED
RED
ORANGE
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address of the
unit
Red
OFF
OFF
Return the unit to
ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
5
flashes
• Firmware version
not compatible
with M1, return to
ReeR for FW
upgrade.
OSSD output error
OFF
4
flashes
OFF
4 flashes
(only the LED
corresponding to
the output in FAIL
mode)
OFF
OFF
• Check OSSD1/2
connections
• If the problem
persists, return
the unit to ReeR
to be repaired
Error in communication
with master
OFF
5
flashes
OFF
OFF
OFF
OFF
• Restart the system
• If the problem
persists, return
the unit to ReeR
to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
OFF
OFF
• Restart the system
• Check which unit
is in FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
• Change the unit's
address (see
NODE SEL)
Power supply missing
on OSSD 3,4 (MO4
only)
ON
OFF
ON
Red
flashes
flashes
OUTPUT
condition
• Connect 13 and
14 pin to power
supply
Status output overload
or short circuit
OFF
OFF
ON
OUTPUT condition
CLEAR
condition
flashes
• Check STATUS
connections
Error on node
detection circuit
OFF
3
flashes
OFF
3
flashes
OFF
OFF
OFF
• Return the MO2/4
to ReeR to be
repaired
STATUS
CLEAR
OSSD
21
2
1
2
1
SEL
1
EXT
0
IN
RUN
ON
FAIL
STATUS
CLEAR
OSSD
21
21
2
1
STATUS
CLEAR
OSSD
4
3
43
43
SEL
1
EXT
0
IN
RUN
ON
FAIL
Figure 31 - MO2 / MO4
MO2 / MO4 (Figure 31)
58 8540780 • 23/03/2017 • Rev.31
Table 52 - Troubleshooting MO2/MO4
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL 0/1
RELAY 1/4
CLEAR1/4
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
Internal fault
OFF
2 / 3 flashes
OFF
Shows the
physical address
of the unit
Rosso
OFF
• Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
• Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
Relais output error
OFF
4
flashes
OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF
• If the problem persists,
return the module to
ReeR to be repaired
Error in
communication with
master
OFF
5
flashes
OFF
OFF
OFF
• Restart the system
• If the problem persists,
return the module to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
OFF
• Restart the system
• Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
• Change the unit's
address (see NODE SEL)
External contactors
feedback error on
Category 4 relay
ON
OFF
4
flashes
4 flashes
(only the LEDs corresponding to the
outputs in FAIL mode)
• Verify connections
5,6,7,8.
Error on node
detection circuit
OFF
3 flashes
OFF
3
flashes
OFF
OFF
• Return the module to
ReeR to be repaired
Figure 32 - MOR4
MOR4 (Figure 32)
8540780 • 23/03/2017 • Rev.3159
Table 53 - Troubleshooting MOR4
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL 0/1
RELAY 1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
Internal fault
OFF
2 / 3
flashes
OFF
Shows the
physical
address of
the unit
Rosso
OFF
• Return the unit to
ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
5
flashes
• Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
Relais output error
OFF
4
flashes
OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF
OFF
• If the problem
persists, return the
module to ReeR to be
repaired
Error in
communication with
master
OFF
5
flashes
OFF
OFF
OFF
OFF
• Restart the system
• If the problem
persists, return the
module to ReeR to be
repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
OFF
OFF
• Restart the system
• Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
• Change the unit's
address
(see NODE SEL)
External contactors
feedback error on
Category 4 relay
ON
OFF
4
flashes
4 flashes (only the LEDs corresponding
to the outputs in FAIL mode)
OFF
• Verify connections
5,6,7,8.
Error on node
detection circuit
OFF
3 flashes
OFF
3
flashes
OFF
OFF
OFF
• Return the module to
ReeR to be repaired
Short circuit or
overload detected on
status output
OFF
OFF
ON
OFF
OUTPUT
condition
CLEAR
condition
flash
• Verify output status
connections
Figure 33 - MOR4S8
MOR4S8 (Figure 33)
60 8540780 • 23/03/2017 • Rev.31
Table 54 - Troubleshooting MOR4S8
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL 0/1
STATUS1/8
GREEN
RED
RED
ORANGE
YELLOW
Internal fault
OFF
2 / 3 flashes
OFF
Shows the physical
address of the unit
OFF
• Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
• Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
Error in communication
with master
OFF
5
flashes
OFF
OFF
• Restart the system
• If the problem persists,
return the module to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
• Restart the system
• Check which unit is in
FAIL mode
Same type of slave with
same address detected
OFF
5
flashes
5
flashes
OFF
• Change the unit's
address
(see NODE SEL)
Error on node detection
circuit
OFF
3 flashes
OFF
3
flashes
OFF
• Return the module to
ReeR to be repaired
Short circuit or overload
detected on status 1-8
output
OFF
OFF
ON
OFF
flash
• Verify output status 1-
8 connections
Power supply missing
on status 1-8 output
OFF
OFF
ON
OFF
flash
alternatively
• Connect 5 pin to power
supply
Figure 34 – MOS8
MOS8 (Figure 34)
8540780 • 23/03/2017 • Rev.3161
Table 55 - Troubleshooting MOS8
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL 0/1
STATUS1/8
STATUS9/16
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
Internal fault
OFF
2 / 3 flashes
OFF
Shows the
physical
address of the
unit
OFF
OFF
• Return the unit to ReeR
to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
• Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
Error in communication
with master
OFF
5
flashes
OFF
OFF
OFF
• Restart the system
• If the problem persists,
return the module to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
OFF
• Restart the system
• Check which unit is in
FAIL mode
Same type of slave with
same address detected
OFF
5
flashes
5
flashes
OFF
OFF
• Change the unit's
address
(see NODE SEL)
Error on node detection
circuit
OFF
3 flashes
OFF
3
flashes
OFF
OFF
• Return the module to
ReeR to be repaired
Short circuit or overload
detected on status 1-8
output
OFF
OFF
ON
OFF
flash
OFF
• Verify output status 1-
8 connections
Short circuit or overload
detected on status 9-16
output
OFF
OFF
ON
OFF
OFF
flash
• Verify output status
9-16 connections
Power supply missing
on status 1-8 output
OFF
OFF
ON
OFF
flash
alternatively
OFF
• Connect 5 pin to power
supply
Power supply missing
on status 9-16 output
OFF
OFF
ON
OFF
OFF
flash
alternatively
• Connect 6 pin to power
supply
Figure 35 – MOS16
MOS16 (Figure 35)
62 8540780 • 23/03/2017 • Rev.31
Table 56 - Troubleshooting MOS16
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL
ENC*
PROX
SH
GREEN
RED
RED
ORANGE
YELLOW
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical
address
of the unit
OFF
OFF
OFF
• Return the unit to
ReeR to be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
5
flashes
• Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
Encoder INTERNAL
error
OFF
3
flashes
OFF
3
flashes
OFF
OFF
• Change the encoder
• Return the unit to
ReeR to be repaired
Proximity
INTERNAL error
3
flashes
OFF
3
flashes
• Change the proximity
• Return the unit to
ReeR to be repaired
Error on node
detection circuit
OFF
3
flashes
OFF
3
flashes
OFF
OFF
OFF
• Return the unit to
ReeR to be repaired
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
• Change the unit's
address
(see NODE SEL)
Encoder not
connected but
requested from the
configuration
OFF
OFF
3
flashes
**
3
flashes
**
OFF
OFF
• Verify encoder
connection and power
supply
• Verify input frequency
(in range)
Proximity not
connected but
requested from the
configuration
OFF
OFF
3
flashes
**
OFF
3
flashes
**
OFF
• Verify proximity
connection
• Verify input frequency
(in range)
Figure 36 - MV1, MV2
MV0, MV1, MV2 (Figure 33)
8540780 • 23/03/2017 • Rev.3163
Table 57 - Troubleshooting MV1/MV2
* NOT PRESENT ON MV0 MODULE
** WITH FAULT OF A SINGLE CHANNEL, THE SIGNAL IS PRESENTED IN TWO TEMPORAL WINDOWS:
IN THE FIRST IS SHOWED TE FAULT, IN THE SECOND IS SHOWED THE CORRECT CHANNEL.
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL 0/1
OSSD 1/4
CLEAR1/4
STATUS1/8
GREEN
RED
RED
ORANGE
RED
GREEN
YELLOW
YELLOW
Internal fault
OFF
2 / 3
flashes
OFF
Shows the
physical
address of
the unit
Rosso
OFF
• Return the unit to ReeR to
be repaired
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
5
flashes
• Firmware version not
compatible with M1,
return to ReeR for FW
upgrade.
OSSD output error
OFF
4
flashes
OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF
OFF
• If the problem persists,
return the module to
ReeR to be repaired
Error in
communication with
master
OFF
5
flashes
OFF
OFF
OFF
OFF
• Restart the system
• If the problem persists,
return the module to
ReeR to be repaired
Error on other
slave or M1
OFF
ON
OFF
OFF
OFF
OFF
• Restart the system
• Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF
OFF
OFF
• Change the unit's address
(see NODE SEL)
Short circuit or
overload detected on
status output
ON
OFF
ON
OUTPUT
condition
CLEAR
condition
flash
• Verify output status
connections
OSSD overload or
load connected to
24VDC
ON
OFF
ON
Blinking (only LED
corresponding to the
relative output)
OFF
OUTPUT
condition
• Verify OSSD connections
Power supply
missing on
OSSD3-OSSD4
ON
OFF
ON
OSSD3/OSSD4
led blinking
OSSD3/OSSD4
led blinking
OUTPUT
condition
• Connect pin 14 to 24VDC
Error on node
detection circuit
OFF
3 flashes
OFF
3
flashes
OFF
OFF
OFF
• Return the module to
ReeR to be repaired
Figure 37 -
MO4LHCS8
MO4LHCS8 (Figure 37)
64 8540780 • 23/03/2017 • Rev.31
Table 58 - Troubleshooting MO4LHCS8
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MOSAIC SAFETY DESIGNER SOFTWARE
The "MOSAIC SAFETY DESIGNER" application software can be used to configure a logic
diagram of the connections between the MOSAIC (Master + expansions) and the
components of the system being developed.
The MOSAIC and its SLAVE units will thus monitor and control the connected safety
components.
The MSD uses a versatile graphic interface to establish the connections between the
various components, as described below:
Installing the software
PC HARDWARE requirements
• RAM: 256 MB
(adequate to run Windows XP SP3 + Framework 4.0)
• Hard disk: > 500Mbyte of free space
• USB connector: 1.1, 2.0 or 3.0
• CD-ROM drive
PC SOFTWARE requirements
- Windows XP with Service Pack 3 installed (or higher OS).
Microsoft Framework 4.0 (or higher) must be installed on the PC
How to install MSD
• Insert the installation CD;
• Wait for the auto-run installer to request the SW setup program;
Alternatively follow the path D:/;
• Double-click on the SetupDesigner.exe file;
When the installation procedure is complete a window is displayed asking you to
close the setup program.
8540780 • 23/03/2017 • Rev.3165
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
Fundamentals
Once the MSD has been correctly installed it creates an icon on the desktop.
To launch the program: double-click on this icon. =>
The opening screen shown below is displayed:
You are now ready to create your project.
Figure 38
66 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Standard tool bar
The standard tool bar is shown in Figure 39. The meanings of the icons are listed below:
Figure 39
1 -> CREATE A NEW PROJECT
2 -> CHANGE CONFIGURATION (composition of different modules)
3 -> CHANGE USER PARAMETERS (name, company, etc)
4 -> SAVE THE ACTUAL PROJECT
5 -> LOAD AN EXISTING PROJECT (FROM THE PC)
6 -> PRINT THE PROJECT SCHEMATIC
7 -> PRINT PREVIEW
8 -> PRINTING AREA
9 -> PRINT THE PROJECT REPORT
10 -> UNDO (CANCEL THE LAST COMMAND)
11 -> REDO (RESTORE THE LAST CANCELLATION)
12 -> VALIDATE THE PROJECT
13 -> CONNECT TO MOSAIC
14 -> SEND PROJECT TO MOSAIC
15 -> DISCONNECT FROM MOSAIC
16 -> DOWNLOAD AN EXISTING PROJECT (FROM MOSAIC)
17 -> MONITOR (Real time I/O status - graphic)
18 -> MONITOR (Real time I/O status - textual)
19 -> DOWNLOAD LOG FILE
20 -> SHOW SYSTEM CONFIGURATION
21 -> CHANGE PASSWORD
22 -> HELP ON-LINE
23 -> PASSWORD RECOVERY
8540780 • 23/03/2017 • Rev.3167
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
Firmware version
Textual tool bar
Optionally the textual tool bar shown below is also available (drop down).
Figure 40
Create a new project (configure the MOSAIC system)
Select icon CREATE (Figure 39) from the standard tool bar to start a new project. The user
authentication window is displayed (Figure 41).
Figure 41
Next the MSD displays a window showing the M1 only.
You may add the various units needed to create your system, using the pull-down menus
at the top of the screen (select slave) and at the bottom to select the relative node (0÷3).
SELECT SLAVE (to add to your configuration)
68 8540780 • 23/03/2017 • Rev.31
Figure 42
SELECT NODE (from 0 to 3) Select to disable MCM operations
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
EDIT CONFIGURATION (composition of the various modules)
The change of the system composition is obtained with the icon .
The configuration window is showed again (Figure 39).
Change user parameters
The change of user parameters is obtained with the icon .
The dialog user identification request appears (Figure 43). To accomplish this operation is
not necessary to Log out from Mosaic. Generally it serves when a new user must create a
new project (even using a previously created).
Figure 43
8540780 • 23/03/2017 • Rev.3169
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
1
2
3
OBJECTS - OPERATOR - CONFIGURATION tool bars
Four large tool windows are displayed to the left and right of the main window
(shown in Figure 44):
Figure 44
4
1 > OBJECT TOOL WINDOW
This contains the various function blocks that will make up your project; these
blocks are divided into 3 different types:
- physical
- inputs
- outputs
- comments
2 > OPERATOR TOOL WINDOW
This contains the various function blocks for connecting the objects in point 1;
these blocks are divided into 6 different types:
- logical
- muting
- memories
- counters
- timers
3 > CONFIGURATION TOOL WINDOW
This contains the description of your project composition.
4 > CONFIGURATION TOOL WINDOW (view)
This contains the graphic representation of your project composition.
70 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
(scheme
side SX)
(scheme
side SX)
Creating the diagram
Once you have selected your system composition, you are ready to configure the project.
The logic diagram is created using a DRAG&DROP function:
• Select the objects as required from the windows described previously (each single
object is described in detail in the following sections) and drag it into the design area.
• Now when you select the object the PROPERTIES window is enabled, where you must
fill in the fields as required.
• When you need to set a specific numerical value with a slide (eg filter) use the left and
right arrows on your keyboard or click the sides of the slider of the slide.
• Connect the objects by moving the mouse over the required pin and then dragging it
onto the pin to be connected.
• If the scheme requires the PAN function (moving working area in the window), select
the object to move and use the arrow keys on your keyboard.
• If the scheme is very complicated and requires a connection between two elements
very far, use the "Interpage" component. The element "Interpage out" must have a
name which, invoked by the corresponding "Interpage in", allows the desired link.
• When you need to duplicate an object, select it and press CTRL+C / CTRL+V keys on
your keyboard.
• When you need to delete an object or a link, select it and press DEL key on your
keyboard.
Use of mouse right button
ON BLOCK INPUT / OUTPUT
Copy / Paste
Delete
Delete all the assigned pins
Alignment with other functional blocks (multiple selection)
On-line Help
Monitor Mode: Show / Hide Properties window
The block Status: pin input enable / disable logical negation
ON BLOCK OPERATORS
Copy / Paste
Delete
Alignment with other functional blocks (multiple selection)
On-line Help
On input pin: activate / deactivate logical negation
Monitor Mode: Show / Hide Properties window
ON TERMINALS
Alignment with other blocks
8540780 • 23/03/2017 • Rev.3171
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
DESIGN
AREA
OBJECT
PROPERTIES
WINDOW
Connection
start point
ON CONNECTION (WIRES)
Delete
Display full path of the connection (network)
Figure 45
72 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Example of a project
Figure 46 shows an example of a project in which the M1 unit only is connected to two
safety blocks (E-GATE and E-STOP).
The M1 inputs (1,2,3) for connecting the contacts of the safety components are shown on
the left, in yellow. The MOSAIC outputs (from 1 to 4) are activated according to the
conditions defined in E-GATE and E-STOP (see the E-GATE - E-STOP sections).
By clicking on a block to select it, you enable the PROPERTIES WINDOW on the right, which
you can use to configure the block activation and test parameters (see the
E-GATE - E-STOP sections).
Figure 46
At the end of the project design stage (or at intermediate steps) you can save the current
configuration using the icon SAVE on the standard tool bar.
Project validation
Now the finished project must be verified. Execute the VALIDATE command (Icon
on the standard toolbar).
If the validation is successful, a sequential number is assigned to the input and output of
the project. Then, this number is also listed in the REPORT and in the MONITOR of MSD.
Only if the validation is successful we will proceed to send the configuration.
The validation function only verifies the consistency of programming with respect to
the characteristics of the MOSAIC system. It does not guarantee that the device has
been programmed to meet all the safety requirements for the application.
8540780 • 23/03/2017 • Rev.3173
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
Project report
Print of the System composition with properties of each block. (Icon on the standard
toolbar).
This definition of PL and of the other related parameters as set forth in ISO 13849-1
only refers to the functions implemented in the Mosaic system by the MSD
configuration software, assuming configuration has been performed correctly.
The actual PL of the entire application and the relative parameters must consider data
for all the devices connected to the Mosaic system within the scope of the
application.
This must only be performed by the user/installer.
74 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Connect to Mosaic
After connecting M1 to the PC via CSU cable (USB) use the icon for the connection.
A window appears to request the password. Enter the password (see "Password
protection").
If a remote connection (via internet) is needed M1 can connect to the appropriate
devices through its USB port.
In this case (ONLY WITH FW > 3.0.1) select "Remote connection".
Figure 47
Sending the configuration to the MOSAIC
To send the saved configuration from a PC to M1 use the icon on the standard
toolbar and wait the execution. M1 will save the project in its internal memory and
(if present) in MCM memory. (Password Required: level 2).
This function is possible only after project validation with OK result.
Download a configuration file (project) from Mosaic M1
To download a project from MOSAIC M1 to MSD use the icon on the Standard toolbar.
MSD will display the project residing in M1. (Sufficient Password level 1).
If the project must be used on other modules M1 verify the components effectively
connected (ref. "System composition" on page 76).
Then perform a "Project Validation" (page 73) and a "System Test" (page 80).
Configuration LOG
Within the configuration file (project), are included the creation date and CRC
(4-digit hexadecimal identification) of a project that are stored in M1.
This logbook can record up to 5 consecutive events, after which these are
overwritten, starting from the least recent event.
The log file can be visualized using the icon in the standard tool bar.
(Password Required: level 1).
8540780 • 23/03/2017 • Rev.3175
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
Figure 48
System composition
The check of the actual composition of the MOSAIC system is obtained using the icon
. (Password Required: level 1). A pop-up window will appear with:
- Connected modules;
- Firmware version of each module;
- Node number (physical address) of each module.
Figure 49
If the modules found are not correct the following window will appear;
e.g. MI12T8 node number not correct (displayed in red color text).
Figure 50
Disconnecting System
To disconnect the PC from M1 use the icon ; when the system is disconnected it is
resetted and it starts with the sent project.
If the system is not composed of all modules provided by the configuration, after
the disconnection, M1 indicates the incongruity and does not starts. (See SIGNALS).
76 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
MONITOR (I/O status in real time - textual)
To activate the monitor use the icon . (Password Required: level 1).
A pop-up window will appear (in real time) with:
- Status of the inputs (when the object has two or more input connections to Mosaic, the
MONITOR will show as active only the first), see the example in figure;
- Inputs Diagnostics;
- OSSD State;
- OSSD Diagnostics;
- Status of Signaling OUTPUTS;
- OUT TEST diagnostics.
Figure 51 - textual monitor
MONITOR (I/O status in real time - textual - graphic)
To activate/deactivate the monitor use the icon . (Password Required: level 1).
The color of links (Figure 33) allows you to view the diagnostics (in real time) with:
RED = OFF
GREEN = ON
DASHED ORANGE = Connection Error
DASHED RED = Pending enable (for example RESTART)
Placing the mouse pointer over the link, you can display the diagnostics.
PARTICULAR CASES
NETWORK OPERATOR, signals NETWORK IN, OUT:
RED CONTINUOUS LINE = STOP
GREEN CONTINUOUS LINE = RUN
ORANGE CONTINUOUS LINE = START
SERIAL OUTPUT OPERATOR:
BLACK CONTINUOUS LINE = data in transmission
8540780 • 23/03/2017 • Rev.3177
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
Figure 52 - graphic monitor
78 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Password protection
The MSD requests a password in order to upload and save the project.
The password entered as default must be modified to avoid manipulation (level 2
password) or so that the configuration loaded on Mosaic (level 1 password) is not
visible.
Level 1 password
All operators using the M1 system must have a Level 1 PASSWORD.
This password allows only to view the LOG file, composition of the system and MONITOR
in real time and upload operations.
The first time the system is initialised the operator must use the password "" (ENTER key).
Designers who know the level 2 password can enter a new level 1 password
(alphanumerical, max 8 characters).
Operators who know this password are enabled to upload (from M1 to PC), modify
or save the project.
Level 2 password
Designers authorised to work on the creation of the project must know a Level 2
PASSWORD. The first time the system is initialised the operator must use the password
"SAFEPASS" (all capital letters).
Designers who know the level 2 password can enter a new level 2 password
(alphanumerical, max 8 characters).
This password enables the project to be uploaded (from PC to M1), modified and
saved. In other words, it allows total control of the PC => MOSAIC system.
When a new project is UPLOADED the level 2 password could be changed.
Should you forget either of these passwords, please contact ReeR which will provide
an unlock file (when the unlock file is saved in the right directory the icon will
appear on the toolbar). When the icon is activated, the password level 1 and level 2
are restored to their original values. This password is only given to the designer and
can only be used once.
Password Change
To activate the PASSWORD Change use icon , after connecting with Level 2 Password.
A window appears (Figure 53) allowing the choice of the new password; insert the old and
new passwords in the appropriate fields (max 8 characters). Click OK.
At the end of the operation disconnect to restart the system.
If MCM is present the new password is also saved in it.
8540780 • 23/03/2017 • Rev.3179
Figure 53
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
TESTING the system
After validating and uploading the project to the M1 and connecting all the safety
devices, you must test the system to verify its correct operation.
This is done by forcing a change of status for each safety device connected to the
MOSAIC to check that the status of the outputs actually changes.
The following example is helpful for understanding the TEST procedure.
Figure 54
(t1) In the normal operating condition (E-GATE closed) Input1 is closed, Input2 is
open and the output of the E-GATE block is set to high logic level; in this mode
the safety outputs (OSSD1/2) are active and the power supply to the relative
terminals is 24VDC.
(t2) When the E-GATE is physically opened, the condition of the inputs and thus of
the outputs of the E-GATE block will change: (OUT= 0VDC--->24VDC); the
condition of the OSSD1-OSSD2 safety outputs will change from 24VDC to
0VDC. If this change is detected the mobile E-GATE is connected correctly.
For the correct installation of each external sensor/component refer to their
installation manual.
This test must be performed for each safety component in the project.
80 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Example of OSSD with correct Feedback signal:
In this case ERROR OUT=FALSE
Example of OSSD with incorrect Feedback signal
(k external time exceeded):
In this case ERROR OUT=TRUE
t = 250ms
5s > t1 > 250ms
t2 = 250ms
OBJECT FUNCTION BLOCKS
OUTPUT OBJECTS
OSSD (safety outputs)
OSSD safety outputs which use semiconductor
technology do not require maintenance, Output1
and Output2 supply 24Vdc if the In is 1 (TRUE) and
vice versa 0Vdc if the In is 0 (FALSE).
Each pair of OSSD outputs has a relative
RESTART_FBK input. This input must always
be connected as indicated in the
RESTART_FBK paragraph.
Parameters
Manual Reset: If selected this enables the request to reset each time the input signal falls.
Otherwise, output enabling directly follows In input conditions.
There are two types of reset:
Manual and Monitored. In
selecting the Manual option
only signal transition from 0
to 1 is verified. If the
Monitored option is selected,
the double transition from 0
to 1 and back to 0 is verified.
Enable Status: If selected,
enables the connection of the
current OSSD state to any
point on the screen.
K external time check: If selected, enables the setting of the time window within which the external
feedback signal is to be monitored (according to output conditions).
With high level (TRUE) OUTPUT, the FBK signal must be at low level (FALSE) and vice versa, within
the set time. Otherwise, OUTPUT is set to low level (FALSE) and the error is indicated on the
master M1 by the flashing CLEAR LED corresponding to the OSSD in error.
Enable Error Out If selected, enables the ERROR OUT output. This output is set to high level
(TRUE) when an external FBK error is detected.
The Error Out signal is reset in case of one of the following events:
1. Switching on and switching off of system.
2. Activation of the RESET M1 operator.
8540780 • 23/03/2017 • Rev.3181
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
SINGLE OSSD (safety output)
SINGLE OSSD safety output uses semiconductor
technology and do not require maintenance,
Output1 supplies 24Vdc if the In is 1 (TRUE) and
vice versa 0Vdc if the In is 0 (FALSE).
Each SINGLE OSSD output has a relative
RESTART_FBK input. This input must always
be connected as indicated in the
RESTART_FBK paragraph.
Parameters
Output Type: There is a choice of 2 different output type:
Single Output Type
Double Output Type
Using one MO4LHCS8 module, the operator can choose between different configurations:
1. Four SINGLE OUTPUTS function blocks (single output type)
2. Two SINGLE OUTPUTS function blocks (double output type)
3. Two SINGLE OUTPUTS function blocks (single output type) + one SINGLE OUTPUTS function
block (double output type)
Example of project
2 single output type function blocks + 1 double output type function blocks
82 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
t = 250ms
5s > t1 > 250ms
t2 = 250ms
Configuration with 2 dual channel
outputs (safety category 4)
Configuration with 4 single outputs
(safety category 4)
Here below you can find the explanation of the four MO4LHCS8 Single OSSDs configuration.
Manual Reset: If selected this enables the request to reset each time the input signal falls.
Otherwise, output enabling directly follows In input conditions.
There are two types of reset: Manual and Monitored. In selecting the Manual option only signal
transition from 0 to 1 is verified. If the Monitored option is selected, the double transition from 0
to 1 and back to 0 is verified.
Enable Status: If selected, enables the connection of the current OSSD state to any point on the
screen.
K external time check: If selected, enables the setting of the time window within which the external
feedback signal is to be monitored (according to output conditions).
With high level (TRUE) OUTPUT, the FBK signal must be at low level (FALSE) and vice versa, within
the set time.
Otherwise, OUTPUT is set to low level (FALSE) and the error is indicated on the master M1 by the
flashing CLEAR LED corresponding to the OSSD in error.
8540780 • 23/03/2017 • Rev.3183
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
Example of OSSD with correct Feedback signal:
In this case ERROR OUT=FALSE
Example of OSSD with incorrect Feedback signal
(k external time exceeded):
In this case ERROR OUT=TRUE
Enable Error Out If selected, enables the ERROR OUT output. This output is set to high level
(TRUE) when an external FBK error is detected.
The Error Out signal is reset in case of one of the following events:
3. Switching on and switching off of system.
4. Activation of the RESET M1 operator.
STATUS (signal output)
STATUS output (NOT SAFETY OUTPUT) makes it possible
to monitor any point on the diagram by connecting it to
the input. The output returns 24Vdc if the input is 1
(TRUE), or 0Vdc if the input is 0 (FALSE).
WARNING: The STATUS output is NOT a safety
output.
FIELDBUS PROBE
Element that permits display of the status of any point
of the scheme on the fieldbus.
Up to 16 probes can be inserted and the bit on which
status is represented must be entered for each.
States are represented with 2 bytes on the fieldbus.
(For more detailed information, consult the fieldbus
manual on the MSD CD-ROM).
WARNING: the PROBE output is NOT a safety output
84 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
RELAY
The Output relay is a N.O. relay output. Relay outputs are closed when the input IN is
equal to 1 (TRUE), otherwise they are open (FALSE).
Parameters
Category There is a choice of 3 different relay
output categories:
Category 1. Outputs with single Category 1 relay. Each
MOR4/S8 unit may have up to 4 of these outputs.
Features:
• Internal relays are monitored.
• EDM feedback (check of FBK 1-4) not used (not
requested for Category 1).
• Each output can be set as AUTO or MANUAL RESTART.
Example with external relay Example with the internal relay only
Category 2. Outputs with single Category 2 relay with OTE outputs. Each MOR4/S8 unit can have
up to 4 of these outputs.
Features:
• Internal relays are always monitored.
• Monitored EDM feedback.
• The output can be configured to Manual or Automatic
restart. The EDM feedback monitor cannot be activated
with the manual restart. To monitor the EDM feedback
must be confi- gured automatic restart. In this case, if
you want to use the manual restart shall be provided a
dedicated logic. Refer to the following note.
(Output Test Equipment)
OTE (Output Test Equipment) is activated; this is necessary with configurations of category 2 for
the reporting of hazardous failures in accordance with EN 13849-1: 2006 / DAM1 (under
development).OTE output: normally ON. In case of fault of internal feedback or EDM => OFF.
This permits to inform the machine logic, with the aim of stopping the dangerous movement or at
least signaling the fault to the user.
OTE: The OTE (Output Test Equipment) output is normally 1 (TRUE) exept in the case of an internal
error or a fault associated with feedback from the external contactors (FALSE).
8540780 • 23/03/2017 • Rev.3185
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
Example of use with only the internal relay and
monitored solenoid valves.
Example of use with external contactors with feedback.
Use with RESTART: Automatic (A) or Manual (B) (Category 2)
Figure 55
Category 4. Outputs with two Category 4 relays. Each
MOR4/S8 unit can have up to 2 of these outputs.
With this output the relays are controlled in pairs.
Features:
• 2 double channel outputs.
• Double internal relays are monitored.
• Each output can be set as AUTO or MANUAL
RESTART.
In order to not affect the outcome of the calculation of the PL, the inputs (sensors or safety
devices) must be of a category equal to or higher than the other devices in the chain.
86 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
Example of RELAY with correct Feedback signal:
In this case ERROR OUT=FALSE
Example of RELAY with incorrect Feedback signal
(k external time exceeded):
In this case ERROR OUT=TRUE
RELAY
External K delay (ms): Select the Maximum delay the external contactors are allowed to
introduce. This value can be used to check the maximum delay between switching of the
internal relays and switching of the external contactors (during both activation and
deactivation).
Manual Reset: If selected this enables the request to reset each time the IN input signal
falls. Otherwise, the output is enabled directly according to the condition of the IN input.
There are two types of reset: Manual and Monitored. When Manual is selected the system
transition from 0 to 1 and then back to 0 is verified.
Enable Status: If selected, enables the connection of the current RELAY state to any point
on the screen.
Enable reading of external K: When this is selected it enables reading and verification of
external contactor switching times:
With Category 1 control of external contactors cannot be enabled.
With Category 4 control of external contactors is mandatory (always enabled).
Enable Error Out If selected, enables the ERROR OUT output. This output is set to high level
(TRUE) when an external FBK error is detected.
The Error Out signal is reset in case of one of the following events:
1. Switching on and switching off of system.
2. Activation of the RESET M1 operator.
8540780 • 23/03/2017 • Rev.3187
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
t = 250ms
t1 > 250ms
t2 = 250ms
INPUT OBJECTS
E-STOP (emergency stop)
E-STOP function block verifies an emergency stop
device inputs status. If the emergency stop button
has been pressed the output is 0 (FALSE). If not the
output is 1 (TRUE).
Parameters
Input type:
- Single NC allows connection of one-way
emergency stops
- Double NC allows connection of two-way
emergency stops .
Manual reset: If selected this enables the request to
reset each time the emergency stop is activated.
Otherwise, enabling of the output directly follows
the input conditions.
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double
transition from 0 to 1 and then back to 0 is verified.
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 and Input 2 are used for the fuctional block, then Input 3 have to
be used for the Reset Input.
Output test: This is used to select which test output signals are to be sent to the
emergency stop (mushroom pushbutton). This additional test makes it possible to detect
and manage any short-circuits between the lines. This additional control permits
detection and management of any short-circuits between the lines. To enable this
control, the test output signals must be configured (amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component
(emergency stop). This test is performed by pressing and releasing the pushbutton to run
a complete function test and enable the output. This test is only requested at machine
start-up (when the unit is switched on).
88 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
t = 250ms
t1 > 250ms
t2 = 250ms
Filter (ms): This is used to filter the signals coming from the emergency stop. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
With Simultaneity: If selected this activates the test to verify concurrent switching of the
signals coming from the emergency stop.
Simultaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in msecs) between the switching of two different signals from the
emergency stop.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
E-GATE (safety gate device)
E-GATE function block verifies a mobile
guard or safety gate device input status. If
the mobile guard or safety gate is open,
the output is 0 (FALSE). Otherwise the
output is 1 (TRUE).
Parameters
Input type:
- Double NC Allows connection of
components with two NC contacts
- Double NC/NO Allows connection of
components with one NO contact and one
NC.
With inactive input (block with Output
FALSE), connect:
- Contact NO to terminal corresponding
to IN1.
- Contact NC to terminal corresponding
to IN2.
Enable reset: If selected this enables the request to reset each time the mobile
guard/safety gate is activated. Otherwise, enabling of the output directly follows the
input conditions.
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double
transition from 0 to 1 and then back to 0 is verified.
8540780 • 23/03/2017 • Rev.3189
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
t = 250ms
t1 > 250ms
t2 = 250ms
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 and Input 2 are used for the fuctional block, then Input 3 have to
be used for the Reset Input.
Output test: This is used to select which test output signals are to be sent to the
component contacts. This additional control permits detection and management of any
short-circuits between the lines. To enable this control, the test output signals must be
configured (amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by opening the mobile guard or safety gate to run a complete
function test and enable the output. This test is only requested at machine start-up
(when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
With Simultaneity: If selected this activates the test to verify concurrent switching of the
signals coming from the external contacts.
Simultaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in msecs) between the switching of two different signals from the
external contacts.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
SINGLE E-GATE (safety gate device)
SINGLE E-GATE function block verifies a
mobile guard or safety gate device input
status. If the mobile guard or safety gate is
open, the output is 0 (FALSE). Otherwise the
output is 1 (TRUE).
Parameters
Enable reset: If selected this enables the
request to reset each time the mobile
guard/safety gate is activated. Otherwise,
enabling of the output directly follows the
input conditions.
There are two types of reset: Manual and
Monitored. When Manual is selected the system only verifies the signal's transition from 0
to 1. If Monitored is selected the double transition from 0 to 1 and then back to 0 is
verified.
90 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 and Input 2 are used for the fuctional block, then Input 3 have to
be used for the Reset Input.
Output test: This is used to select which test output signals are to be sent to the
component contacts. This additional control permits detection and management of any
short-circuits between the lines. To enable this control, the test output signals must be
configured (amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by opening the mobile guard or safety gate to run a complete
function test and enable the output. This test is only requested at machine start-up
(when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
LOCK FEEDBACK
The function block LOCK FEEDBACK verifies
the lock status of the guard lock device for
mobile guard or safety gate. In the case where
the inputs indicate that the guard is locked
the Output will be 1 (TRUE). Otherwise the
output is 0 (FALSE).
Parameters
Input type
- Single NC Allows connection of
components with one NC contact;
- Double NC Allows connection of
components with two NC contacts.
- Double NC/NO Allows connection of
components with one NO contact and one NC.
With inactive input (guard unlocked), connect:
- Contact NO to terminal corresponding to IN1
- Contact NC to terminal corresponding to IN2.
Output test: This is used to select which test output signals are to be sent to the
component contacts. This additional control permits detection and management of any
short-circuits between the lines. To enable this control, the test output signals must be
configured (amongst those available).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
With Simultaneity: If selected this activates the test to verify concurrent switching of the
signals coming from the external contacts.
8540780 • 23/03/2017 • Rev.3191
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
t = 250ms
t1 > 250ms
t2 = 250ms
Simultaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in msecs) between the switching of two different signals from the
external contacts.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
ENABLE (enable key)
ENABLE function block verifies a manual key
device Input status. If the key is not turned the
output is 0 (FALSE). Otherwise the output is 1
(TRUE).
Parameters
Input type
- Single NO Allows connection of
components with one NO contact;
- Double NO Allows connection of
components with two NO contacts.
Enable reset: If selected this enables the
request to reset each time the command is
activated. Otherwise, enabling of the output
directly follows the input conditions.
There are two types of reset: Manual and
Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1.
If Monitored is selected the double transition from 0 to 1 and then back to 0 is verified.
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 and Input 2 are used for the fuctional block, then Input 3 have to
be used for the Reset Input.
92 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
t = 250ms
t1 > 250ms
t2 = 250ms
Output test: This is used to select which test output signals are to be sent to the
component contacts. This additional control permits detection and management of any
short-circuits between the lines. To enable this control, the test output signals must be
configured (amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by opening and activating the enable key to run a complete
function test and enable the output. This test is only requested at machine start-up
(when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
With Simultaneity: If selected this activates the test to verify concurrent switching of the
signals coming from the external contacts.
Simultaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in msecs) between the switching of two different signals from the
external contacts.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
ESPE function block verifies an optoelectronic
safety light curtain (or laser scanner) inputs
state. If the area protected by the light curtain
is occupied, (light curtain outputs FALSE) the
output is 0 (FALSE). Otherwise, with the area
clear and outputs to 1 (TRUE) the output is 1
(TRUE).
Parameters
Enable reset: If selected this enables the
request to reset each time the area protected
by the safety light curtain is occupied.
Otherwise, enabling of the output directly
follows the input conditions.
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double
transition from 0 to 1 and then back to 0 is verified.
8540780 • 23/03/2017 • Rev.3193
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 and Input 2 are used for the fuctional block, then Input 3 have to
be used for the Reset Input.
OUT TEST signals cannot be used in case of safety static output ESPE because the control
is carried out from the ESPE.
Test at start-up: If selected this enables the test at start-up of the safety light curtain.
This test is performed by occupying and clearing the area protected by the safety light
curtain to run a complete function test and enable the output. This test is only requested
at machine start-up (when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the safety light curtain. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
Simultaneity (ms): always active. Determines the maximum permissible time (msec)
between switching of the various signals from the external contacts of the device.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
FOOTSWITCH (safety pedal)
The FOOTSWITCH function block verifies the
status of the inputs of a safety pedal device. If
the pedal is not pressed the output is 0
(FALSE). Otherwise the output is 1 (TRUE).
Parameters
Input type:
- Single NC Allows connection of pedals
with one NC contact
- Single NO Allows connection of pedals
with one NO contact.
- Double NC Allows connection of pedals
with two NC contacts
- Double NC/NO Allows connection of
pedals with one NO contact and one NC.
With inactive input (block with Output
FALSE), connect:
- Contact NO to terminal corresponding to IN1
- Contact NC to terminal corresponding to IN2.
94 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
t = 250ms
t1 > 250ms
t2 = 250ms
Manual reset: If selected this enables the request to reset each time the safety pedal is
activated. Otherwise, enabling of the output directly follows the input conditions.
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double
transition from 0 to 1 and then back to 0 is verified.
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 and Input 2 are used for the fuctional block, then Input 3 have to
be used for the Reset Input.
Output test: This is used to select which test output signals are to be sent to the
component contacts. This additional control permits detection and management of any
short-circuits between the lines. To enable this control, the test output signals must be
configured (amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by pressing and releasing the footswitch to run a complete
function test and enable the output. This test is only requested at machine start-up
(when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
With Simultaneity: If selected this activates the test to verify concurrent switching of the
signals coming from the external contacts.
Simultaneity (ms): This is only active if the previous parameter is enabled. It defines the
maximum time (in msecs) between the switching of two different signals from the
external contacts.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
8540780 • 23/03/2017 • Rev.3195
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
t = 250ms
t1 > 250ms
t2 = 250ms
MOD-SEL (safety selector)
The MOD-SEL function block verifies the status
of the inputs from a mode selector (up to 4
inputs): If only one input is 1 (TRUE) the
corresponding output is also 1 (TRUE). In all
other cases, and thus when all inputs are 0
(FALSE) or more than one input is 1 (TRUE) all the
outputs are 0 (FALSE).
Parameters
Input type:
- Double selector Allows connection of two-
way mode selectors.
- Triple selector Allows connection of three-way mode selectors.
- Quadruple selector - Allows connection of four-way mode selectors.
Filter (ms): This is used to filter the signals coming from the mode selector. The filter can
be configured to between 3 and 250 ms and eliminates any bouncing on the contacts.
The length of the filter affects the calculation of the unit's total response time.
Simultaneity (ms): always active. Determines the maximum permissible time (msec)
between switching of the various signals from the external contacts of the device.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
PHOTOCELL (safety photocell)
The PHOTOCELL function block verifies the
status of the inputs of an optoelectronic safety
photocell. If the beam of the photocell is
occupied (photocell output FALSE) the output is
0 (FALSE). Otherwise with the beam clear and an
output of 1 (TRUE) the output is 1 (TRUE).
Parameters
Manual reset: If selected this enables the
request to reset each time safety photocell is
activated. Otherwise, enabling of the output
directly follows the input conditions.
There are two types of reset: Manual and
Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1.
If Monitored is selected the double transition from 0 to 1 and then back to 0 is verified.
An output test signal is mandatory and can be selected from the 4 possible Test
Output 1 ÷ 4.
If the Manual Reset is active, a consecutive Input have to be used. Example: Input 1
is used for the functional block, then Input 2 have to be used for the Reset Input.
96 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
The response time of the photocell must be >2ms and <20ms.
Output test: This is used to select which test output are to be sent to the photocell test
input. This additional control permits detection and management of any short-circuits
between the lines. To enable this control, the test output signals must be configured
(amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by occupying and clearing the photocell to run a complete function
test and enable the output. This test is only requested at machine start-up (when the unit
is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
TWO-HAND (bimanual control)
The TWO HAND function block verifies the
status of the inputs of a two hand control
switch. Only if both the press-buttons are
pressed within 500 msec the output is 1
(TRUE). Otherwise the output is 0 (FALSE).
Input type:
- Double NO Allows connection of two-hand
switch with one NO contact for each button
(EN 574 III A).
- Quadruple NC-NO - Allows connection of
two-hand switch with a double NO/NC
contact for each button (EN 574 III C).
With inactive input (block with Output FALSE), connect:
- Contact NO to terminal corresponding to IN1
- Contact NC to terminal corresponding to IN2.
Output test: This is used to select which test output signals are to be sent to the
component contacts. This additional control permits detection and management of any
short-circuits between the lines. To enable this control, the test output signals must be
configured (amongst those available).
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by pressing the two buttons (within 500 msec) and releasing them
to run a complete function test and enable the output. This test is only requested at
machine start-up (when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the mode selector. The filter can
be configured to between 3 and 250 ms and eliminates any bouncing on the contacts.
The length of the filter affects the calculation of the unit's total response time.
8540780 • 23/03/2017 • Rev.3197
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
t = 250ms
t1 > 250ms
t2 = 250ms
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
NETWORK_IN
This functional block implements a Network
connection input interface; it generates an LL1
in the OUT output when the line is high,
otherwise an LL0.
Parameters
Type of input:
- Single - enables the connection of Signaling outputs of an additional M1 unit.
- Double - enables the connection of OSSD outputs of an additional M1 unit.
Filter (ms): Enables the filtering of signals from an additional M1 unit.
This filter can be set to between 3 and 250 ms. The length of the filter affects the
calculation of the unit's total response time.
This input can only be allocated on M1.
This input must be used when Mosaic OSSD outputs are connected to the inputs of a
second downstream Mosaic or together with the NETWORK operator.
SENSOR
The SENSOR function block verifies the status of
the input of a sensor (not a safety sensor). If the
beam of the sensor is occupied (sensor output
FALSE) the output is 0 (FALSE). Otherwise, with
the beam clear and an output of 1 (TRUE) then
the output is 1 (TRUE).
Parameters
Manual reset: If selected this enables the request
to reset each time the area protected by the
sensor is occupied. Otherwise, enabling of the
output directly follows the input conditions.
There are two types of reset: Manual and
Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If
Monitored is selected the double transition from 0 to 1 and then back to 0 is verified.
98 8540780 • 23/03/2017 • Rev.31
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
English
t = 250ms
t1 > 250ms
t2 = 250ms
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 is used for the fuctional block, then Input 2 have to be used for
the Reset Input.
Output test: This is used to select which test output signals are to be sent to the
sensor. This additional control permits detection and management of any short-circuits
between the lines. To enable this control, the test output signals must be configured
(amongst those available).
Test at start-up: If selected this enables the test at start-up of the sensor. This test is
performed by occupying and clearing the area protected by the sensor to run a complete
function test and enable the output. This test is only requested at machine start-up
(when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the sensor. The filter can be
configured to between 3 and 250 ms and eliminates any bouncing on the contacts. The
length of the filter affects the calculation of the unit's total response time.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
S-MAT (safety mat)
The S-MAT function block verifies the status of
the inputs of a safety mat. If a person stands
on the mat the output is 0 (FALSE). Otherwise,
with the mat clear, the output is 1 (TRUE).
Parameters
Manual reset: If selected this enables the
request to reset each time the mobile
guard/safety gate is activated. Otherwise,
enabling of the output directly follows the
input conditions.
There are two types of reset: Manual and
Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1.
If Monitored is selected the double transition
from 0 to 1 and then back to 0 is verified.
If the Manual Reset is active, a consecutive Input have to be used. Example: Input 1
and Input 2 are used for the fuctional block, then Input 3 have to be used for the
Reset Input.
8540780 • 23/03/2017 • Rev.3199
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
english
t = 250ms
t1 > 250ms
t2 = 250ms
Two output test signals are mandatory. Each output OUT TEST can be connected to
only one input S-MAT (it is not allowed parallel connection of 2 inputs).
The function block S-MAT can not be used with 2-wire components and termination
resistance.
Output test: This is used to select which test output signals are to be sent to the s-mat
contact. This additional control permits detection and management of any short-circuits
between the lines. To enable this control, the test output signals must be configured
(amongst those available). Test signals are mandatory.
Test at start-up: If selected this enables the test at start-up of the external component.
This test is performed by pressing and releasing the safety mat to run a complete
function test and enable the output. This test is only requested at machine start-up
(when the unit is switched on).
Filter (ms): This is used to filter the signals coming from the external contacts. The filter
can be configured to between 3 and 250 ms and eliminates any bouncing on the
contacts. The length of the filter affects the calculation of the unit's total response time.
Enable Error Out: If selected reports a fault detected by the function block.
Item description: This allows a description of the component's function to be entered. The
text is displayed in the top part of the symbol.
SWITCH
SWITCH function block verifies the input status
of a pushbutton or switch (NOT SAFETY
SWITCHES). If the pushbutton is pressed the
output is 1 (TRUE). Otherwise, the output is 0
(FALSE).
Parameters
Manual reset: If selected this enables the request
to reset each time the device is activated.
Otherwise, enabling of the output directly follows
the input conditions.
There are two types of reset: Manual and
Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1.
If Monitored is selected the double transition from 0 to 1 and then back to 0 is verified.
WARNING: If the Manual Reset is active, a consecutive Input have to be used.
Example : Input 1 is used for the fuctional block, then Input 2 have to be used for
the Reset Input.
Output test: This is used to select which test output signals are to be sent to the switch.
100 8540780 • 23/03/2017 • Rev.31
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.