VDE 0413-7, IEC 61557-7/EN 61557-7
Operating voltage: Multiple connections: 40 to 600V AC
between phases;
Single connection: 120 to 400V AC
between phases
Power supply: 9V alkaline, IEC 6LR61
Power consumption: Max 20 mA
Battery life: Minimum 1 year of average use
Dimensions: 128 x 68 x 30mm
Weight: 185g
Includes: 3 test leads, 3 alligator clips,
and one 9V battery
Rotary Field Direction
Nominal voltage rotary direction: 1 to 400V AC
Nominal voltage phase indirection: 120 to 400V AC
Frequency range: 2 to 400HZ
Test currents (in per phase): <3.5mA
Non-contact rotary eld indication frequency range:
2 to 400HZ
Motor Connection
Nominal test voltage (U me): 1 to 400V AC
Nominal test currents (In per phase): Less than 3.5mA
Frequency range (fn): 2 to 400HZ
www
reedinstruments
www.GlobalTestSupply. com
com
4
Instrument Description
1. Test lead input jack
2. L1, L2, L3 indicators
3. Clockwise rotation
LCD indicator
4. Counter-clockwise
rotation LCD indicator
5. ON/OFF button
6. ON/OFF indicator
7. Orientation symbol
Operating Instructions
Determining the Rotary Field Direction
1. Connect one end of the test leads to the meter. Make sure the L1,
L2, and L3 test leads are connected to the corresponding input
jacks.
2. Connect the test probes to the other end of the test leads.
3. Connect the test probes to the three main phases. Press the ON/
OFF button. The green ON indicator shows that the instrument
is ready for testing. Either the Clockwise or Counter Clockwise
Rotary indicator will illuminate showing the type of rotary eld
direction present.
4. The rotary indicator will light up even if the neutral conductor, N,
is connected instead of the test lead input jack. See Phase
Indication Table for more information.
www
reedinstruments
www.GlobalTestSupply. com
com
5
Phase Indication Table
Non-contact Rotary Field Indication
1. Disconnect all test leads from the unit.
2. Position the unit on the motor so that it is parallel to the length
of the motor shaft. The unit should be one inch or closer to the
motor, and the bottom of the unit should be oriented towards the
drive shaft. See Figure 1.
3. Press the ON/OFF button. The green ON indicator shows that the
instrument is ready for testing.
4. Either the Clockwise or Counter Clockwise Rotary indicator will
illuminate showing the type of rotary eld direction present.
Note: The indicator will not operate with engines controlled by frequency
converters.
(Figure 1) Motor Rotation
www
reedinstruments
www.GlobalTestSupply. com
com
6
Motor Test Requirements
See below for the minimum motor diameter and number of pole pair
needed to obtain a reliable test result.
•Number of pole pair
•Rotary number of rotary eld (1/min) at frequency (HZ)
•Angle between poles
•Minimum diameter of motor case
Determining the Motor Connection
1. Connect one end of the test leads to the unit. Make sure the L1,
L2, and L3 test leads are connected to the corresponding jack.
2. Connect the alligator clamps to the other end of the test leads.
3. Connect the alligator clamps to the motor connections, L1 to U,
L2 to V, L3 to W.
4. Press the ON/OFF button. The green ON indicator shows that the
instrument is ready for testing.
5. Turn the motor shaft half a revolution towards the right.
6. The bottom of this unit should be oriented towards the drive shaft.
Either the Clockwise or Counter Clockwise Rotary indicator will
illuminate showing the type of rotary eld direction present.
Magnetic Field Detection
To detect a magnetic eld, place this unit to a solenoid valve. A magnetic
eld is present if either the Clockwise or the Counter Clockwise Rotary
indicator illuminates.
www
reedinstruments
www.GlobalTestSupply. com
com
7
Battery Replacement
If this unit does not turn on, or shuts off during use, the battery needs to
be replaced. To replace the battery, follow these steps.
1. Place this unit face down on a nonabrasive surface and loosen the
battery-door screw with a screwdriver.
2. Lift the battery access lid away from the unit.
3. Remove the battery and replace with new 9V batteries. Observe
the battery polarity shown in the battery compartment.
4. Secure the battery access lid back in position with the screw.
If the unit continues to malfunction, please contact REED Instruments at
info@reedinstruments.com
Notes _________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________
________________________________________________