MODEL NT100 SERIES – UNMANAGED INDUSTRIAL ETHERNET SWITCHES
 UNMANAGED SWITCH REQUIRES NO CONFIGURATION  SUPPORTS 10/100 MBPS NETWORKS  AUTO HALF/FULL DUPLEX NEGOTIATION  REDUNDANT POWER INPUTS  AUTO-CROSSING DETECTION SUPPORTS STANDARD AND
CROSSOVER ETHERNET CABLES
C
LISTED
U
R
FOR USE IN HAZARDOUS LOCATIONS:
US
L
Class I, Division 2, Groups A, B, C, and D or unclassified or non-hazardous locations only.
65SN
GENERAL DESCRIPTION
The NT series is a range of compact IEEE 802.3 layer two network switches with automatic speed, duplex and cable sensing. The series features ultra-robust construction, capable of withstanding environmental extremes for use in mission critical applications.
These affordable, Class I, Division 2 switches feature redundant power inputs, hardened metal enclosures, and 16 kV port protection. Each switch is capable of auto negotiating 10/100 Mb and half/full duplex communications.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
For 108TX: Use 60/75°C rated copper wire, (0.22Nm) 2 inch-lbs. tightening
For 104TX & 105TX: Use 95°C rated copper wire, (0.22Nm) 2 inch-lbs.
EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR AREA IS KNOWN TO BE NON-HAZARDOUS.
torque for field installed connectors.
tightening torque for field installed connectors.
SPECIFICATIONS
1. POWER: 10-30 VDC NT104TX/NT105TX: 215 mA max. @ 24VDC NT108TX: 250 mA max. @ 24VDC
2. LEDs:
3. ENVIRONMENTAL CONDITIONS:
4. CONSTRUCTION: Brushed aluminum housing
5. CONNECTIONS:
6. MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting
7. CERTIFICA TIONS AND COMPLIANCES:
8. WEIGHT:
1
LED COLOR DESCRIPTION
LNK/ACT
ON Power is Applied. OFF Power is OFF. ON Link established, no Activity on cable. BLINKING Link established, Activity on cable OFF No link activity on cable. ON Link is 100Mbps.
SPD
OFF Link is 10Mbs.
Operating Temperature Range: NT104TX/NT105TX: -40 to +80 °C NT108TX: -40 to +70 °C Storage Temperature Range: -40 to +85 °C Operating Humidity: 10-95%, non-condensing Altitude: Up to 3000 meters.
Power: Removable wire clamp screw terminal block. Wire Gage Capacity: 28 AWG to 16 AWG Torque: 2 in/lb (0.22 Nm) Ethernet: RJ-45 UTP ports
rail according to EN50022 -35 x 7.5 and -35 x 15.
UL Listed (N-Tron Incorporated, Part numbers 104TX, 105TX, 108TX. File
#E214222)
Safety: Suitable for use in Class I, Division 2, Groups A, B, C and D
Hazardous locations, or non-hazardous locations only.
Immunity to Industrial Locations:
EMI: EN61000-6-4, EN55011 - Class A
FCC Title 47, Part 15, Subpart B - Class A ICES-003 – Class A
EMS: EN61000-6-2
EN61000-4-2 (ESD) EN61000-4-3 (RS) EN61000-4-4 (EFT) EN61000-4-5 (Surge) EN61000-4-6 (Conducted Disturbances)
NT104TX/NT105TX: 0.6 lbs. (0.27 Kg) NT108TX0: 0.7 lbs. (0.31 Kg)
DIMENSIONS In inches (mm)
Powered by
1.49
(37.85)
PWR
Powered by
1.49
(37.85)
PWR
1
2 3
4 5
2.87
(72.90)
104TX
1 2
3 4
2.87
(72.90)
105TX
DIMENSIONS In inches (mm)
Powered by
3.50
(88.90)
PWR
1 2
3 4
4.22
(107.19)
3.53
(89.62)
4.22 (107.19)
3.97 (100.95)
3.53 (89.62)
3.17
(80.52)
3.50
(88.90)
5 6
7 8
3.53
(89.62)
108TX
1.49
(37.85)
POWER
Either V1 or V2 can be connected to power for minimal operation. For redundant power operation, V Voltage sources. Use wire sizes of 16-28 gauge.
NOTE: Must use an NEC Class 2 or Limited
Power Source (LPS) rated power supply.
and V2 plugs must be connected to separate DC
1
3.80
(96.52)
1.71
(43.43)
MOUNTING
To install the plastic clip units to 35mm industrial DIN rail, place the top edge of the included mounting bracket on the back of the unit against the DIN rail at a 15° angle as shown. Rotate the bottom of the unit to the back (away from you) until it snaps into place.