! LARGE LED DISPLAY READABLE TO 70 FEET
! VARIOUS ANALOG INPUT MODULES;
DC VOLTAGE AND CURRENT PROCESS SIGNALS TRUE RMS VOLTAGE AND CURRENT THERMOCOUPLE OR RTD STRAIN GAGE/BRIDGE
! CUSTOM UNITS LABEL WITH BACKLIGHT
! PROGRAMMABLE USER INPUTS
! PROGRAMMABLE FUNCTION KEYS
! UNIVERSAL AC/DC POWERED MODELS
! CRIMSON PROGRAMMING SOFTWARE
! NEMA 4/IP65
GENERAL DESCRIPTION
The LPAX Display is a versatile display that can increase productivity by offering the plant floor or production area a large visual display of their current status. Whether your measurement is temperature, weight, or flow, the LPAX can satisfy your requirement. With the use of a units label and backlighting, the display can be tailored to show the actual engineering unit, which further enhances the display. This LPAX display accepts various analog inputs through the use of input modules (MPAX) which allow the unit to adapt to most any application. The MPAX Modules offer the same features as our highly successful PAX Series Panel Meters. Additional plug-in option cards can add alarms, analog output, and communication/bus capabilities, making the LPAX a truly Intelligent Panel Meter.
SAFETY SUMMARY
All safety regulations, local codes and instructions that appear in this and corresponding literature, or on equipment, must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
The protective conductor terminal is bonded to conductive parts of the equipment for safety purposes and must be connected to an external protective earthing system.
SPECIFICATIONS
Additional specifications, wiring, programming, and information for the individual MPAX models are contained in the corresponding standard PAX literature. This PAX literature is shipped with the ordered MPAX model.
1. DISPLAY: 1.5" (38 mm) Red LED 5-Digit: (-19999 to 99999)
2. POWER REQUIREMENTS: AC Modules: 85 to 250 VAC, 50/60 Hz, 18 VA DC Modules: 11 to 36 VDC or 24 VAC ±10%, 50/60 Hz, 14 W
3. INPUT: Accepts analog input modules, see “Selecting your display components.”
4. ANNUNCIATORS: LPAX0500: MAX, MIN, TOT, SP1, SP2, SP3, and SP4 Optional units label with backlight
5. KEYPAD: Five tactile membrane switches integrated into the front panel
6. CERTIFICATIONS AND COMPLIANCES: UL Recognized Component, File #E179259, UL61010A-1, CSA 22.2 No. 1010-1
Recognized to US and Canadian requirements under the Component Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File # E137808, UL508, CSA C22.2 No. 14-M95
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards Type 4 Enclosure rating (Face only), UL50 IECEE CB Scheme Test Certificate #US/8843/UL
CB Scheme Test Report #04ME11209-20041018
Issued by Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
EMC specifications determined by the MPAX module.
MODEL LPAX- 5 DIGIT LARGE PAX DISPLAY FOR ANALOG INPUTS
DIMENSIONS In inches (mm)
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
PANEL CUT-OUT
Bulletin No. LPAX-D
Drawing No. LP0489
Released 12/05
C
US LISTEDUS LISTED
U
L
R
IND. CONT. EQ.
51EB
2
WARNING: Disconnect all power to the unit before
installing Plug-in cards.
Adding Option Cards
The MPAX series meters can be fitted with up to three optional plug-in cards. However, only one card from each function type can be installed at a time. The function types include Setpoint Alarms (PAXCDS), Communications (PAXCDC), and Analog Output (PAXCDL). The cards can be installed initially or at a later date. Each optional plug-in card is shipped with installation and programming instructions.
COMMUNICATION CARDS (PAXCDC)
A variety of communication protocols are available for the PAX and MPAX series. Only one of these cards can be installed at a time. When programming the unit via Crimson, a Windows®based program, the RS232 or RS485 Cards must be used.
*Units available in various connector configurations.
SETPOINT CARDS (PAXCDS)
The MPAX series has four setpoint alarm output plug-in cards. Only one of these cards can be installed at a time. (Logic state of the outputs can be reversed in the programming.) These plug-in cards include:
PAXCDS10 - Dual Relay, FORM-C, Normally open & closed PAXCDS20 - Quad Relay, FORM-A, Normally open only PAXCDS30 - Isolated quad sinking NPN open collector PAXCDS40 - Isolated quad sourcing PNP open collector
LINEAR DC OUTPUT (PAXCDL)
Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available from the analog output plug-in card. The programmable output low and high scaling can be based on the input, max, min, or total display value. Reverse slope output is possible by reversing the scaling point positions.
PAXCDL10 - Retransmitted Analog Output Card
UNITS LABEL (LX)
The LPAX Display has an area on the front panel designed for a custom units label. The units label is applied directly to the panel in the embossed area. The units backlight is then turned on via programming.
Available on 5-digit version only. Refer to the LPAX Accessories Bulletin for a list of available units labels.
PROGRAMMING SOFTWARE (CRIMSON)
Crimson is a Windows®based program that allows configuration of the LPAX meter from a PC. Crimson offers standard drop-down menu commands, that make it easy to program the LPAX meter. The LPAX program can then be saved in a PC file for future use. A PAX serial plug-in card is required to program the meter using the software.
MPAX MODULES *
SIGNAL TYPE INPUT RANGES
85-250 VAC 11 to 36 VDC/ 24 VAC
LPAX DISPLAYS
Universal DC Inputs MPAXD000 MPAXD010 LPAX0500
Process Inputs 0-20 mA or 0-10 VDC MPAXP000 MPAXP010 LPAX0500
Temperature Inputs
Thermocouples-T, E, J, K, R, S, B, N, C, or Custom Scaling RTD’s-100 ohm Pt (platinum) 385/392, 120 ohm Nickel 672, or 10 ohm Copper 427
MPAXT000 MPAXT010 LPAX0500
Strain Gage/ Load Cell 24 mV or 240 mV MPAXS000 MPAXS010 LPAX0500
True RMS AC Voltage/Current
MPAXH000 N/A LPAX0500
AC Voltage 200 mV, 2 V, 20 V, 300 V AC Current 200 uA, 2 mA, 20 mA, 200 mA, 5 Amp
DC Voltage 200 mV, 2 V, 20 V, 300 V DC Current 200 µA, 2 mA, 20 mA, 200 mA, 2 Amp Resistance 100 ohm, 1000 ohm, 10 K ohm
7. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: Determined by the MPAX module Storage Temperature Range: -40 to 60°C Operating and Storage Humidity: 0 to 85% max. RH (non-condensing) Altitude: Up to 2000 meters
8. MOUNTING REQUIREMENTS: Max. panel thickness is 0.375" (9.5 mm) Min. panel thickness for NEMA 4/IP65 sealing is 0.060" (1.57 mm)
9. MODULE INSTALLATION: 24-pin shrouded connector on LPAX engages connector on MPAX module upon installation. Shroud ensures proper alignment by providing a lead-in for the module connector.
10. CONNECTIONS: All wiring connections are made to the MPAX module via high compression cage-clamp terminal blocks. Wiring instructions are provided with the MPAX module.
CAUTION: DISCONNECT ALL POWER BEFORE INSTALLING OR REMOVING MODULE
11. CONSTRUCTION: Steel front panel, enclosure, and rear cover with textured black polyurethane paint for scratch and corrosion resistance protection. Sealed front panel meets NEMA 4/IP65 specifications for indoor use when properly installed. Installation Category II, Pollution Degree 2. Panel gasket and keps nuts included.
12. WEIGHT: 2.7 lbs (1.2 kg) (less module)
*For detailed Module specifications, see corresponding PAX literature. (i.e. For MPAXD specifications, see the PAXD literature)
OPTIONAL PLUG-IN CARDS AND ACCESSORIES
About the MPAX Input Modules
The MPAX Module serves as the input to the LPAX Display. There are several different modules to cover a variety of inputs. The MPAX module provides input scaling which allows the LPAX to display most any engineering unit. Once the MPAX is inserted into the LPAX, the unit has the same functions and capabilities of our PAX Series Intelligent Panel Meters. A full set of PAX programming instructions will be included with the MPAX Module.
Note: The MPAX provides the operating power for the LPAX, therefore you must select either the AC or DC MPAX corresponding with your application and available
power.
Selecting Your Display Components
To build a complete display unit, you will need an LPAX and an MPAX Input Module. The LPAX is only a display and will not operate without an MPAX Module. Please use the following chart to identify the appropriate MPAX Module (including supply power) and LPAX Display that will satisfy your application.
PAXCDC30 - DeviceNet
PAXCDC50 - Profibus-DPPAXCDC2* - RS232 Serial
PAXCDC4* - ModbusPAXCDC1* - RS485 Serial
Loading...