Red Lion G3CN User Manual

Bulletin No. G3CN-E
Drawing No. LP0587
Released 03/14
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL G3CN - CANopen OPTION CARD FOR G3 OPERATOR INTERFACE TERMINALS
Connector (side 2)
mounting holes, 3 plcs.
CONFIGURED USING CRIMSON SOFTWARE (VERSION 2.0 OR
LATER)
DIGITALLY ISOLATED CANOPEN PORT CAPABLE OF
COMMUNICATING WITH ANY CANopen DEVICE
POWERED AND CONFIGURED FROM G3 OPERATOR
INTERFACE TERMINAL
BUILT-IN TERMINATION RESISTOR SELECTABLE THROUGH
JUMPER SETTING
INSTALLATION AND CONNECTION HARDWARE INCLUDED
WITH CARD
GENERAL DESCRIPTION
The G3 proprietary expansion slot provides a high speed, parallel architecture that extends the functionality and flexibility of the G3 series HMI. This approach allows the G3 series to evolve concurrently with the latest advances in communications and standards, without sacrificing performance. This high bandwidth channel has significantly greater throughput when compared to the traditional (external) serial gateway approach.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller.
CONTENTS OF PACKAGE
- G3CN Option Card with pluggable connector
- Cable already attached to G3CN option card
- Hardware pack consisting of three screws and a connector housing for the pluggable connector
- This hardware bulletin
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBER
G3CN G3CN0000
SFCRM2 Crimson 2.0
1
Use this part number to purchase Crimson on CD with a printed
manual, USB cable, and RS-232 cable. Otherwise, download from www. redlion.net/g3.
CANopen option card for G3 operator interfaces with isolated high speed communications ports
1
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, D, HAZARDOUS LOCATIONS, OR NON-HAZARDOUS LOCATIONS ONLY
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.
SFCRM200
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF ANY COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2
1
speCIfICatIOns
1. POWER REQUIREMENTS: Power is supplied to the option card from the main board of your G3 operator interface.
2. COMMUNICATIONS: CANopen Port: The CANopen port has format and baud rates that are
software programmable up to 1M baud and are digitally isolated. This port may be configured for various CANopen protocols. Check www.redlion. net/g3 for currently supported protocols.
Isolation from G3CN Communication ports to G3 operator interface:
1000 VDC for 1 minute.
3. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C Storage Temperature Range: -20 to 80°C Operating and Storage Humidity: 80% maximum relative humidity (non-
condensing) from 0 to 50°C.
Altitude: Up to 2000 meters.
4. CERTIFICATIONS AND COMPLIANCES:
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.
Immunity to Industrial Locations: Reference G3 unit for emissions and
immunity specifications
5. CONSTRUCTION: Installation Category I, Pollution Degree 2.
6. INSTALLATION REQUIREMENTS: Card must be installed inside the rear cover of a G3 operator interface with the hardware provided. See “Installing the G3CN Option Card” for more details.
InstallIng the g3Cn OptIOn Card
INSTALLATION INSTRUCTIONS
Caution: The option and main circuit boards contain static
sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, handle the cards by the edges only. Dirt, oil, or other contaminants that may contact the cards can adversely affect circuit operation.
Figure 2
Warning: Depending upon the G3 operator interface, high voltage
may be present inside the operator interface. Be sure to remove all power before removing the rear cover of the operator interface.
Each G3CN option card comes with a cable for communications and three screws for attaching the option card to the inside of the G3 operator interface's rear cover.
To install the option card, remove all power and I/O communications cables from the unit. The G3 operator interface literature contains instructions for removing the rear cover. Refer to the “Battery & Time Keeping” section.
Using the three screws provided, connect the option card to the rear cover as shown in Figure 1.
Figure 1
Carefully replace the rear cover by reversing the instructions for removing the
rear cover.
THE OPTION CARD LABEL
Place the option card label on your rear cover in the space indicated by the
dashed lines and labeled “COMMS EXPANSION MODULE.”
RS232
COMMS EXPANSION MODULE
RS485
RS232
Connect the cable from the option card to CN11 on the main board of the G3 operator interface as shown in Figure 2. Be sure both ends of the cable are firmly seated into their appropriate connector housings.
POWER SUPPLY REQUIREMENTS
NEW AND EXISTING INSTALLATIONS
The G3CN option card draws all of its power from the main board of your G3 operator interface. The specifications of your G3 operator interface account for the power needs of an option card.
2
COmmunICatIng WIth the g3Cn OptIOn Card
CONFIGURING A G3CN OPTION CARD
The G3CN is configured using Crimson software. Crimson is available as a free download from www.redlion.net/g3, or it can be ordered on CD. Updates to Crimson for new features and drivers are posted on the website as they become available. By configuring the G3CN using the latest version of Crimson, you are assured that your unit has the most up-to-date feature set. Crimson software can configure the G3CN through the RS232 PGM port, USB port, Ethernet port or CompactFlash socket on your G3 operator interface. Additional information can be found in your G3 hardware bulletin and the Crimson user manual.
CANopen PORT PROTOCOLS
The G3CN option card has one CANopen port. This port may be configured for various CANopen protocols. Check www.redlion.net/g3 for currently supported protocols.
G3CN PORT PIN OUTS
Figure 3
TERMINATION RESISTOR
(124 , 1W)
YES
NO
GND
CAN-
CAN+
SHLD (N/C)
TERMINATION
RESISTOR
LED
V+ (N/C)
TERMINATION RESISTOR
An onboard termination resistor is selectable through a jumper setting. The termination resistor is rated for 124 at 1W. If a different termination resistance is desired, choose the jumper setting for no termination resistor. At this point you will be required to connect your own termination resistor between positions 2 and 4 of the five position connector.
CAN GND
Position 1 of the pluggable connector provides a CAN ground connection. This terminal is isolated from the HMI unit.
CAN-
Position 2 of the pluggable connector provides the CAN- bus line (active low). This terminal is isolated from the HMI unit.
SHLD (OPTIONAL CAN SHIELD)
Position 3 of the pluggable connector is provided for optional shield connections. This position is available only to tie shield wires together or to earth ground. There is no internal connection to earth ground. The SHLD position is not connected to any circuitry internal to the G3CN option card or G3 HMI unit.
CAN+
Position 4 of the pluggable connector provides the CAN+ bus line (active high). This terminal is isolated from the HMI unit.
V+ (OPTIONAL 24 VDC)
Position 5 of the pluggable connector is provided for optional 24 VDC connections. This position is available only to tie 24 VDC wires together. The G3CN card neither provides 24 VDC power nor uses 24 VDC power through this connection. The V+ position is not connected to any circuitry internal to the G3CN option card or G3 HMI unit.
+
-
ISOLATING
DC : DC
1CAN GND
4
CAN +
TX/RX
2
CAN -
3
sOftWare/unIt OperatIOn
LED
The LED will illuminate green when the G3CN option card establishes communication with other CANopen devices (RUN). The LED will illuminate red if no communications have been established with other CANopen devices (ERROR).
CRIMSON SOFTWARE
Crimson 2.0 software is available as a free download from www.redlion.net or it can be purchased on a CD, see “Ordering Information” for part number. The latest version of the software is always available from the web site, and updating your copy is free.
TROUBLESHOOTING YOUR G3CN OPTION CARD
If for any reason you have trouble operating, connecting, or simply have questions concerning your new G3CN option card, contact Red Lion’s technical support. For contact information, refer to the back page of this bulletin for phone and fax numbers.
EMAIL: techsupport@redlion.net Web Site: http://www.redlion.net
The Company warrants the products it manufactures against defects in materials and workmanship
LIMITED WARRANTY
for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
Red Lion Controls Headquarters 20 Willow Springs Circle York PA 17406 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839
Red Lion Controls
Europe
Softwareweg 9
NL - 3821 BN Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India 201-B, 2nd Floor, Park Centra Opp 32 Mile Stone, Sector-30
Gurgaon-122002 Haryana, India
Tel +91 984 487 0503
Red Lion Controls
China
Unit 302, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113 3688
Fax +86 21 6113 3683
Loading...