The G310 Operator Interface Terminal combines unique capabilities normally
expected from high-end units with a very affordable price. It is built around a
high performance core with integrated functionality. This core allows the G310
to perform many of the normal features of the Paradigm range of Operator
Interfaces while improving and adding new features.
The G310 is able to communicate with many different types of hardware using
high-speed RS232/422/485 communications ports and Ethernet 10 Base T/100
Base-TX communications. In addition, the G310 features USB for fast downloads
of configuration files and access to trending and data logging. A CompactFlash
socket is provided so that Flash cards can be used to collect your trending and data
logging information as well as to store larger configuration files.
In addition to accessing and controlling of external resources, the G310
allows a user to easily view and enter information. Users can enter data through
the touchscreen or front panel 8-button keypad.
CONTENTS OF PACKAGE
- G310 Operator Interface.
- Panel Gasket.
- This hardware bulletin.
- Template for panel cutout.
- Hardware packet for mounting unit into panel.
- Terminal block for connecting power.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other
actuators not equipped with safeguards. To do so can be potentially harmful to
persons or equipment in the event of a fault to the controller.
WARNING - EXPLOSION HAZARD - SUBSTITUTION
OF ANY COMPONENT MAY IMPAIR SUITABILITY
FOR CLASS I, DIVISION 2
10.4" TFT VGA Display Operator Interface (indoor or
outdoor), Glossy Finish, USB Host, Isolated Comms
10.4" TFT VGA Display Operator Interface (indoor or
outdoor), Glossy Finish, Dual Ethernet, USB Host,
Isolated Comms
G3CFCompactFlash Card
G3RSRS 232/485 Optional Communication CardG3RS0000
G3CNCANopen Optional Communication CardG3CN0000
G3DNDeviceNet Optional Communication CardG3DN0000
G3GSM GSM/GPRS Modem Option Card
G3PBDP Profibus DP Optional Communication CardG3PBDP00
SFCRM Crimson
RS-232 Programming CableCBLPROG0
CBL
USB CableCBLUSB00
Communications Cables
DRDIN Rail Mountable Adapter Products
Replacement Battery
G3FILM Protective FilmsG3FILM10
1
Contact your Red Lion distributor or visit our website for complete selection.
2
Use this part number to purchase Crimson on CD with a printed manual, USB
cable, and RS-232 cable. Otherwise, download for free from www.redlion.net.
3
Antenna (G3QANT00) is NOT included with the card. Must be purchased
separately if needed.
4
Red Lion offers RJ modular jack adapters. Refer to the DR literature for complete
details.
5
Battery type is lithium coin type CR2025
6
Industrial grade two million write cycles. SMART Modular Technologies model
SG9CF (UL Listed Directory Category NWGQ).
7
LED backlight may not be field replaceable. Consult factory.
7
6
3
2
1
4
5
G310C210
G310C230
G310R210
G310R230
G310S210
7
G310S230
G3CFxxxx
G3GSM000
SFCRM
CBLxxxxx
DRxxxxxx
BNL20000
CompactFlash is a registered trademark of CompactFlash Association.
1
SpecificationS
1. POWER REQUIREMENTS:
Must use a Class 2 circuit according to National Electrical Code (NEC),
NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited
Power Supply (LPS) according to IEC 60950-1 or Limited-energy circuit
according to IEC 61010-1.
Power connection via removable three position terminal block.
Supply Voltage:+24 VDC ±20%
G310C/RG310S
Typical Power:16 W16 W
Maximum Power:25 W26 W
Note:
1. The G310’s circuit common is not connected to the enclosure of the
unit. See “Connecting to Earth Ground” in the section “Installing and
Powering the G310.”
2. BATTERY: Lithium coin cell CR2025. Typical lifetime of 10 years.
3. LCD MODULEDISPLAYS:
SIZE10.4-inch10.4-inch10.4-inch
TYPETFTTFTTFT
COLORS32K32K32K
PIXELS640 X 480800 X 600640 X 480
BRIGHTNESS450 cd/m
BACKLIGHT LIFETIME * 70,000 HR typ. 70,000 HR typ. 50,000 HR typ.
BACKLIGHT TYPELEDLEDLED
MODELG310C2G310R2G310S2
2
400 cd/m
2
1000 cd/m
2
* Lifetime at room temperature. Refer to “Display” in the “Software/Unit
Operation” section.
4. 8-KEY KEYPAD: for on-screen menus.
5. TOUCHSCREEN: Resistive analog
6. MEMORY:
On Board User Memory: 32 Mbyte of onboard non-volatile Flash memory.
Memory Card: CompactFlash Type II slot for Type I and Type II
CompactFlash cards.
7. COMMUNICATIONS:
USB Port: Adheres to USB 2.0 specification full speed only via Type B
connection.
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
USB Host Ports: Comply with Universal Serial Bus Specification Rev 2.0.
Support data transfers at full-speed. Hardware over current protected (0.5
A max per port).
Serial Ports: Ports are individually isolated. Format and Baud Rates for each
port are individually software programmable up to 115,200 baud.
PGM Port: RS232 port via RJ12.
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12.
DH485 TXEN: Transmit enable; open collector, VOH = 15 VDC,
VOL = 0.5 V @ 25 mA max.
Note: For additional information on the communications or signal
common and connections to earth ground please see the “Connecting to
Earth Ground” in the section “Installing and Powering the G310.”
Ethernet Ports: 10 BASE-T / 100 BASE-TX
RJ45 jack is wired as a NIC (Network Interface Card). The jack shield is
electrically connected to Earth ground.
A secondary ethernet port (with its own Mac ID) is available as an option.
8. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C
Storage Temperature Range: -20 to 70°C
Operating and Storage Humidity: 80% maximum relative humidity (non-
condensing) from 0 to 50°C.
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
Shock to IEC 68-2-27: Operational 35 g.
Altitude: Up to 2000 meters.
9. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
Safety requirements for electrical equipment for measurement, control, and
laboratory use:
EN 61010-1: General Requirements
RoHS Compliant
UL Listed: File #E179259
UL Hazardous: File #E245515
Type 4X Enclosure rating (Face only)
IP66 Enclosure rating (Face only)
11. CONSTRUCTION: Steel rear metal enclosure with NEMA 4X/IP66
aluminum front plate when correctly fitted with the gasket provided.
Installation Category II, Pollution Degree 2.
12. MOUNTING REQUIREMENTS: Maximum panel thickness is 0.25" (6.3
mm). For NEMA 4X/IP66 sealing, a steel panel with a minimum thickness of
0.125" (3.17 mm) is recommended.
Maximum Mounting Stud Torque: 17 inch-pounds (1.92 N-m)
13. WEIGHT: 5.44 lbs (2.47 Kg)
DIMENSIONS In inches (mm)
12.83 (325.8)2.45 (62)11 .25 (285.8)
9.50
(241.3)
8.25
(209.4)
2
inStallingand poweringthe g310
MOUNTING INSTRUCTIONS
This operator interface is designed for through-panel mounting. A panel cutout diagram and a template are provided. Care should be taken to remove any
loose material from the mounting cut-out to prevent that material from falling
into the operator interface during installation. A gasket is provided to enable
sealing to NEMA 4X/IP66 specification. Install the 14 kep nuts provided and
tighten evenly for uniform gasket compression.
Note: Tightening the kep nuts beyond a maximum of 17 inch-pounds (1.92
N-m) may cause damage to the front panel.
12.25 (311.2)
11.725 (297.8)
6.125 (155.6)
All tolerances ±0.010" (±0.25 mm).
ALL NONINCENDIVE CIRCUITS MUST BE WIRED USING
DIVISION 2 WIRING METHODS AS SPECIFIED IN THE NATIONAL
ELECTRICAL CODE, NFPA 70 FOR INSTALLATION WITHIN THE
UNITED STATES, OR AS SPECIFIED IN THE CANADIAN
ELECTRICAL CODE FOR INSTALLATION IN CANADA.
14X ∅.188 (∅4.8)
8.40
(213.4)
2.975
(75.6)
8.925
(226.7)
CONNECTING TO EARTH GROUND
The chassis ground is not connected to signal common of the unit.
Maintaining isolation between earth ground and signal common is not required
to operate your unit. But, other equipment connected to this unit may require
isolation between signal common and earth ground. To maintain isolation
between signal common and earth ground care must be taken when connections
are made to the unit. For example, a power supply with isolation between its
signal common and earth ground must be used. Also, plugging in a USB cable
may connect signal common and earth ground.
1. USB’s shield may be connected to earth ground at the host. USB’s shield
in turn may also be connected to signal common.
1
POWER SUPPLY REQUIREMENTS
The units require a 24 VDC power supply rated at 26 W. Your unit may draw
considerably less than the rated power depending upon the options being used.
As additional features are used your unit will draw increasing amounts of power.
Items that could cause increases in current are additional communications,
optional communications card, CompactFlash card, and other features
programmed through Crimson.
In any case, it is very important that the power supply is mounted correctly if
the unit is to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not
more than 6 feet (1.8 m) of cable between the supply and the operator
interface. Ideally, the shortest length possible should be used.
– The wire used to connect the operator interface’s power supply should
be at least 22-gage wire. If a longer cable run is used, a heavier gage
wire should be used. The routing of the cable should be kept away from
large contactors, inverters, and other devices which may generate
significant electrical noise.
– A power supply with an NEC Class 2 or Limited Power Source (LPS)
and SELV rating is to be used. This type of power supply provides
isolation to accessible circuits from hazardous voltage levels generated
by a mains power supply due to single faults. SELV is an acronym for
“safety extra-low voltage.” Safety extra-low voltage circuits shall
exhibit voltages safe to touch both under normal operating conditions
and after a single fault, such as a breakdown of a layer of basic
insulation or after the failure of a single component has occurred.
inStalling an option card
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN DISCONNECTED
AND THE AREA IS KNOWN TO BE NON-HAZARDOUS.
Each option card comes with a cable for communications and three
screws for attaching the option card to the G3’s main board.
To install the option card, remove all power and I/O communications
cables from the unit and remove the rear cover. Connect the cable from the
option card to the connector on the main board. Be sure both ends of the
cable are firmly seated into their appropriate connector housings. Use the
three screws provided to mount the option card to the main board as shown
in Figure 1.
Carefully replace the rear cover by reversing the instructions for
removing the rear cover.
TYPICAL EXPANSION CARD INSTALLATION
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT WHILE THE CIRCUIT IS LIVE OR UNLESS THE AREA
IS KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS.
Figure 1
3
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.