Bulletin No. G310-N
Drawing No. LP0581
Released 08/09
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL G310 - GRAPHIC LCD OPERATOR INTERFACE TERMINAL WITH
VGA DISPLAY AND TOUCHSCREEN
CONFIGURED USING CRIMSON® SOFTWARE (VERSION 2.0 OR
LATER)
UP TO 5 RS-232/422/485 COMMUNICATIONS PORTS
(2 RS-232 AND 1 RS-422/485 ON BOARD, 1 RS-232 AND 1
RS-422/485 ON OPTIONAL COMMUNICATIONS CARD)
10 BASE T/100 BASE-TX ETHERNET PORT TO NETWORK
UNITS AND HOST WEB PAGES
USB PORT TO DOWNLOAD THE UNIT’S CONFIGURATION
FROM A PC OR FOR DATA TRANSFERS TO A PC
UNIT’S CONFIGURATION IS STORED IN NON-VOLATILE
MEMORY (8MBYTE FLASH)
COMPACTFLASH® SOCKET TO INCREASE MEMORY CAPACITY
10.4-INCH TFT 256 COLOR VGA 640X480 PIXEL LCD
OUTDOOR UNIT WITH UV RATED OVERLAY AVAILABLE
8-BUTTON KEYPAD FOR ON-SCREEN MENUS
THREE FRONT PANEL LEDS
POWER UNIT FROM 24VDC ±20% SUPPLY
RESISTIVE ANALOG TOUCHSCREEN
LABORATORY EQUIPMENT
63YN
FOR USE IN HAZARDOUS LOCATIONS:
Class I, Division 2, Groups A, B, C, and D
Class II, Division 2, Groups F and G
Class III, Division 2
GENERAL DESCRIPTION
The G310 Operator Interface T erminal combines unique capabilities normally
expected from high-end units with a very affordable price. It is built around a
high performance core with integrated functionality. This core allows the G310
to perform many of the normal features of the Paradigm range of Operator
Interfaces while improving and adding new features.
The G310 is able to communicate with many different types of hardware using
high-speed RS232/422/485 communications ports and Ethernet 10 Base T/100
Base-TX communications. In addition, the G310 features USB for fast downloads
of configuration files and access to trending and data logging. A CompactFlash
socket is provided so that Flash cards can be used to collect your trending and data
logging information as well as to store larger configuration files.
In addition to accessing and controlling of external resources, the G310
allows a user to easily view and enter information. An outdoor version is
available for direct sunlight applications. Users can enter data through the
touchscreen or front panel 8-button keypad.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other
actuators not equipped with safeguards. To do so can be potentially harmful to
persons or equipment in the event of a fault to the controller.
The protective conductor terminal is bonded to conductive
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2/CLASS II, DIVISION 2/CLASS III, DIVISION 2
CAUTION: Risk Of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
CONTENTS OF PACKAGE
- G310 Operator Interface.
- Panel Gasket.
- This hardware bulletin.
- Template for panel cutout.
- Hardware packet for mounting unit into panel.
- Terminal block for connecting power.
ORDERING INFORMATION
MODEL NO.DESCRIPTIONPART NUMBER
Operator Interface for indoor applications only,
textured finish with embossed keys
G310
Operator Interface for indoor or outdoor applications,
glossy finish with UV rated overlay (keys are not
embossed)
G3CFCompactFlash Card
G3RSRS 232/485 Optional Communication CardG3RS0000
G3CNCANopen Optional Communication CardG3CN0000
G3PBDP Profibus DP Optional Communication CardG3PBDP00
G3GSM
SFCRM2 Crimson
G3FILM Protective FilmsG3FILM10
1
Contact your Red Lion distributor or visit our website for complete selection.
2
Use this part number to purchase Crimson on CD with a printed manual, USB
cable, and RS-232 cable. Otherwise, download for free from www.redlion.net.
3
Red Lion offers RJ modular jack adapters. Refer to the DR literature for details.
4
Battery type is lithium coin type CR2025
5
Industrial grade two million write cycles. SMART Modular Technologies model
SG9CF (UL Listed Directory Category NWGQ).
6
For use in non-hazardous locations only.
GSM/GPRS Modem Option Card for G3 operator
6
interface
2
RS-232 Programming CableCBLPROG0
CBL
USB CableCBLUSB00
Communications Cables
DRDIN Rail Mountable Adapter Products
Replacement Battery
G310C Backlight Replacement
G310S Backlight Replacement
5
1
3
4
6
6
G310C000
G310S000
G3CFxxxx
G3GSM000
SFCRM200
CBLxxxxx
DRxxxxxx
BNL20000
CONSULT
FACTORY
CompactFlash is a registered trademark of CompactFlash Association.
1
9.50
(241.3)
12.83 (325.8)
2.2 (55)
11.55 (293.3)
8.27
(210.1)
SPECIFICATIONS
1. POWER REQUIREMENTS:
G310C: +24 VDC ±20% @ 33 W maximum.
G310S: +24 VDC ±20% @ 25 W maximum.
Must use Class 2 or SELV rated power supply.
Power connection via removable three position terminal block.
Notes:
1. The front panel PWR LED indicates power.
2. The G310’s circuit common is not connected to the enclosure of the
unit. See “Connecting to Earth Ground” in the section “Installing and
Powering the G310.”
2. BATTERY: Lithium coin cell. Typical lifetime of 10 years.
3. LCD MODULEDISPLAYS:
MODELG310CG310S
SIZE10.4-inch10.4-inch
TYPETFTTFT
COLORS256 VGA256 VGA
PIXELS640 X 480640 X 480
BRIGHTNESS450 cd/m
BACKLIGHT TYPE
BACKLIGHT LIFE *
50,000 HR TYP.
CCFL
2
2
850 cd/m
LED
50,000 HR TYP.
*Lifetime at room temperature. Refer to “Display” in the “Software/Unit
Operation” section.
4. 8-KEY KEYPAD: for on-screen menus.
5. TOUCHSCREEN: Resistive analog
6. MEMORY:
On Board User Memory: 8 Mbyte of onboard non-volatile Flash memory.
Memory Card: CompactFlash Type II slot for Type I and Type II
CompactFlash cards.
7. COMMUNICATIONS:
USB Port: Adheres to USB specification 1.1. Device only using Type B
connection.
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
Serial Ports: Format and Baud Rates for each port are individually software
programmable up to 115,200 baud.
PGM Port: RS232 port via RJ12.
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12.
DH485 TXEN: Transmit enable; open collector, VOH = 15 VDC,
VOL = 0.5 V @ 25 mA max.
Note: For additional information on the communications or signal
common and connections to earth ground please see the “Connecting to
Earth Ground” in the section “Installing and Powering the G310.”
Ethernet Port: 10 BASE-T / 100 BASE-TX
RJ45 jack is wired as a NIC (Network Interface Card).
8. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50 °C
Storage Temperature Range: -20 to 70 °C
Operating and Storage Humidity: 80% maximum relative humidity (non-
condensing) from 0 to 50 °C.
Vibration According to IEC 68-2-6: Operational 10 to 55 Hz, in X, Y, Z
direction for 1.5 hours, 1 g.
Shock According to IEC 68-2-27: Operational 30 g's, 9 msec in 3 directions.
Altitude: Up to 2000 meters.
9. CERTIFICA TIONS AND COMPLIANCES:
SAFETY
UL Recognized Component, File #E179259, UL61010-1, CSA 22.2 No.61010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
UL Listed, File #E211967, UL61010-1, UL1604, CSA 22.2 No. 61010-1,
CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Enclosure rating (Face only), UL50
IECEE CB Scheme Test Report #E179259-A1-CB-1
Issued by Underwriters Laboratories Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP66 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
11. CONSTRUCTION: Steel rear metal enclosure with NEMA 4X/IP66
aluminum front plate when correctly fitted with the gasket provided.
Installation Category II, Pollution Degree 2.
12. MOUNTING REQUIREMENTS: Maximum panel thickness is 0.25" (6.3
mm). For NEMA 4X/IP66 sealing, a steel panel with a minimum thickness of
0.125" (3.17 mm) is recommended.
Maximum Mounting Stud Torque: 17 inch-pounds (1.92 N-m)
13. WEIGHT: 5.53 lbs (2.51 Kg)
DIMENSIONS In inches (mm)
2
INSTALLINGAND POWERINGTHE G310
2.975
(75.6)
8.925
(226.7)
8.400
(213.4)
11.725 (297.8)
6.125 (155.6)
12.250 (311.2)
14X ∅.188 (∅4.8)
MOUNTING INSTRUCTIONS
This operator interface is designed for through-panel mounting. A panel cutout diagram and a template are provided. Care should be taken to remove any
loose material from the mounting cut-out to prevent that material from falling
into the operator interface during installation. A gasket is provided to enable
sealing to NEMA 4X/IP66 specification. Install the 14 kep nuts provided and
tighten evenly for uniform gasket compression.
Note: Tightening the kep nuts beyond a maximum of 17 inch-pounds (1.92
N-m) may cause damage to the front panel.
All tolerances ±0.010" (±0.25 mm).
ALL NONINCENDIVE CIRCUITS MUST BE WIRED USING
DIVISION 2 WIRING METHODS AS SPECIFIED IN ARTICLE 501-4
(b), 502-4 (b), AND 503-3 (b) OF THE NATIONAL ELECTRICAL
CODE, NFPA 70 FOR INSTALLATION WITHIN THE UNITED
STATES, OR AS SPECIFIED IN SECTION 19-152 OF CANADIAN
ELECTRICAL CODE FOR INSTALLATION IN CANADA.
CONNECTING TO EARTH GROUND
The protective conductor terminal is bonded to conductive
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.
The chassis ground is not connected to signal common of the unit.
Maintaining isolation between earth ground and signal common is not required
to operate your unit. But, other equipment connected to this unit may require
isolation between signal common and earth ground. To maintain isolation
between signal common and earth ground care must be taken when connections
are made to the unit. For example, a power supply with isolation between its
signal common and earth ground must be used. Also, plugging in a USB cable
may connect signal common and earth ground.
1. USB’s shield may be connected to earth ground at the host. USB’s shield
in turn may also be connected to signal common.
POWER SUPPLY REQUIREMENTS
The G310C requires a 24 VDC power supply rated at 33 W, and the G310S
requires a 24 VDC power supply rated at 25 W. Your unit may draw considerably
less the rated power depending upon the options being used. As additional
features are used your unit will draw increasing amounts of power. Items that
could cause increases in current are additional communications, optional
communications card, CompactFlash card, and other features programmed
through Crimson.
In any case, it is very important that the power supply is mounted correctly if
the unit is to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not
more than 6 feet (1.8 m) of cable between the supply and the operator
interface. Ideally, the shortest length possible should be used.
– The wire used to connect the operator interface’s power supply should
be at least 22-gage wire. If a longer cable run is used, a heavier gage
wire should be used. The routing of the cable should be kept away from
large contactors, inverters, and other devices which may generate
significant electrical noise.
– A power supply with a Class 2 or SELV rating is to be used. A Class 2
or SELV power supply provides isolation to accessible circuits from
hazardous voltage levels generated by a mains power supply due to
single faults. SEL V is an acronym for “safety extra-low voltage.” Safety
extra-low voltage circuits shall exhibit voltages safe to touch both under
normal operating conditions and after a single fault, such as a
breakdown of a layer of basic insulation or after the failure of a single
component has occurred.
1
Each G310 has a chassis ground terminal on the back of the unit. Your unit
should be connected to earth ground (protective earth).
COMMUNICATING WITHTHE G310
CONFIGURING A G310
The G310 is configured using Crimson software. Crimson is available as a free
download from Red Lion’s website, or it can be purchased on CD. Updates to
Crimson for new features and drivers are posted on the website as they become
available. By configuring the G310 using the latest version of Crimson, you are
assured that your unit has the most up to date feature set. Crimson software can
configure the G310 through the RS232 PGM port, USB port, or CompactFlash.
The USB port is connected using a standard USB cable with a Type B
connector. The driver needed to use the USB port will be installed with Crimson.
If this driver has not been installed, it can be downloaded from the website.
The RS232 PGM port uses a programming cable made by Red Lion to
connect to the DB9 COM port of your computer. If you choose to make your
own cable, use the “G310 Port Pin Out Diagram” for wiring information.
The CompactFlash can be used to program a G3 by placing a configuration
file and firmware on the CompactFlash card. The card is then inserted into the
target G3 and powered. Refer to the Crimson literature for more information on
the proper names and locations of the files.
CABLES AND DRIVERS
Red Lion has a wide range of cables and drivers for use with many different
communication types. A list of these drivers and cables along with pin outs is
available from Red Lion’s website. New cables and drivers are added on a
regular basis. If making your own cable, refer to the “G310 Port Pin Outs” for
wiring information.
USB, DATA TRANSFERS FROM THE
COMPACTFLASH CARD
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
In order to transfer data from the CompactFlash card via the USB port, a
driver must be installed on your computer. This driver is installed with Crimson
and is located in the folder C:\Program Files\Red Lion Controls\Crimson 2.0\
Device\ after Crimson is installed. This may have already been accomplished if
your G310 was configured using the USB port.
Once the driver is installed, connect the G310 to your PC with a USB cable,
and follow “Mounting the CompactFlash” instructions in the Crimson 2 user
manual.
3