Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
GRAPHITE™ SERIES
10" Color Touchscreen Operator Interface
Installation Guide
U
R
C
US LISTED
L
IND. CONT. EQ.
34AD
Drawing No. LP0909B
Released 04/14
See the Red Lion website at www.redlion.net or the enclosed
USB thumbdrive for full user manual, Crimson software and
software manual.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired. Do not use this unit to directly
command motors, valves, or other actuators not equipped with safeguards. To
do so can be potentially harmful to persons or equipment in the event of a fault
to the unit.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION:
Risk of electric shock.
ORDERING INFORMATION
DESCRIPTION PART NUMBER
10" color touch screen, indoor use, 24 VDC powered G10C0000
10" color touch screen, indoor use, 24 VDC powered,
additional ethernet port
10" high resolution display, color touch screen, indoor use,
24 VDC powered
10" high resolution display, color touch screen, indoor use,
24 VDC powered, additional ethernet port
10" color touch screen, indoor/outdoor use, 24 VDC powered G10S0000
10" color touch screen, indoor/outdoor use, 24 VDC powered,
additional ethernet port
G10C1000
G10R0000
G10R1000
G10S1000
SPECIFICATIONS
POWER: +24 VDC ±20%
G10C/R G10S
Typical Power HMI only: 12 W 18 W
Maximum Power HMI only: 19 W 24 W
HMI With Module(s): 48W 53 W
Must use a Class 2 circuit according to National Electrical Code (NEC),
NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited
Power Supply (LPS) according to IEC 60950-1 or Limited-energy circuit
according to IEC 61010-1.
Power connection via removable three position terminal block.
ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20 to 60 °C
Storage Temperature Range: -20 to 70 °C
Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g
Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays)
Operating and Storage Humidity: 0 to 85% max. RH non-condensing
Altitude: Up to 2000 meters
CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
UL Listed: File #E302106
Type 4X Indoor / IP66 Enclosure rating (Face only) for all models
Type 4X Outdoor Enclosure rating (Face only) for G10Sxxxx models
CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm)
Wire Gauge Capacity: One 14 AWG (2.55 mm) solid,
two 18 AWG (1.02 mm) or four 20 AWG (0.61 mm)
CONSTRUCTION: Cast aluminum enclosure with NEMA 4X/IP66 rating for
indoor use only when correctly fitted with the gasket provided. Installation
Category II, Pollution Degree 2.
WEIGHT: 4.8 lb. (2.18 Kg)
DIMENSIONS In inches (mm)
10.84 (275.2)
8.57
(217.7)
2.06 (52.4)
2.97 (76)
Module sold
separately
1
11.1 (281)
8.8
(224)
(MOUNTING CLIPS INSTALLED)
FOOT MAY BE REMOVED
FOR THICKER PANEL
INSTALLATIONS
ll tolerances ±.059" (±1.5 mm)
OperatOr Interface InstallatIOn
MOUNTING INSTRUCTIONS
This operator interface is primarily designed for
through-panel mounting. Four VESA mount tapped screwholes (M4 x 0.7, 5 mm deep) are present on the rear of the
panels to allow for stand or wall mounting. Care should be
taken to remove any loose material from the mounting cutout to prevent that material from falling into the operator
interface during installation. A gasket is provided to enable
sealing to NEMA 4X/IP66 specification. Install the nine
mounting clips provided and tighten to 6.0 pound-force inch
(96 ounce-force inch) evenly for uniform gasket compression.
ALL NONINCENDIVE CIRCUITS MUST BE
WIRED USING DIVISION 2 WIRING
METHODS AS SPECIFIED IN ARTICLE 501-4
(b), 502-4 (b), AND 503-3 (b) OF THE
NATIONAL ELECTRICAL CODE, NFPA 70
FOR INSTALLATION WITHIN THE UNITED
STATES, OR AS SPECIFIED IN SECTION
19-152 OF CANADIAN ELECTRICAL CODE
FOR INSTALLATION IN CANADA.
PANEL CUT-OUT
10.197 (259.0)
4X R.10 (2.5)
MAX.
7.931
(201.4)
CONNECTING TO EARTH GROUND
The protective conductor terminal is bonded to conductive
parts of the equipment for safety purposes and must be
connected to an external protective earthing system.
Each operator panel has a chassis ground terminal on the back of the unit.
Your unit should be connected to earth ground (protective earth).
The chassis ground is not connected to signal common of the unit.
Maintaining isolation between earth ground and signal common is not required
to operate your unit. But, other equipment connected to this unit may require
isolation between signal common and earth ground. To maintain isolation
between signal common and earth ground care must be taken when connections
are made to the unit. For example, a power supply with isolation between its
signal common and earth ground must be used. Also, plugging in a USB cable
may connect signal common and earth ground.
1
USB’s shield may be connected to earth ground at the host. USB’s shield in
turn may also be connected to signal common.
1
POWER SUPPLY REQUIREMENTS
The G10 requires a 24 VDC power supply. Your unit may draw considerably
less than the maximum rated power depending upon the features being used. As
additional features are used your unit will draw increasing amounts of power.
Items that could cause increases in current are modules, additional on-board
communications, SD card, and other features programmed through Crimson.
In any case, it is very important that the power supply is mounted correctly if
the unit is to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not more
than 6 feet (1.8 m) of cable between the supply and the operator interface.
Ideally, the shortest length possible should be used.
– The wire used to connect the operator interface’s power supply should be
at least 22-gage wire suitably rated for the temperatures of the environment
to which it is being installed. If a longer cable run is used, a heavier gage
wire should be used. The routing of the cable should be kept away from
large contactors, inverters, and other devices which may generate
significant electrical noise.
– A power supply with an NEC Class 2 or Limited Power Source (LPS) and
SELV rating is to be used. This type of power supply provides isolation to
accessible circuits from hazardous voltage levels generated by a mains
power supply due to single faults. SELV is an acronym for “safety extralow voltage.” Safety extra-low voltage circuits shall exhibit voltages safe
to touch both under normal operating conditions and after a single fault,
such as a breakdown of a layer of basic insulation or after the failure of a
single component has occurred.
I/O MODULE INSTALLATION
VESA MOUNT (MIS-D 75) DIMENSIONS
1.48 (37.5)
2.95 (75)
2.95
(75)
.87
(22.1)
Modules must be installed beginning with slot 1 (left-most slot), with no
empty slots between the modules, and the order must match the modules order
in the Crimson database. Torque screws to 6.0 pound-force inch (96 ounceforce inch).
REMOVE RUBBER
MODULE PLUG
WARNING: Disconnect all power
to the unit before installing or
removing modules.
2