Red Lion G07 User Manual

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
GRAPHITE™ SERIES
7" Color Touchscreen Operator Interface Installation Guide
U
R
C
US LISTED
L
IND. CONT. EQ.
34AD
Drawing No. LP0907B
Released 04/14
See the Red Lion website at www.redlion.net or the enclosed USB thumbdrive for full user manual, Crimson software and software manual.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. Do not use this unit to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the unit.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION:
Risk of electric shock.
ORDERING INFORMATION
DESCRIPTION PART NUMBER
7" color touch screen, indoor use, 24 VDC powered G07C0000
7" color touch screen, indoor/outdoor use, 24 VDC powered G07S0000
SPECIFICATIONS
POWER: +24 VDC ±20%
G07C G07S Typical Power HMI only: 9 W 10 W Maximum Power HMI only: 16 W 17 W HMI With Module(s): 37 W 38 W Must use a Class 2 circuit according to National Electrical Code (NEC),
NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited Power Supply (LPS) according to IEC 60950-1 or Limited-energy circuit according to IEC 61010-1. Power connection via removable three position terminal block.
ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20 to 60 °C Storage Temperature Range: -20 to 70 °C Vibration to IEC 68-2-6: Operational 5-500 Hz, 4 g Shock to IEC 68-2-27: Operational 40 g (10 g, modules w/relays) Operating and Storage Humidity: 0 to 85% max. RH non-condensing Altitude: Up to 2000 meters
CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A IEC/EN 61010-1
RoHS Compliant UL Listed: File #E302106 Type 4X Indoor / IP66 Enclosure rating (Face only) for all models Type 4X Outdoor Enclosure rating (Face only) for G07Sxxxx models
CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.3" (7.5 mm) Wire Gauge Capacity: One 14 AWG (2.55 mm) solid,
two 18 AWG (1.02 mm) or four 20 AWG (0.61 mm)
CONSTRUCTION: Cast aluminum enclosure with NEMA 4X/IP66 rating for
indoor/outdoor use when correctly fitted with the gasket provided. Installation Category II, Pollution Degree 2.
WEIGHT: 2.26 lb. (1.03 Kg)
DIMENSIONS In inches (mm)
7.70 (195.5) 2.00 (50.8)
5.51
(139.9)
Module sold
separately
1
7.9 (202)
5.7
(146)
(MOUNTING CLIPS INSTALLED)
FOOT MAY BE REMOVED FOR THICKER PANEL INSTALLATIONS
7.060 (179.3)
OperatOr Interface InstallatIOn
MOUNTING INSTRUCTIONS
This operator interface is primarily designed for
through-panel mounting. Four VESA mount tapped screw-holes (M4 x 0.7, 5 mm deep) are present on the rear of the panels to allow for stand or wall mounting. Care
should be taken to remove any loose material from the
mounting cut-out to prevent that material from falling into the operator interface during installation. A gasket is provided to enable sealing to NEMA 4X/IP66 specification. Install the nine mounting clips provided and tighten to 6.0
pound-force inch (96 ounce-force inch) evenly for uniform gasket compression.
ALL NONINCENDIVE CIRCUITS MUST BE WIRED USING DIVISION 2 WIRING METHODS AS SPECIFIED IN ARTICLE 501-4 (b), 502-4 (b), AND 503-3 (b) OF THE NATIONAL ELECTRICAL CODE, NFPA 70 FOR INSTALLATION WITHIN THE UNITED STATES, OR AS SPECIFIED IN SECTION 19-152 OF CANADIAN ELECTRICAL CODE FOR INSTALLATION IN CANADA.
PANEL CUT-OUT
4X R.10 (2.5)
MAX.
All tolerances ±.059" (±1.5 mm)
4.869
(123.7)
CONNECTING TO EARTH GROUND
The protective conductor terminal is bonded to conductive parts of the equipment for safety purposes and must be connected to an external protective earthing system.
The third pin of the power connector of the G07 is chassis ground for the unit.
Your unit should be connected to earth ground (protective earth).
The chassis ground is not connected to signal common of the unit. Maintaining isolation between earth ground and signal common is not required to operate your unit. But, other equipment connected to this unit may require isolation between signal common and earth ground. To maintain isolation
between signal common and earth ground care must be taken when connections are made to the unit. For example, a power supply with isolation between its
signal common and earth ground must be used. Also, plugging in a USB cable may connect signal common and earth ground.
1
USB’s shield may be connected to earth ground at the host. USB’s shield in
turn may also be connected to signal common.
1
POWER SUPPLY REQUIREMENTS
The Graphite panel requires a 24 VDC power supply. Your unit may draw considerably less than the maximum rated power depending upon the features being used. As additional features are used your unit will draw increasing amounts of power. Items that could cause increases in current are modules, additional on-board communications, SD card, and other features programmed through Crimson.
In any case, it is very important that the power supply is mounted correctly if the unit is to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not more
than 6 feet (1.8 m) of cable between the supply and the operator interface. Ideally, the shortest length possible should be used.
– The wire used to connect the operator interface’s power supply should be
at least 22-gage wire suitably rated for the temperatures of the environment to which it is being installed. If a longer cable run is used, a heavier gage wire should be used. The routing of the cable should be kept away from large contactors, inverters, and other devices which may generate significant electrical noise.
– A power supply with an NEC Class 2 or Limited Power Source (LPS) and
SELV rating is to be used. This type of power supply provides isolation to accessible circuits from hazardous voltage levels generated by a mains power supply due to single faults. SELV is an acronym for “safety extra­low voltage.” Safety extra-low voltage circuits shall exhibit voltages safe to touch both under normal operating conditions and after a single fault, such as a breakdown of a layer of basic insulation or after the failure of a single component has occurred.
2.95 (75)
1.73 (44)
VESA MOUNT (MIS-D 75) DIMENSIONS
1.48 (37.5)
I/O MODULE INSTALLATION
Modules must be installed beginning with slot 1 (left-most slot), with no empty slots between the modules, and the order must match the modules order in the Crimson database. Torque screws to 6.0 pound-force inch (96 ounce­force inch).
2.95 (75)
REMOVE RUBBER MODULE PLUG
WARNING: Disconnect all power to the unit before installing or removing modules.