Red Lion DLC User Manual

Tel +1 (717) 767-6511
OPTIONAL
BOTH FLASHING
ALL FLASHING = CHECKSUM ERROR
0-10V, 0-20mA
ANALOG OUTPUT 1
0-10V, 0-20mA
ANALOG OUTPUT 2
JUMPERS
INPUT ERROR
RS485
MODBUS
PROTOCOL
CH B ALM
=
6
0-10V, 0-20mA
0-10V, 0-20mA
TC+ OR RTD
INPUT COMMON
TC+ OR RTD
INPUT COMMON
RTD EXC.
TBB
12
RTD EXC.
435
INPUTS
CH B CH A
INPUTS
DEFAULT SERIAL SETTING
OUT +
OUT -
789
OUT +
OUT -
1110
PWR/COMM.
INPUT ERROR
BOTH FLASHING
CH A ALM
AUTOTUNE
CH B OP
CH A OP
=
SETTINGS
FACTORY
JUMPER
MODEL DLC
AL2/OP2
AL2/OP2
OUTPUT COMMON
OUTPUTS
10V
20mA
RTD
10V
RTD
20mA
DC- / (AC)
DC+ / (AC)
+24VDC OUT
I1-
I1+
V1+
V1-
V2-
V2+
I2+
I2-
OUTPUTS
CH A CH B
5
OP1
TBA
1ต32ต4 6
AL178OP1
109
AL1
YORK, PA. MADE IN U.S.A.
4.06 (103)
(102)
1.97
4.02
(50)
RED LION CONTROLS
AC 24V ±10%, 50/60 Hz, 15VA
DC 18-36V, 13W
POWER: (FULL LOAD)
!
MODEL DLC
RED LION CONTROLS
Fax +1 (717) 764-0839 www.redlion.net
MODEL DLC - DUAL LOOP CONTROLLER
MODULAR BUILDING BLOCK FOR MULTI-ZONE PROCESS CONTROL TWO INDEPENDENT PID CONTROL LOOPS PID CONTROL WITH REDUCED OVERSHOOT UNIVERSAL INPUTS ACCEPT TC, RTD, 0-10 V and 0/4-20 mA SIGNALS TWO DC ANALOG OUTPUTS (OPTIONAL) WINDOWS RS485 MODBUS™ PROTOCOL CHANNEL B CAN BE ASSIGNED AS A SECOND ANALOG INPUT TO
CHANNEL A FOR REMOTE SETPOINT OPERATION
SETPOINT CONTROLLER OPTION FOR TIME VS. TEMP./PROCESS
UL Recognized Component, File #E156876
(RAMP/SOAK) AND SPECIAL BATCH/RECIPE APPLICA TIONS
SQUARE ROOT EXTRACTION FOR FLOW SENSOR APPLICATIONS
®
Bulletin No. DLC-H Drawing No. LP0495 Released 05/12
GENERAL DESCRIPTION
The Model DLC, Dual Loop Controller, is a full featured, DIN rail mounted, dual input PID controller. The DLC is designed as a modular building block for multi-zone process control applications. The controller has two independent “A” & “B” input channels. Each channel’s input can be configured to accept a wide range of thermocouple, RTD, 0-10 V, 0/4-20 mA, or resistive signals. Each channel can also be configured to extract the square root of the input in both process voltage or process current modes for applications such as flow measurement using a differential flow sensor.
Channel B can be assigned as a Remote Setpoint for Channel A. The two time­proportioning or DC Analog outputs can be programmed to control two independent processes. The two alarms per channel can be configured for various alarm modes, or provide a secondary control output for heat/cool applications.
The control and alarm outputs are N channel open drain MOSFETs capable of switching up to 1 Amp DC. For applications requiring larger loads or A/C loads, several DIN rail mount relays are available.
The controller operates in the PID Control Mode for both heating and cooling, with on-demand auto-tune, that establishes the tuning constants. The PID tuning constants may be fine-tuned through the serial interface. The controller employs a unique overshoot suppression feature, which allows the quickest response without excessive overshoot. The controller can be transferred to operate in the Manual Mode, providing the operator with direct control of the output, or the On/Off Control Mode with adjustable hysteresis.
The controller’s high density packaging and DIN rail mounting saves time and panel space. The controller snaps easily onto standard top hat (T) profile DIN rails.
DIMENSIONS In inches (mm)
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other actuators not equipped with safeguards. To do so can be potentially harmful to persons or equipment in the event of a fault to the controller. An independent and redundant temperature limit indicator with alarm outputs is strongly recommended.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
ALARMS
The DLC’s two solid-state alarms can be configured independently for absolute high or low acting with balanced or unbalanced hysteresis. They can also be configured for deviation and band alarm. In these modes, the alarm trigger values track the setpoint value. Adjustable alarm trip delays can be used for delaying output response. The alarms can be programmed for Automatic or Latching operation. Latched alarms must be reset with a serial command. A standby feature suppresses the alarm during power-up until the temperature stabilizes outside the alarm region. The outputs can also be manually controlled with Modbus register or coil commands.
SETPOINT CONTROLLER OPTION
The Setpoint Controller option is suitable for time vs. temperature/process control applications. The controller allows a profile of up to 20 ramp/soak segments. Profile conformity is assured by using the Error Band Mode and Error Band parameter. The Profile Cycle Count allows the profile to run continuously or a fixed number of cycles. Power-on options automatically stop, abort, start, resume, or pause a running profile.
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBERS
Dual Loop Controller DLC00001
DLC
CBPRO Programming Interface Cable CBPRO007
CBJ Cable RJ11 to RJ11 (6 inch jumper) CBJ11BD5
DRR RJ11 to Terminal Adapter DRRJ11T6
P89 Paradigm to RJ11 Cable P893805Z
See our RSRLYB, RLY6, and RLY7 literature for details on DIN rail mountable relays.
1
Dual Loop Controller w/ 2 Analog Outputs DLC01001
Dual Setpoint Controller w/ 2 Analog Outputs DLC11001
SF PC Configuration Software for Windows SFDLC
COMMUNICATIONS
The RS485 serial communications allows the DLC to be multi-dropped, with Baud rates up to 38400. The CBPRO007 programming cable converts the RS232 port of a PC to RS485 and is terminated with an RJ11 connector. The bi-directional capability of the CBPRO007 allows it to be used as a permanent interface cable as well as a programming cable.
SOFTWARE
The DLC is programmed with Windows® based SFDLC software. The software allows configuration and storage of DLC program files, as well as calibration. Additionally, all setup and control parameters can be interrogated and modified through MODBUS register and coil commands.
ANALOG OUTPUT OPTION
The optional dual DC Analog Output (10 V or 20 mA) can be independently configured and scaled for control or re-transmission purposes. These outputs can be assigned to separate channels, or both outputs can be assigned to the same channel. Programmable output update time reduces valve or actuator activity.
SPECIFICATIONS
1. POWER:
18 to 36 VDC, 13 W (4 W if +24 VDC Output excitation is unused)
24 VAC, ±10% 50/60 Hz, 15 VA (7 VA if +24 VDC Output excitation is unused)
Must use a Class 2 or SELV rated power supply.
2. +24 VDC OUTPUT POWER: 24 VDC, +15%, -5%, 200 mA max
3. MEMORY: Non-volatile memory retains all programmable parameters.
4. INPUT:
Sample Time: 100 msec (9.5 Hz)
Failed Sensor Response: Open or shorted (RTD only) sensor coils
indication, error code returned in Process Value
Common Mode Rejection: >110 dB, 50/60 Hz
Normal Mode Rejection: >40 dB, 50/60 Hz
Temperature Coefficient: 0.013%/°C
Overvoltage: 50 VDC max
Step Response Time: 300 msec typ., 400 msec max
5. THERMOCOUPLE INPUTS:
Types: T, E, J, K, R, S, B, N, C, linear mV
Input Impedance: 20 M
Lead Resistance Effect: 0.25 μV/
Cold Junction Compensation: Less than ±1°C typical (±1.5°C max) over
0 to 50°C ambient temperature range or less than ±1.5°C typical (2°C max) over -20 to 65°C maximum ambient temperature range.
Resolution: 1° or 0.1° for all types except linear mV (0.1 or 0.01 mV)
TYPE
T
E
J
K
R
S
B
N
C
W5/W6
mV -5 mV to 56 mV N/A N/A
MEASUREMENT
RANGE
-200 to +400°C
-328 to +752°F
-200 to +750°C
-328 to +1382°F
-200 to +760°C
-328 to +1400°F
-200 to +1250°C
-328 to +2282°F 0 to +1768°C
+32 to +3214°F
0 to +1768°C
+32 to +3214°F
+149 to +1820°C +300 to +3308°F
-200 to +1300°C
-328 to +2372°F 0 to +2315°C
+32 to +4199°F
No Standard
No Standard
No Standard No Standard
No Standard No Standard
6. RTD INPUTS: Type: 2 or 3 wire Excitation: 150 μA Lead Resistance: 15 max Resolution: 1 or 0.1° for all types
TYPE INPUT TYPE RANGE
385 100 platinum, Alpha = .00385
392 100 platinum, Alpha = .003919
672 120 nickel, Alpha = .00672
ohms Linear Resistance 0 to 320
WIRE COLOR
ANSI BS 1843
(+) Blue
(-) Red
(+) Violet
(-) Red
(+) White
(-) Red
(+) Yellow
(-) Red
(+) Orange
(-) Red
(+) Orange
-200 to +600°C
-328 to +1100°F
-200 to +600°C
-328 to +1100°F
-80 to +215°C
-112 to +419°F
(+) White
(-) Blue
(+) Brown
(-) Blue
(+) Yellow
(-) Blue
(+) Brown
(-) Blue
(+) White
(-) Blue
(+) White
(-) Blue
(-) Blue
7. TEMPERATURE INDICATION ACCURACY: ± (0.3% of span, +1°C).
Includes NIST conformity, cold junction effect, A/D conversion errors, temperature coefficient and linearization conformity at 23 °C after 20 minute warm up.
8. PROCESS INPUT:
INPUT RANGE
10 VDC
(-1 to 11)
20 mA DC
(-2 to 22)
ACCURACY *
(18 to 28°C)
(10 to 75% RH)
0.10% of reading +0.02 V
0.10% of reading
+0.03 mA
IMPEDANCE
1 M 50 V 1 mV
10 100 mA 1 μA
MAX
CONTINUOUS
OVERLOAD
RESOLUTION
* Accuracies are expressed as ± percentages after 20 minute warm-up.
9. ISOLATION LEVEL: 500 VAC @ 50/60 Hz, for one minute (50 V
working) between the following groups:
Ch A Input Ch B Input Control and Alarm Outputs RS485/Analog Output
1
Power Supply
Note:
1
RS485 and Analog Outputs are not internally isolated. Their commons
must not be connected together externally for proper unit function (i.e., earth ground).
10. SERIAL COMMUNICATIONS: Type: RS485; RTU and ASCII MODBUS modes Baud: 300, 600, 1200, 2400, 4800, 9600, 19200, and 38400 Format: 7/8 bits, odd, even, and no parity Transmit Delay: Programmable: See Transmit Delay explanation. Transmit Enable (TXEN): (primarily for 20 mA loop converter) open
collector VOH = 10 VDC max, VOL = 0.5 VDC @ 5 mA max current limit
11. A/D CONVERTER: 16 bit resolution
12. CONTROL AND ALARM OUTPUTS:
Type: Non-isolated switched DC, N Channel open drain MOSFET Current Rating: 1 A max V
: 0.3 V @ 1 A
DS ON
V
: 30 VDC
DS MAX
Offstate Leakage Current: 0.5 mA max
13. MAIN CONTROL: Control: PID or On/Off Output: Time proportioning or DC Analog Cycle Time: Programmable Auto-Tune: When selected, sets proportional band, integral time, derivative
time values, and output dampening time
Probe Break Action: Programmable
14. ALARM: 1 or 2 alarms Modes:
Manual (through register/coil) Absolute High Acting (Balanced or Unbalanced Hysteresis) Absolute Low Acting (Balanced or Unbalanced Hysteresis) Deviation High Acting Deviation Low Acting Inside Band Acting Outside Band Acting
Reset Action: Programmable; automatic or latched Standby Mode: Programmable; enable or disable Hysteresis: Programmable Sensor Fail Response: Upscale
15. COOLING: Software selectable (overrides Alarm 2). Control: PID or On/Off Output: Time proportioning or DC Analog Cycle Time: Programmable Proportional Gain Adjust: Programmable Heat/Cool Deadband Overlap: Programmable
16. ANALOG DC OUTPUTS: (optional) Control or retransmission, programmable update rate from 0.1 sec or 1 to 250 sec Step Response Time: 100 msec
OUTPUT
RANGE**
0 to 10 V
0 to 20 mA
ACCURACY *
(18 to 28°C)
(10 to 75% RH)
0.10% of FS + 1/2 LSD
0.10% of FS + 1/2 LSD
COMPLIANCE
10 K min 1/18000
500 max 1/18000
RESOLUTION
(TYPICAL)
2
OUTPUT
AL1
OP1
9
8
AL2/OP2
10
AL1
AL2/OP2
6
7
3
4
COMM.
5
POWER
INPUT
1
2
PROCESS
CIRCUITRY
TC+ / RTD
COMMON
2
INPUT B
1
0-10V, 0-20mA
4
5
3
7
6
10
ANALOG OUT 1 -
9
ANALOG OUT 1 +
8
11
24 VDC
OP1
SUPPLY
POWER
-0.6V
+13.3V
+18V
+5VS
-3.6VS
+5VC
+5VC DIG
-3.6VC
+5VS DIG
+5V DIG
24VDC
24V
24V
E MEMORY
2
RS485
RTD EXC
INPUT A
INPUT A
INPUT B
RTD EXC
0-10V, 0-20mA
TC+ / RTD
COMMON
INPUT B
CONV.
A/D
4.02K
5VC
10 Ω
4.99K
976K
5VC
20M
0-10V, 0-20mA
ANALOG OUT 2 -
0-10V, 0-20mA
ANALOG OUT 2 +
ISOLATED
V+
I+
I-
V-
A/D
CONV.
4.02K
5VS
10 Ω
4.99K
976K
5VS
20M
+18V
25.5 Ω
DIG
+18V
INPUT A
25.5 Ω
(PWM)
CONV.
D/A
D/A
CONV. (PWM)
I-
V-
I+
V+
ISOLATED
5VC
OUTPUT
ANNUNCIATORS
C
C
C
S
S
S
O
O
O
O
O
O
O
O
I
I
I
I
I
I
I
B-
A+
GND
TXEN
U
MAIN DIG
U
D
5V DIG
24V
24V
24V
24V
(DO NOT CONNECT AND ) O U
DIP SWITCHES
TBB
TBA
DEFAULT SERIAL SETTINGS
+5V MAIN DIG
+24V OUT
+2.5V
o
5V
o
5V MAIN
5V MAIN
DIG
ISOLATED
5VS
D
D
RANGE**
4 to 20 mA
ACCURACY *
(18 to 28°C)
(10 to 75% RH)
0.10% of FS + 1/2 LSD
COMPLIANCE
500 max 1/14400
RESOLUTION
(TYPICAL)
* Accuracies are expressed as ± percentages after 20 minute warm-up.
** Outputs are independently jumper selectable for either 10 V or 20 mA.
The output range may be field calibrated to yield approximate 10% overrange and a small underrange (negative) signal.
17. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: -20 to +65°C
Storage Temperature Range: -40 to +85°C Operating and Storage Humidity: 85% max relative humidity,
noncondensing, from -20 to +65°C
Vibration according to IEC 68-2-6: Operational 5 to 150 Hz, in X, Y, Z
direction, duration: 1.5 hours, 2 g.
Shock according to IEC 68-2-27: Operational 30 g, 11 msec in 3 directions. Altitude: Up to 2000 meters
18. CERTIFICA TIONS AND COMPLIANCE: SAFETY
UL Recognized Component, File # E156876, UL873, CSA 22.2 No. 24
Recognized to U.S. and Canadian requirements under the Component Recognition Program of Underwriters Laboratories, Inc.
IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part I
ELECTROMAGNETIC COMPATIBILITY
Emissions and Immunity to EN 61326:2006: Electrical Equipment for
Measurement, Control and Laboratory use.
Immunity to Industrial Locations:
Electrostatic discharge EN 61000-4-2 Criterion A
2
4 kV contact discharge
Electromagnetic RF fields EN 61000-4-3 Criterion A
8 kV air discharge
3a
10 V/m (80 MHz to 1 GHz) 3 V/m (1.4 GHz to 2 GHz) 1 V/m (2 GHz to 2.7 GHz)
Fast transients (burst) EN 61000-4-4 Criterion B
power 2 kV
Surge EN 61000-4-5 Criterion A
I/O signal 1 kV
power 1 kV L to L, 2 kV L to G
RF conducted interference EN 61000-4-6 Criterion A
3 Vrms
Power freq magnetic fields EN 61000-4-8
30 A/m
AC power EN 61000-4-11
Voltage dip Criterion
0% during 1 cycle A 40% during 10/12 cycle C 70% during 25/30 cycle C
Short interruptions Criterion
0% during 250/300 cycles C
Emissions:
Emissions EN 55011 Class A
1
Criterion A: Normal operation within specified limits.
2
This controller was designed for installation in an enclosure. To avoid
electrostatic discharge to the unit in environments with static levels above 6 kV, precautions should be taken when the device is mounted outside an enclosure. When working in an enclosure (ex. making adjustments, setting switches etc.), typical anti-static precautions should be observed before touching the unit.
3
Criterion B: Temporary loss of performance from which the unit self-recovers.
a.
Note: The module's analog input and/or output signals may deviate during
disturbance, but self-recover when disturbance is removed. For operation without loss of performance: Unit is mounted in a metal enclosure I/O and power cables are routed in metal conduit connected to earth ground.
4
Criterion C: Temporary loss of function where system reset occurs. 19.
CONSTRUCTION: Case body is black high impact plastic. Installation Category I, Pollution Degree 2.
20. CONNECTIONS: Wire clamp screw terminals. Removable terminal blocks.
21. MOUNTING: Snaps on to standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
22. WEIGHT: 10.5 oz. (298 g.)
BLOCK DIAGRAM
3
Channel B Input Jumpers
Channel A Input Jumpers
Analog Output 2 Jumpers (current) Analog Output 1 Jumpers (current)
(RTD)
(As set from factory)
EMC INSTALLATION GUIDELINES
Although this controller is designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, source or coupling method into the controller may be different for various installations. The controller becomes more immune to EMI with fewer I/O connections. Cable length, routing, and shield termination are very important and can mean the difference between a successful or troublesome installation. Listed are some EMC guidelines for successful installation in an industrial environment.
1. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the DIN rail where the controller is mounted to
earth ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is over 1 MHz.
c. Connect the shield to common of the controller and leave the other end of
the shield unconnected and insulated from earth ground.
2. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run through metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
3. Signal or Control cables within an enclosure should be routed as far away as possible from contactors, control relays, transformers, and other noisy components.
4. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on Signal and Control cables as close to the controller as possible. Loop the cable through the core several times or use multiple cores on each cable for additional protection. Install line filters on the power input cable to the controller to suppress power line interference. The following EMI suppression devices (or equivalent) are recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (Red Lion Controls # FCOR0000) TDK # ZCAT3035-1330A Steward # 28B2029-0A0
Line Filters for input power cables:
Schaffner # FN2010-1/07 (Red Lion Controls # LFIL0000) Schaffner # FN670-1.8/07 Corcom # 1 VR3
Note: Reference manufacturer’s instructions when installing a line filter.
5. Long cable runs are more susceptible to EMI pickup than short cable runs. Therefore, keep cable runs as short as possible.
6. Switching of inductive loads produces high EMI. Use of snubbers across inductive loads suppresses EMI.
Snubber: Red Lion Controls # SNUB0000.
STEP 1 SETTING THE JUMPERS AND DIP SWITCHES
The jumpers are accessible from the bottom of the controller. Needle-nose pliers are needed to remove the jumpers. They should be set prior to installation. To insure proper operation, the jumpers must match the controller software configuration.
SERIAL DIP SWITCH SETTINGS
The DLC Serial Communications Settings can be set via DIP Switches or through the serial communications port (software selectable). The software selectable serial settings method using the serial communications port must be set using “RLCPRO” or another software program to write to the DLC Modbus registers (40401-40407). When using the DIP switches to configure the serial settings, the Modbus mode is limited to “RTU” mode only.
ANALOG DC OUTPUTS (OPTIONAL)
Analog Output 1 and Analog Output 2 can be configured for voltage (V) or current (I), independent of each other. Both V/I + and V/I - jumpers of the same channel must be set for the same type of output signal.
I2-
V2+
I2-
V2+
I1-
V1+
I1-
V1+
INPUTS
Channel A and Channel B can be configured independent of each other. Jumper position can be ignored for thermocouple and millivolt inputs.
PARITY
BAUD RATE
DEFAULT
SWA
X128
SWB: ADDRESS
X64 X32 X16 X8 X4 X2 X1
M2802X
4
PARITY
BAUD RATE
DEFAULT
SWA
X128
SWB: ADDRESS
X64
X32 X16 X8 X4 X2 X1
M2802X
20mA
20mA
10V
RTD
10V
RTD
Analog
Output 2
Jumpers
Analog
Output 1
Jumpers
Channel A
Input
Channel B
Input
SWA
SWB
DEFAULT SERIAL
SETTINGS
Use DIP Switch or Software Serial Settings
Use Default Serial Settings
PARITY
None DN DN
None UP
Even UP DN
Odd UP UP
SWITCH POSITION
2 3
DN
SWITCH
POSITION
1
DN
UP
BAUD RATE
300 DN DN DN
600 DN DN UP
1200 DN UP DN
2400 DN UP UP
4800 UP DN DN
9600 UP DN UP
19200 UP UP DN
38400 UP UP UP
Serial Communication Defaults:
RTUProtocol: 247Address: 9600Baud Rate:
SWITCH POSITION
4 5 6
Stop Bit: Parity: Start Bit
1 none 1
UNIT ADDRESS
Software Selectable
Serial Settings
1 DN DN DN DN DN DN DN UP
2 DN DN DN DN DN DN UP DN
3 DN DN DN DN DN DN UP UP
4 DN DN DN DN DN UP DN DN
5 DN DN DN DN DN UP DN UP
6 DN DN DN DN DN UP UP DN
7 DN DN DN DN DN UP UP UP
8 DN DN DN DN UP DN DN DN
247* UP UP UP UP DN UP UP UP
*- Unit will use address 247 for binary switch settings above 247
STEP 2 INSTALLING THE CONTROLLER
INSTALLATION
The controller is designed for attachment to standard DIN style top hat (T) profile mounting rails according to EN50022 -35 x 7.5 and -35 x 15. The controller should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the controller near devices that generate excessive heat should be avoided.
SWITCH POSITION / (BIT WEIGHT)
1
(128)2(64)3(32)4(16)5(8)6(4)7(2)
DN DN DN DN DN DN DN DN
8
(1)
T Rail Installation
To install the DLC on a “T” style rail, angle the controller so that the top groove of the mounting recess is located over the lip of the top rail. Push the controller toward the rail until it snaps into place. To remove a controller from the rail, insert a screwdriver into the slot on the bottom of the controller, and pry upwards until it releases from the rail.
STEP 3 IDENTIFYING THE LEDs - LED FUNCTIONALITY
On power-up, all LEDs are turned on briefly in an alternating pattern to allow visual check of LED functionality.
CONDITION CH A OP CH A ALM CH B OP CH B ALM PWR/COMMPRIORITY AUTOTUNE
Power Applied ------­Communicating ------- ------- ------- -------Flashing1 ------­OP1 On (Channel A) ** On ------- ------- --------------4 ------­OP1 On (Channel B) ** ------- ------- On --------------4 ------­AL1 On (Channel A) * ------- On ------- --------------4 ------­AL1 On (Channel B) * ------- ------- ------- On-------4 ------­AL2 On (Channel A) * Fast Flashing ------- --------------4 ------­AL2 On (Channel B) * ------- ------- ------- Fast Flashing-------4 ------­OP2 On [Cool](Channel A) Fast Flashing ------- ------- --------------5 ------­OP2 On [Cool](Channel B) ------- ------- Fast Flashing --------------5 ------­Auto-Tune On (Channel A) ------- ------- ------- --------------3 On Auto-Tune On (Channel B) ------- ------- ------- --------------3 Fast Flashing Input Error (Channel A) Slow Flashing Slow Flashing ------- --------------3 ------­Input Error (Channel B) Calibration Mode
-------3
-------2
------­On
Checksum Error Slow Flashing Slow Flashing Slow Flashing Slow Flashing-------1 Slow Flashing
-------
------­On
------­On
------- -------On1 -------
Slow FlashingOnSlow Flashing
On
* If AL1 & AL2 outputs are on at the same time, the ALM annunciator will alternate between On and Fast Flashing every ½ second. ** If OP1 and AL2/OP2 (configured for cool) outputs are on at the same time, the annunciator will only show the OP1 state. The OP2 state is only shown when OP1 is off.
5
STEP 4 WIRING THE CONTROLLER
WIRING CONNECTIONS
All conductors should meet voltage and current ratings for each terminal. Also, cabling should conform to appropriate standards of good installation, local codes and regulations. When wiring the controller, use the numbers on the label to identify the position number with the proper function. Strip the wire, leaving approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into the terminal, and tighten the screw until the wire is clamped tightly. (Pull wire to verify tightness.) Each terminal can accept up to one #14 AWG (2.55 mm), two #18 AWG (1.02 mm), or four #20 AWG (0.61 mm) wires.
24 VAC POWER
18 to 36 VDC POWER
CONTROLLER POWER CONNECTIONS
TBA
21
~
~
(AC)
(AC)
­+
2
1
DC-
DC+
TBA
For best results, the power should be relatively “clean” and within the specified limits. Drawing power from heavily loaded circuits or from circuits that also power loads that cycle on and off should be avoided. It is recommended that power supplied to the controller be protected by a fuse or circuit breaker.
INPUT CONNECTIONS
RTD and Resistance *
0-10V, 0-20mA
Exc./ Jumper
Sense
Sense
2 Wire Current Signal Requiring DLC Excitation **
6
3
5
TC+ OR RTD
2
4
INPUT COMMON
1
CH A = Terminals 4, 5 & 6
TBB
CH B = Terminals 1, 2 & 3
RTD EXC.
-
0-10V, 0-20mA
6
3
LOAD
+
+24VDC OUT
(200 mA max)
3
TBA
CH A = Terminals 4, 5 & 6 CH B = Terminals 1, 2 & 3
* For two wire RTDs, install a copper sense lead of the same gauge and length as the RTD leads. Attach one end of the wire at the probe and the other end to input
common terminal. Complete lead wire compensation is obtained. This is the preferred method. If a sense wire is not used, then use a jumper. A temperature offset
error will exist. The error may be compensated by programming a temperature offset. ** +24 VDC OUT (Terminal 3) shares common with Ch A Inputs & All Control/Alarm Outputs.
5
TC+ OR RTD
2
4
INPUT COMMON
1
TBB
Thermocouple and Millivolt
0-10V, 0-20mA
6
3
5
TC+
TC-
RTD EXC.
TC+ OR RTD
2
4
INPUT COMMON
1
CH A = Terminals 4, 5 & 6
TBB
CH B = Terminals 1, 2 & 3
RTD EXC.
DC+
DC-
3 Wire Current or Voltage Signal Requiring DLC Excitation **
Vs
+24VDC OUT
(200 mA max)
3
TBA
CH A = Terminals 4, 5 & 6 CH B = Terminals 1, 2 & 3
Voltage or Current
6
3
2
45
1
TBB
Out
3
LOAD
Comm
2
1
TBB
0-10V, 0-20mA
RTD EXC.
TC+ OR RTD
INPUT COMMON
CH A = Terminals 4, 5 & 6 CH B = Terminals 1, 2 & 3
0-10V, 0-20mA
6
45
INPUT COMMON
RTD EXC.
TC+ OR RTD
CONTROL AND ALARM OUTPUT CONNECTIONS
Load Power from DLC
External Controller Power
+
+
+
CH A = Terminals 5, 6, & 7 CH B = Terminals 8, 9, & 10
Load
Load
Load
­+
-
-
-
10
AL2/OP2
7
9
AL1
6
8
OP1
5
OUTPUT COMMON
4
3
(200 mA max)
12
TBA
+24VDC OUT
DC- / (AC)
DC+ / (AC)
+
-
CH A = Terminals 5, 6, & 7 CH B = Terminals 8, 9, & 10
Separate External Power
For Load and Controller
+
+
+
Load
Load
Load
­+
-
10
AL2/OP2
7
-
9
AL1
6
-
8
OP1
5
OUTPUT COMMON
4
3
1 2
TBA
6
+24VDC OUT
DC- / (AC)
DC+ / (AC)
Combined External Power
For Load and Controller
+
+
+
CH A = Terminals 5, 6, & 7 CH B = Terminals 8, 9, & 10
Load
Load
Load
­+
-
-
-
TBA
10
AL2/OP2
7
9
AL1
6
8
OP1
5
OUTPUT COMMON
4
+24VDC OUT
3
DC- / (AC)
DC+ / (AC)
1 2
ANALOG DC OUTPUT CONNECTIONS
-
1110
OUT -
Controller, Recorder
Output 1 = Terminals 8 & 9 Output 2 = Terminals 10 & 11
Note: Analog Outputs & RS485 are not internally isolated and must not
share the same common (i.e., earth ground).
+
TBB
9
8
OUT +
ANALOG OUTPUT
0-10V, 0(4)-20mA
RS485 SERIAL CONNECTIONS
There are two modular connectors located on the front for paralleling communications. The CBPRO007 programming cable converts the RS232 port of a PC to RS485 and is terminated with an RJ11 connector. The bi-directional capability of the CBPRO007 allows it to be used as a permanent interface cable as well as a programming cable.
DEFAULT SERIAL SETTING CONNECTIONS
TBB
DEFAULT SERIAL
7
SETTING
OUTPUT COMMON
4
TBA
Defaults:
If using software selectable serial settings and the serial settings are unknown or forgotten, they can be temporarily reset to the defaults by connecting the “Default Serial Setting” terminal 7 to “Output Common” terminal 4 with a jumper.
RTUProtocol: 247Address: 9600Baud Rate:
Data Bits: Parity:
8 none
STEP 5 INSTALLING SFDLC (Software for DLC)
Insert the SFDLC diskette into the A: or B: drive. Then Run A:\ SETUP (or B:\SETUP) to install RLCPro onto the hard drive. An icon labeled RLCPro will be created under the group RLCPro.
STEP 6 PROGRAMMING - Getting Started
Run RLCPro by double-clicking the icon, or use the start menu.
You will be prompted to
select the proper device,
Use the FILE pull-down menu
to select a NEW file.
and then the model.
7
STEP 7 PROGRAMMING THE PID SETTINGS
Note: The register numbers correspond to (Channel A/Channel B).Channel B PID control is not functional when the input is assigned as a Remote Setpoint.
The Auto-Tune procedure of the controller sets the Proportional Band, Integral Time, Derivative Time, Digital Filter, Control Ouput Dampening Time, and Relative Gain (Heat/Cool) values appropriate to the characteristics of the process.
Proportional Band (40007/40023): Proportional band, entered as percent of full input range, is the band from
the setpoint where the controller adjusts the percent output power based on how close the process value is to the setpoint. For temperature inputs, the input range is fixed per the entered thermocouple or RTD type. For process inputs, the input range is the difference between the entered Process Low Scaling Value and the Process High Scaling Value. The proportional band should be set to obtain the best response to a process disturbance while minimizing overshoot. A proportional band of 0.0% forces the controller into On/Off Control with its characteristic cycling at setpoint.
Integral Time (40008/40024): Integral time is defined as the time, in seconds, it takes the output power due to integral action alone to equal
the output power due to proportional action alone during a constant process error. As long as the error exists, integral action repeats the proportional action each integral time. Integral action shifts the center point position of the proportional band to eliminate error in the steady state. The higher the integral time, the slower the response. The optimal integral time is best determined during PID Tuning. If time is set to zero, the previous Integral output power value is maintained. Offset Power can be used to provide Manual Reset. Integral Action can be disabled by writing a ‘1’ to the Disable Intergral Action register (40044/40052).
Derivative Time (40009/40025): Derivative time, entered as seconds per repeat, is the time that the controller looks ahead at the ramping
error to see what the proportional contribution will be and it matches that value every Derivative time. As long as the ramping error exists, the Derivative action is repeated by Proportional action every derivative time. Increasing the derivative time helps to stabilize the response, but too high of a derivative time, coupled with noisy signal processes, may cause the output to fluctuate too greatly, yielding poor control. Setting the time to zero disables Derivative Action.
Control Mode (40041/40049): In Automatic Mode, the percentage of Output Power is automatically determined by PID or On/Off Control.
In Manual Mode, the percentage of Output Power is entered manually. For more information, see Control Mode Explanations Section.
Output Power (40005/40021): This parameter can only be changed by direct entry in Manual Mode. For more details on this parameter, see
the Control Mode Explanations Section.
Offset Power (Manual Reset) (40010/40026): If the Integral Time is set to zero (Automatic Reset is off), it may be necessary to modify the
output power to eliminate errors in the steady state. The offset power is used to shift the proportional band to compensate for errors in the steady state. If Integral Action is later invoked, the controller will re-calculate the internal integral value to provide “bumpless” transfer.
Auto-Tune Code (40013/40029): Prior to starting Auto-Tune, this code should be set to achieve the necessary dampening level under PID
Control. When set to zero, it yields the fastest process response with possible overshoot. A setting of 2 yields the slowest response with the least amount of overshoot. If the Auto-Tune Code is changed, Auto-Tune needs to be reinitiated for the changes to affect the PID settings. Auto-tune is initiated by writing a ‘1’ to the Auto-Tune start register (40011/40027). The Auto-Tune phase will be shown in register (40012/40028). For more information, see PID Tuning Explanations Section.
STEP 8 PROGRAMMING THE INPUT SETUP
Input Type (40101/40201): Select the proper input type from the pull down menu. Make sure the input
jumpers are set to match the input signal selection.
Scale (40102/40202): Select either degrees Fahrenheit or Celsius. For mV, resistance, voltage or current types,
this has no effect. If changed, check all temperature related values, as the DLC does not automatically convert these values.
Resolution (40103/40203): For all temperature and ohms Input Types low (x1) resolution selects whole units
of measure. In these same modes, high (x10) resolution selects tenth of units of measure. For mV mode, low selects tenths of mV and high selects hundredths of mV. If changed, be sure to check all parameters because the controller does not automatically convert related parameter values. For voltage or current types, this has no effect.
Rounding (40104/40204): Rounding selections other than 1 cause the process value to round to the nearest
rounding increment selected. (For example, rounding of 5 causes 122 to round to 120 and 123 to round to
125.) Rounding starts at the least significant digit of the process value. If the signal is inherently jittery, the process value may be rounded to a value higher than 1. If the range of the signal exceeds the required resolution (for example, 0-1000 psi, but only 10 psi resolution is required), a rounding increment of 10 will effectively make the reading more stable.
Digital Filtering (40105/40205): The filter is an adaptive digital filter that discriminates between measurement
noise and actual process changes. If the signal is varying too greatly due to measurement noise, increase the filter value. If the fastest controller response is needed, decrease the filter value.
Span Correction (40106/40206): This value is the correction slope. A span of 1.0000 applies no correction.
Span only applies to temperature sensor, millivolt, and ohms inputs.
Offset Correction (40107/40207): This value offsets the temperature value by the entered amount. Offset only
applies to temperature sensor, millivolt, and ohms inputs
Channel B Assignment (40198): This is used to configure Channel B to operate as a Remote Setpoint to
Channel A. Channel B PID control is not functional when the input is assigned as a Remote Setpoint.
8
Local/Remote Setpoint Transfer Mode (40199): When cycling from/to Local or Remote Setpoint (register 40046), the response of the controller can be
programmed to act in a variety of ways. The table summarizes the responses for Setpoint transfer options.
LOCAL/REMOTE SETPOINT
TRANSFER MODE
0 - Normal Output may bump. Output may bump.
1 - Auto No output bump. Process error eliminated
2 - Track Output may bump. Local Setpoint (40002) assumes value
Note: In situations where an output bump may occur, the Setpoint ramp function can be used to reduce or eliminate bumping when switching Setpoint modes.
The setpoint ramp feature ramps the setpoint from the old setpoint to the new Setpoint.
Remote Setpoint Ratio Multiplier (40206): This value is used for channel B when it is assigned as a Remote Setpoint Input. The Ratio Multiplier applies to
all input types (0-15).
Remote Setpoint Bias Offset (40207): This value is used for channel B when it is assigned as a Remote Setpoint Input. Scaling Points (40111-40114/40211-40214): Low and high scaling points are necessary to scale the controller for process voltage and current inputs. Each scaling
point has a coordinate pair of input and process value entries. The process value will be linear between and continue past the entries up to the limit of the input range. Reverse acting measurement can be accomplished by reversing the Input or Process entries, but not both. (Do not reverse the input wires to change the action.) To scale a 4-20 mA Input signal to provide process values of 0 to 100.00 (% in hundredths), the Input Low (40113/40213) and Input High (40114/40214) values would be 4000 and 20000 (0.001 mA resolution), and the Process Low (40111/40211) and Process High (40112/40212) values would be 0 and 10000.
Process Decimal Point (Dec Pt) (40115/40215): The decimal point position is used to enable SFDLC display in desired engineering units for voltage and current
Process values. It is not used internally by the DLC.
at rate of integral action. Ramping disabled during transfer.
LOCAL TO REMOTE REMOTE TO LOCAL
No output bump. Process error eliminated at rate of integral action. Ramping disabled during transfer.
of Remote Setpoint (tracks). No output bump.
STEP 9 PROGRAMMING THE SETPOINTS
Setpoint (40002/40018): Enter the setpoint value. Deviation of Process Value (40001/40017) from
setpoint value can be viewed in the Setpoint Deviation register (40006/40022).
Low Limit (40108/40208); High Limit (40109/40209): The controller has programmable high and low
setpoint limit values to restrict the setting range of the setpoint. Set the limits so that the setpoint value cannot be set outside the safe operating area of the process.
Ramp Rate (40110/40210): The setpoint ramp rate can reduce sudden shock to the process and reduce
overshoot on startup or after setpoint changes, by ramping the setpoint at a controlled rate. The ramp rate is 0.1° for input types 0-11, 0.1 for input type 12, 0.01 for input type 13, and 0.1 unit for input types 14-15 per minute. Writing a ‘0’ disables setpoint ramping. The Disable Setpoint Ramping register (40042/40050) can also be used to disable ramping. The Setpoint Ramping In-Process register (40043/40051) will be a ‘1’ during setpoint ramping. While ramping is enabled, the Ramping Setpoint can be viewed in register (40045/40053). The Ramp Rate for CHB is not functional when it is assigned as a Remote Setpoint Input.
Once the ramping setpoint reaches the target setpoint, the setpoint ramp rate disengages until the setpoint is changed again. If the ramp value is changed during ramping, the new ramp rate takes effect. If the setpoint is ramping prior to starting Auto-Tune, the ramping is suspended during Auto-Tune and then resumed afterward using the present Process value as a starting value. Deviation and band alarms are relative to the target setpoint, not the ramping setpoint. A slow process may not track the programmed setpoint rate. At power-up, the ramping setpoint is initialized to the starting process value. Remote/Local Setpoint Select (40046): Channel A setpoint mode can be switched between Local Setpoint operation and Remote Setpoint operation. The
Channel B input must be assigned as a remote setpoint (register 40198).
STEP 10 PROGRAMMING PROFILE SETUP (Optional)
Profile Power Cycle Mode (40321/40421): Upon controller power-on several profile operating modes
exist. Stop: If the Profile was running when powered down, upon power-up, "Stop" places the profile into the
stop or off mode, regardless of the mode prior to the power-down. The active Setpoint is the setpoint of the last segment that ran before power-down.
Abort: If the Profile status was running, paused, or in Error Delay when powered down, upon power-up,
"Abort" will place the controller in manual mode at 0% Output Power. The Setpoint and Ramp Rate are the values they were prior to running the profile. If the Setpoint Controller was 'paused,' they will be set to the values that they were at power-down.
Start: The Start power cycle mode causes the controller to automatically start the profile at Power-up.
This will occur if the unit was in manual or automatic control mode. During maintenance or at other times when this action is not desired, the Profile Power Cycle mode should be changed appropriately.
Resume: At Power-up, Resume causes the profile to continue from the point and phase when power was
removed. If the unit was in ramp phase, the ramping setpoint will start ramping from the initial process value at power-up.
Pause: Upon Power-up, the controller pauses and maintains control at the initial process value (on
power-up), at the phase where the controller was powered down. The user can then determine how to proceed based on the process that is being controlled.
9
Loading...
+ 19 hidden pages