ALARM NOTIFICATIONS CAN BE SENT VIA EMAIL OR TEXT
MESSAGES
10 BASE-T/100 BASE-TX ETHERNET CONNECTION
CAN CONNECT TO AN UNLIMITED NUMBER OF
DEVICES VIA FOUR PROTOCOLS SIMULTANEOUSLY
GENERAL DESCRIPTION
The Data Station Plus was designed to act as a nexus for industrial data
collection and management. The unit offers multiple protocol conversion, data
logging and remote machine access. With three built in serial ports and a 10
Base-T/100 Base-TX Ethernet port, the unit performs protocol conversion,
allowing disparate devices to communicate seamlessly with one another. The
Ethernet port supports up to four protocols simultaneously so even Ethernet to
Ethernet protocols can be converted.
The CompactFlash card allows data to be collected and stored for later
review. The files are stored in simple CSV file format allowing common
applications, such as Microsoft Excel and Access, to view and manage the data.
The free Websync utility provides a means to synchronize the files with a PC’s
hard drive for permanent storage. The CompactFlash card may also be used to
load new configuration files into the Data Station.
The built-in web server allows log files to be retrieved manually, and also
provides access to the unique “virtual HMI”. The virtual HMI is programmed
just like Red Lion’s G3 series of HMI. Any standard web browser such as
Internet Explorer or Netscape may be used to monitor or control the HMI from
a PC anywhere in the world.
The USB port may be used for blazing fast file downloads, or to mount the
Data Station’s CompactFlash card as an external drive to your PC.
The Data Station’s DIN rail mounting saves time and panel space and snaps
easily onto standard top hat (T) profile DIN rail.
DIMENSIONS In inches (mm)
3.09 (78.5)
RS232/PG
STS
USB/PG
CF
RS485
RS232
5.30 (134.7)
4.15 (105.4)
SOFTWARE
The Data Station is programmed with Crimson® 2.0 software for Windows®
2000 or later platforms. The software is an easy to use graphical interface which
can be purchased as part of a kit that includes a manual and cables, or
downloaded free of charge from www.redlion.net.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use the controller to directly command motors, valves, or other
actuators not equipped with safeguards. To do so can be potentially harmful to
persons or equipment in the event of a fault to the controller. An independent
and redundant temperature limit indicator with alarm outputs is strongly
recommended.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2
THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I,
DIVISION 2, GROUPS A, B, C, D, OR NON-HAZARDOUS
LOCATIONS ONLY
CompactFlash is a registered trademark of CompactFlash Association.
ETHERNET
1
SPECIFICATIONS
1. POWER: 24 VDC ± 10%
200 mA min., without expansion card
1 Amp maximum with expansion card fitted
Must use NEC Class 2 or Limited Power Source (LPS) rated power supply.
2. COMMUNICATIONS:
USB/PG Port: Adheres to USB specification 1.1. Device only using Type B
connection.
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
Serial Ports: Format and Baud Rates for each port are individually software
programmable up to 115,200 baud.
RS232/PG Port: RS232 port via RJ12
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12
DH485 TXEN: Transmit enable; open collector, VOH = 15 VDC,
VOL = 0.5 V @ 25 mA max.
Ethernet Port: 10 BASE-T / 100 BASE-TX
RJ45 jack is wired as a NIC (Network Interface Card).
3. LEDs:
STS – Status LED indicates condition of Data Station.
TX/RX – Transmit/Receive LEDs show serial activity.
Ethernet – Link and activity LEDs.
CF – CompactFlash LED indicates card status and read/write activity
4. MEMORY:
On-board User Memory: 4 Mbytes of non-volatile Flash memory.
On-board SDRAM:
DSPSX: 2 Mbytes
DSPGT: 8 Mbytes
Memory Card: CompactFlash Type II slot for Type I and Type II cards.
5. REAL-TIME CLOCK: Typical accuracy is less than one minute per month
drift. Crimson 2.0’s SNTP facility allows synchronization with external servers.
Battery: Lithium Coin Cell. Typical lifetime of 10 years at 25 ºC.
A “Battery Low” system variable is available so that the programmer can
choose specific action(s) to occur when the battery voltage drops below
its nominal voltage.
This unit is NOT field serviceable. All work must be done by a qualified
technician.
6. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range:
DSPSX000 AND DSPGT000: 0 to 50 °C
DSPSX001 AND DSPGT001: -20 to 70 °C
Storage Temperature Range: -30 to 70 °C
Operating and Storage Humidity: 80% max relative humidity,
non-condensing, from 0 to 50 °C
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
Shock to IEC 68-2-27: Operational 30 g
Altitude: Up to 2000 meters
7. CONSTRUCTION: Case body is burgundy high impact plastic and
stainless steel. For indoor use only. Installation Category II, Pollution
Degree 2.
8. POWER CONNECTION: Removable wire clamp screw terminal block.
Wire Gage Capacity: 24 AWG to 12 AWG
Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)
9. MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
10. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
Safety requirements for electrical equipment for measurement, control, and
laboratory use:
EN 61010-1: General Requirements
EN 61010-2-030: Particular Requirements for Testing and Measuring
Circuits
EN 61010-2-201: Particular Requirements for Control Equipment
RoHS Compliant
UL Listed: File #E302106
UL Hazardous: File #E317425
Refer to EMC Installation Guidelines section of the bulletin for additional
information.
11. WEIGHT: 15.1 oz (428 g)
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR
AREA IS KNOWN TO BE NON-HAZARDOUS.
HARDWARE
INSTALLATION
DIN rail should be mounted horizontally so that the unit’s ventilation holes
are vertical in relation to cabinet orientation. A minimum clearance of 1 inch
(25.4 mm) should be maintained above and below the unit in order to ensure
proper thermal regulation.
1
2
Figure 1 - Attach Data Station To DIN Rail
The unit shall be installed inside a UL Listed Industrial Control Panel or
similar type of enclosure. A minimum 3.2 mm distance shall be maintained
between the hazardous live parts of the equipment and accessible parts of the
fire/electrical enclosure.
TOP
1.00"
min. clearance
RS232/PG
STS
USB/PG
CF
RS485
RS232
ETHERNET
1.00"
min. clearance
BOTTOM
2
COMPACTFLASH® CARD
CompactFlash socket is a Type II socket that can accept either Type I or II
cards. Use cards with a minimum of 4 Mbytes and formatted to a maximum of
2 Gbytes (see Note box below) with the Data Station’s CompactFlash socket.
Cards are available at most computer and office supply retailers. CompactFlash
can be used for configuration transfers, data logging, and trending.
CompactFlashInsert Top Side
Towards Left
CompactFlash
(Top Side)
POWER SUPPLY REQUIREMENTS
It is very important that the power supply is mounted correctly if the unit is
to operate reliably. Please take care to observe the following points:
– The power supply must be mounted close to the unit, with usually not more
than 6 feet (1.8 m) of cable between the supply and the Data Station.
Ideally, the shortest length possible should be used.
– The wire used to connect the Data Station’s power supply should be at least
22-gage wire. If a longer cable run is used, a heavier gage wire should be
used. The routing of the cable should be kept away from large contactors,
inverters, and other devices which may generate significant electrical
noise.
– A power supply with an NEC Class 2 or Limited Power Source (LPS) and
SELV rating is to be used. This type of power supply provides isolation to
accessible circuits from hazardous voltage levels generated by a mains
power supply due to single faults. SELV is an acronym for “safety extralow voltage.” Safety extra-low voltage circuits shall exhibit voltages safe
to touch both under normal operating conditions and after a single fault,
such as a breakdown of a layer of basic insulation or after the failure of a
single component has occurred.
Note: Do not remove or insert
the CompactFlash card while
power is applied.
Information stored on a CompactFlash card can be read by a card reader
attached to a PC. This information is stored in IBM (Windows®) PC compatible
FAT16 file format.
EMC INSTALLATION GUIDELINES
Although Red Lion Controls Products are designed with a high degree of
immunity to Electromagnetic Interference (EMI), proper installation and wiring
methods must be followed to ensure compatibility in each application. The type
of the electrical noise, source or coupling method into a unit may be different
for various installations. Cable length, routing, and shield termination are very
important and can mean the difference between a successful or troublesome
installation. Listed are some EMI guidelines for a successful installation in an
industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly connected
to protective earth.
2. Use shielded cables for all Signal and Control inputs. The shield connection
should be made as short as possible. The connection point for the shield
depends somewhat upon the application. Listed below are the recommended
methods of connecting the shield, in order of their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end where the
unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors, feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run through metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter. Also, Signal or Control cables within
an enclosure should be routed as far away as possible from contactors, control
relays, transformers, and other noisy components.
4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI suppression
devices such as Ferrite Suppression Cores for signal and control cables is
Visit www.redlion.net for a complete list of our PSDR Series of NEC Class
2 power supplies.
NOTE
For reliable operation of this and other Red Lion products, one of the
following brands of CompactFlash card must be used...
SimpleTech SMART® Modular
®
SanDisk
Not all of the above manufacturers offer CompactFlash cards recognized to
UL standards, which may be required for your application.
Although RLC products limit use of CompactFlash card memory to 2 GB,
cards with a larger capacity can be used. They MUST be formatted to 2
GB and use the FAT 16 file system. It is recommended to format the CF
card using the format utility from within Crimson.
effective. The following EMI suppression devices (or equivalent) are
recommended:
Fair-Rite part number 0443167251 (RLC part number FCOR0000)
Line Filters for input power cables:
6. To protect relay contacts that control inductive loads and to minimize radiated
and conducted noise (EMI), some type of contact protection network is
normally installed across the load, the contacts or both. The most effective
location is across the load.
a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide
varistor (MOV) across an AC inductive load is very effective at reducing
EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor
switch, care must be taken not to exceed the breakdown voltage of the
transistor when the load is switched. One of the most effective ways is to
place a diode across the inductive load. Most RLC products with solid state
outputs have internal zener diode protection. However external diode
protection at the load is always a good design practice to limit EMI.
Although the use of a snubber or varistor could be used.
RLC part numbers: Snubber: SNUB0000
Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output devices to the
instrument. When a separate input and output common is provided, they
should not be mixed. Therefore a sensor common should NOT be connected
to an output common. This would cause EMI on the sensitive input common,
which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/Support/InstallationConsiderations.
html for more information on EMI guidelines, Safety and CE issues as they
relate to Red Lion Controls products.
Silicon Systems
3
WIRING
CBLPROG0
Ethernet (Crossover)
CBLxxxxx*
POWER CONNECTION
COMMON
+24 VDC
PROGRAMMING PORTS
RS232/PG
CTS
Rx
RS232
USB/PG
COMM
COMM
Tx
RTS
RS232/PG
STS
USB/PG
CF
RS485
RS232
ETHERNET
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT
WHILE CIRCUIT IS ALIVE UNLESS AREA IS KNOW TO BE
NON-HAZARDOUS.
INPUT AND OUTPUT (I/O) WIRING MUST BE IN
ACCORDANCE WITH CLASS I, DIV. 2 WIRING METHODS
AND IN ACCORDANCE WITH THE AUTHORITY HAVING
JURISDICTION.
COMM
+24
N/C
OR
CBLUSB00
OR
ETHERNET
GREEN/AMBER LED
YELLOW LED
COMMUNICATION PORTS
RS232/PG
CTS
Rx
COMM
COMM
RS232
Tx
RTS
RS232/PG
STS
USB/PG
CF
RS485
RS232
ETHERNET
CBLPROG0
OR
SLC 5/03 CPU
RUN
FORCE
FLT
DH485
BATT
RS232
REM
RUN
PROG
POWER
PWR OUT +24
VDC
USER
POWER
PWR OUT COM
120/240 VAC
VAC NEUT
CHASSIS GND
4
RS232
RTS
Tx
COMM
COMM
Rx
CTS
RS232
RS232/PG
STS
USB/PG
CF
RS485
RS232
ETHERNET
CBLxxxxx*
SLC 5/03 CPU
RUN
FORCE
FLT
DH485
BATT
RS232
PROG
REM
RUN
POWER
PWR OUT +24
VDC
USER
POWER
PWR OUT COM
120/240 VAC
VAC NEUT
CHASSIS GND
* Use appropriate communications cable. See Ordering
Information for descriptions of the available cables.
RS485
RS232/PG
TxA
TxB
COMM
TxEN
RxB
RxA
TxA
TxB
RS485
STS
USB/PG
CF
RS485
RS232
ETHERNET
CBLxxxxx*
PORT 3 - ETHERNET CONNECTION
RS232/PG
STS
GREEN/AMBER LED
YELLOW LED
USB/PG
CF
RS485
RS232
ETHERNET
DATA STATION PORT PIN OUTS
1
COMMON
2
24VDC ±10%
3
N/C
POWER
CTS (PIN 1)
COMMTxCOMM
Rx
RS232
RS232/PG PORT
USB/PG
COMM
RxA
RxB
TxA
TxB (PIN 1)
TxEN
RS485
COMMS
PORT
RTS (PIN 6)
TxA (PIN 8)
CONNECTOR
RS232/PG
STS
USB/PG
CF
RS485
RS232
Standard Ethernet cable
EXPANSION
PORT
SLC 5/03 CPU
RUN
FORCE
FLT
DH485
BATT
RS232
PROG
REM
RUN
POWER
WARNING: Do NOT use a standard DH-485
cable to connect this port to Allen Bradley
PWR OUT +24
VDC
USER
POWER
PWR OUT COM
equipment.
120/240 VAC
VAC NEUT
CHASSIS GND
TROUBLESHOOTING
If for any reason you have trouble operating,
connecting, or simply have questions concerning your
new Data Station, contact Red Lion’s technical support.
For contact information, refer to the back page of this
bulletin for phone and fax numbers.
EMAIL: techsupport@redlion.net
Web Site: http://www.redlion.net
COMM
CTS (PIN 1)
COMMRxTx
RS232
COMMS
PORT
GREEN/
LED
AMBER
ETHERNET
(NIC)
RTS (PIN 6)TxB
YELLOW
LED
ETHERNET
5
TX
5V
8
1
7
2
TxB
TxA
130K
130K
5
TxEN (OC)
RX
130K
5V
130K
RxB
4
RxA
3
GND
6
TxEN (OC)
TX/RX
130K
5
TxA
2
8
130K
5V
7
1
TxB
6 GND
COMMUNICATING WITH THE DATA STATION
CONFIGURING A DATA STATION
The Data Station is configured using Crimson® 2.0 software. Crimson 2.0 is
available as a free download from Red Lion’s website, or it can be ordered on
CD. Updates to the software for new features and drivers are posted on the
website as they become available. By configuring the Data Station using the
latest version of the software, you are assured that your unit has the most up to
date feature set. Crimson® 2.0 software can configure the Data Station through
the RS232/PG port, USB/PG port, Ethernet, or CompactFlash. The USB/PG
port is connected using a standard USB cable with a Type B connector.
The driver needed to use the USB port will be installed with Crimson 2.0.
The RS232/PG port uses a programming cable made by Red Lion to connect to
the DB9 COM port of your computer. If making your own cable, refer to the
“Data Station Port Pin Outs” for wiring information.
The CompactFlash can be used to program a Data Station by placing a
configuration file and firmware on the CompactFlash card. The card is then
inserted into the target Data Station and powered. Refer to the Crimson® 2.0
literature for more information on the proper names and locations of the files.
CABLES AND DRIVERS
Red Lion has a wide range of cables and drivers for use with many different
communication types. A list of these drivers and cables along with pin outs is
available from Red Lion’s website. New cables and drivers are added on a
regular basis. If making your own cable, refer to the “Data Station Port Pin
Outs” for wiring information.
USB, DATA TRANSFERS FROM THE
COMPACTFLASH CARD
WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.
In order to transfer data from the CompactFlash card via the USB port, a
driver must be installed on your computer. This driver is installed with Crimson
2.0 and is located in the folder C:\Program Files\Red Lion Controls\Crimson
2.0\Device\ after Crimson 2.0 is installed. This may have already been
accomplished if your Data Station was configured using the USB port.
Once the driver is installed, connect the Data Station to your PC with a USB
cable, and follow “Mounting the CompactFlash” instructions in the Crimson 2.0
user manual.
Note that using the USB port for frequent data transfers is not recommended.
For frequent data transfers it is recommended that the Ethernet connection be
used. Through the Ethernet connection a web page can be set up to view logged
data. Refer to the Crimson 2.0 manual for details.
Note: The USB port is for system set-up and diagnostics and is not intended for
permanent connection.
RS232 PORTS
The Data Station has two RS232 ports. There is the RS232/PG port and the
COMMS port. Although only one of these ports can be used for programming,
both ports can be used for communications with a PLC. The RS232/PG port can
be used for either master or slave protocols.
RS422/485 PORT
The Data Station has one RS422/485 port. This port can be configured to act
as either RS422 or RS485.
RS422/485 4-WIRE
CONNECTIONS
RS485 2-WIRE
CONNECTIONS
Note: All Red Lion® devices connect A to A and B to B, except for Paradigm
devices. Refer to www.redlion.net for additional information.
DH485 COMMUNICATIONS
The Data Station’s RS422/485 COMMS port can also be used for Allen
Bradley DH485 communications.
WARNING: DO NOT use a standard DH485 cable to connect this port to Allen
Bradley equipment. A cable and wiring diagram are available from Red Lion.
ETHERNET COMMUNICATIONS
Ethernet communications can be established at either 10 BASE-T or 100
BASE-TX. The Data Station’s RJ45 jack is wired as a NIC (Network Interface
Card). For example, when wiring to a hub or switch use a straight-through
cable, but when connecting to another NIC use a crossover cable.
The Crimson 2.0 manual contains additional information on Ethernet
communications.
6
LEDS
STS – STATUS LED
The green Status LED provides information regarding the state of the Data
Station. This includes indication of the various stages of the start-up routine
(power-up), and any errors that may occur.
Startup Routine
INDICATION
Rapidly Flashing
SteadyData Station is operating properly.
Data Station is currently running the boot loader and/
or being flash upgraded by Crimson.
USER COMMUNICATION PORTS - TX/RX LEDS
INDICATIONLED
TransmittingGREEN
ReceivingRED
Note: LEDs are not available on the Programming Port: RS232/PG.
ETHERNET LEDS
INDICATIONLED
Link EstablishedYELLOW (Solid)
Network ActivityYELLOW (Flashing)
CF – COMPACTFLASH LED
INDICATIONLED
No CompactFlash Card is present.Off
Valid CompactFlash card is present.Steady
CompactFlash card is being checked.Flashing Rapidly
Unit is writing to the CompactFlash, either
Flickering
Flashing Slowly
1. Do not turn off power to the unit while this light is flickering. The unit writes
data in two minute intervals. Later Microsoft operating systems will not lock
the drive unless they need to write data; Windows 98 may lock the drive any
time it is mounted, thereby interfering with logging. Refer to “Mounting the
CompactFlash” in the Crimson 2.0 User Manual.
because it is storing data, or because the PC
connected via the USB port has locked the drive.
Incorrectly formatted CompactFlash card present.
1
10 BASE-T CommunicationsGREEN
100 BASE-TX CommunicationsAMBER
ORDERING INFORMATION
TYPEMODEL NO.DESCRIPTIONPART NUMBER
Data Station with multiple protocol converter, data logger, web server with Virtual HMI up to
QVGA (320 x 240) and expansion slot.
Data Station with multiple protocol converter, data logger, web server with Virtual HMI up to
Data Station PlusDSP
Communications
Cables (10 feet)
SoftwareSFCRM2
Power SupplyPSDRDIN Rail Power SupplyPSDRxxxx
Accessories
1
Visit www.redlion.net for a list of communication drivers and cables.
2
Use this part number to purchase the Crimson® software on CD with a printed manual, USB cable, and RS-232 cable. Otherwise, download free of charge
from www.redlion.net.
3
Antenna (G3QANT00) is NOT included with the card. Must be purchased separately if needed.
4
Red Lion offers RJ modular jack adapters. Refer to the DR literature for complete details.
5
Industrial grade two million write cycles. SMART Modular Technologies model SG9CF (UL Listed Directory Category NWGQ).
CBL
XCCNCANopen option card for Modular Controller or Data Station PlusXCCN0000
XCDNDeviceNet option card for Modular Controller or Data Station PlusXCDN0000
XCGSMGSM/GPRS Modem option card for Modular Controller or Data Station Plus
XCPBPROFIBUS option card for Modular Controller or Data Station PlusXCPBDP00
XCRSRS232/485 option card for Modular Controller or Data Station PlusXCRS0000
G3CFCompactFlash Card
QVGA (320 x 240), expansion slot, and extended operating temperature.
Data Station with multiple protocol converter, data logger, web server with Virtual HMI up to VGA
(640 x 480) size and expansion slot with increased SDRAM.
Data Station with multiple protocol converter, data logger, web server with Virtual HMI up to VGA
(640 x 480), expansion slot with increased SDRAM, and extended operating temperature.
RS-232 Programming CableCBLPROG0
USB CableCBLUSB00
Communications Cables
Crimson® 2.0 2, Manual and Download Cable
DRDIN Rail Mountable Adapter Products
1
3
5
4
DSPSX000
DSPSX001
DSPGT000
DSPGT001
CBLxxxxx
SFCRM200
XCGSM000
G3CFxxxx
DRxxxxxx
7
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
The Company warrants the products it manufactures against defects in materials and workmanship
LIMITED WARRANTY
for a period limited to two years from the date of shipment, provided the products have been stored,
handled, installed, and used under proper conditions. The Company’s liability under this limited
warranty shall extend only to the repair or replacement of a defective product, at The Company’s
option. The Company disclaims all liability for any affirmation, promise or representation with
respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against
damages, claims, and expenses arising out of subsequent sales of RLC products or products
containing components manufactured by RLC and based upon personal injuries, deaths, property
damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be
to any extent liable, including without limitation penalties imposed by the Consumer Product Safety
Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty
Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except
those expressly contained herein. The Customer acknowledges the disclaimers and limitations
contained herein and relies on no other warranties or affirmations.
Red Lion Controls
Europe
Softwareweg 9
NL - 3821 BN Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
201-B, 2nd Floor, Park Centra
Opp 32 Mile Stone, Sector-30
Gurgaon-122002 Haryana, India
Tel +91 984 487 0503
Red Lion Controls
China
Unit 302, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113 3688
Fax +86 21 6113 3683
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.