Red Lion CUB5USB User Manual

1
DESCRIPTION
This bulletin serves as a guide for the installation, configuration and operation of the CUB5 USB Programming plug-in card for the CUB5. The plug-in card is a separately purchased option card that plugs into the main circuit board of the meter. The CUB5USB card in conjunction with the Crimson®programming software enables the user to configure CUB5 on a PC. The CUB5USB requires installation of drivers which are included with the Crimson Programming software. Following installation of the drivers, the card appears as a Virtual communications port.
Crimson is a Windows
®
based program that allows configuration of the CUB®5 meters from a PC. Crimson offers standard drop-down menu commands, that make it easy to program the CUB5 meters. The CUB5 program can then be saved in a PC file for future use. A CUB5 serial plug-in card is required to program the meter using the software.
MODEL CUB5USB - USB PROGRAMMING OPTION CARD
INSTALLING PLUG-IN CARDS
The card plugs into the main circuit board of the meter as shown.
Perform USB driver installation below prior to powering the
CUB5 and connecting CUB5USB to a PC USB port.
WARNING: Disconnect all power to the unit before
installing Plug-in card.
CAUTION: The Plug-in cards and main circuit board contain static
sensitive components. Before handling the cards, discharge static charges from your body by touching a grounded bare metal object. Ideally, handle the cards at a static controlled clean workstation. Also, only handle the cards by the edges. Dirt, oil or other contaminants that may contact the cards can adversely affect circuit operation.
USB DRIVER INSTALLATION
1. Download and install the latest Crimson 2 build on your Windows®compatible PC. Earlier builds may not have the RLC Virtual Comm port drivers. Crimson software is available as a free download at http://www.redlion.net.
2. Install CUB5USB card into CUB5 meter and apply power to the CUB5.
3. Connect Type A USB cable to computer and CUB5USB option card. Windows will prompt you for the location of the drivers for the device. The default location for these drivers is “C:\Program Files\Red Lion controls\Crimson 2.0\Device.” When the hardware setup appears, choose “Install from a list or Specific location,” click Next, and then check “Include this location...” and click the Browse button. Point the Wizard at the location specified above or whatever other location you specified during installation of the software. It is important that you perform this step correctly, or you may have to manually remove the drivers using the Device Manager, and repeat the installation once more.
Note: Crimson’s USB drivers have not been digitally signed by Microsoft®,
and you will therefore see a dialog offering you the chance to stop the installation. You should be sure to select the Continue option to indicate that you do indeed wish to install the drivers.
4. Windows will automatically assign a comms port to the CUB5USB. To determine the port assigned, open “System Properties” from within Windows®Control Panel. Select the Hardware tab, and click the “Device Manager” button. Expand the “Ports” line. Take note of which Comms port is assigned to “RLC Virtual Comm port”. It must be Com4 or lower to operate with Crimson 2. If higher, right-click on the entry and select “Properties,” “Port Settings” tab, and then “Advanced” button. Select a Coms port that is COM4 or lower and is not physically being used.
SPECIFICATIONS
CUB5USB PROGRAMMING CARD
Type: USB Virtual Comms Port Baud Rate: 300 to 38.4k Unit Address: 0 to 99
CRIMSON 2 SYSTEM REQUIREMENTS
• Windows 2000, XP, or Vista
• RAM and free disk space as required by the chosen operating system.
• An additional 50 MB of disk space for software installation.
• A display of at least 800 by 600 pixels
• A USB port for downloading to the CUB5
ORDERING INFORMATION
* Crimson software is available for download from http://www.redlion.net/
USB Card
MODEL NO. DESCRIPTION PART NUMBER
SFCRD*
SFCRUSB*
CBLUSB
CUB5USB
Crimson 2 PC Configuration Software for Windows 98, ME, 2000 and XP
USB Programming Kit containing USB Card, USB Cable and Crimson software
Type A to B USB Cable
CUB5 USB Programming Card
SFCRD200
SFCRUSB0
CBLUSB00
CUB5USB0
LIMITED WARRANTY
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
Bulletin No. CUB5USB-A
Drawing No. LP0770
Released 10/08
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
DATA BIT *
ABBREVIATED PRINTING *
PRINT OPTIONS *
PARITY BIT*
300 1200 600 2400
19200 38400
4800 9600
7-bit 8-bit
NO Odd EVEN
NO YES
NO YES
Module 5 is the programming module for the Serial Communications Parameters. The only paramters of concern when utilizing the CUB5USB programming option card to communicate with Crimson 2 programming software is the Baud Rate and Meter Address. The Parameters are only accessible when an optional CUB5USB, RS232 or RS485 serial communications card is installed in the meter.
MODULE 5 - SERIAL
COMMUNICATIONS PARAMETERS (5-SEr)
PARAMETER MENU
BAUD RATE
Set the baud rate to match that of other serial communications equipment. Normally, the baud rate is set to the highest value that all of the serial communications equipment is capable of transmitting and receiving.
Select either 7- or 8-bit data word length. Set the word length to match the other serial communications equipment on the serial link.
This parameter only appears when the Data Bit parameter is set to a 7-bit data word length. Set the parity bit to match that of the other serial equipment on the serial link. The meter ignores parity when receiving data and sets the parity bit for outgoing data. If parity is set to
NO, an additional stop bit is used
to force the frame size to 10 bits.
This parameter determines the formatting of data transmitted from the meter
in response to a Transmit Value command or a Block Print Request. Select NO for a full print transmission, consisting of the meter address, mnemonics, and parameter data. Select YES for abbreviated print transmissions, consisting of the parameter data only. This setting is applied to all the parameters selected in the PRINT OPTIONS. (Note: If the meter address is 0, the address will not be sent during a full transmission.)
This parameter selects the meter values transmitted in response to a Print Request. A print request is also referred to as a block print because more than one parameter can be sent to a printer or computer as a block.
Selecting YES displays a sublist for choosing the meter parameters to appear in the print block. All active parameters entered as YES in the sublist will be transmitted during a block print. Parameters entered as NO will not be sent.
The “Print All” (P-ALL) option selects all meter values for transmitting (YES), without having to individually select each parameter in the sublist.
Note: Inactive parameters will not be sent regardless of the print option setting. For example, the Setpoint value(s) will not be sent unless an optional setpoint card is installed in the meter.
ª
«
9600
bAUd
ª
«
7-bit
dAtA
ª
«
Odd
PAr
ª
«
NO
Abbr
ª
«
NO
OPt
Indicates Program Mode Alternating Display.
Factory Settings are shown.
ª
«

C"6E
Parameter
Selection/Value
* - Disregard these parameters when configuring unit to upload or download wth Crimson.
* - Disregard these parameters when configuring unit to upload or download wth Crimson software.
METER ADDRESS
Enter the serial node address. With a single unit, an address is not needed and a value of zero can be used (RS232 applications). Otherwise, with multiple bussed units, a unique address number must be assigned to each meter. The node address applies specifically to RS485 applications.
ª
«
00
Addr
0 to 99
Red Lion Controls
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls AP
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
Red Lion Controls BV
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Loading...