MODEL CUB5TC - MINIATURE ELECTRONIC 5-DIGIT
THERMOCOUPLE METER
CONFORMS TO ITS-90 TEMPERATURE STANDARD
COLD JUNCTION COMPENSATION (Enable/Disable)
MINIMUM AND MAXIMUM DISPLAY CAPTURE
LCD, REFLECTIVE OR GREEN/RED LED BACKLIGHTING
0.48" (12.2 mm) HIGH DIGITS
OPTIONAL SETPOINT OUTPUT CARD
OPTIONAL SERIAL COMMUNICATION CARD (RS232 or RS485)
OPTIONAL USB PROGRAMMING CARD
OPERATES FROM 9 TO 28 VDC POWER SOURCE
FRONT PANEL OR CRIMSON PROGRAMMABLE
THERMOCOUPLE INPUTS
Thermocouple types T, E, J, K, R, S, B, N, or mV
PROGRAMMABLE TEMPERATURE OFFSET
SELECTABLE °F or °C WITH 1 or 0.1 DEGREE RESOLUTION
°F OR °C DISPLAY ANNUNCIATORS
DISPLAY COLOR CHANGE CAPABILITY AT SETPOINT OUTPUT
NEMA 4X/IP65 SEALED FRONT BEZEL
U
R
C
US LISTED
L
IND. CONT. EQ.
51EB
Bulletin No. CUB5TC-H
Drawing No. LP0643
Released 02/13
GENERAL DESCRIPTION
The CUB5 provides the user the ultimate in flexibility, from its complete user
programming to the optional setpoint control and communication capability.
The CUB5TC accepts a thermocouple input and provides a temperature display
in Celcius or Farenheit. The meter also features minimum and maximum
display capture, display offset, °F or °C indicator, and programmable user input.
The display can be toggled either manually or automatically between the
selected displays.
The CUB5 display has 0.48" (12.2 mm) high digits. The LCD is available in
two versions, reflective and red/green backlight. The backlight version is user
selectable for the desired color and also has variable display intensity.
The capability of the CUB5 can be easily expanded with the addition of
option cards. Setpoint capability is field installable with the addition of the
setpoint output cards. Serial communications capability for RS232 or RS485 is
added with a serial option card.
The CUB5 can be powered from an optional Red Lion Micro-Line/Sensor
Power Supply (MLPS), which attaches directly to the back of a CUB5. The
MLPS is powered from 85 to 250 VAC and provides up to 400 mA to drive the
unit and sensors.
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
.13 (3.3)
1.54 (39.1)
SEL
RST
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in this
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this meter to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the meter.
CAUTION: Risk of Danger.
Read complete instructions prior to
installationand operation of the unit.
1.29 (32.8)
CAUTION: Risk of electric shock.
+.024
1.30
-.000
+6
(33 )
-0
2.95 (74.9)
.15 (3.8)
1.71
+.025
2.68
-.000
+8
(68 )
1
orderinG inforMation
TYPEMODEL NO.DESCRIPTIONPART NUMBER
CUB5CUB5TC
CUB5RLYSingle Relay Option CardCUB5RLY0
Optional Plug-in Cards
Accessories
1
Crimson software is a free download from http://www.redlion.net
CUB5SNKDual Sinking Open Collector Output cardCUB5SNK0
CUB5COM
CUB5USBUSB Programming Card CUB5USB0
MLPS
CBLPROGProgramming Cable RS232 (RJ11-DB9)CBLPROG0
CBPROProgramming Cable RS485 (RJ11-DB9)CBPRO007
SFCRDCrimson PC Configuration Software for Windows 98, ME, 2000, XP
CBLUSBUSB Programming CableCBLUSB00
Thermocouple Meter with Reflective DisplayCUB5TCR0
Thermocouple Meter with Backlight DisplayCUB5TCB0
RS485 Serial Communications CardCUB5COM1
RS232 Serial Communications CardCUB5COM2
+12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max outMLPS1000
+24 VDC Micro-Line Power Supply, 85 to 250 VAC source, 200 mA max outMLPS2000
General Meter SpecificationS
1. DISPLAY: 5 digit LCD 0.48" (12.2 mm) high digits
CUB5TCR0: Reflective LCD with full viewing angle
CUB5TCB0: Transmissive LCD with selectable red or green LED backlight,
viewing angle optimized. Display color change capability with output state
when using an output module.
2. POWER: Input voltage range is +9 to +28 VDC with short circuit and input
polarity protection. Must use an RLC model MLPS or an NEC Class 2 or
Limited Power Source (LPS) rated power supply.
MODEL
NO.
CUB5TCR0---10 mA40 mA
CUB5TCB0Red (max intensity)85 mA115 mA
CUB5TCB0Green (max intensity)95 mA125 mA
DISPLAY COLOR
INPUT CURRENT
@ 9 VDC WITHOUT
CUB5RLY0
INPUT CURRENT
@ 9 VDC WITH
CUB5RLY0
3. READOUT:
Resolution: 1 or 0.1 degrees
Scale: °F or °C
Offset Range: -999 to 9999 display units
4. THERMOCOUPLE INPUTS:
Isolation: TC+ and TC- terminals are not electrically isolated from the power
supply or optional comms cards.
Open Sensor Display:
Overrange/Underrange Input: /
Overrange/Underrange Display : “.....”/“-.....”
Maximum Input Voltage: 30 VDC, TC+ to TC-
Maximum Input Voltage TC-: 3 VDC max. with respect to common
±°C
2.3
2.7
1.9
2.3
4.5
4.5
2.8
ACCURACY
@ -35 to 75°C
±°C
5.8
4.9
4.3
5.8
15.0
15.0
42.6<540°C
15.0>540°C
8.1
0.08 mV
WIRE COLOR
(+) blue
(-) red
(+) purple
(-) red
(+) white
(-) red
(+) yellow
(-) red
no
standard
no
standard
no
standard
(+) orange
(-) red
no
standard
BS 1843ANSI
(+) white
(-) blue
(+) brown
(-) blue
(+) yellow
(-) blue
(+) brown
(-) blue
(+) white
(-) blue
(+) white
(-) blue
no
standard
(+) orange
(-) blue
no
standard
-200 to 400°C
T
-328 to 752°F
-200 to 871°C
E
-328 to 1600°F
-200 to 760°C
J
-328 to 1400°F
-200 to 1372°C
K
-328 to 2502°F
-50 to 1768°C
R
-58 to 3214°F
-50 to 1768°C
S
-58 to 3214°F
200 to 1820°C
B
392 to 3308°F
-200 to 1300°C
N
-328 to 2372°F
ACCURACY
RANGETC TYPE
@ 23°C
9.1<540°C
4.5>540°C
0.02 mV-10.00 to 65.00mV
*After 20 min. warm-up. Accuracy is specified in two ways: Accuracy at
23°C and 15 to 75% RH environment; and Accuracy over a -35 to 75°C and 0
to 85% RH (non condensing) environment. Accuracy specified over the -35 to
75°C operating range includes meter tempco and cold junction tracking effects.
The specification includes the A/D conversion errors, linearization conformity,
and thermocouple cold junction compensation. Total system accuracy is the sum
of meter and probe errors. Accuracy may be improved by field calibrating the
meter readout at the temperature of interest.
5. RESPONSE TIME:
Display: 500 msec min.
Output: 800 msec max (with input filter setting of 0)
6. USER INPUT (USR): Programmable input. Connect terminal to common
(USR COMM) to activate function. Internal 10KΩ pull-up resistor to +9 to
28 VDC.
Threshold Levels: VIL = 0.7 V max; VIH = 2.4 V min; V
Response Time: 5 msec typ.; 50 msec debounce (activation and release)
7. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant
UL Recognized Component: File #E179259
UL Listed: File #E137808
Type 4X Outdoor Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
Refer to EMC Installation Guidelines for additional information.
8. MEMORY: Nonvolatile E2PROM memory retains all programming
parameters and max/min values when power is removed.
10. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range for CUB5TCR0: -35 to 75°C
Operating Temperature Range for CUB5TCB0 depends on display color
and intensity level as per below:
Red Display1 & 2-35 to 75°C
Green Display1 & 2-35 to 75°C
Storage Temperature: -35 to 85°C
Operating and Storage Humidity: 0 to 85% max. relative humidity (non-
condensing)
Vibration to IEC 68-2-6: Operational 5-500 Hz, 5 g
Shock to IEC 68-2-27: Operational 30 g
Altitude: Up to 2000 meters
11. CONSTRUCTION: This unit is rated for NEMA 4X/IP65 requirements for
outdoor use. Installation Category I, Pollution Degree 2. High impact plastic
case with clear viewing window. Panel gasket and mounting clip included.
12. WEIGHT: 3.2 oz (100 g)
1
INTENSITY LEVELTEMPERATURE
3-35 to 70°C
4-35 to 60°C
5-35 to 50°C
3-35 to 65°C
4-35 to 50°C
5-35 to 35°C
SFCRD200
= 28 VDC
MAX
2
optional pluG-in cardS
PANEL
GASKET
BEZEL
PANEL
MOUNTING SCREW
NUT FASTENER
MOUNTING CLIP
ADDING OPTION CARDS
The CUB5 meters can be fitted with optional output cards and/or serial
communications cards. The details for the plug-in cards can be reviewed in the
specification section below. The plug-in cards, that are sold separately,can be
installed initially or at a later date.
WARNING: Disconnect all power to the unit before
installing Plug-in card.
SINGLE RELAY CARD
Type: Single FORM-C relay
Isolation To Sensor & User Input Commons: 1400 Vrms for 1 min.
Note: Non-grounded (isolated) thermocouple probes must be used when
multiple units are connected in an RS485 network, or measurement
errors will occur.
Baud Rate: 300 to 38.4k
Data Format: 7/8 bits; odd, even, or no parity
Bus Address: 0 to 99; max 32 meters per line
Transmit Delay: Selectable (refer to CUB5COM bulletin)
RS232 SERIAL COMMUNICATIONS CARD
Type: RS232 half duplex (non-isolated)
Baud Rate: 300 to 38.4k
Data Format: 7/8 bits; odd, even, or no parity
USB PROGRAMMING CARD
Type: USB virtual comms port
Connection: Type B
Baud Rate: 300 to 38.4k
Unit Address: 0 to 99
INSTALLATION
The meter meets NEMA 4X/IP65 requirements when properly installed. The
unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel
gasket over the rear of the unit to the back of the bezel.
The unit should be installed fully assembled. Insert
the unit into the panel cutout.
While holding the unit in place, push the panel
latch over the rear of the unit so that the tabs of the
panel latch engage in the slots on the case. The
panel latch should be engaged in the
farthest forward slot possible. To achieve a proper seal, tighten the latch screws
evenly until the unit is snug in the panel (Torque to approx. 28 to 36 in-oz [0.202
to 0.26 N-m]). Do not over-tighten the screws.
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the operating
temperature and provides good air circulation. Placing the unit near devices that
generate excessive heat should be avoided.
The bezel should only be cleaned with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the
keypad of the unit.
+.025
2.68
+.8
(68 )
-.0
-.000
1.30
(33 )
+.024
-.000
+.6
-.0
3
2.0 inStallinG pluG-in cardS
WARNING: Exposed line voltage exists on the circuit boards.
Remove all power to the meter and load circuits before
accessing inside of the meter.
CAUTION: The Plug-in cards and main circuit board contain static
sensitive components. Before handling the cards, discharge
static charges from your body by touching a grounded bare
metal object. Ideally, handle the cards at a static controlled
clean workstation. Also, only handle the cards by the edges.
Dirt, oil or other contaminants that may contact the cards can
adversely affect circuit operation.
3.0 WirinGthe Meter
REMOVING THE REAR COVER
To remove the rear cover, locate the cover locking tab below the 2nd and 3rd
input terminals. To release the tab, insert a small, flat blade screwdriver between
the tab and the plastic wall below the terminals. Inserting the screwdriver will
provide enough pressure to release the tab locks. To replace the cover, align the
cover with the input terminals and press down until the cover snaps into place.
The Plug-in cards are separately purchased option cards that perform specific
functions. The cards plug into the main circuit board of the meter.
Setpoint Card
Comms or
Programming
Card
Locking Tab
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the
back of the meter. All conductors should conform to the meter’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that the power
supplied to the meter (DC or AC) be protected by a fuse or circuit breaker.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed
(stranded wires should be tinned with solder.) Insert the lead under the correct
screw-clamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although Red Lion Controls Products are designed with a high degree of
immunity to Electromagnetic Interference (EMI), proper installation and wiring
methods must be followed to ensure compatibility in each application. The type
of the electrical noise, source or coupling method into a unit may be different
for various installations. Cable length, routing, and shield termination are very
important and can mean the difference between a successful or troublesome
installation. Listed are some EMI guidelines for a successful installation in an
industrial environment.
1. A unit should be mounted in a metal enclosure, which is properly connected
to protective earth.
2. Use shielded cables for all Signal and Control inputs. The shield connection
should be made as short as possible. The connection point for the shield
depends somewhat upon the application. Listed below are the recommended
methods of connecting the shield, in order of their effectiveness.
a. Connect the shield to earth ground (protective earth) at one end where the
unit is mounted.
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is over 1 MHz.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors, feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run through metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter. Also, Signal or Control cables within
an enclosure should be routed as far away as possible from contactors,
control relays, transformers, and other noisy components.
4. Long cable runs are more susceptible to EMI pickup than short cable runs.
5. In extremely high EMI environments, the use of external EMI suppression
devices such as Ferrite Suppression Cores for signal and control cables is
effective. The following EMI suppression devices (or equivalent) are
recommended:
Fair-Rite part number 0443167251 (RLC part number FCOR0000)
Line Filters for input power cables:
Schaffner # FN2010-1/07 (RLC part number LFIL0000)
6. To protect relay contacts that control inductive loads and to minimize radiated
and conducted noise (EMI), some type of contact protection network is
normally installed across the load, the contacts or both. The most effective
location is across the load.
a. Using a snubber, which is a resistor-capacitor (RC) network or metal oxide
varistor (MOV) across an AC inductive load is very effective at reducing
EMI and increasing relay contact life.
b. If a DC inductive load (such as a DC relay coil) is controlled by a transistor
switch, care must be taken not to exceed the breakdown voltage of the
transistor when the load is switched. One of the most effective ways is to
place a diode across the inductive load. Most RLC products with solid
state outputs have internal zener diode protection. However external diode
protection at the load is always a good design practice to limit EMI.
Although the use of a snubber or varistor could be used.
RLC part numbers: Snubber: SNUB0000
Varistor: ILS11500 or ILS23000
7. Care should be taken when connecting input and output devices to the
instrument. When a separate input and output common is provided, they
should not be mixed. Therefore a sensor common should NOT be connected
to an output common. This would cause EMI on the sensitive input common,
which could affect the instrument’s operation.
Visit RLC’s web site at http://www.redlion.net/Support/InstallationConsiderations.
html for more information on EMI guidelines, Safety and CE issues as they
relate to Red Lion Controls products.
4
3.1 POWER WIRING
CO
61
DC Power
+9 to +28 VDC: +VDC
Power Common: -VDC
USR COMM
3.2 USER INPUT WIRING
Sinking Logic
USR COMM
USR
TC-
USR
-
+
TC+
The user input of the meter is
internally pulled up to +9 to +28 V
with 10 K resistance. The input is
active when it is pulled low (<0 .7 V).
Connect external switching device between the
}
User Input terminal and User Input Common.
USR
USR COMM
TC-
TC +
PWR COMMON
+9-28 VDC
3.3 INPUT WIRING
Thermocouple
TC-
TC+
-
+
CAUTION: Power input common and sensor input common are NOT isolated
from user input common. In order to preserve the safety of the meter
application, the power input common and the sensor input common must
be suitably isolated from hazardous live earth referenced voltages; or input
common must be at protective earth ground potential. If not, hazardous live
voltage may be present at the User Inputs and User Input Common
terminals. Appropriate considerations must then be given to the potential
of the user input common with respect to earth common; and the common
of the isolated plug-in cards with respect to input common.
3.4 SETPOINT (OUTPUT) WIRING
SINGLE SETPOINT RELAY PLUG-IN CARD
COM
N.O.
N.C.
PWR COMMON
ELECTRICAL CONNECTIONS
COM
N.O.
N.C.
+9-28 VDC
DUAL SETPOINT N-FET OPEN DRAIN PLUG-IN CARD
COM
OSNK1
OSNK2
3.5 SERIAL COMMUNICATION WIRING
SERIAL COMMUNICATIONS PLUG-IN CARD
N/C
COMM
N/C
B-
534
61
RS485
RJ11 CONNECTOR PIN OUTS
A+
N/C
2
N/C
TX
5
RS232
COMM
43
COMM
2
N/C
RX
ELECTRICAL CONNECTIONS
OSNK 1(2)
(30 V MAX.)
M
Output Common is not isolated from DC Power Common. Load must
be wired between OSNK terminal and V+ of the load supply.
3.6 USB PROGRAMMING
USB PROGRAMING PLUG-IN CARD
5
4.0 revieWinGthe front ButtonSand diSplay
SELRST
BUTTON DISPLAY MODE OPERATIONENTERING PROGRAM MODEPROGRAMMING MODE OPERATION
SELIndex display through enabled valuesPress and hold for 2 seconds to activateStore selected parameter and index to next parameter
RSTResets values (MIN / MAX) or outputs
OPERATING MODE DISPLAY DESIGNATORS
MAX - Maximum display capture value
MIN - Minimum display capture value
Pressing the SEL button toggles the meter through the selected displays. If display scroll is enabled, the display will toggle automatically every four seconds between
the enabled display values.
“1” - To the right of the display indicates setpoint 1 output activated.
“2” - To the right of the display indicates setpoint 2 output activated.
Advances through the program menu
Increments selected parameter value or selection
5.0 proGraMMinGthe Meter
DISPLAY
MODE
SEL
OVERVIEW
PROGRAMMING MENU
NO
Secondary
Signal Input
Pro
Parameters
RST
SELSELSELSEL
1-INP
PROGRAMMING MODE ENTRY (SEL BUTTON)
It is recommended that all programming changes be made off line, or before
installation. The meter normally operates in the Display Mode. No parameters
can be programmed in this mode. The Programming Mode is entered by
pressing and holding the SEL button. If it is not accessible then it is locked by
either a security code, or a hardware lock.
MODULE ENTRY (SEL & RST BUTTONS)
The Programming Menu is organized into separate modules. These modules
group together parameters that are related in function. The display will alternate
between Pro and the present module. The RST button is used to select the desired
module. The displayed module is entered by pressing the SEL button.
MODULE MENU (SEL BUTTON)
Each module has a separate module menu (which is shown at the start of each
module discussion). The SEL button is pressed to advance to a particular
parameter to be changed, without changing the programming of preceding
parameters. After completing a module, the display will return to Pro NO.
Programming may continue by accessing additional modules.
SELECTION / VALUE ENTRY
For each parameter, the display alternates between the present parameter and
the selections/value for that parameter. The RST button is used to move through
the selections/values for that parameter. Pressing the SEL button, stores and
activates the displayed selection/value. This also advances the meter to the next
parameter.
For numeric values, press the RST button to access the value. The right hand
most digit will begin to flash. Pressing the RST button again increments the digit
by one or the user can hold the RST button and the digit will automatically
scroll. The SEL button will advance to the next digit. Pressing and holding the
SEL button will enter the value and move to the next parameter.
Function
Parameters
2-SEC
Display and Front
Panel Key
Parameters
3-dSP
Setpoint
Output
Parameters
4-SPt
Serial
Setup
Parameters
5-SEr
SEL
PROGRAMMING MODE EXIT (SEL BUTTON)
The Programming Mode is exited by pressing the SEL button with Pro NO
displayed. This will commit any stored parameter changes to memory and
return the meter to the Display Mode. (If power loss occurs before returning to
the Display Mode, verify recent parameter changes.)
PROGRAMMING TIPS
It is recommended to start with Module 1 and proceed through each module
in sequence. When programming is complete, it is recommended to record the
parameter programming and lock out parameter programming with the user
input or programming security code.
FACTORY SETTINGS
Factory Settings may be completely restored in Module 2. This is useful
when encountering programming problems.
Pressing both the SEL and the RST button on power-up will also load the
factory settings and display rESEt. This allows operation in the event of a
memory failure or corrupted data.
ALTERNATING SELECTION DISPLAY
In the explanation of the modules, the following dual display with arrows will
appear. This is used to illustrate the display alternating between the parameter
on top and the parameter’s Factory Setting on the bottom. In most cases,
selections and values for the parameter will be listed on the right.
Indicates Program Mode Alternating Display
Parameter
USrIN
Factory Settings are shown.
N0
Selection/Value
6
5.1 Module 1 - SiGnal input paraMeterS (1-INP)
1-INP
SEL
tYPE
Thermocouple
tYPE
Type
tc-J
CJC
Cold Junction
Compensation
THERMOCOUPLE TYPE
tc-t
tc-E
tc-j
tc-K
tc-r
Select the thermocouple type used for the application. The appropriate curve
will be automatically loaded for the selected type.
Selecting VOLt displays the millivolt input signal with 10 µV resolution.
COLD JUNCTION COMPENSATION
CJC
This parameter enables or disables internal cold junction compensation. For
most applications, cold junction compensation should be enabled (yES). This
parameter does not appear if tYPE = VOLt.
SCALE
Select the temperature scale. This selection applies for the Input, MAX and
MIN displays. This parameter does not appear if tYPE = VOLt.
dECPt
Select the decimal point location for the desired display resolution. This
selection applies for the Input, MAX and MIN displays. This parameter does
not appear if tYPE = VOLt or for types R, S or B thermocouples which have a
fixed 1 degree resolution.
OFSEt
The temperature display can be corrected with an offset value. This can be
used to compensate for probe errors, errors due to variances in probe placement
or adjusting the readout to a reference thermometer.
yES
°F
TEMPERATURE SCALE
DISPLAY DECIMAL POINT
0
DISPLAY OFFSET VALUE
-999 to 9999
0
SCALE
Temperature
Scale
T
E
J
K
R
NOyES
0.00
SELECTIONTC TYPETC TYPESELECTION
dECPtOFSEtFILtr
Decimal Point
tc-S
tc-b
tc-n
VOLt
°C°F
PARAMETER MENU
Display
S
B
N
Display Offset
Value
Pro
bANd
Filter Setting
Filter values represent no filtering (0), up to heavy filtering (3). A value of 1
for the filter uses 1/4 of the new input and 3/4 of the previous display to
generate the new display. A filter value of 2 uses 1/8 new and 7/8 previous. A
filter value of 3 uses 1/16 new and 15/16 previous.
bANd
The filter will adapt to variations in the input signal. When the variation
exceeds the input filter band value, the filter disengages. When the variation
becomes less than the band value, the filter engages again. This allows for a
stable readout, but permits the display to settle rapidly after a large process
change. The value of the band is in display units, independent of the Display
Decimal Point position. A band setting of ‘0’ keeps the filter permanently
engaged at the filter level selected above.
USrIN
NO
P-Loc
rESEt
d-HLd
d-SEL
d-LEV
COLOr
Print
P-r5t
rSt-1
rSt-2
rSt12
Filter Band
10
USER INPUT FUNCTION
NO
MODE
No Function
Program Mode Lock-out
Reset (Edge triggered)
Display Hold
Display Select
(Edge Triggered)
Display Intensity Level
(Edge Triggered)
Backlight Color
(Edge Triggered)
Print Request
Print and Reset
Setpoint 1 Reset
Setpoint 2 Reset
Setpoint 1 and 2 Reset
USrIN
User Input
Function
FILTER BAND
00 to 199display units
DESCRIPTIONDISPLAY
User Input disabled.
See Programming Mode Access chart
(Module 3).
Resets the assigned value(s) to the
current input value.
Holds the assigned display, but all other
meter functions continue as long as
activated (maintained action).
Advance once for each activation.
Increase intensity one level for each
activation (backlight version only).
Change backlight color with each
activation (backlight version only).
Serial transmit of the active parameters
selected in the Print Options menu
(Module 5).
Same as Print Request followed by a
momentary reset of the assigned value(s).
Resets setpoint 1 output.
Resets setpoint 2 output.
Reset both setpoint 1 and 2 outputs.
U-ASN
User Input
Assignment
FILTER SETTING
FILtr
If the displayed temperature is difficult to read due to small process
variations or noise, increased levels of filtering will help to stabilize the display.
Software filtering effectively combines a fraction of the current input reading
with a fraction of the previous displayed reading to generate the new display.
1
0,1 2 3
USER INPUT ASSIGNMENT
U-ASN
Select the value(s) to which the User Input Function is assigned. The User
Input Assignment only applies if a selection of reset, display hold, or print and
reset is selected in the User Input Function menu.
7
dSP
HI-LO
HI
LO
dSP
5.2 Module 2 - Secondary function paraMeterS (2-SEC)
2-SEC
SEL
HI-EnHI-t
Max Display
Enable
MAX DISPLAY ENABLE
HI-En
Enables the Maximum Display Capture capability.
HI-t
When the Input Display is above the present MAX value for the entered
delay time, the meter will capture that display value as the new MAX reading.
A delay time helps to avoid false captures of sudden short spikes.
LO-En
Enables the Minimum Display Capture capability.
LO-t
When the Input Display is below the present MIN value for the entered delay
time, the meter will capture that display value as the new MIN reading. A delay
time helps to avoid false captures of sudden short spikes.
FCS
Select YES to perform either of the Factory Service Operations shown below.
CodE
will also load the factory settings and display rESEt. This allows operation in
the event of a memory failure or corruted data.
NO
MAX CAPTURE DELAY TIME
0.0 to 999.9 seconds
2.0
MIN DISPLAY ENABLE
NO
MIN CAPTURE DELAY TIME
0.0 to 999.9 seconds
2.0
FACTORY SERVICE OPERATIONS
NO
RESTORE FACTORY DEFAULT SETTINGS
Entering Code 66 will overwrite all user settings with
the factory settings. The meter will display rESEt and then
return to CodE 00. Press SEL button to exit the module.
66
Pressing both the SEL and the RST button on power-up
Max Capture
Delay Time
YESNO
YESNO
yESNO
PARAMETER MENU
LO-EnLO-tFCS
Min Display
Enable
Pro
CodE
Min Capture
Delay TIme
CodE
slowly change. The result is that the stored calibration values may no longer
accurately define the input circuit. For most applications, recalibration every 1
to 2 years should be sufficient.
Calibration of the CUB5TC involves a voltage calibration and a cold
junction calibration. It is recommended that both calibrations be performed.
The voltage calibration MUST precede the cold junction calibration. Allow 30
minute warm up before performing any calibration related procedure. The
following procedures should be performed at an ambient temperature of 15 to
35 °C (59 to 95 °F).
Calibration should only be performed by individuals experienced in
calibrating electronic equipment.
CAUTION: The accuracy of the calibration equipment will directly affect the
accuracy of the CUB5TC.
Factory
Service
Operations
junction temperature values to provide accurate temperature
and voltage measurements. Over time, the electrical
48
characteristics of the components inside the meter could
Input Voltage Calibration
1. Connect a precision DC voltage source with an accuracy of 0.01% or better
to the TC+ (positive) and the TC- (negative) terminals of the CUB5TC. Set
the output of the voltage source to zero.
2. With the display at CodE 48, press and hold the SEL button for 2 seconds. Unit
will display CAL NO.
3. Press the RST button to select INP.
4. Press the SEL button. Display reads 0.0u.
5. With the voltage source set to zero, press SEL. Display reads CALC for about
7. When display reads CAL NO, press SEL twice to exit Module 2 and return to
the normal display mode.
8. Proceed to Cold Junction Calibration.
Cold Junction Calibration
1. Install all option cards needed for your application and the rear cover,
or invalid results will occur.
2. The ambient temperature must be within 20°C to 30°C.
3. Connect a thermocouple (types T, E, J, K, or N only) with an accuracy of 1°C
or better to the meter.
4. Enter programming mode and verify the following settings in Module 1:
tYPE = thermocouple type connected to the unit
CJC = YES; SCALE = °C; dECPt = 0.0; OFSEt = 0
5. Place the thermocouple in close thermal contact to a reference thermometer
probe. (Use a reference thermometer with an accuracy of 0.25°C or better.)
The two probes should be shielded from air movement and allowed sufficient
time to equalize in temperature. (A calibration bath of known temperature
could be used in place of the thermometer.)
6. Compare the unit display with the reference temperature indicator (or
calibration bath). If a difference of more than ±1.0 °C exists, note the
difference (CJ error) and continue with cold junction calibration.
CJ Error = Reference Temperature - Unit Display.
7. Enter programming mode. Step through Module 2 to the Service Access
Code parameter and select CodE 48. Press and hold the SEL button until the
unit displays CAL NO. Press the RST button to select CJC.
8. Press SEL. Display reads CJC followed by the current cold junction value.
Calculate a new cold junction value as follows:
New cold junction = Current cold junction + CJ Error (noted above)
9. Press RST and set the display to the new cold junction value. Press and hold
SEL. Display reads CALC for about four seconds and then returns to CAL NO.
10. Press SEL twice to exit calibration and return to the normal display mode.
Verify the input reading is correct. If not, repeat steps 6 through 10.
Access Code
For Service
Operations
CALIBRATION
The CUB5TC uses stored voltage calibration and cold
8
5.3 Module 3 - diSplayand front panel ButtonparaMeterS (3-dSP)
PARAMETER MENU
3-dSP
SEL
Backlight Unit Only
Pro
dSP-tSELrStScroLCOLOrCodE
Display
Update Time
dSP-t
This parameter sets the display update time in seconds.
SEL
The yES selection allows the SEL button to toggle through the enabled
displays.
rSt
This selection allows the RSTbutton to reset the selected value(s).
1
FRONT PANEL DISPLAY SELECT ENABLE (SEL)
yES
FRONT PANEL RESET ENABLE (RST)
dSP
Front Panel
Display
Select Enable
DISPLAY UPDATE TIME
10.52
Front Panel
Reset Enable
seconds
NOyES
LO
HI
HI-LO
Display
Scroll
Enable
dSPNO
Display
Color
DISPLAY INTENSITY LEVEL (BACKLIGHT UNIT ONLY)
d-LEV
Enter the desired Display Intensity Level (1-5). The display will actively dim
or brighten as levels are changed. This parameter is active for backlight units only.
CodE
The Security Code determines the programming mode and the accessibility
of programming parameters. This code can be used along with the Program
Mode Lock-out (P-Loc) in the User Input Function parameter (Module 1).
Two programming modes are available. Full Programming mode allows all
parameters to be viewed and modified. Quick Programming mode permits only
the Setpoint values to be modified, but allows direct access to these values
without having to enter Full Programming mode.
Programming a Security Code other than 0, requires this code to be entered
at the CodE prompt in order to access Full Programming mode. Depending on the
code value, Quick Programming may be accessible before the CodE prompt
appears (see chart).
5
PROGRAMMING SECURITY CODE
000
d-LEV
Display
Intensity
Level
1 to 5
000 to 999
Programming
Security Code
DISPLAY SCROLL ENABLE
ScroL
The yES selection allows the display to automatically scroll through the
enabled displays. The scroll rate is every 4 seconds.
COLOr
Enter the desired display color, red or green. This parameter is active for
backlight units only.
NO
DISPLAY COLOR (BACKLIGHT UNIT ONLY)
NOyES
rEd
6rnrEd
USER INPUT
FUNCTION
not P-Loc
* Entering Code 222 allows access regardless of security code.
9
P-Loc
USER INPUT
STAT E
______
Active
Not Active0-999Full Programming
SECURITY
CODE
100-999
100-999
MODE WHEN “SEL”
BUTTON IS PRESSED
0Full Programming
1-99Quick Programming
CodE prompt
0Programming Lock
1-99Quick Programming
CodE prompt
FULL PROGRAMMING
MODE ACCESS
Immediate Access
After Quick
Programming with
correct code entry at
CodE prompt *
With correct code entry
at CodE prompt *
No Access
No Access
With correct code entry
at CodE prompt *
Immediate Access
5.4 Module 4 - Setpoint output paraMeterS (4-SPt)
PARAMETER MENU
4-SPt
SEL
SPSEL
Setpoint
Select
Act-nSPt-nHYS-ntON-ntOF-nrSt-nrEn-nChC-n
Setpoint
Action
Setpoint
Value
Hysteresis
Value
On Time
Delay
Off Time
Delay
Output Reset
Action
Output Reset
With Display
Reset Enable
Stb-nbrn-n
Standby
Operation
Probe
Burn-out
Backlight
Unit Only
Change Display
Color with
Output State
Pro
The Setpoint Output Parameters are only active when an optional output
module is installed in the meter.
SETPOINT SELECT
SPSEL
Enter the setpoint (output) to be programmed. The n in the following
parameters will reflect the chosen setpoint number. After the chosen setpoint
is completely programmed, the display will return to SPSEL. Repeat steps for
each setpoint to be programmed. Select NO to exit the module. The number of
setpoints available is setpoint output card dependent.
NO
SP-2SP-1NO
SETPOINT 2 ENABLE
Enb-2
Select YES to enable Setpoint 2 and access the setup parameters. If NO is
selected, the unit returns to SPSEL and setpoint 2 is disabled.
NO
NOYES
SETPOINT ACTION
Act-n
Enter the action for the selected setpoint (output). See Setpoint Output
Figures for a visual detail of each action.
HI-Ub
HI-bL
LO-UbHI-UbLO-bL
SETPOINT VALUE
SPt-n
Enter the desired setpoint value. The decimal point position for the setpoint
and hysteresis values follow the selection set in Module 1.
100
-9999 to 99999
HYSTERESIS VALUE
HYS-n
Enter desired hysteresis value. See Setpoint Output Figures for visual
explanation of how setpoint output actions (balanced and unbalanced) are
affected by the hysteresis. When the setpoint is a control output, usually
balanced hysteresis is used. For alarm applications, usually unbalanced
hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on
the low side for high acting setpoints and functions on the high side for low
acting setpoints.
Note: Hysteresis eliminates output chatter at the switch point, while time delay
can be used to prevent false triggering during process transient events.
1 to 59999
2
ON TIME DELAY
tON-n
Enter the time value in seconds that the output is delayed from turning on
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
0.0
0.0 to 599.9 seconds
=
HI-bL
LO-bL
HI-Ub
LO-Ub
SP + ½Hys
SP
SP - ½Hys
STATE
STATE
OFF
SP
OFF
OUTPUT
High Acting (Balanced Hys) = HI-bL
SP - Hys
OUTPUT
High Acting (Unbalanced Hys) = HI-Ub
High Acting, with balanced hysteresis
=
Low Acting, with balanced hysteresis
=
High Acting, with unbalanced hysteresis
=
Low Acting, with unbalanced hysteresis
OFF
ON
TRIGGER POINTS
OFF
ON
TRIGGER POINTS
SP + ½Hys
SP
Hys
SP - ½Hys
OFF
OUTPUT
STATE
Low Acting (Balanced Hys) = LO-bL
SP + Hys
Hys
SP
STATE
OFF
OUTPUT
Low Acting (Unbalanced Hys) = LO-Ub
ON
TRIGGER POINTS
ON
TRIGGER POINTS
OFF
OFF TIME DELAY
tOF-n
Enter the time value in seconds that the output is delayed from turning off
after the trigger point is reached. A value of 0.0 allows the meter to update the
output status per the response time listed in the Specifications.
Hys
OFF
rSt-n
0.0
Auto
0.0 to 599.9 seconds
OUTPUT RESET ACTION
LAtCHAutoL-dLY
Enter the reset action of the output. See figure for details.
Auto = Automatic action; This action allows the output to automatically reset off
at the trigger points per the Setpoint Action shown in Setpoint Output
Hys
Figures. The “on” output may be manually reset (off) immediately by the
front panel RST button or user input.The output remains off until the trigger
point is crossed again.
LAtCH = Latch with immediate reset action; This action latches the output on at
the trigger point per the Setpoint Action shown in Setpoint Output Figures.
Latch means that the output can only be turned off by the front panel RST
button or user input manual reset, serial reset command or meter power cycle.
10
When the user input or RST button is activated (momentary action), the
corresponding “on” output is reset immediately and remains off until the
trigger point is crossed again. (Previously latched alarms will be off if power
up Display Value is lower than setpoint value.)
L-dLY = Latch with delay reset action; This action latches the output on at the
trigger point per the Setpoint Action shown in Setpoint Output Figures. Latch
means that the output can only be turned off by the front panel RST button
or user input manual reset, serial reset command or meter power cycle. When
the user input or RST button is activated (momentary action), the meter
delays the event until the corresponding “on” output crosses the trigger off
point. (Previously latched outputs are off if power up Display Value is lower
than setpoint value. During a power cycle, the meter erases a previous L-dLY
reset if it is not activated at power up.)
MANUAL
RESET
SP - Hys
OUTPUT
STATE
SP
OFF
OFF
{
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
( )
Auto
( )
LAtCH
( )
L-dLY
Hys
STANDBY OPERATION
Stb-n
When YES, the output is disabled (after a power up) until the trigger point is
crossed. Once the output is on, the output operates normally per the Setpoint
Action and OutputReset Action.
brn-n
Enter the probe burn-out action. In the event of a temperature probe failure
(open), the output can be programmed to be on or off.
YESNO
NO
PROBE BURN-OUT ACTION
OFF
CHANGE DISPLAY COLOR w/OUTPUT STATE
ONOFF
Setpoint Output Reset Actions
OUTPUT RESET WITH DISPLAY RESET
rEn-n
This parameter enables the RST button or user input to reset the output when
the display is reset.
Note: For this parameter to operate, the RST button or User Input being used
must be set to dSP and the Input value must be displayed. If these conditions are
not met, the output will not reset.
YES
YESNO
ChC-n
This parameter enables the backlight CUB5 to switch the backlight color when
the output state changes. This parameter is only active for the backlight version.
NO
5.5 Module 5 - Serial Setup paraMeterS (5-SEr)
5-SEr
SEL
bAUddAtA
Data BitBaud RateParity BitPrint
The Serial Setup Parameters are only active when one of the optional serial communications/programming cards is installed in the meter.
Refer to the CUB5COM bulletin for details and setup for the CUB5 RS232 or RS485 serial communications.
Refer to the CUB5USB bulletin for details on the CUB5 USB programming and programming requirements.
PARAMETER MENU
PArAddrAbbr
Meter
Address
Abbreviated
Printing
OPt
Options
YESNO
Pro
The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years
from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The
Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The
Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses
arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal
injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to
any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability
imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein.
The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations.
LIMITED WARRANTY
11
cuB5tc proGraMMinG QuicK overvieW
User Input
U-ASN
User Input
USrIN
Filter Band
bANd
Assignment
Function
CodE
Access Code
Backlight
Unit Only
CodE
Programming
Security Code
Level
Display
Operations
For Service
d-LEV
Intensity
Change Display
Probe
Standby
Stb-nbrn-n
Output Reset
Output Reset
Off Time
Color with
Output State
Action
Burn-out
Operation
Reset
With Display
Action
Delay
OPt
Print
Options
Press and hold SEL button
to enter Programming Mode.
SEL
End
Exit
Programming
SEL
Filter SettingDisplay Offset
OFSEtFILtr
Display
dECPt
SCALE
Temperature
CJC
Cold Junction
tYPE
Thermocouple
Value
Decimal Point
Scale
Compensation
Type
SEL
Factory
FCS
Min Capture
LO-t
Min Display
LO-En
Max Capture
Max Display
HI-EnHI-t2-SEC
Service
Operations
Delay TIme
Enable
Delay Time
Enable
Backlight Unit Only
SEL
COLOr
ScroL
dSP-tSELrSt
Display
Display
Front Panel
Front Panel
Display
Color
Scroll
Enable
Reset Enable
Display
Select Enable
Update Time
SEL
Act-nSPt-nHYS-ntON-ntOF-nrSt-nrEn-nChC-n
SPSEL
Delay
On Time
Value
Hysteresis
Value
Setpoint
Action
Setpoint
Select
Setpoint
SEL
Abbr
Addr
PAr
dAtA
bAUd
Printing
Abbreviated
Meter
Address
Parity BitBaud Rate
Data Bit
Pro
NO
RST
1-INP
RST
RST
3-dSP
RST
4-SPt
RST
5-SEr
RST
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.