MODEL CUB4 I - MINIATURE D.C. CURRENT METER &
MODEL CUB4V - MINIATURE D.C. VOLTMETER
LCD, POSITIVE REFLECTIVE OR NEGATIVE TRANSMISSIVE
WITH YELLOW/GREEN OR RED BACKLIGHTING
FOUR SELECTABLE D.C. RANGES
0 to 199.9 mV, 1.999 V, 19.99 V, 199.9 V (CUB4V)
0 to 199.9 µA, 1.999 mA, 19.99 mA, 199.9 mA (CUB4I)
0.6 INCH (15.2 mm) HIGH LCD DIGITS
BUILT-IN SCALING PROVIDED
AUTO ZEROING CIRCUIT
SELECTABLE DECIMAL POINTS
WIRE CONNECTIONS MADE VIA SCREW CLAMP TYPE
TERMINALS
FITS DIN STANDARD CUT-OUT 2.68" (68 mm) x 1.30" (33 mm)
UL Recognized Component,
File # E179259
NEMA 4X/IP65 SEALED FRONT PANEL BEZEL
9 TO 28 VDC POWERED
DESCRIPTION
The CUB4 Volt and Current Meters are designed and manufactured using the
latest technology for a high quality, compact, affordable instrument for use in
industrial environments. Each unit has a 3½-digit LCD display with 0.6 inch
(15.2 mm) high digits and a DIP switch selectable decimal point. The displays
are available in positive image reflective (black digits, reflective background) or
negative image transmissive (illuminated digits, dark background) with red or
yellow/green backlighting.
The units are constructed of a lightweight, high impact plastic case with a
clear viewing window. The sealed front panel meets NEMA 4X/IP65
specifications for wash-down and/or dusty environments, when properly
installed. A CUB4V or CUB4I unit can be mounted in the same panel cutout as
the CUBVD and CUBID units.
The optional Micro Line/Sensor Power Supply (MLPS1000) is designed to
attach to the rear of an installed CUB4V or CUB4I to provide the necessary power
for the unit. The optional supply can be powered from a 85-250 VAC source.
ORDERING INFORMATION
MODEL NO. DESCRIPTION PART NUMBERS
DC Voltmeter CUB4V000
CUB4V
CUB4I
MLPS Micro Line/Sensor Power Supply MLPS1000
DC Voltmeter W/Yel-Grn Backlighting CUB4V010
DC Voltmeter W/Red Backlighting CUB4V020
DC Current Meter CUB4I000
DC Current Meter W/Yel-Grn Backlighting CUB4I010
DC Current Meter W/Red Backlighting CUB4I020
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
CAUTION: Read complete
instructions prior to installation
and operation of the unit.
CAUTION: Risk of electric shock.
SPECIFICATIONS
1. DISPLAY: 3½-digit (-1999 to 1999), 0.6" (15.2 mm) high digits. Minus (-)
sign is displayed when voltage or current is negative.
2. DECIMAL POINTS: DIP switch selectable decimal points allow the display
to be read in tenths, hundredths or thousandths.
3. POWER REQUIREMENTS:
Reflective Versions: 9 to 28 VDC at 4 mA max.
Backlight Versions: 9 to 28 VDC @ 35 mA typ., 50 mA max. Above 26
VDC, derate operating temperature to 50°C.
4. INPUT RANGES:
D.C. VOLTAGE D.C. CURRENT
(DIP Switch Selectable) (JMPR. Selectable)
±199.9 mVDC ±199.9 µADC
±1.999 VDC ±1.999 mADC
±19.99 VDC ±19.99 mADC
±199.9 VDC ±199.9 mADC
DIMENSIONS In inches (mm)
2.95 (74.9)
Note: Recommended minimum clearance (behind the panel) for mounting clip
installation is 2.15" (54.6) H x 3.00" (76.2) W.
.13 (3.3)
1.54 (39.1)
1.29 (32.8)
1.96 (49.8).15 (3.8)
1
PANEL CUT-OUT
+.025
2.68
-.000
+.8
(68 )
-.0
1.30
+.6
(33 )
-.0
+.024
-.000
5. ACCURACY: (@ 23°C, less than 85% RH)
D.C. Voltage: ±(0.1% + 1 digit)
D.C. Current:
199.9 µA, 1.999 mA, 19.99 mA ranges: ±(0.1% + 1 digit)
199.9 mA range: ±(0.15% + 1 digit)
6. OVERRANGE RATINGS, PROTECTION & INDICATION:
9 to 28 VDC power circuit is not isolated from the signal circuit.
Max Input Voltage:
0 to 199.9 mVDC Range: 75 VDC
All other voltage Ranges: 300 VDC
Max Input Current:
199.9 µA through 19.99 mA: 10 times max. range current
199.9 mA: 1 amp
Overrange Indication: Overrange is indicated by a “1” displayed in the
most significant digit and the blanking of the three least significant digits.
7. READING RATE: 2.5 readings per second
8. RESPONSE TIME: 1.5 seconds to settle for a step change
9. NORMAL MODE REJECTION: 60 dB 50/60 Hz
10. INPUT IMPEDANCE:
Voltmeter: 1 MΩ
Current Meter:
199.9 µA - 1 KΩ 19.99 mA - 10 Ω
1.999 mA - 100 Ω 199.9 mA - 1 Ω
11. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class B
IEC/EN 61010-1
RoHS Compliant
UL Recognized Component: File #E179259
Type 4X Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)
Refer to EMC Installation Guidelines section of the bulletin for additional
information.
12. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0° to 60°C (above 50°C, derate backlight
operating voltage to 26 VDC maximum).
Storage Temperature: -40° to 80°C
Operating and Storage Humidity: 85% max relative humidity (non-
condensing) from 0 to 60°C.
Vibration to IEC 68-2-6: Operational 5-500 Hz, 5 g
Shock to IEC 68-2-27: Operational 30 g
Temperature Coefficient: 100 PPM/°C
Altitude: Up to 2000 meters.
13. CONSTRUCTION: High impact plastic case with clear viewing window.
(Panel gasket and mounting clip included.) This unit is rated for NEMA 4X/
IP65 indoor use. Installation Category II, Pollution Degree 2
14. WEIGHT: 3.3 oz. (93.5 g)
INSTALLATION ENVIRONMENT
The unit should be installed in a location that does not exceed the
maximum operating temperature and provides good air circulation.
Placing the unit near devices that generate excessive heat should be
avoided. The bezel should be cleaned only with a soft cloth and neutral
soap product. Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate the aging
process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to
operate the keypad of the unit.
Installation
The CUB4 Volt and Current meters meet NEMA 4X/IP65
requirements for indoor use, when properly installed. The
units are intended to be mounted into an enclosed panel. A
sponge rubber gasket, mounting clip, two screws, and nut
fasteners are provided to install and seal the unit in the panel cutout.
The following procedure assures proper installation:
1. Cut panel opening to specified dimensions. Remove burrs and clean panel
opening.
2. Carefully remove center section of the panel gasket and discard. Slide
gasket over rear of the unit to the back of the bezel.
3. Slide nut fastener into slot on mounting clip and then insert mounting screw
through nut on both sides of mounting clip. Tip of mounting screw should
NOT project through hole on clip.
4. Install CUB4 unit through panel cutout.
5. Slide mounting clip over rear of unit until clip is against back of panel. The
mounting clip and CUB4 housing have a latching feature to hold the unit
in place until tightened.
Note: Hold the CUB4 front bezel in place when sliding the mounting clip into
position.
6. Alternately tighten each mounting screw to ensure uniform gasket pressure.
LATCHING
FEATURE
MOUNTING SCREW
NUT FASTENER
MOUNTING CLIP
GASKET
0.093" (2.4 mm)
THICK
LATCHING
FEATURE
BEZEL
EXISTING PANEL
.05" to .20"
(1.3 to 5.1mm)
THICK
Visually inspect the gasket for proper seal. The gasket should be
compressed approximately 75 to 80% of its original thickness.
(Recommended torque is 28 to 36 in-oz.)
7. If the gasket is not adequately compressed and the mounting screws cannot
be tightened any further, loosen mounting screws and insure that the clip is
latched as close as possible to the panel.
8. Repeat step #6 for tightening the mounting screws.
WIRING CONNECTIONS
The electrical connections are made via screw-clamp terminals located on the
back of the unit. When wiring the unit, use the label to identify the wire position
with the proper function. All conductors should meet voltage and current ratings
for each terminal. Also cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that power supplied
to the unit be protected by a fuse or circuit breaker. Strip the wire, leaving
approximately ¼" bare wire exposed (stranded wires should be tinned with
solder). Insert the wire into the screw-clamp terminal and tighten the screw until
the wire is clamped tightly. Each terminal can accept up to two #14 AWG wires.
DECIMAL POINT SELECTION
The CUB4 Volt and Current Meters can be set-up to read in 10ths, 100ths, or
1000ths. The decimal point position is DIP switch selectable for one of three
locations. If all the DIP switches are set to the “OFF” position, then NO
decimal point will appear in the display. The DIP switches are located at the rear
of the unit.