Red Lion CUB4CL Data Sheet

1
z DUAL RANGE, 4 to 20 mA OR 10 to 50 mA
z 3½-DIGIT, 0.6" (15.2 mm) HIGH DIGITS
z POSITIVE IMAGE TRANSFLECTIVE LCD WITH RED BACKLIGHT
OR POSITIVE IMAGE REFLECTIVE LCD (CUB4LP)
z POSITIVE IMAGE TRANSFLECTIVE LCD WITH RED BACKLIGHT
OR NEGATIVE IMAGE TRANSMISSIVE WITH RED OR YELLOW/GREEN BACKLIGHT (CUB4CL)
z SPAN AND OFFSET CAPABILITY
z SELECTABLE DECIMAL POINT POSITION
z NEMA 4X/IP65 SEALED FRONT PANEL BEZEL
z FITS DIN STANDARD CUT-OUT 2.68" (68 mm) X 1.30" (33 mm)
DESCRIPTION
The CUB4LP and CUB4CL are additions to the CUB4 product line. The CUB4LP uses a 4 to 20 mA or a 10 to 50 mA input signal as operating power. The input signal is also used to power the backlighting on the CUB4LP40 unit. The CUB4CL uses a 4 to 20 mA or a 10 to 50 mAinput signal to power the unit. An external power supply is used to power the CUB4CL backlighting to provide a brighter, more consistent display and a lower compliance voltage.
The units have a 3½-digit LCD display with 0.6" (15.2 mm) high digits and a DIP switch selectable decimal point. The CUB4LP display is available in positive image reflective (dark digits, reflective background) or positive image transflective (dark digits, illuminated background) with red backlighting. The CUB4CL display is available in positive image transflective (dark digits, illuminated background) with red or yellow/green backlighting or negative image transmissive (illuminated digits, dark background) with red or yellow/green backlighting.
The ability to scale the display allows indication in any desired unit of measurement such as temperature, pressure, humidity, fluid flow, etc. The unit is calibrated at the factory with 0.0 displayed @ 4 mA input and 100.0 displayed @ 20 mA input.
The units are contained in a lightweight, high impact plastic case with a clear viewing window. When properly installed, the sealed front panel meets NEMA 4X/IP65 specifications for wash-down and dusty environments.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the manual or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it. If equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2 / CLASS II, DIVISION 2 / CLASS III, DIVISION 2
SPECIFICATIONS
1. DISPLAY: 3½-digit (-1999 to 1999), 0.6" (15.2 mm) high digits.
The CUB4LP is available with a positive image reflective LCD or a red
backlit positive image transflective LCD. The intensity of the backlighting
will vary with the input signal.
The CUB4CL is available with a positive image transflective LCD with red
or yellow/green backlighting or a negative image transmissive with red or
yellow/green backlight.
A minus sign is displayed when the indicator is adjusted for a negative offset.
Overrange: Overrange is indicated by a “1” in the most significant digit and
the blanking of the three least significant digits.
2. EXTERNAL BACKLIGHT POWER: (CUB4CL only)
9 - 28 VDC, @ 35 mA typ., 50 mA max. Power Supplies must be Class 2
(NEC) or SELV rated. Above 26 VDC, derate the operating temperature to
50°C.
3. DECIMAL POINTS: Three DIP switch selectable, decimal point positions
allow the display to be read in tenths, hundredths or thousandths.
MODEL CUB4LP - LOOP POWERED PROCESS INDICATOR MODEL CUB4CL - CURRENT LOOP INDICATOR
DIMENSIONS In inches (mm)
Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 2.15" (54.6) H x 3.00" (76.2) W.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
Bulletin No. CUB4LP-L
Drawing No. LP0318
Released 4/08
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
FOR USE IN HAZARDOUS LOCATIONS:
Class I, Division 2, Groups A, B, C, and D Class II, Division 2, Groups F and G Class III, Division 2
2
INSTALLATION
When properly installed, the CUB4LP/CL meets NEMA 4X/IP65 requirements for indoor use. The units are intended to be mounted into an enclosed panel. A sponge rubber gasket, mounting clip, two screws, and nut fasteners are provided to install and seal the unit in the panel cutout.
Installation Environment
The unit should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided.
The bezel should be cleaned only with a soft cloth and neutral soap product. Do NOT use solvents.
Continuous exposure to direct sunlight may accelerate the aging process of the bezel.
The following procedure assures proper installation:
1. Cut the panel opening to the specified dimensions. Remove
burrs and clean the panel opening.
2. Slide nut fastener into slot on mounting clip and then insert
mounting screw through nut on both sides of mounting clip. The
tip of mounting screw should not project through hole on clip.
3. Slide the panel gasket over the rear of the unit to the back of the bezel.
Install CUB4LP/CL unit through panel cutout.
4. Slide mounting clip over rear of unit until the clip is against back of panel.
The mounting clip and CUB4LP/CL housing have a latching feature to hold
the unit in place until tightened.
Note: Hold the CUB4LP/CL front bezel in place when sliding the mounting
clip into position.
5. Alternately tighten each mounting screw to ensure uniform gasket pressure.
Visually inspect the gasket for proper seal. The gasket should be compressed
to approximately 75 to 80% of its original thickness. (Recommended torque is 28 to 36 in-oz.)
6. If the gasket is not adequately compressed and the mounting screws cannot be tightened any further, loosen the mounting screws and insure that the clip is latched as closely as possible to the panel.
7. Repeat Step #6 for tightening the mounting screws.
SPECIFICATIONS (Cont’d)
4. MAXIMUM VOLTAGE DROP:
3.2 VDC for CUB4LP00
4.0 VDC for CUB4LP40
3.2 VDC for CUB4CL all models
5. EQUIVALENT RESISTANCE: CUB4LP00: 800 Ω max. @ 4 mA; 160 max. @ 20 mA
320 max. @ 10 mA; 65 max. @ 50 mA
CUB4LP40: 1000
max. @ 4 mA; 200 max. @ 20 mA
400 max. @ 10 mA; 80 max. @ 50 mA
CUB4CL (all models): 800
max. @ 4 mA; 160 max. @ 20 mA
320
max. @ 10 mA; 65 max. @ 50 mA
6. MAXIMUM ALLOWABLE INPUT CURRENT: 100 mA
7. SCALING RANGE: Span: Two potentiometers provide a coarse and fine span adjustment. Span
range = 0 to 2000.
Offset: Two potentiometers provide a coarse and fine zero offset adjustment.
Offset range = -1999 to 1999.
8. LINEARITY: (@ 23°C, Less than 85% RH) ±(0.1% + 1 digit).
9. READING RATE: 2.5 per second, nominal.
10. RESPONSE TIME: 1.5 seconds to settle for a step change.
11. NORMAL MODE REJECTION: 60 dB 50/60 Hz
12. TEMPERATURE EFFECTS:
Span Temperature Coefficient: 100 PPM/°C Offset Temperature Coefficient: 0.2 digits/°C
13. CONSTRUCTION: High impact plastic case with clear viewing window. (Panel gasket and mounting clips included.) This unit is rated for NEMA 4X/IP65 indoor use. Installation Category I, Pollution Degree 2
14. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Listed, File #E184589, UL1604, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Indoor Enclosure rating (Face only), UL50
IEC 61010-1, EN 61010-1: Safety requirements for electrical
equipment for measurement, control and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. Self-recoverable loss of performance during EMI disturbance at 10 V/m: Process Signal may deviate during EMI disturbance.
For operation without loss of performance:
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent) connected to earth ground.
2. Self-recoverable loss of performance during EMI disturbance at 10 Vrms. Process signal may deviate during EMI disturbance.
For operation without loss of performance:
Install 1 ferrite core, RLC #FCOR0000 or equivalent, to signal cable at the unit.
Refer to the EMC Installation Guidelines of this bulletin for additional
information.
15. ENVIRONMENTAL CONDITIONS: Operating Temperature: 0° to 60°C
(Derate backlight voltage to 26 VDC above 50°C.)
Storage Temperature: -40° to 80°C Operating and Storage Humidity: 85% max. (non-condensing) from 0°C to
60°C.
Vibration According to IEC 68-2-6: Operational 5 to 500 Hz, in X, Y, Z
direction for 1.5 hours, 5g’s.
Shock According to IEC 68-2-27: Operational 30 g, 11 msec in 3 directions. Altitude: Up to 2000 meters
16. WEIGHT: 3.3 oz. (93.5 g)
Power mains class B
Enclosure class BEN 55011RF interference
Emissions to EN 50081-1
Level 4; 30 A/mEN 61000-4-8Power frequency magnetic fields
150 KHz - 80 MHz
Level 3; 10 V/rms
2
EN 61000-4-6RF conducted interference
Level 3; 2 Kv power
Level 4; 2 Kv I/OEN 61000-4-4Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/m
1
EN 61000-4-3Electromagnetic RF fields
Level 3; 8 Kv air
Level 2; 4 Kv contactEN 61000-4-2Electrostatic discharge
Immunity to EN 50082-2
Loading...