2
INSTALLATION
When properly installed, the CUB4LP/CL meets
NEMA 4X/IP65 requirements for indoor use. The
units are intended to be mounted into an enclosed
panel. A sponge rubber gasket, mounting clip, two
screws, and nut fasteners are provided to install and
seal the unit in the panel cutout.
Installation Environment
The unit should be installed in a location that
does not exceed the maximum operating
temperature and provides good air circulation.
Placing the unit near devices that generate excessive
heat should be avoided.
The bezel should be cleaned only with a soft
cloth and neutral soap product. Do NOT use
solvents.
Continuous exposure to direct sunlight may
accelerate the aging process of the bezel.
The following procedure assures proper installation:
1. Cut the panel opening to the specified dimensions. Remove
burrs and clean the panel opening.
2. Slide nut fastener into slot on mounting clip and then insert
mounting screw through nut on both sides of mounting clip. The
tip of mounting screw should not project through hole on clip.
3. Slide the panel gasket over the rear of the unit to the back of the bezel.
Install CUB4LP/CL unit through panel cutout.
4. Slide mounting clip over rear of unit until the clip is against back of panel.
The mounting clip and CUB4LP/CL housing have a latching feature to hold
the unit in place until tightened.
Note: Hold the CUB4LP/CL front bezel in place when sliding the mounting
clip into position.
5. Alternately tighten each mounting screw to ensure uniform gasket pressure.
Visually inspect the gasket for proper seal. The gasket should be compressed
to approximately 75 to 80% of its original thickness.
(Recommended torque is 28 to 36 in-oz.)
6. If the gasket is not adequately compressed and the mounting screws cannot be
tightened any further, loosen the mounting screws and insure that the clip is
latched as closely as possible to the panel.
7. Repeat Step #6 for tightening the mounting screws.
SPECIFICATIONS (Cont’d)
4. MAXIMUM VOLTAGE DROP:
3.2 VDC for CUB4LP00
4.0 VDC for CUB4LP40
3.2 VDC for CUB4CL all models
5. EQUIVALENT RESISTANCE:
CUB4LP00: 800 Ω max. @ 4 mA; 160 Ω max. @ 20 mA
320 Ω max. @ 10 mA; 65 Ω max. @ 50 mA
CUB4LP40: 1000
Ω max. @ 4 mA; 200 Ω max. @ 20 mA
400 Ω max. @ 10 mA; 80 Ω max. @ 50 mA
CUB4CL (all models): 800
Ω max. @ 4 mA; 160 Ω max. @ 20 mA
320
Ω max. @ 10 mA; 65 Ω max. @ 50 mA
6. MAXIMUM ALLOWABLE INPUT CURRENT: 100 mA
7. SCALING RANGE:
Span: Two potentiometers provide a coarse and fine span adjustment. Span
range = 0 to 2000.
Offset: Two potentiometers provide a coarse and fine zero offset adjustment.
Offset range = -1999 to 1999.
8. LINEARITY: (@ 23°C, Less than 85% RH) ±(0.1% + 1 digit).
9. READING RATE: 2.5 per second, nominal.
10. RESPONSE TIME: 1.5 seconds to settle for a step change.
11. NORMAL MODE REJECTION: 60 dB 50/60 Hz
12. TEMPERATURE EFFECTS:
Span Temperature Coefficient: 100 PPM/°C
Offset Temperature Coefficient: 0.2 digits/°C
13. CONSTRUCTION: High impact plastic case with clear viewing window.
(Panel gasket and mounting clips included.) This unit is rated for NEMA
4X/IP65 indoor use. Installation Category I, Pollution Degree 2
14. CERTIFICATIONS AND COMPLIANCES:
SAFETY
UL Listed, File #E184589, UL1604, CSA 22.2 No. 213-M1987
LISTED by Und. Lab. Inc. to U.S. and Canadian safety standards
Type 4X Indoor Enclosure rating (Face only), UL50
IEC 61010-1, EN 61010-1: Safety requirements for electrical
equipment for measurement, control and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
Process Signal may deviate during EMI disturbance.
For operation without loss of performance:
Unit is mounted in a metal enclosure (Buckeye SM7013-0 or equivalent)
connected to earth ground.
2. Self-recoverable loss of performance during EMI disturbance at 10 Vrms.
Process signal may deviate during EMI disturbance.
For operation without loss of performance:
Install 1 ferrite core, RLC #FCOR0000 or equivalent, to signal cable at
the unit.
Refer to the EMC Installation Guidelines of this bulletin for additional
information.
15. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0° to 60°C
(Derate backlight voltage to 26 VDC above 50°C.)
Storage Temperature: -40° to 80°C
Operating and Storage Humidity: 85% max. (non-condensing) from 0°C to
60°C.
Vibration According to IEC 68-2-6: Operational 5 to 500 Hz, in X, Y, Z
direction for 1.5 hours, 5g’s.
Shock According to IEC 68-2-27: Operational 30 g, 11 msec in 3 directions.
Altitude: Up to 2000 meters
16. WEIGHT: 3.3 oz. (93.5 g)
Power mains class B
Enclosure class BEN 55011RF interference
Emissions to EN 50081-1
Level 4; 30 A/mEN 61000-4-8Power frequency magnetic fields
150 KHz - 80 MHz
Level 3; 10 V/rms
2
EN 61000-4-6RF conducted interference
Level 3; 2 Kv power
Level 4; 2 Kv I/OEN 61000-4-4Fast transients (burst)
80 MHz - 1 GHz
Level 3; 10 V/m
1
EN 61000-4-3Electromagnetic RF fields
Level 3; 8 Kv air
Level 2; 4 Kv contactEN 61000-4-2Electrostatic discharge
Immunity to EN 50082-2