This appliance must be installed and commissioned by an experienced oil heating engineer.
PR0655 Issue 2 (November 2006)
TECHNICAL SPECIFICATION
TECHNICAL DATA:
Burner SpecificationDon 8" Natural Draught
Vaporising Type
ppliance Type/FuelOil Fired Kerosene to BS2869
A
1988 Class 2
Country of OriginUnited Kingdom
Oil Flow RatesLow – 4ml/min.
High – 10ml/min.
Flue DraughtMin. 0.02" wg (0.5mm wg)
Max. 0.04" wg (1.0mm wg)
Heat InputLow – 2.55kw (8.721 Btu/hr)
High – 6.37kw (21.734 Btu/hr)
Size of hot plates:346mm diameter
Size of main oven:507mm depth x 384mm width
x 310mm height
Size of warming oven507mm depth x 384mm width
x 249mm height
Gross weightApprox. 397kg
Electrical Supply230V 50Hz supplying
transformer 12VAC 1.5A
1
724mm
583mm
643mm
32
940mm
1007mm
17
2
INSTALLATION INSTRUCTIONS
WARNING
CONTROL OF SUBSTANCES HARMFUL TO HEALTH
It is the responsibility of the user and installer to ensure that protective clothing is worn when materials known to be injurious to
ealth and safety are being handled.
h
Avoid inhalation when working with insulation materials such as ceramic board, glass fibre or mineral wool.
•
se disposable protection for the eyes, skin and throat.
U
•
Use disposable gloves when handling fuels, fire cement and firebricks.
•
ALWAYS ENSURE THAT WORKING AREAS ARE WELL VENTILATED DURING INSTALLATION AND COMMISSIONING.
1. IMPORTANT INFORMATION
To ensure optimum performance from this range cooker, it
must be installed and commissioned by a REDFYRE/OFTEC
approved engineer.
Installation must be carried out to accepted standards, and
comply with all regional and national regulations. Redfyre
Cookers will accept no responsibility or liability for any faults
arising from poor or incorrect installation.
Any alteration not approved by Redfyre Cookers could
invalidate the approval of the appliance and the operation of
its warranty, as well as adversely affecting the purchaser’s
statutory rights.
It is recommended that a qualified OFTEC engineer should
carry out servicing once, or preferably twice, a year.
It is a requirement under OFTEC regulations that the
installation is recorded on a CD 10 form (a copy is attached at
the end of this book). Once completed, a copy is to be given to
the end user and one copy sent to Gazco Ltd. Failure to do so
may invalidate the guarantee.
The appliance is delivered fully assembled, with the exception of
the following items packed in a box in the Simmering Oven.
Set of Burner Shells
•
Burner Lid – 2 parts
•
Burner Ring
•
Vapour Chamber Lid
•
Flue Collar & Filler Plate
•
KBB Fire Valve
•
Set of Wicks
•
The location for the appliance must fit in with the layout and style
of the kitchen, and have:
access to services (oil and electricity);
enough space for the appliance, allowing access for
installation and maintenance;
3. DELIVERY
Astonish Cleaner
•
Shelves (3)
•
Cold Shelf
•
Roasting Dish (Lge)
•
Roasting Dish (Smll)
•
Cookbook
•
Instructions
•
4. LOCATION
EVIDENCE OF FAULTCAUSE
Burner soots up1. Too little primary air.
2. Too low a flue pull.
3. Downdraught in flue. Fit suitable anti-downdraught cowl.
4. Vapourising Chamber lid not fully seated.
5. Shells not correctly seated.
6. Incorrect or contaminated fuel. Very little can cause
trouble. Clean out tank and refill with a new fuel.
COOKERS
Not reaching required temperature1. Too little primary air.
2. To high a flue pull.
3. Flue partly or fully blocked.
4. High fire screw set too low.
Overheating1. Too low a flue pull.
2. Low fire screw set too high.
Variations in temperature1. Variations in flue draught. Fit suitable stabiliser.
2. COMPLIANCE
Installation must comply with these regulations:
The Building Regulations: Part J England and Wales; Part F,
Section III Scotland; Part L Northern Ireland; Part J Eire.
BS5440 Parts 1 & 2 installation of Flues and Ventilation.
BS5410 Part 1.
D.M.2. Installation in Timber Frame Buildings.
All OFTEC Codes of Practice.
Where a Standard or a Code of Practice is quoted, the current
version must be used.
a satisfactory flue;
a solid non-combustible hearth capable of supporting the
weight of the appliance.
You need to allow at least a 3 mm gap between the
kitchen surfaces, cupboards or walls for expansion and
services.
4
3
16
EVIDENCE OF FAULTCAUSE
Black stain around any door1. Too little primary air.
. Too low a flue pull.
2
3. Downdraught in flue. Fit suitable anti-downdraught cowl.
4. Flue partly or fully blocked.
. High fire screw set too high.
5
Burner carbons up after short period1. Low fire screw set too low.
2. Oil Control filter blocked. Remove and clean with boiling
water and dry thoroughly before replacing.
. Incorrect or contaminated fuel. Very little can cause
3
trouble. Clean out tank and refill with a new fuel.
Unable to light burner1. Control metering stem slot obstructed. To clear, turn
Control Knob from OFF to full ON several times.
2. Oil Control filter blocked. Remove and clean with boiling
water and dry thoroughly before replacing.
3. Metering stem in oil control sticking. Replace control.
4. Fuel inlet blocked. Service.
5. Oil depth in burner base too shallow.
6. Oil level in tank too low.
7. Air lock in oil line tank – burner – control.
8. Incorrect or contaminated fuel. Very little can cause
trouble. Clean out tank and refill with a new fuel.
9. Electrical supply failed or turned off. Check power supply. If there is
a power cut, switch control to manual. See User’s Instructions.
Burner goes out after burning 1-2 hours1. Too little primary air.
2. Downdraught in flue. Fit suitable anti-downdraught cowl.
3. Low fire screw set too low.
4. Control metering stem slot obstructed. To clear, turn Control
Knob from OFF to full ON several times.
5. Fuel inlet blocked. Service.
6. Oil depth in burner base too shallow.
7. Oil level in tank too low.
8. Air lock in oil line tank – burner – control.
9. Incorrect or contaminated fuel. Very little can cause
trouble. Clean out tank and refill with a new fuel.
Burner goes out for no apparent reason1. Too little primary air.
2. Downdraught in flue. Fit suitable anti-downdraught cowl.
3. Flue partly or fully blocked.
Low fire screw set too low.
4.
5. Control metering stem slot obstructed. To clear, turn
Control Knob from OFF to full ON several times.
6. Trip lever operated.
7. Oil Control filter blocked. Remove and clean with boiling
water and dry thoroughly before replacing.
Fuel inlet blocked. Service.
8.
9. Oil level in tank too low.
10. Air lock in oil line tank – burner – control.
Incorrect or contaminated fuel. Very little can cause trouble.
11.
Clean out tank and refill with a new fuel.
12. Electrical supply failed or turned off. Check power supply. If there is
a power cut, switch control to manual. See User’s Instructions.
5
. ELECTRICAL SUPPLY
All electrical work must be carried out by competent persons.
his cooker requires an electrical supply 230V 50Hz. A 3Amp
T
fused spur is to be positioned within 90cm of the LH side of the
cooker, See diagram 14.
In addition, the supply can be wired in via an optional timer
control, see diagram 14.
This supply needs a transformer which connects to the oil valve
thermostat control fitted inside the cooker. Easy access is provided
ia a magnetic access panel on the LH side of the cooker.
v
The cooker has a manual overide in the event of a power cut. See
ser’s Instructions.
U
6. FLUE SYSTEMS
5
Approved anti-downdraught
Min Height
This appliance is designed to operate with a Class 2 flue,
nominally 125mm (5") diameter. To ensure correct performance,
both flue and termination should conform to the relevant British
Standard.
NOTE: COMBUSTION TESTING, FLUE GAS ANALYSIS AND
DRAUGHT MEASUREMENT MUST BE CARRIED OUT ON SITE
BY THE APPROVED COMMISSIONING ENGINEER.
The quality of the flue is vital for satisfactory operation. A thorough
pre-installation check by a flue specialist is advisable. If an existing
flue is to be used, the specialist will advise on re-lining and the
correct choice of cowl or terminal for site wind conditions etc.
Before installing the appliance into an existing flue, check that:
the flue is clear of obstructions. Repair any structural damage.
•
the flue pipe is continuous. Any breaks in seals, flue liners etc.
•
must be rectified. A flexible steel liner (oil grade), BS4543 Parts
1 & 3 is highly recommended.
the flue diameter is uniform over its entire length.
•
the flue is not serving another appliance. Never connect to a
•
shared flue.
the flue is not constructed wholly of a single-skin pipe. This
•
must not be used under any circumstances. It has minimal heat
Typical Flue Arrangements
25mm (5") Diameter Flue
1
flue terminal
ermiculite
V
Clay liner
Sealing and
clamping plate
toBend
=600mm
NOTE: THESE DRAWINGS ARE SCHEMATIC REPRESENTATIONS ONLY
ermiculite or
V
similar filter
Flexible flue liner
Closure plate
5" diameter flue
Cleaning hatch
etention properties, and will lead to an overall loss of
r
efficiency, as well as condensation in flue and ovens.
vermiculite backfill, or the equivalent, is used whenever a
•
lexible liner is installed. It must be sealed top and bottom.
f
salt-glazed clay or pre-cast liners are acceptable.
•
the most appropriate cowl depends entirely on conditions at
•
he site. Several may have to be tried before one is found that
t
gives good all-year performance. In some circumstances it
may not be possible to entirely exclude downdraughts
aused by surrounding buildings or trees, so fit an anti-
c
downdraught cowl, preferably of the O-H type.
A ‘Chinaman’s Hat’ is not sufficient.
7. FLUE HEIGHT
A minimum of 4 metres (15 feet) is required between cowl and
round level.This ensures that the flue gases are vented into
g
relatively non-turbulent air, and will be less affected by nearby
buildings or trees etc. In certain circumstances, trees or other
bstructions may need to be removed.
o
Installation with flues in excess of 10M in height is not
recommended. Very tall flues are likely to exceed the maximum
flue draught specified in the technical data. High flue draughts can
cause problems with oven and hob temperatures and increase
running costs.
The cowl must be at least 1 metre above any obstruction within
600mm, and the siting of the flue should comply with OFTEC
regulations.
8. HORIZONTAL RUNS
Horizontal runs of greater than 450mm (18") should be avoided.
If the flue has to be offset, the recommended angle is 60° and the
legal minimum 45°. Never use a bend of 90°.
If the installation is using an existing flue, horizontal runs should be
avoided. A vertical rise of 600mm is the mandatory minimum
before turning into the flue. If it is necessary to exhaust into an
extended flue after the mandatory 600mm rise, the horizontal run
must not exceed 450mm.
NOTE: ALL FLUE CONNECTIONS MUST BE FULLY SEALED
AND INSPECTED BY THE INSTALLER ON COMPLETION.
9. FLUE CLEANING
Annual inspection and cleaning of the flue is recommended.
Therefore a cleaning door, or some other means of access, should
be incorporated into the system.
10. HEARTH CONSTRUCTION
The cooker must be installed on a non-combustible surface
designed to take its weight. For example, concrete slabs or similar.
11. CLEARANCE TO COMBUSTIBLES
Allow 15mm to the rear of the unit for the circulation of air and
the escape of cooking vapours. Do not tile down as far as the top
plate surface – if the top plate has to be removed at some time in
the future, the tiles would be damaged.
Allow 20mm to either side. Vertical filler pieces can be used.
15
4
12. OIL TANK SUPPLY PIPING
The appliance must be supplied by an oil tank and pipework of an
OFTEC approved standard, and installed to current OFTEC Codes
f Practice. Mild steel tanks should conform to BS541, plastic
o
tanks to OFT100.
14. FLUE DRAUGHT INTERFERENCE
ppliances with the ability to extract air should not be located in
A
the same room as the oil-fired Range Cooker. If this proves to be
impracticable, then additional air inlets to should be provided to
ompensate. A Flue Draught Interference Test will determine
c
whether or not there is an adequate air supply.
FAULT FINDING
GENERAL FAULT FINDING CHART FOR SINGLE, COMBINATION AND
DOUBLE OIL BURNERS
5
A = 450mm minimum height above the Cooker Oil Control Valve
H = Head of oil not more than 3m above the Cooker Oil Control Valve
It is important that the oil supply pipe and the height of the tank
are sufficient to enable 0.8 litres of oil per hour to pass freely into
the burner. Calculate the size taking into account the total friction
losses in the pipe, including bends etc.
Run the oil supply pipe to the rear LH side of the cooker, where it
will join with the Preformed 8mm Feed Pipe, which connects to
the Oil Valve. Easy access is gained to this pipe via a magnetic
access panel.
NOTE: A FUEL SHUT-OFF VALVE MUST BE FITTED AS CLOSE
TO THE APPLIANCE AS POSSIBLE – AND BE ACCESSIBLE AT
ALL TIMES. IT SHOULD BE CLOSED WHEN THE PROPERTY IS
VACANT FOR ANY LENGTH OF TIME.
Oil tank and pipe installation
13. AIR SUPPLY
Whenever a flued appliance is installed, a permanent air vent
must be provided. It must be located to take its air either from an
external source, or from an adjacent room which itself must have
a permanent external air vent of at least the same size.
For oil fired appliances, British Standard Code of Practice BS
5410: Part 1: 1997 requires that combustion air must be provided
into the room containing the appliance through purpose made
non-closable openings, having a total free area of 550mm
of the appliance maximum output rating above 5 kW.
This requirement does not apply if a room sealed balanced flue
appliance is used.
The Building Regulation for England, Wales, Scotland require that
an air supply to each appliance is provided, in accordance with
the requirement of BS 5410: Part 1: 1997. In the Republic of
Ireland, the Regulations advise that an air supply of 550mm
each kW of appliance output above 5 kW is provided.
This appliance requires a minimum of 755m2.
2
per kW
2
for
LUE DRAUGHT INTERFERENCE TEST
F
When the extractor is in the same room as the appliance – all
doors, windows and additional ventilation openings to the room
ust first be closed.
m
When the extractor is elsewhere in the building – all doors,
windows and additional ventilation openings must be closed, and
internal doors left open. The extractor should then be run at
maximum speed. As soon as the normal airflow pattern has been
established, the appliance should be set to maximum.
Combustion condition readings should then be taken with and
without the extractor fan running. The appliance should work
satisfactorily in either case. If not, additional ventilation must be
provided.
VENTILATION RESTRICTIONS
Where the appliance has a Vaporising Burner, the mechanical
extract rate from the area in which it is installed must not exceed
20 litres per second.
In the case of a Pressure Jet Burner, the rate must not exceed 40
litres per second.
OTHER INTERFERENCE WITH AIR SUPPLY
Other appliances like tumble driers, which discharge air to the
outside, have the same effect as extractor fans.
Other heating appliances in the same area using different fuels can
also have an adverse effect. They must have their own air supply
complying with Building Regulations for that particular fuel.
15. BURNER INSTALLATION
6
Burner Assembly
When the appliance is in its final position and has been levelled,
connect the 10mm Oil Feed Pipe to the KBB Remote Acting Fire
Valve, 8mm connection to the Preformed Feed Pipe on the LH
side of the cooker, and then to the inlet of the Oil Control Valve.
Purge the Oil Feed Pipe to remove air locks, then open all valves
to allow oil into the Oil Control Valve.
EVIDENCE OF FAULTCAUSE
Trip/Reset lever operates repeatedly1. Oil level in control too high.
2. Top of tank over 10 feet above oil control unit.
Yellow flame on high fire only1. High fire screw set too high.
2. Burner out of level.
Yellow flame on low fire only1. Low fire screw set too low.
2. Burner out of level.
Yellow flame at all Control Knob positions1. Too much primary air.
2. Too little secondary air.
3. Vapourising Chamber lid not fully seated.
4. Shells not correctly seated.
5. Burner out of level.
Yellow flame at one point of burner only1. Wicks incorrectly positioned or upside down.
2. Vapourising Chamber lid not fully seated.
3. Shells not correctly seated.
4. Lighting flap not correctly seated.
5. Burner out of level.
Flame funnelling at centre of burner1. Wicks incorrectly positioned or upside down.
Flame appears to leave top of burner1. Too little primary air.
2. Too low a flue pull.
3. Flue partly or fully blocked.
Burner Popping1. Too little primary air.
2. Too much secondary air.
3. Too low a flue pull.
4. Downdraught in flue. Fit suitable anti-downdraught cowl.
5. Wicks incorrectly positioned or upside down.
6. Oil depth in burner base too deep.
7. Vapourising Chamber lid not fully seated.
Burner surging1. Variations in flue draught. Fit suitable stabiliser.
2. Fuel inlet overheating. Insulate with fireproof material.
3. Oil depth in burner base too deep.
Impossible to set high fire high enough1. Too little primary air.
Flue partly or fully blocked.
2.
Impossible to set high fire low enough1. Too much primary air.
Impossible to set low fire high enough1. Too little primary air.
Too much primary air.
Impossible to set low fire low enough
Oil smell apparent1. Too little primary air.
1.
2. Too low a flue pull.
Downdraught in flue. Fit suitable anti-downdraught cowl.
NOTE: AVOID KINKING IN THE OIL FEED PIPE, IT CAUSES AIR
LOCKS. ALWAYS RUN THE PIPE TO A LOW POINT, THEN
PROVIDE A GRADUAL UPWARD SLOPE TO THE BURNER.
Open the Burner Door, and remove the Burner Cover.
Adjust the front support levelling screws of the Burner Assembly
until it is level in all directions by using a Cross Test Level. Then
tighten the locknuts on the levelling screws, and re-check for level.
Check that the oil depth in the burner base is between 5 to 6mm.
Correct if necessary by adjusting the position of the Oil Control
Valve.
NOTE: The Burner Base must be level in all directions.
It is a requirement under OFTEC regulations that the
installation is recorded on a CD 10 form (a copy is attached at
the end of this book). Once completed, a copy is to be given to
the end user and one copy sent to Gazco Ltd. Failure to do so
may invalidate the guarantee.
Fit the Burner wicks, and check that the ‘cut-outs’ face downwards
nd line up with the radial oilways in the Burner Base.
a
Now fit the Vapour Chamber Lid with its machined face
ownwards, and turn, pressing down to get a mechanical seal.
d
Also check that each Perforated Shell Assembly has a near-airtight
eal with the Burner Base – and that the seams are arranged
s
approximately at right angles to each other, with the Lighting Port
at the bottom facing forward. Take care not to trap a wick thread
between the Shell and the Base.
8
icks
W
Galleries
ross Ports
C
18. ADJUSTING THE OIL CONTROL VALVE
– BM30 SERIES
The BM30 Oil Control Valve is a safety component, and so must
e handled carefully. Installation, adjustment and servicing can
b
only be performed by authorised personnel, and must conform to
Local Authority codes and requirements.
NOTE: BEFORE ADJUSTING THE OIL CONTROL VALVE,
CHECK THE VALVE AND FILTER FOR CONTAMINATION.
9
The performance of the Oil Control Valve is governed by an
adjustable Control Rail. It is mounted on a toothed rack, moved by
a pinion connected to the Oil Control Knob. Before adjusting the
rates, remove the punched section of the Cover Plate.
10
Low fire limit screw (F)
Control Valve Adjustment
Control rail
Control Oil Knob
High and Low fire adjusting
screw position (E)
24
Carefully remove the mineral wool insulation to reveal the
Cleaning Door, then remove it.
Removal of the mineral
wool insulation
25
Removal of the flueway cover plate
Remove both top Flueway Cover Plates – and thoroughly clean all
combustion products from the flueways with a wire brush.
Replace the Cover Plates, making sure the gaskets are sound and
form a gas-tight joint. Replace the insulation.
Fit the Burner Shells, starting with the inner one and working
utwards. Arrange the seams at 90˚ to one another, with the outer
o
shell Lighting Port facing forwards. Check that each shell is
accurately located on its spigot, and has not trapped a strand of
ick material.
w
it the Cast Iron Flame Ring, taking care not to disturb the Outer
F
Shell, then fit the Burner Lids.
eplace the Boiling and Simmering Hotplates, using the tool
R
provided. When in place, tighten the fixing screws – making sure
both hobs are uniformly bedded on the rope seal, and level after
inal tightening.
f
Replace the Inner Control Box Assembly, and re-fit the Tempomat
o the Oil Control Valve.
t
Re-fit the Oil Control Box Casing, and the control knobs.
Turn on the electrical supply, press the Safety Button to turn on
the oil supply – allowing 10-15 minutes for sufficient oil to enter
the Burner.
Then turn the Oil Control Knob to ‘High +’ setting, and switch on
the Thermostat.
Lift the Lighting Port Cover, light the Burner, and then replace the
Burner Cover.
With the Thermostat at the mid-position, let the cooker get back
up to its working temperature.
The Servicing Procedure is now complete.
17. CHECKING THE BURNER OIL LEVEL
Open the Oil Control Box Cover.
After making sure that all valves have been opened, press down
the Trip/Reset Lever, and turn the Oil Control Knob to the
‘Number 6’ setting.
8
Oil Control Knob
Trip/Reset Lever
High fire position
Control knob (A)
Low fire position
To adjust the minimum flow rate turn the Oil Control Knob to
‘position 1’ and turn the Adjustment Screw, which is visible
through the knockout in the cover, anti-clockwise to increase the
flow, clockwise to decrease it.
To adjust the maximum flow rate turn the Oil Control Knob to
‘position 6’ and turn the Adjustment Screw, which is visible
through the knockout in the cover, anti-clockwise to increase the
flow, clockwise to decrease it.
Actuating pin
Check that the integral Draught Stabiliser is free from obstruction
and can move freely.
Thoroughly clean the passages across the top of the cooker before
the Boiling and Simmering Hotplates are replaced.
25. RE-ASSEMBLY
First, replace the Burner Assembly in the Combustion Chamber
and lightly tighten the 2 retaining nuts.
Using a Cross Test Level, make sure the base is level in all
directions by adjusting the Jacking Screws – then tighten the two
retaining nuts. Re-check that the Burner is level.
Re-connect the Oil Supply Pipe to the Oil Control Valve, checking
all joints for leaks.
Allow oil to enter the Burner and check the oil depth is between
5 to 6mm.
Replace the Vapour Chamber Lid, and turn, pressing down, to get
a mechanical seal.
Insert new wicks, making sure the cut-outs are facing downwards
and in line with the radial ports.
7
12
urner Cover fixing nut
9
1
B
23. CLEANING BURNER AND FILTERS
19. CHECKING AND ADJUSTING BURNER
12
FLOW RATES
urner
B
over
C
lean the Burner Base thoroughly, paying particular attention to
C
the cross ports and galleries. Make sure the annular shell location
spigots are clean and undamaged, and that the Vapour Chamber
id seating is flat and unmarked.
L
fter making sure that the Burner is level, and that the oil is at the
A
correct depth, disconnect the feed pipe from the Oil Control Valve
to the Burner and measure the flow rate by the Drip Feed Method.
Burner Door
Remove the Burner Cover by releasing the hexagonal nut with the
ool provided, and lifting the door clear.
t
20
Check the machined face of the Vapour Chamber Lid to make
ure the surface is flat and free of inclusions.
s
Make sure the carbon leg (fuel inlet) is free from any carbon
o not use
eposits. When re-assembling it into the Burner Base
d
PTFE tape as a seal
, always use a jointing compound like Foliac.
22
d
apour Chamber Lid
V
achined face
m
Annular shell location
spigots
apour Chamber Lid
V
seating
Thoroughly clean soot deposits from all burner components.
Remove the Oil Filter Element from the Oil Control Valve, wash
out with clean kerosene, and re-assemble. Check that the
neoprene gasket makes a leak-proof seal.
NOTE: ALLOW 10 MINUTES FOR THE FLOW RATE TO
STABILISE BEFORE MEASURING. AFTER RESETTING, ALLOW
MINUTES BEFORE THE NEXT MEASUREMENT.
2
To check the low setting
ontrol Valve to ‘position 1’, and check the flow. It should be
C
- turn the Oil Control Knob on the Oil
4.0ml/min. If it needs adjusting, turn the Low Setting Screw in
the direction shown on the cover plate to increase or decrease
he flow.
t
To check the high setting - turn the Oil Control Knob to ‘position
’, allow time for the flow to settle, then check. It should be
6
10.0ml/min. If it needs adjusting, turn the High Setting Screw in
the direction shown on the cover plate to increase or decrease
the flow.
When adjusting the burner flow rates, the screws musrt only be
turned a quarter of a turn at a time and the flow allowed to
stabilise before turning further.
20. LIGHTING THE OIL BURNER
WARNING
NEVER try to re-light a hot burner! The burner MUST
be cool before you turn on the oil!
nner burner door
I
Lift up the Burner Cover, and remove it.
13
O
T
ven Heat
hermostat
Lift the Oil Control Valve Cover
Oil Control
Thermostat
Over-ride
ower Indicator
P
il control
O
alve cover
v
afety Button
S
Lift up the Controls cover. Push down the Safety Button to turn on
the oil supply, and turn the Oil Control Knob to ‘High +’.
Carefully dismantle the Burner, Flame Ring, Burner Lids, Shells,
Vapour Chamber Lid, and Wicks.
21
Withdrawal of the assembly
Check that the oil supply has been isolated, then disconnect the
Oil Supply Pipe from the Oil Control Valve, avoiding spillage.
Remove the Burner Assembly by undoing the two nuts securing it
to the Combustion Chamber and lifting it out.
In exceptional cases, it may be necessary to remove the Oil
Control Valve metering stem. This must be done with great care,
avoiding any damage to the slot – which must be cleaned with a
wooden cocktail stick, or similar. Never use anything metallic, as it
could increase the slot width and seriously affect flow rates.
24. CLEANING THE FLUEWAYS
23
Removal of the
right side panel
11
Burner Door
Burner Cover fixing nut
Burner
Cover
Open the Burner Door, then unscrew large hexagonal nut on the
Burner Cover using the tool provided.
Remove the right-hand panel in the Combustion Chamber.
11
8
14
Optional Timer Control
3A Fused Spur
Indicator
Neon
2VAC
1
1234
Thermostat
with detail
Element
T/Stat
il Valve
O
Oil Valve Thermostat
SERVICING INSTRUCTIONS
IMPORTANT
It is essential that range cookers are serviced, and flue ways inspected and cleaned, at regular 6-monthly intervals. The frequency
ay be increased if a lower quality fuel is used. The work must be carried out by Don/Oftec trained service engineers.
m
The appliance should be turned off at least 4 hours before the arrival of the engineer, to allow it to cool.
NOTE: BEFORE STARTING WORK, MAKE SURE THAT BOTH
IL AND ELECTRICAL SUPPLIES HAVE BEEN ISOLATED.
O
22. DISMANTLING
Lift the Oil Control Box Cover and remove the 3 control knobs by
oosening the grubscrews.
l
Remove the fixing screws, then lift out the Oil Control Box Casing
nd the Inner Assembly.
a
SWITCHED OUT
40V
2
50Hz
MAINS IN
Connect the secondary leads from the 12 Volt Transformer to the
Tempomat (oil valve thermostat activator). See wiring diagram
above.
Plug the 12 Volt Transformer into the Fused Spur provided and
turn on the electricity.
If the optional Timer Control is fitted, please follow the
instructions supplied with the Timer for setting procedures.
Turn the Thermostat to its maximum position and allow 15
minutes for the oil to enter the Burrner Base.
15
lug In
P
Transformer
ess than 900mm
L
2 3 4
12VAC
1
Leave the Oil Control Knob at ‘High +’, and turn the Thermostat
to its mid position. Shut the Burner Door, and leave for 20
minutes until the burner is hot, then reset the Thermostat to its
maximum ‘Hot +’ position.
The Burner will gradually increase its oil flow rate and raise the
temperature of the oven, taking about two and a half hours to
reach 200˚C (400˚F). Turn the Thermostat to the mid position,
and the oven will maintain its temperature. When cooking is not
required, the Thermostat can be turned to its minimum
‘Warm –‘ setting.
When the appliance is first fired, it may give off a slight odour for
a short time. This is normal, and no cause for concern.
Remove the Boiling and Simmering Hotplates. First release the 3
screws on each hotplate, and wind the plate out to expose
approximately 30mm. Attach the spider tool provided by locating
it under the 3 countersunk screw heads, then rotate the plate
anti-clockwise and lift it clear of the cooker. The Boiling Plate is
much heavier, so take care as you remove it.
16
(Illustration i)
Outer burner door
Oil control
box cover
Securing screws
(Illustration ii)
Remove control box outer
cover and inner assembly
17
Remove the screw on top of the Tempomat to expose the
electrical connections.
18
Lighting port
cover
Lighting port
Insert a lit taper through the lighting port
Lift the hinged cover of the Lighting Port on the front of the
burner, and light the wick.
Replace the Lighting Port Cover, then the Burner Cover. The
hotplate covers must also be closed, to conserve heat.
21. TESTING BURNER
SMOKE
Using the Sampling Hole in the front of the Flue Hood Assembly,
sample the flue products with a Baccarach Smoke Pump and
check the flue draught. Adjust the draught divertor to give the
required flue draught. See Technical Specification on page 2.
All readings should give a Smoke Number of 0-1 at both low rate
and high rate.
NOTE: NOW COMPLETE THE COMMISSIONING CHECKLIST
ON THE FOLLOWING PAGE – AND MAKE SURE THE USER IS
FAMILIAR WITH BOTH THE OPERATION OF THE APPLIANCE,
AND THE SAFETY MEASURES.
It is a requirement under OFTEC regulations that the
comissioning is recorded on a CD
11 form, available from
Oftec. Once completed, a copy is to be given to the end user
and one copy sent to Gazco Ltd. Failure to do so may invalidate
the guarantee.
9
(Illustration iii)
Inner assembly removed
Remove the fixing screws from the Tempomat, and move it clear
of the assembly without disconnecting the wiring.
10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.