Model No.
U.S. Patent Numbers 5,069,042 5,522,229
®
Tamper Resistant
83230
(EZT230)
Float Switch Assembly (1)
Red/Blue Service Label (1)
Yellow Cleaning Label (1)
(EZT113)
Kit Contents
3/4″ Standard Trap (1)
3/4″ Cross (1)
3/4″ Tee (1)
3/4″ Locking Cap (1)
Brush Holder (1)
72″ Modular Cable (1)
3/4″ Adaptor (1)
Cleaning Brush (1)
Scan for more info
3/4ʺ Condensate Trap
with Overow Switch
1” DROP
New!
Compact Modular
Switch Assembly
▼
2 Year
LIMITED WARRANTY. RectorSeal® warrants to the original consumer purchaser (“Purchaser”)
of its product, EZ Trap
from the date of the original consumer purchase this product shall prove to be defective, it shall be repaired or replaced at
RectorSeal’s option. Your original receipt of purchase is required to determine warranty eligibility.
RectorSeal® 2601 Spenwick Drive - Houston, TX 77055
ph: 713.263.8001 - 800.231.3345 fax: 713.263.7577 - 800.441.0051
www.rectorseal.com - Like Us on Facebook
961810
®
, that it is free from defects in material or workmanship. If within two years (24 months)

Wiring Instructions
1. Turn off power at main panel before opening unit and
working on electrical system.
2. An inline fuse is necessary to protect the 24V circuit .
3. Connect Float Switch using wiring diagram. (below)
4. Test system for proper operation by lifting oat.
instructions
®
Important:
as well as all applicable local
plumbing, drainage and
Install in strict accordance
electrical codes.
with RectorSeal
K
Note: Wiring diagram shown cuts power to thermostat when oat switch
operates to stop operation of the A/C unit. To inhibit mold growth during long
absences, connect terminals into yellow cooling circuit so when oat
switch operates, condenser will switch off but fan will continue running.
F
5° angle
Not included
E
THERMOSTAT
red
black
TERMOSTATO
rojo
negro
black
X1
negro
24V
TRANSFORMER
X2
EZ-TRAP SWITCH
TRANSFORMADOR
Installation Instructions
Model No.
H
D
C
G
J
B
Not included
A
Drain Pan Outlet
Trap Assembly Instructions
1. Screw Adaptor (A) into 3/4” primary drain pan outlet.
2. Dry t, and mark components. Rotate U-Bend (D)
and Outlet Tee (E) to required angles for installation.
3. Glue components (B thru E) using dry t markings.
Glue assembly into Adaptor (A).
4. Glue Drain Line (F) into center leg of Outlet Tee (E). Drain Line must exit building with at least a 5°angle.
5. Press t Float Switch (G) into opening at top of Inlet Cross (C). DO NOT USE GLUE.
Check that Actuator Arm moves freely inside Inlet Cross.
6. Check that Locking Cap (H) is tightly secured.
7. Press plug end of Modular Cable (J) into Float Switch Assembly (G).
8. Place cleaning brush into retaining hole on Brush Holder (K).
9. Attach service & cleaning labels as indicated.
Note: Insulation is required when trap is installed in unconditioned space where sweating can occur.
83230
(EZT230)