Rec Temovex G10125, G10126 User Manual

Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
1
User manual
1.6-1-01
DESIGN & TECHNICAL INFORMATION
OPERATION & CONTROL
MAINTENANCE & SERVICE
Exhaus
t air filter, article No
: G10125
Supply
air filter, article No
: G10126
CONTENTS
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
2
page
Design & technical information
Product description 3 Casing 3 Filter, exhaust air 3 Bypass damper 3 Fan, exhaust air 3 Fan, supply air 3 Heat exchanger 3 Filter, supply air 3 Inspection door 3 Adjustable feet 3 Condensate drain 3 Control panel 3 Afterheater 3 Functional diagram supply air control 4 Chiller / Cooling coil (optional) 4 Technical specification 5 Dimensions 5
Operation & control unit
Overview 6
Control unit main screen The menu system
How to change values and settings Menu screens, structure and contents Fel! Bokmärket är inte definierat.
Main menu
Version
Language
Address
1. Temperature 8
Temperatures
ECO-adjustment
Control function
2. Mode 9-10
Fan control
Timer adjustments
Date, time and summer/wintertime
Activate timer
Time schedule
Holiday schedule
3. In/Outputs 11
Analog inputs status
Digital inputs status
Analog outputs status
Digital outputs status
Calibrate sensors
4. Manual/Auto 12
Supply air controller
Fans, by-pass damper, heat and chill
Digital outputs
Filter timer
5. Alarm 13
Alarm history
6. Load settings 14
7. Authorization 14
Options
Setpoint adjustment Remote panel - Easy (TG-R4) 15 Remote panel - Without display 15 Remote panel – With display 15
Maintenance & service
Cleaning 17 Changing filter 17 Cleaning fans 17 Cleaning the heat exchanger 17 Checking the condensate drain 17 Cleaning, air diffusers 18 Cleaning the duct system 18 Checking the outdoor air intake 18 Service 18 Disposal 18
DESIGN & TECHNICAL NFORMATION
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
3
Product description
Temovex Blue 4 is an air handling unit (AHU) fitted in a cabinet. The unit is designed for the ventilation of homes, offices, nurseries and other small premises. The Temovex unit should be installed in a heated room, such as a scullery, laundry or similar.
The standard Temovex unit consists of a counterflow heat exchanger, 2 fans, 2 filters, after­heater, by-pass damper and a control system.
Positioning guide
1. Casing
2. Filter, exhaust air (behind inspection door)
3. By-pass damper
4. Fan, exhaust air
(backside)
5. Fan, supply air
6. Counterflow heat
exchanger
7. Filter supply air
(behind 2.)
8. Elevator device
9. Adjustable feet
10. Condensate
drain
11.Control panel
12.After-heater
1. Casing
Inside is the unit made of EPP (Expanded PolyPropylene). The outside casing is made of galvanised sheet metal with 30mm insulation. As a standard, the side panels and the front are white (powder paint). The front door has a magnetic strip which keeps the door closed. The unit top has sleeve connections made of EPP, where all ducts are connected.
2. Exhaust air filter
G4, bag (art. No. G10125)
3. By-pass damper
The Temovex AHU has an automatic by-pass damper which makes the air by-pass the heat exchanger whenever heat recovery is not necessary. The by-pass setting is adjusted on the control panel.
4. Exhaust air fan
The unit has low-energy fan of EC type with integrated overheating.
5. Supply air fan
The same type as exhaust air fan (see point 4).
6. Heat exchanger
The heat exchanger is a standard highly efficient counterflow heat exchanger from Recair. The heat exchanger is made of very thinny, pleated plastic sheets and and the supply air and exhaust air sides are completely sealed from each other. This is important in order to avoid odours and other contaminants from old air seeping through to fresh air. The heat exchanger has no moving parts, which eliminates wear.
7. Supply air filter
F7, bag (art. No. G10126)
8. Elevator device
The elevator device must unfasten to make it possible to take out the heat exchanger for cleaning. (See chapter "Maintenance & service").
9. Adjustable feet The cabinet has adjustable rubber feet.
10. Condensate drain
The Temovex unit is fitted with a condensate drain at the bottom of the unit. This should be connected to a drain or fed to a floor drain.
11. Control panel
All settings for fan speed, after-heating, by-pass etc. are made via the control panel and the AHU's integrated control system. If you have added optional parts to your Temovex AHU, these functions, too, are set via the control panel.
12. After-heater
Temovex Blue 4 is fitted with an electric after­heater, 0.9 kW. As an optional extra, a reinforced electric after­heater, 1,8 kW, or a water coil (two different sizes) for waterborne heating is offered. The heater is integrated in the unit and settings are made via the control panel. In the case of a water coil, the water connections are at the top of the unit, dimension DN12. The Temovex Blue 4 with water coil includes a two­way valve and valve motor in the consignment from REC.
11
1
2 3 4 5 6 7 8 9 10 12
FUNKTION & UPPBYGGNAD
Ventilationsaggregat Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
4
Functional diagram
VVX Counterflow heat exchanger ST1 Damper motor, heat recovery (By-pass) EVBV After-heater, electricity/water GT1 Sensor, supply air temperature GT11 Sensor, outdoor air temperature TFR Filter, outdoor air FFR Filter, exhaust air
TF Fan, supply air FF Fan, exhaust air GT2 Overheating protection (when electric coil) GT3 Sensor, extract air temperature GT7 Freeze protection (when water coil) GT5 Sensor, exhaust air temperature
Chiller (cooling coil) EKB (optional)
FUNKTION & UPPBYGGNAD
Ventilationsaggregat Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
5
Tecnical specifications
Electrical version HW version
Power consumptions standard version 1172 W 272 W whereof fans 265 W 265 W whereof heater 900 W ­Extended heater 900 W ­Output water coil small (standard) - 1500 W
1
Output water coil extended - 2800 W
1
Voltage/Frequenzy input 230 V, 50 Hz 230 V, 50 Hz Fuse 10 A 10 A Filter, supply air / exhaust air Bag F7 / Bag G4 Bag F7 / Bag G4 Mass 98 kg 98 kg Water connection - DN12 Dimensions (WxDxH) 482x670x1940 mm 482x670x1940 mm Duct connections 4 x Ø160 mm 4 x Ø160 mm Condensate drain 8 mm 8 mm Storage Temperature Range -20 . +50ºC Operating Temperature 0 . +50ºC
1
At water temp. 55/45 °C and 70% of maximum flow.
Dimensions
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
6
Overview
On the following pages you will find information about the basic functions that you yourself can adjust to fit your requirements and wishes. The unit control system optimizes its function according to the settings you define.
Please note the following: In the menus regarding heating and cooling, where you have the option of making changes, Auto Mode gives you an optimized function. If you select a manual setting, On or Off, the manual setting overrules auto settings.
Control unit
Up
Down
Right
Left
Confirm
Show alarm
Delete
Alarm
Flashing There are one or more alarms that have not been acknowledged..
Steady There are one or more acknowledged alarms left.
Setting
Flashing You are in a menu where it is possible to change some parameters.
Steady You are now in change position.
The menu system
The AHU's settings and status can be studied by scrolling the menu screens. Some parameters and settings can be changed. Basic system configurations cannot be changed without authorized access code (technician level). If no buttons are pressed for 25 minutes, the system will automatically revert to the control unit's Main screen. When the access code has been used to log in, the system will automatically log out when 25 minutes have passed.
How to change values and settings
The yellow LED is flashing in menus where adjustments can be made by the user (see page 6). If you press OK, the changeable parameter will flash. Changes are made using the arrow buttons up or down. Move between positions sideways using the arrow buttons right and left. When the desired value shows, confirm with OK. The cursor automatically indicates next variable that is possible to adjust in this menu.
OK
C
REC TEMOVEX Mode: Normal Status: Heating 100%
Temp. : 21.0 °C
OK
C
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
7
Menu and structure
The manual shows the menus roughly the same way as they appear on the terminal. If jumps between different menus are possible, these are shown in the manual. In some cases, more information about menus are shown after each section. The walk through the menus starts with the main menu below.
Main menu
Mode shows current fan mode. The unit can work in different modes, depending on for instance temperature and commands given to the unit. Available modes are Stop, Low, Normal, Boost, Max, Kitchen mode, Stove mode, Night cooling, Defrost, ECO, Fire, ECO2 and Safe mode. Further information can be found under the various heading in this manual. Status shows the current level of heating or cooling. Available modes are Heating xx%, By-pass xx% and Cooling xx%. If they all show level 0%, the unit shows ------ 0%. Temp shows current set temp.
Version
Shows current program version and the serial number of the electronics. Present date and time is shown and can be changed here.
Language choice
Choose Swedish, English or Polish.
Address
Shows the address to the unit. Possible to change.
~
~
|
}
|
}
|
}
|
}
|
}
|
}
|
}
|
}
~
~
~
~
|
}
REC TEMOVEX
Mode: Normal Status: Heating 100% Temp. : 20.0 ºC Ô
Temperature Ó Mode In/Outputs Manual/Auto
Temperatur
e, continue to page
8
Temperature Ó Mode In/Outputs Manual/Auto
Temperature Ó Mode In/Outputs Manual/Auto
Mode Ó In/Outputs Manual/Auto Alarm history
Mode, continue to page 9
Alarm
history, continue to page
13 Lo
ad settings
, continue to
page
14
Version Version:1.3-0-03 ID number:13261274 14:02:18 08:02
Choose language English
Address: PLA: 254 ELA: 30
Main menu
Move sideways with the arrow buttons right/left.
The menu-tree continues on page in the manual.
Manual/Auto Ó Alarm history Load settings Authorization
In/Outputs Ó Manual/Auto Alarm history Load settings
In/Outputs, continue to page 11
Manual/Auto, continue to page 12
Move vertically with the arrow buttons up/down.
~
|
}
Authorization
, continue to
page
Manual/Auto Ó Alarm history Load settings Authorization
depending on configuration, may be some menus are not visible.
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
8
1. Temperature.
Temperature
The outdoor temperature is measured on incoming air close to the AHU. The temperature can differ a little from the real outdoor temperature, depending on the duct length, insulation etc. The supply air temperature is measured in the supply air duct, normally about one meter from the AHU. Supply air is the fresh air that - after possible heating - is sent into the room. The exhaust air temperature is measured close to the AHU. Exhaust air is the air that leaves the room and goes
back to the AHU, where the heat is recovered. The extract air temperature is measured close to the AHU. Extract air leaves the AHU and is sent out from the house.
The room temperature is measured with an external sensor, placed in an appropriate place in the flat/house. The freeze protection temperature is only used with water heating and shows the temperature of the return water
from the heater. To prevent freezing of the water heater, the AHU will stop if the water temperature is too low.
ECO adjust.
ECO adjust. is only used with exhaust air control and room control, and gives a temperature range where heating and cooling is disabled. Example: ECO-adjust 2 degrees and a set temp at 20 degrees means heating and cooling will be disabled between 18 and 22 degrees. ECO-adjust is activated when ECO is enabled.
Control function
What is shown in the temperature menu depends on the selected control function. There are four control functions to choose between, depending on application: a) supply air control, b) cascade exhaust air control, c) cascade room control and d) outdoor compensated supply air control.
For temperature settings and reading, choose the column that corresponds to your configuration.
a) Supply air control b) Exhaust air control c) Room control d) Outdoor compensated supply air control
* The menu Freeze P temp. is only shown if water heater is configured.
| | | |
|
}
|
|
| | |
|
} | | | | |
|
} | | | |
|
}
| |
Continued from Temperature, page
~
Freeze P. temp. ↑ Actual: 8.5 ºC
~
Freeze P. temp. Actual: 8.5 ºC
*
*
~
Freeze P. temp. ↑ Actual: 8.5 ºC
~
Extract air temp. ↑ Actual: 11.5 ºC
~
Extract air temp. ↑ Actual: 11.5 ºC
~
Freeze P. temp. Actual: 8.5 ºC
*
*
~
Extract air temp. ↑ Actual: 11.5 ºC
~
Exhaust air temp. ↑ Actual: 20.1 ºC
~
Exhaust air temp. ↑ Actual: 20.1 ºC
~
Extract air temp. ↑ Actual: 11.5 ºC
Exhaust air temp. ↑ Actual: 20.1 ºC
~
Outdoor comp. setp. 10 ºC = 18 ºC 15 ºC = 12 ºC
~
Exhaust air temp. ↑ Actual: 20.1 ºC
~
Supply air temp. ↑ Actual: 25.1 ºC
~
Supply air temp. ↑ Actual: 25.1 ºC
~
~
Outdoor comp. setp.↑
-5 ºC = 23 ºC 0 ºC = 22 ºC 5 ºC = 20 ºC
~
Supply air temp. ↑ Actual: 25.1 ºC
~
Outdoor air temp. ↑ Actual: 15.5 ºC
~
Outdoor air temp. ↑ Actual: 15.5 ºC
~
Outdoor air temp. ↑ Actual: 15.5 ºC
|
}
Supply air temp. Actual : 25.1 ºC Setpoint: 25.0 ºC
Exhaust air temp. ↑ Actual : 20.1 ºC Setpoint: 20.0 ºC ECO adjust.: 2 ºC
Room temp. ↑ Actual : 20.1 ºC Setpoint: 20.0 ºC ECO adjust.: 2 ºC
OD temp.: 15.5 ºC ↑ Supply air temp. Act.: 25.1 ºC Setp.-> Comp.SP: 12.0 ºC
Outdoor comp. setp.
-20 ºC = 25 ºC
-15 ºC = 24 ºC
-10 ºC = 23 ºC
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
9
2. Operation mode
In the mode menu, the operation mode of the fans can be changed. Date and time can be set and the timer can be configured.
|
|
} |
~
|
}
|
} |
|
}
|
}
|
}
~
~
|
}
Fan control Mode: Auto
Time: 08:59
Date: 14:02:25 Weekday: Tuesday Summer/winter time
Adjust clock Automatically for Summer time: Yes
Fan control Timer
Fan control Timer
Activate timer No The timer controls: ECO
Schedule Holiday schedule
Schedule
Holiday schedule
Continued from Mode, page
Fel!
~
~
~
~
~
~
|
|
} | | | | | |
~
Holiday (mm:dd) 1: 01-01 - 01-01 2: 01-01 - 01-01 3: 01-01 - 01-01
Holiday (mm:dd) ↑ 4: 01-01 - 01-01 5 01-01 - 01-01 6: 01-01 - 01-01
Holiday (mm:dd) ↑ 7: 01-01 - 01-01 8 01-01 - 01-01 9: 01-01 - 01-01
Holiday (mm:dd)
10: 01-01 - 01-01 11: 01-01 - 01-01 12: 01-01 - 01-01
Holiday (mm:dd) ↑ 13: 01-01 - 01-01 14: 01-01 - 01-01 15: 01-01 - 01-01
Holiday (mm:dd) ↑ 16: 01-01 - 01-01 17: 01-01 - 01-01 18: 01-01 - 01-01
Holiday (mm:dd) ↑ 19: 01-01 - 01-01 20: 01-01 - 01-01 21: 01-01 - 01-01
Holiday (mm:dd) 22: 01-01 - 01-01 23: 01-01 - 01-01 24: 01-01 - 01-01
| |
~
~
~
~
~
~
~
| | | | |
|
}
|
}
|
}
Monday->Friday: Per 1: 08:00- 17:00 Per 2: 00:00- 00:00
Monday: Per 1: 08:00- 17:00 Per 2: 00:00- 00:00
Tuesday:
Per 1: 08:00- 17:00 Per 2: 00:00- 00:00
Wednesday:
Per 1: 08:00- 17:00 Per 2: 00:00- 00:00
Thursday:
Per 1: 08:00- 17:00 Per 2: 00:00- 00:00
Friday:
Per 1: 08:00- 17:00 Per 2: 00:00- 00:00
Saturday:
Per 1: 08:00- 17:00 Per 2: 00:00- 00:00
Saturday->Holiday: Per 1: 00:00- 00:00 Per 2: 00:00- 00:00
Sunday:
Per 1: 00:00- 00:00 Per 2: 00:00- 00:00
Public holiday: Per 1: 08:00- 17:00 Per 2: 00:00- 00:00
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
10
Fan control
Five modes are always available:
· Auto: gives you an optimized function. The temperature is automatically controlled in accordance with the unit's internal and optimized algorithms.
· Min. flow: The system is forced to use a set minimum air flow.
· Boost flow: The system is forced to boost the air flow. Useful for example if you need to air the building
very fast.
· Max. flow: The system works at set maximum air flow.
· Off: All fans are switched off.
Four other modes are available if those functions are installed and configured. (It is possible to choose these modes even if the function is not configured, but the system will return to earlier choice after a few seconds.
· Stove: This mode should be used when the stove/fireplace is used. The supply air fan works at a higher speed than the exhaust air fan, to compensate for the air the stove extracts. The cooling is disabled for a while after the stove/fireplace has been used, in order to retain the good stove heat.
· Kitchen: Use this mode when the cooker fan is running. The supply air fan works at a higher speed than the exhaust air fan, to compensate for the air the cooker fan extracts.
· ECO: Suitable to use when no one is at home. The fans switch to minimum flow, but gradually increase to normal flow when there is need for higher or lower temperature. ECO-adjust gives a temperature range around the setpoint and neither heat nor cool is enabled.
· Fire: To be used above all when testing the fire function. The supply air fan stops at the same time as the exhaust air fan works at its maximum speed.
Timer settings
The clock and summer/winter time
The clock can be set and the change between summer and winter time can be made automatic.
Enable timer
The timer is enabled upon delivery and connected to the function Min flow. If the timer is disabled, so are preset times and holiday schedules.
Time schedule
Two periods a day may be set. Note! To enable the timer from, for example Monday 20:00 until Tuesday 06:00 the settings should be Monday Per 2: 20:00 – 24:00 and Tuesday Per 1: 00:00 – 06:00. To repeat the same time every day of the week, use the function Monday Ú Friday. If you want the same time on Saturdays, Sundays and all holidays (specified in holiday settings), use the macro function Saturday Ú Holiday. There is a separate menu for holiday schedules.
Holiday schedule
Up to 24 separate holiday periods for a complete year may be programmed. A holiday period may consist of a succession of days, from 1 to 365. The date is written: MM:DD. (It is important to set the time period from 00:00 one day until 00:00 next day. For example holiday June 6 will be written 06:06 – 06:07.) If that particular day falls during a holiday period, the system will use the schedule for Holiday.
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
11
3. In/Outputs
In this menu it is possible to check the status of every input and output. It is also possible to calibrate the sensors in this menu.
Analog inputs status.
All current temperatures are displayed here. The room temperature is only displayed if room control is configured. Freeze temperature is only displayed if water heater is configured. UAI3 displays the adjusted setpoint if TG-R4 is chosen as option.
Digital inputs status.
Not active means that the input is not in use (nothing is configured to the input). On means 24V on the input and the function that is configured to the input is active. Off means 0V on the input and the function that is configured to the input is not active. The alarm inputs can have status Ok or Alarm.
Analog outputs status.
Current voltage on the output is displayed.
Digital outputs status.
On means that the output is active and Off consequently that the output is not active.
Calibrating the temperature sensors.
The sensors values may be adjusted up or down. (Set an offset value). For example, the old common thermometer could be synchronized with the AHU temp. State the difference here and they will show the same.
|
} |
|
|
|
}
~
~
DI4 SA fan :Ok ↑ DI5 EA fan :Ok DI6 Not active :Off DI7 Overheat p:Ok
Analog inputs Digital inputs Analog outputs Digital outputs
DI1 AHU On/Off :On DI2 Not active :Off DI3 Not active :Off
~
DI8 FilterAla:Ok ↑
|
|
}
AO1 SA fan: 5.0 V AO2 EA fan: 5.0 V AO3 Heater: 10.0 V AO4 Chiller : 0.0 V
Analog inputs Digital inputs Analog outputs Digital outputs
~
|
|
|
}
~
DO1 BP opening :On DO2 BP closing :Off DO3 PWM heat :Off DO4 Sum alarms :Off
Digital inputs Analog outputs Digital outputs Calibrate sensors
DO5 CP heater :Off DO6 KAVK :Off DO7 ULS :On
~
|
~
|
}
|
UAI1: 24.7ºC K: 0.0 UAI2: NaN ºC K: 0.0 UAI3: ºC K: UAI4: ºC K:
AI1: 18.3ºC K: 0.0 AI2: 24.6ºC K: 0.0 AI3: 23.2ºC K: 0.0 AI4: 13.3ºC K: 0.0
Digital inputs
Analog outputs Digital outputs Calibrate sensors
~
~
|
|
}
AI1 OB temp 10.0ºC AI2 SA temp 20.0ºC AI3 EA temp 21.3ºC AI4 EXT temp 14.0ºC
UAI1 Room t. 10.0ºC UAI2 Freeze t. 12.0ºC UAI3 TG-R4. 0.5 ºC UAI4 Aux 2 NaN ºC
Analog inputs Digital inputs Analog outputs Digital outputs
Continued from In/outputs, page
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
12
4.
Manual/Auto
In Manual/Auto it is possible to control a number of functions manually, which is very useful during the start-up process and for troubleshooting.
Available menus are shown here. All functions cannot be configured at the same time as there are not enough outputs available. Furthermore, some functions are not needed in the application.
If an output is controlled manually, it means that the normal regulation is out of order. Therefore, an alarm will be generated as soon an output is changed to anything else than Auto.
Supply air controller
The output from the supply air controller may be adjusted manually between 0-100%. The output from the temperature controller will follow if it is in Auto mode.
Fans, By-pass damper, Heat and Cool.
The output to the fans, heater, by-pass damper and cooling may be adjusted manually between 0-100%. The actual position of the by-pass damper is displayed in the menu.
Digital outputs
All configured digital output signals, such as ULS, KAVK, CP etc, can be assigned Auto, On or Off (or a similar word that indicates the two possible levels of a digital signal).
Filter timer
The filter timer is administered here. The interval between the filter changes may be set from 6 to 18 months. The menu displays how many months remain before the filters must be changed. NOTE! This value is updated only ones a day. This means that if Interval is changed, Remains will not be updated before next day. Do not forget to reset the timer when the filters are changed (even if the filters are changed earlier than expected).
Continued from Manual/Auto, page
~
|
| |
|
|
~
~
~
~
~
~
~
~
~
~
|
|
} | |
| | | |
~
SA controller Auto Man. output: 0
Supply air fan ↑ Auto Man. output: 0
Exhaust air fan ↑ Auto Man. output: 0
Heater ↑ Auto Man. output: 0
PreHeat ↑ Auto Man. output: 0
BP / By-pass damper↑ Auto Man. output: 0 Pos.: 100% open
Chiller ↑ Auto Man. output: 0
ULS/OD air damper ↑ Auto
KAVK / Cond. boiler↑ Auto
CP/Circ. pump ↑ Heater: Auto
CP/Circ. pump ↑ Chiller: Auto
Fire damper ↑ Auto
Filter timer ↑ Interval: 12 mån Remains: 10 mån Set zero: No
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
13
5. Alarm
All current alarms and the status can be seen by pressing the red button. In this menu alarms can be acknowledged, blocked or unblocked (allow alarm).
There are 2 types of alarms: A and C alarms. A-alarms do not disappear until they have been fixed and acknowledged. C-alarms are internal alarms and will disappear automatically as soon as the alarm reason has disappeared. Some faults cause immediate stop of the unit, as continued operation would be dangerous. An acknowledged alarm that has not yet been dealt with remains on the menu as Acknowledged. It disappears from the menu when the fault has been dealt with. It is possible to block an alarm and continue to run the unit. Note! Do not do this unless you really know what you are doing, since it could be dangerous and in worst case damage both unit and property.
Alarm history
The last 21 alarms are displayed. You can see when the alarm went off, when it was acknowledged and/or returned and so on. In this menu, it is not possible to acknowledge or block any alarms.
List of alarms. (abbreviations – see page 43)
A-a
larm C-a
larm
Sensor error OD temp Sensor error SA temp Sensor error EA temp Sensor error EXT temp Sensor error RM temp Sensor error FRP temp Freeze P alarm Supply fan failure Exhaust fan failure
El. heat. overheated Filter alarm
Filter guard Fire damper alarm
Fire alarm
SA controller man. SA fan manual EA fan manual Heater manual By-pass manual Chiller manual ULS (Outdoor air damper) manual KAVK (Condensation boiler) manual P1-heating manual P1-cooling manual Int. battery failure Warning temperature deviati
|
~
|
Sensor error OD
28 Feb 15:20 Klass:A
Any menu Back to earlier menu
EL.heat. overheated
28 Feb 14:34 Klass:A
EL.heat. overheated
Acknowledge
Block
OK
~
28 Feb 15:20 A
EL.heat. overheated
Activated
Continued from Alarm history, page
28 Feb 13:50 A
Sensor error OD
Acknowledge
|
}
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
14
6. Load settings
Earlier saved settings are loaded back to the DUC here. If nothing has been saved, the standard settings apply. All settings except date and time will be loaded.
7. Authorization
This is where an authorized technician can log in to adjust the system and, if necessary, change parameters.
|
}
|
}
Log in
Log in State code: **** Cur.level:None
Continued from Authorization, page
|
}
Load saved settings: No
Continued from Load settings, page
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
15
Options
Remote panel – Easy (art.no. Q100446)
Remote panel - Easy (TG-R4) has a temperature sensor and a set point knob. The unit is used as room sensor with possibility to adjust the set point within preprogrammed limits. The normal set point is set on the display at the ventilation unit. This set point can later be moved some degrees up or down on the Remote panel – Easy. The adjusted value is displayed on the display at the ventilation unit. Remote panel – Easy has analog transmission of data to the ventilation unit.
Remote panel – Without display (art.nr. Q100040)
Remote panel – Without display has a temperature sensor and a set point knob. The unit is used as room sensor with possibility to adjust the set point within preprogrammed limits. Remote panel – Without display has the same functions as Remote panel – Easy, but works with serial data (RS485) to the ventilation unit.
Remote panel – With display (art.nr. Q101299)
Remote panel – With display is the most advanced remote panel. It has a temperature sensor that could be used as room sensor. This unit has a display and buttons that enables you to see different temperatures and to set them. It is also possible to change the fan speed and see a lot of other information. In addition to this there is an away” button included.
Display the temperature set point.
When no buttons have been pressed for 10 seconds, the set point is displayed and both the indoor temperature symbol and the house symbol are lit.
Changing of temperature set point.
Press the navigation button once and the set point symbol starts blinking. It is now possible to change set point with the setting buttons. The value is saved by pressing the navigation button, or if no button is pressed for 10 seconds.
Away button
Setting buttons
Navigation button
Remote panel – With display
Set point symbol
Fan speed
Kitchen/S
tove Fan symbol
Indoor temp. symbol, outdoor temp. symbol and house symbol
A
t home
By-
pass open
Temperature
Remote panel - Easy
Remote panel – Without display
OPERATION & CONTROL
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
16
Display actual temperature.
Press the navigation button once more (within 10 sec) and the set point symbol will be turned off. The indoor temperature symbol will start blinking and the display shows the actual value. At this point, the setting buttons have no function. When no buttons are pressed for 10 seconds, the display will again show the set point.
Display outdoor temperature.
Press the navigation button once more (within 10 sec) and the indoor temp. symbol will be turned off. The outdoor temperature symbol will start blinking and the display shows the outdoor temperature. At this point, the setting buttons have no function. When no buttons are pressed for 10 seconds, the display will again show the set point.
Fan speed:
Press the navigation button once more (within 10 sec) and the fan symbol, the fan speed symbol as well as MAN or AUTO will light up. The fan symbol starts blinking and the fan speed can be changed to desired position (min, normal, boost or max) with the setting buttons. The positions correspond with the possible settings in menu choice MODE on the main display. A change made on the remote panel will also be seen on the main display. The symbol MAN tells that the unit works in a different mode than AUTO. The unit may run at a fan speed between minimum and normal, or between normal and boost flow, due to boosting or safe mode. The symbol fan speed shows actual fan mode as follow:
· Fan speed zero no box is lit
· < normal mode the box leftmost is lit
· = normal mode the two boxes leftmost are lit
· > normal mode but < = boost mode the three boxes leftmost are lit
· = max mode all boxes are lit
If the unit has been put in manual mode on the main display, nothing will happen to the fan speed if you try to change it on the remote panel. The symbols in the menu MODE on both the remote panel and the main display will change, but the fans speed will not change until you shift from manual mode to AUTO on the main display.
The new settings will be saved when the navigation button is pressed, or when no buttons are pressed for 10 seconds. The main display again shows the set point.
Kitchen/Stove.
The symbol Kitchen/Stove will light up when the unit is placed in stove mode or kitchen mode.
Away mode/ECO-mode.
By pressing the "away" button, the "at home" symbol will be turned off and the unit will change to ECO mode. Turn off ECO mode by pressing once more.. The function requires that ECO is configured on the main display.
By-pass damper.
The By-pass symbol will light up when the by-pass is open > 0 %.
Cool.
COOL will light up if cooling is configured at the main display and the cooling-valve is open > 0 %.
Heat.
HEAT will light up if the regulator is calling > 0 % heat.
Alarm.
SERVICE will light up if there are unacknowledged alarms.
Off.
OFF will light up if the unit is turned off.
MAINTENANCE
& SERVICE
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
17
Cleaning
For best possible performance and a long life, the AHU should be kept clean. Please see instructions below on how to clean fans and heat exchanger.
Changing filters
There are two filters in this AHU: exhaust air filter and supply air filter (fresh air). Both filters should be changed at least once a year, and more often if need be. Do not wash the filters, but exchange them for new ones. To buy new filters, please contact the local dealer in your country or order from www.rec-indovent.se
NOTE! The Temovex AHU must be fitted with the Temovex filters listed on page 1 of this manual. If the unit operates without filters, the performance will be affected adversely and fans and heat exchanger may be seriously damaged.
· Cut off the power.
· Open the unit door.
· Remove Cover plate.
· Remove EPP spacer by
pulling straight out.
· Remove the old outdoor air filter.
· Release the inner cover by turn the two hooks. Remove the cover. (Behind the cover is the exhaust air filter).
· Remove the old exhaust air filter.
· Clean accessible surfaces if necessary.
· Fit the new filters and cover in reverse order.
(The shortest filter first).
· Close the unit door.
· Turn on the power.
The unit operates even if the filters are dirty, but the performance would be less good; energy consumption increases and heat recovery decreases. To turn off/aknowledge filter alarm, see Ch 5.
Cleaning the fans
.
· Cut off the power.
· Open the unit door.
· Remove both upper and lower cover.
· Unfasten the elevator
device at the bottom of the front side of the unit, so that the heat exchanger package is released from the topunit. Loosen until it can not rotate more.
· Pull out the whole exchanger package.
· Unconnect the fan cables from
the PC board.
· The fan package is now standing on rails at both sides. Pull out the entire fan package.
· Loosen respectively fan holder and take out holder inkluding fan from the EPP package.
· Clean the impeller using a brush or compressed air.
· Clean accessible surfaces and ducts in the EPP package if necessary.
· Refit the fans in the fan package.
· Refit the fan package on the rails.
· Refit the exchanger package in the unit.
· Tighten the elevator device and be careful that
the grooves in the different EPP units will fit each other. Tighten until the grooves are completely together.
· Reconect the fan cables.
· Refit the covers.
· Close the unit door.
· Turn on the power.
NOTE! The fans must under no circumstances be cleaned under running water!.
Cleaning the heat exchanger
· Cut off the power.
· Open the unit door.
· Remove the cover.
· Unfasten the elevator device at
the bottom of the front side of the unit, so that the heat exchanger package is released from the topunit. Loosen until it can not rotate more.
· Pull out the whole exchanger package. Respectively exchanger is sealed in their EPP housing and can not be separated.
· Vacuum clean the exchangers from all sides.
· Refit the exchanger package in the unit.
· Tighten the elevator device and be careful that
the grooves in the different EPP units will fit each other. Tighten until the grooves are completely together.
· Refit the cover.
· Close the unit door.
· Turn on the power.
! !
MAINTENANCE
& SERVICE
Air Handling Unit Temovex Blue 4
REC Indovent AB, Box 37, SE
-
|
+46-31-675500
| www.rec
-
ind
ovent.se
18
Checking the condensate drain
· Open the unit door.
· Remove the
condens hose and make sure the hose is not blocked. Even make sure that the hose connection to the unit not is clogged.
· If the drain is clogged, try to remove the obstruction.If need be, call a plumber.
· Reconnect the hose.
· Close the unit door.
Cleaning the air diffusers
The building's air diffusers must be cleaned regularly in order to maintain correct ventilation. Use a dry cloth and/or a small brush to reach inside the opening of the diffuser. It can also be taken down if that makes cleaning easier. Use a duster or a dry cloth to remove possible dirt marks in the ceiling around the device. NOTE! The air diffuser's setting must not be changed. If taken down, each diffuser must be returned to its original place.
Cleaning the duct system
The exhaust air ducts - and sometimes the supply air ducts as well - may need cleaning at long intervals. Dust and dirt will deteriorate the capacity of the AHU if not removed.
Authorized ventilation cleaners should carry out the cleaning. However, you yourself can easily clean the part of the duct which is close to the air diffusers. Take down the diffuser. Use a vacuum cleaner or duster to clean the inner part of the duct as far as you can reach. Refit the diffuser, making sure the setting is not changed.
Checking the outdoor air intake
Once a year the outdoor air intake should be checked. Make sure it is not clogged by for example leaves, snow or ice.
Service
Service and repairs, beyond normal maintenance, should be carried out by professionals in the ventilation field, or - if electricity is involved - by an authorized electrician.
The electric panel must not be opened by other than authorized specialist.
Interferance with the AHU system may affect the warranty terms.
Use original spare parts only.
Disposal
Prevent accidents when the AHU is disposed of. Remove the cable from the wall socket and cut it as close to the unit as possible. Store and transport the waste unit lying down. Please leave the unit to be recycled where such facilities exist. Check with your local authority for recycling advice.
List of abbreviations
AHU air handling unit BP by-pass damper Comp. compensate(d) CP circulation pump DUC controller EA exhaust air El.heat. electric heating EXT extract air FRP freeze protection h hour Int. Internal KAVK condensation boiler mm:dd month:day
OD outdoor P protection per period pos. position RM room s second Setp. setpoint SA supply air Temp. temperature ULS outdoor air damper
DATE is shown in the format YY-MM-DD. TIME is shown in 24-hour format.
! ! !
19
Notes:
20
REC Indovent AB reserves the right to make alterations to specification and construction without prior notification.
REC Indovent AB
Box 37, SE-431 21 Mölndal, Sweden Visiting address: Kärragatan 2
Tel: +46 31 67 55 00 Fax: +46 31 87 58 45
www.rec-indovent.se Certified acc. to ISO 9001/14001
REC 15-11-19