RDZ EASY CLIMA User Manual

Regulation
EASY CLIMA
1.6
USER MANUAL
WARNINGS
SAFETY WARNINGS
Read this manual carefully before installation and/or use of the equipment and keep it in an accessible place.
The Manufacturer’s Technical Dept. is available at the numbers indicated on the back cover of this manual, for consultancy or particular technical requests.
• Only use original spare parts: failure to comply with this norm can make the warranty null and void.
CAUTION Installation and maintenance must only be performed by qualified staff; if this is not the case the warranty will become null and void
DISPOSAL
In accordance with the provisions of the following European directives 2011/65/EU, 2012/19/EU and 2003/108/EC, regarding reducing the use of hazardous substances in electrical and electronic equipment, in addition to waste disposal.
The symbol of the crossed-out wheely bin as shown on the product indicates that at the end of its useful life it must be disposed of separately from other waste. The user must therefore dispose of the above equipment at the end of its useful life at an appropriate centre for the collection of electronic and electro-technical waste, or return it to the dealer when purchasing a similar new device in terms of one to one. Proper waste collection leading to the subsequent recycling, treatment and environmentally friendly disposal of the equipment helps to avoid possible negative eects on the environment and on health and promotes the recycling of the materials of which the equipment is made up. Illegal disposal of the product by the user will lead to the application of penalties prescribed by current legislation in force.
3
INDEX
Num Description Page
WARNINGS 3
SAFETY WARNINGS 3
DISPOSAL 3
1 DESCRIPTION 5
GENERAL DESCRIPTION 5
DESCRIPTION OF DISPLAY 5
DESCRIPTION OF KEYS 7
2 SETTINGS 7
DATE AND TIME 7
USER SET-POINT 8
MAIN VALUES SHOWN ON THE DISPLAY 9
3 TIME BAND MANAGEMENT 10
EVENTS 10
PROFILES 10
PARAMETERS 10
ENABLING 12
PRIORITY 12
BLACK OUT 12
EXAMPLE OF TIME BANDS PROGRAMMING 13
4 EASY CLIMA CONTROLLER 16
DESCRIPTION 16
DESCRIPTION OF KEYS 16
DESCRIPTION OF SYMBOLS AND ICONS 16
DESCRIPTION OF DISPLAY 17
SET-POINT MODIFICATION 17
TIME BAND MANAGEMENT 17
5 DIAGNOSTICS 18
4
1 DESCRIPTION
GENERAL DESCRIPTION
The “local” user interface of Easy Clima device consists in:
• Display showing temperature/pressure, time, menu/parameters labels and parameter values.
• Icons to display machine status, the unit of measurement of the value displayed and the state of the resources.
• Keys for menu navigation, to set parameters, to silence the alarms, to enter programming, and for the activation of the direct functions.
The display of information and programming of the device via user interface are developed in menus with navigation using the four keys as described in the relevant section.
N.B. Easy Clima Controller can be coupled to hydraulic kits that
manage Low Temperature and/or High Temperature systems such as: Easy Clima Kit, LT only.
MTR Easy Clima both LT and HT. The manual refers to the complete conguration for HT/LT management
DISPLAY DESCRIPTION
The display is used to show the following information:
Main Display: value that can be set from parameter (as specied further on in this chapter).
Menu Navigation: the status folders, parameters, etc. can be accessed.
Within every folder, it is then possible to enter the sub-folders or parameters list
Alarms Display: the Alarm icon will switch on in the event of alarms. When accessing the Alarms menu, see the corresponding Alarm Code displayed in alternating mode.
If there are several alarms simultaneously, the one with the lowest index will be displayed: using the possible to display the alarm codes present at the same time. If the fundamental value is also in error mode, the Alarm icon will be displayed, along with the “Err” string or “Outr”.
DISPLAY KEY
1 3 42
8
7
5
6
and , keys it will be
Num Description
1 Alarm icon
2 Mode icon
3 Economy icon
4 Clock icon
5 Unit of measurement of the value displayed
6 Menu navigation icon
7 Resources icon
8 Values display
5
Display icons table
Icon Description On with xed light On ashing
Cooling icon SUMMER = ON (Cool)
Heating icon WINTER = ON (Heat)
Stand-by icon STAND-BY = ON
Dehumidication icon DEHUMIDIFIER = ON
Economy icon ECONOMY MODE = ON
Alarm icon One or more alarms active
Time band operating icon Time band operating enabled
Display values values display
°C
% R.H.
Menu icon The menu is shown in the display
Low temperature system solenoid valve icon
Low temperature system pump icon
Modulating mixing valve
3 point mixing valve
Chiller icon CHILLER = ON
Boiler icon BOILER = ON
the value displayed is a temperature value in °C
the value displayed is % relative humidity
Low temperature system solenoid valve = ON
Low temperature system pump = ON
VMIX completely OPEN (Pos.=100%) LED o = VMIX completely CLOSED (Pos.=0% )
VMIX in OPENING mode (indicates the opening “direction” of the servomotor, NOT the duration of the impulse towards the actuator)
POST-CIRCULATION in progress, after the COOLING or HEATING request has stopped
POST-CIRCULATION in progress, after the COOLING or HEATING request has stopped
VMIX in OPENING or CLOSURE mode, however in position dierent to 100% or 0% and in movement.
VMIX in CLOSING mode (indicates the closing “direction” of the servomotor, NOT the duration of the impulse towards the actuator)
High temperature system solenoid valve icon
High temperature system pump
It is possible to decide which value to display in normal operating conditions (not in menu navigation mode, not in the event of alarm signals) using the “SET/Info” key.
High temperature system solenoid valve = ON
High temperature system pump = ON
6
POST-CIRCULATION in progress, after the COOLING or HEATING request has stopped
POST-CIRCULATION in progress, after the COOLING or HEATING request has stopped
DESCRIPTION OF KEYS
Key Description
Short
SET key
ESC key
UP key
DOWN key
press
Long press From the main display, access is given to the selection of the fundamental value to be displayed.
Short press
Long press From main display, the operating STATUS is changed from ON to STAND-BY and vice versa.
Short press
Long press From main display, the operating condition is changed from heating to cooling and vice versa.
Short press
Long press
• From the main display, access is given to the user set-point menu.
• From the operational parameters menu, the SET key allows you to:
- access to the menu sub-folders
- access to the value of any parameter of one of the menu sub-folders
- conrm the parameter and/or output value
• With display o, the same is reactivated.
• Exit menus, list of parameters and parameter value (without saving the value) and go back to the previous level
• Scrolling the folders and parameters display upwards
• Parameter value increase
• From the main display, the room set adjustment is activated at the current time (heating or
cooling, comfort or economy) with ashing set value to be adjusted
• Scrolling the folders and parameters display downwards
• Parameter value decrease (if in parameter value modication mode)
• From the main display, the system date and time adjustment is activated.
From the main display, if enabled, the operating MODE from ON-Comfort to ON-Economy and vice versa.
+
access is given to the parameter and machine status menus folders.
2 SETTINGS
DATE AND TIME
This chapter describes the screenshots that can be accessed by a short press of the key.
Screenshot Description
1 2 3 4 5
N.B. in the event of a power cut lasting more than two days, the device loses the date and time setting. In this case, the values must be reset.
min
ora gior mese anno
Minutes set
Hour set
Day set
Month set
Year set
7
DATETIME MODIFICATION PROCEDURE
HOME
00
••••
59
00
••••
23
01
••••
31
USER SETPOINT
This chapter describes the screenshots that can be accessed by a short press of the key.
set
appears on the DISPLAY. Use the and keys to scroll the items in the menu. Use the Use the Use the Use the
N.B. on the basis of the type of data, the temperature symbol
First level Second level Description of the third level screenshot
1
key to conrm the selection and access the value of the item selected. and keys to adjust the value within the pre-dened elds. key to conrm the new value introduced. key, go back to the upper level until reaching the main display.
switches on (if it is a constant for example).
Comfort temperature set in winter mode
Economy temperature set in winter mode
Comfort temperature set in summer mode
Economy temperature set in summer mode
set
1 2 3 4
S_Hc S_hr S_cc S_cr
or humidity symbol switches on, or no symbol
01
••••
12
00
••••
99
5
S_um
2
cf
3
time
4
hour
5
all
ATTENTION: The set-point value will follow the trend of the room only in the presence of the Easy Clima Controller installed. If this is not the case, the set-point set can aect the system ow temperature. The humidity set-point will have no function if there is no humidity probe installed in the room.
1
1
1
2
mode
te00
ore
rst
Humidity set
Setting the ON or OFF operating mode to control the LT Area and the HT Area. The VALUE eld means “ON” or “OFF”. If “OFF” is set, the main display will show “OFF”.
Setting TIME BAND or NORMAL operation. The VALUE eld means “ON” or “OFF”. If “ON” is set, the symbol switches on
Display of the operating hours of the LT Area Pump, the timer is shown on the DISPLAY up to a maximum of 9999 hours.
RESET procedure: “OFF” is shown, which can be switched to “ON” using the key.At this point, pressing the
to “rst”.
Display of alarm codes in progress. See relevant paragraph.
key conrms the decision to reset the timer and then goes back
8
.....
.....
.....
.....
.....
SETPOINT MODIFICATION PROCEDURE
HOME
.....
19.9 °C
20.0 °C
20.1 °C
MAIN VALUES SHOWN ON THE DISPLAY
In this chapter, select the data that will be displayed in the main screenshot and vary between the options described in the table below.
Access the menu with a long press of the
• by pressing the
• by pressing the
• by pressing the
/ keys, scroll the main values displayed key, exit the menu key, the value is transferred into the main screenshot and the menu is exited
First level Description
The LT area room temperature value will start to ash after a few seconds.
1
2
3
4
amb
est
umid
mand
If the room probe is congured but not connected or in short circuit conditions, ashing will be shown on the DISPLAY. If the room probe IS NOT congured, this screenshot will not be displayed
The external temperature value will start to ash after a few seconds. If the external probe is congured but not connected or in short circuit conditions, ashing will be shown
Outr
on the DISPLAY.
If the external probe IS NOT congured, this screenshot will not be displayed.
The LT area room humidity value will start to ash after a few seconds. If the room probe is congured but not connected or in short circuit conditions, ashing will be shown on the DISPLAY. If the humidity sensor IS NOT congured, this screenshot will not be displayed
The ow temperature value will start to ash after a few seconds. If the ow probe is congured but not connected or in short circuit conditions, ashing will be shown on the DISPLAY.
key, and then:
.....
16.9 °C
17.0 °C
17.1 °C
.....
24.9 °C
25.0 °C
25.1 °C
.....
27.9 °C
28.0 °C
28.1 °C
.....
54.9 °C
55.0 °C
55.1 °C
Outr
Outr
err
250
5
6
7
8 9
10
setm
pos
ora
Gior mese
anno
After a few seconds the Set-Point calculated for the Area mixed system ow will start to ash.
After a few seconds the current value of the position from 0% to 100% of the area 1 mixing valve starts to ash.
After a few seconds the time in progress is displayed in hours and minutes (e.g. 12:00) in a permanent way, with the ashing.
After a few seconds the value of the day of the month in progress will be displayed (from 1 to 31)
After a few seconds the value of the month in progress will be displayed.
After a few seconds the value of the year in progress will be displayed. The last two characters indicating the year are displayed (e.g. for 2011 will be displayed 11).
9
3 TIME BAND MANAGEMENT
For various reasons, mainly linked to the necessity to save energy, it is useful to be able to dierentiate device operation into time bands. The “time band” control is only relative to the LT Area system.
The device allows time band management, with the division of each day of the week into time periods (time bands) in which the LT system controller can vary, on the basis of the program performed, from Comfort to Economy operating mode or in Stand-by.
EVENTS
The “event” concept is introduced to identify the various time bands. For every event:
• The starting time (in hours and minutes)
• The operating mode that is activated (Comfort, Economy or Stand By
PROFILES
To distribute the various events per day of the week, the “prole” concept is introduced. For every prole:
• The prole number (up to a maximum of 3 dierent proles can be dened)
• The distribution of the events within every prole, up to a maximum of 4 events for every prole
The prole to be associated can be specied for every day of the week. The default association will be “prole 1”.
Note: as the events available for every prole are HOWEVER 4, to disable an event (i.e. to reduce the number of time bands for a specic prole), it will be sucient to give them the same start point and the same operating mode as the previous event.
PARAMETERS
To access the parameters modication described in the table below, follow the procedure given:
HOME
Mask Description U.M. Min Max Note Default
Enabling of time band management Num On O O
Prole selection, Monday Num 1 3
Prole selection, Tuesday Num 1 3 1
Prole selection, Wednesday Num 1 3 1
Prole selection, Thursday Num 1 3 1
Prole selection, Friday Num 1 3 1
Prole selection, Saturday Num 1 3 2
Prole selection, Sunday Num 1 3 2
1 = Prole 1 2 = Prole 2 3 = Prole 3
1
WEEKLY
PROGRAMMING
te00 te01
te02 te03 te04 te05 te06 te07
N.B. On Easy Clima Controller display TE01, TE02, ... TE07 screenshots are called MON, TUE, WED, THU, FRI, SAT, SUN
10
te10 te11
te12
Event 1 start hours, prole 1 hh 0 23 6
Event 1 start minutes, prole 1 mm 0 59 30
0 = Comfort
Operating mode from event 1, prole 1 Num 0 2
1 = Economy 2 = Stand by
0
te17 te18
te19
te24 te25
PROFILE 1
te26
te31 te32
te33
te38 te39
te40
Event 2 start hours, prole 1 hh 0 23 8
Event 2 start minutes, prole 1 mm 0 59 30
0 = Comfort
Operating mode from event 2, prole 1 Num 0 2
Event 3 start hours, prole 1 hh 0 23 17
Event 3 start minutes, prole 1 mm 0 59 30
Operating mode from event 3, prole 1 Num 0 2
Event 4 start hours, prole 1 hh 0 23 22
Event 4 start minutes, prole 1 mm 0 59 30
Operating mode from event 4, prole 1 Num 0 2
Event 1 start hours, prole 2 hh 0 23 7
Event 1 start minutes, prole 2 mm 0 59 30
Operating mode from event 1, prole 2 Num 0 2
1 = Economy 2 = Stand by
0 = Comfort 1 = Economy 2 = Stand by
0 = Comfort 1 = Economy 2 = Stand by
0 = Comfort 1 = Economy 2 = Stand by
1
0
2
0
te45 te46
te47
te52 te53
PROFILE 2
te54
te59 te60
te61
Event 2 start hours, prole 2 hh 0 23 13
Event 2 start minutes, prole 2 mm 0 59 30
0 = Comfort
Operating mode from event 2, prole 2 Num 0 2
Event 3 start hours, prole 2 hh 0 23 17
Event 3 start minutes, prole 2 mm 0 59 30
Operating mode from event 3, prole 2 Num 0 2
Event 4 start hours, prole 2 hh 0 23 23
Event 4 start minutes, prole 2 mm 0 59 30
Operating mode from event 4, prole 2 Num 0 2
1 = Economy 2 = Stand by
0 = Comfort 1 = Economy 2 = Stand by
0 = Comfort 1 = Economy 2 = Stand by
1
0
2
11
te66
Event 1 start hours, prole 3 hh 0 23 0
te67
te68
te73 te74
te75
te80 te81
PROFILE 3
te82
te87 te88
te89
Event 1 start minutes, prole 3 mm 0 59 0
0 = Comfort
Operating mode from event 1, prole 3 Num 0 2
Event 2 start hours, prole 3 hh 0 23 0
Event 2 start minutes, prole 3 mm 0 59 0
Operating mode from event 2, prole 3 Num 0 2
Event 3 start hours, prole 3 hh 0 23 0
Event 3 start minutes, prole 3 mm 0 59 0
Operating mode from event 3, prole 3 Num 0 2
Event 4 start hours, prole 3 hh 0 23 0
Event 4 start minutes, prole 3 mm 0 59 0
Operating mode from event 4, prole 3 Num 0 2
1 = Economy 2 = Stand by
0 = Comfort 1 = Economy 2 = Stand by
0 = Comfort 1 = Economy 2 = Stand by
0 = Comfort 1 = Economy 2 = Stand by
0
0
0
0
ENABLING
“Time band” operation can be activated with the tE00 time band management enabling parameter. Moreover, the RTC (internal clock) must be present and enabled to operate (it must not be faulty and/or not regulated, for further details refer to the specic alarms). The “Time band” operating mode only aects the operating mode change from ON-Comfort to STAND-BY, from ON-Economy to STAND-BY, from ON-Comfort to ON-Economy, and vice versa. The mode change procedure always takes place with the rules (times, etc.) envisioned by the basic adjustment. The time band management is an exclusive function of the parameters set.
PRIORITY
In the “time band” management ambit, the change events mode has the same priority as the local change mode via keyboard and serial port, clearly limited to ON-Comfort, ON-Economy and STAND-BY. Refer to that stated in the “Selection of the operating mode” (priority level 4). For example: if a change intervenes in manual mode from keyboard, which implements an ON-Economy with time band management enabled, which managed an ON-Comfort, the eect of this manual ON-Economy operation will have immediate priority, but will ONLY remain valid until the successive event envisioned by the “time band” management, which will then retake control of the operating mode. The events all have the same priority level: the controller behaves according to the last event occurring. In the event of simultaneous events, the one with the lowest index is performed (1,2,3 or 4).
BLACK OUT
1. Time band management DISABLED: when the black-out is restored, the device behaves with mode already dened.
2. Time band management ENABLED: when black-out is restored, the device assumes the status of the last event occurring
before the black-out.
12
EXAMPLE OF TIME BANDS PROGRAMMING
Below nd and example of the structure of prole 1 containing 4 events:
• Event 1 = start time 06.30 – ON-Comfort operating mode
• Event 2 = start time 09.30 – ON-Economy operating mode
• Event 3 = start time 06.30 – ON-Comfort operating mode
• Event 4 = start time 22.00 – Stand-By operating mode
SYSTEM OPERATING WITH PROFILE 1 GRAPHICS
20 °C
19 °C
18 °C
Economy
17 °C
Heating WINTERCooling SUMMER
Stand By
ON
Comfort
ON
Economy
Temperature
ON
Comfort
Stand By
Time
00:00 06:00 12:00 18:00 24:00
Economy
28 °C
27 °C
26 °C
25 °C
Stand By
00:00 06:00 12:00 18:00 24:00
60 %
55 %
ON
Comfort
ON
Economy
Temperature
ON
Comfort
Relative humidity
Stand By
Time
50 %
Stand By Stand By
ON Controllo umidità
Time
00:00 06:00 12:00 18:00 24:00
N.B. Dehumidication is only enabled in the summer. Its operation is forced in Stand-By (dehumidier o ) in concomitance with the stand-by event set. In the other cases, dehumidication is controlled with the set in the
13
s_um
parameter.
WEEKLY MANAGEMENT TABLE
PROGRAMMING
TIME SLOT AND
Below nd an assignment example of the 3 prole in the days of the week:
Screenshot Day Prole
te01 te02 te03 te04 te05 te06 te07
TIME BAND PROGRAMMING PROCEDURE
Below nd and example of the structure of prole 2 containing 4 events:
• Event 1 = start time 06.30 – ON-Comfort operating mode
• Event 2 = start time 09.30 – ON-Economy operating mode
• Event 3 = start time 06.30 – ON-Comfort operating mode
• Event 4 = start time 22.00 – Stand-By operating mode
Below nd and example of the structure of prole 3 containing 4 events:
• Event 1 = start time 06.30 – ON-Comfort operating mode
• Event 2 = start time 22.00 – Stand-By operating mode events 3 and 4 will be programmed as the event 2 so that these are annulled.
Monday 1
Tuesday 1
Wednesday 1
Thursday 1
Friday 1
Saturday 2
Sunday 3
ENABLEMENT
WEEKLY
HOME
14
PROFILE 1PROFILE 2PROFILE 3
15
4 EASY CLIMA CONTROLLER
DESCRIPTION
Room interface from Easy Clima Controller is an optional device that can be coupled to Easy Clima controller. The interface allows you to remote control the information on the Easy Clima controller in the room. Fitted with temperature and humidity probe, it allows to control the winter temperature, the summer temperature and dehumidication.
DESCRIPTION OF KEYS
Short press keys table*
Key Description
Modication of the temperature set-point
Modication of the temperature set-point
set
* Operation from main display, for the use from menu, see the
successive user paragraphs
Set-point modication
Long press keys table
Key Description
( / )
( )
set
esc
( )
Key combination table
Key Description
set
esc
+
DESCRIPTION OF SYMBOLS AND ICONS
Summary table of the symbols and icons
Icon Description Icon Description
Cooling icon Menu icon
Heating icon Low temperature system solenoid valve icon
Season change
Economy/Comfort
Set main display
Stand by/On
• Time Band programming
• Parameters programming (see technical manual)
Stand-by icon Low temperature system pump icon
Dehumidication icon Modulating mixing valve
Economy icon Chiller icon
Alarm icon Boiler icon
Time band operating icon High temperature system solenoid valve icon
°C High temperature system pump
% R.H.
16
DESCRIPTION OF DISPLAY
1
SETPOINT MODIFICATION
Label Parameters
First level Second level Description
1 2 3 4 5
6
7
8
9
10
S_Hc S_hr S_cc S_cr S_um
mode
time
hour
orol
all
1 2 3 4 5
Hour
Min gior Mese Anno
Comfort temperature set in winter mode
Economy temperature set in winter mode
Comfort temperature set in summer mode
Economy temperature set in summer mode
Humidity set
Setting the ON or OFF operating mode to control the LT Area and the HT Area. The VALUE eld means “ON” or “OFF”. If “OFF” is set, the main display will show “OFF”.
Setting TIME BAND or NORMAL operation. The VALUE eld means “ON” or “OFF”. If ON is set, the Display of the operating hours of the LT Area Pump, the timer is shown on the DISPLAY up
to a maximum of 9999 hours.
Hour set
Minutes set
Day set
Month set
Year set
Display of alarm codes in progress. See relevant paragraph.
2
symbol switches on
Num Description
small display for showing:
• time (hh: mm)
1
• label menu
• label parameters
• label alarms large display for showing:
• temperature
2
• parameters folders
• parameters value
TIME BAND MANAGEMENT
“Time band” operation by Easy Clima controller can be activated with the “time” band management enabling parameter.
HOME
par
For management of the time bands follow the instructions described below to access the parameters and ”3 Time Band Management” chapter for all details regarding programming.
All orol hour time
ON
OFF
HOME
17
5 DIAGNOSTICS
The diagnostics consists in the management of everything that is associated to the alarms. For Easy Clima device, all alarms have “automatic rearm”.
Easy Clima Control unit Easy Clima Controller
HOME HOME
par par
Below nd the list of various alarm codes that appear and their diagnostic meaning:
Code Alarm Alarm management Digital/Analogue
Er00 Er01 Er02 Er03
Er04
Er04
Er05
Er06
Er07
Er08
Er09
Er46
General alarm All outputs are switched o Digital
LT Flow Temperature Probe Error All outputs are switched o Analogue
External Temperature Probe Error Operation without Ext. probe Analogue
Area 1 Room Temperature Probe Error Operation without Env. probe Analogue
Area 1 Room Humidity Probe Error from AIL2
Area 1 Room Humidity Probe Error from AIL3 Operating only with humidistat in DIL5 Analogue
Clock fault error
Exceeding humidity maximum threshold in progress
Automatic stand-by in progress Anti-freeze management only Digital
LT system temperature below lower SAFETY limit, parameter
LT system higher temperature SAFETY limit exceeded, parameter
Clock to adjust error
tr31
tr30
Operation only with humidistat in DIL5 or with 4-20 mA probe in AIL3
Operating without automatism of the time bands (reset date/time)
Dehumidier switch-o with Chiller and system (HT or LT ) remaining in operating mode
Switch-o of all LT system loads. Manual rearm in main page with long pressure of the "ESC" key until the error disappears
Switch-o of all LT system loads. Manual rearm in main page with long pressure of the "ESC" key until the error disappears
Operating without automatism of the time bands
Analogue
Digital
Digital
Digital
Digital
Digital
18
bit.ly/rdzwebsite
05/2016
9120206.03