RCS TU16 Installation And Operation Manual

Model TU16
UPB Thermostat
INSTALLATION AND OPERATION MANUAL
Rev P HVAC Control Unit
DCN: 141-01435
Rev 01
8/30/06
This revision of the document applies to the following part numbers and revisions or later.
*** IMPORTANT NOTICE ***
DO NOT USE THIS PRODUCT FOR BUILDING FREEZE PROTECTION! YOU ARE ADVISED TO
INSTALL A MECHANICAL FREEZE PROTECTION DEVICE FOR THIS PURPOSE.
Product Rev Part No Firmware
TU16-485 Thermostat P 001-01435-01 TS16 Wall Display Unit G 001-00910-13 TS16v350 HFUP HVAC Control Unit P 001-01435-03 HFUP0102
RCS Residential Control Systems Inc.
DCN: 141-01435-01 8/30/06
2
TU16 Operation
The TU16 thermostat provides the latest technology in a full-featured universal thermostat with UPB powerline communications. The TU16 has many unique features including:
Separate Heating and Cooling setpoints
Multistage HVAC systems support
Wall Display Unit setting of
o Unit ID o F/C temperature display mode o Sensor calibration (internal and remotes)
Automatic Remote Sensor detection
AutoSend Mode for easy network communication
Enhanced two way UPB protocol
The TU16 thermostat consists of two parts, a Wall Display Unit (WDU) and a HVAC Control Unit. The Wall Display Unit provides users functions like a traditional thermostat and connects to the Control Unit by a 4 wire cable. The Control Unit connects at the HVAC system using the standard thermostat connections and provides the thermostatic temperature control of the system. The Control Unit also has the UPB powerline network connection via a UPB CIM or PIM powerline interface module.
The TU16 has separate heating and cooling setpoints. The display shows the setpoint of the current operating mode (in Auto mode, the system keeps track of the current operating mode of the last call, either heating or cooling).
In addition to the universal Standard or Heat Pump HVAC systems support, the TU16 has multistage heating/cooling system outputs. The control unit can support 2 stages of heating and cooling for Standard systems. It supports 3 stages of heating and 2 stages of cooling for Heat Pump systems.
The TU16 has a convenient setup mode from the Wall Display Unit. You can set the network Unit ID, F or C display mode and easily calibrate the internal and all attached remote sensors.
The TU16 has automatic detection and setup of remote temperature sensors. Remote sensors have address settings that, when detected by the TU16, will be used for specific functions, such as, in lieu of the internal sensor, averaging with other sensors.
UPB Communications: the TU16 provides a robust two way communication protocol that allows for full control and monitoring of the thermostat.
The thermostat temperature, setpoints and mode can be monitored or changed via the UPB network. In addition, the HVAC system operation modes and even relay status can also be accessed from the network.
The UPB Network ID for the thermostat can be set via the Wall Display Unit. The Network address and other configuration data can be read and set via network commands.
The TU16 can be used in a polled network or can be set to AutoSend mode that will transmit changes in thermostat data as it occurs.
DCN: 141-01435-01 8/30/06
3
TS16 Wall Display Unit
The TS16 Wall Display Unit has a LCD display and control buttons for changing the setpoint, system operating mode and manual fan mode. The WDU also has an internal temperature sensor. The display serves as a common display for many functions. It normally shows the current room temperature but switches to show setpoint, mode or other functions when buttons are pushed. Two on-screen indicators show the state of the manual fan and setback mode.
Any changes, such as the temperature or control button operations at the WDU are sent to the HVAC Control Unit. In turn, the Control unit sends changes in setpoint or modes from the serial communications network to the WDU. When updates are received by the WDU, they are displayed on the LCD display for 3 seconds and then the display returns to the current room temperature.
LCD Display
The LCD display is a two digit multifunction display that normally shows the current room temperature. It has a continuous backlight for easy viewing anytime. Whenever any of the control buttons are pushed, the LCD display will change to show that function’s current status. The LCD display will stay in the new display mode as long as buttons are being pushed. After 3 seconds of no activity, the display will change back to show current temperature.
The right decimal point on the LCD display will turn on whenever manual fan is ON. The left decimal point will flash whenever the setback mode is ON.
Remote changes in setpoint or modes that are received by the WDU from the Control Unit will cause the LCD display to switch and display the updated data for 3 seconds and then return to room temperature.
Temperature Display
The WDU will normally display the room temperature from the internal digital temperature sensor or a remote sensor if attached.
The WDU will display temperatures from -9°F/C to 127°F/C. Temperatures less than 0° will be displayed down to -9 ° as negative numbers. Temperatures below –9 will also be displayed but no minus sign can be displayed. Temps over 100° will be displayed without the leading 1 (ex: 102 will be displayed as 02°.)
Outside Temperature Display
If you attached a remote temperature sensor to the WDU that is set to remote sensor address “4”, you can view this outside temperature by pressing the UP and DOWN buttons simultaneously. Outside temperature data may also be sent to the WDU via network commands and viewed this way. Note if you press the UP/DOWN buttons and no temperature information is available, the display will show “- -“.
.7.5
MODE
FAN
Manual Fan On Indicator
LCD DISPLAY
Shows current temp normally.
Shows setpoint or mode
when buttons pushed.
Setback Mode On Indicator
TS16 WDU
Setpoint Increase Button
Setpoint Decrease Button
System Mode Button Manual Fan Button
DCN: 141-01435-01 8/30/06
4
Control Buttons
The UP and DOWN buttons control the heating or cooling setpoint temperature. To View The Current Setpoint: Push either the UP or DOWN buttons once will cause the LCD display to
change to show the current setpoint temperature (but won’t change it). To Change The Setpoint: With the setpoint displayed as above, push the UP button to increase the
setpoint temperature by one degree or push the DOWN button to decrease the setpoint by one degree. Pushing and holding a button down will cause the setpoint to continuously ramp up/down until the button is released. After 3 seconds of no activity, the LCD display will change back to show the current room temperature and the new setpoint value will be sent to the Control Unit.
NOTE: You cannot change the setpoint when in the OFF mode.
Setpoint Display
The displayed setpoint shows the setpoint of the current operating mode (heating or cooling) of the system. If you change modes, the setpoint displayed will change to the new operating mode setpoint.
If you set the mode to AUTO mode, the setpoint displayed will be the current operating mode of the system, either heating or cooling. This will change if the operating mode changes automatically.
MODE The MODE button sets the HVAC system Heating or Cooling mode. To View The Current Mode: Push the MODE button once and the LCD display will change to show the
current mode. To Change The Mode: While the mode is being displayed, pushing the MODE button again will go to the
next mode. The system mode cycles from Off to Heat to Cool to Auto and back to Off again with each push of the MODE button. Once you stop pushing the button (for 3 seconds) the new mode will take affect and the display will change back to room temperature.
When Heat Pump HVAC system type is selected on the Control Unit dipswitch, an additional system mode of “EH”, or Emergency Heat, is included in the TS16 mode selections. EH is used when Heat Pump compressor failure requires the use of Auxiliary Heat (heat strips) for primary heating. When EH mode is selected, the display will alternate between current temperature and “EH” to remind you that the EH mode has been selected.
FAN
The FAN button controls the HVAC system’s manual fan mode. Pushing the FAN button once will turn the fan ON and pushing it again will turn the fan to the AUTO mode (which is OFF unless the fan is automatically turned ON by the heating or cooling operation ). The decimal point in the middle of the two digits on the LCD display will come on when the manual fan is ON. Changes in the fan mode will be sent to the HVAC Control Unit.
Setpoint UP and DOWN Buttons
MODE Button
FAN Button
DCN: 141-01435-01 8/30/06
5
System Setup Mode
The TU16 has a setup mode to allow the user to set the following functions from the WDU:
UPB Network Device ID address
F/C mode
Sensor Calibration
Entering into the setup mode.
Enter the setup mode by the following procedure:
1. First press and hold the Mode button
2. Simultaneously press the Fan button.
3. The display will change to show “SU”.
4. Release all buttons.
5. The display will change to show the setup menu, starting with “Ad” (address)
6. Select what setup function you want to change or view by pressing the Mode button to cycle through the menu options:
“Ad” = UPB Network ID address “FC” = Fahrenheit or Celsius mode “C1” = Calibrate Internal Sensor (or Remote Sensor address 1 if attached) and if additional external sensors are attached they will appear also:
“C2” = if Remote Sensor address 2 attached
Viewing the Network ID Address
When you first enter the setup mode, the first menu selection displayed on the LCD display is “Ad”. To view the current address setting, press the UP or DOWN button once. With the current address displayed, you can either change the setting or exit by pressing the mode button or wait for the screen to time out.
Changing the Network Address. While the current address is being displayed, as above, use the UP/Down buttons to set the new network address desired, 1 to 254 (default set to 200). Since the TS16 WDU has only two digits of display, the decimal point between the digits is used to indicate when you are in the 100 to199 range (shown as 0.0 to 9.9). The decimal point to the left of the digits is used to indicate addresses in the 200 to 254 range (shown as .00 to .54). To exit press the mode button again or wait for the screen to time out and return to the normal thermostat temperature display.
Setting the Fahrenheit or Celsius mode
In the setup mode, press the mode button to select “FC” mode. The TU16 is default set to F mode. To change the degree mode, press the UP/DOWN buttons to select F or C as desired. To exit press mode again to move another setup mode or wait for the screen to time out and return to the normal thermostat temperature display.
Setting the Sensor Calibration
In the setup mode, press the mode button to display the sensor calibration address, “C1”, to be calibrated. ”C1” is the internal sensor and normally that is all that will be available to calibrate unless external remote sensors are attached. These will show up as “C2”, and “C4” in the menu selection, if present. With the desired sensor address displayed, press the UP/DOWN buttons to change the sensor calibration to the desired temperature. See calibration explanation below.
Exit setup mode
When you are done making changes and no button is pressed for 5 seconds, the display will automatically exit setup mode and return to the thermostat mode and current temperature display.
Temperature Display Calibration
The TS16 WDU has the capability for the user to adjust the temperature display calibration of the internal sensor as well as all attached remote sensors from the WDU in the setup mode.
Normally the TS16, with no attached remote sensors, will only show the internal sensor as “C1” in the calibration setup menu. The TS16 can have additional remote sensors attached. These are addressed as remote sensors 1 and 2. If they are detected by the TS16, they will show up in the calibration menu as
DCN: 141-01435-01 8/30/06
6
additional sensors to calibrate as C1 and C2. Note that if remote sensor with address 1 is attached it replaces the internal sensor and becomes the “C1” sensor. See the remote sensor section for more details.
When the desired sensor is selected in the setup menu, you can adjust its displayed temperature calibration up or down 7 degrees by pressing the UP/DOWN buttons.
The calibration menu selections are: C1 = calibrate internal sensor or remote sensor address 1 if attached C2 = calibrate remote sensor address 2 (only shows up in menu if attached)
Remote Sensors
The TS16 Wall Display Unit has a remote sensor terminal block, J2, on the base for connection of a remote temperature sensor. Remote sensors have an address that can be set to 1, 2, or 4. Without any remote sensor attached, the WDU uses the internal sensor for the current temperature information. When a remote sensor is attached, the WDU will detect it automatically and will use the remote sensor(s) according to its address selection. Modes of operation are as follows:
Address 1: Use this remote sensor instead of the internal sensor. (becomes C1 in the calibration setup). Address 2: Average remote sensor 2 with internal sensor or sensor address 1 if attached. (C2)
Table of Remote Sensor Functions and Sensor Addresses
Function Remote Addr 1 Remote Addr 2
Use internal sensor only No Yes Used as remote sensor only Yes No Average internal and one remote No Yes Average two remotes (only 2) Optional with A2 Yes with A1
When averaging sensors are used, the average temperature is displayed on the WDU and reported to the HVAC control unit. You cannot view an individual remote averaging sensor temperatures as the main thermostat display or report individual sensor temperatures on the communication port. However, you can check the individual sensor temperatures by going to the calibration setup menu and selecting the sensor address. You can view the outside temperature by pressing both the UP/DOWN buttons simultaneously.
Display Lock
The TU16 WDU control buttons can be locked to prevent unauthorized changes in system operation from the WDU. The display lock/unlock state can only be set by the “DL” network command. See the Serial Protocol Manual for details on this command.
“CF” or “SF” Error Displays
If the WDU is not properly wired or if communications to the Control Unit is interrupted, the LCD display will display “CF” to denote Communication Failure. Momentary display of “CF” caused by bad or lost data, will clear automatically when data communication is restored.
If the “CF” continues to be displayed, check wiring for problems. A continuous “CF” display may indicate a problem with the Control Unit or the WDU itself.
An “SF” display indicates a temperature sensor failure. If this is displayed continuously, the sensor is failing to respond and must be replaced. This can also be displayed when attempting to view the outside temperature if this sensor has failed or been disconnected.
Loading...
+ 14 hidden pages