RCS TS40 Installation And Operation Manual

Page 1
RCS
Model TS40
Wall Display Unit
Installation and Operation Manual
DCN: 141-01060
Date: 1/01/05
Applies to these TS40 Revisions or later Model Part Number Firmware Version TS40 WDU 001-01060-16 3.06.4
Residential Control Systems Inc.
Page 2
TS40 OPERATION
y
The TS40 Wall Display Unit provides the typical thermostat user interface for RCS thermostats and HVAC Zone Controllers.
The Wall Display Unit looks and functions like a traditional thermostat. The TS40 can be a part of a TR40 thermostat or used as one of the zone WDUs when connected to a ZCV2/4/6 zone control units.
The TS40 has a graphical LCD display for temperature, setpoints and mode information. It has 6 pushbuttons for control of thermostat functions and an internal temperature sensor
The WDU connects to a HVAC Control Unit (CU) by a 4 wire cable. The Control Unit connects to the HVAC system in place of a standard thermostat. Together, the WDU/CU combination makes up a complete thermostat or zone system The communications port on the Control Unit allows full remote control of the system.
The TS40 WDU can be used with up to 4 RS15 remote temperature sensors for remote temperature sensing and/or averaging temperature sensors.
The TS40 has a comprehensive on-screen setup mode that allows virtually all of the thermostat operating parameters to viewed and changed.
TS40 Wall Display Unit
The WDU has a backlit LCD graphical display, control buttons, LEDs and a digital temperature sensor. The WDU can display multiple screens. In the main thermostat screen, it shows the current temperature, setpoint, mode and manual fan mode, time, outside temperature and other information.
Any changes in temperature, or control button operations, are transmitted to the Control Unit. Updates received from the network by the Control Unit are sent up and displayed on the TS40.
Indicator LEDs
On-screen
dynamic labels
Other standard screens are selected by the Menu button and include: Messages, Schedules, User Settings, and Thermostat Info. Others may be present and selectable from the menu button in special versions of the WDU.
The TS40’s LCD features a backlit display for low light and night visibility. It can be set to remain on constant or to turn out after a 20-45 second delay .
TS40 WDU Thermostat Screen
10:25
s Off
S Econ Run No Msg
MENU
Function Control Buttons
Outside 60
75
OFF
MODE
AUTO
FAN
RUN
76 H
74 C
Setpoint
Up/Down
Buttons
Large Graphical
LCD Screen
DCN: 141-01060-13 1/05 TS40 Manual
2
Page 3
TS40 OPERATION
Wall display Unit Control Buttons
All 6 buttons on the TS40 Wall Display Unit are “Soft Keys” meaning that they change functions when you change screens. The function of the buttons is defined by “on-screen labels” that are dynamic and change when you change screens. The following are definitions for the buttons for the main “Thermostat screen” and their primary mode of operation. Other screens and their button operations are defined in following sections.
Wall Display Unit LEDs
The TR40 has four LED’s that display various status information. The LEDs have dynamic “on-screen” labels that can change with the screen being displayed.
Wall Display Unit “Screens”
One of the unique features of the TS40 WDU graphical display is the ability to have multiple display screens. In addition to a main thermostat screen, menus and other control screens for special functions are provided. This makes an intuitive and easy to use “user interface”. It allows the many functions of the TS40 to be easily navigated.
You move to other screens by pressing the Menu button from the main thermostat screen. A new Main Menu “screen” will be displayed with a list of menu functions. When a menu item is selected, a new “screen” will be displayed for that function. Refer to the individual screen descriptions that follow for details on navigating each screen.
The Minimized Main Thermostat Screen
The main thermostat screen will go to a “minimized” screen after a timeout period. This presents a simple uncluttered display of the current room temperature and outside temperature (if an OT sensor is attached).
Pressing any button causes the full Main Thermostat screen to be restored and displayed.
Screen Timeouts
When you menu to other screens, you have the option of exiting those screens to return to the main thermostat screen or just waiting until the automatic screen timeout occurs that will return the display to the main thermostat screen.
The main thermostat screen normally reverts to the minimized screen after 30 seconds. This can be adjusted from 15 to 127 seconds in the User Settings Menu under Screen Timeout. You can also set the timeout period to “0”. In this case the Main Thermostat screen will NEVER timeout and revert to the minimized screen.
DCN: 141-01060-13 1/05 TS40 Manual
3
Page 4
Main Thermostat Screen
y
The main thermostat screen is the default display screen and is the screen that is normally displayed on the Wall Display Unit. It will revert to a minimized screen after 30 seconds of display, if this feature is set.
Temperature Display
The WDU will normally display the current temperature from the internal digital temperature sensor or a remote sensor. The sensors have an accuracy of +/- 1°F(+/- .5°C). The WDU will display temperatures from -63°F to 191°F. NOTE: If averaging remote sensors are attached, the display will show the
average temperature of ALL the sensors.
Setpoint Display
The heating and cooling setpoints are displayed next to the Setpoint Up/Down buttons. In the HEAT mode, the Up/Down buttons change the heat setpoint. In the COOL mode, they change the cooling setpoint. When in AUTO mode, the buttons change the last call’s heating or cooling setpoint. Note that the setpoints will “push” each other if they are adjusted to get within the minimum Heat/Cool separation (delta T) setting. This is normally 4 degrees.
Clock Display
The current time is displayed in the upper left corner of the main screen. Set the clock from the Users Settings menu.
Outside Temperature Display
The outside temperature is displayed in the top center of the main screen. OT is only displayed if outside temperature information has been sent to the thermostat from the network or a remote temperature sensor set to address 4 is connected to the WDU.
Main Thermostat Screen Buttons UP and DOWN Buttons
The UP and DOWN buttons control the setpoint temperature. Pushing the UP button will increment the setpoint value by one degree and conversely, pushing the Down button will decrement the setpoint one degree. Pushing and holding a button down will cause the setpoint to continuously change until the button is released.
DCN: 141-01060-13 1/05 TS40 Manual
10:25 Outside 60
S
s Off Econ Run No Msg
MENU
75
OFF
MODE
4
AUTO
FAN
76 H
74 C
RUN
Page 5
Main Thermostat Screen
The WDU displays both the current heating and cooling setpoints. The Up and Down buttons will change the setpoint of the current MODE (heating or cooling). When in the AUTO MODE, the buttons will change the setpoint of the last call’s mode – heating or cooling.
Heating setpoints can be set from 40 to 106 degrees. (5 to 40 deg C) Cooling setpoints can be set from 44 to 110 degrees. (6 to 44 deg C)
The high setpoints are intended for use with Pool/Spa heating applications. High and Low setpoint limits can be set in the Installer Settings menu.
Setpoint Deadband and Push
You cannot lower the cooling setpoint below the heating setpoint or raise the heating setpoint above the cooling setpoint. There is a 4 deg deadband between heating and cooling setpoints. If you try to set the setpoints closer than 4 degrees, the setpoints will “push” each other to maintain the 4 degree separation. Changing the heating setpoint up will push the cooling setpoint. Setting the cooling setpoint down will push the heating setpoint.
Main Thermostat Screen MENU Button
The Menu button changes the screen display to the MAIN MENU screen which show what other functions are available on the Thermostat. These are dynamic and can change with the version of the thermostat you have, but the standard ones include:
Main Thermostat Screen
Menu Button
Main Menu Screen
Messages Schedules User Settings Thermostat Info
MENU
Main Thermostat Screen MODE Button
The MODE button controls the HVAC system mode. The current mode selected is displayed above the button. Pushing the MODE button will cause the mode and display to change to the next mode. The system mode cycles from Off to Heat to Cool to Auto and back to Off again with each push of the MODE button. When the HVAC system type is set to Heat Pump, the mode selection will include EH for Emergency Heat mode.
Mode Button
Off Heat Cool Auto EH (if HP system type)
Off Mode: System is off. No heating or cooling will come on.
DCN: 141-01060-13 1/05 TS40 Manual
MENU
OFF
MODE
OFF
MODE
5
AUTO
FAN
AUTO
FAN
RUN
RUN
Page 6
Main Thermostat Screen
Heat Mode: Only heating will occur. Cool Mode: Only cooling will occur. Auto Mode: Heating or cooling will come on according to the heating and cooling setpoints. The
system will automatically switch between heating and cooling when the temperature exceeds the setpoints.
EH Mode: Only available when Heat Pump HVAC System type is selected. When there is a compressor failure with the heat pump system, setting the mode to EH will allow the supplemental heat to come on whenever there is a heat call to provide heating. It also disables the compressor outputs to prevent further damage to the system.
Main Thermostat Screen FAN Button
The FAN button controls the HVAC system’s manual fan. The current manual fan mode is displayed above the button. Normally this button is in the Auto mode. Pushing the FAN button once will turn the manual fan operation On. Pushing it again will turn the manual fan off and return to the Auto mode (which means OFF unless turned on by the furnace or AC). Changes in the fan mode are sent to the Control Unit.
Fan Button
Auto On
MENU
Main Thermostat Screen RUN/HOLD Button
The RUN/HOLD button controls the automatic schedule operation. In the HOLD mode, the current temperature is maintained until changed by manual or remote network command. In the Run mode, the schedule loaded into the thermostat is activated and setpoints will change according to the schedule and the time and day of week. There is also an AWAY mode that you can select if you press and hold the button for 3 seconds. In the Away mode, preset Heating and Cooling setpoints are used.
Run Button
Run Hold Away
(Press and hold button)
MENU
OFF
MODE
OFF
MODE
AUTO
FAN
AUTO
FAN
RUN
RUN
DCN: 141-01060-13 1/05 TS40 Manual
6
Page 7
Main Thermostat Screen LED Displays
The Main Thermostat screen has the following LEDs, numbered from top to bottom, 1-4.
o LED 1 Green: System Operation display.
o LED Off, “SYS OFF” displayed > HVAC system is OFF o LED Off, “SYS MOT” displayed > HVAC is Off and Minimum Off Time (MOT) delay on is
active
o LED On, “SYS ON” displayed > HVAC System is ON o LED On, “SYS MRT” displayed > HVAC System is ON and the Minimum Run Time
(MRT) delay off is active
o LED 2 Green: System Economy Mode display
o LED OFF or On, “Econ” displayed > Economy or 1 o LED On, “2 o LED On, “3
nd
Stg” displayed > Stage 2 heating or cooling is ON
rd
Stg” displayed > Stage 3 heating is ON
st
stage heating or cooling ON
o LED On, “Vent” displayed > fresh air venting is ON
o LED 3 Green: Run/Hold display. Shows state of Schedule Run/Hold Mode.
o LED Off, “Run” displayed > Schedule is running o LED On, “Hold” displayed > Schedule is off, temperature setpoint hold in effect.
o LED 4 RED: Alert LED. Used for Messaging and other system alerts
o LED Off, “No Msg” displayed > No text messages or Alerts present o LED On, Mail icon or Alert Text displayed > Message waiting or specific alert text
“Communications Error” Display
If the WDU is not properly wired or if communications to the Control Unit is interrupted, the LCD display will display “Comm Failure” at the top center of the Main Thermostat Screen (where outside temperature is normally displayed).
Momentary display of “Comm Failure” caused by loss of data, will clear automatically when data communication is restored. If the “Communications Failure” display stays on, check wiring or control unit for problems.
DCN: 141-01060-13 1/05 TS40 Manual
7
Page 8
Main Menu Screen
Main Menu
The TS40 Thermostat has a menu tree that can be accessed by pressing the “Menu” button on the Main Thermostat screen. Various configurations of the TS40 can have different screen contents. The first screen that will come up is the Main Menu screen that list the other menus or functions that can be accessed. Standard Main Menu screens are listed below.
SmartVent Screen
If SmartVent is installed on your HVAC system and has been enabled in the installer setup, the SmartVent control screen is the first option in the main menu. Select “SmartVent” to go to the control screen.
Message Screen
This is a text messaging subsystem that allows message of up to 80 characters to be sent to the thermostat. Select “Messages” to go to the Message screen to view message that have been received.
Schedules Screen
Select “Schedules” to go to the Schedules screen to view and program the setback schedules of the thermostat.
User Settings Screen
Select “Users Settings” to go to a User Settings submenu to select user setup options: Set Clock, Filter Service, Maint Service, Screen Timeout, F/C mode, Sensor Calibration and Backlight Timeout functions.
Thermostat Info Screen
Select “Thermostat Info” to go to the screen that shows the firmware versions of the WDU and Control Unit, HVAC system type and equipment options, and the Network Address of the thermostat/zone.
SmartVent Messages Schedules User Settings
Done
Main Menu Screen navigation buttons:
Done
Select
Return to Main Thermostat Screen Select Menu Item at cursor
Menu Selection
Select
Scroll up to next item Scroll down to next item
DCN: 141-01060-13 1/05 TS40 Manual
8
Page 9
Main Menu > SmartVent
Smart Vent
SmartVent is an automatic fresh air ventilation system. It is an optional feature of TS40 wall display units when used with ZCV2/4/6 zone control units and depends on if a SmartVent damper has been installed on the HVAC system. The SmartVent control must be enabled in the Installer Setup menu for the SmartVent menu option to appear in the Main Menu selections.
SmartVent is designed to be set and function automatically to provide for fresh air ventilation. Its benefits are improved indoor air quality and economy cooling for energy savings.
SmartVent operation and setup are controlled from the SmartVent Control Screen. Select the menu option from the Main Menu to go to the SmartVent control screen.
SmartVent has several modes of operation. They are:
Manual
Auto
Timed
Scheduled
Manual Mode
When Manual vent mode is selected, the vent damper will open and the HVAC system fan will come on. Fresh air will be circulated throught the house until the Manual mode is turned off or set to another mode.
Auto Mode
When in Auto vent mode, the SmartVent will turn on when the following conditions are met:
Outside temperature is lower than the inside temperature by 5 degrees (default setting that can be changed in the Installer Setup menu).
Inside temperature is higher than the vent setpoint.
Turns off when either of these two conditions are not met, i.e., it cools down to vent setpoint or heats up outside hotter than inside.
Timed Mode
The timed vent mode is used for a quick vent. Press the Timed Vent button once and the system will turn on and vent for 30 min. You can press the Timed Vent button again and the time will increase to 60min and so on up to 120 minutes. Press the button one more time and it will cycle to OFF.
Scheduled Mode
You can set a ventilation schedule that will run each day. You can schedule up to four vent run times per day. To access the Vent Schedule, in the SmartVent control screen, press the Setup button. You can turn the vent schedule ON/OFF or set the vent schedule.
Vent LED Is ON
when system is
venting
VENT
DONE
SMART VENT
INSIDE 76
OUTSIDE 68
SETUP
OFF
MODE
SETPOINT
70
TIMED
Set the Vent setpoint with these Up/Down buttons.
DCN: 141-01060-13 1/05 TS40 Manual
9
Page 10
Main Menu > Messages
Messages
The TS40 Message Screen allows you to retrieve text messages sent from the serial network to the thermostat. The message screen features navigation buttons to read new and old messages and delete them.
Up to 16 messages can be stored in the thermostat, if more than 16 messages are received, the oldest is erased to make room for the newest message. New messages will turn on and flash the Message LED and Mail Icon in the main thermostat screen.
Viewing messages makes them “old” and turns off the indicators. If you view some, but not all new messages, the new message notification LED and icon will stay on. Messages are entered as most recent message as number 1 message.
Message Screen
Messages
Message 1 10/14 5:35 PM
The TR40 can receive 16 text
messages, each up to 80 characters
long. They are date/timed stamped.
Done Del Prev Next
Message Screen navigation buttons:
When you first select the Message Screen, the most recently received message will be displayed as Message 1. If other messages are stored in memory, they can be recalled and viewed or deleted by using the message memory navigation buttons.
Done
Del
Prev
Next
Return to Main Menu Screen Delete the Message being displayed Display previous message. Scroll up in message stack Display next message. Scroll down in the message stack
DCN: 141-01060-13 1/05 TS40 Manual
10
Page 11
Main Menu > Schedules
Schedules
The Schedules Screen allows you to review and set the setback schedule for the thermostat. The TS40 has 4 x 7 schedule. Four times a day can be selected for Heating and Cooling setpoints. Each day of the week can have a different schedule. Groups of days can be copied with the same schedule. When the TS40 is set to “Run” mode, the schedule will be executed daily, with the setpoints being changed as per that days schedule stored in the thermostat. “Hold” mode stops schedule operation and holds the current setpoints until changed manually or by network commands.
The schedules Screen gives you the option of setting an custom setback schedule or to load one of two preset schedules.
Menu Options
Heat and Cool: You can change the individual day/hour and setpoints for the Heat and Cool schedule by selecting this menu item.
Preset: Comfort: This is a preset schedule with mild setbacks. Select this menu item to load the Comfort schedule into the thermostat.
Preset: EnergyMiser: This is a preset schedule with deeper setbacks. Select this menu item to load the EnergyMiser schedule into the thermostat.
Schedules Screen
DCN: 141-01060-13 1/05 TS40 Manual
Done
Select
Return to Main Menu Screen
Select the schedule to view or modify
Heat and Cool Preset: Comfort Preset: EnergyMiser
Done
Select Schedule
Select
11
Page 12
_
Main Menu > Schedules > Heat and Cool Schedule Screen
Heat and Cool Schedule
When you select the Heat and Cool Schedule menu item, the Schedule programming screen opens and the schedule for the current day will be displayed. Use the scroll buttons to highlight the data to be modified. Once the data has been highlighted, use the +/- buttons to change the value of the data.
To copy a days schedule to another or group of days, move the cursor to “c” on the bottom right of the schedule screen. When you highlight “c”, the button below will become “Copy”. Press this button to change to the Copy Schedule Screen.
Morn 6:00 A 72 82 Day 9:00 A 68 84 Eve 5:00 P 74 76 Nite 10:00 P 70 78
Done Next
Schedule Screen navigation buttons:
Done
Next
Copy
+
Monday Schedule
Time Heat Cool
+
c
Return to Main Menu Screen Scroll Back Scroll Forward Select the next Day schedule
OR if the copy “c” is selected, go to copy schedule screen. Increase the time or temperature selected Decrease the time or temperature selected
DCN: 141-01060-13 1/05 TS40 Manual
12
Page 13
Main Menu > Schedules > Heat and Cool > Copy Schedule
py
Copy Schedule
The Copy Schedule screen is a sub screen of the Schedule screen. The Copy Schedule screen allows you to copy a day’s schedule to another day or group of days.
First select the day to be copied in the Schedule screen. Scroll to the “c” at the bottom of the Schedule screen to highlight it. The “Next” button will change to the “Copy” button. Press the “Copy” button to open the Copy Schedule screen.
Scroll through the days and select the days the schedule is to be copied to day to “Y” by using the Yes/No buttons.
After selecting all the days desired, press the “Copy” button. Exit the Copy Schedule screen with the “Back” button.
Copy Schedule Screen
Copy Monday Schedule
to
Sun Tue Wed Thu Fri Sat N Y Y Y Y N
by setting the “N” under each
Yes No
Back Co
Copy Schedule screen navigation buttons:
Back
Copy
Yes
No
Return to Schedule Screen Move back with selection bar to previous day Move forward with selection bar to next day Copy the schedule to the selected days Copy schedule to this day Do not copy schedule to this day
DCN: 141-01060-13 1/05 TS40 Manual
13
Page 14
Main Menu > User Settings
Users Settings
The User Settings screen allows you to set or change various user options of the thermostat such as the clock, timeouts, Fahrenheit/Celsius mode or sensor calibration.
Menu options:
Set Clock Select this menu item to go to the Clock setting screen.
Screen Timeout
This sets the time before the current screen times out and returns to the minimized screen. If the time is set to 0, the current screen will not time out and will stay displayed until another screen is selected. Options are 0, 15-127 seconds. Select menu item and adjust value with +/- buttons.
F/C Select
Select which temperature display mode you desire, Fahrenheit (F) or Celsius (C) with +/- buttons.
Sensor Calibration
Select this menu item to go to the Sensor Calibration screen.
Backlight Timeout
The LCD backlight can be always on or set to timeout and go off after a preset timeout time. The
timeout time can be adjusted from 0 (always on), or 20 to 45 seconds before going off. Use +/- buttons to set time desired. Default set to 30 seconds.
Done
+ _
Select
User Settings
Set Clock Screen Timeout 60 F/C Mode F Sensor Calibration
Done
Return to Main Menu Increment value Decrement value Select the function to be set
+
_
Select
DCN: 141-01060-13 1/05 TS40 Manual
14
Page 15
Main Menu > User Settings > Set Clock
_
Set Clock
The Set Clock screen allows you to set the system clock. To set the Time and Day, move the cursor with the navigation arrows until the data you want to change is
highlighted. Using the + and – arrows to increment or decrement the data to the desired setting. When finished, press the SET button to return to the Main Menu screen or wait for screen to timeout.
NOTE: If the clock has been reset by an extended power outage, the Clock display on the thermostat screen will be blinking. Pressing the MENU button will take you directly to this screen to set the clock.
Set Clock Screen
Time 12:00 PM Date 7/13/04 Day Tue
Back Set
Set Clock Screen navigation buttons:
Back
Set
+
Return to User Settings menu without changing clock settings Move back with selection box Move forward with selection box Set the time Increment Time/Day Decrement Time/Day
Set Clock
+
DCN: 141-01060-13 1/05 TS40 Manual
15
Page 16
Main Menu > User Settings > Sensor Calibration
Sensor Calibration
The Sensor Calibration screen allows you to change the temperature calibration for the internal and any external remote temperature sensors attached to the TS40 WDU. You can change the temperature calibration by +/- 7 degrees. Each Remote Sensor has an address, 1 to 4, that defines its function.
When the Sensor Calibration screen is selected it will show the internal and all detected remote sensors attached to the WDU. Each sensor found will show the current temperature, like the (75) in the example screen below. Next to the current temperature is the current number of degrees of offset being applied (1 deg in the example). N/a means that no remote sensor is attached. If the sensor’s actual temp is (74) with 0 degrees of offset and you want it to be 75, then press + to add 1 deg and it will show (75). This is what the example shows.
To change the temperature calibration, use the scroll buttons to select the Internal or a Remote Sensor. Once selected, use the + and – buttons to change the temperature calibration to the desired setting.
The temperature shown in the (xx) is the adjusted temperature that will be displayed or used.
Sensor Calibration Screen
Internal (75) 1 Remote 1 n/a 0 Remote 2 n/a 0 Remote 3 n/a 0
Done +
Sensor Calibration navigation buttons:
DCN: 141-01060-13 1/05 TS40 Manual
Done
+
Return to Main Menu Screen Increase the temperature by 1 deg Decrease the temperature by 1 deg Not used Scroll Up Scroll Down
Sensor Calibration
16
Page 17
DCN: 141-01060-13 1/05 TS40 Manual
17
Page 18
Main Menu > Thermostat Info
Thermostat Info
The Thermostat Info screen displays the current configuration of the Thermostat Wall Display Unit and the HVAC Control Unit. This is VIEW only screen and the configuration cannot be changed from this screen. Some of the settings are dipswitch settings on the Control Unit and others are set in the Installers Setup screen. This information is useful for quick check of firmware versions and HVAC system setup. It also shows the network address setting.
Thermostat information displayed is:
Wall Display Unit Type and Firmware version number.
Control Unit Type and Firmware version number.
System Type setting: Standard or Heat Pump HVAC system
Fan Type setting for Standard systems: No Fan w/heat (Gas systems) or Fan w/heat (Electric systems)
OR
Changeover setting for Heat Pump systems: Changeover with cool or changeover with heat.
Network address setting: 1-254 valid
When finished viewing this screen press the Done button to return to the main Menu screen or wait for screen to timeout.
Thermostat Info Screen
TS40R Ver: 03.06.6 HCFRL Ver: 03.05.1 System Type: Standard Fan Type: No Fan w/HT Network Address: 01
Done
Thermostat Info
Thermostat Info Screen navigation buttons:
Done
DCN: 141-01060-13 1/05 TS40 Manual
Return to Main Menu screen.
18
Page 19
Main Menu > Installer Settings (Hidden Screen)
Installer Settings
The Installer Settings screen is a hidden screen designed for installer use only. Do not change any settings in this screen unless you are a qualified service technician. Changing these settings will affect the operation of the heating/cooling system.
To enter this screen, go to the Main Menu selection screen and press and hold the two inner buttons for 3 seconds until the Installer Settings screen appears.
The Installer Settings screen displays the current internal settings of the thermostat. You can view and change the settings from this screen. Scroll to the desired function and use the +/- buttons to change.
Display Lock N
Service Mode Network Addr 1 Max Heat SP 80
Done +
Thermostat Setup screen navigation buttons:
Done
+
Return to Main Menu screen Increase setting by 1 or change from Y to N Decrease setting by 1 or change from Y to N Scroll Up Scroll Down
Installer Settings Menu Items
These are the installer settings menu items that can be viewed and/or changed from this screen. The default settings are in parentheses.
DCN: 141-01060-13 1/05 TS40 Manual
Installer Settings
Press and hold these two buttons when in the Main Menu Screen to enter the Installer Settings Screen.
19
Page 20
Installer Settings Screen > Menu Items
Display Lock Allows you to lock or unlock the thermostat buttons. When the buttons are locked, you can still access the main menu, but you will not be allowed to select any menu options. The Installer Settings hidden button operation is still operational, allowing you to return to this screen and turn Display Lock off. (Off)
Service Mode Sets the thermostat to a test mode. All delays are shortened to 15 seconds to speed up system checkout and testing. Caution: compressor short cycle protection is lost in this mode. (Off)
Network Address Sets the serial communications network address. 1-254 valid. (1) Max Heat SP Sets the maximum heating setpoint that is allowed. Will not ramp or accept setpoints
higher that this maximum. (106) Min Cool SP Sets the minimum cooling setpoint that is allowed. Will not ramp or accept setpoints lower
than this minimum. Caution: this value needs to be reset if you are going to use degree C mode. (6)
Minimum Run Time Sets the minimum run time before a heating/cooling cycle can turn off. 1-9 Min (6) Minimum Off Time Sets the minimum off time before another heating/cooling cycle can begin.1-9 Min.
(6) Delta T Settings This is a submenu of the delta, or difference between, the setpoint and current temp for
determining when a heat or cool call comes on. Deltas are the number of degrees away from setpoint.
Delta T Settings Submenu
H/C Delta Minimum separation between heating and cooling setpoints. Setting a setpoint closer that this delta will “push” the other setpoint higher (heat) or lower (cool). When the thermostat is in the AUTO mode, this maintains a sufficient separation between setpoints to prevent overshoot from causing auto-changeover and subsequent alternating heating/cooling oscillations. (4)
H Delta Stg 1 ON Sets the temperature delta from setpoint for a stage one heating call. (1)
H Delta Stg 2 ON Sets the temperature delta from setpoint for a stage two heating call. (3)
H Delta Stg 3 ON Sets the temperature delta from setpoint for a stage three heating call. (5)
C Delta Stg 1 ON Sets the temperature delta from setpoint for a stage one cooling call. (1)
C Delta Stg 2 ON Sets the temperature delta from setpoint for a stage two cooling call. (3)
Auto Send Mode Sets the thermostat to automatically send changes out the serial port as they occur. (Off)
CAUTION! Do not change these settings unless you are sure of the effect these changes will make. Changing the network address will make the thermostat not respond if the address is incorrect.
DCN: 141-01060-13 1/05 TS40 Manual
20
Page 21
Remote Sensors
Remote Sensors
The TS40 Wall Display Unit has a Remote Sensor terminal block, J2, on the base for connection of an optional remote temperature sensor. The remote sensor has an address that can be set to 1, 2, 3, or 4.
Without any remote sensor attached, the WDU will use the internal sensor for the current room temperature information. When a remote sensor is attached, the WDU will detect it automatically and will use the remote sensor according to its address selection.
See the Remote Sensor installation document for correct dipswitch setting. The dipswitch on the remote sensor can be set to one of the following functions:
Remote Sensor Address 1: Use Remote Sensor address 1 instead of the Internal sensor. Remote Sensor Address 2: Average Remote Sensor address 2 with Internal sensor. Remote Sensor Address 3: Average Remote Sensor address 3 with Remote Sensor address 2. Remote Sensor Address 4: Use Remote Sensor address 4 as an outside temperature sensor.
All remote sensors are wired in parallel to the WDU remote sensor terminal block, J2.
DCN: 141-01060-13 1/05 TS40 Manual
21
Page 22
RCS
_
_
_
A
_
A
A
Wiring Instructions
Remove power from control unit.
Connect the WDU to the Thermostat Control Unit (TS40).
For Zone Controllers, connect each zone’s WDU to its respective zone input.
Connect optional Remote Sensors to the Wall Display Unit’s remote sensor input. See Remote
Sensor wiring information for sensor address setting.
Double check wiring before applying power to control unit.
Optional
RS15
Remote Sensor
ddress
Remote Sensor Address
must be set for correct
sensor operation
ddress
dditional Remote Sensors wire in parallel
to the WDU remote sensor connector.
DCN: 141-01060-13 1/05 TS40 Manual
+
C
D
+
C
D
TS40 Wiring Diagram
TS40
Wall Display Unit
Remote Sensor
RS
+
C D
Control Unit
C
+
C
D
Wall Display Units
GND 12V
C D
Check wiring before applying power.
CAUTION!
Mis-wiring the WDU to Control unit connections may result in damage.
GND 12V
C D
22
GND 12V
C D
TR40 Thermostat or
ZCV2/4/6 Zone Controllers
HVAC Control Unit
Zone 1
Thermostats have
only one WDU
Zone Controllers can
Zone 2
Zone 6
have up to 6 WDU’s
Loading...