RBI SPECTRUM Installation and Operation Instruction

SPMIOM-5
82-0255
SPECTRUM FINNED COPPER GAS BOILERS (MODEL SB) &
WATER HEATERS (MODEL SW)
INSTALLATION & OPERATION MANUAL
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 160 PSI, 1103 kPa WATER
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
WARNING: Failure to properly vent this unit can cause excessive amounts of carbon monoxide resulting in severe personal injury or death!
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
260 North Elm Street 7555 Tranmere Drive Westfi eld, MA 01085  Mississauga, Ontario L5S 1L4 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 2
AVERTISSMENT. Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides infl ammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifi é ou par le fournisseur de gaz.
CONTENTS
Before Your Start ................................................ page 2
Ratings & Capacities .......................................... page 3
Boiler/Water Heater Location .............................page 3
Combustion Air & Ventilation ............................. page 3
Chimney & Vent Pipe Connections ....................page 4
Common Vent Systems ......................................page 5
Outdoor Venting .................................................page 8
General Piping Requirements ............................page 8
Heating System Piping ....................................... page 9
Domestic Water Supply Piping ......................... page 13
Gas Supply Piping ............................................page 17
Electrical Wiring ................................................ page 18
General Operation ............................................page 19
Lighting Instructions .........................................page 20
Operating Instructions ......................................page 21
Checking & Adjustments ..................................page 22
Control Description ...........................................page 22
Maintenance ..................................................... page 23
Repair Parts ......................................................page 25
BEFORE YOU START
This manual covers the application, installation, operation and maintenance of a Spectrum finned copper heating boiler/water heater/pool heater.
To obtain the safe, dependable, effi cient operation and long life for which this heating boiler/water heater was designed, these instructions must be read, understood and followed.
The Spectrum fi nned copper heating boiler/water heaters have been design certifi ed by CSA for use with natural and propane gas under the latest revision of ANSI­Z21.10.3/CSA 4.3, Gas Water Heaters, ANSI-Z21.13/CSA
4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers and CAN-1-3.1, Industrial and Commercial Gas Fired Boilers. Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160 psi, 1103 KPa in accordance with Section IV of the A.S.M.E. Boiler and Pressure Vessel Code.
All aspects of the boiler/water heater installation must conform to the requirements of the authority having jurisdiction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA54-latest revision.
In Canada, the installation must be in accordance with the requirements of CAN/CGA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
If installed in the Commonwealth of Massachusetts, you MUST FOLLOW the additional instructions contained in RBI's instruction sheet MACODE-3. If you do not have a copy, call your RBI distributor or contact the RBI Customer Service Department.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the service organization for future reference.
Direct all questions to your RBI distributor or contact the RBI Customer Service Department, 260 North Elm Street, Westfi eld, MA 01085 for U.S. or 7555 Tranmere Drive, Mississauga ONT L5S 1L4 for Canada. Always include the model and serial numbers from the rating plate of the boiler/water heater in question.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 3
RATINGS & CAPACITIES
Before undertaking the installation of the Spectrum boiler/water heater check the rating plate to ensure that the unit has been sized properly for the job. The "Net I=B=R Ratings" specify the equivalent amount of direct cast iron radiation that the unit can supply under normal conditions. Also ensure that the unit has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1. This boiler/water heater is suitable for indoor and outdoor installations. Locate the boiler/water heater in an area that provides good access to the unit. Servicing may require the removal of jacket panels. Allow the minimum clearances between adjacent construction and the boiler/water heater as listed in Table 1.
NOTE: Service clearances are not mandatory, but are recommended to ensure ease of service should it be required.
Table 1 Clearance Service to Combustibles Clearance
in mm in mm Top 14 356 18 457 Back 6 152 18 457 Left Side 6 152 24 609 Right Side 6 152 24 609 Front 6 152 24 609 Flue 6 152 6 152
Table 2 - Special Base for Combustible Floors
Model Number Part Number 100 70-1248 150 70-1249 200 70-1250 250 70-1251 300 70-1252 350 70-1253 400 70-1254
4. Locate the boiler/water heater in an area that will prevent water damage to adjacent construction should a leak occur or during routine maintenance. If such a location doesn’t exist, a suitable drain pan that’s adequately drained must be installed under the unit. The pan must not restrict the flow of combustion air to the unit.
5. DO NOT place this boiler/water heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure, see “GENERAL VENTING GUIDELINES”.
6. NEVER place this boiler/water heater in a location that would subject it to temperatures at or near freezing. See the “Freeze Protection” section on page
8.
WARNING: Never store combustible materials, gasoline or any product containing fl ammable vapors or liquids in the vicinity of the boiler/water heater. Failure to comply with this warning can result in an explosion or fire causing extensive property damage, severe personal injury or death!
CAUTION: Units installed outdoors MUST be protected from ice and snow accumulation or the unit will be damaged voiding the warranty!
2. An optimum site will be level, central to the piping system, close to a chimney and have adequate fresh air for combustion. Ensure that the boiler/water heater is level from front to back and from side to side. Use metal shims to level the boiler/water heater. Electrical and electronic components must also be protected from exposure to water during operation and maintenance. DO NOT install this boiler/water heater in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
3. Ensure that the fl oor is structurally sound and will support the weight of the boiler/water heater.
NOTE: The Spectrum may be installed directly on combustible fl ooring, only if RBI supplied special fl oor pan is used but never on carpeting, see Table
2.
COMBUSTION AIR & VENTILATION
WARNING: This boiler/water heater must be supplied with combustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and all applicable local building codes. Canadian installations must comply with CSA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. Failure to provide adequate combustion air for this boiler/water heater can result in excessive levels of carbon monoxide that can result in severe personal injury or death!
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 4
To operate properly and safely this boiler/water heater requires a continuous supply of air for combustion. NEVER store objects on or around the boiler/water heater!
CAUTION: Combustion air contaminated with fl uorocarbons or other halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. These acids will cause premature failure of the boiler/water heater voiding the warranty!
CAUTION: If the boiler/water heater is operated while the building is under construction it MUST be protected from wood, concrete, sheet rock and other types of dust. Failure to properly protect the unit from construction dust will damage the unit voiding the warranty!
All Air From Inside The Building
If the boiler/water heater is to be located in a confi ned space, minimum clearances listed in Table 1 must be maintained between the boiler/water heater and any combustible construction. When installed in a confi ned space, Figures 1 and 2, two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have suffi cient volume to meet the criteria for an unconfi ned space. The total air requirements of all gas utilization equipment, fireplaces, wood stoves or any type of exhaust fan must be considered when making this determination. Each opening must have a minimum free area of 1 in
2
/1000 Btu/hr, 2200 mm2/kW based on the
total input rating of ALL gas utilization equipment in the confi ned area. Each opening must be no less than
100 in2, 64,516 mm2 in size. The upper opening must
be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure. The bottom
opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bottom of the enclosure.
All Air From Outside The Building
When installed in a confi ned space two permanent openings communicating directly with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure. The bottom opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bottom of the enclosure.
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in2/4000 Btu/hr, 550 mm2/kW of the total input rating of all of the equipment in the enclosure.
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in2/2000 Btu/hr, 1100 mm2/kW of the total input rating of all of the equipment in the enclosure.
When louvers and screens are used, they must have the same cross-sectional area as the free area of the opening to which they connect.
When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration must be given to the blockage effects of louvers, grills and screens. Screens must have a minimum mesh size of 1/4 in, 6.4mm. If the free area through a louver or grill is not known, ducts should be sized per Table 3.
Canadian installations must comply with CSA B149.1 when air supply is provided by natural air fl ow from the outdoors for natural draft, partial fan-assisted, fan­assisted, or power draft-assisted burners, there shall be a permanent air supply opening(s) having a cross­sectional area of not less than 1 in2 per 7,000 Btuh (310 mm2 per kW) up to and including 1 million Btuh, plus 1 in2 per 14,000 Btuh (155 mm2 per kW) in excess
of 1 million Btuh.
Table 3 - Make-up Air Louver Sizing
Required Cross Sectional Area
Input 1/4 in 6.4 mm (MBH) Wire Screen Metal Louvers Wooden Louvers in 100 25 161 33 213 100 645 150 37 858 50 322 150 967 200 50 322 67 432 200 1290 250 62 400 83 535 250 1612 300 75 484 100 645 300 1934 350 87 561 117 754 350 2257 400 100 645 133 858 400 2579
2
cm
75% Free Area 25% Free Area
2
in
2
cm
2
in
2
cm
2
CHIMNEY & VENT PIPE CONNECTIONS
WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or applicable provisions of the local building codes. Canadian installations must comply with CSA B149.1 or .2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 5
Chimney Inspection & Sizing
A thorough inspection of the masonry chimney must be performed to ensure that the chimney is clean, properly constructed, lined and sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems. Table 4 lists the equivalent breeching and fl ue sizes required for the boiler/water heater.
Table 4 - Equivalent Breeching & Chimney Size
Model Size Size
Size in mm 100 5 127 150 6 152 200 7 178 250 8 203 300 8 203 350 9 229 400 10 254
Note: These sizes are based on a 20 ft, 6.1 m chimney height.
When more than one appliance is connected to the same chimney fl ue, the fl ue must be large enough to safely vent the combined output of all the appliances.
WARNING: If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney fl ue, never connect any other appliances to this fl ue. Doing so can result in the accumulation of carbon monoxide which can cause severe personal injury or death!
Vent Connections
Always use a type B or single wall galvanized metal vent pipe the same diameter as the draft hood fl ue collar, Table 4. Use the shortest, straightest vent system possible for the installation. If horizontal runs exceed 6 ft, 1.8 m they must be supported at 6 ft, 1.8 m intervals with overhead hangers. The vent system should be sloped up toward the chimney at a minimum rate of 1/4 in/ft, 20 mm/m and terminate fl ush with the inside of the chimney fl ue. Fasten each connection with at least 3 corrosion resistant sheet metal screws.
WARNING: Never modify or alter any part of the boiler’s draft hood. This includes the removal or alteration of any baffl es. Never install a vent pipe of a diameter different than that of the boiler draft hood fl ue collar. Failure to comply with this warning can result in severe personal injury or death!
WARNING: Failure to maintain minimum clearances between vent connectors and any combustible material can result in a fi re causing extensive property damage, severe personal injury or death!
To determine the appropriate power venter for the boiler/ water heater, see Table 5, Power Venter Sizes. Follow the power venter manufacturer’s installation instructions.
Table 5 - Power Venter Sizes
Spectrum Power Venter Max. Pipe Length Model Size FT m
100-250 HS-1 100 31 300-400 HS-2 100 31
COMMON VENT SYSTEMS
If an existing boiler/water heater is removed from a common venting system, the common venting system may then be too large for the proper venting of the remaining appliances connected to it. At the time of removal of an existing boiler/water heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d’évacuation commun et qui fonctionne alors que d’autres appareils toujours raccordés au système d’évacuation ne fonction­nent pas: système d’évacuation.
a) Seal any unused openings in the common venting
system.
Sceller toutes les ouvertures non utilisées du sys-tème d’évacuation.
b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no block­age or restriction, leakage, corrosion and other defi ­ciencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d’évacuation
pour déterminer la grosser et l’inclinaison horizontale qui conviennent et s’assurer que le système est ex­empt d’obstruction, d’étranglement de fruite, de cor­rosion et autres défaillances qui pourraient présenter des risques.
Always provide a minimum clearance of 6 in,152 mm between type C vent pipe and any combustible materials. Type B1 vent may be used, clearance between it and any combustible material must be as listed.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 6
c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bath­room exhaust, so they will operate at maximum speed. Do not operate a summer exhaust fan for a boiler installation. Close fi replace dampers.
Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les portes entre l’espace où les appareils toujours raccordés du système d’évacuation sont installés et les autres espaces du bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au système d’évacuation commun et tous les ventilateurs d’extraction comme les hottes de cuisinère et les ventilateurs des salles de bain. S’assurer que ces ventilateurs fonctionnent à la vitesse maximale. Ne pas faire fonctionner les ventilateurs d’été. Fermer les registres des cheminées.
d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Mettre l’appareil inspecté en marche. Suivre les in-
structions d’allumage. Régler le thermostat de façon que l’appareil fonctionne de façon continue.
f) After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fi replace dampers and any other gas-burning appliance to their previous condition of use.
Une fois qu’il a été déterminé, selon la métode
indiquée ci-dessus, que chaque appareil raccordé au système d’évacuation est mis à l’air libre de façor adéquate. Remettre les portes et les fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
g) Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 in the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 and or CAN/CGA B149 Installation Codes.
Tout mauvais fonctionnement du systéme
d’évacuation commun devrait étré corrigé de façor que l’installation soit conforme au National Fue Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d’installation CAN/CGA-B149. Si la grosseur d’une section du système d’ évacuation doit étré modifi ée, le système devrait étré modifi é pour.
e) Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the fl ame of a match or candle, or smoke from a cigarette, cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min
ensuite, déterminer si le coupe-tirage déborde à l'ouverture de décharge. Utiliser la fl amme d'une allunette ou d'une chandelle ou la fumée d'une ciga­rette, d'un cigare ou d'une pipe.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 7
Figure 1 - Vertical Venting with a Metal Chimney System and Inside Air
10 FT 3.1m
Figure 2 - Vertical Venting using a Masonry Chimney and Inside Air
RIOM-51
RIOM-52
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 8
OUTDOOR VENTING
When installed outdoors the Spectrum must be fi tted with the factory supplied outdoor hood assembly, see Figure 3. Multiple units must be spaced per Figure 3A.
The boiler/water heater must be at least 10 ft, 3.1 m from any door, window or gravity air inlet into any building and at least 3 ft, 0.9 m from any overhang unless local codes dictate differently.
Avoid locations where wind deflection off of adjacent walls, buildings or shrubbery might cause a down draft. The unit(s) should be located at least 3 ft, 0.9 m from structures. Outdoor installations are not recommended in areas where the danger of snow blockage exists.
CAUTION: Do not place the boiler/water heater in a location that would subject it to runoff from adjacent buildings or damage may occur voiding the warranty!
Figure 3 - Outdoor Venting
EXHAUST HOOD
SUPPLY/RETURN
HEADER HOOD
SPECTRUM
COMBUSTION AIR HOOD
GENERAL PIPING REQUIREMENTS
CAUTION: Improper piping of this boiler/water heater will void the manufacturer’s warranty and can cause boiler failure resulting in flooding and extensive property damage! Excessive water hardness causing lime build-up in the copper heat exchanger tubes is NOT covered under the manufacturer’s warranty. Excessive pitting and erosion of the internal surface of the copper heat exchanger tubes is NOT covered under the manufacturer’s warranty if the result of high water fl ow rates, see Table 7 or 8. Return water temperatures below 110°F, 43°C will result in heat exchanger damage from excessive condensation voiding the manufacturer’s warranty, see Primary/Secondary Piping Figure 5.
NOTE: Shut off valves and unions should be installed at the inlet and outlet connections of the boiler water heater to provide for isolation of the unit should servicing be necessary.
Freeze Protection
This boiler/water heater is CSA designed certifi ed for outdoor installation. Outdoor installations in areas where the danger of freezing exists are not recommended unless proper freeze protection is provided. If the unit is to be installed in such an area the following precautions MUST be observed:
Figure 3A -Multiple Outdoor Units
3'
0.9 m
4'
1.2 m
HEADER HOOD
RIOM-53
1. A continuous fl ow of water through the boiler/water heater MUST be maintained! The pump responsible for fl ow through the boiler/water heater must run continuously!
2. An ethylene glycol/water mixture suitable for the minimum temperature that the unit will be exposed to must be used. The pump must be capable of producing 15% more fl ow and overcoming a 20% increase in head loss. Domestic water systems must be isolated from the water heater by the use of a heat exchanger or other approved method.
3. If the boiler/water heater must be shut off for any reason the electric, gas and water supplies MUST be shut off and the unit and its pump completely drained.
CAUTION: Improper outdoor installation of this boiler/water heater can cause boiler failure voiding the manufacturer's warranty!
RIOM-54
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 9
Relief Valve
Pipe the discharge of the pressure relief valve to prevent scalding in the event of a discharge, see Figure 4. The discharge piping must be sized the same as the pressure relief valve outlet and installed to allow complete drainage of both the relief valve and the discharge piping.
Figure 4
1",
25 mm
RIOM-57
WARNING: Never install any type of valve between the boiler/water heater and the relief valve or an explosion causing extensive property damage, severe personal injury or death may occur!
Flow Switch
The fl ow switch supplied with the boiler/water heater must be wired to the terminal strip in the control panel to prevent the boiler from fi ring unless there’s adequate water fl ow through the unit. The fl ow switch must be installed in the supply piping adjacent to the boiler outlet connection.
CAUTION: Failure to properly install the fl ow switch may result in damage to the boiler/water heater heat exchanger voiding the warranty!
HEATING SYSTEM PIPING
The thermal expansion of the system must be considered when supporting the system. A minimum system pressure of 12 psig, 82.7 kPa must be maintained.
Heating Boiler Piping Connections
The supply and return connections should be sized to suit the system, see Table 6.
Table 6 - Supply & Return Pipe Sizing
Model Size Supply Return 100 thru 400 1
1
/2" NPT 11/2" NPT
Pump Requirements
This low mass boiler requires a continuous minimum water fl ow for proper operation. The boiler pump must be sized to overcome the head loss of the boiler and the near piping in order to achieve the required temperature rise. Table 7 and 8 provides the heat exchanger pressure drop and temperature rise fi gures.
The temperature rise across the boiler must never exceed 30°F, 16.7 °C. A pump delay is installed, the pump delay turns the pump on each time the burners fi re and runs the pump up to 10 minutes after the call for heat is satisfi ed.
CAUTION: A temperature rise outside of the range listed in Tables 7 or 8 indicates that the fl ow rate through the heat exchanger is incorrect which will damage the heat exchanger voiding the warranty!
The maximum allowable flow rate through a Spectrum boiler with copper heat exchanger is 92 GPM, 5.8 L/s (2-pass heat exchanger) and 46 GPM,
2.9 L/s (4-pass heat exchanger).
Low Water Cutoff
If a boiler is installed above any radiation elements it must be fi tted with a low water cutoff device.
Refer to wiring diagram supplied with the boiler/water heater for proper wiring connections.
General Piping Requirements
All heating system piping must be installed by a qualifi ed technician in accordance with the latest revision of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV, and ANSI/ASME CSD-1, Standard for Controls and Safety Devices for Automatically Fired Boilers. All applicable local codes and ordinances must also be followed. A minimum clearance of 1 in, 25 mm must be maintained between heating system pipes and all combustible construction. All heating system piping must be supported by suitable hangers not the boiler.
Expansion Tank
An expansion tank or other means to control thermal expansion must be installed in the heating system. An expansion tank must be installed close to the boiler on the suction side of the system pump.
Primary/Secondary Piping
Boilers connected to heating systems using zone valves, zone pumps, or systems that have excessive fl ow rates or return water temperatures less than 110°F, 43 °C must be isolated from these systems to protect the boiler.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 10
Table 7 - Temperature Rise Table – 2 Pass Headers
ΔT = 10°F
Flow
Model
Number
100
150
200
250
300
350
400
Note: Unit equipped with 4 pass headers, see Table 8.
Table 8 - Temperature Rise Table – 4 Pass Headers
Rate
GPM
16.4
24.6
32.4
40.5
49.8
58.1
66.4
ΔT = 10°F
Pres. Drop
Ft
0.05
0.13
0.27
0.48
0.82
1.23
1.77
ΔT = 5.5°C
Flow Rate
L/s kPa
1.0
1.6
2.0
2.6
3.1
3.7
4.2
ΔT = 5.5°C
Pres. Drop
0.1
0.4
0.8
1.4
2.4
3.6
5.2
ΔT = 20°F
Flow Rate
GPM
16.2
20.3
24.9
29.1
33.2
ΔT = 20°F
Pres. Drop
Ft
0.07
0.13
0.23
0.34
0.49
ΔT = 11.1°C
Flow Rate
L/s kPa
1.0
1.3
1.6
1.8
2.1
ΔT = 11.1°C
Pres. Drop
0.2
0.4
0.7
1.0
1.4
ΔT = 30°F
Flow Rate
GPM
16.6
19.4
22.1
ΔT = 30°F
Pres. Drop
Ft
0.10
0.20
0.20
ΔT = 16.7°C
Flow Rate
L/s
1.0
1.2
1.4
ΔT = 16.7°C
Pres. Drop
kPa
0.3
0.5
0.7
Flow
Model
Number
100
150
200
250
300
350
400
Note: Unit equipped with 2 pass headers, see Table 7. *Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupro-nickel heat exchanger should be considered.
Rate
GPM
16.4
24.6
32.4
40.5
49.8*
Pres. Drop
Ft
0.34
0.94
1.92
3.46
5.89
Flow Rate
L/s kPa
1.0
1.6
2.0
2.6
3.1
See Note
Pres. Drop
1.0
2.8
5.7
10.2
17.3
Flow Rate
GPM
16.2
20.3
24.9
29.1
33.2
Pres. Drop
Ft
0.53
0.96
1.63
2.47
3.54
Flow Rate
L/s
1.0
1.3
1.6
1.8
2.1
Pres. Drop
kPa
1.6
2.8
4.8
7.3
10.4
Flow Rate
GPM
16.6
19.4
22.1
Pres. Drop
Ft
0.80
1.20
1.70
Flow Rate
L/s
1.0
1.2
1.4
Pres. Drop
kPa
2.3
3.4
4.9
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 11
Figure 5 - Typical Primary/Secondary Piping System
(See Notes)
Pump
Gate Valve
Globe Valve
NOTES:
1
1. Boiler circuit piping must be sized large enough to handle maximum fl ow through unit.
2. Boiler pump sized to boiler design fl ow requirements.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
Notice: These drawings show suggested piping confi guration and valving. Check with local codes and ordinances for specifi c requirements.
Figure 6 - Low Temperature Piping with Thermostatic Valve
(See Notes and Adjustment Procedures)
3
H-1 Rev 2
Angle Valve
Bufferfly Valve
Balance Valve
Ball Valve
Motorized Valve
Solenoid
Operated Valve
Self-Operated
Val ve
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
NOTES:
1. For pump selection consult factory.
2. Boiler pump sized to boiler and thermostatic 3-way valve design fl ow requirements.
3. Boiler circuit piping must be sized large enough to handle maximum fl ow through unit.
4. All boilers furnished with factory mounted outlet water temperature gauge.
5. Boiler pump purging required. Use terminals supplied.
6. Valve is precalibrated for 140°F return temperature.
Notice: These drawings show suggested piping confi guration and valving. Check with local codes and ordinances for specifi c requirements.
H-18
Thermometer
Aquastat Union
Pressure Switch
Gas Pressure
Regulator
Automatic
Air Vent
Backflow­Prevention
Device
3-Way Valve
Expansion
Tan k
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 12
Figure 6A - Low Temperature Piping
(See Notes and Adjustment Procedures)
1
Adjustment Procedure
To Maintain Inlet Temperature
Above Dew Point
T1-Temp-Min+110° For Atmospheric
T1-Temp-Min=125° Sealed Combusion
1. Turn heater on and open valves A & B.
2. After steady-state operation, if T1 is less than Temp-Min slowly close valve B until T1 climbs to desired operating temperature above Temp-Min.
3. If T1 is greater than desired operating temperature, slowly close valve A to adjust to lower desired temperature above Temp-Min.
4. Check after system operating temperature has stabiized. Make fi nal adjustments.
5. Follow same adjustment procedure for sealed combustion.
H-3 Rev 2
Pump
Gate Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve
Ball Valve
Motorized Valve
Solenoid
Operated Valve
Self-Operated
Val ve
Figure 7 - Multiple Boiler Piping (See notes)
5
1
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
Thermometer
Aquastat Union
Pressure Switch
Gas Pressure
Regulator
Automatic
Air Vent
Backflow­Prevention
Device
H-15 Rev 3
NOTES:
1. Boiler circuit piping must be large enough to handle maximum fl ow through unit.
2. Boiler pump sized to boiler design fl ow requirements.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
5. Secondary loop pipe diameter must be sized large enough to handle maximum fl ow through all units.
Notice: These drawings show suggested piping confi guration and valving. Check with local codes and ordinances for specifi c requirements.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 13
Variable Water Flows
Figure 5 shows a typical primary/secondary piping system. A dedicated pump is used to maintain a constant water fl ow through the boiler. This boiler pump is sized to overcome the head loss of the boiler and near piping while supplying the fl ow rate required to maintain the desired temperature rise across the boiler heat exchanger. The system pump is sized to provide the required fl ow to the heating system. The boiler piping connections to the heating system piping must not be more than 12 in, 305 mm apart to ensure zero pressure drop, see Figure 5.
Low Return Water Temperatures
To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary/secondary piping system with a bypass and bypass valve must be installed, see Figures 6 and 6A. The bypass and bypass valve must be sized the same as the secondary piping. A balancing valve must also be installed in the supply side of the secondary piping downstream of the bypass. The balancing valve should be adjusted to divert some of the heated discharge water into the return water until the required inlet water temperature is achieved. The primary and secondary pumps should be sized to provide the required flow through each system. The boiler piping connections to the heating system piping must not be more than 12 in, 305 mm apart to ensure zero pressure drop, see Figures 6 and 6A.
Multiple Boiler Systems
Systems using multiple boilers can also be installed using a primary/secondary manifold system, Figure 7.
Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler. Appropriate valves must be used to prevent the chilled water from entering the boiler.
When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device, the piping system must be equipped with fl ow­control valves or some other automatic means of preventing gravity circulation of the boiler water during the cooling cycle.
DOMESTIC WATER SUPPLY PIPING
CAUTION: Proper controls must be used to prevent water supplied for domestic use from exceeding 130°F, 54°C or a scald injury will occur! When higher water temperatures are required for appliances such as a dishwasher, a mixing valve or some other tempering means must be installed. Households with small children may require water temperatures less than 120°F, 49°C. Local codes must be complied with!
General Piping Requirements
Ensure that the water heater is equipped with bronze headers. Piping and components connected to the water heater must be suitable for use with potable water. The water heater must not be connected to any heating system piping or components previously used with a non-potable water heating appliance. No toxic chemicals, such as those used for boiler treatment, are to be introduced into any potable water used for space heating. If a hot water storage tank is used in the system, it must be equipped with a temperature and pressure relief valve that complies with ANSI Z21.22 or CAN-4.4 and CAN-4.6.
NOTE: The storage tank must be located as close to the water heater as possible to prevent excessive head loss which will reduce fl ow.
Water Chemistry
The required temperature rise across the water heater is based on water having a hardness between 5 and 25 grains per gallon with a level of dissolved solids not exceeding 350 ppm. Water having a hardness less than 5 grains can cause excessive corrosion of the heat exchanger. Water that has a hardness greater than 25 grains per gallon and/or a level of dissolved solids exceeding 350 ppm will require a recalculation of the pump size and temperature rise.
A cupro-nickel heat exchanger may also be required. The manufacturer should be consulted when these water conditions are encountered. See Table 9A.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 14
RBI water heaters are designed to run scale free. Due to the extreme variables of water conditions world wide it is necessary to consider pH values and water hardness in relationship to scaling. It is crucial to consider these two variables when making heat exchanger and pump selections. If local water conditions are extreme follow the guidelines in the Heat Exchanger Selection Table (Table 9A) and the Pumping Performance Table (Table 9B). Scale free operation can be achieved by using water with a hardness between 8 and 18 and by maintaining the pH between 5 and 9. Follow the conditions listed under NORMAL in the table. In some areas of the country additional precautions must be observed due to unusual characteristics of the local water supply. Call the nearest RBI representative for details.
To properly size the pump a grain hardness and pH test must be taken at the installation site before the order is placed. Proper pump sizing will improve heater performance and help ensure heater longevity.
Expansion Tank
An expansion tank or other means to control thermal expansion must be installed in the water heating system if back fl ow prevention devices are installed.
Pump Requirements
This low-mass water heater requires a continuous mini­mum water flow for proper operation. The factory recommended circulating pump has been sized to overcome the head loss of the water heater plus a 30 foot piping loop under normal water conditions. provides the heat exchanger pressure drop chart and temperature rise table. The temperature rise across the
water heater must never exceed 30°F, 16.7 °C.
Table 9B
Temperature Rise Control
Water returned to the water heater inlet must not be less than 110°F, 43°C or excessive condensation of the products of combustion will damage the water heater voiding the warranty. The method outlined below can be employed to prevent this condition from occurring.
A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the fl ow rate through the heat exchanger. Thermometers are installed on both the inlet and outlet of the water heater for determining the temperature rise through the unit.
The proper velocity through the water heater must be maintained in accordance with Table 9B for efficient operation and long life. If the temperature rise through the water heater is lower than recommended, the water velocity is too high. Premature erosion of the heat exchanger will occur. Conversely, if the temperature rise is higher than recommended in Table 9B the fl ow rate is too low. Scaling and softening of the heat exchanger will occur.
Thermostatic Mixing Valve - Water Above 140°F, 60°C Water can be stored at temperatures above 140°F,
60 °C provided that a thermostatically controlled mixing valve is used to temper the hot water to an acceptable temperature before it’s supplied for domestic use.
The mixing valve MUST be set to prevent a scald injury from occurring, see the caution against scalding.
Storage of water for domestic use above 140°F, 60°C will provide an increased quantity of tempered water and help prevent the growth of water born bacteria.
CAUTION: The maximum allowable fl ow rate through a Spectrum water heater is 92 GPM, 5.8 L/s (2-pass heat exchanger) and 46 GPM, 2.9 L/s (4-pass heat exchanger). The cupro-nickel heat exchanger allows for 100 GPM, 6.3 L/s (2-pass heat exchanger) and 50 GPM, 3.2 L/s (4-pass heat exchanger). See Table 9B.
Cold Water Supply
The cold water supply must be piped to the storage tank on the water heater’s outlet piping between the water heater and the hot water storage tank. This will prevent untempered water from entering the water heater, see the Temperature Rise Control section. A typical water heating system is shown in Figures 8 and 9.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 15
Table 9A - Spectrum Heat Exchanger Selection Graph
Table 9B - Spectrum Pumping Performance Requirement Table
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 16
(Typ.)
Figure 8 - Typical Water Heating Piping (MW Models Only)
(See Notes)
3
8
2
1
4
7
Attention:
Not all RBI stock storage tanks
incorporate this tapping: See Note 1.
Figure 9 - Multiple Water Heating Piping (MW Models Only)
(See Notes)
D-1 Rev 6
Pump
Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve
Ball Valve
Motorized Valve
Solenoid
Operated Valve
Self-Operated
Valve
SELF BALANCIN G DOUBLE REVERSE RETURN MAKE-UP & SUPPLY, CIRCULATION
4
3
6
8
4
1
7
2
7
2
6
D-4 Rev 6
Attention:
Not all RBI stock storage tanks
incorporate this tapping: See Note 1.
NOTES:
1. Optional cold water make up and recirculation line location.
2. When using intermittent pump and pump delay, locate remote aquastat well in lower 1/3 of tank. Install aquastat with heat sensing compound.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30’ total, 6-90° elbows, full pipe size.
5. CAUTION: MEASURE WATER HARDNESS AND pH AT JOB SITE. The pH and water hardness must be measured before selecting heat exchanger and pump. Consult the Heat Exchanger Graph and
Pumping Performance Table before making selection.
6. Common piping must be sized for maximum combined heater fl ow.
7. Hot water tanks should be equipped with a combination temperature & pressure relief valve.
8. MA Code requires an 1/8” hole in check valve to compensate for thermal expansion.
Notice: These drawings show suggested piping confi guration and valving. Check with local codes and ordinances for specifi c requirements.
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
Thermometer
Aquastat Union
Pressure Switch
Gas Pressure
Regulator
Automatic
Air Vent
Temperature &
Pressure
Relief Valve
Vacuum
Relief Valve
Drain Valve
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 17
GAS SUPPLY PIPING
WARNING: Check the boiler/water heater rating plate to make sure that the boiler/water heater is for the type of gas that will be used. If it isn’t, do not connect the boiler/water heater to the gas supply. Gas supply piping must be in accordance with the National Fuel Code, ANSI Z223.1-latest revision or applicable provisions of the local building codes. Canadian Installations must comply with CAN/CGA B149.1 or .2 Installation Code. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
The Spectrum boiler/water heaters come from the factory ready to be piped to the gas supply. If for any reason the boiler/water heater is not for the type of gas available at the installation site, call the nearest RBI representative to resolve the problem.
NOTE: A minimum gas supply pressure of 5 in, 127 mm W.C. natural or 12 in, 305 mm W.C. propane and maximum gas supply pressure of 14 in, 356 mm W.C. natual or propane, must be available at the safety shutoff valve inlet with the unit(s) operating.
Table 11 - Equivalent Pipe Length
Nominal Iron Pipe Size, (in)
1" 1 1/4" 1 1/2"
2" 2 1/2"
3"
4"
Notes: 1. For fl ow through branch.
2. For fl ow at full open.
Type of pipe fi tting
90°
Elbow
Te e
Equivalent of pipe length (ft)
5.2
2.6
6.9
3.5
8.0
4.0
10.3
5.2
12.3
6.2
15.3
7.7
15.3
7.7
Gate
1
Val ve
0.6
0.8
0.9
1.2
1.4
1.8
1.8
Gas
Cock
1.5
1.9
2.3
3.0
3.7
4.5
4.5
2
2
Figure 10 depicts the proper way to connect the boiler/water heater to the gas supply piping. The manual shut-off valve MUST be installed in the supply piping. It should be installed 5 ft, 1.5 m above the fl oor where required by local codes. Provide a sediment trap at the bottom of the vertical section of the gas supply pipe upstream of the gas controls.
A ground joint union should be installed between the boiler gas controls and the supply piping. Each of these items are needed to ensure long life and ease of servicing. Always use a pipe sealant that is suitable for use with LP gas.
Table 10 should be used to ensure that the gas supply piping is sized properly. If more than one appliance is supplied by the same supply pipe, the piping must be sized based on the maximum possible demand. Do not neglect the pressure drop due to pipe fi ttings. Table 10 should be used in conjunction with Table 11 to ensure that the gas supply piping has the capacity to meet the demand.
Table 10 - Gas Pipe Capacity
Maximum pipe capacity in ft3/hr based on 0.60 specifi c gravity gas at a pressure of 0.5 psig or less and a 0.3" W.C. pressure drop.
Nominal Iron Pipe Size, (in)
3/4"
1" 1 1/4" 1 1/2"
2" 2 1/2"
3"
4"
Note: Multiply the gas volume by 0.62 for propane fl ow capacity in ft3/hr. Multiply the propane fl ow capacity by 2500 Btu/ft3 to determine the propane Btu/hr
capacity for a given pipe size and length.
10
278 520 1050 1600 3050 4800 8500 17,500
20
190 350 730 1100 2100 3300 5900 12,000
Pipe length in feet
30
Maximum gas volume of pipe, (ft
152 285
590 890 1650 2700 4700 9700
40
130 245 500 760 1450 2300 4100 8300
50
115 215
440 670 1270 2000 3600 7400
105 195
400 610 1150 1850 3250 6800
60
3
/hr)
90 170
350 530 990 1600 2800 5800
80
100
79 150 305 460 870 1400 2500 5100
150
64 120 250 380 710 1130 2000 4100
Figure 10 - Gas Supply Piping
RIOM-47
CAUTION: Always use a wrench on the gas valve body when making gas connections to it. Never over-tighten the piping entering the gas valve body or gas valve failure may result!
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 18
When applicable, provisions for vent, bleed and gas relief lines must be made in accordance with the latest revision of ANSI Z223.1/NFPA 54.
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler. All gas connections MUST be leak tested before putting the boiler into operation.
WARNING: Never use an open fl ame to test for gas leaks. Always use an approved leak detec­tion method. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
Whenever the gas supply piping is pressure tested the boiler/water heater gas controls must be protected. If the test pressure is equal to, or less than 1/2 psig, 3.5 kPa isolate the boiler/water heater by closing it’s manual shut off valve, see Figure 10. If the test pressure is greater than, or equal to 1/2 psig, 3.5 kPa, disconnect the boiler/water heater and its individual shut-off valve.
Required Gas Pressure
Provide gas supply pressure at inlet to boiler gas train as follows: LP Nat
Minimum (in W.C.) 12 5 Maximum (in W.C.) 14 14
Measure pressure when boiler is fi ring at full rate. Low gas pressure could indicate undersized gas line or insuffi cient gas supply.
"Static and operating gas pressure required at the gas valve inlet is between 5" W.C. and 14" W.C. for natural gas and 12" W.C. and 14" W.C. for propane. If the gas pressure is above this limit, a lock-up style regulator suitable for dead end service such as an Equimeter or Fisher must be installed to prevent increase (creep) of gas pressure when the units are not operating. This pressure regulator (supplied by others) may be installed at the service entrance to each unit or a "master" regulator sized to handle multiple units may be utilized. Consult local gas utility or regulator manufacturer for recommendations to meet specifi c job site requirements."
ELECTRICAL WIRING
Electrical Power Connections
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation! Verify proper operation after servicing!
ATTENTION. Au moment de l’entretien des commandes, étiquetez tous les fi ls avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement inadéquat et dangereux. S’assurer que l’appareil fonctionne adéquatement une fois l’entretirn terminé.
The electrical connections to this boiler/water heater must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI/NFPA-70. Installation should also conform with CSA C22.1 Canadian Electrical Code Part I if installed in Canada.
Install a separate 120 volt 15 amp circuit for the boiler/ water heater and circulator pump. A shut-off switch should be located at the boiler/water heater. The boiler/ water heater must be grounded in accordance with the authority having jurisdiction, or if none, the latest revision of the National Electrical Code, ANSI/NFPA-70.
Line voltage fi eld wiring of any controls or other devices must conform to the temperature limitation of type T wire at 95˚F, 35˚C above room temperature. Use copper conductors with a minimum size of #14 awg.
Refer to the wiring diagram supplied with the boiler/ water heater for proper wiring connections.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 19
GENERAL OPERATION
WARNING: Before proceeding read and fully understand the instructions contained in this manual. Do not attempt to operate this boiler/ water heater if it has not been installed in accordance with the guidelines set forth in this manual. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. Do not interrupt water fl ow through the boiler/ water heater.
En cas de surchauffe ou si l’alimentation en gaz ne s’arrête pas, fermez manuellement le robinet d’arrêt de l’admission de gaz.
Hydronic Heating Boilers
Open the make-up water valve and slowly fi ll the boiler and all of the radiation with water. Ensure that all bleed and drain valves are closed.
Adjust the make-up water pressure regulator so a minimum 12 psig, 82.7 kPa system pressure is maintained at the highest point in the system piping. If a make-up water pump is used adjust to maintain a minimum 12 psig, 82.7 kPa system pressure.
Open the system bleed and drain valves, one at a time, to purge the air trapped in the heating system piping.
With the boiler off, run the system pump for at least 30 minutes and bleed the system piping using the bleed valves. If strainers are used in the system piping, the make-up water valve should be closed and the strainers checked and cleaned.
The system expansion tank should be checked to ensure that the correct water level in the tank is maintained. The tank should be less than half full of water with the system full and adjusted to the correct operating pressure.
Start the boiler as described in the “LIGHTING AND OPERATING INSTRUCTIONS” on the next page. Run the boiler for at least an hour. The system pump(s) and all radiation units must be operated during this time. Ensure that the make-up water valve is open.
Shut the boiler off and open the bleed valves to purge the air trapped in the heating system piping. Close the make-up water valve and check and clean the strainers and make-up water pressure reducing valve.
Open the make-up water valve and adjust the system pressure if necessary. The system should be checked and bled after three days of operation.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 20
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
A. If this appliance is equipped with a continuous
pilot, it must be lit by hand. Follow the lighting
instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the fl oor because some gas is heavier than air and will settle on the fl oor.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualifi ed service technician. Force or attempted repair may re­sult in a fi re or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
LIGHTING INSTRUCTIONS
DANGER: Propane gas may not always be detected by smell. Propane gas is heavier than air and can collect in low areas.
Propane gas can ignite or explode if an ignition source is present and result in death, serious injury and property damage!
FOR YOUR SAFETY:
• Have only qualifi ed licensed professionals install, service and maintain this appliance and your gas system in accordance with all applicable codes.
• Install a nationally listed combustible gas detector(s) in your home.
• If you suspect a leak:
1. Have everyone leave the building immediately.
2. Do not attempt to light any appliance.
3. Do not touch any electrical or electronic switches
in the building.
4. Do not use any phone in the building.
5.
Call your gas supplier from a phone outside of the building.
6. If you cannot reach your gas supplier call the fi re
department.
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Remove control access panel.
4. Push in gas control knob slightly and turn clock wise
to “OFF”,
PRESSURE REGULATOR ADJUSTMENT (UNDER CAP SCREW)
GAS INLET GAS OUTLET
OFF
PILOT
OUTLET PRESS. TAP
ON
GAS CONTROL KNOBRED RESET BUTTON
5. Wait fi ve (5) minutes to clear out any gas. Then smell for gas, including near the fl oor. If you smell gas, STOP! Follow “B” in the safety information above (to the left) on this label. If you do not smell gas, go to the next step.
6. Open the pilot sight door above the main burners.
7. Find pilot – follow metal tube from the gas control. The pilot is between the two burner tubes behind the pilot sight door.
TO TURN OFF GAS TO APPLIANCE
8. Turn knob on gas control counterclockwise
to
“PILOT”.
9.
Push in control knob all the way and hold in. Immediately light the pilot with a match. Continue to hold the control knob in for about one (1) minute after the pilot is lit. Re­lease knob and it will pop back up. Pilot should remain lit. If it goes out, repeat step 4 through 9.
• If knob does not pop up when released, STOP and immediately call your service technician or gas supplier.
• If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call your service technician or gas supplier.
10. Close pilot sight door.
11. Turn gas control knob counterclockwise
to “ON”
12. Replace control access panel.
13. Set thermostat to desired setting.
1. Set the thermostat to lowest setting.
2. Remove control access panel.
3. Push in gas control knob slightly and turn
clockwise
to “OFF”. Do not force.
4. Replace control access panel.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 21
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
A. If this appliance is equipped with an electronic
ignition device, this automatically lights the burner. Do
not try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance
area for gas. Be sure to smell next to the fl oor because some gas is heavier than air and will settle on the fl oor.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not push in or turn by hand, don't try to repair it, call a qualifi ed service technician. Force or attempted repair may re­sult in a fi re or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
OPERATING INSTRUCTIONS
DANGER: Propane gas may not always be detected by smell. Propane gas is heavier than air and can collect in low areas.
Propane gas can ignite or explode if an ignition source is present and result in death, serious injury and property damage!
FOR YOUR SAFETY:
• Have only qualifi ed licensed professionals install,
service and maintain this appliance and your gas system in accordance with all applicable codes.
• Install a nationally listed combustible gas detector(s)
in your home.
• If you suspect a leak:
1. Have everyone leave the building immediately.
2. Do not attempt to light any appliance.
3. Do not touch any electrical or electronic switches
in the building.
4. Do not use any phone in the building.
5.
Call your gas supplier from a phone outside of the building.
6. If you cannot reach your gas supplier call the fi re
department.
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device, which automatically lights the pilot. Do not try to light the pilot by hand!
PRESSURE REGULATOR ADJUSTMENT (UNDER CAP SCREW)
GAS INLET GAS OUTLET
ON
OFF
OUTLET PRESS. TAP
GROUND TERMINALS (2)
GAS CONTROL KNOB
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control access panel.
5. Remove control access panel.
6. Push in gas control knob slightly and turn clockwise to “OFF”.
Wait fi ve (5) minutes to clear out any gas. Then smell for
7.
gas, including near the fl oor. If you smell gas, STOP! Follow “B” in the safety information above (to the left) on this label. If you do not smell gas, go to the next step.
8. Turn the gas control knob counterclockwise to
“ON”.
9. Replace control access panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the instructions
“TO TURN OFF GAS TO APPLIANCE” and call your service technician or gas supplier.
4. Push in gas control knob slightly and turn
clockwise
to “OFF”. Do not force.
5. Replace control access panel.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 22
CHECKING & ADJUSTMENTS
Pilot Adjustment The pilot burner fl ame should envelope 3/8 in to 1/2 in,
9.5 mm to 12.7 mm of the fl ame sensing probe, Figure
11. To adjust the pilot the following steps must be taken:
1. Remove the pilot gas pressure regulator cap.
2. Turn the pressure regulator adjustment screw clock­wise to decrease the fl ame and counterclockwise to increase it.
3. Replace the pressure regulator adjustment screw cap.
Figure 11 - Pilot Flame Adjustment
RIOM-48
Gas Pressure Adjustment
CAUTION: The maximum inlet gas pressure listed on the rating plate must not be exceeded or damage to the boiler/water heater may occur!
The minimum supply pressure listed on the rating plate is for input adjustment.
PROPANE GAS: A manifold pressure of 11 in, 279 mm W.C. must be maintained for proper operation of the boiler. If the manifold pressure is off by more than 5% adjust it according to steps 1 through 4.
Input Rate, Natural Gas
Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 2000 ft, 610 m. At elevations above 2000 ft, 610 m, input ratings should be reduced by 4% for each additional 1000 ft, 305 m.
Check the input rate as follows:
1. Turn off all other gas appliances that use the same gas meter as the boiler/water heater.
2. Call your gas supplier and ask for the heating value of the gas.
3. Start the boiler/water heater and let it run for 15 minutes.
4. Using the gas meter and a stopwatch, clock the time that it takes to burn 10 ft3, 0.28m3 of gas and divide this time by 10.
5. Insert the heating value and the time, in seconds, into the formula below.
6. Input = (heating value, Btu/hr)(3600)/(time, seconds)
7. If the computed rate deviates by more than 5% from the rated input value of the unit adjust the manifold pressure accordingly. DO NOT adjust the manifold pressure by more than 5%. If a proper rate cannot be maintained without adjusting the manifold pressure beyond the 5% limit, the main burner orifi ces must be replaced. If the input rate is too low, go to the next larger size of main burner orifi ces. If the input rate is too high, go to the next smaller size.
NATURAL GAS: Optimum results are obtained when the boiler/water heater is operated at its full input rating, with
3.8 in to 4.2 in, 96.5 mm to 106.7 mm W.C. of manifold pressure. The manifold pressure should not vary outside this range. The gas valve pressure regulator has been preset at the factory. If adjustment is necessary the following steps must be followed:
1. Attach a 20 in, 508 mm W.C. manometer to the tap
on the manifold.
2. Remove the regulator adjustment screw cap from the gas regulator. On systems that do not use a separate gas regulator, remove the adjustment screw cap from the gas valve body on the valve closest to the gas supply piping.
3. Rotate the regulator adjustment screw clockwise to increase the manifold pressure, counterclockwise to decrease it.
4. Replace the regulator adjustment screw cap and manifold pressure tap plug.
CAUTION: Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur!
CAUTION: Never increase the input to the boiler/ water heater above that for which it is rated. Doing so can cause premature failure of the unit!
CONTROL DESCRIPTION
Low Water Cutoff
If the boiler is to be installed above radiation or if required by other codes or regulations, install a low water cutoff in appropriate piping.
If installed, ensure that the low water cutoff device(s) function properly. Test in accordance with the manufacturer’s instructions included with the device(s).
Boiler Thermostat
If a thermostat is to be used to control the boiler always follow the instructions included with the thermostat. Proper location of the thermostat will ensure effi cient trouble-free operation of the boiler. Mount the thermostat to an inside wall at a height approximately fi ve feet above the fl oor.
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 23
Avoid placing the thermostat in areas that will not provide an accurate measurement of the room temperature. Locating the thermostat behind a door, in an alcove, close to a source of thermal radiation or in a drafty area will cause poor or sporadic heating.
For a thermostat that employs an adjustable heat anticipator, adjust the anticipator to match the current measured in the thermostat circuit. An increased anticipator setting may be necessary if the unit cycles frequently. If the room temperature over-shoots the thermostat setting, reduce the anticipator setting.
Operating Control
The preferred control setting for potable hot water is 130˚F, 54˚C. The operating control should be set to the lowest setting that will satisfy the consumer's needs.
WARNING: Setting the thermostat or operating control too high can result in scalding resulting in severe personal injury!
High Limit (Aquastat)
The high limit is located in the top control area of the boiler/water heater. A remote capillary bulb is run to a well on the outlet side of the supply header.
The water heater high limit should be set a minimum of 20°F, 11°C higher than the operating control. Refer to the HOT WATER SUPPLY section for the proper supply water temperature.
Flow Switch
A fl ow switch is provided in the water outlet piping to prevent the boiler/water heater from firing without adequate water fl ow through the heat exchanger.
MAINTENANCE
WARNING: Disconnect electrical power and close the manual gas shut off valve before performing maintenance or severe personal injury may result!
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, exposure to hazardous materials or loss of life. Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier who must read and follow the supplied instructions before installing, servicing or removing this boiler. This boiler contains crystalline silica materials that have been identifi ed as carcinogenic or possibly carcinogenic to humans when inhaled.
AVERTISSMENT: Une instqallation, un réglage, une réparation ou un entretien non comforme aux normes peut entraîner des dommages matériels, des blessures,exposition à des matiéres dangereuses ou la mort. L’installation et l’entretien doivent être effectués par un installateur ou un service d’entretien qualifi é ou le foumisseur de gaz qui doivent avoir lu les in­structions foumies avant de faire l’installation, l’entretien ou l’enlèvement de la chaudière et les respecter, Cette chaudière contient des matériaux qui ont été identifi és comme étant cancérogènes ou pouvant l’être.
CAUTION: Servicing, inspection and adjustment must be done by a trained technician in accordance with all applicable local and national codes. Improper servicing or adjustment can damage the boiler/water heater!
WARNING: The ceramic combustion chamber contains crystalline silica. Wear a tightly fi tted dust mask when removing the burners or heat exchanger to prevent inhalation of airborn fi bers. Crystalline silica fi bers have been identifi ed as carcinogenic, or possibly carcinogenic when inhaled.
The boiler/water heater should be cleaned and inspected once a year and before each heating season. Make sure that the burners and ignition components are free from dust, soot, dirt, corrosion or other deposits that would impair the boiler’s performance. Refer to page 24 for component identifi cation.
CAUTION: Improper burner servicing can result i premature burner failure voiding the warranty!
Burner Drawer & Burner Removal
1. Close the manual shutoff valves in the gas supply lines and turn off electrical power to the boiler/water heater.
2. Disconnect the gas train from the gas supply piping at the ground joint union.
3. Remove the fl ame roll-out shield.
4. Remove the two screws that attach the burner drawer to the base panel, Figure 12.
5. Disconnect the electrical wires going to the gas valve and burner drawer.
6. On intermittent pilot models disconnect the ignition cable from the ignition module.
7. Pull the burner drawer out until the burners are fully exposed.
8. Inspect each burner for damage or signs of deterio­ration. Use a brush or compressed air to remove any debris from the burner ports.
9. DO NOT install damaged or badly corroded burners, replace them.
10. Reinstall the burner drawer and fl ame roll-out shield following the removal steps in reverse order.
11. Reconnect all electrical wires.
12. Reconnect the gas piping.
n
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 24
Figure 12 - Burner Drawer Assembly
RIOM-55
Combustion Chamber Inspection
1. Remove the burner drawer following the instructions above.
2. Inspect the combustion chamber panels using a mirror and light. If any of the combustion chamber panels are damaged or show signs of deterioration replace them.
3. Replacement of the combustion chamber panels requires that the heat exchanger be removed as outlined below.
4. Reinstall the burner drawer as outlined above.
Heat Exchanger Inspection & Cleaning
1. Close the manual shutoff valve in the gas supply line and turn off electrical power to the boiler/water heater.
2. Close the shut off valves in the inlet and outlet pip­ing. Relieve the system pressure from the boiler/ water heater by carefully opening the drain valve.
3. Disconnect the boiler/water heater from the system piping.
4. Remove the left and right headers and mounting studs.
5. Disconnect the fl ue pipe at the boiler/water heater.
6. Remove the top jacket panel.
7. On indoor units remove the draft hood from the back of the unit. On outdoor units remove the rear jacket panel.
8. Remove the fl ue collector.
9. Carefully lift the heat exchanger out of the unit and thoroughly inspect it.
10. The outside surfaces of the copper tubes should be free of any soot deposits. A slight black smudge is normal with some types of gases. Black soot indicates poor combustion. Green deposits indicate condensation due to low return water temperatures. In either case the heat exchanger must be cleaned thoroughly with water and the problem resolved before the boiler/water heater is returned to service.
11. Replace the cleaned heat exchanger and other components in the reverse order of their removal.
2. A damaged heat exchanger must be replaced and the condition that caused the damage resolved before the boiler/water heater is returned to service.
Vent System
Thoroughly inspect the vent system for any signs of blockage, corrosion or leakage. Immediately replace any unsound vent system piping.
Controls
Use the “GENERAL OPERATION” and “CHECKING AND ADJUSTMENTS” sections of this manual for reference.
1. Check the thermostat or operating controls for proper operation.
2. A fl oat type low water cutoff device must be fl ushed out per the manufacturers’ instructions. The probe on a probe low water cut off must be removed, cleaned and inspected at least once a year. Ensure that the low water cutoffs operate properly. If not, replace them.
3. The fl ow switch contacts must be open when water fl ow is not present.
4. The relief valve should not weep or discharge water at normal system pressure. If it does contact a quali­fi ed service technician to have it inspected. NEVER try to clean or repair the relief valve! If the valve fails to operate properly, have it replaced!
5. The aquastat high limit controls the maximum water temperature in the boiler. It should be set at least 20°F, 11°C above the operator set point. If the water temperature reaches the set temperature before the demand for heat has been met, the aquastat high limit should shut the boiler off. The water temperature should never exceed the maximum set point of 240°F, 116°C. The aquastat high limit cannot be repaired. If it fails to function properly, replace it.
6. Visually check the pilot and main burner fl ames to ensure proper operation, see Figures 11 & 13.
WARNING: Yellow, fl oating fl ames indicate a lack of combustion air. A lifting fl ame indicates too much combustion air. Do not operate the boiler until the problem is solved or severe personal injury or death may occur!
Figure 13 - Main Burner Flames
NORMAL
(HARD FLAME)
LIFTING
(TOO MUCH AIR)
Heat Exchanger Replacement
1. Sagging or distorted heat exchanger tubes are an indication of low water fl ow through the system.
YELLOW TIPPING
(MARGINAL)
YELLOW FLAME (TOO LITTLE AIR)
RIOM-49
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 25
Figure 14 - Replacement Parts
17
11
7
23
18
5
2
37
34
33
32
14
19
25
28
31
30
36
35
21
20
8
3
12
4
9
10
24
4
13
6
27
26
22
1
16
15
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 26
SERVICE AND REPLACEMENT PARTS LIST (MODELS 100-400)
Model Size With Item Quantities Below
Ref # Name of Part Part No.
1 Combustion Chamber Base Assembly 70-1221 1
(Outdoor) 70-1222 1
70-1223 1
70-1224 1
70-1225 1
70-1226 1
70-1227 1
Combustion Chamber Base Assembly 70-1240 1
70-1241 1
70-1242 1
70-1243 1
70-1244 1
70-1245 1
70-1246 1
Combustion Chamber Rear Panel 03-0886 1
03-0887 1
03-0888 1
03-0889 1
03-0890 1
03-0891 1
03-0892 1
Combustion Chamber Front Panel 03-0894 1
03-0895 1
03-0896 1
03-0897 1
03-0898 1
03-0899 1
03-0900 1
2 Rear Refractory Panel 05-0035 1
05-0036 1
05-0037 1
05-0038 1
05-0039 1
05-0040 1
05-0041 1
3 Upper Refractory Channel 03-0884 2 2 2 2 2 2 2
4 Side Refractory Panel, Left & Right 05-0033 2 2 2 2 2 2 2
5 Front Refractory Panel 05-0043 1
05-0044 1
05-0045 1
05-0046 1
05-0047 1
05-0048 1
05-0049 1
Combustion Chamber Side Panel, Left & Right
03-0901 2 2 2 2 2 2 2
100 150 200 250 300
350 400
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 27
Model Size With Item Quantities Below
Ref # Name of Part Part No.
2, 4, 5 Tile Kit
6
70-1328 1
70-1329 1
70-1330 1
70-1331 1
70-1332 1
70-1333 1
70-1335 1
70-1336 1
70-1337 1
70-1338 1
70-1339 1
70-1340 1
70-1356 1
70-1357 1
70-1358 1
70-1359 1
70-1360 1
70-1361 1
70-1363 1
70-1364 1
70-1365 1
70-1366 1
70-1367 1
70-1368 1
7 Flue Collector 70-1256 1
70-1257 1
70-1258 1
70-1259 1
70-1260 1
70-1261 1
70-1262 1
8 Jacket Rear Panel 03-0749 1
03-0750 1
03-0751 1
03-0752 1
03-0753 1
03-0754 1
03-0755 1
Burner Drawer Assembly, NG, Continuous Pilot
Burner Drawer Assembly, LP, Continuous Pilot
Burner Drawer Assembly, NG, Intermittent Pilot
Burner Drawer Assembly, LP, Intermittent Pilot
70-1554K
70-1555K
70-1556K
70-1557K
70-1558K
70-1559K
70-1560K
70-1327 1
70-1334 1
70-1355 1
70-1362 1
100 150 200 250 300
1
1
1
1
1
1
1
350 400
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 28
Model Size With Item Quantities Below
Ref # Name of Part Part No.
9 Draft Hood Assembly 70-1272 1
70-1273 1
70-1274 1
70-1275 1
70-1276 1
70-1277 1
70-1278 1
10 Jacket Rear Panel (Outdoor) 03-0719 1
03-0720 1
03-0721 1
03-0722 1
03-0723 1
03-0724 1
03-0725 1
11 Jacket Left Side Panel 03-0774 1 1 1 1 1 1 1
12 Jacket Right Side Panel 03-0775 1 1 1 1 1 1 1
13 Jacket Front Panel 03-0767 1
03-0768 1
03-0769 1
03-0770 1
03-0771 1
03-0772 1
03-0773 1
14 Jacket Upper Front Panel 03-0757 1
03-0758 1
03-0759 1
03-0760 1
03-0761 1
03-0762 1
03-0763 1
15 Jacket Front Panel (Outdoor) 03-0727 1
03-0728 1
03-0729 1
03-0730 1
03-0731 1
03-0732 1
03-0733 1
16 Outdoor Hood Assembly 70-1213 1
70-1214 1
70-1215 1
70-1216 1
70-1217 1
70-1218 1
70-1219 1
NS Vent Cap & Collar Kit (Outdoor) 09-0121 1
09-0122 1
09-0123 1
09-0124 1 1
09-0125 1
09-0126 1
100 150 200 250 300
350 400
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 29
Model Size With Item Quantities Below
Ref # Name of Part Part No.
17 Jacket Top Panel 03-0741 1
03-0742 1
03-0743 1
03-0744 1
03-0745 1
03-0746 1
03-0747 1
NS Jacket Top Panel (Outdoor) 70-1205 1
70-1206 1
70-1207 1
70-1208 1
70-1209 1
70-1210 1
70-1211 1
18 Spill Switch 14-0226 1 1 1 1
19 Flame Roll-Out Switch 14-0225 1 1 1 1
20 Tube Bundle (Copper) 70-1312 1
70-1313 1
70-1314 1
70-1315 1
70-1316 1
70-1317 1
70-1318 1
Tube Bundle (Cupronickel) 70-1320 1
70-1321 1
70-1322 1
70-1323 1
70-1324 1
70-1325 1
70-1326 1
NS O Ring, Inlet/Outlet & Return Headers 06-0001 16 16 16 16 16 16 16
NS Nut, Inlet/Outlet & Return Headers 57-0492 12 12 12 12 12 12 12
NS Stud, Inlet/Outlet & Return Headers 57-0220 12 12 12 12 12 12 12
21 Inlet/Outlet Header, Cast Iron
Inlet/Outlet Header, Bronze
NS Inlet/Outlet Header, Cast Iron (Mod)
NS Inlet/Outlet Header, Bronze (Mod)
NS Inlet/Outlet Header, Bronze (4 Pass)
NS Inlet/Outlet Header Bronze (Pool Heater)
22 Return Header, Cast Iron
Return Header, Bronze
NS Return Header, Bronze (4 Pass)
23 Inlet/Outlet Cover (Outdoor) 03-0734 1 1 1 1 1 1 1
24 Return Cover (Outdoor) 03-0737 1 1 1 1 1 1 1
NS Heat Exchanger “V” Baffl e 03-0869 7
03-0870 7
03-0871 7
03-0872 7
03-0873 7
03-0874 7
03-0875 7
01-0008S
01-0010S
01-0008M
01-0010M
01-0010-1S
01-0027S
01-0009S
01-0011S
01-0011-1S
100 150 200 250 300
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
1 1 1 1 1 1 1
350 400
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 30
Model Size With Item Quantities Below
Ref # Name of Part Part No.
25 Flame Roll-Out Shield 03-0904 1
03-0905 1
03-0906 1
03-0907 1
03-0908 1
03-0909 1
03-0910 1
26 Burner Tube, Stainless Steel 10-0251 2 3 4 5 6 7 8
27 Manifold 10-0452 1
10-0453 1
10-0454 1
10-0455 1
10-0456 1
10-0457 1
10-0458 1
28 Gas Valve, VR8300A, Con, NG 11-0065 1 1 1
Gas Valve, VR8300A, Con, NG 11-0066 1 1 1 1
Gas Valve, VR8300A, Con, LP 70-1551 1 1 1
Gas Valve, VR8300A, Con, LP 70-1552 1 1 1 1
Gas Valve, VR8304M, Int, NG 11-0056 1 1 1 1 1 1 1
Gas Valve, VR8304M, Int, LP 70-1076 1 1 1 1 1 1 1
Gas Valve, VR8304Q, NG (2 Stage) 11-0084 1 1 1 1 1 1 1
Gas Valve, VR8304Q, LP (2 Stage) 70-1579 1 1 1 1 1 1 1
Gas Valve, 5D5241, NG (Mod) 11-0353 1 1 1 1 1 1 1
NS Ignitor, PSE-NA29, NG 70-9019 1 1 1 1 1 1 1
Ignitor, PSE-NA29, LP 70-9020 1 1 1 1 1 1 1
NS Thermocouple, Q309A 10-0211 1 1 1 1 1 1 1
30 Ignition Module, S8610M 16-0054 1 1 1 1 1 1 1
31 Transformer, 40 VA 15-0002 1 1 1 1 1 1 1
NS High Limit, EMf-1, (SB) 14-0118 1 1 1
High Limit, EMF-5, (SB) 14-0009 1 1 1 1
High Limit, EMf-1, (SW) 14-0116 1 1 1
High Limit, EMf-5, (SW) 14-0008 1 1 1 1
NS Operator, EMf-1, (SB) 14-0118 1 1 1 1 1 1 1
Operator, EMf-23, (SB) 2 Stage 14-0007 1 1 1 1 1 1 1
Operator, EMf-1, (SW) 14-0116 1 1 1 1 1 1 1
Operator, EMf-23, (SW) 2 Stage 14-0010 1 1 1 1 1 1 1
Operator, T6031A (pool heater) 14-0003 1 1 1 1 1 1 1
32 Inlet Thermometer 14-0004 1 1 1 1 1 1 1
Outlet Thermometer 14-0004 1 1 1 1 1 1 1
NS Thermometer Well, 3/8 x 2 13-0102 2 2 2 2 2 2 2
NS High Limit Well, 3/8 x 3 13-0104 2 2 2 2 2 2 2
33 High Limit/Operator Knob 14-0120 1 1 1 1 1 1 1
34 98145.45189 40-0052 1 1 1 1 1 1 1
35 Relay, 24V AC 15-0113 1 1 1 1 1 1 1
36 Terminal Block 2P 48-0151 1 1 1 1 1 1 1
Terminal Block 4P 48-0152 1 1 1 1 1 1 1
Terminal Block 8P 48-0154 1 1 1 1 1 1 1
NS Pressure Relief Valve 30# 13-0004 1 1 1 1 1 1 1
NS Pressure Relief Valve 125# 30-0364 1 1 1 1 1 1 1
NS Flow Switch 14-0203 1 1 1 1 1 1 1
NS Flow Switch (Outdoor) 14-0205 1 1 1 1 1
100 150 200 250 300
350 400
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 31
OPTIONS
Model Size With Item Quantities Below
Ref # Name of Part Part No.
NS Flow Switch (Potter) 14-0201 1 1 1 1 1 1 1
NS Flow Switch (Potter Outdoor) 14-0202 1 1 1 1 1 1 1
NS Tridicator 30 - 60 psi 13-0308 1 1 1 1 1 1 1
NS Tridicator 75 - 160 psi 13-0305 1 1 1 1 1 1 1
37 On/Off Switch 48-0010 1 1 1 1 1 1 1
NS Orifi ce, #30, NG 10-0035 2 3 4 5 6 7 8
Orifi ce, #31 (2,000’ - 3,999’), NG 10-0036 2 3 4 5 6 7 8
Orifi ce, #37 (4,000’ - 5,999’), NG 10-0037 2 3 4 5 6 7 8
Orifi ce, #43 (6,000’ - 7,999’), NG 10-0043 2 3 4 5 6 7 8
Orifi ce, #47, LP 10-0038 2 3 4 5 6 7 8
Orifi ce, #49 (2,000’ - 3,999’), LP 10-0040 2 3 4 5 6 7 8
Orifi ce, #50 (4,000’ - 5,999’), LP 10-0041 2 3 4 5 6 7 8
Orifi ce, #51 (6,000’ - 7,999’), LP 10-0042 2 3 4 5 6 7 8
NS Stainless Steel Wipes 66-0050 1 1 1 1 1 1 1
NS Rating Plate 82-0054 1 1 1 1 1 1 1
NS Paint 66-0013 1 1 1 1 1 1 1
NS Induced Draft Kit, HS1
Induced Draft Kit, HS2
NS Vent Termination Hood 4” 09-0134 1 1 1 1
Vent Termination Hood 6” 09-0112 1 1 1
NS Vent Damper 5” 09-0007 1
Vent Damper 6” 09-0008 1
Vent Damper 7” 09-0009 1
Vent Damper 8” 09-0010 1 1
Vent Damper 9” 09-0012 1
Vent Damper 10” 09-0011 1
NS Combustible Floor Pan 70-1248 1
70-1249 1
70-1250 1
70-1251 1
70-1252 1
70-1253 1
70-1254 1
12-0009BK
12-0010DK
100 150 200 250 300
1 1 1 1
1 1 1
350 400
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONSPage 32
MACODE-3
NOTICE!
Commonwealth of Massachusetts
Installation Requirements
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above fi nished grade, in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfi ed:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfi tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl
space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent fl oor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of
installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certifi ed.
3. SIGNAGE. A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
WARNING: Improper venting can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 33
MACODE-3
NOTICE!
Commonwealth of Massachusetts
Installation Requirements
In the Commonwealth of Massachusetts, the installation must be performed by a licensed plumber or gas fi tter.
(b) Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identifi es “special venting systems”, the following requirements shall be satisfi ed by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
WARNING: Improper venting can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
LIMITED WARRANTY
Boilers/Water Heaters
Industrial, Commercial and Other Non-Residential Use
The “Manufacturer” warrants to the original owner at the original installation site that the heat exchanger of the Industrial, Commercial, and other Non-Residential Use Boiler (the “Product”) will be free from defects in material or workmanship for ten (10) years from the date of installation. Additional twenty one (21) year thermal shock warranty on heat exchanger. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective. All other RBI supplied Boiler/Water Heater parts are warranted against defects in material and workmanship for one (1) year from date of installation or 18 months from date of shipment from RBI.
The “Manufacturer” warrants to the original owner at the original installation site that the heat exchanger of the Industrial, Commercial, and other Non-Residential Use Water Heater (the “Product”) will be free from defects in material or workmanship for fi ve (5) years from the date of installation. Additional twenty one (21) year thermal warranty on heat exchanger. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective. All other RBI supplied Boiler/Water Heater parts are warranted against defects in
material and workmanship for one (1) year from date of installation or 18 months from date of shipment from RBI.
This limited warranty does not apply: (a) if the Product has been subjected to misuse or neglect, has been accidentally or intentionally damaged, has
not been installed, maintained or operated in accordance with the furnished written instructions, or has been altered or modifi ed in any way.
These include but not limited to:
• Excessive water hardness causing a lime build-up in the heat exchanger tubes is not a fault of the equipment and is not covered under the manufacturer’s warranty.
• Excessive pitting and erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer’s warranty. (See Installation Instructions for proper pump performance.)
• Chemical corrosion, no corrosive chemical (freon, dry cleaning chemicals, degreasing liquids, chlorine or any chemicals that produce hydrochloric acid) can be present in the boiler room as it rapidly destroys the heating equipment and voids the warranty.
• All copper fi n boilers should not operate with a return water temperature less than 110°F, 43°C atmospheric combustion, 125°F, 52°C fan assist combustion. If a lower temperature is required, an external bypass should be installed to prevent condensation. The manufacturer’s warranty does not cover damage done by condensation.
(b) to any expenses, including labor or material, incurred during removal or reinstallation of the Product or
parts thereof.
(c) to damage as a result of settlement, distortion, collapse, or cracking of any foundation area, beams or pipes
surrounding the Product.
(d) to any workmanship of any installer of the Product; or to Products installed outside the continental United
States or Canada.
This limited warranty is conditional upon: (a) shipment, to the Manufacturer, of that part of the Product thought to be defective. Goods can only be returned
with prior written approval from the Manufacturer. All returns must be freight prepaid.
(b) determination in the reasonable opinion of the Manufacturer that there exists a defect in material or
workmanship.
Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY EACH JURISDICTION.
260 North Elm Street 7555 Tranmere Drive Westfi eld, MA 01085 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
www.rbiwaterheaters.com
Mississauga, Ontario L5S 1L4
SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 35
260 North Elm Street 7555 Tranmere Drive Westfi eld, MA 01085  Mississauga, Ontario L5S 1L4 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
Loading...