RBI Series 8800, Series 8900 Installation And Operation Manual

Page 1
CIOM-3
42-9134 Rev. 4
SERIES 8800 & 8900 FINNED COPPER
GAS BOILERS & WATER HEATERS
INSTALLATION & OPERATION MANUAL
MEA#117-96-E
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 160 PSI WATER.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
260 North Elm Street 1300 Midway Boulevard Westfield, MA 01085 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
Page 2
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 2
AVERTISSMENT. Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
CONTENTS
Before Your Start ................................................ page 2
Ratings & Capacities ..........................................page 3
Location.............................................................. page 3
Combustion Air & Ventilation ..............................page 3
Chimney & Vent Pipe Connections ....................page 4
Common Vent Systems ......................................page 5
Heating System Piping .......................................page 6
Domestic Water Supply Piping .........................page 11
Gas Supply Piping............................................ page 13
Electrical Wiring ...............................................page 14
Operation ......................................................... page 14
Lighting Instructions .........................................page 15
Checking & Adjustment ....................................page 16
Maintenance..................................................... page 17
Repair Parts, 8900 ...........................................page 19
Repair Parts, 8900 ...........................................page 25
BEFORE YOU START
This manual covers the application, installation, operation and maintenance of a Series 8800 and 8900 finned copper heating boiler/water heater.
To obtain the safe, dependable, efficient operation and long life for which this heating boiler/water heater was designed, these instructions must be read, understood and followed.
The Series 8800 and 8900 finned copper heating boiler/ water heaters have been design certified by A.G.A and CGA for use with natural and propane gas under the latest revision of ANSI-Z21.10.3/CSA 4.3, Gas Water Heaters, ANSI-Z21.13/CSA 4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers and CGA 3.3, Industrial and Commercial Gas-Designed Atmospherically-Fired Vertical Flue Boilers & Hot Water Supply Boilers. Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160 psi in accordance with Section IV of the A.S.M.E. Boiler and Pressure Vessel Code.
All aspects of the boiler/water heater installation must conform to the requirements of the authority having jurisdiction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest revision. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the requirements of CAN/CGA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the service organization for future reference.
Direct all questions to your RBI Water Heaters distributor or contact the RBI Customer Service Department, 260 North Elm Street, Westfield, MA 01085. Always include the model and serial numbers from the rating plate of the boiler/water heater in question.
Page 3
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 3
RATINGS & CAPACITIES
Before undertaking the installation of the Series 8800 and 8900 boiler/water heater check the rating plate to ensure that the unit has been sized properly for the job. The “Net I=B=R Ratings” specify the equivalent amount of direct cast iron radiation that the unit can supply under normal conditions. Also ensure that the unit has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1. Locate the boiler/water heater in an area that provides good access to the unit. Servicing may require the removal of jacket panels. Allow the minimum clearances between adjacent construction and the boiler/water heater as listed in Table 1. Accessibility clearances must take precedence over fire protection clearances.
Table 1 - Clearance to Combustibles
8800/8900 Top 24" 610 mm Back 24" 610 mm Left Side 24" 610 mm Right Side 24" 610 mm Front 48" 1220 mm Flue 6" 152 mm
2. An optimum site will be level, central to the piping
system, close to a chimney and have adequate fresh air for combustion. Ensure that the boiler/water heater is level from front to back and from side to side. Use metal shims to level the boiler/water heater. Electrical and electronic components must also be protected from exposure to water during operation and maintenance. in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
3. Ensure that the floor is structurally sound and will
support the weight of the boiler/water heater. Never install a Series 8800 or 8900 boiler/water heater on a concrete floor that contains wires, cables, water pipes or hoses. This boiler/water heater is designed for noncombustible floors only! Never install this boiler/water heater on combustible materials or carpeting even if a non-combustible foundation material is placed over them!
WARNING: Never install a Series 8800 or 8900 boiler/water heater on top of combustible flooring! Failure to comply with this warning may result in a fire causing extensive property damage, severe personal injury or death!
DO NOT
install this boiler/water heater
4. Locate the boiler/water heater in an area that will prevent water damage to adjacent construction should a leak occur or during routine maintenance. If such a location doesn’t exist, a suitable drain pan that’s adequately drained must be installed under the unit. The combustion air to the unit.
5.
DO NOT
that would restrict the introduction of combustion air into the unit or subject it to a negative pressure.
6.
NEVER
that would subject it to temperatures at or near freezing.
WARNING: Never store combustible materials, gasoline or any product containing flammable vapors or liquids in the vicinity of the boiler/water heater. Failure to comply with this warning can result in an explosion or fire causing extensive property damage, severe personal injury or death!
place this boiler/water heater in a location
pan must not restrict the flow of
place this boiler/water heater in a location
COMBUSTION AIR & VENTILATION
WARNING: This boiler/water heater must be supplied with combustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1 and all applicable local building codes. Canadian installations must comply with CAN/ CGA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. Failure to provide adequate combustion air for this boiler/water heater can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
To operate properly and safely this boiler/water heater requires a continuous supply of air for combustion.
NEVER
CAUTION: Combustion air contaminated with fluorocarbons or other halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. These acids will cause premature failure of the boiler/water heater voiding the warranty!
Buildings will require the installation of a fresh air duct or other means of providing make-up air. Any building utilizing other gas burning appliances, a fireplace, wood stove or any type of exhaust fan must be checked for adequate combustion air when all of these devices are in operation at one time. Sizing of an outside air duct must be done to meet the requirements of all such devices.
store objects on or around the boiler!
Page 4
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 4
WARNING: Never operate the boiler/water heater in an environment subjected to a negative pressure. This can result in excessive levels of carbon monoxide causing severe personal injury or death!
All Air From Inside The Building
If the boiler/water heater is to be located in a confined space minimum clearances of 24" (610 mm) must be maintained between the boiler/water heater and any combustible construction. When installed in a confined space two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have sufficient volume to meet the criteria for an unconfined space. The total air requirements of all gas utilization equipment, fireplaces, wood stoves or any type of exhaust fan must be considered when making this determination. Each opening must have a minimum free area of
2
1 in
/1000 Btu/hr (2200 mm2/kW) based on the total input rating of confined area.Each opening must be no less than 100 square inches (64516 mm2) in size. The upper opening must be within 12 inches (300 mm) of, but not less than 3 inches (80 mm) from, the top of the enclosure. The bottom opening must be within 12 inches (300 mm) of, but not less than 3 inches (80 mm) from, the bottom of the enclosure.
All Air From Outside The Building
When installed in a confined space two permanent openings communicating directly with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 inches (300 mm) of, but not less than 3 inches (80 mm) from, the top of the enclosure. The bottom opening must be within 12 inches (300 mm) of, but not less than 3 inches (80 mm) from, the bottom of the enclosure.
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in2/ 4000 Btu/hr (550 mm2/kW) of the total input rating of all of the equipment in the enclosure.
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in2/2000 Btu/hr (1100 mm2/kW) of the total input rating of all of the equipment in the enclosure.
When ducts are used, they must have the same cross­sectional area as the free area of the opening to which they connect.
ALL
gas utilization equipment in the
When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration must be given to the blockage effects of louvers, grills and screens. Screens must have a minimum mesh size of 1/4" (6.4mm). If the free area through a louver or grill is not known ducts should be sized per Table 2 below.
Table 2 - Make-up Air Duct Sizing
Required Cross Sectional Duct Area in2 (cm2)
Input 1/4" (6.4 mm) Metal Wooden
(MBH) Wire Screen Louvers Louvers
420 105 (677) 140 (903) 420 (2710) 530 133 (858) 177 (1142) 530 (3419) 630 158 (1019) 210 (1355) 630 (4064) 735 184 (1187) 245 (1581) 735 (4742) 840 210 (1355) 280 (1806) 840 (5419) 950 238 (1535) 317 (2032) 950 (6129) 1050 263 (1697) 350 (2258) 1050 (6774) 1160 290 (1871) 387 (2497) 1160 (7484) 1260 315 (2032) 420 (2710) 1260 (8129) 1370 343 (2213) 457 (2948) 1370 (8839) 1470 368 (2374) 490 (3161) 1470 (9484) 1580 395 (2548) 527 (3400) 1580 (10,194) 1685 421 (2716) 562 (3626) 1685 (10,871) 1790 448 (2890) 597 (3852) 1790 (11,548) 1900 475 (3065) 633 (4084) 1900 (12,258) 2000 500 (3226) 667 (4303) 2000 (12,903) 2400 600 (3871) 800 (5161) 2400 (15,483) 2800 700 (4516) 933 (6019) 2800 (18,064) 3200 800 (5161) 1067 (6884) 3200 (20,645) 3600 900 (5806) 1200 (7742) 3600 (23,226) 4000 1000 (6452) 1333 (8600) 4000 (25,806)
CHIMNEY & VENT PIPE CONNECTIONS
WARNING: The vent installation must be in
accordance with Part 7, Venting of Equipment,
of the National Fuel Gas Code, ANSI Z223.1-
latest revision or applicable provisions of the
local building codes. Canadian installations
must comply with CAN/CGA B149.1 or .2
Installation Code. Improper venting can result in
excessive levels of carbon monoxide which can
result in severe personal injury or death!
Chimney Inspection & Sizing
If this boiler/water heater will be connected to a masonry chimney, a thorough inspection of the chimney must be performed. Ensure that the chimney is clean, properly constructed and properly sized. Table 3 lists the equivalent breeching and flue sizes required for the boiler/water heater.
Page 5
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 5
Table 3 - Equivalent Breeching & Chimney Size
Model Size Model Size
Size in (mm) Size in (mm) 420 10 (254) 1580 18 (457) 530 10 (254) 1685 18 (457)
630 12 (305) 1700 20 (508) 735 14 (356) 1900 20 (508) 840 14 (356) 2000 22 (559) 950 14 (356) 2400 24 (610) 1050 16 (406) 2800 26 (660) 1160 16 (406) 3200 28 (711) 1260 16 (406) 3600 30 (762) 1370 18 (457) 4000 30 (762) 1470 18 (457)
Note: These sizes are based on a 20 foot (6.1m) chimney height.
When more than one appliance is connected to the same chimney flue the flue must be large enough to safely vent the combined output of all the appliances.
WARNING: If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney flue, never connect any other appliances to this flue. Doing so can result in the accumulation of carbon monoxide which can cause severe personal injury or death!
VENT CONNECTIONS
Always use a type B or single wall galvanized metal vent pipe the same diameter as the draft diverter flue collar. Use the shortest, straightest vent system possible for the installation. If horizontal runs exceed 6 feet (1.8 m) they must be supported at 6 foot (1.8 m) intervals with overhead hangers. The vent system should be sloped up toward the chimney at a minimum rate of 1/4 inch/ foot (2 cm/m) and terminate flush with the inside of the chimney flue. Fasten each connection with at least 3 corrosion resistant sheet metal screws.
WARNING: Never modify or alter any part of the boiler’s draft diverter. This includes the removal or alteration of any baffles. Never install a vent pipe of a diameter different than that of the boiler draft hood flue collar. Failure to comply with this warning can result in severe personal injury or death.
Always provide a minimum clearance of 6 inches (152 mm) between type C vent pipe and any combustible materials. Type B1 vent may be used, clearance between it and any combustible material must be as listed.
WARNING: Failure to maintain minimum clearances between vent connectors and any combustible material can result in a fire causing extensive property damage, severe personal injury or death!
COMMON VENT SYSTEMS
If an existing boiler/water heater is removed from a common venting system, the common venting system may then be too large for the proper venting of the remaining appliances connected to it. At the time of removal of an existing boiler/water heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d’évacuation commun et qui fonctionne alors que d’autres appareils toujours raccordés au système d’évacuation ne fonction­nent pas: système d’évacuation
a) Seal any unused openings in the common venting
system.
Sceller toutes les ouvertures non utilisées du sys­tème d’évacuation.
b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d’évacu-ation pour déterminer la grosser et l’inclinaison horizontale qui conviennent et s’assurer que le système est exempt d’obstruction, d’étranglement de fruite, de corrosion et autres défaillances qui pourraient présenter des risques.
Page 6
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 6
c) Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliance
not connected to the common venting system. Turn
on any exhaust fans, such as range hoods and
bathroom exhaust, so they will operate at maximum
speed. Do not operate a summer exhaust fan for a
boiler installation. Close fireplace dampers.
Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l’espace où les appareils toujours
raccordés du système d’évacuation sont installés et
les autres espaces du bâtiment. Mettre en marche
les sécheuses, tous les appareils non raccordés au
système d’évacuation commun et tous les
ventilateurs d’extraction comme les hottes de
cuisinère et les ventilateurs des salles de bain.
S’assurer que ces ventilateurs fonctionnent à la
vitesse maximale. Ne pas faire fonctionner les
ventilateurs d’été. Fermer les registres des
cheminées.
d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so
appliance will operate continuously.
Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat de
façon que l’appareil fonctionne de façon continue.
e) Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame
of a match or candle, or smoke from a cigarette,
cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min
ensuite, déterminer si le coupe-tirage déborde à
l’ouverture de décharge. Utiliser la flamme d’une
allunette ou d’une chandelle ou la fumée d’une
cigarette, d’un cigare ou d’une pipe.
f) After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance to their
previous condition of use.
Une fois qu’il a été d éterminé, selon la métode
indiquée ci-dessus, que chaque appareil raccordé
au système d’évacuation est mis à l’air libre de façor
adéquate. Remettre les portes et les fenêtres, les
ventilateurs, les registres de cheminées et les
appareils au gaz à leur position originale.
g) Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 in the National Fuel Gas Code, ANSI Z223.1
Tout mauvais fonctionnement du systéme d’évacuation commun devrait étré corrigé de façor que l’installation soit conforme au National Fue Gas Code, ANSI Z223.1 et (ou) aux codes d’installation CAN/CGA-B149. Si la grosseur d’une section du système d’ évacuation doit étré modifiée, le système devrait étré modifié pour.
GENERAL PIPING REQUIREMENTS
CAUTION: Improper piping of this boiler/water heater will void the manufacturer’s warranty and can cause boiler failure resulting in flooding and extensive property damage! Excessive water hardness causing lime build-up in the copper heat exchanger tubes is manufacturer’s warranty, see Table 5. Excessive pitting and erosion of the internal surface of the copper heat exchanger tubes is the manufacturer’s warranty if the result of high water flow rates, see Table 5. Return water temperatures below 115°F will result in heat exchanger damage from excessive condensation voiding the manufacturer’s warranty, see Primary/ Secondary Piping below.
Shut off valves and unions should be installed at the inlet and outlet connections of the boiler/hot water heater to provide for isolation of the unit should servicing be necessary.
Relief Valve
Install the pressure relief valve in the 3/4" NPT opening on the outlet side of the inlet/outlet header. On units where the relief valve is larger than 3/4" NPT, install the relief valve in the supply piping adjacent to the header. Pipe the discharge of the pressure relief valve to prevent scalding in the event of a discharge, see Figure 1. The discharge piping must be sized the same as the pressure relief valve outlet and installed to allow complete drainage of both the relief valve and the discharge piping.
WARNING: Never install any type of valve between the boiler/water heater and the relief valve or an explosion causing extensive property damage, severe personal injury or death may occur!
NOT
covered under the
NOT
covered under
Page 7
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 7
Flow Switch
The flow switch supplied with the boiler/water heater must be wired to the terminal strip in the junction box to prevent the boiler from firing unless there’s adequate water flow through the unit. The flow switch must be installed in the supply piping adjacent to the boiler outlet connection.
CAUTION: Failure to properly install the flow switch may result in damage to the boiler/water heater heat exchanger voiding the warranty!
HEATING SYSTEM PIPING
General Piping Requirements
All heating system piping must be installed by a qualified technician in accordance with the latest revision of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV, and ANSI/ASME CSD-1, Standard for Controls and Safety Devices for Automatically Fired Boilers. All applicable local codes and ordinances must also be followed. A minimum clearance of 1" must be maintained between heating system pipes and all combustible construction. All heating system piping must be supported by suitable hangers not the boiler. The thermal expansion of the system must be considered when supporting the system. A minimum system pressure of 12 psig must be maintained.
Heating Boiler Piping Connections
The supply and return connections should be sized to suit the system, see Table 4.
Table 4 - Supply & Return Pipe Sizing
Boiler Model Supply Size (in) Return Size (in) 8900 21/2" NPT 21/2" NPT 8800 3" Victaulic 3" Victaulic *Models 420-950 may have 21/2” x 2” reducing fitting installed.
Pump Requirements
This low mass boiler requires a continuous minimum water flow for proper operation. The system pump must be sized to overcome the head loss of the boiler and the heating system in order to achieve the required temperature rise. Table 5 provides the heat exchanger pressure drop and temperature rise figures. The
temperature rise across the boiler must never exceed 30°F (17°C). The pump should be wired to run
continuously unless the optional pump delay is installed. The pump delay turns the pump on each time the burners fire and runs the pump for 100 seconds after the call for heat is satisfied.
CAUTION: A temperature rise outside of the range listed in Table 5 indicates that the flow rate through the heat exchanger is incorrect which will damage the heat exchanger voiding the warranty! The maximum allowable flow rate through an 8900 boiler is 100 GPM, 200 GPM for an 8800. If higher flow rates are required the optional Cupro-Nickel heat exchanger should be considered.
Low Water Cutoff
If a boiler is installed above any radiation elements it must be fitted with a low water cutoff device.
Expansion Tank
An expansion tank or other means to control thermal expansion must be installed in the heating system. An expansion tank must be installed close to the boiler on the suction side of the pump.
Primary/Secondary Piping
Boilers connected to heating systems using zone valves, zone pumps, or systems that have excessive flow rates or return water temperatures less than 110 °F (43°C) must be isolated from these systems to protect the boiler.
Variable Water Flows
Figure 1 shows a typical primary/secondary piping system. A dedicated pump is used to maintain a constant water flow through the boiler. This secondary pump is sized to overcome the head loss of the boiler and secondary piping system while supplying the flow rate required to maintain the desired temperature rise across the boiler. The primary pump is sized to provide the required flow to the heating system. The secondary piping connections to the primary system piping must not be more than 12" apart to ensure zero pressure drop in the primary system, see Figure 1.
Low Return Water Temperatures
To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary/secondary piping system with a bypass and bypass valve must be installed, see Figure
2. The bypass and bypass valve must be sized the same as the secondary piping. A balancing valve must also be installed in the supply side of the secondary piping downstream of the bypass. The balancing valve should be adjusted to divert some of the heated discharge water into the return water until the required inlet water temperature is achieved. The primary and secondary pumps should be sized to provide the required flow through each system. The secondary piping connections to the primary system piping must not be more than 12" apart to ensure zero pressure drop in the primary system, see Figure 2.
Page 8
Figure 1 Typical Primary/Secondary Piping System
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 8
Figure 2 Low Temperature Piping
Page 9
Figure 3 Multiple Boiler Piping
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 9
Table 5 - Temperature Rise Table
Heat Exchanger Head Loss & Temperature Rise
20°F
Model
420 530 630 735 840
950 1050 1160 1260 1370 1470 1580 1685 1790 1900 2000 2400 2800 3200 3600 4000
*Flow exceeds recommended maximum rate, use a greater temperature rise or consult factory for applications in this range
GPM l/s P Ft KPa
34.0
42.9
51.0
59.5
68.0
77.0
85.1
94.0
102.1*
111.0*
119.1*
128.0* — — —
164.0
196.8
229.6*
262.4* — —
2.1
2.7
3.2
3.8
4.3
4.9
5.4
5.9
6.4
7.0
7.5
8.1 — — —
10.3
12.4
14.5
16.6 — —
0.6
1.0
1.6
2.5
3.4
4.5
6.1
7.7
9.5
11.7
14.2
17.1 — — —
5.9
9.5
14.2
20.0 — —
1.8
3.0
4.7
7.4
10.1
13.5
18.2
22.9
28.3
35.0
42.4
51.1 — — —
17.5
28.3
42.4
59.9 — —
GPM l/s P Ft KPa GPM l/s P Ft
34.3
40.8
47.6
54.4
61.6
68.1
75.2
81.7
88.8
95.2
102.4*
109.2*
116.0*
123.1*
131.2
157.4
183.6
209.9*
236.1* —
25°F 30°F
2.2
2.6
3.0
3.4
3.9
4.3
4.7
5.2
5.6
6.0
6.5
6.9
7.3
7.9
8.3
9.9
11.6
13.2
14.9 —
0.6
1.0
1.6
2.2
2.9
3.9
4.9
6.0
7.5
9.1
10.9
13.0
15.3
16.3
3.7
6.0
9.1
12.8
17.6 —
1.9
3.0
4.7
6.5
8.6
11.6
14.6
18.1
22.4
27.1
32.7
38.8
45.6
48.7
11.2
18.1
27.1
38.3
52.5 —
— —
34.0
39.0
45.3
51.3
56.7
62.7
68.1
74.0
79.4
85.3
91.0
96.6
102.6*
109.3
131.2
153.1
174.9
196.8
218.6*
— —
2.1
2.5
2.9
3.2
3.6
4.0
4.3
4.7
5.0
5.4
5.7
6.1
6.5
6.9
8.3
9.7
11.0
12.4
13.8
— —
0.7
1.1
1.5
2.0
2.7
3.4
4.2
5.2
6.3
7.6
9.0
10.6
11.3
2.6
4.2
6.3
8.9
12.2
15.1
KPa
— —
2.1
2.2
4.5
6.0
8.1
10.2
12.6
15.6
18.9
22.8
30.6
32.4
33.9
7.8
12.6
18.8
26.5
36.5
45.1
Page 10
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 10
Multiple Boiler Systems
Systems using multiple boilers can also be installed using a primary/secondary manifold system, Figure 3.
Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler. Appropriate valves must be used to prevent the chilled water from entering the boiler, see Figure 4.
Figure 4 - Chilled Medium Piping
FOR HEATING: VALVES “H” OPEN, VALVES “C” CLOSED.
FOR COOLING: VALVES “H” CLOSED, VALVES “C” OPEN.
EXP. TANK
RELIEF
VALVE
NOTE
VENT
PUMP
ROOM
UNIT
H
C
DRAIN
DOMESTIC WATER SUPPLY PIPING
CAUTION: Proper controls must be used to prevent water supplied for domestic use from exceeding 130°F (54°C) or a scald injury will occur! When higher water temperatures are required for appliances such as a dishwasher, a mixing valve or some other tempering means must be installed. Households with small children may require water temperatures less than 120 °F (49°C). Local codes must be complied with!
General Piping Requirements
Ensure that the water heater is equipped with bronze headers. Piping and components connected to the water heater must be suitable for use with potable water. The water heater must not be connected to any heating system piping or components previously used with a non-potable water heating appliance. Toxic chemicals, such as those used for boiler treatment, are not to be introduced into any potable water used for space heating. If a hot water storage tank is used in the system it must be equipped with a temperature and pressure relief valve that complies with ANSI Z21.22 or CAN-4.4 and CAN-4.6.
FILL
VALVE
C
H
DRAIN
BOILER
CHILLER
When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device, the piping system must be equipped with flow­control valves or some other automatic means of preventing gravity circulation of the boiler water during the cooling cycle.
NOTE: The storage tank must be located as close to the water heater as possible to prevent excessive head loss which will reduce flow.
Water Chemistry
The required temperature rise across the water heater is based on water having a hardness between 8 and 18 grains per gallon with a level of dissolved solids not exceeding 350 ppm. Water having a hardness less than 8 grains can cause excessive corrosion of the heat exchanger. Water that has a hardness greater than 18 grains per gallon and/or a level of dissolved solids exceeding 350 ppm will require a recalculation of the pump size and temperature rise. A Cupro-Nickel heat exchanger may also be required. The manufacturer should be consulted when these water conditions are encountered.
Page 11
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 11
Expansion Tank
An expansion tank or other means to control thermal expansion must be installed in the water heating system if back flow prevention devices are installed.
Pump Requirements
This low-mass water heater requires a continuous mini­mum water flow for proper operation. The factory recommended circulating pump has been sized to overcome the head loss of the water heater plus a 30 foot piping loop under normal water conditions.
Table 5 provides the heat exchanger pressure drop chart and temperature rise table. The temperature
rise across the water heater must never exceed 30°F (17 °C).
CAUTION: The pump should be wired to run continuously unless the optional pump delay is installed. If the pump delay is used a tank-mounted aquastat must be wired to the remote operator terminals in the control box and adjusted so it acts as the primary operator.
Cold Water Supply
The cold water supply must be piped to the water heaters outlet piping between the water heater and the hot water storage tank. This will prevent untempered water from entering the water heater, see the TEMPERATURE RISE CONTROL section below. A typical water heating system is show in Figure 5.
Temperature Rise Control
Water returned to the water heater inlet must not be less than 110°F (43°C) or excessive condensation of the products of combustion will damage the water heater voiding the warranty. The method outlined below can be employed to prevent this condition from occurring.
IMPORTANT: A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the flow rate through the heat exchanger. Thermometers are installed on both the inlet and outlet of the water heater for determining the temperature rise through the unit. The proper velocity through the water heater must be maintained in accordance with Table 5 for efficient operation and long life. If the temperature rise through the water heater is lower than recommended the water velocity is too high. Premature erosion of the heat exchanger will occur. Conversely, if the temperature rise is higher than recommended in Table 5 the flow rate is too low. Scaling and softening of the heat exchanger will occur.
Thermostatic Mixing Valve
Water Above 140°F (60°C) can be stored at temper­atures above 140°F (60 °C) provided that a thermo­statically controlled mixing valve is used to temper the hot water to an acceptable temperature before it’s supplied for domestic use. The mixing valve set to prevent a scald injury from occurring, see the caution against scalding above. Storage of water for domestic use above 140°F (60°C) will provide an increased quantity of tempered water and help prevent the growth of water born bacteria.
MUST
be
Page 12
Figure 5 Typical Water Heating Piping
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 12
Figure 6 Multiple Water Heating Piping
Page 13
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 13
GAS SUPPLY PIPING
WARNING: Check the boiler/water heater rating plate to make sure that the boiler/water heater is for the type of gas that will be used. If it isn’t, do not connect the boiler/water heater to the gas supply. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
The Series 8800 and 8900 come from the factory ready to be piped to the gas supply. If for any reason the boiler/ water heater is not for the type of gas available at the installation site, call the nearest RBI Water Heaters representative to resolve the problem.
Table 6 should be used to ensure that the gas supply piping is sized properly. If more than one appliance is supplied by the same supply pipe, the piping must be sized based on the maximum possible demand. Do not neglect the pressure drop due to pipe fittings. Table 6 should be used in conjunction with Table 7 to ensure that the gas supply piping has the capacity to meet the demand.
Figure 7 depicts the proper way to connect the boiler/ water heater to the gas supply piping. Provide a sediment trap at the bottom of the vertical section of the gas supply pipe upstream of the gas controls.
Table 6 - Gas Pipe Capacity
Maximum pipe capacity in ft3/hr based on 0.60 specific gravity gas at a pressure of 0.5 psig or less and a 0.3" WC pressure drop.
Nominal Iron Pipe Size, (in)
1" 1 1/4" 1 1/2"
2" 2 1/2"
3"
4"
Note: Multiply the gas volume by 0.62 for propane flow capacity in ft3/hr.
Multiply the propane flow capacity by 2500 Btu/ft3 to determine the propane Btu/hr capacity for a given pipe size and length.
10
520 1050 1600 3050 4800 8500 17,500
20
350 730 1100 2100 3300 5900 12,000
Table 7- Equivalent Pipe Length Chart
Nominal Iron Pipe Size, (in)
1" 1 1/4" 1 1/2"
2" 2 1/2"
3"
4"
Notes: 1. For flow through branch.
2. for flow at full open.
90°
Elbow
2.6
3.5
4.0
5.2
6.2
7.7
7.7
Pipe length in feet
30
40
50
60
Maximum gas volume of pipe, (ft3/hr)
285
245
215
195
590
500
440
400
890
760
670
1650
1450
2700
2300
4700
4100
9700
8300
Type of pipe fitting
1
Te e
Equivalent of pipe length (ft)
5.2
6.9
8.0
10.3
12.3
15.3
15.3
1270 2000 3600 7400
Valve
Gate
0.6
0.8
0.9
1.2
1.4
1.8
1.8
610 1150 1850 3250 6800
2
Cock
80
170
350 530 990 1600 2800 5800
Gas
1.5
1.9
2.3
3.0
3.7
4.5
4.5
100
150
150
120
305
250
460
380
870
710
1400
1130
2500
2000
5100
4100
3
A ground joint union should be installed between the boiler gas controls and the supply piping. Each of these items are needed to ensure long life and ease of servicing. Always use a pipe sealant that is suitable for use with LP gas.
Figure 7 - Gas Supply Piping
TO GAS SUPPLY
GROUND JOINT UNION
SEDIMENT TRAP & DRIP LEG ( TO EXTEND TO FLOOR )
MANUAL SHUTOFF VALVE
TO GAS CONTROL(S)
CAUTION: Always use a wrench on the gas valve body when making gas connections to it. Never over-tighten the piping entering the gas valve body or gas valve failure may result!
When applicable, provisions for vent, bleed and gas relief lines must be made in accordance with the latest revision of ANSI Z223.1.
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler. All gas connections
MUST
be leak tested
before putting the boiler into operation.
WARNING: Never use an open flame to test for gas leaks. Always use an approved leak detection method. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
Whenever the gas supply piping is pressure tested the boiler/water heater gas controls must be protected. If the test pressure is equal to, or less than 1/2 psig (3.5 kPa) isolate the boiler/water heater by closing its manual shut off valve, see Figure 16. If the test pressure is greater than, or equal to 1/2 psig (3.5 kPa), disconnect the boiler/water heater and its individual shut-off valve.
Page 14
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 14
ELECTRICAL WIRING
Electrical Power Connections
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation! Verify proper operation after servicing!
ATTENTION. Au moment de l’entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement inadéquat et dangereux. S’assurer que l’appareil fonctionne adéquatement une fois l’entretirn terminé.
The electrical connections to this boiler/water heater must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI /NFPA-70. Installation should also conform with CSA C22.1 Canadian Electrical Code Part I if installed in Canada. Install a separate 120 volt 15 amp circuit for the boiler/water heater. A shut-off switch should be located at the boiler/water heater. The boiler/ water heater must be grounded in accordance with the authority having jurisdiction, or if none, the latest revision of the National Electrical Code, ANSI/NFPA-70.
Line voltage field wiring of any controls or other devices must conform to the temperature limitation of type T wire at 95°F(35°C) above room temperature. Use copper conductors with a minimum size of #14 awg.
Refer to the wiring diagram supplied with the boiler/ water heater for proper wiring connections.
Hydronic Heating Boilers
Open the make-up water valve and slowly fill the boiler and all of the radiation with water. Ensure that all bleed and drain valves are closed.
Adjust the make-up water pressure regulator so a minimum 12 psig system pressure is maintained at the highest point in the system piping. If a make-up water pump is used adjust it as stated above.
Open the system bleed and drain valves, one at a time, to purge the air trapped in the heating system piping.
With the boiler off, run the system pump for at least 30 minutes and bleed the system piping using the bleed valves. If strainers are used in the system piping the make-up water valve should be closed and the strainers checked and cleaned.
The system expansion tank should be checked to ensure that the correct water level in the tank is maintained. The tank should less than half full of water with the system full and adjusted to the correct operating pressure.
Start the boiler as described in the LIGHTING INSTRUCTIONS below. Run the boiler for at least an hour. The system pump(s) and all radiation unit must be operated during this time. Ensure that the make-up water valve is open.
Shut the boiler off and open the bleed valves to purge the air trapped in the heating system piping. Close the make-up water valve and check and clean the strainers and make-up water pressure reducing valve.
BOILER/WATER HEATER OPERATION
WARNING: Before proceeding read and fully understand the instructions contained in this manual. Do not attempt to operate this boiler/ water heater if it has not been installed in accordance with the guidelines set forth in this manual. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. Do Not interrupt water flow through the boiler/ water heater.
En cas de surchauffe ou si lalimentation en gaz ne sarrête pas, fermez manuellement le robinet darrêt de ladmission de gaz.
Open the make-up water valve and adjust the system pressure if necessary.
The system should be checked and bled after three day of operation.
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
POUR VOTRE SÉCURITÉ LISEZ AVANT DE METTRE EN MARCHE
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do the pilot by hand.
Cet appareil est muni dun dispositif dallumage qui allume automatiquement la veilleuse. Ne tentez pas dallumer la veilleuse manuellement.
not
try to light
Page 15
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 15
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
What To Do If You Smell Gas
Do not try to light any appliance.
Do not tough any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbors phone. Follow the gas suppliers instructions.
If you cannot reach your gas supplier, call the fire department.
AVANT DE FAIRE FONCTIONNER, reniflez tout autour de lappareil pour déceler une odeur de gaz. Reniflez près du plancher, car certains gaz sont plus lourds que lair et peuvent saccumuler au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
Ne pas tenter dallumer dappareil.
Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
Appelez immédiatement votre fournisseur de gaz
depuis un voisin. Suives les instructions du fournisseur.
Si vous ne pouvez rejoindre le fournisseur, appelez le service de incendies.
C) Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
6. Wait five (5) minutes to clear out any gas. Then small for gas, including near the floor. If you smell gas,
STOP!
above. If you dont smell gas go to next step.
7. Connect a manometer having a minimum capacity of 20" WC to the outlet pressure port of the gas valve. Make sure that the gas supply piping has been purged of air and that all gas joints up to the gas valve have been thoroughly checked for leaks.
8. Open the manual pilot valve.
9. Turn on all electric power to the boiler.
10. Set the operating control or thermostat to the desired setting.
11. The pilot(s) should automatically light. Do not try to light the pilot(s) by hand!
12. With the pilot(s) lit, open the main gas shut-off valve.
13. The burners should light with proper boiler operation.
14. A boiler designed for use with natural gas should have a manifold gas pressure of approximately 4.0" WC. For an LP boiler, the manifold pressure should be 11" WC. To adjust the manifold gas pressure see the
GAS PRESSURE ADJUSTMENT
the
CHECKING AND ADJUSTMENT
15. With the burners in operation, close the manual shutoff valve in the gas supply line. As soon as the main burner flames go out, open the manual shutoff valve. A normal ignition sequence should take place. If the burners fail to light the system will make one more ignition attempt. If the burners have not lit after the last ignition try, the gas valve will close and the system will go into lock out. DO reset the system until the ignition system has been inspected and the problem resolved.
Follow “B” in the safety infomration
instructions in
section.
NOT
attempt to
Nutilisez pas cet appareil sil a été plongé dans leau, même partiellement. Faites inspecter lappareil par un tecnicien qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
CAUTION: To prevent being burned, stand clear of the boiler during ignition and don’t touch any hot metal parts!
Operating Instructions
1.
STOP!
time, the appliance will not operate properly, follow the instructions TO TURN OFF GAS TO APPLIANCE and call your service technician or gas supplier.
2. Set the operating control or thermostat to off or its lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the pilot. Do the pilot by hand.
5. Close the manual main and pilot gas shut-off valves.
Read the safety information above. If, at any
not
try to light
With the burners in operation, interrupt the power to the control circuit by lowering the operating control or thermostat. The main burners should go out. Reset the operating control or thermostat, a normal ignition sequence should follow.
To test the ignition safety shutoff device, close the manual shutoff valve in the gas supply line. Within 5 seconds of main burner flame extinction, the main gas valve solenoid should close with an audible noise.
A sparking noise should be heard while the ignition module tries to relight the pilot. After 15 seconds the module should lockout and the trial for ignition end. After 5 minutes a second trial for ignition should occur. Open the manual shutoff valve in the gas supply line and reset the ignition control system. A normal ignition sequence should take place.
Page 16
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 16
Instructions De Mise En Marche
1. ARRÊTEZ! Lisez les instructions de sécurité sur la portion supérieure de cette étiquette.
2. Réglez le thermostat à la température la plus basse.
3. Coupez l’alimentation électrique de l’appareil.
4. Cet appareil est muni dun dispositif dallumage qui allume automatiquement la veilleuse. Ne tentez pas dallumer la veilleuse manuellement.
5.
Fermer la vanne manuelle darrêt d’alimintation de gaz.
6. Attendre cinq (5) minutes pour laisser échapper tout le gaz. Reniflez tout autour de lappareil, y compris près du plancher, pour déceler une odeur de gaz. Si vous sentez une odeur de gaz, ARRÊTEZ! Passez à l’étape B des instructions de sécurité sur la portion supérieure de cette étiquette. Sil n’y a pas dodeur de gaz, passez à l’étape suivante.
7.
Ouver la vanne manuelle d’arrêt dalimintation de gaz.
8. Mettez lappareil sous tension.
9. Réglez le thermostat à la température désirée.
10. Si l’appareil ne se met pas en marche, suivez les instructions intitulées «Comment couper l’admission de gaz de l’appareil» et appelez un technicien qualifié ou le fournisseur de gaz.
To Turn Off Gas To Appliance
1. Set the operating control or thermostat to its lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Close the manual main and pilot gas shut-off valves.
COMMENT COUPER L’ADMISSION DE GAZ DE L’APAREIL
1. Réglez le thermostat à la température la plus basse.
2. Coupez lalimentation électrique de l’appareil sil faut procéder à lentretien.
3.
Fermer la vanne manuelle darrêt d’alimintation de gaz.
CHECKING & ADJUSTMENT
Pilot Adjustment
The pilot burner flame should envelope 3/8" to 1/2" of the flame sensing probe, Figure 8. To adjust the pilot the following steps must be taken:
1. Remove the pilot gas pressure regulator cap.
2. Turn the pressure regulator adjustment screw clock­wise to increase the flame and counterclockwise to decrease it.
3. Replace the pressure regulator adjustment screw cap.
Figure 8 - Pilot Flame Adjustment
Gas Pressure Adjustment
CAUTION: The maximum inlet gas pressure listed on the rating plate must not be exceeded or damage to the boiler/water heater may occur!
The minimum supply pressure listed on the rating plate is for input adjustment.
NATURAL GAS: Optimum results are obtained when the boiler/water heater is operated at its full input rating, with
3.8" WC to 4.2" WC of manifold pressure. The manifold pressure should not vary outside this range. The gas valve pressure regulator has been preset at the factory. If adjustment is necessary the following steps must be followed:
1. Attach a 20" manometer to the tap on the manifold.
2. Remove the regulator adjustment screw cap from the gas regulator. On systems that do not use a separate gas regulator, remove the adjustment screw cap from the gas valve body on the valve closest to the gas supply piping.
3. Rotate the regulator adjustment screw clockwise to increase the manifold pressure, counterclockwise to decrease it.
4. Replace the regulator adjustment screw cap and manifold pressure tap plug.
CAUTION: Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur!
PROPANE GAS: A manifold pressure of 11" WC must be maintained for proper operation of the boiler. If the manifold pressure is off by more than 5% adjust it according to steps 1 through 4 above.
Input Rate, Natural Gas
Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 2000 feet. At elevations above 2000 feet, input ratings should be reduced by 4% for each 1000 feet above sea level.
Page 17
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 17
Check the input rate as follows:
1. Turn off all other gas appliances that use the same gas meter as the boiler/water heater.
2. Call your gas supplier and ask for the heating value of the gas.
3. Start the boiler/water heater and let it run for 15 minutes.
4. Using the gas meter and a stopwatch, clock the time that it takes to burn 10 cubic foot of gas and divide this time by 10.
5. Insert the heating value and the time, in seconds, into the formula below.
6. Input = (heating value, Btu/hr)(3600)/(time, seconds)
7. If the computed rate deviates by more than 5% from the rated input value of the unit adjust the manifold pressure accordingly. pressure by more than 5%. If a proper rate cannot be maintained without adjusting the manifold pressure beyond the 5% limit, the main burner orifices must be replaced. If the input rate is too low, go to the next lager size of main burner orifices. If the input rate is too high, go to the next smaller size.
CAUTION: Never increase the input to the boiler/ water heater above that for which it is rated. Doing so can cause premature failure of the unit!
Low Water Cutoff
If installed, ensure that the low water cutoff device(s) function properly. Test in accordance with the manufacturer’s instructions included with the device(s).
Boiler Thermostat
If a thermostat is to be used to control the boiler always follow the instructions included with the thermostat. Proper location of the thermostat will ensure efficient trouble-free operation of the boiler. Mount the thermostat to an inside wall at a height approximately five feet above the floor.
Avoid placing the thermostat in areas that will not provide an accurate measurement of the room temperature. Locating the thermostat behind a door, in an alcove, close to a source of thermal radiation or in a drafty area will cause poor or sporadic heating.
For a thermostat that employs an adjustable heat anticipator, adjust the anticipator to match the current measured in the thermostat circuit. An increased anticipator setting may be necessary if the unit cycles frequently. If the room temperature over-shoots the thermostat setting, reduce the anticipator setting.
DO NOT
adjust the manifold
Water Heater Operation Controls
The operating control on the water heater is set to its lowest setting when the water heater leaves the factory. The preferred control setting for potable hot water is 130°F. The operating control should be set to the lowest setting that will satisfy the consumers needs. The water heater high limit should be set a minimum of 40°F (22°C) higher than the operating control. Refer to the HOT WATER SUPPLY section for the proper supply water temperature.
WARNING: Setting the thermostat or operating control too high can result in scalding resulting in severe personal injury!
BOILER/WATER HEATER MAINTENANCE
WARNING: Disconnect electrical power and close the manual gas shut off valve before performing maintenance or severe personal injury may result!
CAUTION: Servicing, inspection and adjustment must be done by a trained technician in accordance with all applicable local and national codes. Improper servicing or adjustment can damage the boiler /water heater!
The boiler/water heater should be cleaned and inspected once a year, before each heating season. Make sure that the burners and ignition components are free from dust, soot, dirt, corrosion or other deposits that would impair the boilers performance. Refer to pages 19 & 27 for component identification.
Combustion Chamber Inspection
1. Remove the left or right lower jacket end panel, item 5 or 24 (8900) or item 5 or 26 (8800).
2. Remove the upper end refractory brackets and carefully remove the end refractory panel.
3. Inspect the combustion chamber, heat exchanger and burner tray components for sign of corrosion and/or deterioration.
4. Clean or replace components are required.
Burner Drawer & Burner Removal
1. Close the manual shutoff valves in the gas supply lines and turn off electrical power to the boiler/water heater.
2. Disconnect the gas train from the gas supply piping at the ground joint union, Figure 9.
3. Remove the Flame Roll-Out Shield, 8900 only.
4. Remove the two bolts that attach the burner drawer to the base frame.
5. Disconnect the pilot tubing from the solenoid valve and the ignition lead from the ignition control.
Page 18
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 18
6. Pull the burner drawer out until the burners are fully exposed.
7. Inspect each burner for damage or signs of deterioration. Use a brush or compressed air to remove any debris from the burner ports.
8.
DO NOT
install damaged or badly corroded burners,
replace them.
9. Install the burners making sure that they are properly seated in the burner drawer.
10. Replace the Burner Drawer and Flame Roll Out Shield, 8900 only, following the removal steps in reverse order.
Heat Exchanger Inspection & Cleaning
1. Close the shut off valves in the inlet and outlet piping. Relieve the system pressure from the boiler by carefully lifting the relief valve or opening the drain valve.
2. Disconnect the boiler/water heater from the system piping.
3. Remove the left and right headers and mounting studs.
4. Remove the left & right upper and left & right lower jacket end panels, items 5 & 24 (8900) or items 5 & 26 (8800).
5. Remove the left & right front corner trim panels,
8900.
6. Remove the flue collector front panel shown as part of item 19 (8900) or item 21 (8800).
7. Remove the upper front refractory channel assembly and front refractory panels.
8. Slide the heat exchanger out and thoroughly inspect it.
9. The outside surfaces of the copper tubes should be free of any soot deposits, A slight black smudge is normal with some types of gases. Black soot indicates poor combustion. Green deposits indicate condensation due to low return water temperatures. In either case the heat exchanger must be cleaned thoroughly with water and the problem resolved before the boiler/water heater is returned to service.
10. Replace the cleaned heat exchanger and other components in the reverse order of their removal.
Controls
Use the BOILER/WATER HEATER OPERATION and CHECKING AND ADJUSTMENT sections of this manual for reference.
1. Check the thermostat or operating controls for proper operation.
2. A float type low water cutoff device must be flushed out per the manufacturers’ instructions. The probe on a probe low water cut off must be removed, cleaned and inspected at least once a year. Ensure that the low water cutoffs operate properly. In not, replace them.
3. The relief valve should not weep or discharge water at normal system pressure. If it does contact a qualified service technician to have it inspected.
NEVER
try to clean or repair the relief valve! If the
valve fails to operate properly, have it replaced!
4. The aquastat high limit controls the maximum water temperature in the boiler. It is adjustable from 140°F (60C) to 250°F (121°C). If the water temperature reaches the set temperature before the demand for heat has been met, the aquastat high limit should shut the boiler off. The water temperature should never exceed the maximum set point of 250°F (121°C). The aquastat high limit cannot be repaired. If it fails to function properly replace it.
5. Visually check the pilot and main burner flames to ensure proper operation, see Figures 8 & 9.
WARNING: Yellow, floating flames indicate a lack of combustion air. Do not operate the boiler until the problem is solved or severe personal injury or death may occur!
Figure 9 - Main Burner Flames
NORMAL
(HARD FLAME)
LIFTING
(TOO MUCH AIR)
Heat Exchanger Replacement
1. Sagging or distorted heat exchanger tubes are an indication of low water flow through the system.
2. A damaged heat exchanger must be replaced and the condition that caused the damage resolved before the boiler/water heater is returned to service.
Vent System
Thoroughly inspect the vent system for any signs of blockage, corrosion or leakage. Immediately replace any unsound vent system piping.
YELLOW TIPPING
(MARGINAL)
YELLOW FLAME
(TOO LITTLE AIR)
Page 19
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 19
PARTS LIST (MODELS 420-1900)
Series 89
1 - Jacket Lower
Front Panel
2 - Jacket Lower
Rear Panel
3 - Jacket Lower
Rear Corner Post
4 - Jacket Lower
Front Corner Post
5 - Jacket Lower
End Panel
6 - Inlet Outlet
Header 7 - Return Header 8 - Black O-Rings 9 - Stud Bolts
10 - Flange Nuts 11 - V Baffle 12 - Frame Assembly 13 - Main Burner 14 - Union 15 - Firing Valve 16 - Main Gas Valve 17 - A Valve 18 - Refractory 19 - Flue Collector
End
20 - Down Draft
Preventer
21 - Flue Collector
To p
22 - Jacket Upper
Front Panel
23 - Jacket Panel
Anchor Bracket
24 - Jacket Upper End
Panel
25 - Jacket Upper
Front Corner Post
26 - Jacket Upper
Rear Corner Post
27 - Jacket Top Panel 28 - Jacket Upper
Rear Panel
29 - Burner Tray Side 30 - Copper Fin Tube
Page 20
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 20
SERVICE AND REPLACEMENT PARTS LIST (MODELS 420-1900)
Ref # Name of Part
1 Lower Front Jacket Panel 72-0001 1
2 Lower Rear Jacket Panel 72-0001 1
3 Lower Lt Rear Jacket Corner Posts 72-0017 111111111111111
Lower Rt Rear Jacket Corner Posts 72-0017 111111111111111
4 Lower Lt Front Jacket Corner Posts 72-0017 111111111111111
Lower Rt Front Jacket Corner Posts 72-0017 111111111111111 5 Lower Left & Right Jacket End Pnl. 72-0016 222222222222222 6 Inlet/Outlet Header, Cast Iron 01-0001 111111111111111
Inlet/Outlet Header, Bronze 01-0003 111111111111111 7 Return Header, Cast Iron 01-0002 111111111111111
Return Header, Bronze 01-0004 111111111111111 8 O Ring, Headers 06-0001 16 16 16 16 16 16 16 16 16 16 16 16 16 16 16 9 Stud, Headers 57-0223 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
10 Nut, Headers 57-0491 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 11 Heat Exchanger “V” Baffle 03-0244 7
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
72-0002 1 72-0003 1 72-0004 1 72-0005 1 72-0006 1 72-0007 1 72-0008 1 72-0009 1 72-0010 1 72-0011 1 72-0012 1 72-0013 1 72-0014 1 72-0015 1
72-0002 1 72-0003 1 72-0004 1 72-0005 1 72-0006 1 72-0007 1 72-0008 1 72-0009 1 72-0010 1 72-0011 1 72-0012 1 72-0013 1 72-0014 1 72-0015 1
03-0245 7 03-0246 7 03-0247 7 03-0248 7 03-0249 7 03-0250 7 03-0251 7 03-0252 7 03-0253 7 03-0254 7 03-0255 7 03-0256 7 03-0257 7 03-0258 7
Page 21
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 21
Ref # Name of Part
Not Shown
Heat Exchanger Edge Baffle 03-0259 2
12 Base Frame Assembly 70-0192 1
13 Burner Tube, Aluminized Steel Nat 10-0252 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
Burner Tube, Aluminized Steel LP 10-0253 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
Burner Tube, Aluminized w/ Bracket 70-0499 1 11111111111111
Burner Tube, Stainless Steel 10-0254 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
Burner Tube, Stainless w/ Bracket 70-0500 1 11111111111111
14 Union, 1" 53-0054 1 11111
Union, 1 1/4" 53-0055 1111111
Union, 1 1/2" 53-0056 1 1
15 Firing Valve, 1" 11-0456 1 11111
Firing Valve, 1 1/4" 11-0457 1111111
Firing Valve, 1 1/2" 11-0458 1 1
16 Main Gas Valve, HW V88A, 1" 11-0156 1 11111
Main Gas Valve, HW V88A, 1 1/4" 11-0157 1111111
Main Gas Valve, HW V88A, 1 1/2" 11-0158 1 1
Main Gas Valve, V8944B, 1" 11-0171 1 11111
Main Gas Valve, V8944B, 1 1/4" 11-0172 1111111
Main Gas Valve, V8944B, 1 1/2" 11-0173 1 1
17 “A” Valve, 1" 11-0451 1 11111
A Valve, 1 1/4" 11-0452 1111111
A Valve, 1 1/2" 11-0453 1 1
18 End Refractory Panel, Left & Right 05-0001 2 22222222222222 18 Center Refractory Panel 05-0002 2
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
03-0260 2 03-0261 2 03-0262 2 03-0263 2 03-0264 2 03-0265 2 03-0266 2 03-0267 2 03-0268 2 03-0269 2 03-0270 2 03-0271 2 03-0272 2 03-0273 2
70-0193 1 70-0194 1 70-0195 1 70-0196 1 70-0197 1 70-0198 1 70-0199 1 70-0200 1 70-0201 1 70-0202 1 70-0203 1 70-0204 1 70-0205 1 70-0206 1
05-0003 2 05-0004 0002222444666
Page 22
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 22
Ref # Name of Part
Not Shown
Heat Shield 70-0482 1
Burner Spacers 70-0363 1
Upper Front Refractory Channel 70-0177 1
Upper Rear Refractory Channel 70-0162 1
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
70-0483 1 70-0484 1 70-0485 1 70-0486 1 70-0487 1 70-0488 1 70-0489 1 70-0490 1 70-0491 1 70-0492 1 70-0493 1 70-0494 1 70-0495 1 70-0496 1
70-0364 1 70-0365 1 70-0366 1 70-0367 1 70-0368 1 70-0369 1 70-0370 1 70-0371 1 70-0372 1 70-0373 1 70-0374 1 70-0375 1 70-0376 1 70-0377 1
70-0178 1 70-0179 1 70-0180 1 70-0181 1 70-0182 1 70-0183 1 70-0184 1 70-0185 1 70-0186 1 70-0187 1 70-0188 1 70-0189 1 70-0190 1 70-0191 1
70-0163 1 70-0164 1 70-0165 1 70-0166 1 70-0167 1 70-0168 1 70-0169 1 70-0170 1 70-0171 1 70-0172 1 70-0173 1 70-0174 1 70-0175 1 70-0176 1
Page 23
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 23
Ref # Name of Part
18 Corner Refractory Panel 05-0005 4
19 Draft Diverter, Left Side Panel 03-0191 1 11111111111111
Draft Diverter, Right Side Panel 03-0192 1 11111111111111
20 Draft Diverter Down Draft Baffle 03-0193 1 1
21 Draft Diverter Top Panel Assembly 70-0030 1
22 Upper Front Jacket Panel 72-0001 1
23 No Longer Used 24 Upper Left & Right Jacket End Pnl. 72-0016 2 22222222222222 25 Upper Left Front Jacket Corner Post 72-0017 1 11111111111111
Upper Rt Front Jacket Corner Post 72-0017 1 11111111111111
26 Upper Left Rear Jacket Corner Post 72-0017 1 11111111111111
Upper Right Rear Jacket Corner Post 72-0017 1 11111111111111
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
05-0006 4 05-0007 4 05-0008 4 05-0009 4 05-0010 4 05-0011 4 05-0012 4 05-0013 4 05-0014 4 05-0015 4 05-0016 4 05-0017 4
03-0194 1 03-0195 1 1 1 03-0196 1 1 1 03-0197 1111 03-0198 1 1
70-0031 1 70-0032 1 70-0033 1 70-0034 1 70-0035 1 70-0036 1 70-0037 1 70-0038 1 70-0039 1 70-0040 1 70-0041 1 70-0042 1 70-0043 1 70-0044 1
72-0002 1 72-0003 1 72-0004 1 72-0005 1 72-0006 1 72-0007 1 72-0008 1 72-0009 1 72-0010 1 72-0011 1 72-0012 1 72-0013 1 72-0014 1 72-0015 1
Page 24
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 24
Ref # Name of Part
27 Top Jacket Panel 72-0001 1
28 Upper Rear Jacket Panel 72-0001 1
29 Burner Drawer Side Rail Assy, Left 70-0361 1 11111111111111
Burner Drawer Side Rail Assy, Right 70-0362 1 11111111111111
30 Heat Exchanger, SB75 Tubes 70-0132 1
Standard ASME (no headers) 70-0133 1
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
72-0002 1 72-0003 1 72-0004 1 72-0005 1 72-0006 1 72-0007 1 72-0008 1 72-0009 1 72-0010 1 72-0011 1 72-0012 1 72-0013 1 72-0014 1 72-0015 1
72-0002 1 72-0003 1 72-0004 1 72-0005 1 72-0006 1 72-0007 1 72-0008 1 72-0009 1 72-0010 1 72-0011 1 72-0012 1 72-0013 1 72-0014 1 72-0015 1
70-0134 1 70-0135 1 70-0136 1 70-0137 1 70-0138 1 70-0139 1 70-0140 1 70-0141 1 70-0142 1 70-0143 1 70-0144 1 70-0145 1 70-0146 1
Page 25
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 25
Ref # Name of Part
30 Heat Exchanger, SB111 Tubes 70-0147 1
Optional Cupro-Nickel ASME (no headers) 70-0148 1
Not Shown
Not Shown
Not Shown Not Shown Not Shown Not Shown Not Shown Not Shown
Not Shown
Not Shown
Not Shown
Not Shown Not Shown Not Shown Not Shown
Pilot, Natural Gas 10-0104 1 11111111111111
Pilot, LP Gas 70-0477 1 11111111111111
Pilot Orifice, Natural Gas 10-0003 1 11111111111111
Pilot Orifice, LP Gas 10-0002 1 11111111111111
Pilot Valve, 24 V 11-0017 1 11111111111111
Pilot Regulator, RV12LT 11-0041 1 11111111111111
Manual Pilot Valve 11-0031 1 11111111111111
Ignition Module, S8610M 16-0054 1 11111111111111
Transformer, 40 VA 15-0002 1 11111111111111
High Limit, L4008E (US only) 14-0104 1 11111111111111
High Limit, GIP 9869 (CAN only) 14-0117 1 11111111111111
High Limit, L4008E (Boiler) 14-0104 1 11111111111111
High Limit, L4008E-1313 (Water Heaters) 14-0105 1 11111111111111
Operator, L4008A (US only) 14-0102 1 11111111111111
Operator, GIP 9868 (CAN only) 14-0116 1 11111111111111
Operator, L6008A-1242 (Water Heaters) 14-0106 1 11111111111111
Operator, L6008G-1009B (2 Stage) 14-0107 1 11111111111111
Operator, T991E-1018 (Mod) Boilers 14-0108 1 11111111111111
Operator, T991E-1034 (Mod) Water Heaters
Operator, L4008A-1445 Water Heaters 14-0103 1 11111111111111
Orifice, Blank 10-0011 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, Natural Gas, # 29 10-0016 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, Nat Gas, # 31 (2000-4500 ft) 10-0018 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, LP Gas, # 44 10-0031 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orifice, LP Gas, # 46 (2000-4500 ft) 10-0033 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
50# Pressure relief Valve (Boilers) 13-0040 1 1 1
125# Pressure Relief Valves (Water Heaters)
Pressure Gauge (Boilers) 13-0301 1 11111111111111
Thermostat w/ Well 13-0320 1 11111111111111
Flow Switch (Water Heaters) 14-0201 1 11111111111111
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
70-0149 1 70-0150 1 70-0151 1 70-0152 1 70-0153 1 70-0154 1 70-0155 1 70-0156 1 70-0157 1 70-0158 1 70-0159 1 70-0160 1 70-0161 1
14-0110 1 11111111111111
13-0001 1111111 13-0002 11111 13-0009 1 11111111111111
Page 26
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 26
Ref # Name of Part
Not Shown
Not Shown
Not Shown
Not Shown
Natural to LP Conversion Kit 21-0131 1
LP to Natural Conversion Kit 21-0146 1
Natural to LP Conversion Kit 21-0161 1
(2000 to 4500 feet) 21-0162 1
LP to Natural Conversion Kit 21-0176 1
(2000 to 4500 feet) 21-0177 1
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
21-0132 1 21-0133 1 21-0134 1 21-0135 1 21-0136 1 21-0137 1 21-0138 1 21-0139 1 21-0140 1 21-0141 1 21-0142 1 21-0143 1 21-0144 1 21-0145 1
21-0147 1 21-0148 1 21-0149 1 21-0150 1 21-0151 1 21-0152 1 21-0153 1 21-0154 1 21-0155 1 21-0156 1 21-0157 1 21-0158 1 21-0159 1 21-0160 1
21-0163 1 21-0164 1 21-0165 1 21-0166 1 21-0167 1 21-0168 1 21-0169 1 21-0170 1 21-0171 1 21-0172 1 21-0173 1 21-0174 1 21-0175 1
21-0178 1 21-0179 1 21-0180 1 21-0181 1 21-0182 1 21-0183 1 21-0184 1 21-0185 1 21-0186 1 21-0187 1 21-0188 1 21-0189 1 21-0190 1
Page 27
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 27
PARTS LIST (MODELS 2000-4000)
Series 89
1 - Jacket Lower
Front Panel
2 - Jacket Lower
Rear Panel
3 - Jacket Lower
Rear Corner Post
4 - Jacket Lower
Front Corner Post
5 - Jacket Lower
End Panel
6 - Inlet Outlet
Header 7 - Return Header 8 - Copper Fin Tube 9 - Black O-Rings
10 - Stud Bolts 11 - Flange Nuts 12 - V Baffle 13 - Frame Assembly 14 - Main Burner 15 - Union 16 - Firing Valve 17 - Main Gas Valve 18 - A Valve 19 - Burner Drawer
Side
20 - Refractory 21 - Flue Collector
End Panel
22 - Down Draft
Preventer
23 - Flue Collector
To p
24 - Jacket Upper
Front Panel
25 - Jacket Upper
Rear Panel
26 - Jacket Upper End
Panel
27 - Jacket Upper
Rear Corner Post
28 - Jacket Upper
Front Corner Post
29 - Jacket Top Panel 30 - Jacket Top End
Panel
Page 28
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 28
SERVICE AND REPLACEMENT PARTS LIST (MODELS 2000-4000)
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
1 Lower Front Jacket Panely 03-1077 1
03-1078 1 03-1079 1 03-1080 1 03-1081 1 03-1082 1
2 Lower Rear Jacket Panel 03-1071 1
03-1072 1 03-1073 1 03-1074 1 03-1075 1 03-1076 1
3 Lower Rear Corner Jacket Trim Panel, Left 03-1088 111111
Lower Rear Corner Jacket Trim Panel, Right 03-1089 111111
4 Lower Front Corner Jacket Trim Panel, Left 03-1090 111111
Lower Front Corner Jacket Trim Panel, Right 03-1091 111111 5 Lower Jacket End Panel, Left & Right 03-1083 111111 6 Inlet/Outlet Header, Bronze 01-0012 111111 7 Return Header, Bronze 01-0013 111111 8 Heat Exchanger, SB75 Tubes 70-1684 1
70-1685 1 70-1686 1 70-1687 1 70-1688 1 70-1689 1
Not Shown
Not Shown
Not Shown
Heat Exchanger, SB111 Tubes 70-1690 1
70-1691 1 70-1692 1 70-1693 1 70-1694 1 70-1695 1
9 O Ring, Inlet/Outlet & Return Headers 06-0001 32 32 32 32 32 32
10 Stud, Inlet/Outlet & Return Headers 57-0223 24 24 24 24 24 24 11 Nut, Inlet/Outlet & Return Headers 57-0491 24 24 24 24 24 24 12 Heat Exchanger “V” Baffle 03-1147 15
03-1148 15 03-1149 15 03-1150 15 03-1151 15 03-1152 15
13 Base Frame Assembly 70-1708 1
70-1709 1 70-1710 1 70-1711 1 70-1712 1 70-1713 1
14 Burner Tube, Aluminized Steel 10-0256 19 23 27 30 34 38
Burner Tube, Aluminized w/ Bracket 70-1851 111222
Burner Tube, Stainless Steel 10-0258 19 23 27 30 34 38
Burner Tube, Stainless w/ Bracket 70-1852 111222
15 Union, 1 1/2" 53-0056 1
Union, 2" 53-0057 1 1 1
Union, 2 1/2" 53-0058 1 1
16 Firing Valve, 1 1/2" 11-0458 1
Firing Valve, 2" 11-0459 1 1 1
Firing Valve, 2 1/2" 11-0460 1 1
17 Main Gas Valve, V8944B, 1 1/2", ( 1 or 2 Stage) 11-0173 1
Main Gas Valve, V8944B, 2", (1 or 2 Stage) 11-0174 1 1 1
Main Gas Valve, V88A, 1 1/2", (1 Stage) 11-0158 1
Main Gas Valve, V88A, 2", (1 Stage) 11-0159 1 1 1
Main Gas Valve, V88A, 2 1/2", (1 Stage) 11-0160 1 1
Page 29
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 29
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
Not Shown
Not Shown
Not Shown
Not Numbered Not Shown
24 &25 Upper Rear & Front Jacket Panel 03-1064 1
Not Shown
Main Gas Valve, V5055B, 1 1/2", (Modulating) 11-0253 1
Main Gas Valve, V5055B, 2, (Modulating) 11-0254 1 1 1
Main Gas Valve, V5055B, 2 1/2", (2 Stage or Mod.) 11-0255 1 1
Main Gas Valve Actuator, V4055A, (1 Stage) 11-0301 1 1
Main Gas Valve Actuator, V4055A, (2 Stage) 11-0302 1 1
Main Gas Valve Actuator, V9055A, (Modulating) 11-0303 111111
Main Gas Pressure Regulator RV81, 1 1/2" 11-0503 1
Main Gas Pressure Regulator RV91, 2" 11-0504 1 1 1
Main Gas Pressure Regulator RV111, 2 1/2" 11-0505 1 1
18 “A” Valve, 1 1/2" 11-0453 1
A Valve, 2" 11-0454 1 1 1
A Valve, 2 1/2" 11-0455 1 1
19 Burner Drawer Side Rail Assy, Left 70-1793 111111
Burner Drawer Side Rail Assy, Right 70-1794 111111
Burner Spacers 70-1795 1
70-1796 1 70-1797 1 70-1798 1 70-1799 1 70-1800 1
Heat Shield 70-1733 1
70-1734 1 70-1735 1 70-1736 1 70-1737 1
70-1738 1 End Refractory Panel, Left & Right 05-0050 222222 Center Refractory Panel 05-0051 4468810
20 Corner Refractory Panel 05-0052 4
05-0053 4
05-0054 4
05-0055 4
05-0056 4
05-0057 4
21 Draft Diverter Side Panel, Left & Right 03-1109 222222 22 Draft Diverter Down Draft Baffle 03-1116 1
03-1117 1
03-1118 1
03-1119 1
03-1120 1 1
23 Draft Diverter Top Panel Assembly 70-1666 1
70-1667 1
70-1668 1
70-1669 1
70-1670 1
70-1671 1
03-1065 1
03-1066 1
03-1067 1
03-1068 1
03-1069 1
26 Upper Jacket End Panel, Left & Right 03-1070 222222 27 Upper Rear Corner Jacket Trim Panel, Left 03-1084 111111
Upper Rear Corner Jacket Trim Panel, Right 03-1085 111111
28 Upper Front Corner Jacket Trim Panel, Left 03-1086 111111
Upper Front Corner Jacket Trim Panel, Right 03-1087 111111
29 Top Jacket Panel 03-1051 1
03-1052 1
03-1053 1
03-1054 1
03-1055 1
03-1056 1
30 Top Jacket Channel, Left & Right 03-1063 222222
Pilot, Natural Gas, Q348 10-0103 1 1 1 1 Pilot, LP Gas, Q348 70-0478 1 1 1 1
Page 30
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 30
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
Not Shown
Not Shown
Not Shown Not Show Not Shown Not Shown
Not Shown Not Shown
Not Shown
Not Shown
Not Shown
Not Shown Not Shown Not Shown Not Shown
Not Shown
Not Shown
Not Shown
Pilot, Natural Gas, Q179C (*IRI Only) 10-0103 1* 1* 1211 Pilot, LP Gas, Q179C (*IRI Only) 70-0478 1* 1* 1211 Pilot Orifice, Natural Gas 10-0005 111222 Pilot Orifice, LP Gas 10-0004 111222 Pilot Valve, 24 V 11-0017 111111
n Pilot Regulator, RV12LT 11-0041 111111
Manual Pilot Valve 11-0031 111111 Ignition Module, S8610M 16-0054 1 1 1 1 Ignition Module, RM7890A (*IRI Only) 16-0001 1* 1* 1111 Transformer, 40 VA 15-0002 111111 High Limit, L4008E (US only) 14-0104 111111 High Limit, GIP 9869 (CAN only) 14-0117 111111 High Limit, L4008E-1313 (Water Heaters) 14-0105 111111 High Limit, L4008E-1040 (Boilers) 14-0104 111111 Hight Limit, L4008A-1445 (Water Heaters) 14-0103 111111 High Limit, L4008A-1007 (Boilers) 14-0102 111111 Operator, L4008A (US only) 14-0102 111111 Operator, GIP 9868 (CAN only) 14-0116 111111 Operator, L4008A-1007 (Boilers) 14-0102 11111 Operator, L6008A-1242 (Water Heaters) 14-0106 11111 Operator, L4008A-1445 (Water Heaters) 14-0103 11111 Operator, L6008G1009 (2 Stage) 14-0107 11111 Operator, T991E-1018 (Modulating) Boilers 14-0108 11111 Operator, T991E-1034 (Modulating) Water Heaters 14-0110 11111 Operator, T6031A-1052 (Pool Heaters) 14-0003 11111 Orifice, Blank 10-0011 8 10 12 14 16 18 Orifice, Natural Gas, # 17 10-0014 8 10 12 14 16 18 Orifice, Nat Gas, # 18 (2000-4500 ft) 10-0015 8 10 12 14 16 18 Orifice, LP Gas, # 39 10-0026 8 10 12 14 16 18 Orifice, LP Gas, # 40 (2000-4500 ft) 10-0027 8 10 12 14 16 18 Pressure Relief Valve 50# 1 x 1 1/4 13-0002 1 Pressure Relief Valve 50# 1 1/4 x 1 1/4 13-0026 11111 Pressure Relief Valve 125# 3/4 x 3/4 13-0009 1 1 Pressure Relief Valve 125# 3/4 X 1 13-0003 1 Pressure Relief Valve 125# 1 x 1 13-0053 1 1 1 Pressure Gauge 13-0301 111111 Thermometer w/ Well 13-0320 111111 Flow Switch 14-0201 111111 Natural to LP Conversion Kit 21-0107 1
21-0108 1
21-0109 1
21-0110 1
21-0111 1
21-0112 1 Conversion Kit Natural to LP Gas 21-0113 1
21-0114 1
21-0115 1
21-0116 1
21-0117 1
21-0118 1 Conversion Kit LP to Nat Gas (2000-4500 ft) 21-0119 1
21-0120 1
21-0121 1
21-0122 1
21-0123 1
21-0124 1 Conversion Kit Nat to LP Gas (2000-4500 ft) 21-0125 1
21-0126 1
21-0127 1
21-0128 1
21-0129 1
21-0130 1
Page 31
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 31
TROUBLE SHOOTING FLOW CHART FOR HONEYWELL S8610 CONTROL SYSTEM
Proper line voltage L1 to L2 on heater
terminal strip
24V on secondary
terminals of Heater
transformer
24V across 24V and 24V
(GND). terminals of S8610
ignition module
On application of 24V,
control produces audible
spark at pilot
Pilot
Ignites
Adjust the pilot gas
pressure using the
pilot regulator. Pilot
ignition problems
can be caused by high or low pilot
pressure.
Pilot ignites
Check for tripped breaker or open safety
/ limit switch in supply voltage circuit
Check for broken or loose
connection to transformer if none
replace transformer
Check for open Limit in this 24V circuit
Operating Control, High limit, Flow Switch,
LWCO, High / Low Gas Pressure Switches,
Remote Operating Controls etc.
Check for loose or broken ignition lead. Check for shorted pilot electrode.
If pilot and ignition lead test good replace S8610 module
During pilot ignition period (audible spark present)
check for 24V between PV and MV/PV terminals
of S8610 module.
24V at pilot gas
valve leads
A tripped Manual reset
High Limit may
indicate insufficient
Check for loose or
broken wire between
pilot valve and
PV-MV/PV terminals
water flow.
Replace
S8610
module.
Main Flame
Ignites
Manifold pressure in proper
range (3.8”-4.2” N.G.,
10”-11” L.P.) If no pressure on
manifold, during main flame trial for ignition period. Check for pressure at tappings of each
main valve. Replace valve
that shows no pressure at
downstream tapping while
powered with pressure at
upstream tapping
With pilot lit: 24V between the MV and MV/PV terminals of
the S8610 module
24V at terminals of
all valves in main
gas train
Pilot valves opens. Confirm that gas is
present at pilot valve
inlet
Insure pilot line and
pilot orifice are clear
and that the pilot is
undamaged. The pilot
ignites.
Check for loose or
broken wire between
MV-MV/PV terminals
Replace pilot solenoid
valve
Replace the pilot
assembly
Replace S8610
module
main valves and
Page 32
TROUBLE SHOOTING
NOTE Installation and service must be performed by a qualified installer, service agency or the gas supplier. An electrical multi meter and slack tube manometer are required for trouble shooting.
Problem
Boiler pounds or knocks
Relief valve leaks
Sooting of heat exchanger
Cause
Low or no water flow
Low or no system pressure
Heat exchanger blocked
System pressure too high
Expansion tank is waterlogged
Expansion tank is isolated
Return water temperature to low
Inadequate combustion air
Rated input has been exceeded
Incorrect fuel type
Solution
Ensure that pump is operating properly - look for voltage through flow switch.
Ensure that all system valves are open.
Ensure that all air has been bled from the system.
Ensure that the maximum temperature rise of 30°F has not been exceeded.
Ensure that water makeup valve is open and functioning.
Remove return header and inspect the heat exchanger tubes.
Ensure relief valve is properly sized for the system - never exceed 160 psi.
Ensure expansion tank is properly sized for the system.
Ensure valve between expansion tank and the system is open.
Adjust balancing valves for a minimum return water temperature of 110°F (43°C).
Ensure that the make up air supply is adequate per NFPA 54/ ANSI Z223.
Ensure that the vent system is sized properly, is not blocked or restricted and that there is adequate draft present in the breeching.
Ensure that the input rate is correct.
Ensure that the fuel type supplied matches the rating plate.
260 North Elm Street 1300 Midway Boulevard Westfield, MA 01085 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
Loading...