RBI MW-500, MW-1250, MW-750, MW-1000, MW-200 Installation & Operation Manual

...
FTIII-IOM-HN-2
82-0300
FUTERA III SERIES FINNED COPPER
WITH CONTROL
GAS BOILERS (MODEL MB)
& WATER HEATERS (MODEL MW)
INSTALLATION & OPERATION MANUAL
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch. Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
WARNING: Failure to properly vent this unit can cause excessive amounts of carbon monoxide resulting in severe personal injury or death!
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE BOILER / WATER HEATER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
260 North Elm Street 7555 Tranmere Drive Westfi eld, MA 01085 Mississauga, Ontario L5S 1L4 Canada Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
www.rbiwaterheaters.com
10/09
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
AVERTISSMENT. Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides infl ammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifi é ou par le fournisseur de gaz.
CONTENTS
Before Your Start page 2 Ratings & Capacities page 3 Boiler/Water Heater Location page 3 Combustion Air & Ventilation page 3 General Venting Guidelines page 5 Outdoor Venting page 11 Common Vent Systems page 11 General Piping Requirements page 12 Heating System Piping page 13 Domestic Water Supply Piping page 17 Gas Supply Piping page 21 Electrical Wiring page 22 General Operation page 22 Operating Instructions page 23 Sequence of Operation page 25 Checking & Adjustments page 26 HeatNet Field Wiring page 27 Control Description page 29 Diagnostics page 29 Maintenance page 32 Trouble-Shooting page 34 Repair Parts page 35 Startup Sheet page 42
BEFORE YOU START
This manual covers the application, installation, operation and maintenance of a Futera III Series finned copper heating boiler/water heater.
To obtain the safe, dependable, effi cient operation and long life for which this heating boiler/water heater was designed, these instructions must be read, understood and followed.
The Futera III Series fi nned copper heating boiler/water heaters have been design certifi ed by CSA for use with natural and propane gas under the latest revision of ANSI­Z21.10.3/CSA 4.3, Gas Water Heaters, ANSI-Z21.13/CSA
4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers and CAN1-3.1, Industrial and Commercial Gas Fired Packaged Boilers. Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160 psi, 1103 kPa in accordance with Section IV of the A.S.M.E. Boiler and Pressure Vessel Code.
All aspects of the boiler/water heater installation must conform to the requirements of the authority having juris­diction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ ASME CSD-1.
In Canada, the installation must be in accordance with the requirements of CSA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
If installed in the Commonwealth of Massachusetts, you MUST FOLLOW the additional instructions contained in RBI’s instruction sheet MACODE-3. Which is located in the back of this manual.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the service organization for future reference.
Direct all questions to your RBI distributor or contact the RBI Customer Service Department at: 260 North Elm Street, Westfi eld, MA 01085 for US or 7555 Tranmere Drive, Mississauga ONT L5S 1L4 for Canada. Always include the model and serial numbers from the rating plate of the boiler/water heater in question.
2
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
RATINGS & CAPACITIES
Before undertaking the installation of the Futera III Series boiler/water heater check the rating plate to ensure that the unit has been sized properly for the job. The “Net I=B=R Ratings” specify the equivalent amount of direct copper radiation that the unit can supply under normal conditions. Also ensure that the unit has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1. This boiler/water heater is suitable for indoor and oudooor installations. Locate the boiler/water heater in an area that provides good access to the unit. Servicing may require the removal of jacket panels. Allow the minimum clearances between adjacent construction and the boiler/water heater as listed in Table 1.
NOTE: Service clearances are not mandatory, but are recommended to ensure ease of service should it be required.
Table 1 Clearance to Service Combustibles Clearance in mm in mm
Top 6 153 30 762 Back 6 153 24 610 Left Side 6 153 12 306 Right Side 6 153 12 306 Front 6 153 30 762
2. An optimum site will be level, central to the piping system, close to a chimney or outside wall and have adequate fresh air for combustion. Ensure that the boiler/water heater is level from front to back and from side to side. Use metal shims to level the boiler/water heater. Electrical and electronic components must also be protected from exposure to water during operation and maintenance. DO NOT install this boiler/water heater in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
3. Ensure that the fl oor is structurally sound and will support the weight of the boiler/water heater.
NOTE: The Futera III may be installed directly on combustible fl ooring, but never on carpeting.
4. Locate the boiler/water heater in an area that will
prevent water damage to adjacent construction should a leak occur or during routine maintenance. If such a location doesn’t exist, a suitable drain pan that’s adequately drained must be installed under the unit.
5. DO NOT place this boiler/water heater in a location that
would restrict the introduction of combustion air into the unit or subject it to a negative pressure, see “GENERAL VENTING GUIDELINES”.
6. NEVER place this boiler/water heater in a location that would subject it to temperatures at or near freezing, see the “FREEZE PROTECTION” section on page 12.
WARNING: Never store combustible materials, gasoline or any product containing flammable vapors or liquids in the vicinity of the boiler/water heater. Failure to comply with this warning can result in an explosion or fire causing extensive property damage, severe personal injury or death!
COMBUSTION AIR & VENTILATION
WARNING: This boiler/water heater must be supplied with combustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and all applicable local building codes. Canadian installations must comply with CAN/ CGA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. Failure to provide adequate combustion air for this boiler/ water heater can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
To operate properly and safely this boiler/water heater requires a continuous supply of air for combustion. NEVER store objects on or around the boiler/water heater!
CAUTION: Combustion air contaminated with fl uorocarbons or other halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. These acids will cause premature failure of the boiler/water heater voiding the warranty!
CAUTION: If the boiler/water heater is operated while the building is under construction it MUST be protected from wood, concrete, sheet rock and other types of dust. Failure to properly protect the unit from construction dust will damage the unit voiding the warranty!
Buildings will require the installation of a fresh air duct or other means of providing make-up air if the intake air option isn’t used. Any building utilizing other gas burning appliances, a fi replace, wood stove or any type of exhaust fan must be checked for adequate combustion air when all of these devices are in operation at one time. Sizing of an outside air duct must be done to meet the requirements of all such devices.
WARNING: Never operate the Futera III in an environment subjected to a negative pressure unless it is Direct Vented. Failure to comply with this warning can result in excessive levels of carbon monoxide causing severe personal injury or death!
3
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
All Air From Inside The Building
If the Futera III is to be located in a confi ned space, the minimum clearances listed in Table 1 must be maintained between it and any combustible construction. When installed in a confi ned space without the intake air option, Figures 5, 6 and 7, two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have suffi cient volume to meet the criteria for an unconfi ned space. The total air requirements of all gas utilization equipment, fireplaces, wood stoves or any type of exhaust fan must be considered when making this determination. Each opening must have a minimum free area of 1 in
2
/1000 Btu/hr, 2200 mm2/kW based on the
total input rating of ALL gas utilization equipment in the confined area. Each opening must be no less than
2
100 in
, 64,516 mm2 in size. The upper opening must
be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure. The bottom opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bottom of the enclosure.
All Air From Outside The Building When installed in a confi ned space without utilizing the intake air option two permanent openings communicating directly with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure. The bottom opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bottom of the enclosure.
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of
2
/4000 Btu/hr, 550 mm2/kW of the total input rating
1 in
of all of the equipment in the enclosure.
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of
2
/2000 Btu/hr, 1100 mm2/kW of the total input rating
1 in
of all of the equipment in the enclosure.
When ducts are used, they must have the same cross­sectional area as the free area of the opening to which they connect.
When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration must be given to the blockage effects of louvers, grills and screens. Screens must have a minimum mesh size of 1/4 in, 6.4 mm. If the free area through a louver or grill is not known, ducts should be sized per Table 2.
Table 2 – Make-up Air Louver Sizing
Required Cross Sectional Area
Input 1/4 in 6.4 mm (MBH) Wire Screen Metal Louvers Wooden Louvers in
2
cm
75% Free Area 25% Free Area
2
in
2
cm
2
in
2
cm
2
500 125 806 167 1077 500 3226 750 187 1206 250 1613 750 4839 1000 250 1613 333 2148 1000 6452 1250 313 2019 416 2684 1250 8065 1500 375 2419 500 3226 1500 9677 1750 437 2819 583 3761 1750 11,290 1999 500 3226 667 4303 2000 12,900
Intake Air Option – General Guidelines This confi guration provides combustion air directly to the boiler/water heater’s air intake adapter using a dedicated pipe when using the direct vent option. Combustion air can be drawn in horizontally through the same outside wall which terminates the exhaust gases or vertically through the roof, see Figures 1, 2, 3 & 4.
WARNING: Common intake air systems may be used provided the common duct is sized properly. An intake combustion air damper should be installed if the common vent option is used in the intake air pipe of each heater. Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Single wall galvanized smoke pipe, single wall aluminum pipe, fl exible aluminum pipe, PVC or CPVC pipe can be used for the intake air pipe. It must be sized per Table 3.
Table 3 - Intake Air Pipe Sizing
Model For Vertical For Horizontal Size (Up to 60') (Up To 60') in mm in mm 500 8 203 6 152 750 8 203 6 152 1000 8 203 6 152 1250 10 254 8 203 1500 10 254 10 254 1750 12 305 12 305 2000 12 305 12 305
All joints in metal intake air systems must be secured using corrosion resistant fasteners and sealed using a suitable Silicone caulk. If PVC or CPVC is used, the joints must be cleaned with a suitable solvent and connected using a solvent based PVC cement. The combustion air system
MUST be supported by the building structure not the boiler/water heater.
Canadian installations must comply with CSA B149.1 when air supply is provided by natural air fl ow from the outdoors for natural draft, partial fan-assisted, fan-assisted, or power draft-assisted burners, there shall be a permanent air supply opening(s) having a cross-sectional area of not less than 1 in and including 1 million Btuh, plus 1 in
(155 mm
2
per 7,000 Btuh (310 mm2 per kW) up to
2
per kW) in excess of 1 million Btuh.
2
per 14,000 Btuh
4
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
CAUTION: A combustion air damper interlocked with the unit should be installed in the intake air pipe when the infi ltration of subfreezing air could occur, otherwise the unit could freeze up voiding the warranty!
Intake Air Option – Vertical Guidelines
The maximum equivalent length for the vertical intake air pipe is 60 ft, 18.3 m. Each 90˚ elbow and the intake air terminal are equal to 10 linear ft, 3.0 m of pipe, see Table 3.
An approved, nonrestrictive intake air terminal must be used. The intake air terminal must terminate as shown in Figure 3. The penetration point in the roof must be properly fl ashed and sealed.
Intake Air Option – Horizontal Guidelines
The maximum equivalent length for the horizontal intake air pipe is 60 ft, 18.3 m. Each 90˚ elbow and the intake air terminal are equal to 10 linear ft, 3.0 m of pipe. If horizontal runs exceed 5 ft, 1.5 m they must be supported at 3 ft,
0.9 m intervals with overhead hangers. The certifi ed intake air terminal from RBI must be used, see Figures 1, 2 and 4.
GENERAL VENTING GUIDELINES
WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1/NFPA 54­latest revision or applicable provisions of the local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
VENT SYSTEM OPTIONS
The fl ue products in the vent system may be cooled below their dew point and form condensate in the flue. The materials used for a Category IV vent must be resistant to any corrosive damage from fl ue gas condensate. The fl ue from a Category IV vent system must have a condensate drain with provisions to properly collect and dispose of any condensate that may occur in the venting system.
The Futera III may be vented the following ways:
1) Direct Vent, Positive Pressure, Category IV uses a
vent system certifi ed to UL 1738 for installations in the United States, ULC S636 for installations in Canada. Combustion air is piped from the outdoors to the blower inlet.
2) Side Wall Vent, Positive Pressure, Category IV uses
a vent system certifi ed to UL 1738 for installations in the United States, ULC S636 for installations in Canada. Combustion air is obtained from the space in which the unit is installed.
Vertical/Chimney Vent, Negative Pressure , Category II
3)
uses a metal chimney system approved for Categor y II.
Vertical Vent, Positive Pressure, Category IV
4)
vent system certifi ed to UL 1738 for installations in the United States, ULC S636 for installations in Canada. Combustion air is obtained from the outdoors or the space in which the unit is installed.
NOTE: All venting and combustion air material supplied by installer. All venting materials must be approved for the application. Consult the vent manufacturer’s product literature.
uses a
All vent systems must be fully supported by the building structure and not by the boiler/water heater. Appropriate thimbles and fi re-stops must be used where required.
WARNING: Common vent systems must be properly engineered and sized to provide a negative draft of .03 in, 0.8 mm to .1 in, 2.5 mm W. C. at the fl ue outlet. Common positive pressure vent systems are not to be used. Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
5
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
DIRECT VENT, POSITIVE PRESSURE, CATEGORY IV
In this confi guration the boiler/water heater blower is used to push the fl ue products to the outdoors while drawing combustion air from the outdoors. The Intake Air Option instructions under the “COMBUSTION AIR & VENTILATION” section must be followed! The vent system must be sized per Table 4.
Table 4 – Category IV
Model Pipe Diameter Size (Up to 60') in mm 500 5 127 750 5 127 1000 6 152 1250 6 152 1500 8 203 1750 10 254 2000 10 254
Horizontal Direct Vent Systems – Figures 1 & 2 The vent materials used in horizontal vent systems must be certifi ed to UL 1738 for installations in the United States, ULC S636 for installations in Canada. The certifi ed vent terminal from RBI must also be used.
The maximum equivalent length for the horizontal vent pipe is 60 ft, 18.3 m. Each 90˚ elbow and the vent terminal are equal to 10 linear ft, 3.0 m of pipe. If any part of a single wall metal vent system passes through an unheated space, it must be insulated with insulation rated for 400°F, 204°C. Structrual penetrations must be made using approved fi re­stops. For best results, horizontal vent systems should be as short and straight as possible.
Horizontal vent systems shall terminate at least 4 ft,
1.2 m below, 4 ft, 1.2 m horizontally from or 1 ft,
0.30 m above any door, window or gravity air inlet into
any building. It must not terminate less than horizontally from, and in no case above or below, unless a 4 ft, 1.2 m horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment and not less than 7 ft, 2.1 m above adjacent public walkway. The bottom of the vent terminal(s) shall be located at least 5 ft, 1.5 m above the air intake terminal(s) unless there is a minimum 5 ft, 1.5 m horizontal separation between them. Avoid terminal locations likely to be affected by winds, snowdrifts, people and pets. Protect building materials and vegetation from degradation caused by the fl ue gases.
Vertical Direct Vent Systems – Figure 3
If any part of a single wall metal vent system passes through an unheated space, it must be insulated with insulation rated for 400˚F, 204°C. Structural penetrations must be made using approved fi re-stops.
An approved, nonrestrictive vent terminal must be used. The top of a vertical vent system must extend at least
1
/2 ft, 1.7 m above the roof surface and maximum snow
5
line that it passes through, 4 ft, 1.2 m above the intake air terminal, see Figure 3.
In addition the vent system must conform to the dimensions shown in Figure 3. The penetration point in the roof must be properly fl ashed and sealed.
The vent system must be gas tight. All seams and joints in metal pipes must be joined and sealed in accordance with the vent system manufacturer’s instructions.
4 ft, 1.2 m
The vent system must be both gas tight and watertight. All seams and joints in metal pipes must be joined and sealed in accordance with the vent system manufacturer’s instructions.
When horizontal vent runs exceed 5 ft, 1.5 m they must be supported at 3 ft, 0.9 m intervals with overhead hangers. The vent system must be pitched down, toward the vent terminal, 1/4 in/ft, 20 mm/m. If any part of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400˚F, 204°C.
Combination Direct Vent Systems – Figure 4 The boiler/water heater can be vented vertically with the intake air piped horizontally through an outside wall. Follow the instructions in the Intake Air Option – Horizontal Guidelines on page 5. Also follow the general instructions in the “COMBUSTION AIR & VENTILATION” and “GENERAL VENTING GUIDELINES” sections.
6
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
Figure 1– Horizontal Air Intake and Venting for a Single Direct Vent System
1/4IN.PERFOOT
20mm/m
16FT 4.9m
1.5FT 0.5m
When running horizontal combustion air and venting for single or multiple units, exhaust and combustion air terminals must be installed on the same plane (outside wall) in order to prevent pressure differences due to prevailing winds. In cold climates, double-wall or insulated inlet pipe recommended to prevent condensation.
Figure 2 – Horizontal Air Intake and Venting for Multiple Direct Vent Systems
MBH
500 TO 1000
1001 TO 2000 2001 TO 4000
4001 & LARGER
kW 146 TO 293 293 TO 586
586 TO 1172
1172 & LARGER
FT m
5 1.5 10 3.1 15 4.6 20 6.1
5 FT 1.5 m
1.5 FT 0.5 m
1000BTU'S
2 IN. 5.0 cm
7
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
Figure 3 - Vertical Air Intake and Venting for Direct Vent System
4 FT
1.2 m
1.5 FT
0.5 m
10 FT 3.1 m
5 1/2 FT
1.7 m
Figure 4 – Combination Direct Vent Systems
3 FT. 1 m
5 FT
1.5 m
10 FT. 3.1 m
1.5 FT. .5 m
8
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
SIDE WALL VENT, POSITIVE PRESSURE, CATEGORY IV
In this confi guration the boiler/water heater blower is used to push the fl ue products horizontally to the outdoors, see Figure 5. The air for combustion is taken from the space in which the unit is installed. The applicable instructions under the “COMBUSTION AIR & VENTILATION” section must be followed! The vent guidelines under the Horizontal Direct Vent Systems section must also be followed.
VERTICAL VENT, NEGATIVE PRESSURE, CATEGORY II
The Futera III is listed as a Category II appliance when vented vertically into a listed metal chimney system, Figures 6 & 7. The chimney must provide a negative pressure not greater than 0.15 in, 3.8 mm W.C. at the boiler/water heater flue collar with the unit running. A barometric damper must be installed between the fl ue collar and the vent connector when negative pressures exceed 0.15 in, 3.8 mm W.C.
NOTE: When using a listed metal chimney system the chimney system manufacturer’s instructions must be followed.
When more than one appliance is connected to the same chimney fl ue, the fl ue must be large enough to safely vent the combined output of all of the appliances.
WARNING: If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney fl ue, never connect any other appliances to this fl ue. Doing so can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Chimney Inspection & Sizing
A thorough inspection of the masonry chimney must be performed to ensure that the chimney is clean, properly constructed, lined and sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems. Table 5 lists the equivalent breeching and fl ue sizes required for the boiler/ water heater.
Table 5 - Equivalent Breeching & Chimney Size, Negative Pressure
Model Size Pipe Diameter in mm 500 6 152 750 6 152 1000 7 178 1250 8 203 1500 8 203 1750 10 254 2000 10 254
Note: These sizes are based on a 20 ft, 6.1m chimney height.
Figure 5 – Side Wall Venting
1.5 FT 0.5 m
4 FT
1.2 m
3 FT
0.9 m
1/4 IN. PER F00T 20 mm/m
24"
0.6 m
9
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
VERTICAL VENT, POSITIVE PRESSURE, CATEGORY IV
(Vent pipe equivalent length up to 60 ft, 18.3 m maximum)
WARNING: Masonry chimneys, when used, must be lined with a metal liner certifi ed for Category IV venting.
A through inspection of the masonry chimney must be performed to ensure that the chimney is clean, properly constructed lined, and sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems.
Vent Connections
Locate the boiler/water heater as close to the chimney as possible. Use the shortest, straightest vent connector possible for the installation. If horizontal runs exceed 5 ft,
1.5 m they must be supported at 3 ft, 0.9 m intervals with overhead hangers. Use a single wall stainless steel vent pipe the same diameter as the fl ue collar to connect the boiler/water heater to a masonry chimney. When using a listed metal chimney system use the appropriate vent connector.
The vent connector should be sloped up toward the chimney at a minimum rate of 1/4 in/ft, 21 mm/m. On masonry chimneys the connector must terminate fl ush with the inside of the chimney fl ue, Figure 7. Fasten each single wall vent connection with at least 3 corrosion resistant sheet metal screws.
Always provide a minimum clearance of 6 in, 152 mm between single wall vent pipe and any combustible materials.
WARNING: Failure to maintain minimum clearances between vent connectors and any combustible material can result in a fi re causing extensive property damage, severe personal injury or death!
Figure 6 – Vertical Venting with a Metal Chimney System
24"
.6 m
Figure 7 – Vertical Venting using a Lined Masonry Chimney
10 FT. 3.1 m
24"
.6 m
10
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
A
Figure 7A – Outdoor Venting Figure 7B – Multiple Outdoor Units
2 FT
(0.62 M)
RIOM-59-REV. A
GAS TRAIN COWLING
AIR INLET UNDER COWLING
DISCHARGE VENT
FLUE TEST PORT
CONDENSATE DRAIN WITH PIG TAIL
3 FT
(1 M)
RIOM-60 REV.
OUTDOOR VENTING
When installed outdoors the Futera III must be fi tted with the factory supplied outdoor hood, air intake adapter with fi lter and exhaust terminal, see Figure 7A. Multiple units must be spaced per Figure 7B.
The boiler/heater must be at least 2 ft, .62 m from any door, window or gravity air inlet into any building and at least 3 ft, 1 m from any overhang unless local codes dictate differently.
Avoid locations where wind defl ection off of adjacent walls, buildings or shrubbery might cause a downdraft. The unit(s) shouild be located at least 3 ft, 1 m from structures. Outdoor installations are not recommended in areas where the danger of snow blockage exists.
CAUTION: Do not place the boiler/water heater in a location that would subject it to runoff from adjacent buildings or damage may occur voiding the warranty!
COMMON VENT SYSTEMS
On multiple boiler common vent applications, the master boiler may be required to be fi rst on and installed closest to the verticle chimney (consult factory).
If an existing boiler/water heater is removed from a common venting system, the common venting system may then be too large for the proper venting of the remaining appliances connected to it. At the time of removal of an existing boiler/water heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Au moment du retrait d’une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d’évacuation commun et qui fonctionne alors que d’autres appareils toujours raccordés au système d’évacuation ne fonction­nent pas: système d’évacuation
a) Seal any unused openings in the common venting system.
Sceller toutes les ouvertures non utilisées du sys­ tème d’évacuation.
b) Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other defi ciencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d’évacu-ation pour déterminer la grosser et l’inclinaison horizontale qui conviennent et s’assurer que le système est exempt d’obstruction, d’étranglement de fruite, de corrosion et autres défaillances qui pourraient présenter des risques.
c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system.Turn on any exhaust fans, such as range hoods and bathroom exhaust, so they will operate at maximum speed. Do not operate a summer exhaust fan for a boiler installation. Close fi replace dampers.
11
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
Dans la mesure du possible, fermer toutes les portes et les fenêtres du bâtiment et toutes les portes entre l’espace où les appareils toujours raccordés du système d’évacuation sont installés et les autres espaces du bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au système d’évacuation commun et tous les ventilateurs d’extraction comme les hottes de cuisinère et les ventilateurs des salles de bain. S’assurer que ces ventilateurs fonctionnent à la vitesse maximale. Ne pas faire fonctionner les ventilateurs d’été. Fermer les registres des cheminées.
d) Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat de façon que l’appareil fonctionne de façon continue.
e) Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the fl ame of a match or candle, or smoke from a cigarette, cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min
ensuite, déterminer si le coupe-tirage déborde à l’ouverture de décharge. Utiliser la flamme d’une allunette ou d’une chandelle ou la fumée d’une cigarette, d’un cigare ou d’une pipe.
f) After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fi replace dampers and any other gas-burning appliance to their previous condition of use.
Une fois qu’il a été d éterminé, selon la métode indiquée ci-dessus, que chaque appareil raccordé au système d’évacuation est mis à l’air libre de façor adéquate. Remettre les portes et les fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
g) Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix F in the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 and or CAN/CGA B149 Installation Codes.
Tout mauvais fonctionnement du systéme d’évacu-tion commun devrait étré corrigé de façor que l’installation soit conforme au National Fue Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d’installation CAN/ CGA-B149. Si la grosseur d’une section du système d’ évacuation doit étré modifi ée, le système devrait étré modifié pour respecter les valeurs minimales des tableaux pertinents de l’appendice F du National Fuel Gas Code, ANSI Z223.1/ NFPA 54 et (ou) des codes d’installation CAN/CGA-B149.
GENERAL PIPING REQUIREMENTS
CAUTION: Improper piping of this boiler/water heater will void the manufacturer’s warranty and can cause boiler failure resulting in flooding and extensive property damage! Excessive water hardness causing scaling in the copper heat exchanger tubes is NOT covered under the manufacturer’s warranty, see Table
8. Excessive pitting and erosion of the internal surface of the copper heat exchanger tubes is NOT covered under the manufacturer’s warranty if the result of high water flow rates, see Table 7. Return water temperatures below 125˚F, 52°C will result in heat exchanger damage from excessive condensation voiding the manufacturer’s warranty, see Primary / Secondary Piping, Figure 9.
NOTE: Shut off valves and unions should be installed at the inlet and outlet connections of the boiler/hot water heater to provide for isolation of the unit should servicing be necessary.
Freeze Protection
Installations in areas where the danger of freezing exists are not recommended unless proper freeze protection is provided. The following precautions MUST be observed:
1. A continuous fl ow of water through the unit MUST be maintained! The pump responsible for fl ow through the boiler/water heater must run continuously!
2. An ethylene glycol/water mixture suitable for the minimum temperature that the unit will be exposed to must be used. The pump must be capable of producing a minimum of 15% more fl ow and overcoming a 20% increase in head loss. Domestic water systems must be isolated from the water heater by the use of a heat exchanger or other approved method.
3. If the unit must be shut off for any reason the electric,
gas and water supplies MUST be shut off and the unit and its pump completely drained.
CAUTION: Improper outdoor installation of this unit can cause boiler failure voiding the manufacturer’s warranty!
12
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
Relief Valve
Pipe the discharge of the pressure relief valve as shown in Figure 8.
WARNING: Never install any type of valve between the boiler/water heater and the relief valve or an explosion causing extensive property damage, severe personal injury or death may occur!
Figure 8 – Futera III Piping
Flow Switch
The fl ow switch supplied with the boiler/water heater must be wired to the terminal strip in the control panel to prevent the boiler from fi ring unless there’s adequate water fl ow through the unit. The fl ow switch must be installed in the supply piping adjacent to the boiler outlet connection.
CAUTION: Failure to properly install the fl ow switch may result in damage to the boiler/water heater heat exchanger voiding the warranty!
HEATING SYSTEM PIPING
General Piping Requirements
All heating system piping must be installed by a qualifi ed technician in accordance with the latest revision of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV, and ANSI/ASME CSD-1, Standard for Controls and Safety Devices for Automatically Fired Boilers. All applicable local codes and ordinances must also be followed. A minimum clearance of 1 in, 25 mm must be maintained between heating system pipes and all combustible construction. All heating system piping must be supported by suitable hangers not the boiler. The thermal expansion of the system must be considered when supporting the system. A minimum system pressure of 12 psig, 82.7 kPa must be maintained.
Heating Boiler Piping Connections
The supply and return connections should be sized to suit the system, see Table 6.
Table 6 – Supply & Return Pipe Sizing (Flanged)
ModelSize SupplySize Return Size 500 thru 1000 2" 2" 1250 thru 2000 2 1/2" 2 1/2"
13
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
Pump Requirements
This low mass boiler requires a continuous minimum water fl ow for proper operation. The system pump must be sized to overcome the head loss of the boiler and the heating system in order to achieve the required temperature rise. Table 7 provides the heat exchanger pressure drop and temperature rise fi gures. The temperature rise across the boiler must never exceed 35˚F, 19.4˚C. The adjustable pump delay turns the pump on each time the burner fi res and runs the pump for 20 to 600 seconds after the call for heat is satisfi ed.
CAUTION: A temperature rise outside of the range listed in Table 7 indicates that the fl ow rate through the heat exchanger is incorrect which will damage the heat exchanger voiding the warranty! The maximum allowable temperature rise is 35°F, 19.4°C.
The maximum allowable fl ow rate through a Futera III boiler is 97 GPM, 6.1 L/s on 500 through 1000 models and 136 GPM, 8.6 L/s for 1250 through 2000 models. The Cupro-Nickel heat exchanger allows for 108 GPM,
6.8 L/s on 500 through 1000 models and 151 GPM,
9.5 L/s on 1250 through 2000 models.
Table 7 - Temperature Rise Table
ΔT = 20°F ΔT = 11.1°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop Number GPM Ft L/s kPa 500 43.5 0.55 2.7 1.6 750 65.3 1.63 4.1 4.8 1000 87.0 3.59 5.5 10.6 1250 108.8 2.21 6.9 6.5 1500 130.5 3.73 8.2 11.0
ΔT = 25°F ΔT = 13.9°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop Number GPM Ft L/s kPa 500 34.8 0.36 2.2 1.1 750 52.2 1.08 3.3 3.2 1000 69.6 2.37 4.4 7.0 1250 87.0 1.46 5.5 4.3 1500 104.4 2.46 6.6 7.3 1750 121.8 3.84 7.7 11.3 2000 139.2 5.63 8.8 16.6
ΔT = 30°F ΔT = 16.7°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop Number GPM Ft L/s kPa 750 43.5 0.77 2.7 2.3 1000 58.0 1.69 3.7 5.0 1250 72.5 1.04 4.6 3.1 1500 87.0 1.76 5.5 5.2 1750 101.5 2.74 6.4 8.1 2000 116.0 4.01 7.3 11.8
ΔT = 35°F ΔT = 19.4°C
Model Flow Rate Pres. Drop Flow Rate Pres. Drop Number GPM Ft L/s kPa 750 37.3 0.58 2.4 1.7 1000 49.7 1.27 3.1 3.8 1250 62.1 0.78 3.9 2.3 1500 74.6 1.32 4.7 3.9 1750 87.0 2.06 5.5 6.1 2000 99.4 2.02 6.3 8.9
Low Water Cutoff
If a boiler is installed above any radiation elements it must be fi tted with a low water cutoff device.
Refer to the wiring diagram supplied with the boiler/water heater for proper wiring connections.
Expansion Tank & Air Separator An expansion tank or other means to control thermal expansion must be installed in the heating system. An expansion tank must be installed close to the boiler on the suction side of the pump. An air scoop and automatic air vent must also be installed to eliminate air trapped in the system.
Primary/Secondary Piping Boilers connected to heating systems using zone valves, zone pumps, or systems that have excessive fl ow rates or return water temperatures less than 125˚F, 52˚C must be isolated from these systems to protect the boiler.
Variable Water Flows Figure 9 shows a typical primary/secondary piping system. A dedicated pump is used to maintain a constant water fl ow through the boiler. This secondary pump is sized to overcome the head loss of the boiler and secondary piping system while supplying the fl ow rate required to maintain the desired temperature rise across the boiler. The primary pump is sized to provide the required fl ow to the heating system. The secondary piping connections to the primary system piping must not be more than 12 in, 305 mm apart to ensure zero pressure drop in the primary system, see Figure 9.
Low Return Water Temperatures To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary/secondary piping system with a bypass and bypass valve must be installed, see Figure 10 and 10A. The bypass system must be sized the same as the secondary piping. The primary and secondary pumps should be sized to provide the required fl ow through each system. The secondary piping connections to the primary system piping must not be more than 12 in, 305 mm apart to ensure zero pressure drop in the primary system, see Figure 10 and 10A.
Multiple Boiler Systems
Systems using multiple boilers can also be installed using a primary/secondary manifold system, Figure 11.
Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler. Appropriate valves must be used to prevent the chilled water from entering the boiler.
When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device, the piping system must be equipped with fl ow-control valves or some other automatic means of preventing gravity circulation of the boiler water during the cooling cycle.
14
FUTERA III INSTALLATION AND OPERATION INSTRUCTIONS
Figure 9 - Typical Primary/Secondary Piping System
(See Notes)
Pump
Gate Valve
Globe Valve
NOTES:
1. Boiler circuit piping must be sized large enough to handle maximum fl ow through unit.
2. Boiler pump sized to boiler design fl ow requirements.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
Notice: These drawings show suggested piping confi guration and valving. Check with local codes and ordinances for specifi c requirements.
Figure 10 - Low Temperature Piping with Thermostatic Valve
(See Notes and Adjustment Procedures)
H-1 Rev 3
Angle Valve
Bufferfly Val ve
Balance Valve
Ball Valve
Motorized Valve
Solenoid
Operated Valve
Self-Operated
Val ve
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
Thermometer
NOTES:
1. For pump selection consult factory.
2. Boiler pump sized to boiler and thermostatic 3-way valve design fl ow requirements.
3. Boiler circuit piping must be sized large enough to handle maximum fl ow through unit.
4. All boilers furnished with factory mounted outlet water temperature gauge.
5. Boiler pump purging required. Use terminals supplied.
6. Valve is precalibrated for 140°F return temperature.
Notice: These drawings show suggested piping confi guration and valving. Check with local codes and ordinances for specifi c requirements.
15
H-18 Rev 2
Aquastat Union
Pressure Switch
Gas Pressure
Regulator
Automatic
Air Vent
Backflow­Prevention
Device
3-Way Valve
Expansion
Tan k
Loading...
+ 33 hidden pages