RBI LCD Series Installation & Operation Manual

Page 1
LCD-IOM-1
7/1/02
LCD SERIES FINNED COPPER GAS BOILERS
& WATER HEATERS INSTALLATION
& OPERATION MANU AL
MEA#117-96-E
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 160 PSI WATER.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch. Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
WARNING: Failure to properly vent this unit can cause excessive amounts of carbon monoxide resulting in severe personnal injury or death!
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE BOILER/WATER HEATER.
CONSUMER: RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
260 North Elm Street 1300 Midway Boulevard Westfield, MA 01085 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
Page 2
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 2
AVERTISSMENT. Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
CONTENTS
Before Your Start ................................................page 2
Ratings & Capacities..........................................page 3
Boiler/Water Heater Location .............................page 3
Combustion Air & Ventilation..............................page 3
General V enting Guidelines................................page 9
Venting Options ..................................................page 9
V ertical/Chimney V enting ...................................page 9
Horizontal V enting ............................................page 10
Outdoor V enting ...............................................page 11
Common V ent Systems....................................page 12
General Piping Requirements ..........................page 13
Heating System Piping.....................................page 14
Domestic Water Supply Piping .........................page 18
Gas Supply Piping............................................page 22
Electrical Wiring ...............................................page 23
General Operation............................................page 23
Operating Instructions ......................................page 26
Checking & Adjustment....................................page 28
Control Description ..........................................page 30
Maintenance.....................................................page 31
Trouble Shooting ..............................................page 34
Repair Parts .....................................................page 36
BEFORE YOU START
This manual covers the application, installation, operation and maintenance of a LCD Series finned copper heating boiler/water heater/pool heater.
To obtain the safe, dependable, efficient operation and long life for which this heating boiler/water heater was designed, these instructions must be read, understood and followed.
The LCD Series finned copper heating boiler/water heaters have been design certified by CSA for use with natural and propane gas under the latest revision of ANSI-Z21.10.3/CSA 4.3, Gas Water Heaters, and ANSI­Z21.13/CSA 4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers. Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160 psi, the A.S.M.E. Boiler and Pressure Vessel Code.
All aspects of the boiler/water heater installation must conform to the requirements of the authority having jurisdiction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the requirements of CSA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
In the Commonwealth of Massachusetts, the installation must be performed by a licensed plumber or gas fitter.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the service organization for future reference.
Direct all questions to your RBI Water Heaters distributor or contact the RBI Customer Service Depar tment, 260 North Elm Street, Westfield, MA 01085. Always include the model and serial numbers from the rating plate of the boiler/water heater in question.
1103 kPa
in accordance with Section IV of
Page 3
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 3
RATINGS & CAPACITIES
Before undertaking the installation of the LCD Series boiler/water heater check the rating plate to ensure that the unit has been sized properly for the job. The “Net I=B=R Ratings” specify the equivalent amount of direct cast iron radiation that the unit can supply under normal conditions. Also ensure that the unit has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1. This boiler/water heater is suitable for indoor and outdoor installations. Locate the boiler/water heater in an area that provides good access to the unit. Servicing may require the removal of jacket panels. Allow the minimum clearances between adjacent construction and the boiler/water heater as listed in Table 1.
NOTE: Service clearances are not mandatory, but are recommended to ensure ease of service should it be required.
Table 1
Clearance to Service
Combustibles Clearance
in
Top 6 Back 6 Left Side 6 Right Side 6 Front 6 Flue 6
2. An optimum site will be level, central to the piping system, close to a chimney or outside wall and hav e adequate fresh air for combustion. Ensure that the boiler/water heater is level from front to back and from side to side. Use metal shims to level the boiler/water heater. Electrical and electronic components must also be protected from exposure to water during operation and maintenance. DO NOT install this boiler/water heater in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
3. Ensure that the floor is structurally sound and will support the weight of the boiler/water heater.
NOTE: The LCD may be installed directly on combustible flooring, but never on carpeting.
4. Locate the boiler/water heater in an area that will prevent w ater damage to adjacent construction should a leak occur or during routine maintenance. If such a location doesn’t exist, a suitable drain pan that’s adequately drained must be installed under the unit.
mm 153 153 153 153 153 153
in 20 24 24 24 30
mm 508 610 610 610 762
5. DO NOT place this boiler/water heater in a location that would restrict the introduction of combustion air into the unit or subject the air inlet to a negative pressure, see “GENERAL VENTING GUIDELINES”.
WARNING: Never store combustible materials, gasoline or any product containing flammable vapors or liquids in the vicinity of the boiler/ water heater. Failure to comply with this warning can result in an explosion or fire causing extensive property damage, severe personal injury or death!
6. NEVER place this boiler/water heater in a location that would subject it to temperatures at or near freezing. See the “Freeze Protection Section” on page 14.
CAUTION: Units installed outdoors MUST be protected from ice and snow accumulation or the unit will be damaged voiding the warranty!
COMBUSTION AIR & VENTILATION
WARNING: This boiler/water heater must be supplied with combustion air in accordance with Section 5.3, Air for Combustion & V entilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and all applicable local building codes. Canadian installations must comply with CSA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local b uilding codes. Failure to provide adequate combustion air for this boiler/water heater can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
To operate properly and safely this boiler/water heater requires a continuous supply of air for combustion. NEVER store objects on or around the boiler/water heater!
CAUTION: Combustion air contaminated with fluorocarbons or other halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. These acids will cause premature failure of the boiler/water heater voiding the warranty!
CAUTION: If the boiler/water heater is operated while the building is under construction it MUST be protected from wood, concrete, sheet rock and other types of dust. Failure to properly protect the unit from construction dust will damage the unit voiding the warranty!
Page 4
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 4
Buildings will require the installation of a fresh air duct or other means of providing make-up air if the intake air option isn’t used. Any building utilizing other gas burning appliances, a fireplace, wood stove or any type of exhaust fan must be checked for adequate combustion air when all of these devices are in operation at one time. Sizing of an outside air duct must be done to meet the requirements of all such devices.
All Air From Inside The Building
If the LCD is to be located in a confined space the minimum clearances listed in Table 1 must be maintained between it and any combustible construction. When installed in a confined space without the intake air option, Figures 1, 2 & 3, two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have sufficient volume to meet the combustion air
WARNING: Never operate the LCD in an environment subjected to a negative pressure unless the air intake is connected to the outdoors. Failure to comply with this warning can result in excessive levels of carbon monoxide causing severe personal injury or death!
requirements of all gas utilization equipment. Fireplaces , wood stoves or any type of exhaust fan must be considered when making this determination. Each opening must have a minimum free area of 1 in2/1000 Btu/hr,
2200 mm2/kW
ALL gas utilization equipment in the confined area. Each opening must be no less than 100 in2, size. The upper opening must be within 12 in, of, but not less than 3 in, enclosure. The bottom opening must be within 12 in,
305 mm
of, but not less than 3 in,
bottom of the enclosure.
Figure 1 - Vertical Venting with a Metal Chimney System and Inside Air
based on the total input rating of
64,516 mm
2
in
305 mm
76 mm
from, the top of the
76 mm
from, the
10 FT 3.1m
Page 5
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 5
Figure 2 - Vertical Venting using a Masonry Chimney and Inside Air
VENT PIPE DIAMETER
IN. mm FT mm
5" TO 10"
12" TO 18"
127 TO 254 305 TO 457
Figure 3 - Horizontal Venting using Inside Air All Air From Outside The Building
4 FT
1.2 m
3 FT
0.9 m
MINIMUM VERTICAL RISE
OFF THE TOP OF UNIT "A"
12" 24"
305 610
1/4 IN. PER F00T 20 mm/m
1.5 FT 0.5 m
Page 6
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 6
All Air From Outside The Building When installed in a confined space without utilizing the intake air option two permanent openings
communicating directly with, or by ducts to , the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 in,
305 mm
of, but not less than 3 in,
76 mm
from, the top of
the enclosure. The bottom opening m ust be within 12 in,
305 mm
of, but not less than 3 in,
76 mm
from, the bottom
of the enclosure. Where directly communicating with the outdoors
or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in
/4000 Btu/hr,
550 mm2/kW
of the total input
2
rating of all of the equipment in the enclosure. Where communicating with the outdoors through
horizontal ducts, each opening shall have a minimum free area of 1 in
2
/2000 Btu/hr,
1100 mm2/kW
of the total input rating of all of the equipment in the enclosure. When louvers and screens are used, they must ha ve the same cross-sectional area as the free area of the opening to which they connect.
When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration must be given to the blockage effects of louvers, grills and screens. Screens must have a minimum mesh size of 1/4 in,
6.4mm
. If the free area through a louver or grill is not known the louver or grill should be sized per Table 2.
Intake Air Option - General Guidelines
This configuration provides combustion air directly to the boiler/water heater’s air intake using a dedicated pipe to obtain combustion air from the outdoors. Combustion air can be drawn in horizontally through an outside wall or vertically through the roof, see Figures 4, 5, 6 & 7.
WARNING: Each boiler/water heater must have its own intake air system. Common intake air systems are not to be used! Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Single wall galvanized smok e pipe, single wall aluminum pipe or flexible aluminum pipe can be used for the in-take air pipe. It must be sized per Table 3. All joints in metal combustion air systems must be secured using corrosion resistant fasteners and sealed using a suitable Silicon caulk or tape. The combustion air system
MUST be supported by the building structure not the boiler/water heater.
Table 3 - Combustion Air Pipe Sizing
Model Size Pipe Diameter
in
mm
225 - 300 5
400 6
600 - 750 8 900 - 1050 10 1200 - 2300 12
127 152 203 254 305
Table 2 - Make-up Air Louver Sizing
Required Cross Sectional Area
Input 1/4 in
(MBH) Wire Screen
225 57 300 75 399 100 600 150 750 190 900 225 1050 263 1200 300 1480 370 1650 413 1970 493 2300 575
in
6.4 mm
2
cm 363 484 645
968 1210 1451 1696 1936 2388 2662 3179 3711
75% Free Area 25% Free Area
Metal Louvers Wooden Louvers
2
2
in
75 100 133 200
250 300 350 400 494
3182
550
3548
657
4236
767
2
cm
484 645 858
1290
1613
1935 2258 2580
4945
in
225 300
399 600 750
900 1050 1200 1480 1650 1970 2300
2
2
cm 1452 1935
2573 3870 4840 5805 6773 7740 9546
10,643 12,707 14,835
Canadian installations must comply with CSA B149.1 when
air supply
outdoors for assisted, or power draft-assisted be a permanent
is provided by natural air flow from the
natural draft
air supply
, partial fan-assisted, fan-
burners
, there shall
opening(s) having a cross-
sectional area of not less than 1 in2 per 7,000 Btuh
(310 mm2 per kW)
plus 1 in2 per 14,000 Btuh
up to and including 1 million Btuh,
(155 mm2 per kW)
in e xcess
of 1 million Btuh.
CAUTION: A stack damper interlocked with the unit should be installed in the intake air pipe when the infiltration of sub-freezing air could occur, otherwise the unit could freeze up voiding the warranty!
Intake Air Option - Horizontal Guidelines
The Maximum equivalent length for the horizontal combustion air pipe on installations that used the Direct Vent option is 35 ft,
10.8 m
. The maximum equivalent length for the horizontal combustion air pipe on installations that use the Horizontal V ent option is 100 ft ,
30.5 m
are equal to 10 linear ft, exceed 5 ft,
. Each 90° elbow and the combustion air terminal
3.0 m
of pipe. If horizontal runs
1.5 m
they must be supported at 3 ft,
0.9 m
intervals with overhead hangers. The certified combustion air terminal from RBI must be used and installed as shown in Figures 4 and 5.
Intake Air Option - Vertical Guidelines
The maximum length for the vertical combustion air pipe is 30 ft,
9.1 m
plus two 90° elbows. A listed, nonrestrictive combustion air cap must be used. The combustion air cap must terminate as shown in Figure
6. The penetration point in the roof must be properly flashed and sealed.
Page 7
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 7
Figure 4 - Horizontal Combustion Air and Venting Figure 4 - Horizontal Combustion Air and Venting for a Single Unit
4 FT
1.2 m
1/4 IN. PER FOOT
20 mm/m
3 FT 0.9 m
16 FT 4.9 m
5 FT 1.5 m
1.5 FT 0.5 m
5 FT 1.5 m
When running horizontal combustion air and venting for single or m ultiple units, exhaust and combustion air terminals must be installed on the same plane (outside wall) in order to prevent pressure differences due to prevailing winds. In cold climates, double-wall or insulated inlet pipe recommended to prevent condensation.
Figure 5 - Horizontal Combustion Air and Venting for Multiple Units
Page 8
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 8
Figure 6 - Vertical Combustion Air and Venting, Metal Chimney System Shown
Figure 7 - Combination Air Intake And Venting, Masonry Chimney Shown
MINIMUM VERTICAL RISE
OFF THE TOP OF UNIT "A"
12"
24"
10 FT 3.1 m
VENT PIPE DIAMETER
IN. mm FT mm
5" TO 10"
12" TO 18"
3 FT 1 m
127 TO 254 305 TO 457
305 610
1.5 FT .5m
Page 9
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 9
GENERAL VENTING GUIDELINES
WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54-latest revision or applicable provisions of the local building codes. Canadian installations must comply with CSA B149.1 or .2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
All vent systems must be fully supported by the building structure and not by the boiler/water heater. Appropriate thimbles and fire-stops must be used where required.
WARNING: Common vent systems must be properly engineered and sized to provide a negative draft of 0.01 to 0.08 in, W.C. at the flue outlet! Common positive pressure vent systems are not to be used. Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
NOTE: A double acting installed directly to the boiler/water heater flue outlet to ensure proper operation. This does not apply to outdoor units or direct vent positive pressure units.
barometric damper
.25 to 2.0 mm
must be
VENT SYSTEM OPTIONS
The LCD may be vented the following ways:
A barometric damper must be installed when the horzontal run is longer than 35 equivalent feet. (90 degree elbow = 10 equivalent feet). If this is the case, a power venter must also be used.
If horizontal run is less than 35 equivalent feet, do not use a barometric damper. F ollow applicab le instructions under the “COMBUSTION AIR & VENTILA TION” section.
4)
Outdoor Installation -
Barometric damper is not required.
NOTE: All venting, comb usiton air material supplied by installer.
uses the outdoor option kit.
VERTICAL/CHIMNEY VENTING
The LCD is listed as a Category I appliance when vented vertically into a metal chimney system or properly sized masonry chimney, Figures 1,2, 6 & 7. The chimney must provide a negative pressure of 0.01 to
0.08 in, flue collar with the unit running at full load. A barometric damper must be installed between the flue collar and the vent connector. Approved thimbles and fire-stops must be used when combustible construction is penetrated.
.25 to 2.0 mm
WARNING : If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney flue, never connect an y other appliances to this flue. Doing so can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
W.C. at the boiler/water heater
1)
Vertical/Chimney V enting -
chimney system or properly lined masonry chimney. Combustion air is obtained from the space in which the unit is installed or from outdoors. A double acting barometric damper must be installed near the flue outlet when venting vertically. See Figures 6 and 7. This also applies to any fan-assisted chimneys or vents.
2)
Direct Vent, Positive Pressure -
runs equivalent to 35 ft, 10.8 m or less. A stainless steel vent system certified to UL 1738 for installations in the United States. ULS636 for installations in Canada must be used when combustion air is ducted from outdoors, from the same wall.
3)
Horizontal Vent, Negative Pressure -
vent runs equivalent to more than 35 ft, 10.8 m (90 degree elbow equals 10 equivalent feet). A dedicated wall mounted power venter must be used. The vent system can be single wall galvanized steel or type B vent pipe. Combustion air is obtained from the space in which the unit is installed or from the outdoors.
uses an approved metal
for horizontal vent
for horizontal
Chimney Inspection & Sizing
A thorough inspection of the masonry chimney must be performed to ensure that the chimney is clean, properly constructed, lined and sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems. Table 4 lists the equivalent breeching and flue sizes required for the boiler/water heater. When more than one appliance is connected to the same chimney flue the flue must be large enough to safely vent the combined output of all of the appliances.
Table 4 - Equivalent Breeching & Chimney Size
Model Size Pipe Diameter
in
mm
225 5 300 - 400 6 600 - 750 8
900 - 1050 10 1200 - 1480 12 1650 - 2300 14
Note: These sizes are based on a 20 ft,
6.1m
127 152 203 254 305 356
chimney height.
Page 10
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 10
Vent Connections
Locate the boiler/water heater as close to the chimney as possible. Use the shortest, straightest vent connector possible for the installation. If horizontal runs exceed 5 ft,
1.5 m
they must be supported at 3 ft, intervals with overhead hangers. Use a type B, single wall stainless or single wall galvanized steel vent pipe the same diameter as the flue collar to connect the boiler/water heater to a masonry chimney. When using an approved metal chimney system use the appropriate vent connector. The vent connector should be sloped up toward the chimney at a minimum rate of 1/4 in/ft,
2 cm/m
terminate flush with the inside of the chimney flue, Figure 2. Fasten each single wall vent connection with at least 3 corrosion resistant sheet metal screws.
Always provide a minimum clearance of 6 in, between single wall vent pipe and any combustible materials. Type B1 vent may be used, clearance between it and any combustible material must be as listed.
. On masonry chimneys the connector must
WARNING: Never install a vent pipe having a diameter different than that of the boiler/water heater flue collar. Failure to comply with this warning can result in excessive levels of carbon monoxide which can cause severe personal injury or death.
0.9 m
152 mm
Horizontal Direct Vent Systems - Figures 4 & 5
The vent materials used in horizontal vent systems must be certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. The certified vent terminal from RBI must also be used. The following manufactures have systems that meet these requirements:
Heat-Fab, Inc. 38 Hayward Street Greenfield, MA 01301, (800) 772-0739.
Z-Flex U.S., Inc., 20 Commerce Park North Bedford, NH 03110-6911, (800) 654-5600.
Protech Systems Inc. 26 Gansevoort Street Albany, NY 12202, (518) 463-7284
The maximum equivalent length for the horizontal vent and combustion air pipes is 35 ft,
Each 90˚ elbow and the intake air and vent terminals are equal to 10 ft, the performance of single wall sheet metal vent systems locate 90˚ elbows as far from the boiler as possible and from one another. For best results, horizontal vent systems should be as straight as possible.
3.3 m
of straight pipe. To maximize
10.8 m
for each.
WARNING: Failure to maintain minimum clearances between vent connectors and any combustible material can result in a fire causing extensive property damage, severe personal injury or death!
DIRECT VENT , POSITIVE PRESSURE
In this configuration the boiler/water heater blower is used to push the flue products to the outdoors while drawing combustion air from the outdoors. The equivalent length of the vent and combustion air systems must not exceed 35 ft, instructions under the “COMBUSTION AIR & VENTILATION SECTION” must be followed! The vent system must be sized per Table 4.
10.8 m
for each. The Intake Air Option
The vent system must be both gas tight and watertight. All seams and joints in metal pipes must be joined and sealed in accordance with the vent system manufacturer’s instructions.
When horizontal vent runs exceed 5 ft, must be supported at 3 ft, overhead hangers. The vent system must be pitched down, toward the vent terminal, 1/4 in/ft, If any part of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400˚F,
204˚C
0.98 m
.
1.5 m
they
intervals with
21 mm/m
.
Page 11
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 11
Horizontal vent systems shall terminate at least 4 ft,
1.3 m
below , 4 ft, 1.3 m horizontally from or 1 ft, above any door, window or gravity air inlet into any building. It must not terminate less than 4 ft, horizontally from, and in no case above or below , unless a 4 ft, electric meters, gas meters, regulators and relief equipment and not less than 7 ft, public walkway. The bottom of the vent terminal(s) shall be located at least 5 ft, terminal(s) unless there is a minimum 5 ft, horizontal separation between them. Avoid terminal locations likely to be affected b y winds, snowdrifts, people and pets. Protect building materials and vegetation from degradation caused by the flue gases.
Vertical Direct Vent Systems - Figure 6
The maximum length for the vertical vent and combustion air pipes is 35 ft, elbows. If any par t of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400˚F, penetrations must be made using approved fire-stops.
A listed, nonrestrictive vent cap must be used. The top of a vertical vent system must extend at least 5 1/2 ft,
1.8 m
4 ft,
1.3 m
horizontal distance is maintained, from
2.3 m
from any adjacent
1.5 m
above the air intake
10.8 m
plus two 90˚
204˚C
above the roof surface that it passes through,
1.3 m
above the intake air cap, see Figure 6.
0.23 m
1.3 m
1.5 m
. Structural
HORIZONT AL VENT , NEGATIVE PRESSURE
In this configuration a wall-mounted power venter must be used to pull the flue products horizontally from the unit and vent them to the outdoors, see Figures 3, 4 &
5. The air for combustion is taken from the space in which the unit is installed, or from the outdoors. The applicable instructions under the “COMBUSTION AIR & VENTILATION SECTION” must be followed!
To maximize the performance of single wall sheet metal vent systems locate 90˚ elbows as far from the boiler as possible and from one another. For best results, horizontal vent systems should be as short and straight as possible.
When horizontal vent runs exceed 5 ft, must be supported at 3 ft, overhead hangers. The vent system must be pitched down, toward the vent terminal, 1/4 in/ft, If any part of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400˚F,
204˚C
0.98 m
.
1.5 m
they
intervals with
21 mm/m
Horizontal vent systems shall terminate at least 4 ft,
1.3 m
below, 4 ft,
0.23 m
into any building. It must not terminate less than 4 ft, or below, unless a 4 ft, is maintained, from electric meters, gas meters, regulators and relief equipment and not less than 7 ft,
2.3 m
of the vent terminal(s) shall be located at least 5 ft,
m
a minimum 5 ft, them. Avoid terminal locations likely to be affected by winds, snowdrifts, people and pets. Protect building materials and vegetation from degradation caused by the flue gases.
To determine the appropriate power venter for the boiler/water heater, see Table 5. Follow the power venter manufacturer’s installation instructions.
Table 5 - Power Venter Sizes
*Choose HS115-2 for 100 ft. Max. Pipe length **Choose HS-3 for 100 ft.
above any door, window or gravity air inlet
1.3 m
horizontally from, and in no case above
from any adjacent public walkway. The bottom
above the air intake terminal(s) unless there is
LCD Po wer Venter Max. Pipe Length
Model Model FT m
225 - 300 HS-1 30* 9.3
400 HS-2 100 31.0 600 HS-2 67** 20.8
750-900 HS-3 100 31.0 1050-1200 HS-4 100 31.0 1480-2300 HS-5 100 31.0
1.3 m
horizontally from or 1 ft,
1.3 m
horizontal distance
1.5 m
horizontal separation between
31 m
, Max. Pipe Length
OUTDOOR VENTING
When installed outdoors the LCD must be fitted with the factory supplied outdoor vent hood and air intake hood, see Figure 8. Multiple units must be spaced per Figure 9.
The boiler/water heater must be at least 10 ft, from any door, window or gravity air inlet into any building and at least 3 ft, unless local codes dictate differently.
CAUTION: Do not place the boiler/water heater in a location that would subject it to runoff from adjacent buildings or damage may occur voiding the
.
warranty!
0.9 m
from any overhang
1.5
3.0 m
Page 12
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 12
Figure 8 - Outdoor Venting
Figure 9 - Multiple Outdoor Units
a) Seal any unused openings in the common venting
system. Sceller toutes les ouvertures non utilisées du sys-
tème d'évacuation.
b) Visually inspect the venting system for proper size
and horizontal pitch and determine if there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d'évacu-ation pour déterminer la grosser et l'inclinaison horizontale qui conviennent et s'assurer que le système est exempt d'obstruction, d'étranglement de fruite, de corrosion et autres défaillances qui pourraient présenter des risques.
c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Tur n on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust, so they will operate at maxim um speed. Do not operate a summer exhaust fan for a boiler installation. Close fireplace dampers.
COMMON VENT SYSTEMS
If an existing boiler/water heater is removed from a common venting system, the common venting system may then be too large for the proper venting of the remaining appliances connected to it. At the time of removal of an existing boiler/water heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Au moment du retrait d'une chaudière existante, les mesures suivantes doivent être prises pour chaque appareil toujours raccordé au système d'évacuation commun et qui fonctionne alors que d'autres appareils toujours raccordés au système d'évacuation ne fonction­nent pas: système d'év acuation
Dans la mesure du possible, fermer toutes les portes et les fenêtres du bâtiment et toutes les portes entre l'espace où les appareils toujours raccordés du système d'évacuation sont installés et les autres espaces du bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au système d'évacuation commun et tous les ventilateurs d'extraction comme les hottes de cuisinère et les ventilateurs des salles de bain. S'assurer que ces ventilateurs fonctionnent à la vitesse maximale. Ne pas faire fonctionner les ventilateurs d'été. Fermer les registres des cheminées.
d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Mettre l'appareil inspecté en marche. Suivre les instructions d'allumage. Régler le thermostat de façon que l'appareil fonctionne de façon continue.
Page 13
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 13
e) After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
Une fois qu'il a été d éterminé, selon la métode indiquée ci-dessus, que chaque appareil raccordé au système d'évacuation est mis à l'air libre de façor adéquate. Remettre les portes et les fenêtres, les ventilateurs, les registres de cheminées et les appareils au gaz à leur position originale.
f) Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix F in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and or CSA B149 Installation Codes.
Tout mauvais fonctionnement du systéme d'évacu­tion commun devrait étré corrigé de façor que l'installation soit conforme au National Fue Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d'installation CAN/CGA-B149. Si la grosseur d'une section du système d' évacuation doit étré modifiée, le système devrait étré modifié pour respecter les valeurs minimales des tableaux pertinents de l'appendice F du National Fuel Gas Code, ANSI Z223.1/ NFPA 54 et (ou) des codes d'installation CSA-B149.
GENERAL PIPING REQUIREMENTS
CAUTION: Improper piping of this boiler/water heater will void the manufacturer's warranty and can cause boiler failure resulting in flooding and extensive property damage! Excessive water hardness causing scaling in the copper heat exchanger tubes is covered under the manufacturers warranty. Excessive pitting and erosion of the internal surface of the copper heat exchanger tubes is
NOT
under the manufacturer’s warranty if the result of high water flow rates, see Table 6. Return water temperatures below 125°F,
52°C
will result in heat exchanger damage from excessive condensation voiding the manufacturer’s warranty, see Primar y/ Secondary Piping Figure 11.
NOT
covered
Table 6 - Temperature Rise Table
T = 15 °F
Model Flow Rate Pres. Drop
Number GPM Ft
225 24.6 0.18 300 32.8 0.31 400 43.7 0.70 600 65.6 1.84 750 82.0 3.32 900 98.4 * 5.42
T = 20 °F
Model Flow Rate Pres. Drop
Number GPM Ft
300 24.6 0.18 400 32.8 0.41 600 49.2 1.08 750 61.5 1.95
900 73.8 3.18 1050 86.1 5.16 1200 98.4* 8.14 1480 121.4* 7.94
T = 25 °F
Model Flow Rate Pres. Drop
Number GPM Ft
400 26.2 0.27
600 39.4 0.71
750 49.2 1.29
900 59.0 2.10 1050 68.9 3.41 1200 78.7 5.38 1480 97.1 5.25 1650 108.2 7.02
T = 30 °F
Model Flow Rate Pres. Drop
Number GPM Ft
600 32.8 0.51
750 41.0 0.92
900 49.2 1.50 1050 57.4 2.44 1200 65.6 3.84 1480 80.9 3.75 1650 90.2 5.01 1970 107.7 8.75 2300 125.7* 12.45
T = 35 °F
Model Flow Rate Pres. Drop
Number GPM Ft
600 28.1 0.38
750 35.1 0.69
900 42.2 1.13 1050 49.2 1.83 1200 56.2 2.89 1480 69.3 2.89 1650 77.3 3.79 1970 92.3 6.58 2300 107.8 9.36
*Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupro-Nickel exchanger should be
considered.
T = 8.3 °C
Flow Rate Pres. Drop
L/s kPa
1.6 0.5
2.1 0.9
2.8 2.1
4.1 5.4
5.2 9.8
6.2 16.0 T = 11.1 °C
Flow Rate Pres. Drop
L/s kPa
1.6 0.5
2.1 1.2
3.1 3.2
3.9 5.7
4.7 9.4
5.4 15.2
6.2 24.0
7.7 23.4 T = 13.9 °C
Flow Rate Pres. Drop
L/s kPa
1.7 0.8
2.5 2.1
3.1 3.8
3.7 6.2
4.3 10.1
5.0 15.9
6.1 15.5
6.8 20.7 T = 16.7 °C
Flow Rate Pres. Drop
L/s kPa
2.1 1.5
2.6 2.7
3.1 4.4
3.6 7.2
4.1 11.3
5.1 11.0
5.7 14.8
6.8 25.8
7.9 36.7 T = 19.4 °C
Flow Rate Pres. Drop
L/s kPa
1.8 1.1
2.2 2.0
2.7 3.3
3.1 5.4
3.5 8.5
4.4 8.3
4.9 11.1
5.8 19.4
6.8 27.6
NOTE: Shut off valves and unions should be installed at the inlet and outlet connections of the boiler/water heater to provide for isolation of the unit should servicing be necessary.
Page 14
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 14
Freeze Protection
This boiler/water heater is CSA designed certified for outdoor installation. Outdoor installations in areas where the danger of freezing exists are not recommended unless proper freeze protection is provided. If the unit is to be installed in such an area the following precautions MUST be observed:
1. A continuous flow of water through the boiler/water heater MUST be maintained! The pump responsible for flow through the boiler/water heater must run continuously!
2. An ethylene glycol/water mixture suitable for the minimum temperature that the unit will be exposed to must be used. The pump must be capable of producing 15% more flow and overcoming a 20% increase in head loss. Domestic w ater systems m ust be isolated from the water heater by the use of a heat exchanger or other approved method.
3. If the boiler/water heater must be shut off for any reason the electric, gas and water supplies MUST be shut off and the unit and its pump completely drained.
CAUTION: Improper outdoor installation of this boiler/water heater can cause boiler failure voiding the manufacturer's warranty!
Relief Valve
Pipe the discharge of the pressure relief valve to pre vent scalding in the event of a discharge, see Figure 10. The discharge piping must be sized the same as the pressure relief valve outlet and installed to allow complete dr ainage of both the relief valve and the discharge piping.
Figure 10 - Relief Valve Piping
WARNING: Never install any type of valve between the boiler/water heater and the relief valve or an explosion causing extensive property damage, severe personal injury or death may occur!
Flow Switch
The flow switch supplied with the boiler/water heater must be wired to the terminal strip in the control panel to prevent the boiler from firing unless there’s adequate water flow through the unit. The flow switch must be installed in the supply piping adjacent to the boiler outlet connection.
CAUTION: Failure to properly install the flow switch may result in damage to the boiler/water heater heat exchanger voiding the warranty!
HEATING SYSTEM PIPING
General Piping Requirements
All heating system piping must be installed by a qualified technician in accordance with the latest revision of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV, and when required, ANSI/ASME CSD-1, Standard for Controls and Safety Devices for Automatically Fired Boilers. All applicable local codes and ordinances must also be followed. A minimum clearance of 1 in, must be maintained between heating system pipes and all combustible construction. All heating system piping must be supported by suitable hangers not the boiler.
The thermal expansion of the system must be considered when supporting the system. A minimum system pressure of 12 psig, maintained.
Heating Boiler Piping Connections
The supply and return piping should be sized to suit the system. The supply and return connection sizes are listed in Table 7.
82.7 kPa
25 mm
must be
Table 7 - Supply & Return Connection Sizes
Model Size Supply Return
225 thru 300 1-1/2" NPT 1-1/2" NPT
400 thru 2300 2-1/2" NPT 2-1/2" NPT
Pump Requirements
This low mass boiler requires a continuous minimum water flow for proper operation. The system pump must be sized to overcome the head loss of the boiler and the heating system in order to achieve the required temperature rise. Table 6 provides the heat exchanger pressure drop and temperature rise figures.
Page 15
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 15
CAUTION: A temperature rise outside of the range listed in Table 6 indicates that the flow rate through the heat exchanger is incorrect which will damage the heat exchanger voiding the warranty! The maximum allowable temperature rise is 35°F,
The maximum allowable flow rate through a LCD boiler with copper heat exchanger is 92 GPM,
5.8 L/s
on 1480 to 2300 models. The cupro-nickel heat exchanger allows for 100 GPM, 1200 models and 125 GPM, models.
Low Water Cutoff
If a boiler is installed above any radiation elements it must be fitted with a low water cutoff device.
Refer to wiring diagram supplied with the boiler/water heater for proper wiring connections.
Expansion Tank & Air Separator
An expansion tank or other means to control thermal expansion must be installed in the heating system. An expansion tank must be installed close to the boiler on the suction side of the pump. An air scoop and automatic air vent must also be installed to eliminate air trapped in the system.
Primary/Secondary Piping
Boilers connected to heating systems using zone valves , zone pumps, or systems that have excessive flow rates or return water temperatures less than 125°F, must be isolated from these systems to protect the boiler.
Variab le Water Flows
Figure 11 shows a typical primary/secondary piping system. A dedicated pump is used to maintain a constant water flow through the boiler.
on 225-1200 models and 115 GPM,
6.3 L/s
7.9 L/s
on 1480 to 2300
19.4°C
7.3 L/s
on 225 to
52°C
Low Return Water Temperatures
To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary/secondary piping system with
.
a bypass and bypass valve must be installed, see Figure
12. The bypass and bypass valve must be sized the same as the secondary piping.
A balancing valve must also be installed in the supply side of the secondary piping downstream of the bypass. The balancing valve should be adjusted to divert some of the heated discharge water into the return water until the required inlet water temperature is achieved. The primary and secondary pumps should be sized to provide the required flow through each system. The secondary piping connections to the primary system piping must not be more than 12 in, ensure zero pressure drop in the primary system, see Figure 12.
Multiple Boiler Systems
Systems using multiple boilers can also be installed using a primary/secondary manifold system, Figure 13.
Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler. Appropriate valves must be used to prevent the chilled water from entering the boiler.
When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device, the piping system must be equipped with flow­control valves or some other automatic means of preventing gravity circulation of the boiler water during the cooling cycle.
305 mm
apart to
This secondary pump is sized to overcome the head loss of the boiler and secondary piping system while supplying the flow rate required to maintain the desired temperature rise across the boiler. The primary pump is sized to provide the required flow to the heating system. The secondary piping connections to the primary system piping must not be more than 12 in,
mm
apart to ensure zero pressure drop in the primar y
system, see Figure 11.
305
Page 16
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 16
Figure 11 - Typical Primary/Secondary Piping System See Notes
Figure 12 - Low Temperature Piping See Notes and Adjustment Procedures
Page 17
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 17
Figure 13 - Multiple Boiler Piping (See notes)
ax
Page 18
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 18
DOMESTIC WATER SUPPLY PIPING
CAUTION: Proper control settings must be used to prevent water supplied for domestic use from exceeding 130°F, When higher water temperatures are required for appliances such as a dishwasher, a mixing valve or some other tempering means must be installed. Households with small children may require water temperatures less than 120°F, must be complied with!
General Piping Requirements
Ensure that the water heater is equipped with bronze headers. Piping and components connected to the water heater must be suitable for use with potable water. The water heater must not be connected to any heating system piping or components previously used with a non­potable water heating appliance. No toxic chemicals, such as those used for boiler treatment, are to be introduced into the potable water used for space heating. If a hot water storage tank is used in the system it must be equipped with a temperature and pressure relief valve that complies with ANSI Z21.22 or CAN-4.4 and CAN-4.6.
NOTE: The storage tank must be located as close to the water heater as possible to prevent excessive head loss which will reduce flow.
Water Chemistry
The required temperature rise across the water heater is based on water having a hardness between 8 and 18 grains per gallon with a level of dissolved solids not exceeding 350 ppm. Water having a hardness less than 8 grains can cause excessive errosion of the heat exchanger. Water that has a hardness greater than 18 grains per gallon and/or a level of dissolved solids exceeding 350 ppm will require a recalculation of the pump size and temperature rise.
54°C
or a scald injury will occur!
49°C
. Local codes
A Cupro-Nickel heat exchanger may also be required. The manufacturer should be consulted when these water conditions are encountered.See Table 8A
CAUTION: a LCD water heater with copper heat exchanger is 92 GPM,
L/s
on 1480 to 2300 models. The cupro-nickel heat exchanger allows for 100 GPM, models 125 GPM, T able 8B .
RBI water heaters are designed to run scale free. Due to the extreme variables of water conditions world wide it is necessary to consider pH values and water hardness in relationship to scaling. It is crucial to consider these two variables when making heat exchanger and pump selection. If local water conditions are extreme follo w the guidelines in the Heat Exchanger Selection Table (Table 8A) and the Pumping Performance Table (Table 8B). Scale free operation can be achieved by using water with a hardness between 8 and 18 and by maintaining the pH between 5 and 9. Follow the conditions listed under NORMAL in the table. In some areas of the country additional precautions must be observed due to unusual characteristics of the local water supply. Call the nearest RBI representative for details.
To properly size the pump a grain hardness and pH test must be taken at the installation site before the order is placed. Proper pump sizing will improve heater performance and help ensure heater longevity .
The maximum allowable flow rate through
5.8 L/s
on 225-1200 models and 115 GPM,
6.3 L/s
on 225 to 1200
7.9 L/s
on 1480 to 2300 models, see
7.3
Page 19
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 19
T able 8A - LCD Heat Exchanger Selection Graph
T able 8B - LCD Pumping Perf ormance Requirement
Page 20
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 20
Expansion T ank
An expansion tank or other means to control thermal expansion must be installed in the water heating system if back flow prevention devices are installed.
Cold Water Supply
The cold water supply must be piped to the water heater’s outlet piping between the water heater and the hot water storage tank. This will prevent untempered water from entering the water heater, see the Temperature Rise Control section below. A typical water heating system is shown in Figure 14 and 15.
Pump Requirements
This low-mass water heater requires a continuous minimum water flow for proper operation. The low water flow switch provided for this unit will shut down the water heater if flow falls below the required minimum level. Table 8A provides the heat exchanger pressure drop chart and temperature rise table.
Temperature Rise Control
Water returned to the water heater inlet must not be less than 125°F,
52°C
or excessive condensation of the products of combustion will damage the water heater voiding the warranty. The method outlined below can be employed to prevent this condition from occurring.
A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the flow rate through the heat exchanger . Thermometers are installed on both the inlet and outlet of the water heater for determining the temperature rise through the unit. The proper velocity through the water heater must be maintained in accordance with Table 8B for efficient operation and long life. If the temperature rise through the water heater is lower than recommended the water v elocity is too high. Premature erosion of the heat e xchanger will occur. Con versely, if the temperature rise is higher than recommended in Table 8B the flow rate is too low . Scaling and softening of the heat exchanger will occur .
Thermostatic Mixing Valve - Water Above 140°F,
60°C
Water can be stored at temperatures above 140°F,
60°C
provided that a thermostatically controlled mixing valve is used to temper the hot water to an acceptable temperature before it’s supplied for domestic use.
The mixing valve MUST be set to prevent a scald injury from occurring, see the caution against scalding above.
Page 21
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 21
Figure 14 - Typical Water Heating Piping See Notes
Figure 15 - Multiple Water Heating Piping See Notes
Page 22
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 22
GAS SUPPLY PIPING
WARNING: Check the boiler/water heater rating plate to make sure that the boiler/water heater is for the type of gas that will be used. If it isn’t, do not connect the boiler/water heater to the gas supply. Failure to comply with this warning can result in extensive property damage, severe personal injury or death!
The LCD comes from the factory ready to be piped to the gas supply. If for any reason the boiler/water heater is not for the type of gas available at the installation site, call your RBI Water Heaters representative to resolve the problem.
Note: A minimum gas supply pressure of 6 in,
152 mm,
and maximum 14 in, propane, must be available at the safety shutoff valve inlet with the unit(s) operating.
Table 9 should be used to ensure that the gas supply piping is sized properly. If more than one appliance is supplied by the same supply pipe, the piping must be sized based on the maximum possible demand. Do not neglect the pressure drop due to pipe fittings. Table 9 should be used in conjunction with Table 10 to ensure that the gas supply piping has the capacity to meet the demand.
W.C. natural or 11 in,
356 mm
279 mm
W .C. propane
W.C. natural or
Table 10 - Equivalent Pipe Length Chart
Nominal Iron Pipe Size, (in)
1 11/4 11/2
2 21/2
3
Notes: 1. For flow through branch.
90° Elbow Tee
2.6 5.2 0.6 1.5
3.5 6.9 0.8 1.9
4.0 8.0 0.9 2.3
5.2 10.3 1.2 3.0
6.2 12.3 1.4 3.7
7.7 15.3 1.8 4.5
2. For flow at full open.
Type of pipe fitting
1
Gas Valv e2Gas Cock
Equivalent pipe length, (ft)
2
CAUTION: Always use a wrench on the gas valve body when making gas connections to it. Never over-tighten the piping entering the gas valve body or gas valve failure may result!
Figure 16 - Gas Supply Piping
Figure 16 depicts the proper way to connect the boiler/ water heater to the gas supply piping. Provide a sediment trap at the bottom of the vertical section of the gas supply pipe upstream of the gas controls.
A ground joint union should be installed between the boiler gas controls and the supply piping. Each of these items are needed to ensure long life and ease of servicing. Always use a pipe sealant that is suitable for use with LP gas.
Table 9 - Gas Pipe Capacity
Maximum pipe capacity in ft3/hr based on 0.60 specific gravity gas at a pressure of 0.5 psig or less and a 0.3" WC pressure drop.
Nominal Iron Pipe Size, (in)
3
1 11/4 11/2
2 21/2
3
Note: Multiply the gas volume by 0.62 for propane flow capacity in ft3/hr. Multiply the propane flow capacity by 2500 Btu/ft3 to determine the propane Btu/hr capacity for a given pipe size and length.
10 20 30 40 50 60 80 100 150
Maximum gas volume of pipe, (ft3/hr)
278 190 152 130 115 105 90 79 64
/4
520 350 285 245 215 195 170 150 120 1050 730 590 500 440 400 350 305 250 1600 1100 890 760 670 610 530 460 380 3050 2100 1650 1450 1270 1150 990 870 710 4800 3300 2700 2300 2000 1850 1600 1400 1130 8500 5900 4700 4100 3600 3250 2800 2500 2000
Pipe length in feet
When applicable, provisions for vent, bleed and gas relief lines must be made in accordance with the latest revision of ANSI Z223.1/NFPA 54.
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler. All gas connections MUST be leak tested before putting the boiler into operation.
WARNING: Never use an open flame to test for gas leaks. Always use an approved leak detection method. Failure to comply with this warning can cause extensive property damage, severe personal injury or death!
Whenever the gas supply piping is pressure tested the boiler/water heater gas controls must be protected. If the test pressure is equal to, or less than 1/2 psig,
3.5 kPa
isolate the boiler/water heater by closing it's manual shut off valve, see Figure 16. If the test pressure is greater than, or equal to 1/2 psig,
3.5 kPa
, disconnect the
boiler/water heater and its individual shut-off valve.
Page 23
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 23
ELECTRICAL WIRING
Electrical Power Connections
CAUTION:Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation! Verify proper operation after servicing.
ATTENTION. Au moment de l'entretien des commandes, étiquetez tous les fils avant de les débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement inadéquat et dangereux. S'assurer que l'appareil fonctionne adéquatement une fois l'entretirn terminé.
The electrical connections to this boiler/water heater must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI/NFPA-70. Installation should also conform with CSA C22.1 Canadian Electrical Code Part I if installed in Canada.
Install a separate 120 volt 15 amp circuit breaker for the boiler/water heater and pump, see Table 11. A properly rated shut-off switch should be located at the boiler/ water heater. The boiler/water heater must be grounded in accordance with the authority having jurisdiction, or if none, the latest revision of the National Electrical Code, ANSI/NFPA-70.
GENERAL OPERATION
WARNING: Before proceeding read and fully understand the instructions contained in this manual. Do not attempt to operate this boiler/ water heater if it has not been installed in accordance with the guidelines set forth in this manual. F ailure to comply with this warning can result in extensive property damage, severe personal injury or death!
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance. Do not interrupt water flow through the boiler/ water heater.
En cas de surchauffe ou si l'alimentation en gaz ne s'arrête pas, fermez manuellement le robinet d'arrêt de l'admission de gaz.
Hydronic Heating Boilers
Open the make-up water valve and slowly fill the boiler and all of the radiation with water. Ensure that all bleed and drain valves are closed.
Adjust the make-up water pressure regulator so a minimum 12 psig, maintained at the highest point in the system piping. If a make-up water pump is used adjust it to maintain a minimum 12 psig,
83 kPa
83 kPa
system pressure is
system pressure.
Table 11 - LCD Electrical Requirements
Recommended
LCD Circuit Breaker *Running
Model (Amps) Amps LB/LW 225-600 15 3.9 LB/LW 750-900 15 6.0
LB/LW 1050-1970 20 11.4
LB/LW 2300 20 14.4 *Use separate circuit breaker that is properly sized for pump and pump contactor.
Line voltage field wiring of any controls or other devices must use copper conductors with a minimum size of #14 awg. Use appropriate wiring materials for units installed outdoors. The wire size must be compatible with the total amp draw of the circuit.
Refer to the wiring diagram supplied with the boiler/ water heater for proper wiring connections.
Open the system bleed and drain valves one at a time to purge the air trapped in the heating system piping.
With the boiler off, run the system pump for at least 30 minutes and bleed the system piping using the bleed valves. If strainers are used in the system piping the make-up water valve should be closed and the strainers checked and cleaned.
The system expansion tank should be checked to ensure that the correct water level in the tank is maintained. The tank should be less than half full of water with the system full and adjusted to the correct operating pressure.
Start the boiler as described in the “OPERATING INSTRUCTIONS”. Run the boiler for at least an hour. The system pump(s) and all radiation units must be operated during this time. Ensure that the make-up water valve is open.
Shut the boiler off and open the bleed valves to purge the air trapped in the heating system piping. Close the make-up water valve and check and clean the strainers and make-up water pressure reducing valve.
Page 24
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 24
Open the make-up water valve and adjust the system pressure if necessary. The system should be checked and bled after three days of operation.
BOILER W A TER HEA TER OPERATION
Staging Operation
The LCD boiler/water heater series is separated into on/ off and 2-stage units depending on the model selected. The 225 and 300 models have on/off staging, while the 400 through 2300 models have a two stage option. Input staging is controlled from an aquastat controller that signals the relays to select the blower and gas valve modes. Table 12 identifies the stages and firing modes associated with the standard single stage units. Table 13 identifies the stages and firing modes associated with the two stage option.
Table 12 - Firing Modes (L225-L2300)
Stage Firing Mode
Off Off
1On
Table 13 - Firing Modes (L400-L2300)
Stage Firing Mode
Off Off
1 Low Fire 2 High Fire
The outlet water temperature is automatically controlled by the aquastat. The optional staging function is controlled by a return water aquastat. The return water aquastat utilizes inputs from the inlet water temperature sensors or optional tank sensors to stage the boiler/ water heater as required.
Pressure Switch Settings
Differential pressure switches are provided in the LCD to shut down gas flow under a blocked flue or inlet condition. A single pressure switch is used on the standard models. One low fire and one high fire pressure switch is used when the two-stage option is employed. The low fire pressure switch serves to shut down gas flow if there is a blocked flue or inlet condition during low fire operation. Similarly, the high fire switches will shut down gas flow if there is a blocked flue or inlet condition during high fire operation. The differential
pressure is taken between the air plenum and the pressure inside one of the main burners.
Pressure taps are provided in the control compartment for taking the differential pressure readings, Figure 17. Table 14 lists the differential pressure settings for all of the models.
Figure 17 - Pressure Switch Tap(s)
Table 14 - Differential Pressure Settings (All Units)
Firing Mode Differential Pressure
Inches W .C.
Optional Low Fire 0.7 ± 0.1
High Fire 1.0 ± 0.2
On all units, the pressure switch(es) will interrupt power to the control module under a blocked flue or inlet condition. This will cause the pilot and main gas valves to close. Tables 15 and 16 identify how pressure switch control changes during boiler/water heater staging. Tables 17 and 18 identify the control actions if a low air condition occurs at any stage.
Table 15 - Pressure Switch Control,
L225-L300
Stage Pressure Switch Mode
Off Off
1 High Fire
Table 16 - Pressure Switch Control,
L400-L2300
Stage Pressure Switch Mode
Off Off
1 Low Fire 2 High Fire
Table 17 - Low Air Condition Action,
L225-L2300
Stage Control Action
1 No Power to Flame Sense Module
Table 18 - Low Air Condition Action,
L400-L2300
Stage Control Action
1 No Power to Flame Sense Module 2 No Power to Flame Sense Module
mm W .C .
16.8 ± 2.5
24.9 ± 5.1
Page 25
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 25
OPERATION SEQUENCE, ON/OFF L225 through L2300
Note: Refer to the wiring diagram included with the unit for further control system info.
POWER ON:
Demand for Heat:
1. The operator switch closes, energizing pump delay
timer TD4 and the w ater pump(s).
2. Water flow through the unit closes the water flow
switch contacts energizing blower delay timer TD3.
3. The system checks all primary limit(s) and other
interlocks before starting pre-purge. The unit will not start if any switch is open.
Prepurge:
1. Blower delay timer TD3 energizes the high speed
windings of the blower(s).
2. Air pressure in the combustion chamber is sensed.
If the air pressure is sufficient, the pressure switch closes allowing the blower delay timer TD1 to start a 7 second pre-purge.
Ignition T rial:
1. Blower delay timer TD1 times out and the flame
sense module, FSM, is energized.
2. The FSM starts the 10-second ignition trial,
energizing relay R7, the pilot solenoid valve and the spark generator.
3. The pilot valve and spark generator are energized
for the 10-second ignition trial. When the pilot flame is sensed, the FSM sends 24VAC to its MV terminal energizing the safety and main solenoid valves and relay R8, de-energizing relay R7 and the spark generator.
4. If the pilot flame isn’t sensed, the FSM de-energizes
the PV terminal and waits 5 minutes before initiating the second ignition trial. The blower(s), pump(s) and optional power venter will remain on during this time.
5. On CSD-1 equipped units the blower(s) and optional
power venter will shut down and the boiler/water heater will lock if the second ignition trial fails. The unit must then be manually reset by depressing the reset button on the left jacket panel.
6. On non-CSD-1 equipped units the FSM will wait 10
minutes after the second unsuccessful ignition attempt then begin the ignition process described in step 3 above. The FSM will continue to cycle the unit through steps 3, 4 and 6 until the unit lights or the demand for heat is removed.
Main Burner
Once the pilot is proven, the MV terminal on the FSM is energized sending 24VAC to the safety and main solenoid valves.
Normal Operation
On single stage units the blowers and gas valves operate at one input.
Demand Satisfied:
1. When the demand for heat is satisfied the operator switch will open, de-energizing relay R8, TD1, TD3, TD4 the FSM and the pilot, main and safety solenoid valves. The pilot and main flames are extinguished.
2. The blower delay timer TD3 star ts the 80 second post-purge timing. The blower(s) shut(s) off when TD3 times out.
3. The pump delay timer TD4 starts the post-purge timing. The pump(s) remain on for 0.1 to 10 minutes then shut(s) off when TD4 times out.
High Limit, Low Water Flow, Low Gas Pressure, High Gas Pressure, Power Venter Interlock Faults
1. Electrical power to the gas valves, blower(s) and optional power venter will be interrupted if any saf ety is tripped.
2. The manual reset high limit can be reset by depressing the rubber plug in the front top jacket panel.
Low Air (Blocked Flue/Air Inlet)
• The pressure switch will monitor blower airflow.
• Air monitoring will begin at pre-purge. If a low air
condition is present power will not be supplied to the FSM. The blower(s) will remain on.
OPERATION SEQUENCE, 2 STAGE OPTION L400 through L2300
Note: Refer to the wiring diagram included with the unit for further control system info.
POWER ON:
Demand for Heat:
1. The operator switch closes, energizing pump delay timer TD4 and the w ater pump(s).
2. Water flow through the unit closes the water flow switch contacts energizing blower delay timer TD3.
3. The system checks all primary limit(s) and other inter-locks before starting pre-purge. The unit will not start if any switch is open.
Prepurge:
1. Blower delay timer TD3 energizes the low speed windings of the blower(s).
2. Once sufficient air pressure in the combustion chamber is sensed the pressure switch closes allowing the blower delay timer TD1 to start a 7 second pre-purge.
Page 26
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 26
Ignition T rial:
1. Blower delay timer TD1 times out and the flame sense module, FSM, is energized.
2. The FSM starts the 10-second ignition trial, energizing relay R7, the pilot solenoid valve and the spark generator.
3. The pilot valve and spark generator are energized for the 10-second ignition trial. When the pilot flame is sensed, the FSM sends 24VAC to its MV terminal energizing the safety and low fire-side of the main solenoid valves and relay R8, de-energizing R7 and the spark generator.
4. If the pilot flame isn’t sensed, the FSM de-energizes the PV terminal and waits 5 minutes before initiating the second ignition trial. The blower(s), pump(s) and optional power venter will remain on during this time.
5. On CSD-1 equipped units the blower(s) and optional power venter will shut down and the boiler/water heater will lock if the second ignition trial fails. The unit must then be manually reset by depressing the reset button on the left jacket panel.
6. On non-CSD-1 equipped units the FSM will wait 10 minutes after the second unsuccessful ignition attempt then begin the ignition process described in step 3 above. The FSM will continue to cycle the unit through steps 3, 4 and 6 until the unit lights or the demand for heat is removed.
Demand Satisfied:
1. When the demand for heat is satisfied the operator switch will open, de-energizing relays R2, R2R, R8, R9, TD1, TD3, TD4, the FSM and the pilot, main and safety solenoid valves. The pilot and main flames are extinguished.
2. The blower delay timer TD3 star ts the 80 second post-purge timing. The blower(s) shut(s) off when TD3 times out.
3. The pump delay timer TD4 starts the post-purge timing. The pump(s) remain on for 0.1 to 10 minutes then shut(s) off when TD4 times out.
High Limit, Low Water Flow, Low Gas Pressure, High Gas Pressure, Power Venter Interlock Faults
1. Electrical power to the gas valves, blower(s) and power venter will be interrupted if any safety is tripped.
2. The manual reset high limit can be reset by depressing the rubber plug in the front top jacket panel.
Low Air (Blocked Flue/Air Inlet)
• The pressure switches will monitor blower airflow.
• Air monitoring will begin at pre-purge. If a low air
condition is present, power will not be supplied to the FSM. The blower(s) will remain on.
Main Burner
Once the pilot is proven, the FSM sends 24VAC to its MV terminal energizing the safety and low-fire side of the main solenoid valves.
Normal Operation
• Staging is controlled by the return water aquastat. Relays R2 and R2R are energized by the return water aquastat when more heat input is required. The hi-speed windings of the blower(s) are energized.
• Relay R9 is energized when the hi-fire pressure switch senses adequate air pressure to sustain hi-fire combustion. R9 energizes the hi-fire side of the pilot and main solenoid valves.
• Stage 1 will operate first and last.
NOTE: For a change from stage 1 to 2, a 7 second LCD time delay is provided in the pressure switch switching circuit (PD6). The time delay provides a hold state that allows the blower to reach full speed and close the high fire pressure switch before it is energized to confirm proper air flow.
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
POUR VO TRE SÉCURITÉ LISEZ AVANT DE METTRE EN MARCHE
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light the pilot by hand.
Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
Page 27
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 27
DANGER: Propane gas may not always be detected by smell. Propane gas is heavier than air and can collect in low areas.
Propane gas can ignite or explode if an ignition source is present and result in death, serious injury and property damage!
FOR YOUR SAFETY
•Have only qualified licensed professionals install,
service and maintain this appliance and your gas system in accordance with all applicable codes.
•Install a nationally listed combustible gas
detector(s) in your home.
•If you suspect a leak:
1. Have everyone leave the building immediately.
2. Do not attempt to light any appliance.
3. Do not touch any electrical or electronic switches in the building.
4. Do not use any phone in the building.
5. Call your gas supplier from a phone outside of the building.
6. If you cannot reach your gas supplier call the fire department.
2. Set the operating control or thermostat to off or its lowest setting.
3. Turn off all electric power to the appliance.
4. Close the main manual gas shut-off valve, Figure 16.
5. Wait five (5) minutes to clear out any gas.
6. Remove the upper front jacket panel.
7. Turn the knob on the pilot valve to off, Figure 18.
8. Turn the knob on the main gas valve to off, 225 through 400 models, Figure 18. On 600 through 2300 models close the manual shutoff valve located in the control compartment, Figure 19.
9. Locate pilot and manifold pressure taps in the upper compartment. Remove the 1/8" screw plugs, see Figure 19.
Figure 18 - Pilot Valve (All Models)
Main Valve (225 - 400 Models)
AVANT DE FAIRE FONCTIONNER, reniflez tout autour de l’appareil pour déceler une odeur de gaz. Reniflez près du plancher, car certains gaz sont plus lourds que l’air et peuvent s’accumuler au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suives les instructions du fournisseur.
• Si vous ne pouvez rejoindre le four nisseur, appelez le service de incendies.
C. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
N’utilisez pas cet appareil s’il a été plongé dans l’eau, même partiellement. Faites inspecter l’appareil par un tecnicien qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
10. Connect a 20 in,
508 mm W.C
. manometer to each
valve, see Figure 19.
11. Turn the knob on the pilot valve to on, Figure 18.
12. Turn the knob on the main gas valve to on, 225 through 400 models, Figure 18. On 600 through 2300 models open the manual shutoff valve located in the control compartment, Figure 19.
13. Make sure that the gas supply piping has been purged of air and that all gas joints up to the gas valve have been thoroughly checked for leaks.
14. Turn on all electric power to the boiler.
Figure 19 - Manual Valve & Manifold Pressure Tap
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above. If, at any time, the appliance will not operate properly, follow the instructions “TO TURN OFF GAS TO APPLIANCE” and call your service technician or gas supplier.
Page 28
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 28
15. Set the operating control or thermostat to the desired setting.
16. The pilot should automatically light. Do
not try to
light the pilot by hand!
17. The burners should light with proper boiler/water heater operation.
18. The pilot and manifold pressures should match those listed in Table 19. To adjust the manifold gas pressure see the “GAS PRESSURE ADJUSTMENT” instructions in the “CHECKING AND ADJUSTMENT” section.
Provide gas supply pressure at inlet to boiler gas train as follows:
LP Nat Minimum (in WC) 11 6 Maximum (in WC) 14 14
Measure pressure when the boiler is firing at full rate. Low gas pressure could indicate undersized gas line or insufficient gas supply.
Static and operating gas pressure required at the gas valve inlet is between 6" W.C. and 14" W.C. for natural gas and 11" W.C. and 14" W.C. for propane. If the gas pressure is above this limit, a lock-up style regulator suitable for dead end service such as an Equimeter or Fisher must be installed to prevent increase (creep) of gas pressure when the units are not operating. This pressure regulator (supplied by others) may be installed at the service entrance to each unit or a “master” regulator sized to handle multiple units may be utilized. Consult local gas utility or regulator manufacturer for recommendations to meet specific job site requirements.
Table 19 - Pilot & Manifold Pressures
LCD-225, 300 & LCD-400 to 1200
1480 to 2300
Natural Gas
inches W.C.
Low Fire* 1.3 ± 0.2 High Fire 2.5 ± 0.2
inches W.C.
Low Fire* 3.6 +/- 0.2 High Fire 8.0 +/- 0.2
*Optional
mm W.C .
33 ± 5 64 ± 5
LP Gas
mm W.C .
91 ± 5
204 ± 5
inches W.C.
1.6 ± 0.2
2.5 ± 0.2
inches W.C.
4.0 ± 0.2
8.0 ± 0.2
mm W.C .
41 ± 5 64 ± 5
mm W.C .
102 ± 5 204 ± 5
Instructions De Mise En Marche
1. ARRÊTEZ! Lisez les instructions de sécur ité sur la portion supérieure de cette étiquette.
2. Réglez le thermostat à la température la plus basse.
3. Coupez l’alimentation électrique de l’appareil.
4. Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement.
5. Fermer la vanne manuelle d’arrêt d’alimintation de gaz.
6. Attendre cinq (5) minutes pour laisser échapper tout le gaz. Reniflez tout autour de l’appareil, y compris près du plancher, pour déceler une odeur de gaz. Si vous sentez une odeur de gaz, ARRÊTEZ! Passez à l’étape B des instructions de sécurité sur la portion supérieure de cette étiquette. S’il n’y a pas d’odeur de gaz, passez à l’étape suivante.
7. Ouver la vanne manuelle d’arrêt d’alimintation de gaz.
8. Mettez l’appareil sous tension.
9. Réglez le thermostat à la température désirée.
10. Si l’appareil ne se met pas en marche, suivez les instructions intitulées couper l’admission de gaz de l’appareil et appelez un technicien qualifié ou le fournisseur de gaz.
To Turn Off Gas To Appliance
1. Set the operating control or thermostat to its lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Close the manual main valves.
COUPER L’ADMISSION DE GAZ DE L’APAREIL
1. Réglez le thermostat à la température la plus basse.
2. Coupez l’alimentation électrique de l’appareil s’il faut procéder à l’entretien.
3. Fermer la vanne manuelle d’arrêt d’alimintation de gaz.
CHECKING & ADJUSTMENT
1. With the burners in operation, close the manual shutoff valve in the gas supply line. As soon as the main burner flames go out, open the manual shutoff valve . A normal ignition sequence should take place. If the burners fail to light, the gas valves will close and the system will go into a 5-minute lock out period. The flame sense module will then make a second ignition attempt. If the unit w on’t light ensure that the gas piping is fully purged of air. Inspect the ignition system and ensure that it is operating properly.
2. To test the ignition safety shutoff device, close the manual shutoff valve in the gas supply line. Within 5 seconds of main burner flame extinction, the main gas valve solenoid should close with an audible noise. After 10 seconds the module should lockout and the trial for ignition end. After 5 minutes a second trial for ignition should occur. Open the manual shutoff valve in the gas supply line and reset the ignition control system. A normal ignition sequence should take place.
3. With the burners in operation, interrupt the power to the control circuit by turning down the operator or thermostat. The boiler/water heater should shut down. Reset the operating control or thermostat. A normal ignition sequence should follow.
Page 29
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 29
Input Rate, Natural Gas
Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 5000 ft,
1524 m
. At elevations above 5000 ft,
1524 m
, input ratings should be reduced by 4% for each additional 1000 ft,
305 m
.
Check the input rate as follows:
1. Turn off all other gas appliances that use the
same gas meter as the boiler/water heater.
2. Call your gas supplier and ask for the heating
value of the gas.
3. Connect a flue gas analyzer to the vent pipe.
4. Start the boiler/water heater and let it run for 15
minutes.
5. Using the gas meter and a stopwatch, clock the
time that it takes to burn 10 cubic feet of gas and divide this time by 10.
6. Inser t the heating value and the time, in seconds,
into the formula below.
7. Input = (heating value, Btu/hr)(3600)/(time, seconds)
8. If the computed rate deviates by more than 5% from
the rated input value of the unit adjust the manifold pressure accordingly. DO NOT adjust the manifold pressure by more than 5%. If a proper rate cannot be maintained without adjusting the manifold pressure beyond the 5% limit, the main burner orifices must be replaced. If the input rate is too low , go to the next lager size of main burner orifices. If the input rate is too high, go to the next smaller size .
9. At full input the CO2 should be between 7.5% and
8.5% with a CO reading of less than 50 ppm.
CAUTION: Never increase the input of the boiler/ water heater above that for which it is rated. Doing so can cause premature failure of the unit!
Pilot Adjustment
The pilot burner is actually an isolated main burner that’s controlled by a separate pilot valve. Pilot pressure settings are as shown in Table 19. These pressures are measured at the pilot pressure valve, see Figure 19. Tables 12 and 13 above list the firing mode that is associated with each stage.
To view the pilot without main burner operation, take the following steps:
For L225-L400:
1. Remove the upper front jacket panel.
2. Tur n off main burner gas flow by turning the main
burner gas valve knob to the off position, Figure 18.
3. Observe the pilot flame through one of the
observation ports located at the left and right ends of the unit.
For L600-L2300:
1. Remove the upper front jacket panel.
2. T urn off main burner gas flow by turning the manual gas valve(s) in the control compartment to the off position, see Figure 19.
3. Observe the pilot flame through one of the observation ports located at the left and right ends of the unit.
Pilot pressures will be set at the factory. However, if it is necessary to adjust the pilot pressure to match those in Table 19, take the following steps:
1. Remove the upper front jacket panel.
2. Remove the 1/8" plug from the pilot pressure test port and connect a 20 in,
508 mm
W .C . manometer
to it, see Figure 18.
3. Remove the gas pressure regulator cap from the pilot valve. See Figure 18 for the location of the regulator and cap.
4. Use a 3/32 hex wrench to turn the pressure regulator adjustment screw clockwise to increase the pilot pressure and counterclockwise to decrease it.
5. Replace the pressure regulator adjustment screw cap.
Gas Pressure Adjustment
CAUTION: The maximum inlet gas pressure listed on the rating plate must not be exceeded or damage to the boiler/water heater may occur voiding the warranty!
The minimum supply pressure listed on the rating plate is for input adjustment.
NATURAL GAS: Optimum results are obtained when the boiler/water heater is operated with the manifold pressure(s) set per Table 19. The manifold pressure should not vary outside these ranges. Each gas valve pressure regulator has been preset at the factory. If adjustment is necessary the following steps must be followed:
1. Remove the 1/8" plug from the manifold pressure tap valve. Connect 20 in,
508 mm
WC mano-meters
to it, see Figure 19.
2. Remove the regulator adjustment screw cap from the main gas valve .
3. Rotate the regulator adjustment screw clockwise to increase the manifold pressure, counter clock-wise to decrease it.
4. Replace the regulator adjustment screw cap and manual shut off valve pressure tap plug.
CAUTION: Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur!
Page 30
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 30
PROPANE GAS: Optimum results are obtained when the boiler/water heater is operated with the manifold pressure(s) set per Table 19. If the manifold pressure is off by more than 5% adjust it according to steps 1 through 4 above.
Airflow Adjustment
1. Remove the upper front jacket panel.
2. Connect both sides of a manometer to the pressure switch tee, Figure 18, going to one of the pressure switches.
3. With the unit operating at high fire the differential pressure should be between 0.6 and 0.8 in,
20 mm
W.C. Do not change air pressure in lower
15 and
stages.
4. To fine tune the air settings once the upper front jacket panel is installed, remove the plastic plug(s) on the upper front jacket panel. Use a Phillips screwdriver to rotate the screw(s) to obtain the CO and CO readings in the INPUT RATE section above.
CONTROL DESCRIPTION
Boiler Thermostat
If a thermostat is to be used to control the boiler always follow the instructions included with the thermostat.
Proper location of the thermostat will ensure efficient trouble-free operation of the boiler. Mount the thermostat to an inside wall at a height approximately five feet above the floor. Avoid placing the thermostat in areas that will not provide an accurate measurement of the room temperature. Locating the ther mostat behind a door, in an alcove, close to a source of thermal radiation or in a drafty area will cause poor or sporadic heating.
For a thermostat that employs an adjustable heat anticipator, adjust the anticipator to match the current measured in the thermostat circuit. An increased anticipator setting may be necessary if the unit cycles frequently. If the room temperature over-shoots the thermostat setting, reduce the anticipator setting.
Operating Control
The operating control on the water heater is set to its lowest setting when the water heater leaves the factory. The preferred control setting for potable hot water is 130˚F, lowest setting that will satisfy the consumer’s needs.
54˚C
. The operating control should be set to the
WARNING: Setting the thermostat or operation control too high can result in scalding resulting in severe personal injury!
High Limit (Aquastat)
The high limit is located in the top control area of the boiler/water heater. A remote capillary bulb is run to a well on the outlet side of the supply header. The high limit can be reset by depressing the black rubber plug in the front top jacket panel.
The water heater high limit should be set a minimum of 20˚F,
11˚C
higher than the operating control. Refer to the HOT WATER SUPPLY section for the proper supply water temperature.
Flow Switch
A flow switch is provided in the water outlet piping to prevent the boiler/water heater from firing without adequate water flow through the heat exchanger.
Low Water Cutoff
If the boiler is to be installed above radiation or if
2
required by other codes or regulations, install a low water cutoff in appropriate piping. Wire the switch and any external controls in series to the “Interlock” contacts in the control box, see the wiring diagrams included with the unit for details. Ensure that the low water cutoff device(s) will function properly. Test in accordance with the manufacturer’s instructions included with the device(s).
Flame Sense Module
The flame sense module is located in the control box. It is an intermittent pilot control device that controls the pilot gas flow, spark energy to ignite the pilot gas and the main valve(s) once pilot ignition has been proven.
Two flame failure alarm terminals are provided on the flame sense module. For CSD-1 these terminals are utilized to shut the unit down in case of flame failure. The two terminals are connected to a lockout control module located in the control box. This lockout control module contains a magnetic latch relay that requires manual reset when de-energized. To reset after flame failure, push and release the momentary contact switch located on the left jacket panel.
Relay Board
The relay board is located in the control panel. It provides sequencing of the gas valves and blower(s) based on the staging controller's input. It also provides the following time delays for proper unit operation:
• A 7 second prepurge when stage 1 is energized.
• A 7 second pressure switch sequencing delay when
the blowers switch from low fire to high fire. The delay enables the blower to come up to speed before the high pressure side of the pressure switch confirms proper air flow.
These time delays are set within the separate time delay board connected to the relay board.
Page 31
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 31
Optional Gas Pressure Switches
Optional low and/or high-pressure gas pressure switches will shut down the 24 VAC circuit if excessively high or low gas pressure exists in the gas train or supply piping.
MAINTENANCE
WARNING: Disconnect electrical power and close the manual gas shut off valve before performing maintenance or severe personal injury may result!
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, exposure to hazardous materials or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier who must read and follow the supplied instructions before installing, servicing or removing this boiler. This boiler contains crystalline silica materials that have been identified as carcinogenic or possibly carcinogenic to humans when inhaled.
AVERTISSEMNET: Une installation, un réglage, une modification, une réparation ou un entretien non comforme aux normes peut entraîner des dommages matériels, des blessures, exposition à des matières dangereuses ou la mort. L’installation et l’entretien doivent être effectués par un installateur ou un service d’entretien qualifié ou le fournisseur de gaz qui doivent avoir lu les instructions fournies avant de faire linstallation, lentretien ou lenlèvement de la chaudière et les respecter, Cette chaudière contient des matériaux qui ont été identifiés comme étant cancérogènes ou pouvant l’ être.
CAUTION: Servicing, inspection and adjustment must be done by a trained technician in accordance with all applicable local and national codes. Improper servicing or adjustment can damage the boiler/water heater voiding the warranty!
WARNING: The ceramic combustion chamber contains crystalline silica. Wear a tightly fitted dust mask when removing the burners or heat exchanger to prevent inhalation of airborne fibers. Crystalline silica fibers have been identified as carcinogenic, or possibly carcinogenic when inhaled.
The boiler/water heater should be cleaned and inspected once a year, before each heating season. Make sure that the burner and ignition components are free from dust, soot, dirt, corrosion or other deposits that would impair the boiler/water heater ‘s performance.
Burner Inspection And Removal - Figure 20
1. Close the manual shutoff valves in the gas supply
lines and turn off electrical power to the boiler/water heater.
2. Remove the front jacket panels.
3. Disconnect the manifold gas piping at the ground
joint union(s). Also disconnect the pressure sensing lines, pilot tubing and ignition and sensing leads.
4. Remove the manifold(s).
5. Remove the burner(s) from the lower front combus-
tion chamber panel.
6. Inspect the burners for damage or signs of
deterioration. Use a brush or compressed air to remove any debris from the burner ports.
7. DO NOT install a damaged or badly corroded
burner replace it.
8. Install the burner(s) making sure that the burner
gasket is not torn or deteriorated. If it is replace it.
9. Reassemble the unit following the removal steps in
reverse order.
Heat Exchanger Inspection - Figure 20
1. Close the manual shutoff valve in the gas supply
line and turn off electrical power to the boiler/water heater.
2. Remove the jacket front panels.
3. Disconnect the gas piping at the ground joint
union(s). Also disconnect the pressure sensing lines, pilot tubing and ignition and sensing leads.
4. Remove the 1/4 inch nuts and washers holding the
upper combustion chamber front panel in place and carefully remove it.
5. Inspect the inside and outside of the heat exchanger
for signs of damage, sooting or corrosion.
6. The outside surfaces of the copper tubes should be
free of any soot deposits. A slight black smudge is normal with some types of gases. Black soot indicates poor combustion. Green deposits indicate condensation due to low return water temperatures. In either case the heat exchanger must be cleaned thoroughly and the problem resolved before the boiler/water heater is returned to service
7. If there are no signs of damage, sooting or corrosion
reassemble the unit following the previous steps in reverse order.
8. A badly corroded or damaged heat exchanger must
be replaced, see the HEAT EXCHANGER REMOVAL section below.
Page 32
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 32
Heat Exchanger Removal, Cleaning & Replacement ­See Figure 20
1. Close the shut off valves in the inlet and outlet piping. On heating systems close the system fill valve and relieve the system pressure from the boiler by carefully lifting the relief valve or opening the drain valve.
2. Drain the boiler/water heater and disconnect it from the system piping.
3. Remove the inlet/outlet and return headers.
4. Remove the jacket front panels.
5. Loosen, 4 turns, but dont remove the 6 screws, (3 on each side) holding the heat exchanger upper rails in place, Figure 21.
6. Disconnect the gas piping at the ground joint unions. Also disconnect the pressure sensing lines, pilot tubing and ignition and sensing leads.
7. Remove the upper partition panel, 1050 through 2300 models.
8. Remove the 1/4 inch nuts and washers holding the upper combustion chamber front panel in place and carefully remove it.
9. Carefully slide the heat exchanger out of the unit.
10. Remove the “V” baffle straps and “V” baffles.
11. Thoroughly inspect the heat exchanger for signs of damage. If there is no damage, clean the heat exchanger with water from a high-pressure hose. Use a soft bristle brush if necessary.
CAUTION: Never clean the heat exchanger while it’s in the boiler/water heater or the combustion chamber will be destroyed!
12. Sagging or distor ted heat exchanger tubes are an indication of low water flow through the system. A leaking or otherwise damaged heat exchanger must be replaced and the condition that caused the damage resolved before the boiler/water heater is returned to service.
13. If the heat exchanger isn’t damaged rewire the heat exchanger baffles in place and slide the heat exchanger back into the unit.
14 Reinstall all of the other components in the reverse
order of their removal.
Figure 20-Burner and Heat Exchanger Servicing
Page 33
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 33
Vent System
Thoroughly inspect the vent system for any signs of blockage, corrosion or leakage. Immediately replace any unsound vent system piping.
Figure 21- Heat Exchanger Upper Rail
Controls
Use the “BOILER/WATER HEATER OPERATION” and “CHECKING AND ADJUSTMENT” sections of this manual for reference.
1. Check the thermostat or operating controls for proper operation.
2. A float type low water cutoff device must be flushed out per the manufacturers’ instructions. The probe on a probe low water cut off must be cleaned and inspected per the manufacturers’ instructions. Ensure that the low water cutoffs operate properly. If not, replace them.
3. The flow switch contacts must be open when water flow is not present.
4. The relief valve should not weep or discharge water at normal system pressure. If it does contact a qualified service technician to have it inspected. NEVER try to clean or repair the relief valve! If the valve fails to operate properly, have it replaced!
5. The aquastat high limit controls the maximum water temperature in the boiler. It should be set at least 20°F,
11°C
above the operater setpoint. If the water temperature reaches the set temperature before the demand for heat has been met, the aquastat high limit should shut the boiler off. The water temperature should never exceed the maximum set point of 240°F,
116°C
. The aquastat high limit cannot be repaired. If it fails to function properly replace it.
6. Visually check the pilot and main burner flames to ensure proper operation, see Figure 22.
WARNING: A yellow, floating flame indicates a lack of combustion air. A lifting flame indicates too much combustion air. Do not operate the boiler/water heater until the problem is solved or severe personal injury or death may occur!
Figure 22 - Pilot & Main Burner Flame
Page 34
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 34
TROUBLESHOOTING
PROBLEM POSSIBLE CAUSES REMEDIES
No Power To Control Circuit Power not connected Wire unit to line voltage
External circuit breaker open Reset breaker Transformer circuit breaker open Reset breaker
No Action On Call For Heat Primary limit or other •Reset limit or control or resolve
control/interlock open problem as applicable
•If not resolved, check wiring and condition of limit
Low water cutoff open •Check circulating pump
•Check pump contact in control box
•Check LWCO wiring and condition
No Power to Pump Pump contact not wired Wire pump contact in control box
Pump malfunctioning Replace pump Defective pump timer TD4 Replace pump timer TD4
No Power to Optional Power Venter Power venter not wired to Wire power venter as shown in
external power connection diagram Power venter fault Replace power venter
Power Venter On, No Action Power venter interlock not wired Wire power venter interlock as From Unit shown in connection diagram
No Power To Blower(s) Blower(s) not plugged in Plug in blower(s)
Defective blower timer TD3 Replace Blower Timer TD3 Blower(s) malfunctioning Replace blower(s)
Unit Does Not Spark Incorrect spark gap or shorted Properly adjust igniter gap or
igniter lead correct short Bad ground on flame sense Check ground connections,
module adjust as necessary Defective flame sense module Replace flame sense module Low air (blocked flue/inlet) • If condition exists, check inlet,
condition flue & chimney for blockage
• Check combustion air/ventilation openings in space
•Check inlet air filter, clean/replace as necessary
Spark generator fault check spark generator wiring Defective air purge timer TD1 Replace Timer TD1
Unit Sparks But Will Not Fire Low gas pressure Check gas supply pressure during
ignition trial, adjust as necessary Pilot valve manual knob closed Open pilot valve manual knob Pilot valve not wired Connect pilot valve wires Low pilot pressure Check pilot pressure, adjust as
necessay Pilot valve malfunctioning Replace pilot valve
Page 35
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 35
TROUBLESHOOTING
PROBLEM POSSIBLE CAUSES REMEDIES
Pilot Lights But Main Burners Bad flame sense lead from igniter Check sense lead & ground ........
Will Not Fire to flame sense module connections, adjust as necessary
Defective flame sense module Replace flame sense module Manual valve(s) in air plenum Remove upper front jacket panel,
closed open manual valve(s) Main valve(s) not wired Wire main valve(s) Low manifold pressure Check manifold pressure during
ignition trial, adjust as necessary Main valve(s) malfunctioning Replace main valve(s)
Insufficient Heating Operating control set too low Increase control temperature
setting
Unit Consistently Shuts Down High limit set too low Increase high limit setting On High Limit
Bad Combustion Insufficient air •Check CO & CO2, adjust blower (High CO, Yellow Flames) inlet damper(s) to increase airflow
• Check for plenum air leakage
from lower front jacket panel
seams, repair as necessary Dirty inlet air filter Remove, inspect and clean inlet air
filter as necessary Too much air Check CO & CO2, adjust blower
inlet damper(s) to decrease airflow
Gas Flow Shuts Off During Low air (blocked flue/inlet) •If condition exists,check inlet, Operation (Blowers Remain On) condition flue, chimney for blockage
•Check combustion air/ventilation openings in space
•Check inlet air filter, clean/replace as necessary
• Check pressure switch for correct
setting
Page 36
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 36
Page 37
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 37
SERVICE AND REPLACEMENT PARTS LIST (MODELS 225-2300)
Ref # Name of Part
1 Jacket Lower Front Panel Assembly 70-2716 1 1
2 Jacket Upper Front Panel Assembly 70-2706 1 1
3 Left Jacket Panel 70-3111 11111111
4 Control Box Assembly Standard 70-3113 111111111111
Control Box Assembly Optional 2 Stage 70-3114 1111111111 Control Box Assembly Standard CSD-1 70-3115 111111111111
Control Box Assembly 2 Stage CSD-1 70-3116 1111111111 5 Control Box Cover 03-2153 111111111111 6 Right Jacket Panel 03-2158 1111
7 Combustion Air Inlet Assembly (Indoor) 70-2744 1 1
Rear Intake Option available on 70-2746 1 1
750-2300 models only 70-2748 1 1
8 Combustion Air Inlet Assembly (Outdoor) 70-2820 1 1
9 Jacket Rear Panel 03-1811 1 1
10 Combustion Air Inlet Cover 03-1881 1
11 Jacket T op Panel 03-1801 1 1
Part # 225 300 400 600 750 900 1050 1200 1480 1650 1970 2300
70-2717 1 70-2718 1 70-2719 1 70-2720 1 70-2721 1 70-2722 1 1 70-2723 1 70-2724 1 70-2725 1
70-2707 1 70-2708 1 70-2709 1 70-2710 1 70-2711 1 70-2712 1 1 70-2713 1 70-2714 1 70-2715 1
70-3112 1111
03-2159 1111 03-1825 1111
70-2749 1111
70-2821 1 1 70-2822 1 1 70-2823 1111
03-1812 1 03-1813 1 03-1814 1 03-1815 1 03-1816 1 03-1817 1 1 03-1818 1 03-1819 1 03-1820 1
03-1882 1 1 03-1883 11111
03-1802 1 03-1803 1 03-1804 1 03-1805 1 03-1806 1 03-1807 1 1 03-1808 1 03-1809 1 03-1810 1
Page 38
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 38
Ref # Name of Part
12 Base Panel Legs 03-1862 222222444444 13 Jacket Base Panel 03-1847 1 1
14 Combustion Chamber Base Panel 03-1974 1 1
15 Combustion Chamber Lower Front Panel 03-2170 1
16 Comb.Chamber Upper Front Panel 03-1939 1 1
17 Comb. Chamber Lower Left Side Panel 03-1936 111111111111
Comb.Chamber Lower Right Side Panel 03-1937 111111111111
18 Comb.Chamber Upper Left Side Panel 03-1934 111111111111
Comb. Chamber Upper Right Side Panel 03-1935 111111111111
19 Heat Exchanger Guide Rail 03-1938 444444444444 20 Combustion Chamber Rear Panel 03-1904 1
Part # 225 300 400 600 750 900 1050 1200 1480 1650 1970 2300
03-1848 1 03-1849 1 03-1850 1 03-1851 1 03-1852 1 03-1853 1 1 03-1854 1 03-1855 1 03-1856 1
03-1975 1 03-1976 1 03-1977 1 03-1978 1 03-1979 1 03-1980 1 1 03-1981 1 03-1982 1 03-1983 1
03-1962 1 03-1963 1 03-1964 1 03-1965 1 03-1966 1 03-1967 1 03-2171 1 03-1968 1 03-1969 1 03-2172 1 03-1971 1
03-1940 1 03-1941 1 03-1942 1 03-1943 1 03-1944 1 03-1945 1 03-1946 1 03-1947 1 03-1948 1
03-1905 1 03-1906 1 03-1907 1 03-1908 1 03-1909 1 03-1910 1 1 03-1911 1 03-1912 1 03-1913 1
Page 39
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 39
Ref # Name of Part
21 Combustion Chamber Top Panel 03-1884 1 1
22 Flue Box Wrapper Assembly 70-2798 1 1
23 Flue Outlet Assembly 70-3117 1
24 Lower Front Refractory Panel 05-0110 1
Lower Left Front Refractory Panel 05-0091 1 1
Lower Right Front Refractory Panel 05-0096 1 1
Lower Center Front Refractory Panel 05-0151 1
25 Upper Front Refractory Panel 05-0070 1 1
Upper Left Front Refractory Panel 05-0075 1
Upper Right Front Refractory Panel 05-0080 1
Upper Center Front Refractory Panel 05-0085 1
26 End Refractory Panel, Left & Right 05-0058 111111111111
Part # 225 300 400 600 750 900 1050 1200 1480 1650 1970 2300
03-1885 1 03-1886 1 03-1887 1 03-1888 1 03-1889 1 03-1890 1 1 03-1891 1 03-1892 1 03-1893 1
70-2799 1 70-2800 1 70-2801 1 70-2802 1 70-2803 1 70-2804 1 1 1 70-2805 1 1
70-2736 1 70-2737 1 70-2738 1 70-2739 1 70-2740 1 70-2741 1 70-2742 1 1 1 70-2743 1 1
05-0086 1 05-0087 1 05-0088 1 05-0089 1 05-0090 1
05-0111 1 05-0092 1 05-0093 1 05-0112 1 05-0095 1
05-0113 1 05-0097 1 05-0098 1 05-0114 1 05-0100 1
05-0071 1 05-0072 1 05-0073 1 05-0074 1
05-0076 1 1 05-0077 1 05-0078 1 05-0079 1
05-0081 1 1 05-0082 1 05-0083 1 05-0084 1
Page 40
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 40
Ref # Name of Part
27 Rear Refractory Panel 05-0059 1 1
Left & Right Rear Refractory Panel 05-0066 1
Center Rear Refractory Panel 05-0069 1
28 Manifold 10-0465 1 1
29 Main Orifice, Natural Gas 10-0087 2 3 7 9 11 13 15 17 19 25 27
Main Orifice, LP Gas 10-0088 2 3 7 9 11 13 15 17 19 25 27
Main Orifice, Natural Gas 10-0093 5
Main Orifice, LP Gas 10-0116 5
Pilot Orifice, Natural Gas 10-0089 1 1 111111111
Pilot Orifice, LP Gas 10-0090 1 1 111111111
Pilot Orifice, Natural Gas 10-0115 1
Pilot Orifice, LP Gas 10-0119 1
30 Main Burner Tube 10-0275 34681012141618202628
Pilot Burner Assembly (tubings and fittings) 70-2896 111111111111
31 Spark Ignitor 16-0327 111111111111
NS Heat Exchanger Assembly (Copper) 70-3001 1
(Cast Iron Headers) 70-3002 1
Heat Exchanger Assembly (Copper) 70-3025 1
(Bronze Headers) 70-3026 1
Part # 225 300 400 600 750 900 1050 1200 1480 1650 1970 2300
05-0060 1 05-0061 1 05-0062 1 05-0063 1 05-0064 1 05-0065 1 1
05-0067 1 05-0068 1
10-0466 1 10-0467 1 10-0468 1 10-0469 1 30-0746 1 30-0747 1 30-0748 1 30-0749 1 30-0750 1 30-0751 1
70-3003 1 70-3004 1 70-3005 1 70-3006 1 70-3007 1 70-3008 1 70-3009 1 70-3010 1 70-3011 1 70-3012 1
70-3027 1 70-3028 1 70-3029 1 70-3030 1 70-3031 1 70-3032 1 70-3033 1 70-3034 1 70-3035 1 70-3036 1
Page 41
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 41
Ref # Name of Part
NS Heat Exchanger Assembly (Cupronickel) 70-3013 1
(Cast Iron Headers) 70-3014 1
Heat Exchanger Assembly (Cupronickel) 70-3037 1
(Bronze Headers) 70-3038 1
32 Tube Bundle (Copper) 70-3049 1
Tube Bundle (Cupronickel) 70-3061 1
33 Heat Exchanger "V" Baffle 03-2011 7 7 36
34 V Baffle Hold-down 03-2021 222244444666
NS Heat Exchanger Support Channel 03-2022 1
Part # 225 300 400 600 750 900 1050 1200 1480 1650 1970 2300
70-3015 1 70-3016 1 70-3017 1 70-3018 1 70-3019 1 70-3020 1 70-3021 1 70-3022 1 70-3023 1 70-3024 1
70-3039 1 70-3040 1 70-3041 1 70-0342 1 70-0343 1 70-0344 1 70-0345 1 70-0346 1 70-0347 1 70-0348 1
70-3050 1 70-3051 1 70-3052 1 70-3053 1 70-3054 1 70-3055 1 70-3056 1 70-3057 1 70-3058 1 70-3059 1 70-3060 1
70-3062 1 70-3063 1 70-3064 1 70-3065 1 70-3066 1 70-3067 1 70-3068 1 70-3069 1 70-3070 1 70-3071 1 70-3072 1
03-2012 7 36 03-2013 7 03-2014 7 03-2015 7 03-2016 7 03-2017 7 9 03-2018 9 03-2019 9 03-2020 9
03-2023 1 03-2024 1
Page 42
LCD INSTALLATION AND OPERATION INSTRUCTIONSPage 42
Ref # Name of Part
35
Combustion Cham. Refr. Retainer (F/R Edge Baffle)
36 O Ring, Inlet/Outlet & Return Headers 06-0001 16 16 16 16 16 16 16 16 16 16 16 16 37 Stud, Inlet/Outlet & Return Headers 57-0223 666666666666 38 Nut, Inlet/Outlet & Return Headers 57-0492 666666666666 39 Return Header, Bronze
Return Header, Cast Iron
40 Inlet/Outlet Header, Bronze
Inlet/Outlet Header, Cast Iron
41 Blower, Fasco 70625413 12-0013 1 1 1 1
Blower, Fasco 70830370 12-0014 111222222
42 Combustion Air Damper Assembly 70-2818 1 1 1 1
43 Low Pressure Switch 14-0059 1111111111 43 High Pressure Switch 14-0061 111111111111 44 High Limit L4008E1305 (LB) 14-0112 111111111111
High Limit L4008E1313 (LW) 14-0105 111111111111
NS Operator L4008A1015 (LB) 14-0102 111111111111
Operator L6008A1242 (LW) 14-0106 111111111111
Operator L6008G1009 - 2 Stage 14-0107 1111111111
NS NG STD/FM Gas Train Assembly 73-0824 1
NS LP STD/FM Gas Train Assembly 73-0830 1
Part # 225 300 400 600 750 900 1050 1200 1480 1650 1970 2300
03-1972 111111111111
01-0011-1S 01-0004S 01-0018S
01-0009S 01-0002S 01-0022S 01-0010-1S 01-0003S 01-0019S 01-0008S 01-0001S 01-0023S
70-2819 111222222
73-0825 1 73-0826 1 73-0827 1 73-0828 1 73-0829 1 73-0776 1 73-0777 1 73-0778 1 73-0779 1 73-0780 1 73-0781 1
73-0831 1 73-0832 1 73-0833 1 73-0834 1 73-0835 1 73-0782 1 73-0783 1 73-0784 1 73-0785 1 73-0786 1 73-0787 1
111
11111
1111
111
11111
1111
111
11111
1111
111
11111
1111
Page 43
LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 43
Ref # Name of Part
45 Firing Valv e, 3/4" 11-0461 1 1 1
Firing Valve , 1" 11-0456 1 1 1 Firing Valve, 1 1/4" 11-0457 1 1 Firing Valve, 1 1/2" 11-0458 1 1 Firing Valve , 2" 11-0459 1 1
NS Manifold Pressure Valve 11-0031 111111111111
46 Main Gas Valve, VR8305 11-0087 1 1 1
Main Gas Valve, V8944B, 1" 11-0186 1 1 1 Main Gas Valve, V8944B, 1 1/4" 11-0187 1 1 Main Gas Valve, V8944B, 1 1/2" 11-0188 1 1 Main Gas Valve, V8944B, 2" 11-0174 1 1
47 Safety Valve, V48A, 1" 11-0151 1 1 1
Safety Valve, V48A, 1 1/4" 11-0152 1 1 Safety Valve, V48A, 1 1/2" 11-0153 1 1 Safety V alve , V48A, 2" 11-0154 1 1
48 Pilot Valve, VR8304M 11-0055 111111111111
Pilot Valve, VR8205Q 2 Stage 11-0086 1111111111 Manual Shut Off Valve, 1" 11-0465 1 1 1 Manual Shut Off Valve, 1 1/4" 11-0466 1 1 Manual Shut Off Valve, 1 1/2" 11-0467 1 1 Manual Shut Off Valve, 2" 11-0454 1 1
50
Flame Sensor UTC 1003-61A Ignition Module
51 Q652B1006, Spark Generator 16-0008 111111111111
NS Ignition Lead 16-0202 111111111111
52 Transformer, 75 VA 15-0008 111111111111 55 Relay, 9 Pin 15-0115 55555777777
Relay, 4 Pin 15-0116 22222222222
NS Manual Reset Board, CSD-1 16-0013 111111111111
Relief Valve 1" 50# (LB) 30-0379 111111111111 Relief Valve 3/4" 125# (LW) 30-0364 111111111111 Tridicator 0-100 PSI (LB) 13-0308 111111111111 Tridicator 0-230 PSI (LW) 13-0305 111111111111
NS On/Off Switch 48-0010 111111111111
Part # 225 300 400 600 750 900 1050 1200 1480 1650 1970 2300
16-0059 111111111111
Page 44
260 North Elm Street 1300 Midway Boulevard Westfield, MA 01085 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
Loading...