DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE
VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE
OF 160 PSI,
WARNING: If the information in this manual is not followed exactly, a fire
or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
WARNING: Failure to properly vent this unit can cause excessive amounts of carbon
monoxide resulting in severe personal injury or death!
1103 kPa
WATER.
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
260 North Elm Street7555 Tranmere Drive
Westfield, MA 01085
Phone: (413) 568-9571Phone: (905) 670-5888
Fax: (413) 568-9613Fax: (905) 670-5782
Mississauga, Ontario L5S 1L4 Canada
䡲
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 2
AVERTISSMENT. Assurez-vous de bien suivre les instructions données dans cette
notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter
tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides inflammables
à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans
le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les
intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service
d’entretien qualifié ou par le fournisseur de gaz.
CONTENTS
Before You Start .................................................page 2
This manual covers the application, installation,
operation and maintenance of a Series 8800
and 8900 finned copper heating boiler/water heater/pool
heater.
To obtain the safe, dependable, efficient operation and
long life for which this heating boiler/water heater was
designed, these instructions must be read, understood
and followed.
The Series 8800 and 8900 finned copper heating boiler/
water heaters have been design certified by CSA for use
with natural and propane gas under the latest revision of
ANSI-Z21.10.3/CSA 4.3, Gas Water Heaters, ANSIZ21.13/CSA 4.9, Gas-Fired Low Pressure Steam and Hot
Water Boilers and CAN1-3.1, Industrial and Commercial
Gas Fired Packaged Boilers. Each unit has been
constructed and hydrostatically tested for a maximum
working pressure of 160 psi,
Section IV of the A.S.M.E. Boiler and Pressure Vessel
Code.
All aspects of the boiler/water heater installation must
conform to the requirements of the authority having
jurisdiction, or, in the absence of such requirements, to
the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest
revision. Where required by the authority having
jurisdiction, the installation must conform to the Standard
for Controls and Safety Devices for Automatically Fired
Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the
requirements of CAN/CGA B149.1 or .2, Installation Code
for Gas Burning Appliances and Equipment.
If installed in the Commonwealth of Massachusetts, you
MUST FOLLOW the additional instructions contained in
RBI's instruction sheet MACODE-3. If you do not have a
copy, call your RBI distributor or contact the RBI Customer
Service Department.
The owner should maintain a record of all service work
performed with the date and a description of the work
done. Include the name of the service organization for
future reference.
1103 kPa
in accordance with
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 3
Direct all questions to your RBI distributor or contact the
RBI Customer Service Department, 260 North Elm Street,
Westfield, MA 01085 for U.S. or 7555 Tranmere Drive,
Mississauga ONT L5S 1L4 for Canada. Always include the
model and serial numbers from the rating plate of the boiler/
water heater in question.
RATINGS & CAPACITIES
Before undertaking the installation of the Series 8800
and 8900 boiler/water heater check the rating plate to
ensure that the unit has been sized properly for the job.
The “Net I=B=R Ratings” specify the equivalent amount
of direct cast iron radiation that the unit can supply under
normal conditions. Also ensure that the unit has been
set up for the type of gas available at the installation
site. Other important considerations are the availability
of an adequate electrical supply, fresh air for combustion
and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1.Locate the boiler/water heater in an area that
provides good access to the unit. Servicing may
require the removal of jacket panels.
minimum clearances between adjacent construction
and the boiler/water heater as listed in Table 1 or 1A.
NOTE: Service clearances are not mandatory, but
are recommended to ensure ease of service should
it be required.
Table 1 (8800)
Clearance to Service
Combustibles Clearance
in
To p24
Back24
Left Side24
Right Side24
Front48
Flue6
Table 1A (8900)
Clearance to Service
Combustibles Clearance
in
To p24
Back18
Left Side18
Right Side18
Front48
Flue6
mm
610
610
610
610
1220
152
mm
610
457
457
457
1220
152
Allow the
in
18
18
24
24
48
6
in
18
18
18
18
36
6
mm
457
457
610
610
1220
152
mm
457
457
457
457
914
152
2.An optimum site will be level, central to the piping
system, close to a chimney and have adequate fresh
air for combustion. Ensure that the boiler/water heater
is level from front to back and from side to side. Use
metal shims to level the boiler/water heater. Electrical
and electronic components must also be protected
from exposure to water during operation and
maintenance. DO NOT install this boiler/water heater
in a location that would subject any of the gas ignition
components to direct contact with water or excessive
moisture during operation or servicing.
3.Ensure that the floor is structurally sound and will
support the weight of the boiler/water heater.
NOTE: Never install a Series 8800 or 8900 boiler/
water heater on a concrete floor that contains wires,
cables, water pipes or hoses. This boiler/water
heater is designed for noncombustible floors only!
Never install this boiler/water heater on combustible
materials or carpeting even if a non-combustible
foundation material is placed over them!
4. Locate the boiler/water heater in an area that will
prevent water damage to adjacent construction
should a leak occur or during routine maintenance.
If such a location doesn’t exist, a suitable drain pan
that’s adequately drained must be installed under
the unit. The
combustion air to the unit.
5.
DO NOT place this boiler/water heater in a location
that would restrict the introduction of combustion air
into the unit or subject it to a negative pressure, see
“GENERAL VENTING GUIDELINES”.
6. NEVER place this boiler/water heater in a location
that would subject it to temperatures at or near
freezing.
WARNING: Never store combustible materials,
gasoline or any product containing flammable vapors
or liquids in the vicinity of the boiler/water heater.
Failure to comply with this warning can result in an
explosion or fire causing extensive property damage,
severe personal injury or death!
pan must not restrict the flow of
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 4
COMBUSTION AIR & VENTILATION
WARNING: This boiler/water heater must be
supplied with combustion air in accordance with
Section 5.3, Air for Combustion & Ventilation, of
the latest revision of the National Fuel Gas
Code, ANSI Z223.1/ NFPA 54 and all applicable
local building codes. Canadian installations
must comply with CAN/ CGA B149.1 or .2
Installation Code for Gas Burning Appliances
and Equipment, or applicable provisions of the
local building codes. Failure to provide adequate
combustion air for this boiler/water heater can
result in excessive levels of carbon monoxide
which can result in severe personal injury or
death!
To operate properly and safely this boiler/water heater
requires a continuous supply of air for combustion.
NEVER store objects on or around the boiler/water heater!
CAUTION: Combustion air contaminated with
fluorocarbons or other halogenated compounds
such as cleaning solvents and refrigerants will
result in the formation of acids in the combustion
chamber. These acids will cause premature failure
of the boiler/water heater voiding the warranty!
CAUTION: If the boiler/water heater is operated while
the building is under construction it MUST be
protected from wood, concrete, sheet rock and other
types of dust. Failure to properly protect the unit
from construction dust will damage the unit voiding
the warranty!
All Air From Inside The Building
If the boiler/water heater is to be located in a confined
space minimum clearances listed in Table 1 or 1A must
be maintained between the boiler/water heater and any
combustible construction. When installed in a confined
space, Figures 1, 2, 3, 4 and 5, two permanent openings
communicating with an additional room(s) are required.
The combined volume of these spaces must have
sufficient volume to meet the criteria for an unconfined
space. The total air requirements of all gas utilization
equipment, fireplaces, wood stoves or any type of
exhaust fan must be considered when making this
determination. Each opening must have a minimum free
area of 1 in2/1000 Btu/hr,
total input rating of
confined area. Each opening must be no less than
100 in2,
be within 12 in,
76 mm
opening must be within 12 in,
than 3 in,
All Air From Outside The Building
When installed in a confined space two permanent
openings communicating directly with, or by ducts
to, the outdoors or spaces that freely communicate with
the outdoors must be present. The upper opening must
be within 12 in,
76 mm
opening must be within 12 in,
than 3 in,
Where directly communicating with the outdoors
or communicating with the outdoors through vertical
ducts, each opening shall have a minimum free area
of 1 in2/4000 Btu/hr,
rating of all of the equipment in the enclosure.
64,516 mm
from, the top of the enclosure. The bottom
76 mm
from, the top of the enclosure. The bottom
76 mm
ALL
305 mm
from, the bottom of the enclosure.
305 mm
from, the bottom of the enclosure.
2200 mm2/kW
gas utilization equipment in the
2
in size. The upper opening must
of, but not less than 3 in,
305 mm
of, but not less than 3 in,
305 mm
550 mm2/kW
based on the
of, but not less
of, but not less
of the total input
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 5
Where communicating with the outdoors through
horizontal ducts, each opening shall have a minimum
free area of 1 in2/2000 Btu/hr,
1100 mm2/kW
of the total
input rating of all of the equipment in the enclosure.
When ducts are used, they must have the same crosssectional area as the free area of the opening to which
they connect.
Canadian installations must comply with CSA B149.1
when
air supply
outdoors for
assisted, or power draft-assisted
be a permanent
is provided by natural air flow from the
natural draft
air supply
, partial fan-assisted, fan-
burners
, there shall
opening(s) having a cross-
sectional area of not less than 1 in2 per 7,000 Btuh
(310 mm2 per kW)
plus 1 in2 per 14,000 Btuh
up to and including1 million Btuh,
(155 mm2 per kW)
in excess
of1 million Btuh.
When calculating the free area necessary to meet
the make-up air requirements of the enclosure,
consideration must be given to the blockage effects
of louvers, grills and screens. Screens must have
a minimum mesh size of 1/4 in,
6.4 mm
. If the free
area through a louver or grill is not known, ducts
should be sized per Table 2.
Figure 1 - Vertical Venting Using A Metal Chimney And Inside Air (8900/8800 Series)
2 FT .6 m
10 FT 3.4 m
3 FT 1 m
3 FT 1 m
5 FT 1.52 m
RIOM-40
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 6
Figure 2 - Vertical Venting Using A Masonary Chimney And Inside Air (8900/8800 Series)
10 FT 3.1 m
3 FT 1 m
3 FT 1 m
5 FT 1.52 m
Figure 3 - Dual Flue Outlets And Inside Air (8900/8800 Series)
2 FT .6 m
10 FT 3.4 m
3 FT 1 m
10 FT 3.4 m
5 FT 1.5 m
RIOM-41
RIOM-42
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 7
Figure 4 - Common Vents and Inside Air (8900/8800 Series)
10FT 3.1 m
3FT 1m
5FT 1.52m
3FT 1m
Figure 4A - Common Vents and Inside Air (8800/8900 Series) Dual Flue
10 FT
3.1 m
3 FT
1 m
RIOM-43
3 FT
1 m
5 FT
1.52 m
Figure 5 - Horizontal Venting And Inside Air (8900/8800 Series)
BUILDING OVERHANG
4FT 1.2 M MAX.
PITCH PIPE DOWN TOWARDS TERMINAL
CAP 1/4 IN. PER FOOT 20 MM/M OF RUN TO
3FT .9 m
1.5 FT 0.5m MINIMUM DIST ANCE FROM
EXHAUST TO MAXIMUM SNOW LINE.
ALLOW FOR CONDENSATE DRAINAGE
3FT 1 m
5FT 1.52 m
RIOM-44
RIOM-45
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 8
CHIMNEY & VENT PIPE
CONNECTIONS
WARNING: The vent installation must be in
accordance with Part 7, Venting of Equipment, of
the National Fuel Gas Code, ANSI Z223.1/NFPA
54-latest revision or applicable provisions of the
local building codes. Canadian installations must
comply with CAN/CGA B149.1 or .2 Installation
Code. Improper venting can result in excessive
levels of carbon monoxide which can result in
severe personal injury or death!
Chimney Inspection & Sizing
A thorough inspection of the masonry chimney must be
performed to ensure that the chimney is clean, properly
constructed, lined and sized. Exterior masonry chimneys
should not be used unless properly lined to prevent
condensation and draft problems. Table 3A and 3B lists
the equivalent breeching and flue sizes required for the
boiler/water heater.
When more than one appliance is connected to the
same chimney flue, the flue must be large enough to
safely vent the combined output of all the appliances.
WARNING: If an appliance using any type of a
mechanical draft system operating under
positive pressure is connected to a chimney
flue, never connect any other appliances to this
flue. Doing so can result in the accumulation of
carbon monoxide which can cause severe
personal injury or death!
Vent Connections
Always use a type B or single wall galvanized metal vent
pipe the same diameter as the draft diverter flue collar.
Use the shortest, straightest vent system possible for
the installation. If horizontal runs exceed 6 ft,
must be supported at 6 ft,
1.8 m
intervals with overhead
1.8 m
they
hangers. The vent system should be sloped up toward
the chimney at a minimum rate of 1/4 in/ft,
20 mm/m
and terminate flush with the inside of the chimney flue.
Fasten each connection with at least 3 corrosion
resistant sheet metal screws.
WARNING: Never modify or alter any part of the
boiler’s draft diverter. This includes the removal
or alteration of any baffles. Never install a vent
pipe of a diameter different than that of the
boiler draft hood flue collar. Failure to comply
with this warning can result in severe personal
injury or death.
Always provide a minimum clearance of 6 in,
152 mm
between type C vent pipe and any combustible
materials. Type B1 vent may be used, clearance
between it and any combustible material must be as
listed.
WARNING: Failure to maintain minimum
clearances between vent connectors and any
combustible material can result in a fire causing
extensive property damage, severe personal
injury or death!
To determine the appropriate power venter for the boiler/
water heater, see Table 4, Power Venter Sizes. Follow
the power venter manufacturer’s installation instructions.
Table 4 - Power Venter Sizes
8900Power VenterMax. Pipe Length
ModelSizeFT
420-530HS-2100
630HS-3100
735-1160HS-4100
1260-1900HS-5100
m
31
31
31
31
Models 2000-4000 - Consult Tjernlund
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 9
COMMON VENT SYSTEMS
If an existing boiler/water heater is removed from a
common venting system, the common venting system
may then be too large for the proper venting of the
remaining appliances connected to it. At the time of
removal of an existing boiler/water heater, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in
operation, while the other appliances remaining
connected to the common venting system are not in
operation.
Au moment du retrait d’une chaudière existante, les
mesures suivantes doivent être prises pour chaque
appareil toujours raccordé au système d’évacuation
commun et qui fonctionne alors que d’autres appareils
toujours raccordés au système d’évacuation ne fonctionnent pas: système d’évacuation
a) Seal any unused openings in the common venting
system.
Sceller toutes les ouvertures non utilisées du système d’évacuation.
b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no
blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d’évacu-ation
pour déterminer la grosser et l’inclinaison
horizontale qui conviennent et s’assurer que le
système est exempt d’obstruction, d’étranglement
de fruite, de corrosion et autres défaillances qui
pourraient présenter des risques.
c) Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common
venting system are located and other spaces of the
building. Turn on clothes dryers and any appliance
not connected to the common venting system. Turn
on any exhaust fans, such as range hoods and
bathroom exhaust, so they will operate at maximum
speed. Do not operate a summer exhaust fan for a
boiler installation. Close fireplace dampers.
Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l’espace où les appareils toujours
raccordés du système d’évacuation sont installés et
les autres espaces du bâtiment. Mettre en marche
les sécheuses, tous les appareils non raccordés au
système d’évacuation commun et tous les
ventilateurs d’extraction comme les hottes de
cuisinère et les ventilateurs des salles de bain.
S’assurer que ces ventilateurs fonctionnent à la
vitesse maximale. Ne pas faire fonctionner les
ventilateurs d’été. Fermer les registres des
cheminées.
d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so
appliance will operate continuously.
Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat de
façon que l’appareil fonctionne de façon continue.
e) Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the flame
of a match or candle, or smoke from a cigarette,
cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min
ensuite, déterminer si le coupe-tirage déborde à
l'ouverture de décharge. Utiliser la flamme d'une
allunette ou d'une chandelle ou la fumée d'une
cigarette, d'un cigare ou d'une pipe.
f)After it has been determined that each appliance
remaining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers
and any other gas-burning appliance to their
previous condition of use.
Une fois qu’il a été d éterminé, selon la métode
indiquée ci-dessus, que chaque appareil raccordé
au système d’évacuation est mis à l’air libre de façor
adéquate. Remettre les portes et les fenêtres, les
ventilateurs, les registres de cheminées et les
appareils au gaz à leur position originale.
g) Any improper operation of the common venting
system should be corrected so the installation
conforms with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54. When resizing any portion of the
common venting system, the common venting
system should be resized to approach the minimum
size as determined using the appropriate tables in
Part 11 in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and or CAN/CGA-B149 Installation
Codes.
Tout mauvais fonctionnement du systéme d'évacution commun devrait étré corrigé de façor que
l'installation soit conforme au National Fue Gas
Code, ANSI Z223.1/NFPA 54 et (ou) aux codes
d'installation CSA-B149. Si la grosseur d'une section
du système d'évacuation doit étré modifiée, le
système devrait étré modifié pour respecter les
valeurs minimales des tableaux pertinents de
l'appendice F du National Fuel Gas Code, ANSI
Z223.1/NFPA 54 et (ou) des codes d'installation
CSA-B149.
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 10
GENERAL PIPING REQUIREMENTS
CAUTION: Improper piping of this boiler/water heater
will void the manufacturer’s warranty and can cause
boiler failure resulting in flooding and extensive
property damage! Excessive water hardness causing
lime build-up in the copper heat exchanger tubes is
NOT
covered under the manufacturer’s warranty.
Excessive pitting and erosion of the internal surface
of the copper heat exchanger tubes is
under the manufacturer’s warranty if the result
of high water flow rates, see Table 6A and 6B. Return
water temperatures below 110°F, 43°C will result
in heat exchanger damage from excessive
condensation voiding the manufacturer’s warranty,
see Primary/Secondary Piping Figure 7.
NOTE: Shut off valves and unions should be
installed at the inlet and outlet connections of the
boiler/hot water heater to provide for isolation of the
unit should servicing be necessary.
Relief Valve
Pipe the discharge of the pressure relief valve to prevent
scalding in the event of a discharge, see Figure 6. The
discharge piping must be sized the same as the
pressure relief valve outlet and installed to allow
complete drainage of both the relief valve and the
discharge piping.
Figure 6
1" (25mm) CLEARANCE MUST
BE MAINTAINED BETWEEN HOT
WATER PIPING AND COMBUSTIBLE
CONSTRUCTION.
NOT
covered
CAUTION: Failure to properly install the flow switch
may result in damage to the boiler/water heater heat
exchanger voiding the warranty!
HEATING SYSTEM PIPING
General Piping Requirements
All heating system piping must be installed by a qualified
technician in accordance with the latest revision of the
ANSI/ASME Boiler and Pressure Vessel Code, Section
IV, and ANSI/ASME CSD-1, Standard for Controls and
Safety Devices for Automatically Fired Boilers. All
applicable local codes and ordinances must also be
followed. A minimum clearance of 1 in,
maintained between heating system pipes and all
combustible construction. All heating system piping must
be supported by suitable hangers not the boiler.
The thermal expansion of the system must be
considered when supporting the system. A minimum
system pressure of 12 psig,
maintained.
Heating Boiler Piping Connections
The supply and return connections should be sized to
suit the system, see Table 5.
Table 5 - Supply & Return Pipe Sizing
ModelSupplyReturn
890021/2" NPT21/2" NPT
88003" Victaulic3" Victaulic
*Models 420-950 may have 21/2" x 2" reducing fitting
installed.
25 mm
82.7 kPa
must be
must be
DISCHARGE PIPE SIZE TO
EQUAL VALVE OUTLET.
OUTLET
INLET
RIOM-46
DO NOT RESTRICT FLOW.
DISCHARGE SO AS TO AVOID
EXPOSURE OF PERSONS TO
HOT LIQUID OR VAPOR AND
ALLOW COMPLETE DRAINAGE
0F RELIEF VALVE AND PIPING
.
WARNING: Never install any type of valve
between the boiler/water heater and the relief
valve or an explosion causing extensive
property damage, severe personal injury or
death may occur!
Flow Switch
The flow switch supplied with the boiler/water heater
must be wired to the terminal strip in the junction box
to prevent the boiler from firing unless there’s adequate
water flow through the unit. The flow switch must be
installed in the supply piping adjacent to the boiler outlet
connection.
Pump Requirements
This low mass boiler requires a continuous minimum
water flow for proper operation. The system pump must
be sized to overcome the head loss of the boiler and
the heating system in order to achieve the required
temperature rise. Table 6A and 6B provides the heat
exchanger pressure drop and temperature rise figures.
The temperature rise across the boiler must never
exceed 35°F,
19.4°C
. The pump delay turns the pump
on each time the burners fire and runs the pump for up
to 10 minutes after the call for heat is satisfied.
CAUTION: A temperature rise outside of the range
listed in Table 6A and 6B indicates that the flow rate
through the heat exchanger is incorrect which will
damage the heat exchanger voiding the warranty!
The maximum allowable flow rate through an 8900
boiler with copper heat exchanger is 92 GPM,
5.8 L/s
and 185 GPM,
11.7 L/s
on single pass.
The maximum allowable flow rate through an 8800
boiler with copper heat exchanger is 185 GPM,
11.7 L/s
and 370 GPM,
23.3 L/s
on single pass.
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 11
Table 6A - Temperature Rise Table — 2 Pass Headers
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 12
Low Water Cutoff
If a boiler is installed above any radiation elements it
must be fitted with a low water cutoff device.
Refer to the wiring diagram supplied with the boiler/
water heater for proper wiring connections.
Expansion Tank
An expansion tank or other means to control thermal
expansion must be installed in the heating system. An
expansion tank must be installed close to the boiler on
the suction side of the pump.
Primary/Secondary Piping
Boilers connected to heating systems using zone
valves, zone pumps, or systems that have excessive
flow rates or return water temperatures less than 110°F,
43°C
must be isolated from these systems to protect the
boiler.
Variable Water Flows
Figure 7 shows a typical primary/secondary piping
system. A dedicated pump is used to maintain a
constant water flow through the boiler. This secondary
pump is sized to overcome the head loss of the boiler
and secondary piping system while supplying the flow
rate required to maintain the desired temperature rise
across the boiler. The primary pump is sized to provide
the required flow to the heating system. The secondary
piping connections to the primary system piping must
not be more than 12 in,
305 mm
apart to ensure zero
pressure drop in the primary system, see Figure 7.
Low Return Water Temperatures
To prevent the problems associated with condensation
of the products of combustion due to low return water
temperatures a primary/secondary piping system with
a bypass and bypass valve must be installed, see
Figure 8. The bypass and bypass valve must be sized
the same as the secondary piping. A balancing valve
must also be installed in the supply side of the
secondary piping downstream of the bypass. The
balancing valve should be adjusted to divert some of
the heated discharge water into the return water until
the required inlet water temperature is achieved. The
primary and secondary pumps should be sized to
provide the required flow through each system. The
secondary piping connections to the primary system
piping must not be more than 12 in,
305 mm
apart to
ensure zero pressure drop in the primary system, see
Figure 8.
Multiple Boiler Systems
Systems using multiple boilers can also be installed
using a primary/secondary manifold system, Figure 9.
Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration
system, must be installed so the chilled medium is piped
in parallel with the boiler. Appropriate valves must be
used to prevent the chilled water from entering the
boiler.
When a boiler is connected to a heating coil that may
be exposed to refrigerated air from an air handling
device, the piping system must be equipped with flowcontrol valves or some other automatic means of
preventing gravity circulation of the boiler water during
the cooling cycle.
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 13
Figure 7 - Typical Primary/Secondary Piping System
Adjustment Procedure To Maintain Inlet Temperature
Above Dew Point
T1-Temp-Min=110° For Atmospheric
T1-Temp-Min=125° Sealed Combustion
1. Turn heater on and open valves A & B.
2. After steady-state operation, if T1 is less than Temp-Min
slowly close valve B until T1 climbs to desired operating
temperature above Temp-Min.
3. If T1 is greater than desired operating temperature, slowly
close valve A to adjust to lower desired temperature above
Temp-Min.
4. Check after system operating temperature has
stabilized. Make final adjustments.
5. Follow same adjustment procedure for sealed combustion.
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 14
Figure 9 - Multiple Boiler Piping
(See Notes)
5
Circuit Setter
1
NOTES:
1. Boiler circuit piping must be sized large enough to handle
maximum flow through unit.
2. Boiler pump sized to boiler design flow requirements.
3. All boilers furnished with factory mounted outlet water
temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
5. Secondary loop pipe diameter must be sized large enough to
handle maximum flow through all units.
Notice: These drawings show suggested piping configuration and valving.
Check with local codes and ordinances for specific requirements.
H-15 Rev 2
Pump
Valve
Check Valve
Backflow-Prevention
Device
Pressure
Relief Valve
Thermometer
Aquastat
Epansion
Tank
Union
Automatic
Air Vent
Pressure
Reducing
Valve
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 15
DOMESTIC WATER SUPPLY PIPING
CAUTION: Proper controls must be used to prevent
water supplied for domestic use from exceeding
130°F,
higher water temperatures are required for
appliances such as a dishwasher, a mixing valve or
some other tempering means must be installed.
Households with small children may require water
temperatures less than 120°F,
must be complied with!
General Piping Requirements
Ensure that the water heater is equipped with bronze
headers. Piping and components connected to the water
heater must be suitable for use with potable water. The
water heater must not be connected to any heating
system piping or components previously used with a
non-potable water heating appliance. Toxic chemicals,
such as those used for boiler treatment, are not to be
introduced into any potable water used for space
heating. If a hot water storage tank is used in the system
it must be equipped with a temperature and pressure
relief valve that complies with ANSI Z21.22 or CAN-4.4
and CAN-4.6.
NOTE: The storage tank must be located as close
to the water heater as possible to prevent excessive
head loss which will reduce flow.
Water Chemistry
The required temperature rise across the water heater
is based on water having a hardness between 8 and
18 grains per gallon with a level of dissolved solids not
exceeding 350 ppm. Water having a hardness less than
8 grains can cause excessive corrosion of the heat
exchanger. Water that has a hardness greater than 18
grains per gallon and/or a level of dissolved solids
exceeding 350 ppm will require a recalculation of the
pump size and temperature rise.
54
°C or a scald injury will occur! When
49
°C. Local codes
CAUTION:
through a water heater with copper heat exchanger
on an 8900 is 92 GPM,
on single pass. The cupro-nickel heat exchanger
allows for 100 GPM,
single pass.
The maximum allowable flow rate through a water
heater with copper heat exchanger on an 8800 is 185
GPM,
11.7 L/s
The cupro-nickel heat exchanger allows for 200 GPM,
12.6 L/s
Tables 6A and 6B.
RBI water heaters are designed to run scale free. Due
to the extreme variables of water conditions world wide
it is necessary to consider pH values and water
hardness in relationship to scaling. It is crucial to
consider these two variables when making heat
exchanger and pump selections. If local water conditions
are extreme, follow the guidelines in the Heat Exchanger
Selection Table (Table 7A) and the Pumping
Performance Table (Table 7B). Scale free operation can
be achieved by using water with a hardness between 8
and 18 and by maintaining the pH between 5 and 9.
Follow the conditions listed under NORMAL in the table.
In some areas of the country additional precautions
must be observed due to unusual characteristics of the
local water supply. Call the nearest RBI representative
for details.
To properly size the pump a grain hardness and pH test
must be taken at the installation site before the order is
placed. Proper pump sizing will improve heater
performance and help ensure heater longevity.
Expansion Tank
An expansion tank or other means to control thermal
expansion must be installed in the water heating system
if back flow prevention devices are installed.
The maximum allowable flow rate
5.8 L/s
and is 185 GPM,
6.3 L/s
and 370 GPM,
and 400 GPM,
and 200 GPM,
23.3 L/s
25.2 L/s
on single pass. See
on single pass.
11.7 L/s
12.6 L/s
on
A cupro-nickel heat exchanger may also be required. The
manufacturer should be consulted when these water
conditions are encountered. See Table 7A.
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.