RBI Futera II Series Installation & Operating Instructions Manual

FTII-IOM-3
FUTERA II SERIES FINNED COPPER
GAS BOILERS & WATER HEATERS
INSTALLATION & OPERATING
INSTRUCTION
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 160 PSI WATER.
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch. Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE BOILER / WATER HEATER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.
260 North Elm Street 1300 Midway Boulevard Westfield, MA 01085 Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
www.rbiwaterheaters.com
Mississauga, Ontario L5T 2G8 Canada
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
AVERTISSMENT. Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualifié ou par le fournisseur de gaz.
CONTENTS
Before Your Start page 2 Ratings & Capacities page 3 Location page 3 Combustion Air & Ventilation page 3 Venting Guidelines page 5 Common Vent Systems page 11 General Piping Requirements page 11 Heating System Piping page 12 Domestic Water Supply Piping page 15 Gas Supply Piping page 17 Electrical Wiring page 17 Boiler/Water Heater Operation page 18 Operating Instructions page 18 Checking, Adjustment & Operation page 19 Diagnostics page 22 Maintenance page 22 Trouble-Shooting page 24
Repair Parts page 25
BEFORE YOU START
This manual covers the application, installation, operation and maintenance of a Futera II Series finned copper heating boiler/water heater.
To obtain the safe, dependable, efficient operation and long life for which this heating boiler/water heater was designed, these instructions must be read, understood and followed.
The Futera II Series finned copper heating boiler/water heaters have been design certified by CSA for use with natural and propane gas under the latest revision of ANSI­Z21.10.3/CSA 4.3, Gas Water Heaters, ANSI-Z21.13/CSA
4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers and CAN1-3.1, Industrial and Commercial Gas Fired Packaged Boilers. Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160 psi in accordance with Section IV of the A.S.M.E. Boiler and Pressure Vessel Code.
All aspects of the boiler/water heater installation must conform to the requirements of the authority having juris­diction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1-latest revision. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the requirements of CSA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the service organization for future reference.
Direct all questions to your RBI Water Heaters distributor or contact the RBI Customer Service Department at: 260 North Elm Street, Westfield, MA 01085 for US or 1300 Midway Boulevard, Mississauga ONT L5T 2G8 for Canada. Always include the model and serial numbers from the rating plate of the boiler/water heater in question.
2
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
RATINGS & CAPACITIES
Before undertaking the installation of the Futera II Series boiler/water heater check the rating plate to ensure that the unit has been sized properly for the job. The “Net I=B=R Ratings” specify the equivalent amount of direct cast iron radiation that the unit can supply under normal conditions. Also ensure that the unit has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1. This boiler/water heater is suitable for indoor and outdoor installations. Locate the boiler/water heater in an area that provides good access to the unit. Servicing may require the removal of jacket panels. Allow the minimum clearances between adjacent construction and the boiler/water heater as listed in Table 1. Accessibility clearances must take precedence over fire protection clearances.
Table 1 Clearance to Service
Combustibles Clearance
Top 24" (610 mm) 36" (914 mm) Back 14" (356 mm) 24" (610 mm) Left Side 6" (153 mm) 12" (306 mm) Right Side 6" (153 mm) 12" (306 mm) Front 8" (203 mm) 36" (914 mm)
2. An optimum site will be level, central to the piping system, close to a chimney or outside wall and have adequate fresh air for combustion. Ensure that the boiler/ water heater is level from front to back and from side to side. Use metal shims to level the boiler/water heater. Electrical and electronic components must also be protected from exposure to water during operation and maintenance. DO NOT install this boiler/water heater in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
3. Ensure that the floor is structurally sound and will support the weight of the boiler/water heater.
NOTE: The Futera II may be installed directly on combustible flooring, but never on carpeting.
4. Locate the boiler/water heater in an area that will prevent water damage to adjacent construction should a leak occur or during routine maintenance. If such a location doesn’t exist, a suitable drain pan that’s adequately drained must be installed under the unit.
CAUTION Units installed outdoors MUST be protected from ice and snow accumulation or the unit will be damaged voiding the warranty!
WARNING Never store combustible materials, gasoline or any product containing flammable vapors or liquids in the vicinity of the boiler/water heater. Failure to comply with this warning can result in an explosion or fire causing extensive property damage, severe personal injury or death!
COMBUSTION AIR & VENTILATION
WARNING This boiler/water heater must be supplied with combustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1 and all applicable local building codes. Canadian installations must comply with CAN/ CGA B149.1 or .2 Installation Code for Gas Burning Appliances and Equip-ment, or applicable provisions of the local building codes. Failure to provide adequate combustion air for this boiler/water heater can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
To operate properly and safely this boiler/water heater requires a continuous supply of air for combustion. NEVER store objects on or around the boiler/water heater!
CAUTION Combustion air contaminated with fluorocarbons or other halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. These acids will cause premature failure of the boiler/water heater voiding the warranty!
CAUTION If the boiler/water heater is operated while the building is under construction it MUST be protected from wood, concrete, sheet rock and other types of dust or the unit will be damaged voiding the warranty!
Buildings will require the installation of a fresh air duct or other means of providing make-up air if the intake air option isn’t used. Any building utilizing other gas burning appliances, a fireplace, wood stove or any type of exhaust fan must be checked for adequate combustion air when all of these devices are in operation at one time. Sizing of an outside air duct must be done to meet the requirements of all such devices.
5. DO NOT place this boiler/water heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure, see VENTING GUIDELINES.
6. NEVER place this boiler/water heater in a location that would subject it to temperatures at or near freezing. See the Freeze Protection Section on page 12.
WARNING Never operate the Futera II in an environment subjected to a negative pressure unless it is Direct Vented. Failure to comply with this warning can result in excessive levels of carbon monoxide causing severe personal injury or death!
3
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
All Air From Inside The Building
If the Futera II is to be located in a confined space the minimum clearances listed in Table 1 must be maintained between it and any combustible construction. When installed in a confined space without the intake air option two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have sufficient volume to meet the criteria for an unconfined space. The total air requirements of all gas utilization equipment, fireplaces, wood stoves or any type of exhaust fan must be considered when making this determination. Each opening must have a minimum free area of 1 in
2
/1000 Btu/hr (2200 mm2/kW) based on the total input rating of ALL gas utilization equipment in the confined area. Each opening must be no less than 100 square inches (64516 mm
2
) in size. The upper opening must be within 12 inches (300 mm) of, but not less than 3 inches (80 mm) from, the top of the enclosure. The bottom opening must be within 12 inches (300 mm) of, but not less than 3 inches (80 mm) from, the bottom of the enclosure.
All Air From Outside The Building When installed in a confined space without the intake air option two permanent openings communicating directly
with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 inches (300 mm) of, but not less than 3 inches (80 mm) from, the top of the enclosure. The bottom opening must be within 12 inches (300 mm) of, but not less than 3 inches (80 mm) from, the bottom of the enclosure.
must be given to the blockage effects of louvers, grills and screens. Screens must have a minimum mesh size of 1/ 4" (6.4mm). If the free area through a louver or grill is not known ducts should be sized per Table 2 above.
Intake Air Option – General Guidelines
This configuration provides combustion air directly to the boiler/water heater’s air intake using a dedicated pipe when using the direct vent option. The RBI air intake adapter must be fitted to the blower inlet. Combustion air can be drawn in horizontally through an outside wall or vertically through the roof, see Figures 1, 2, 3 & 4.
WARNING Each boiler/water heater must have it’s own intake air system. Common intake air systems are not to be used! Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Single wall galvanized smoke pipe, single wall aluminum pipe, flexible aluminum pipe, PVC or CPVC pipe can be used for the intake air pipe. It must be sized per Table 3.
Table 3 – Intake Air Pipe Sizing
2
Model Size Pipe Diameter in
(mm2) 500 8 (203) 750, 1000 10 (254) 1250, 1500 12 (305) 1750, 1950 14 (356)
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in Btu/hr (550 mm
2
/kW) of the total input rating of all of the
2
/4000
equipment in the enclosure.
Where communicating with the outdoors through hori­zontal ducts, each opening shall have a minimum free area
2
/2000 Btu/hr (1100 mm2/kW) of the total input rating
of 1 in of all of the equipment in the enclosure.
When ducts are used, they must have the same cross­sectional area as the free area of the opening to which they connect.
Table 2 – Make-up Air Duct Sizing
2
Required Cross Sectional Duct Area in
(cm2) Input 1/4" (6.4 mm) Metal Wooden (MBH) Wire Screen Louvers Louvers 500 125 (806) 167 (1077) 500 (3226) 750 187 (1206) 250 (1613) 750 (4839) 1000 250 (1613) 333 (2148) 1000 (6452) 1250 313 (2019) 416 (2684) 1250 (8065) 1500 375 (2419) 500 (3226) 1500 (9677) 1750 437 (2819) 583 (3761) 1750 (11,290) 1950 486 (3135) 649 (4187) 1950 (12,581)
When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration
All joints in metal intake air systems must be secured using corrosion resistant fasteners and sealed using a suitable Silicone caulk. If PVC or CPVC is used, the joints must be cleaned with a suitable solvent and connected using a solvent based PVC cement. The intake air system MUST
be supported by the building structure not the boiler/ water heater.
A stack damper interlocked with the unit should be instal­led in the intake air pipe when the infiltration of subfreez­ing air could occur, otherwise the unit could freeze up.
Intake Air Option – Vertical Guidlines
The maximum equivalent length for the vertical intake air pipe is 60 feet (19.7 m). Each 90˚ elbow and the intake air cap are equal to 10 linear feet (3.3 m) of pipe.
A listed, nonrestrictive intake air cap must be used. The intake air cap must terminate as shown in Figure 3. The penetration point in the roof must be properly flashed and sealed.
Intake Air Option – Horizontal Guidlines
The maximum equivalent length for the horizontal intake air pipe is 60 feet (19.7 m). Each 90˚ elbow and the intake air terminal are equal to 10 linear feet (3.3 m) of pipe. If horizontal runs exceed 5 feet (1.5 m) they must be supported at 3 foot (0.98 m) intervals with overhead hangers. The certified intake air terminal from RBI must be used, see Figures 1, 2 and 4.
4
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
GENERAL VENTING GUIDELINES
WARNING The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1-latest revision or applicable provisions of the local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
All vent systems must be fully supported by the building structure and not by the boiler/water heater. Appropriate thimbles and fire-stops must be used where required.
WARNING Each boiler/water heater must have it’s own vent system. Common positive pressure vent systems are not to be used! Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Note: When a barometric damper is used it must be installed directly to the boiler/water heater flue outlet to ensure proper operation.
VENT SYSTEM OPTIONS
The Futera II may be vented the following ways:
1) Direct Vent (Positive Pressure), uses a vent system
certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Combustion air is piped from the outdoors to the blower inlet.
2) Side Wall Vent (Positive Pressure), uses a vent
system certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Combustion air is obtained from the space in which the unit is installed.
Horizontal Direct Vent Systems – Figures 1 & 2
The vent materials used in horizontal vent systems must be certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. The certified vent terminal from RBI must also be used.
The maximum equivalent length for the horizontal vent pipe is 60 feet (19.7 m). Each 90˚ elbow and the intake
air terminal are equal to 10 linear feet (3.3 m) of pipe. To maximize the performance of single wall sheet metal vent systems locate 90˚ elbows as far from the boiler as possible and from one another. For best results, horizontal vent systems should be as short and straight as possible.
The vent system must be both gas tight and watertight. All seams and joints in metal pipes must be joined and sealed in accordance with the vent system manufacturer’s instructions.
When horizontal vent runs exceed 5 feet (1.5 m) they must be supported at 3 foot (0.98 m) intervals with overhead hangers. The vent system must be pitched down, toward the vent terminal, 1/4" per foot (21 mm per meter). If any part of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400˚F.
Horizontal vent systems shall terminate at least 4 feet (1.3 m) below, 4 feet (1.3 m) horizontally from or 1 foot (0.23 m) above any door, window or gravity air inlet into any building. It must not terminate less than 4 feet (1.3 m) horizontally from, and in no case above or below, unless a 4 feet (1.3 m) horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment and not less than 7 feet (2.3 m) from any adjacent public walkway. The bottom of the vent terminal(s) shall be located at least 5 feet (1.5 m) above the air intake terminal(s). Avoid terminal locations likely to be affected by winds, snowdrifts, people and pets.
3) Vertical/Chimney Vent (Negative Pressure), uses an
approved metal chimney system or masonry chimney. Combustion air is obtained from the space in which the unit is installed.
4) Outdoor Installation uses the outdoor option kit.
DIRECT VENT (POSITIVE PRESSURE)
In this configuration the boiler/water heater blower is used to push the flue products to the outdoors while drawing combustion air from the outdoors. The Intake Air Option instructions under the COMBUSTION AIR & VENTILATION SECTION must be followed! The vent system must be sized per Table 4.
Table 4 – Direct Vent Pipe Size, Positive Pressure
Model Size Pipe Diameter in.(mm) 500 6 (152) 750 8 (203) 1000 9 (229) 1250, 1500 10 (254) 1750, 1950 12 (305)
Protect building materials and vegetation from degradation caused by the flue gases.
Vertical Direct Vent Systems – Figure 3
The maximum length for the vertical vent pipe is 30 feet (19.7m) plus two 90˚ elbows. If any part of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400˚F. Structural penetrations must be made using approved fire-stops.
A listed, nonrestrictive vent cap must be used. The top of a vertical vent system must extend at least 5 m) above the roof surface that it passes through, 4 feet (1.3 m) above the intake air cap, see Figure 3.
1
/2 feet (1.8
5
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
In addition the vent system must conform to the dimensions shown in Figure 3. The penetration point in the roof must be properly flashed and sealed.
Figure 1– Horizontal Air Intake and Venting for a Single Direct Vent System
The vent system must be gas tight. All seams and joints in metal pipes must be joined and sealed in accordance with the vent system manufacturer’s instructions.
Figure 2 – Horizontal Air Intake and Venting for Multiple Direct Vent Systems
6
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
Figure 3 - Vertical Air Intake and Venting for Direct Vent System
Combination Direct Vent Systems – Figure 4
The boiler/water heater can be vented vertically with the intake air piped horizontally through an outside wall. Follow the instructions in the Intake Air Option –
Figure 4 – Combination Direct Vent Systems
Horizontal Guidelines on page 4. Also follow the general
instructions in the COMBUSTION AIR & VENTILATION and GENERAL VENTING GUIDELINES sections.
7
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
SIDE WALL VENT (POSITIVE PRESSURE)
In this configuration the boiler/water heater blower is used to push the flue products horizontally to the outdoors, see Figure 5. The air for combustion is taken from the space in which the unit is installed. The applicable instructions
Figure 5 – Side Wall Venting
under the COMBUSTION AIR & VENTILATION SECTION must be followed! The vent guidelines under the Horizontal Direct Vent Systems section must also be followed.
VERTICAL/CHIMNEY VENT (NEGATIVE PRESSURE) The Futera II is listed as a Category I
appliance when vented vertically into a listed metal chimney system or properly sized masonry chimney, Figures 6 & 7. The chimney must provide a negative pressure of 0.02 to 0.08 in. W.C. at the boiler/water heater flue collar with the unit running. A single acting barometric damper must be attached directly to the flue collar increaser as shown.
Note: DO NOT remove the damper stops. For proper operation the damper must remain as single acting.
Multiple Futera II’s can be vented into a single vertical chimney provided that the breeching and chimney are properly sized per the latest revision of the National Fuel Gas Code, ANSI Z223.1.
When more than one appliance is connected to the same chimney flue the flue must be large enough to safely vent the combined output of all of the appliances.
WARNING If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney flue, never connect any other appliances to this flue. Doing so can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
Chimney Inspection & Sizing
A thorough inspection of the masonry chimney must be performed to ensure that the chimney is clean, properly con-structed and properly sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems. Table 5 lists the equivalent breeching and flue sizes required for the boiler/ water heater.
Table 5 – Equivalent breeching & chimney size,
Negative Pressure
Model Size Breech & Flue Diameter in (mm) 500 8 (203) 750, 1000 10 (254) 1250, 1500 12 (305) 1750, 1950 14 (356)
Note: These sizes are based on a 20 foot (6.1m) chimney height.
Vent Connections
Locate the boiler/water heater as close to the chimney as possible. Use the shortest, straightest vent connector possible for the installation. If horizontal runs exceed 5 feet (1.5 m) they must be supported at 3 foot (0.9 m) intervals with overhead hangers. Use a type B, single wall stainless or single wall galvanized steel vent pipe the same diameter as the flue collar to connect the boiler/water heater to a masonry chimney. When using a listed metal chimney system use the appropriate vent connector.
8
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
The vent system should be sloped up toward the chimney at a minimum rate of 1/4 inch/foot (2 cm/m). On masonry chimneys the connector must terminate flush with the inside of the chimney flue, Figure 7. Fasten each single wall vent connection with at least 3 corrosion resistant sheet metal screws.
WARNING Never install a vent pipe of a diameter different thatn that of the boiler/water heater's flue outlet. Failure to comply with this warning can result in excessive levels of carbon monoxide which can cause severe personal injury or death.
Figure 6 – Vertical Venting with a Metal Chimney System
Always provide a minimum clearance of 6 inches (152 mm) between single wall vent pipe and any combustible materials. Type B1 vent may be used, clearance between it and any combustible material must be as listed.
WARNING Failure to maintain minimum clearances between vent connectors and any combustible material can result in a fire causing extensive property damage, severe personal injury or death!
9
FUTERA II INSTALLATION AND OPERATION INSTRUCTIONS
Figure 7 – Vertical Venting using a Masonry Chimney
OUTDOOR VENTING
When installed outdoors the Futera II must be fitted with the factory supplied outdoor hood, air intake adapter with filter and exhaust terminal, see Figure 8.
The boiler/water heater must be at least 10 feet (3.2 m) from any door, window or gravity air inlet into any building and at least 3 feet (0.98 m) from any overhang unless local codes dictate differently.
Figure 8 – Outdoor Venting
Do not place the boiler/water heater in a location that would subject it to runoff from adjacent buildings.
Multiple outdoor units must be spaced as shown in Figure 9 to prevent flue gasses from one unit from being inngested by an adjacent unit.
Figure 9 – Multiple Outdoor Units
10
Loading...
+ 22 hidden pages