Finned Copper Tube
Gas Boilers (MB) &
Water Heaters (MW)
Boiler Manual
Installation and Operation
Instructions
Also read and follow:
HeatNet® Control Manual
is manual is intended only for use by a qualied heating installer/technician. Read and follow this manual, all supplements and related
instructional information provided with the boiler. Install, start and service the boiler only in the sequence and methods given in these
instructions. Failure to do so can result in severe personal injury, death or substantial property damage.
Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause contamination
of the burner, resulting in possible severe personal injury, death or substantial property damage. e boiler can only be operated with
a dust-free air supply. Follow the instruction manual procedures to duct air to the boiler air intake. If the boiler has been contaminated
by operation with contaminated air, follow the instruction manual guidelines to clean, repair or replace the boiler if necessary.
Ax these instructions near to the boiler. Instruct the building owner to retain the instructions for future use by a qualied service
technician, and to follow all guidelines in the User’s Information Manual.
12/15 Copyright 2015 Mestek, Inc.
Page 2
Finned copper tube gas boilers & water heaters – Boiler Manual
If the information in this manual is not followed
exactly, a re or explosion may result causing property,
personal injury or loss of life.
Do not store or use gasoline or other ammable vapors
and liquids in the vicinity of this or any other applianc
is manual covers the application, installation, operation and
maintenance of a Futera III Series nned copper heating boiler/
water heater/pool heater (Canada only). To obtain the safe,
dependable, ecient operation and long life for which this heating
boiler/water heater was designed, these instructions must be read,
understood and followed.
e Futera III Series nned copper heating boiler/water heaters
have been design certied by CSA for use with natural and propane
gas under the latest revision of ANSI-Z21.10.3/CSA 4.3, Gas Water
and Hot Water Boilers ANSI-Z21.56/CSA 4.7 Gas-Fired Pool
Heaters (Canada only) and CAN1-3.1, Industrial and Commercial
Gas Fired Packaged Boilers. Each unit has been constructed and
hydrostatically tested for a maximum working pressure of 160 psi,
1103 kPa in accordance with Section IV of the A.S.M.E. Boiler
and Pressure Vessel Code.
2
Page 3
Finned copper tube gas boilers & water heaters – Boiler Manual
All aspects of the boiler/water heater installation must conform to
the requirements of the authority having jurisdiction, or, in the
absence of such requirements, to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54-latest revision. Where required by the authority
having jurisdiction, the installation must conform to the Standard
for Controls and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the require-
ments of CSA B149.1 or .2, Installation Code for Gas Burning
Appliances and Equipment.
If installed in the Commonwealth of Massachuses, you MUST
FOLLOW the additional instructions contained in RBI’s instruction
sheet MACODE-3. Which is located in the back of this manual.
e owner should maintain a record of all service work performed
with the date and a description of the work done. Include the name
of the service organization for future reference.
Direct all questions to your RBI distributor or contact the
RBI Customer Service Department at: 260 North Elm Street,
Westeld, MA 01085 for US or 7555 Tranmere Drive, Mississauga
ONT L5S 1L4 for Canada. Always include the model and serial
numbers from the rating plate of the boiler/water heater in question.
RATINGS & CAPACITIES
Before undertaking the installation of the Futera III Series boiler/
water heater check the rating plate to ensure that the unit has been
sized properly for the job. e “Net I=B=R Ratings” specify the
equivalent amount of direct copper radiation that the unit can supply
under normal conditions. Also ensure that the unit has been set
up for the type of gas available at the installation site. Other important
considerations are the availability of an adequate electrical supply,
fresh air for combustion and a suitable chimney or vent system.
2. An optimum site will be level, central to the piping system, close
to a chimney or outside wall and have adequate fresh air for
combustion. Ensure that the boiler/water heater is level from
front to back and from side to side. Use metal shims to level
the boiler/water heater. Electrical and electronic components
must also be protected from exposure to water during operation
and maintenance. DO NOT install this boiler/water heater in
a location that would subject any of the gas ignition components
to direct contact with water or excessive moisture during
operation or servicing.
3. Ensure that the oor is structurally sound and will support the
weight of the boiler/water heater.
e Futera III may be installed directly on combustible
ooring, but never on carpeting.
4. Locate the boiler/water heater in an area that will prevent water
damage to adjacent construction should a leak occur or during
routine maintenance. If such a location doesn’t exist, a suitable
drain pan that’s adequately drained must be installed under the
unit.
5. DO NOT place this boiler/water heater in a location that would
restrict the introduction of combustion air into the unit or
subject it to a negative pressure, see “GENEL VENTING
GUIDELINES”.
6. NEVER place this boiler/water heater in a location that would
subject it to temperatures at or near freezing, see the “FREEZE
PROTECTION” section on page 13.
Never store combustible materials, gasoline or any
product containing ammable vapors or liquids in the
vicinity of the boiler/water heater. Failure to comply
with this warning can result in an explosion or re
causing extensive property damage, severe personal
injury or death!
BOILER/WATER HEATER LOCATION
1. is boiler/water heater is suitable for indoor and oudooor
installations. Locate the boiler/water heater in an area
that provides good access to the unit. Servicing may
require the removal of jacket panels. Allow the minimum
clearances between adjacent construction and the boiler/water
heater as listed in Table 1.
Service clearances are not mandatory, but are
recommended to ensure ease of service should it be
required.
Table 1
Clearance to
Combustibles
Top6 15330 762
Back615324610
Left Side615312306
Right Side615312306
Front615330762
inmminmm
Service
Clearance
COMBUSTION AIR & VENTILATION
is boiler/water heater must be supplied with
combustion air in accordance with Section 5.3, Air
for Combustion & Ventilation, of the latest revision
of the National Fuel Gas Code, ANSI Z223.1/NFPA
54 and all applicable local building codes. Canadian
installations must comply with CAN/ CGA B149.1
or .2 Installation Code for Gas Burning Appliances
and Equipment, or applicable provisions of the local
building codes. Failure to provide adequate combustion
air for this boiler/water heater can result in excessive
levels of carbon monoxide which can result in severe
personal injury or death!
To operate properly and safely this boiler/water heater requires a
continuous supply of air for combustion. NEVER store objects on
or around the boiler/water heater!
3
Page 4
Finned copper tube gas boilers & water heaters – Boiler Manual
Combustion air contaminated with uorocarbons
or other halogenated compounds such as cleaning
solvents and refrigerants will result in the formation
of acids in the combustion chamber. ese acids will
cause premature failure of the boiler/water heater
voiding the warranty!
If the boiler/water heater is operated while the building
is under construction it MUST be protected from
wood, concrete, sheet rock and other types of dust.
Failure to properly protect the unit from construction
dust will damage the unit voiding the warranty!
Buildings will require the installation of a fresh air duct or other
means of providing make-up air if the intake air option isn’t used.
Any building utilizing other gas burning appliances, a replace, wood
stove or any type of exhaust fan must be checked for adequate
combustion air when all of these devices are in operation at one
time. Sizing of an outside air duct must be done to meet the
requirements of all such devices.
Never operate the Futera III in an environment
subjected to a negative pressure unless it is Direct
Vented. Failure to comply with this warning can result
in excessive levels of carbon monoxide causing severe
personal injury or death!
Where directly communicating with the outdoors or communi-
cating with the outdoors through vertical ducts, each opening shall
have a minimum free area of 1 in2/4000 Btu/hr, 550 mm2/kW
of the total input rating of all of the equipment in the enclosure.
Where communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1 in2/
2000 Btu/hr, 1100 mm2/kW of the total input rating of all of
the equipment in the enclosure.
When ducts are used, they must have the same cross-sectional area
as the free area of the opening to which they connect.
When calculating the free area necessary to meet the make-up air
requirements of the enclosure, consideration must be given to the
blockage eects of louvers, grills and screens. Screens must have a
minimum mesh size of 1/4 in, 6.4 mm. If the free area through a
louver or grill is not known, ducts should be sized per Table 2.
Canadian installations must comply with CSA B149.1 when air
supply is provided by natural air ow from the outdoors for natural
draft, partial fan-assisted, fan-assisted, or power dra-assisted
burners, there shall be a permanent air supply opening(s) having
a cross-sectional area of not less than 1 in2 per 7,000 Btuh
(310 mm2 per kW) up to and including 1millionBtuh, plus
1 in2 per 14,000 Btuh (155 mm2 per kW) in excess of
1 million Btuh.
All Air From Inside The Building
If the Futera III is to be located in a conned space, the minimum
clearances listed in Table 1 must be maintained between it and any
combustible construction. When installed in a conned space
withouttheintakeairoption, Figures 5, 6 and 7, two permanent
openings communicating with an additional room(s) are required.
e combined volume of these spaces must have sucient volume
to meet the criteria for an unconned space. e total air
requirements of all gas utilization equipment, replaces, wood stoves
or any type of exhaust fan must be considered when making this
determination. Each opening must have a minimum free area of
1 in2/1000 Btu/hr, 2200 mm2/kW based on the total input rating
of ALL gas utilization equipment in the conned area. Each opening
must be no less than 100 in2, 64,516 mm2 in size. e upper
opening must be within 12 in, 305 mm of, but not less than 3 in,
76 mm from, the top of the enclosure. e boom opening must
be within 12 in, 305 mm of, but not less than 3 in, 76 mm from,
the boom of the enclosure.
All Air From Outside The Building
When installed in a conned space withoututilizingtheintake
air option two permanent openings communicating directly with,
or by ducts to, the outdoors or spaces that freely communicate
with the outdoors must be present. e upper opening must be
within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the
top of the enclosure. e boom opening must be within 12 in,
305 mm of, but not less than 3 in, 76 mm from, the boom of
the enclosure.
is conguration provides combustion air directly to the boiler/
water heater’s air intake adapter using a dedicated pipe when using
the direct vent option. Combustion air can be drawn in horizontally
through the same outside wall which terminates the exhaust gases
or vertically through the roof, see Figures 1, 2, 3 & 4.
Common intake air systems may be used provided the
common duct is sized properly. An intake combustion
air damper should be installed if the common vent
option is used in the intake air pipe of each heater.
Improper installation can result in excessive levels of
carbon monoxide which can cause severe personal
injury or death!
Single wall galvanized smoke pipe, single wall aluminum pipe,
exible aluminum pipe, PVC or CPVC pipe can be used for the
intake air pipe. It must be sized per Table 3.
4
Page 5
Finned copper tube gas boilers & water heaters – Boiler Manual
All joints in metal intake air systems must be secured using corro-
sion resistant fasteners and sealed using a suitable Silicone caulk.
If PVC or CPVC is used, the joints must be cleaned with a suitable
solvent and connected using a solvent based PVC cement. e
combustion air system MUST be supported by the building
structurenotthe boiler/waterheater.
A combustion air damper interlocked with the unit
should be installed in the intake air pipe when the
inltration of subfreezing air could occur, otherwise
the unit could freeze up voiding the warranty!
Intake Air Option – Vertical Guidelines
e maximum equivalent length for the vertical intake air pipe is
60 , 18.3 m. Each 90° elbow and the intake air terminal are equal
to 10 linear , 3.0 m of pipe, see Table 3.
An approved, nonrestrictive intake air terminal must be used. e
intake air terminal must terminate as shown in Figure 3. e
penetration point in the roof must be properly ashed and sealed.
Intake Air Option – Horizontal Guidelines
e maximum equivalent length for the horizontal intake air pipe
is 60 , 18.3 m. Each 90° elbow and the intake air terminal
are equal to 10 linear , 3.0 m of pipe. If horizontal runs exceed
5 , 1.5 m they must be supported at 3 , 0.9 m intervals with
overhead hangers. e certied intake air terminal from RBI must
be used, see Figures 1, 2 and 4.
GENERAL VENTING GUIDELINES
e vent installation must be in accordance with Part
7, Venting of Equipment, of the National Fuel Gas
Code, ANSI Z223.1/NFPA 54-latest revision or applicable provisions of the local building codes. Canadian
installations must comply with CAN/CGA B149.1
or .2 Installation Code. Improper venting can result
in excessive levels of carbon monoxide which can
result in severe personal injury or death!
All vent systems must be fully supported by the building structure
and not by the boiler/water heater. Appropriate thimbles and restops must be used where required.
Common vent systems must be properly engineered
and sized to provide a negative dra of .03 in, 0.8 mm
to .1 in, 2.5 mm W.C. at the ue outlet. Common
positive pressure vent systems are not to be used.
Improper installation can result in excessive levels of
carbon monoxide which can cause severe personal
injury or death!
VENT SYSTEM OPTIONS – (CATEGORY I, II, IV)
Correctly identify the type of vent system the appliance
requires before proceeding. Category identication is
noted on the unit rating plate.
e ue products in a Category II and IV vent system may be
cooled below their dew point and form condensate in the ue. e
materials used for a Category II and IV vent must be resistant
to any corrosive damage from ue gas condensate. e ue from
a Category II and IV vent system must have a condensate drain
with provisions to properly collect and dispose of any condensate
that may occur in the venting system.
e Futera III may be vented the following ways:
1) DirectVent,PositivePressure,CategoryIV uses a vent
system certied to UL 1738 for installations in the United
States, ULC S636 for installations in Canada. Combustion air
is piped from the outdoors to the blower inlet.
2) Side WallVent,PositivePressure,Category IV uses a
vent system certied to UL 1738 for installations in the
United States, ULC S636 for installations in Canada. Combustion air is obtained from the space in which the unit is installed.
uses a metal chimney system approved for Category II.
4)
VerticalVent,PositivePressure,CategoryIV
system certied to UL 1738 for installations in the United States,
ULC S636 for installations in Canada. Combustion air is
obtained from the outdoors or the space in which the unit is
installed.
uses an approved metal
chimney system or masonry chimney. Combustion air is obtained from the space in which the unit is installed.
All venting and combustion air material supplied by
installer. All venting materials must be approved for the
application. Consult the vent manufacturer’s product
literature.
e maximum equivalent length for the ue outlet vent
system for Category IV conditions is 60 , 18.3 m.
Use Table 4 for the equivalent lengths per ing.
Table 4 “Category Equivalent Length Per Fiing”
chart is meant as a guideline for preliminary sizing.
If vent length approaches 75% of maximum length
listed an engineered vent system calculation must be
performed, consult factory.
uses a vent
5
Page 6
Finned copper tube gas boilers & water heaters – Boiler Manual
DIRECT VENT, POSITIVE PRESSURE,
CATEGORY IV
In this conguration the boiler/water heater blower is used
to push the ue products to the outdoors while drawing combustion
air from the outdoors. e Intake Air Option instructions under
the “COMBUSTION AIR & VENTILATION” section must be
followed! e vent system must be sized per Table 4.
Table 4 Category IV
Model/
Outlet Diameter
Standard Tee1.2515 ft20 ft 25 ft
Boot Tee0.6510 ft10 ft15 ft
Cap - Low Res. (UL)0.5010 ft10 ft 10 ft
45° w/Bird Screen0.407 ft7 ft 10 ft
Elbow – 90°0.3810 ft10 ft 10 ft
Elbow – 45°0.155 ft5 ft 5 ft
Model/
Outlet Diameter
Standard Tee1.2525 ft35 ft40 ft 40 ft
Boot Tee0.6515 ft15 ft20 ft20 ft
Cap - Low Res. (UL)0.5010 ft10 ft15 ft 15 ft
45° w/Bird Screen0.4010 ft10 ft10 ft 10 ft
Elbow – 90°0.3810 ft10 ft15 ft 15 ft
Elbow – 45°0.155 ft5 ft5 ft 5 ft
Equivalent Feet of Straight Pipe (ft)
K5007501000
5"5"6"
Equivalent Feet of Straight Pipe (ft)
K1250150017502000
6"8"10"10"
Horizontal Direct Vent Systems
Figures 1 & 2
e vent materials used in horizontal vent systems must be certied
to UL 1738 for installations in the United States, ULC S636 for
installations in Canada. e certied vent terminal from RBI must
also be used.
If any part of a single wall metal vent system passes through an
unheated space, it must be insulated with insulation rated for 400°F,
204°C. Structrual penetrations must be made using approved re-
stops. For best results, horizontal vent systems should be as short
and straight as possible.
e vent system must be both gas tight and watertight. All seams
and joints in metal pipes must be joined and sealed in accordance
with the vent system manufacturer’s instructions.
When horizontal vent runs exceed 5 , 1.5 m they must be supported
at 3 , 0.9 m intervals with overhead hangers. e vent system
must be pitched down, toward the vent terminal, 1/4 in/, 20 mm/m.
If any part of a single wall metal vent system passes through an
unheated space it must be insulated with insulation rated for 400°F,
204°C.
Horizontal vent systems shall terminate at least 4 , 1.2 m below,
4 , 1.2 m horizontally from or 1 , 0.30 m above any door, window
or gravity air inlet into any building. It must not terminate less than
4 , 1.2 m horizontally from, and in no case above or below, unless
a 4 , 1.2 m horizontal distance is maintained, from electric meters,
gas meters, regulators and relief equipment and not less than 7 ,
2.1 m above adjacent public walkway. e boom of the vent
terminal(s) shall be located at least 5 , 1.5 m above the air intake
terminal(s) unless there is a minimum 5 , 1.5 m horizontal
separation between them. Avoid terminal locations likely to be
aected by winds, snowdris, people and pets. Protect building
materials and vegetation from degradation caused by the ue gases.
Vertical Direct Vent Systems – Figure 3
If any part of a single wall metal vent system passes through an
unheated space, it must be insulated with insulation rated for 400°F,
204°C. Structural penetrations must be made using approved re-
stops.
An approved, nonrestrictive vent terminal must be used e top
of a vertical vent system must extend at least 51/2 , 1.7 m above
the roof surface and maximum snow line that it passes through,
4 , 1.2 m above the intake air terminal, see Figure 3.
In addition the vent system must conform to the dimensions shown
in Figure 3. e penetration point in the roof must be properly
ashed and sealed.
e vent system must be gas tight. All seams and joints in metal
pipes must be joined and sealed in accordance with the vent system
manufacturer’s instructions.
Combination Direct Vent Systems – Figure 4
e boiler/water heater can be vented vertically with the intake
air piped horizontally through an outside wall. Follow the instructions in the Intake Air Option – Horizontal Guidelines on page
5. Also follow the general instructions in the “COMBUSTION
AIR & VENTILATION” and “GENEL VENTING GUIDE
LINES” sections.
6
Page 7
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 1 Hoizontal Air Intake an Venting for a Single Direct Vent System (Category IV)
1/4 IN. PER FOOT
20 mm/m
1.5 FT0.5 m
1/4 IN. PER FOOT
20 mm/m
16 FT 4.9 m
1.5 FT 0.5 m
When running horizontal combustion air and venting for
single or multiple units, exhaust and combustion air terminals must be installed on the same plane (outside wall)
in order to prevent pressure dierences due to prevailing
winds. In cold climates, double-wall or insulated inlet pipe
recommended to prevent condensation.
Figure 2 Horizontal Air Intake and Venting for Multiple Direct Vent Systems (Category IV)
MBH
500 TO 1000
1001 TO 2000
2001 TO 4000
4001 & LARGER
kW
146 TO 293
293 TO 586
586 TO 1172
1172 & LARGER
FT m
5 1.5
10 3.1
15 4.6
20 6.1
5 FT 1.5 m
1.5 FT 0.5 m
1000 BTU'S
2 IN. 5.0 cm
7
Page 8
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 3 Vertical Air Intake and Venting for a Direct Vent System (Category IV)
4 FT
1.2 m
1.5 FT
0.5 m
5 FT
1.5 m
5 1/2 FT
1.7 m
10 FT 3.1 m
Figure 4 Combination Direct Vent Systems (Category IV)
3 FT. 1 m
1.5 FT. .5 m
10 FT. 3.1 m
8
Page 9
Finned copper tube gas boilers & water heaters – Boiler Manual
SIDE WALL VENT, POSITIVE PRESSURE,
CATEGORY IV – Figure 5
VERTICAL VENT, NEGATIVE PRESSURE –
CATEGORY I & II
In this conguration the boiler/water heater blower is used to push
the ue products horizontally to the outdoors, see Figure 5. e
air for combustion is taken from the space in which the unit is
installed. e applicable instructions under the “COMBUSTION
AIR & VENTILATION” section must be followed! e vent
guidelines under the Horizontal Direct Vent Systems section must
also be followed.
VERTICAL VENT, POSITIVE PRESSURE,
CATEGORY IV – Figures 7 & 9
(Vent pipe equivalent length up to 60 , 18.3 m maximum)
Masonry chimneys, when used, must be lined with a
metal liner certied for Category IV venting.
A thorough inspection of the masonry chimney must be performed
to ensure that the chimney is clean, properly constructed lined, and
sized. Exterior masonry chimneys should not be used unless
properly lined to prevent condensation and dra problems.
e Futera III when listed as a Category II appliance and vent-
ed vertically into a listed metal chimney system, Figures 7 & 9.
e chimney must provide a negative pressure not greater than 0.10
in, 2.5 mm W.C. at the boiler/water heater ue collar with the unit
running. e Futera III when listed as a Category I appliance and
vented vertically into a listed metal chimney system, Figures 6 & 8.
e chimney must provide a negative pressure not greater than
0.01to0.10in, 0.25 to 2.5 mm W.C. at the boiler/water heater
ue collar with the unit running. A barometric damper must be
installed between the ue collar and the vent connector when negative pressures exceed 0.10in, 2.5 mm W.C.
W hen using a listed metal chimney system the chimney
system manufacturer’s instructions must be followed.
Masonry chimneys, when used with Category II
appliances, must be lined with a metal liner certied
to UL 1738 for installations in the United States and
ULC S636 for installations in Canada.
When more than one appliance is connected to the same chimney
ue, the ue must be large enough to safely vent the combined
output of all of the appliances.
If an appliance using any type of a mechanical dra
system operating under positive pressure is connected
to a chimney ue, never connect any other appliances
to this ue. Doing so can result in excessive levels of
carbon monoxide which can cause severe personal
injury or death!
Figure 5 Side Wall Venting (Category IV )
9
Page 10
Finned copper tube gas boilers & water heaters – Boiler Manual
Chimney Inspection & Sizing – Category I and II
A thorough inspection of the masonry chimney must be performed to
ensure that the chimney is clean, properly constructed, lined and sized.
Exterior masonry chimneys should not be used unless properly lined
to prevent condensation and dra problems. Tables 5 & 6 list the
equivalent breeching and ue sizes required for the boiler/water heater.
Correctly identify the ty pe of vent system the appliance
requires before proceeding. Category identication is
noted on the unit rating label.
Note: These sizes are based on a 20 ft, 6.1m chimney height.
–
8
10
10
10
12
12
in
6
6
7
8
8
10
10
mm
–
203
254
254
254
305
305
mm
152
152
178
203
203
254
254
Vent Connections
Locate the boiler/water heater as close to the chimney as
possible. Use the shortest, straightest vent connector possible for
the installation. If horizontal runs exceed 5 , 1.5 m they must be
supported at 3 , 0.9 m intervals with overhead hangers. Use a
single wall stainless steel vent pipe the same diameter as the ue
collar to connect the boiler/water heater to a masonry chimney.
When using a listed metal chimney system use the appropriate vent
connector.
e vent connector should be sloped up toward the chimney at a
minimum rate of 1/4 in/, 21 mm/m. On masonry chimneys
the connector must terminate ush with the inside of the chimney
ue, Figures 8 & 9. Fasten each single wall vent connection with at
least 3 corrosion resistant sheet metal screws.
Always provide a minimum clearance of 6 in, 152 mm between
single wall vent pipe and any combustible materials.
Failure to maintain minimum clearances between vent
connectors and any combustible material can result
in a re causing extensive property damage, severe
personal injury or death!
Exit cones are favorable when used to increase
the velocity of the ue gas exiting the stack and,
may also help, in cold climates, to reduce ice buildup. Exit cone terminations must be supplied by
others, installed per manufacturer’s instructions,
and meet local and federal code.
generic exit cone
Figure 6 Vertical Venting with a Metal Chimney System
(Category I)
10
Figure 7 Vertical Venting with a Metal Chimney System
(Category II)
Page 11
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 8 Vertical Venting Using a Lined Masonry Chimney
(Category I)
Figure 9 Vertical Venting Using a Lined Masonry Chimney
(Category II)
Figure 10 Outdoor Venting (Category IV)
DISCHARGE VENT
AIR INLET LOUVERS
Figure 11 Multiple Outdoor Units
2 FT
(0.62M)
3 FT
(1M)
RIOM-60 REV.B
11
Page 12
Finned copper tube gas boilers & water heaters – Boiler Manual
OUTDOOR VENTING
When installed outdoors the Futera III must be ed with the factory
supplied outdoor hood, air intake adapter with lter and exhaust
terminal, see Figure 10. Multiple units must be spaced per Figure 11.
e boiler/heater must be at least 2 , .62 m from any door, window
or gravity air inlet into any building and at least 3 , 1 m from any
overhang unless local codes dictate dierently.
Avoid locations where wind deection o of adjacent walls, buildings
or shrubbery might cause a downdra. e unit(s) should be located
at least 3 , 1 m from structures. Outdoor installations are not
recommended in areas where the danger of snow blockage exists.
Do not place the boiler/water heater in a location that
would subject it to runo from adjacent buildings or
damage may occur voiding the warranty!
COMMON VENT SYSTEMS
On multiple boiler common vent applications, the master boiler
may be required to be rst on and installed closest to the verticle
chimney (consult factory).
If an existing boiler/water heater is removed from a common venting
system, the common venting system may then be too large for the
proper venting of the remaining appliances connected to it. At the time
of removal of an existing boiler/water heater, the following steps shall
be followed with each appliance remaining connected to the common
venting system placed in operation, while the other appliances remaining
connected to the common venting system are not in operation.
Au moment du retrait d’une chaudière existante, les mesures suivantes
doivent être prises pour chaque appareil toujours raccordé au système
d’évacuation commun et qui fonctionne alors que d’autres appareils
toujours raccordés au système d’évacuation ne fonction-nent pas:
système d’évacuation
a) Seal any unused openings in the common venting system.
Sceller toutes les ouvertures non utilisées du système d’évacuation.
b) Visually inspect the venting system for proper size and horizontal
pitch and determine there is no blockage or restriction, leakage,
corrosion and other deciencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d’évacuation pour déterminer
la grosser et l’inclinaison horizontale qui conviennentet s’assurer que
le système est exempt d’obstruction, d’étranglement de fruite, de
corrosion et autres défaillances qui pourraient présenter des risques.
c) Insofar as is practical, close all building doors and windows and
all doors between the space in which the appliances remaining
connected to the common venting system are located and other
spaces of the building. Turn on clothes dryers and any appliance
not connected to the common v enting system.Tu rn on any exhaus t
fans, such as range hoods and bathroom exhaust, so they will
operate at maximum speed. Do not operate a summer exhaust
fan for a boiler installation. Close replace dampers.
Dans la mesure du possible, fermer toutes les portes et les fenêtres
du bâtiment et toutes les portes entre l’espace où les appareils
toujours raccordés du système d’évacuation sont installés et les
autres espaces du bâtiment. Mere en marche les sécheuses, tous
les appareils non raccordés au système d’évacuation commun et
12
tous les ventilateurs d’extraction comme les hoes de cuisinère
et les ventilateurs des salles de bain.
S’assurer que ces ventilateurs fonctionnent à la vitesse maximale.
Ne pas faire fonctionner les ventilateurs d’été. Fermer les registres
des cheminées.
d) Place in operation the appliance being inspected. Follow the lighting
instructions. Adjust thermostat so appliance will operate continuously.
Mere l’appareil inspecté en marche. Suivre les instructions
d’allumage. Régler le thermostat de façon que l’appareil fonctionne de façon continue.
e) Test for spillage at the dra hood relief opening aer 5
minutes of main burner operation. Use the ame of a match
or candle, or smoke from a cigaree, cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min ensuite,
déterminer si le coupe-tirage déborde à l’ouverture de décharge.
Utiliser la amme d’une allunee ou d’une chandelle ou la fumée
d’une cigaree, d’un cigare ou d’une pipe.
f) Aer it has been determined that each appliance remaining
connected to the common venting system properly vents when
tested as outlined above, return doors, windows, exhaust fans,
replace dampers and any other gas-burning appliance to their
previous condition of use.
Une fois qu’il a été d éterminé, selon la métode indiquée ci-dessus,
que chaque appareil raccordé au système d’évacuation est mis à l’air
libre de façor adéquate. Remere les portes et les fenêtres, les ventilateurs,
les registres de cheminées et les appareils au gaz à leur position originale.
g) Any improper operation of the common venting system should be
corrected so the installation conforms with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54. When resizing any portion of the
common venting system, the common venting system should be
resized to approach the minimum size as determined using the
appropriate tables in Appendix F in the National Fuel Gas Code,
ANSI Z223.1/ NFPA 54 and or CAN/CGA B149 Installation Codes.
Tout mauvais fonctionnement du systéme d’évacu-tion commun
devrait étré corrigé de façor que l’installation soit conforme au
National Fue Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes
d’installation CAN/CGA-B149. Si la grosseur d’une section du
système d’ évacuation doit étré modiée, le système devrait étré
modié pour respecter les valeurs minimales des tableaux pertinents
de l’appendice F du National Fuel Gas Code, ANSI Z223.1/ NFPA
54 et (ou) des codes d’installation CAN/CGA-B149.
GENERAL PIPING REQUIREMENTS
Improper piping of this boiler/water heater will void the
manufacturer’s warranty and can cause boiler failure
resulting in ooding and extensive property damage!
Excessive water hardness causing scaling in the copper heat
exchanger tubes is NOT covered under the manufacturer’s
warranty, see Table 9. Excessive piing and erosion of the
internal surface of the copper heat exchanger tubes is NOT
covered under the manufacturer’s warranty if the result of
high water ow rates, see Table 8. Return water temperatures
below 125°F, 52°C will result in heat exchanger damage
from excessive condensation voiding the manufacturer’s
warranty, see Primary/Secondary Piping, Figure 13.
Page 13
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 12 Futera III Piping
Shut o valves and unions should be installed at the
inlet and outlet connections of the boiler/hot water
heater to provide for isolation of the unit should
servicing be necessary.
Freeze Protection
Installations in areas where the danger of freezing exists are not
recommended unless proper freeze protection is provided. e
following precautions MUST be observed:
1. A continuous ow of water through the unit MUST be maintained! e pump responsible for ow through the boiler/water
heater must run continuously!
2. An ethylene glycol/water mixture suitable for the minimum
temperature that the unit will be exposed to must be used. e
pump must be capable of producing a minimum of 15% more
ow and overcoming a 20% increase in head loss. Domestic
water systems must be isolated from the water heater by the
use of a heat exchanger or other approved method.
3. If the unit must be shut o for any reason the electric, gas and
water supplies MUST be shut o and the unit and its pump
completely drained.
Improper outdoor installation of this unit can cause
boiler failure voiding the manufacturer’s warranty!
Valve
Pipe the discharge of the pressure relief valve as shown in Figure 12.
Flow Switch
e ow switch supplied with the boiler/water heater must be wired to
the terminal strip in the control panel to prevent the boiler from ring
unless there’s adequate water ow through the unit. e ow switch must
be installed in the supply piping adjacent to the boiler outlet connection.
Failure to properly install the ow switch may result
in damage to the boiler/water heater heat exchanger
voiding the warranty!
HEATING SYSTEM PIPING
General Piping Requirements
All heating system piping must be installed by a qualied technician in
accordance with the latest revision of the ANSI/ASME Boiler and
Pressure Vessel Code, Section IV, and ANSI/ASME CSD-1, Standard
for Controls and Safety Devices for Automatically Fired Boilers. All
applicable local codes and ordinances must also be followed. A minimum
clearance of 1 in, 25 mm must be maintained between heating system
pipes and all combustible construction. All heating system piping must
be supported by suitable hangers not the boiler. e thermal expansion
of the system must be considered when supporting the system. A
minimum system pressure of 12 psig, 82.7 kPa must be maintained.
Heating Boiler Piping Connections
e supply and return connections should be sized to suit the system,
see Table 7.
Never install any type of valve between the boiler/
water heater and the relief valve or an explosion causing
extensive property damage, severe personal injury or
death may occur!
Table 7 Supply & Return Pipe Sizing (Flanged)
Model Size Supply Size Return Size
500 thru 1000 2” 2”
1250 thru 2000 2 1/2”2 1/2”
13
Page 14
Finned copper tube gas boilers & water heaters – Boiler Manual
Pump Requirements
is low mass boiler requires a continuous minimum water ow
for proper operation. e system pump must be sized to overcome
the head loss of the boiler and the heating system in order to achieve
the required temperature rise. Table 8 provides the heat exchanger
pressure drop and temperature rise gures. e temperature rise
across the boiler must never exceed 35°F, 19.4°C. e adjustable
pump delay turns the pump on each time the burner res and runs
the pump for 20 to 600 seconds aer the call for heat is satised.
A temperature rise outside of the range listed in Table
8 indicates that the ow rate through the heat exchanger
is incorrect which will damage the heat exchanger
voiding the warranty! e maximum allowable
temperature rise is 35°F, 19.4°C.
Low Water Cutoff
If a boiler is installed above any radiation elements it must be ed
with a low water cuto device.
Refer to the wiring diagram supplied with the boiler/water heater
for proper wiring connections.
Expansion Tank & Air Separator
An expansion tank or other means to control thermal expansion
must be installed in the heating system. An expansion tank must
be installed close to the boiler on the suction side of the pump. An
air scoop and automatic air vent must also be installed to eliminate
air trapped in the system.
e maximum allowable ow rate through a Futera III
boiler is 97 GPM, 6.1 L/s on 500 through 1000 models
and 136 GPM, 8.6 L/s for 1250 through 2000 models.
e Cupro-Nickel heat exchanger allows for 108 GPM,
6.8 L/s on 500 through 1000 models and 151 GPM,
9.5 L/s on 1250 through 2000 models.
Table 8 Temperature Rise Table
∆T = 20°F
Model
Number
500
750
1000
1250
1500
Model
Number
500
750
1000
1250
1500
1750
2000
Model
Number
750
1000
1250
1500
1750101.5
2000
Model
Number
750
1000
1250
1500
1750
2000
Flow RatePres. Drop
GPMFt
43.50.55
65.31.63
87.03.59
108.82.21
130.53.73
∆T = 25°F
Flow RatePres. Drop
GPMFt
34.80.36
52.21.08
69.62.37
87.01.46
104.42.46
121.83.84
139.25.63
∆T = 30°F
Flow RatePres. Drop
GPMFt
43.50.77
58.01.69
72.51.04
87.01.76
116.04.01
∆T = 35°F
Flow RatePres. Drop
GPMFt
37.30.58
49.71.27
74.61.32
87.02.06
99.43.02
2.74
62.10.78
∆T = 11.1°C
Flow RatePres. Drop
L/skPa
2.71.6
4.14.8
5.510.6
6.96.5
8.211.0
∆T = 13.9°C
Flow RatePres. Drop
L/skPa
2.21.1
3.33.2
4.47.0
5.54.3
6.67.3
7.711.3
8.816.6
∆T = 16.7°C
Flow RatePres. Drop
L/skPa
2.72.3
3.75.0
4.63.1
5.55.2
6.48.1
7.311.8
∆T = 19.4°C
Flow RatePres. Drop
L/skPa
2.41.7
3.13.8
3.92.3
4.73.9
5.56.1
6.38.9
14
Primary/Secondary Piping
Boilers connected to heating systems using zone valves, zone pumps, or
systems that have excessive flow rates or return water temperatures less than
125°F, 52°C must be isolated from these systems to protect the boiler.
Variable Water Flows
Figure 13 shows a typical primary/secondary piping system. A
dedicated pump is used to maintain a constant water ow through
the boiler. is secondary pump is sized to overcome the head loss
of the boiler and secondary piping system while supplying the ow
rate required to maintain the desired temperature rise across the
boiler. e primary pump is sized to provide the required ow to
the heating system. e secondary piping connections to the primary
system piping must not be more than 12 in, 305 mm apart to
ensure zero pressure drop in the primary system, see Figure 13.
Low Return Water Temperatures
To prevent the problems associated with condensation of the products
of combustion due to low return water temperatures a primary/secondary
piping system with a bypass conguration must be installed, see Figure
14. e bypass system must be sized the same as the secondary piping.
e primary and secondary pumps should be sized to provide the
required ow through each system. e secondary piping connections
to the primary system piping must not be more than 12 in, 305 mm
apart to ensure zero pressure drop in the primary system, see Figure 14.
Multiple Boiler Systems
Systems using multiple boilers can also be installed using a primary/
secondary manifold system, Figure 15.
Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration system, must be
installed so the chilled medium is piped in parallel with the boiler. Appropriate
valves must be used to prevent the chilled water from entering the boiler.
When a boiler is connected to a heating coil that may be exposed to
refrigerated air from an air handling device, the piping system must be
equipped with ow-control valves or some other automatic means of
preventing gravity circulation of the boiler water during the cooling cycle.
Page 15
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 13 Typical Primary/Secondary Piping System (See Notes)
NOTES:
1. Boiler circuit piping must be sized
large enough to handle maximum
flow through unit.
2. Boiler pump sized to boiler design
flow requirements.
3. All boilers furnished with factory
mounted outlet water temperature
gauge.
4. Boiler pump purging required.
Use terminals supplied.
5. For HeatNet operation, a sensor is
required and installed at a minimum
of 12” from primary loop tee.
Notice: These drawings show suggested
piping configuration and valving.
Check with the local codes and ordinances
for specific requirements.
H-1 Rev 5
Figure 14 Low Temperature Piping with Thermostatic Valve (See Notes and Adjustment Procedures)
NOTES:
1. For pump selection consult factory.
2. Boiler pump sized to boiler and thermostatic
3-way valve design flow requirements.
3. Boiler circuit piping must be sized large enough
to handle maximum flow through unit.
4. All boilers furnished with factory mounted
outlet water temperature gauge.
5. Boiler pump purging required. Use terminals
H-18 Rev 4
supplied.
6. Valve is pre-calibrated for 140oF return temperature.
7. For HeatNet operation a sensor is required and
installed at a minimum of 12” from primary loop tee.
supplied.
Notice: These drawings show suggested piping
configuration and valving.
Check with the local codes and ordinances for specific
requirements.
15
Page 16
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 15 Multiple Boiler Piping (See Notes)
H-15 Rev 6
NOTES:
1. Boiler circuit piping must be sized large enough to handle maximum flow through unit.
2. Boiler pump sized to boiler design flow requirements.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
5. Secondary loop pipe diameter must be sized large enough to handle maximum flow through all units.
6. For HeatNet operation, a sensor is required and installed at a minimum of 12” from primary loop tee.
Notice: Theses drawings show suggested piping configuration and valving.
Check with local codes and ordinances for specific requirements.
16
Page 17
Finned copper tube gas boilers & water heaters – Boiler Manual
DOMESTIC WATER SUPPLY PIPING
Proper controls must be used to prevent water sup-
plied for domestic use from exceeding 130°F, 54°C
or a scald injury will occur! When higher water temperatures are required for appliances such as a dishwasher, a mixing valve or some other tempering means
must be installed. Households with small children may
require water temperatures less than 120°F, 49°C.
Local codes must be complied with!
To properly size the pump a grain hardness and pH test
must be taken at the installation site before the order is placed.
Proper pump sizing will improve heater performance and help
ensure heater longevity.
Expansion Tank
An expansion tank or other means to control thermal expansion
must be installed in the water heating system if back ow prevention devices are installed.
headers. Piping and components connected to the water heater
must be suitable for use with potable water. e water heater must
not be connected to any heating system piping or components
previously used with a non-potable water heating appliance. No
toxic chemicals, such as those used for boiler treatment, are to be
introduced into the potable water used for space heating. If a hot
water storage tank is used in the system it must be equipped with
a temperature and pressure relief valve that complies with ANSI
Z21.22 or CAN-4.4 and CAN-4.6.
e storage tank must be located as close to the water
heater as possible to prevent excessive head loss which
will reduce ow.
Water Chemistry
e required temperature rise across the water heater is based on
water having a hardness between 8 and 18 grains per gallon with
a level of dissolved solids not exceeding 350 ppm. Water having a
hardness less than 8 grains can cause excessive corrosion of the
heat exchanger. Water that has a hardness greater than 18 grains
per gallon and/or a level of dissolved solids exceeding 350 ppm
will require a recalculation of the pump size and temperature rise.
A cupro-nickel heat exchanger may also be required. e manufacturer should be consulted when these water conditions are
encountered. See Table 9.
e maximum allowable ow rate through a Futera III
water heater is 97 GPM, 6.1 L/s on 500 through 1000
models and 136 GPM, 8.9 L/s for 1250 through 2000
models. e cupro-nickel heat exchanger allows for
108 GPM, 6.8 L/s on 500 through 1000 models and
151 GPM, 9.5 L/s on 1250 through 2000 models, see
Table 8B.
RBI water heaters are designed to run scale free. Due to the extreme
variables of water conditions world wide it is necessary to
consider pH values and water hardness in relationship to scaling.
It is crucial to consider these two variables when making heat
exchanger and pump selections. If local water conditions are extreme,
follow the guidelines in the Heat Exchanger Selection (Table 9)
and the Pumping Performance (Table 10). Scale free operation
can be achieved by using water with a hardness between 8 and 18
and by maintaining the pH between 5 and 9. Follow the conditions
listed under NORMAL in the table. In some areas of the country
additional precautions must be observed due to unusual characteristics of the local water supply. Call the nearest RBI representative for details.
Pump Requirements
is low-mass water heater requires a continuous mini-mum water
ow for proper operation. e low water ow switch provided for
this unit will shut down the water heater if ow falls below the
required minimum level. Table 10 provides the heat exchanger pres-
sure drop chart and temperature rise table. e temperature rise acrossthewaterheatermust neverexceed 35°F, 19.4°C.
Cold Water Supply
e cold water supply must be piped to the water heater’s outlet
piping between the water heater and the hot water storage tank.
is will prevent untempered water from entering the water heater,
see the Temperature Rise Control section below. Two typical water
heating systems are shown in Figures 16 & 17.
Temperature Rise Control
Water returned to the water heater inlet must not be less than 125°F,
52°C or excessive condensation of the products of combustion will
damage the water heater voiding the warranty. e method outlined
below can be employed to prevent this condition from occurring.
A balancing valve should be installed on the outlet side of
the water heater for purposes of adjusting the ow rate through
the heat exchanger. ermometers are installed on both the inlet
and outlet of the water heater for determining the temperature rise
through the unit.
e proper velocity through the water heater must be maintained
in accordance with Table 10 for ecient operation and long life.
If the temperature rise through the water heater is lower than
recommended the water velocity is too high. Premature erosion of
the heat exchanger will occur. Conversely, if the temperature rise
is higher than recommended in Table 10 the ow rate is too low.
Scaling and soening of the heat exchanger will occur.
ermostatic Mixing Valve – Water Above 140°F, 60°C Water
can be stored at temperatures above 140°F, 60°C provided that a
thermostatically controlled mixing valve is used to temper the hot
water to an acceptable temperature before it’s supplied for domestic
use.
e mixing valve MUST be set to prevent a scald injury from
occurring, see the caution against scalding.
Storage of water for domestic use above 140°F, 60°C will provide
an increased quantity of tempered water and help prevent the growth
of water born bacteria.
17
Page 18
Finned copper tube gas boilers & water heaters – Boiler Manual
Table 9 Futera III Heat Exchanger Selection Graph
Table 10 Futera III Pumping Performance Requirement
18
Page 19
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 16 Typical Water Heating Piping (MW Models Only)
These drawings show sug-
gested piping configuration
and valving. Check with
local codes and ordinances
Figure 17 Multiple Water Heating Piping (MW Models Only)
for specific requirements.
(See Notes)
NOTES:
1. Optional cold water make up and recirculation line location.
2. When using intermittent pump and pump delay, locate remote HeatNet sensor with well in lower 1/3 of tank. Install sensor with heat sensing compound.
For multiple tanks, self balancing reverse-return systems, a single HeatNet sensor is applied.
3. ermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30 total, 6-90° elbows, full pipe size.
5. CAUTION: MEASURE WATER HARDNESS AND pH AT JOB SITE.
6. e pH and water hardness must be measured before selecting heat exchanger and pump. Consult the Heat Exchanger Graph and Pumping Performance
Table before making selection.
7. Common piping must be sized for maximum combined heater flow.
8. Hot water tanks should be equipped with a combination temperature & pressure relief valve.
9. MA Code requires an 1/8 in hole in check valve to compensate for thermal expansion.
Notice: ese drawings show suggested piping configuration and valving. Check with local codes and ordinances for specific requirements.
19
Page 20
Finned copper tube gas boilers & water heaters – Boiler Manual
GAS SUPPLY PIPING
Check the boiler/water heater rating plate to make
sure that the boiler/water heater is for the type of gas
that will be used. If it isn’t, do not connect the boiler/
water heater to the gas supply. Gas supply piping must
be in accordance with the National Fuel Code, ANSI
Z223.1-latest revision or applicable provisions of the
local building codes. Canadian installations must
comply with CAN/CGA B149.1 or .2 Installation
Code. Failure to comply with this warning can result
in extensive property damage, severe personal injury
or death!
e Futera III comes from the factory ready to be piped to the gas
supply. If for any reason the boiler/water heater is not for the type
of gas available at the installation site, call your RBI representative
to resolve the problem.
A minimum gas supply pressure of 2 in, 51mm, W.C.
natural or propane and maximum 14 in, 356 mm W.C.
natural or propane, must be available at the safety
shuto valve inlet with the unit(s) operating.
Table 11 should be used to ensure that the gas supply piping is
sized properly. If more than one appliance is supplied by the same
supply pipe, the piping must be sized based on the maximum possible
demand. Do not neglect the pressure drop due to pipe ings. Table
11 should be used in conjunction with Table 12 to ensure that the
gas supply piping has the capacity to meet the demand.
Figure 18 depicts the proper way to connect the boiler/water heater
to the gas supply piping. e manual shut-o valve MUST be
installed in the supply piping. It should be installed 5 , 1.5 m
above the oor where required by local codes. Provide a sediment
trap at the boom of the vertical section of the gas supply pipe
upstream of the gas controls.
A ground joint union should be installed between the boiler gas
controls and the supply piping. Each of these items are needed to
ensure long life and ease of servicing. Always use a pipe sealant
that is suitable for use with LP gas.
Table 11 Gas Pipe Capacity
Maximum pipe capacity in ft3/hr based on 0.60 specific gravity gas
at a pressure of 0.5 psig or less and a 0.3" WC pressure drop.
Note: Multiply the gas volume by 0.62 for propane flow capacity in ft3/hr.
Multiply the propane flow capacity by 2500 Btu/ft
the propane Btu/hr capacity for a given pipe size and length.
making gas connections to it. Never over-tighten the
piping entering the gas valve body or gas valve failure
may result!
Figure 18 Gas Supply Piping
20
When applicable, provisions for vent, bleed and gas relief lines must
be made in accordance with the latest revision of ANSI Z223.1/
NFPA 54. e main Dungs gas valve supplied with boiler/water
heater does not require external venting.
Safe lighting and other performance criteria were met with the gas
manifold and control assembly provided on the boiler. All gas
connections MUST be leak tested before puing the boiler into
operation.
Page 21
Finned copper tube gas boilers & water heaters – Boiler Manual
Never use an open ame to test for gas leaks. Always
use an approved leak detection method. Failure to
comply with this warning can cause extensive property
damage, severe personal injury or death!
Refer to the wiring diagram supplied with the boiler/water heater
for proper wiring connections and boiler full load amperage (FLA).
Whenever the gas supply piping is pressure tested the boiler/water
heater gas controls must be protected. If the test pressure is equal
to, or less than 1/2 psig, 3.5 kPa isolate the boiler/water heater
by closing it’s manual shut o valve, see Figure 18. If the test pressure
is greater than, or equal to 1/2 psig, 3.5 kPa, disconnect the boiler/
water heater and its individual shut-o valve.
ELECTRICAL WIRING
Electrical Power Connections
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation! Verify proper operation aer
servicing.
Au moment de l’entretien des commandes, étiquetez
tous les ls avant de les débrancher. Des erreurs de
câblage peuvent entraîner un fonctionnement inadéquat et dangereux. S’assurer que l’appareil fonctionne
adéquatement une fois l’entretirn terminé.
e electrical connections to this boiler/water heater must be made
in accordance with all applicable local codes and the latest revision
of the National Electrical Code, ANSI /NFPA-70. Installation should
also conform with CSA C22.1 Canadian Electrical Code Part I if
installed in Canada.
Install a separate 120 volt 15 amp or 20 amp circuit breaker for the
boiler/water heater and pump, see Table 13. A properly rated shuto switch should be located at the boiler/water heater. e boiler/
water heater must be grounded in accordance with the authority
having jurisdiction, or if none, the latest revision of the National
Electrical Code, ANSI/NFPA-70.
Table 13 Futera III Electrical Requirements
Recommended
Futera IIICircuit Breaker*Running
Model(Amps)Amps
500153.9
750 - 1000156.0
1250 - 20002011.4
*Use separate circuit breaker that is properly sized for pump and
pump contactor.
Line voltage eld wiring of any controls or other devices must
conform to the temperature limitation of type TEW wire at 95°F,
35°C above room temperature. Use copper conductors with a
minimum size of #14 awg. Use appropriate wiring materials for
units installed oudoors. e wire size must be compatible with the
total amp draw of the circuit.
GENERAL OPERATION
Before proceeding read and fully understand the
instructions contained in this manual. Do not aempt
to operate this boiler/water heater if it has not been
installed in accordance with the guidelines set forth
in this manual. Failure to comply with this warning
can result in extensive property damage, severe personal injury or death!
Should overheating occur or the gas supply fail to shut o, turn o
the manual gas control valve to the appliance. Do not interrupt
water ow through the boiler/water heater.
En cas de surchaue ou si l’alimentation en gaz ne s’arrête pas, fermez
manuellement le robinet d’arrêt de l’admission de gaz.
Hydronic Heating Boilers
Open the make-up water valve and slowly ll the boiler and all of
the radiation with water. Ensure that all bleed and drain valves are
closed.
Adjust the make-up water pressure regulator so a minimum12 psig,
82.7 kPa system pressure is maintained at the highest point in the
system piping. If a make-up water pump is used adjust it to maintain
a minimum 12 psig, 82.7 kPa system pressure.
Open the system bleed and drain valves, one at a time, to purge
the air trapped in the heating system piping.
With the boiler o, run the system pump for at least 30 minutes
and bleed the system piping using the bleed valves. If strainers are
used in the system piping, the make- up water valve should be closed
and the strainers checked and cleaned.
e system expansion tank should be checked to ensure that the
correct water level in the tank is maintained. e tank should be
less than half full of water with the system full and adjusted to the
correct operating pressure.
Start the boiler as described in the “OPETING INSTRUCTIONS”
section. Run the boiler for at least an hour. e system pump(s)
and all radiation units must be operated during this time. Ensure
that the make-up water valve is open.
Shut the boiler o and open the bleed valves to purge the air trapped
in the heating system piping. Close the make-up water valve and
check and clean the strainers and make-up water pressure reducing
valve.
Open the make-up water valve and adjust the system pressure if
necessary. e system should be checked and bled aer three days
of operation.
21
Page 22
Finned copper tube gas boilers & water heaters – Boiler Manual
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING.
POUR VOTRE SÉCURITÉ LISEZ AVANT DE
METTRE EN MARCHE
A. is appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot by
hand.
Cet appareil est muni d’un dispositif d’allumage qui allume
automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse
manuellement.
B. BEFORE OPETING smell all around the appliance area for
gas. Be sure to smell next to the oor because some gas is heavier
than air and will sele on the oor.
Propane gas may not always be detected by smell.
Propane gas is heavier than air and can collect in low
areas.
Propane gas can ignite or explode if an ignition source
is present and result in death, serious injury and
property damage!
maintain this appliance and your gas system in accordance with
all applicable codes.
• Ifyoususpectaleak:
1. Have everyone leave the building immediately.
2. Do not aempt to light any appliance.
3. Do not touch any electrical or electronic switches in the
building.
4. Do not use any phone in the building.
5. Call your gas supplier from a phone outside of the building.
6. If you cannot reach your gas supplier call the re department.
AVANT DE FAIRE FONCTIONNER, reniez tout autour de
l’appareil pour déceler une odeur de gaz. Reniez près du
plancher, car certains gaz sont plus lourds que l’air et peuvent
s’accumuler au niveau du sol.
C. Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect the
appliance and to replace any part of the control system and any
gas control that has been under water.
N’utilisez pas cet appareil s’il a été plongé dans l’eau, même
partiellement. Faites inspecter l’appareil par un tecnicien qualié
et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
Operating Instructions
1. STOP! Read the safety information above. If, at any time, the
appliance will not operate properly, follow the instructions “TO
TURN OFF GAS TO APPLIANCE” and call your service
technician or gas supplier.
2. Set the operating control to o and disable any outside (BMS)
call for heat.
3. Turn o all electric power to the appliance.
4. Close main isolation gas valve (eld supplied), Figure 18.
5. Purge the gas piping up to the manual valve ahead of the main
gas control of air. When the bleeding is complete, check all gas
joints up to the gas valve for leaks.
6. Wait ve (5) minutes to clear out any gas.
7. Install a ing at the supply test port and connect a manometer
having a minimum range of 20 in, 508 mm WC to it, Figure
18.
8. Remove the 1/8" pipe plug from the pilot test port located on
the CV100 pilot/reg combination gas valve and connect a
manometer having a minimum range of 6 in, 154 mm WC to
it, Figure 20.
9. Open the main isolation gas valve (eld supplied), Figure 18.
10. Place the “Remote/Local” switch to Remote inside control
cabinet, Figure 19.
11. Turn the power switch on the front of the boiler to “on”. It will
light up when the power is on. If all interlocks are properly
closed, the display will say “Standby”, Figure 19.
12. Slide the Low Fire Hold Switch (on HeatNet control board)
to Low Fire position.
13. e boiler will begin the start sequence.
14. When the main display reads “PILOT RUNNING” and the
ame current is 5 VDC, switch the Honeywell 7800 to the “test”
position, Figure 19. is will hold the Honeywell 7800 in its
ignition state.
15. Adjust the pilot pressure per the CHECKING, ADJUSTMENT
& OPETION section.
16. Remove the demand from the 7800 control by disabling the
Low Fire switch allowing the boiler to stop.
17. Close main isolation gas valve (eld supplied), Figure 18.
18. Remove the manometer ing from the pilot test port and
replace the plug. Place monitor tube on to the test port tee
located along the1/8" hose piped directly o of the manifold
test port, Figure 20.
19. Switch the Honeywell 7800 back to “run”.
20. Create a min input demand as before (enable Low Fire Hold
switch.) e boiler will begin the start sequence.
22
Page 23
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 19 HeatNet Control Panel
Table 16 Elbow Pressure signal (Nat Gas) - Category I
Firing
rate
100%
85%*-3.1-7.1-3.2-3.8-6.2-6.8
To determine signal in mm wc, multiply signal pressure by 25.4.
* Maximum turndown on units listed as CAT I
Table 16a Elbow Pressure signal (Nat Gas) - Category II and IV
50075010001250150017502000
Signal
Inches
%
wc
N/A
Signal
Inches
Signal
Inches
wc
-4.4 -8.2-3.7-5.8-7.3-8.5
wc
Signal
Inches
wc
Signal
Inches
wc
Signal
Inches
wc
Signal
Inches
wc
21. Monitor the ame current on the 7800. No ame current should
be detected and the 7800 should lock out. If ame current is
detected at any time up to the 7800 locking out, the 120V wiring
on the ignition transformer must be reversed and the test run
again to insure that no ame is detected.
Improper wiring of the ignition transformer can result
in an explosion causing extensive property damage,
severe personal injury or death!
22. Open main isolation gas valve (eld supplied).
23. Reset the Honeywell 7800. e boiler will start and will run
at minimum input rate.
24. Seingthe lowre: Allow the low re to sele out for a few
minutes and observe the combustion reading. Refer to “Combustion
Reading” tables 14 and 15 for proper combustion readings and
table 16 and 16a for proper elbow pressure signal at low re.
Table 14 Combustion Readings (Category I)
Natural Fuel Propane Fuel
CO
%
2
O
%
2
For factory set gas manifold (elbow) pressures see label on
inner cabinet door.
Table 15 Combustion Readings (Category II and IV)
CO
%
2
O
%
2
For factory set gas manifold (elbow) pressures see label on
inner cabinet door.
8.0 - 8.2 (min.)9.4 - 9.6 (min.)
8.2 - 8.5 (100%)9.6 - 9.9 (100%)
6.6 - 6.2 (min.)6.6 - 6.2 (min.)
6.2 - 5.8 (100%)6.2 - 5.8 (100%)
Natural Fuel Propane Fuel
8.0 - 8.5 (min.)9.4 - 9.9 (min.)
8.8 - 9.8 (100%)10.3 - 11.5 (100%)
6.6 - 5.8 (min.)6.6 - 5.8 (min.)
5.2 - 3.5 (100%)5.2 - 3.5 (100%)
Firing
rate
100%-2.2-4.5-7.1-4.3-6.0-8.5-8.7
33%-0.5-0.6-0.7-0.6-0.8-1.0-1.0
25%-0.2-0.3-0.5-0.3-0.5-0.6-0.6
To determine signal in mm wc, multiply signal pressure by 25.4.
50075010001250150017502000
Signal
Inches
%
wc
Signal
Inches
wc
Signal
Inches
wc
Signal
Inches
wc
Signal
Inches
wc
Signal
Inches
wc
Signal
Inches
wc
Correctly identif y the type of vent system the appliance
requires before proceeding. Category identication is
noted on the unit rating plate.
e low re O2-CO2 can be adjusted in the eld by opening the
low re adjustment door located on the forward facing side of the
main gas valve, see Figure 20. Inserting an allen wrench and rotating
the allen screw clock-wise will increase the CO
rotating counter clock-wise will decrease the CO2 and increase the
and lower the O2,
2
O2. DO NOT LEAVE THE BURNER IN AN INFRED STATE. A few random speckles of red are ne, but large
concentrations of spots or large areas of red are not. If large amounts
of red concentrations are observed, verify combustion readings.
25. Jumper the “AA” terminals located on the HeatNet control board. The
boiler input will rise to its maximum input, “Run 100%”, see Figure 22.
26. Allow the boiler to reach steady state and verify supply gas
pressure and check input rates as explained in the “Gas Supply
Piping” section. Also, refer to “Combustion Reading” tables 14
and 15 for proper combustion readings, and table 16 and 16a
for proper elbow pressure signal at high re. e high ve trim
is located on the outlet ange of the gas valve, see Figure 20.
O2-CO
can be adjusted by inserting a screw driver and rotating
2
clockwise to increase the CO2 and lower the O2 . Rotating
counterclockwise will decrease the CO2 and increase the O2.
27. Remove jumper “AA” and allow boiler to sele into minimum
input. Observe the combustion readings and make any nal
adjustments. When nished disable the Low Fire Hold Switch
and replace test ports to normal state.
28. Boiler allows for many modes of operation and control methods.
Reference the “HeatNet Control Manual”.
23
Page 24
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 20
INSTRUCTIONS DE MISE EN MARCHE
1. ARRÊTEZ! Lisez les instructions de sécurité sur la portion
supérieure de cee étiquee.
2. Réglez le thermostat à la température la plus basse..
3. Coupez l’alimentation électrique de l’appareil.
4. Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse
manuellement.
5. Fermer la vanne manuelle d’arrêt d’alimintation de gaz.
6. Aendre cinq (5) minutes pour laisser échapper tout le gaz.
Reniez tout autour de l’appareil, y compris près du plancher,
pour déceler une odeur de gaz. Si vous sentez une odeur de
gaz, ARRÊTEZ! Passez à l’étape B des instructions de sécurité
sur la portion supérieure de cee étiquee. S’il n’y a pas d’odeur
de gaz, passez à l’étape suivante.
7. Ouver la vanne manuelle d’arrêt d’alimintation de gaz.
8. Meez l’appareil sous tension.
9. Réglez le thermostat à la température désirée.
10. Si l’appareil ne se met pas en marche, suivez les instructions
intitulées couper l’admission de gaz de l’appareil et appelez un
technicien qualié ou le fournisseur de gaz.
TO TURN OFF GAS TO APPLIANCE
1. Set the operating control to its lowest seing.
2. Turn o all electric power to the boiler if service is to be
performed.
3. Close the manual main and pilot gas shut-o valves.
COMMENT COUPER L’ADMISSION DE GAZ DE
L’APAREIL
1. Réglez le thermostat à la température la plus basse.
2. Coupez l’alimentation électrique de l’appareil s’il faut procéder
à l’entretien.
3. Fermer la vanne manuelle d’arrêt d’alimintation de gaz.
SEQUENCE OF OPERATION
NO DEMAND
Standby
1. e boiler is idle with no interlocks in the fault condition.
DEMAND
Pre-Purge
1. e blower operates at purge RPM. e water ow interlock
must ‘make’ within 15 seconds aer the demand signal is
initiated.
2. e Honeywell 7800 starts a 10 second purge delay once the
air prove switch contacts close.
Pilot Run - % Input
1. e blower operates at minimum ignition seing. See the
calibration section in the “HeatNet Control-IOM” to enter the
calibration menus.
2. e ignition transformer is energized. e pilot solenoid valve
opens for the 10 second pilot ignition trial.
Main Run % Input
1. e main gas valve opens.
2. e ignition transformer is de-energized.
3. e pilot solenoid valve closes.
4. e blower stays at the minimum input seing for 3 seconds
then operates at demand % input. See the calibration section
in the “HeatNet Control-IOM” to enter the calibration menus.
NO DEMAND
Post-Purge
1. e main gas valve closes.
2. e blower operates at purge RPM for 10 seconds.
3. e boiler is idle with no interlocks in the fault condition.
24
Page 25
Finned copper tube gas boilers & water heaters – Boiler Manual
CHECKING & ADJUSTMENTS
Spark Gap
With the main and pilot gas manual valves in the closed position
energize the unit. Observe the trial for ignition to conrm that the
spark is strong and continuous. If not check and adjust the spark
gap as shown in Figure 21.
Figure 21 Spark Gap
Pilot Adjustment
e pilot pressure has been factory set at 3 in. W.C. for natural and
LP gas and shouldn’t need adjustment. To check the pilot pressure
close the manual main shut-o valve 2 and the pilot gas shut-o
valve, Figure 18. Remove the 1/8" pipe plug from the pilot tee and
connect a manometer having a minimum range of 6 in, 152 mm
WC to it. Open the pilot gas shut-o valve. With the unit powered,
generate a call for heat. When the prepurge is complete the ignition/
pilot trial will begin. At this point put the Honeywell RM7800 test
switch in the test position. e control will hold in the ignition/
pilot sequence allowing you to check the pressure.
Measure pressure when the boiler is ring at full rate. Low
gas pressure could indicate undersized gas line or insucient gas
supply.
“Static and operating gas pressure required at the gas valve inlet is
between 2" W.C. and 14" W.C. for natural gas and 2" W.C. and
14" W.C. propane. If the gas pressure is above this limit, a lock-up
style regulator suitable for dead end service such as an Equimeter
or Fisher must be installed to prevent increase (creep) of gas
pressure when the units are not operating. is pressure regulator
(supplied by others) may be installed at the service entrance to
each unit or a “master” regulator sized to handle multiple units may
be utilized. Consult local gas utility or regulator manufacturer for
recommendations to meet specic job site requirements.”
Input Rate, Natural Gas
Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 2000 , 610 m. At elevations
above 2000 , 610 m input ratings should be reduced by 4% for
each 1000 , 305 m.
Check the input rate as follows:
1. Turn o all other gas appliances that use the same gas meter
as the boiler/water heater.
2. Call your gas supplier and ask for the heating value of the gas.
3. Start the boiler/water heater and let it run for 15 minutes.
4. Using the gas meter and a stopwatch, clock the time that it takes
to burn 10 3, 0.28 m3 of gas and divide this time by 10.
5. Insert the heating value and the time, in seconds, into the formula
below.
7. If the computed rate deviates by more than 5% from the rated
input value of the unit, consult factory.
Never increase the input to the boiler/water heater
above that for which it is rated. Doing so can cause
premature failure of the boiler!
25
Page 26
Finned copper tube gas boilers & water heaters – Boiler Manual
RBI FIELD WIRING TO HEATNET BOARD
Figure 22 RBI Field Wiring to HeatNet Board (Board Revision 3.0 and greater)
26
Page 27
Finned copper tube gas boilers & water heaters – Boiler Manual
Figure 23
RBI HEATNET FIELD WIRING TO TERMINAL BLOCK
NOTES:
1. Remove jumper “A” when using a low water
cutoff interlock.
2. For multiple boilers utilizing a system air damper
when in a master/member configuration consult
factory or reference wiring diagram 42-0501
sheet 3 for wiring connections.
3. For single boilers or multiple boilers with
individual dampers connect the end proving
switch to main terminal block 15 and 16.
Terminals 17 and 18 provide 120V power to the
damper motor.
4. There are two methods in which a 4-20mA
signal can be used to control HeatNet equipped
boilers.
Method 1
A 4-20mA signal can be used to directly
modulate each boiler from a remote panel or
building management system. On multiple
boiler installations, there is no communication
between boilers, no HeatNet system sensor;
therefore no master/member relationship exists.
(Use Menu: Setup: Setpoints: Setpoint Source:
Auto)
Method 2
A 4-20mA signal can be used to change
the setpoint temperature the HeatNet is
maintaining. This can be used on single
or multiple boilers with a master/member
relationship. (Use Menu: Setup: Setpoints:
Setpoint Source: 4-20, then set the parameters
for the temperature and boiler start point.)
5. The ‘local’ pump relay in the control panel is
rated for 1 hp, 1Ø motors. For larger or 3Ø
reference factory wiring diagram.
27
Page 28
Finned copper tube gas boilers & water heaters – Boiler Manual
CONTROL DESCRIPTION
Low Water Cutoff
If the boiler is to be installed above radiation or if required by other
codes or regulations, install a low water cuto in appropriate piping.
Wire the switch to the “Interlock” contacts as illustrated on “Field
Wiring” schematic. Ensure that the low water cuto device(s) will
funtion properly.
Operating Control
e preferred control seing for potable hot water is 130°F, 54°C.
e operating control should be set to the lowest seing that will
satisfy the consumer’s needs.
Seing the thermostat or operation control too high
can result in scalding resulting in severe personal injury!
STATUS SCREEN FAULT DISPLAY
ere are numerous interlock switches and soware limits that are
detected. Each of these, when tripped will produce a display message,
an audible beeping, and an alarm relay closure. e fault is displayed
rst, then aer a second, the time the fault occurred is displayed.
is cycle will keep occurring until the fault is cleared. ese faults
are:
HIGH LIMIT: When the high limit aquastat trips the following
message is displayed:
FAULT
SYSTEM SET
HIGH LIMIT
160˚F
High Limit (Aquastat)
e high limit is located in the top control area of the boiler/water
heater. A remote capillary bulb is run to a well on the outlet side
of the supply header. e high limit can be reset by depressing
the red buon.
e water heater high limit should be set a minimum of 20°F,
11°C higher than the operating control. Refer to the HOT WATER
SUPPLY section for the proper supply water temperature.
Flow Switch
A ow switch is provided in the water outlet piping to prevent the
boiler/water heater from ring without adequate water ow through
the heat exchanger.
DIAGNOSTICS
e Futera III has a display that indicates the sequence of
operation. e display will also list faults should the unit fail
to operate. An explanation of each status message and fault
can be located in HeatNet Control Manual under status screen
fault display section.
FAULT
SYSTEM SET
10/27 9:16
160˚F
e high limit interlock breaks power to the ignition control
(shuing it o) and eectively removes any chance of the gas valve
receiving power. e FIII series control will remain powered to
display the fault, latch the alarm relay/audible beeper, and to access
the log. e interlock is located on J5, HIGH LIMIT.
INTERLOCK SPARE 3: is is a reserved interlock input that is
normally jumpered at the factory, but can have a remote interlock
connected as a eld install. e interlock is located on J11A, SPARE 3.
FAULT
SYSTEM SET
INTERLOCK SPARE 3
160˚F
28
LOW WATER CUTOFF: If there is a low water condition reported
by the low water cuto switch this fault is displayed. Check that
there is water ow and water in the boiler. ere is a reset switch
located on the LWCO box. e interlock connection is located
on J11A, LWCO.
FAULT
SYSTEM SET
LOW WATER CUTOFF
160˚F
Page 29
Finned copper tube gas boilers & water heaters – Boiler Manual
VAR FREQ DRIVE: e variable frequency drive, which controls
the blower, reports this fault in the event of over current or other
conditions that would cause it to shut down. If this is the case, check
the fault indicators on the VFD. e interlock is located on J11A, VFD.
FAULT
VAR FREQ DRIVE
SYSTEM SET
160˚F
GAS PRESSURE: e optional gas pressure switches (high pressure
and low pressure) are connected in series, so if either trip, a fault
will be reported here. A reset switch is located on the gas pressure
switches. e interlock is located on J11A, GAS PR.
FAULT
GAS PRESSURE
SYSTEM SET
160˚F
FLOW SWITCH ERROR: Once the FIII series boiler receives a
call for heat, it closes the circulator pump relay. It then waits 10
seconds to prove ow. If there is no ow, the ow switch alarm will
be set. Every 10 seconds the circulator pump relay will cycle ON
for 10 seconds and then OFF for 10 seconds to try and establish
ow. e interlock connection is located on J11B, WTR FLW.
FAULT
WATER FLOW SWITCH
SYSTEM SET
160˚F
IGNITION CTRL ALARM: e ignition control alarm is displayed
if the ignition control detects a fault. is could be a ame failure,
air proving switch, or other fault associated with the ignition control. When this fault occurs, you will need to refer to the ignition
control for the reason.
FAULT
IGNITION CTRL ALARM
SYSTEM SET
INTERLOCK SPARE 4: is is also a spare interlock (similar to
INTERLOCK SPARE 3) for future expansion or use as a eld
interlock. e interlock is located on J11B, SPARE 4.
FAULT
INTERLOCK SPARE 4
SYSTEM SET
160˚F
160˚F
IRI ALARM: e optional IRI alarm is the alarm from the gas valve.
If this alarm is set check the gas valve.
FAULT
IRI ALARM
SYSTEM SET
160˚F
29
Page 30
Finned copper tube gas boilers & water heaters – Boiler Manual
COMBUST AIR DAMPER: If the combustion air damper has been
selected for use (MASTER BOILER, AUX FUNCTIONS), and
the proof switch does not make, this fault will be displayed.
When the combustion air damper is used, the master’s BOILER3/
DAMPER relay contacts at J13 are closed. ese should be wired
to the combustion air damper or preferably an isolation relay. e
prove switch on the combustion air damper must be wired to J10B,
SPARE 1.
SHORTED ***** SENSOR: If the shorted sensor fault is
displayed, the sensor in the position reported was originally detected,
but has since shorted. e boiler will shut down on any SHORTED
sensor.
FAULT
SYSTEM SET
SHORTED OUTSIDE SENSOR
FAULT
SYSTEM SET
COMBUSTION AIR DAMPER
160˚F
When the master boiler receives a call for heat and needs to start
a boiler, the BOILER3/DAMPER relay K5 closes. At the same
time, the boiler is started, res, and continues to re. If the
combustion air damper does not prove within the proof time
specied in the combustion air damper menu, the boiler will shut
down and display the fault. e fault on the Master boiler can be
cleared by removing the call for heat on the master boiler and xing
the combustion air damper problem. A combustion damper fault
on a Member boiler can only be cleared by power cycling.
e Master boiler controls a system damper and Member boilers
control their own respective dampers. When the call for heat is
removed, the damper will remain open for 30 seconds before closing.
is allows for post purge cycles to complete.
OPEN ***** SENSOR: If the open sensor fault is displayed, the
sensor in the position reported was originally detected, but has since
opened. e boiler will shut down on any OPEN sensor.
160˚F
DELTA TEMP > 40°F: If the temperature across the heat
exchanger rises above the maximum designated temperature for
the FIII model boiler, a warning or fault will be displayed. is
protection is required to prevent damage to the heat exchanger in
the event high dierential temperatures are encountered. e fault
or warning condition may be changed in the AUX FUNCTIONS
menu under ALARM TYPE. e default condition is WARNING
with LIM->HALF TE = YES.
When this condition exists and the ALARM TYPE is set to
WARNING and LIM-> HALF TE, the boiler is limited to 1/2
it’s input rate. So, if the boiler is trying to re at 80%, the rate is
limited to 40% until the temperature across the heat exchanger falls
at least 10°F below the maximum designated temperature for the
FIII boiler model. In this case: 40°F - 10°F = 30°F.
If the ALARM TYPE is set to FAULT, the boiler will display the
FAULT message and this condition will be treated as an interlock,
thus shuing down the boiler until the Delta Temp drops 10°F
below the maximum designated temperature.
1/2 INPUT
DELTA TEMP > 40°F
LOCAL SET
FAULT
SYSTEM SET
OPEN OUTSIDE SENSOR
160˚F
30
41˚F
RETURN TEMP < 130°F: If the Return Inlet temperature is
less than 130°F this warning will be displayed. is warning does
not aect operation and does not set the alarm relay. A log entry is
made to aide in diagnosing why this may be occuring. Condensing
will occur with return temperatures below 130°F and a shortened
heat exchanger life will occur.
PREPURGE
LOCAL SET
RETURN TEMP < 130°F
41˚F
Page 31
Finned copper tube gas boilers & water heaters – Boiler Manual
MAINTENANCE
Disconnect electrical power and close the manual gas
shut o valve before performing maintenance or severe
personal injury may result!
6. If there are no signs of damage, sooting or corrosion, reassemble
the unit following the previous steps in reverse order.
7. A badly corroded or damaged heat exchanger must be replaced,
see the Heat Exchanger Repair & Replacement section.
Servicing, inspection and adjustment must be done
by a trained technician in accordance with all applicable local and national codes. Improper servicing or
adjustment can damage the boiler/water heater!
e boiler/water heater must be cleaned and inspected at least once
a year and before each heating season. Make sure that the burner
and ignition components are free from dust, soot, dirt, corrosion
or other deposits that would impair the boiler/water heater’s
performance. Refer to Figure 25 for component identication.
Improper burner servicing can result in premature
burner failure voiding the warranty!
Burner Removal
1. Close the manual shuto valves in the gas supply line and turn
o electrical power to the boiler/water heater.
2. Remove the jacket top panel.
3. Disconnect the wires to the fan and remove the four bolts that
secure the fan to the transition piece.
4. Remove wires from the spark rods and remove the UV sense
from the transition piece.
5. Disconnect the compression nut at the back of the transition
piece to remove pilot gas tubing.
6. Remove the four nuts holding the transition piece to the heat
exchanger.
7. Li and remove the transition piece and burner together from
the boiler/water heater, taking care not to damage the spark
rods and or their alignment.
8. Disconnect the compression nut from the inside of the transition
piece.
9. Remove the transition piece, taking care not to damage the
spark rods and or their alignment.
Heat Exchanger Inspection
1. Close the manual shuto valves in the gas supply lines and turn
o electrical power to the boiler/water heater.
2. Remove burner following the instructions in the Burner Removal section.
3. Remove the front jacket panel and combustion chamber door.
4. Inspect the inside and outside of the heat exchanger for signs
of damage, sooting or corrosion.
5. e outside surfaces of the copper tubes should be free of any
soot deposits. A slight black smudge is normal with some types
of gases. Black soot indicates poor combustion. Green deposits
indicate condensation due to low return water temperatures. In
either case the heat exchanger must be cleaned thoroughly and
the problem resolved before the boiler/water heater is returned
to service.
Heat Exchanger Cleaning
1. Close the shut o valves in the inlet and outlet piping. On heating systems close the system ll valve and relieve the system
pressure from the boiler by carefully liing the relief valve or
opening the drain valve.
2. Disconnect the boiler/water heater from the system piping.
3. Remove the eight bolts on the rear pipe enclosure panel.
4. Remove the front jacket panel and combustion chamber door.
5. Slide the heat exchanger out of the unit.
6. Remove the “V” bae straps and “V” baes.
7. oroughly clean the heat exchanger with water from
a high-pressure hose. Use a so bristle brush if necessary.
8. Replace the cleaned heat exchanger and other components in
the reverse order of their removal.
Heat Exchanger Repair & Replacement
1. A leaking or otherwise damaged tube(s) can be replaced as
outlined in steps 2 through 8.
2. Remove the heat exchanger from the boiler/water heater as
outlined in the Heat Exchanger Cleaning section.
3. Remove the pipe plugs from the inlet/outlet and return headers
opposite from the ends of the tube(s) being replaced.
4. Carefully cut the damaged tube(s) in half, taking care not to
damage the adjacent tubes and remove.
5. Install and swage/expand in place the new tube(s).
6. Replace the pipe plugs using a suitable thread sealant on each
one.
7. Sagging or distorted heat exchanger tubes are an indication of
low water ow through the system. A damaged heat exchanger
must be replaced and the condition that caused the damage
resolved before the boiler/water heater is returned to service.
8. Replace the heat exchanger and other components in the reverse
order of their removal.
9. e recommended torque value for the heat exchanger plugs
is approximately 45 . lbs, not to exceed 50 . lbs.
Air Intake & Vent System
oroughly inspect the air intake and vent systems for any
signs of blockage, corrosion or leakage. Immediately replace any
unsound vent system piping. Inspect the air lter and wash with
warm water and soap if dirty.
31
Page 32
Finned copper tube gas boilers & water heaters – Boiler Manual
Controls
Use the “GENEL OPETION” and “CHECKING AND ADJUSTMENTS” sections of this manual for reference.
1. Check the operating controls for proper operation.
2. A oat type low water cuto device must be ushed out per
the manufacturers’ instructions. e probe on a probe low water
cut o must be removed, cleaned and inspected at least once
a year. Ensure that the low water cutos operate properly. If not,
replace them.
3. e ow switch contacts must be open when water ow is not
present.
4. e relief valve should not weep or discharge water at normal
system pressure. If it does, contact a qualied service technician
to have it inspected. NEVER try to clean or repair the relief
valve! If the valve fails to operate properly, have it replaced!
5. e aquastat high limit controls the maximum water temperature
in the boiler. If the water temperature reaches the set temperature
before the demand for heat has been met, the aquastat high
limit should shut the boiler o. e water temperature should
never exceed the maximum set point of 250°F, 121°C, for
boilers and 210°F, 99°C for water heaters. e aquastat high
limit cannot be repaired. If it fails to function properly, replace
it.
6. Visually check the pilot and main burner ames to ensure proper
operation, see Figure 24.
A yellow, oating ame indicates a lack of combustion
air. Do not operate the boiler/water heater until the
problem is solved or severe personal injury or death
may occur!
Figure 24 Main Burner Flame
32
Page 33
Finned copper tube gas boilers & water heaters – Boiler Manual
Troubleshooting A Startup
ActionCheckIdentify SourceSymptom
An Interlock is tripped.
1.1. Is it a 24 VA C Interlock?
2. Is it a 120 VA C Interlock/
Alarm?
3. Internal Alarms
1. All 24 VA C Interlocks are
located on J11A and J11B.
Examples of 24 VA C Interlocks:
1.SPARE3
2. Variable Frequency Drive(VFD)
3. Low Water Cutoff(LWCO),
4. Gas Pressure
5. Spare 4
6. Operator OPLIM
7. Water Flow
8. Air Pressure from UV Sensor.
2. All 120 VA C interlocks/Alarms
are located on J5. These include:
1.FLAME SAFE ALARM (Ignition
CTRL ALARM)
2. Valve Alarm (IRI ALARM)
3. XS_FACTORY (Reserved
4. HIGH LIMIT
1. OPEN SENSOR
2. SHORTED SENSOR
3. COMBUSTION AIR DAMPER
1.Use a multimeter and check
for 24 VA C on J11A,J11B to
identify which interlock has
tripped. Reset the Interlock or
check for disconnected wiring
or shorts.
The Air Pressure from UV
Sensor interlock if displayed
will allow the boiler to
function, but it needs to be
functional while the boiler is
running for it to clear.
1. Use a multimeter on J5 to
to check for 120 VA C on
these interlocks (except the
HIGH LIMIT). The High Limit
Interlock is displayed when
there is no 120 VA C, since
the HIGH LIMIT breaks the
120VA C to the Ignition
Control.
NOTE: Stray Voltages
Greater than 8 VA C and less
than 18 VA C on these
interlocks can cause
intermittant operation. If this
is the case, check for back
fed voltages from field wiring.
Check sensor voltages at
J10A and J10B. The
Temperature sensor inputs
should be between 0 VDC
and 5 VDC measured across
the sensor. Example: At 77 °F,
the voltage would read 2.5
VDC.
2.
Proceed to HeatNet
Control Manual for
more details and
problem resolution.
The combustion air damper
prove switch must be wired
across SPARE 1 and must be
a "DRY" contact. Do not
apply a voltage to this input,
the input supplies it's own
voltage/current.
33
Page 34
Finned copper tube gas boilers & water heaters – Boiler Manual
REPAIR PARTS
Figure 25 Exploded View
34
Page 35
Finned copper tube gas boilers & water heaters – Boiler Manual
REPAIR PARTS (CONTINUED)
RIOM-74 REV E
35
Page 36
Finned copper tube gas boilers & water heaters – Boiler Manual
REPAIR PARTS (CONTINUED)
Model Size with Item Quantities Below
Ref # Name of PartPart #50075010001250150017502000
15Burner for Turbo Pilot
15a
Transition Gasket
15b
Burner Gasket
16
Solenoid Valve w/Regulator, NG
Solenoid Valve w/Regulator, LP
17
Flange 1" (Inlet)
Flange 1-1/2" (Inlet)11-021422
18Gas Valve
Test Port (CSD-1)11-03542222222
Flange 1" (Outlet)11-02281111
19
Flange 1-1/2" (Outlet)11-0229111
NSOrifice Gasket 06-00221111111
Gas Injectors NG10-10091111
NS
Gas Injectors NG10-1002111
Gas Injectors LP10-10101111111
20Ball Valve11-03951111111
Firing Valve, 1"11-045611
21
Firing Valve, 1-1/2"11-0458111
“A” Valve, 1"11-046511
22
“A” Valve, 1-1/4"11-0466111
“A” Valve, 1-1/2"11-046711
Blower, Fasco 704370-2348-001111
23
Blower, Fasco 703512-00171111
Flow Switch14-02031111111
25
Flow Switch (Outdoor)14-02051111111
Flow Switch (Potter) 14-02011111111
Flow Switch (Outdoor Potter) 14-02021111111
26Frequency Drive15-0237-0011111111
27Jacket Top Panel
36Combustion Chamber Top Panel
Manning Glass Insulation (per square foot)
70-2529.11
70-2530.11
70-2531.11
70-2532.11
70-2533.11
70-2534.11
70-2535.11
(must order as kit 21-2007)
(must order as kit 21-2008)
(must order as kit 21-2007)
(must order as kit 21-2008)
11-03721111111
11-03741111111
11-023111111
11-02301111
11-0227111
70-2412111
70-24131111
70-2356111
70-23571111
05-01044445555
36
Page 37
Finned copper tube gas boilers & water heaters – Boiler Manual
REPAIR PARTS (CONTINUED)
Model Size with Item Quantities Below
Ref # Name of PartPart #50075010001250150017502000
Individual copper/cupronickel tubes* available for field repair *model and serial number required
Tube Expansion Tool
Heat Exchanger Assembly (Cupronickel)
Cast Iron (prior to 0209 must replace
combustion chamber top panel #36)
Heat Exchanger Assembly (Cupronickel)
Bronze
06-014650505050505050
21-2005111
21-20061111
09-0483111
09-04841111
70-2515.1R1
70-2516.1R1
70-2517.1R1
70-2518.1R1
70-2519.1R1
70-2520.1R1
70-2521.1R1
70-2186.1R1
70-2187.1R1
70-2188.1R1
70-2189.1R1
70-2190.1R1
70-2191.1R1
70-2192.1R1
30-07611111111
70-2522.1R1
70-2523.1R1
70-2524.1R1
70-2525.1R1
70-2526.1R1
70-2527.1R1
70-2528.1R1
70-2193.1R1
70-2194.1R1
70-2195.1R1
70-2196.1R1
70-2197.1R1
70-2198.1R1
70-2199.1R1
37
Page 38
Finned copper tube gas boilers & water heaters – Boiler Manual
REPAIR PARTS (CONTINUED)
Model Size with Item Quantities Below
Ref # Name of PartPart #50075010001250150017502000
NSInlet Adapters (Flanged)
Outlet Adapters (Flanged)
Outlet Adapters (Threaded)
Inlet/Outlet Header Gasket
NSHeat Exchanger “V” Baffle
Heat Exchanger “V” Baffle Strap
High Limit, Jumo, (MB)14-00131111111
48
High Limit, Jumo, (MW)14-00141111111
NSOperator, T6031A (pool heater)14-00031111111
NSHigh Limit Well, 3/8 x 313-01042222222
NS10K Temperature Sensor14-03253333333
50Transformer, 50 VA15-00071111111
51Purge Timer, ST780016-00071111111
52Spark Generator, Q652B16-00361111111
53Flame Safeguard, RM78957C16-0024R1111111
NSKeyboard Display Module, S7800A16-00101111111
54Main Board (HeatNet)16-00471111111
55Display Board (HeatNet)40-00881111111
NSRibbon Cable 40-01151111111
NSPower Switch48-00131111111
NSToggle Switch Remote / Local48-00141111111
56Air Pressure Switch11-04161111111
NSLow Gas Pressure Switch (Manual Reset)11-04221111111
NSHigh Gas Pressure Switch (Manual Reset)11-04111111111
NSHigh Gas Pressure Switch Adapter11-04231111111
NSUV Amplifier, R7849A16-00061111111
NSIgnition Cable44-00631111111
60Transition Assembly (prior to 0209
must upgrade to turbo pilot by
replacing burner, spark rod and
transition assembly)
01-0044GL
01-0045GL
01-0046GL
01-0047GL
01-0042111
01-00431111
03-161220
03-161320
03-161420
03-161528
03-161628
03-161728
03-161828
03-1619222
03-16202222
70-2305111
70-23061111
111
1111
111
1111
(must order as kit 21-2007)
(must order as kit 21-2008)
38
Page 39
Finned copper tube gas boilers & water heaters – Boiler Manual
REPAIR PARTS (CONTINUED)
Model Size with Item Quantities Below
Ref # Name of PartPart #50075010001250150017502000
60aGasket
61Pump Contactor Relay15-01371112222
NSRating Plate82-00541111111
NSFutera III Overlay (HeatNet)82-02001111111
77Keypad Overlay82-01891111111
78Mini Fan12-00211111111
79Air Solenoid Valve11-03761111111
803/8" Aluminum Tubing62-01021111111
Pilot Orifice, .052 NG10-01401111111
81
Pilot Orifice, .040 LP10-01391111111
82Mini Peeper, C7027A16-00091111111
83Spark Plate Gasket
NSSpark Rod Assembly
84Electrode16-0335111111
NSSpark Rod O’ring06-0008111111
861/2" Aluminum Tubing62-0103111111
NSSilicone66-0151111111
NSSilicone Tubing06-0051222222
Vent Termination Hood 5"09-011711
NS
Vent Termination Hood 6"09-011211
Vent Termination Hood 8"09-01131
Vent Termination Hood 10"09-01151
Air Intake Hood 6"09-0102111
NS
Air Intake Hood 8"09-01031
Air Intake Hood 10"09-01041
Air Intake Hood 12"09-01051
06-0102111
06-00371111
70-2566111
70-2567111
(must order as kit 21-2007)
(must order as kit 21-2008)
1
1
1
1
1
2
1
1
39
Page 40
Finned copper tube gas boilers & water heaters – Boiler Manual
START-UP REPORT
:
T
:
:
:
:
ST
T
N
D
D
D
L
V
D
S
R
f
.
.
T
f
.
.
.
.
.
.
J
.
.
.
0.
.
.
dby.
.
DATE
E C HNI C IAN:
MPANY
PH O NE N U MBER
PRE
NO VISIBLE DAMAGE TO UNI
IPING PROPERLY CONNECTE
B O ILER CIRC U LAT O R WIRE
ENT / STACK C O NNECTE
LE
Note: Locate the AA terminals and minimum hold switch in the bottom-right of the electrical panel on the main
HeatNet board. Also locate the manometer test mani
Disable an y external call f or heat and toggle the remote/local switch to REMOTE
.
oggle the LOW FIRE switch to c y cle the boiler then hold at trial
2
et pressure to 3–3.5" w.c. (flame signal should read 5.0 VDC)
3.
Release boiler to main flame trial for ignition
4
heck for stable flame
.
ecord combustion and manifold pressure at minimum firing rate.
um p er the AA terminals to force 100% input
ecord combustion and manifold pressure.
emove the AA j umper to place the boiler at minimum rate
9
ake any final adjustments on low fire.1
heck all combustion results using a calibrated flue gas anal y zer
11
e l ease t h e LOW FIRE switc h to p l ace b oi l er in stan
12
T
HE CK LI
T
E
U
N C E
JOB NAME:
OCATION:
DEL CATEGORY:
ERIAL #
INLET AIR FILTER IN S TALLED AND C LEA
PROPER SERVICE CLEARANCES PROVIDE
UMP RUNNING, HEAT EX C HANGER FUL
GAS LINES PURGED, N O LEAKS, N O MISSING TEST
L U G
old in the bottom o f the electrical panel
or pilot ignition
In addition to completing the Fusion/Futera III start-up report, complete the control set-up information in
the rear of the HeatNet manual.
40
Page 41
Finned copper tube gas boilers & water heaters – Boiler Manual
M
A
YSIS
TE
00%
TE
.
.
O
)
E
C.
ST
S
CH
D
S
B
R
R
H
S
D
D
L
T
R
______________________________________
)
_
DD
S
STI O N
F I N
1
F IN
GAS PRESSURE AT SUPPLY TEST PORTINCHES W.C
C
CO ( PPM
NET S TA C K TEMPERAT U R
MANIFOLD PRESSURE (W.C.) IN C HE S W.
AF TY
L O W SWITCHE
OW WATER CUT-OFF
C O MMISSIONIN
NIT CYCLED MINIMUM O F 15 TIME
CUSTOMER INSTRUCTE
ALL COVERS REPLACE
UST O MER GIVEN MANUA
ARGET TEMPERAT U RE SET PER C U ST O ME
E S T
Verify that the piping and controls ensure the boiler return water temperature does NOT drop below 140°F, 60°C. Operating
at lower return temperatures is likely to cause condensation in the primary heat exchanger, resulting in corrosion and possible
failure of the heat exchanger.
HE CK LI
IR S WIT
IGH LIMIT
I
E
E
THE DELTA T BETWEEN THE HEATER
INLET AND OUTLET IS CRITICAL TO
PROPER FLOW. BEFORE YOU LEAVE
THE JOBSITE, YOU MUST RECORD THE
DELTA T. THIS READING SHOULD NOT
EXCEED 35°F, 19.4°C, NOR BE LOWER
THAN 20°F, 11.2°C.
NCHES W.C
M
N C HE S W. C.
FLAME SAFEGUAR
COMMISSIONED BY:
SIGNATURE
DATE: ___________________________
A
TI ON
N O TE
C O MMENTS
ELTA T =
41
Page 42
Finned copper tube gas boilers & water heaters – Boiler Manual
Commonwealth of Massachusetts
NOTICE!
Installation Requirements MACODE-3
In the Commonwealth of Massachusetts, the installa-
tion must be performed by a licensed plumber or gas
fitter.
1. For all side wall horizontally vented gas fueled equipment
installed in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned or
operated by the commonwealth and where the side wall exhaust
vent termination is less than seven (7) feet above finished grade,
in the area of the venting, including but not limited to decks and
porches, the following requirements shall be satisfied:
d. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the
time of installation of the side wall horizontal vented gas
fueled equipment, the installing plumber or gasfitter shall
observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level
where the gas equipment is to be installed. In addition, the
installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an
alarm is installed on each additional level of the dwelling,
building or structure served by the side wall horizontal
vented gas fueled equipment. It shall be the responsibility of
the property owner to secure the services of qualified
licensed professionals for the installation of hard wired
carbon monoxide detectors.
i. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an attic,
the hard wired carbon monoxide detector with alarm and
battery back-up may be installed on the next adjacent
floor level.
ii. In the event that the requirements of this subdivision can
not be met at the time of completion of installation, the
owner shall have a period of thirty (30) days to comply
with the above requirements; provided, however, that
during said thirty (30) day period, a battery operated
carbon monoxide detector with an alarm shall be
installed.
e. APPROVED CARBON MONOXIDE DETECTORS. Each carbon
monoxide detector as required in accordance with the above
provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certified.
f. SIGNAGE. A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line
with the exhaust vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The sign shall read,
in print size no less than one-half (1/2) inch in size, “GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
g. INSPECTION. The state or local gas inspector of the side wall
horizontally vented gas fueled equipment shall not approve
the installation unless, upon inspection, the inspector
observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1
through 4.
Improper venting can result in excessive levels of
carbon monoxide which can cause severe personal
injury or death!
2. Exemptions — The following equipment is exempt from
248 CMR 5.08(2)(a) 1 through 4:
a. The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
b. Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure used in
whole or in part for residential purposes.
3. MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING
SYSTEM PROVIDED.
a. When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system
shall include:
i. Detailed instructions for the installation of the venting
system design or the venting system components; and
ii. A complete parts list for the venting system design or
venting system.
4. MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING
SYSTEM NOT PROVIDED.
a. When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide
the parts for venting the flue gases, but identifies “special
venting systems”, the following requirements shall be
satisfied by the manufacturer:
i. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
ii. The “special venting systems” shall be Product
Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation
instructions.
5. A copy of all installation instructions for all Product Approved
side wall horizontally vented gas fueled equipment, all
venting instructions, all parts lists for venting instructions,
and/or all venting design instructions shall remain with the
appliance or equipment at the completion of the installation.
Improper venting can result in excessive levels of
carbon monoxide which can cause severe personal
injury or death!
42
Page 43
LIMITED WARRANTY
Boilers/Water Heaters
Industrial, Commercial and Other Non-Residential Use
e “Manufacturer” warrants to the original owner at the original installation site that the heat exchanger of the Industrial, Commercial, and other
Non-Residential Use Boiler (the “Product”) will be free from defects in material or workmanship for ten (10) years from the date of installation.
Additional twenty one (21) year thermal shock warranty on heat exchanger. If upon examination by the Manufacturer the Product is shown to
have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product
which is shown to be defective. All other RBI supplied Boiler/Water Heater parts are warranted against defects in material and workmanship for
one (1) year from date of installation or 18 months from date of shipment from RBI.
e “Manufacturer” warrants to the original owner at the original installation site that the heat exchanger of the Industrial, Commercial, and other
Non-Residential Use Water Heater (the “Product”) will be free from defects in material or workmanship for five (5) years from the date of
installation. Additional twenty one (21) year thermal warranty on heat exchanger. If upon examination by the Manufacturer the Product is shown
to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the
Product which is shown to be defective. All other RBI supplied Boiler/Water Heater parts are warranted against defects in material and
workmanship for one (1) year from date of installation or 18 months from date of shipment from RBI.
is limited warranty does not apply:
(a) if the Product has been subjected to misuse or neglect, has been accidentally or intentionally damaged, has not been installed,
maintained or operated in accordance with the furnished wrien instructions, or has been altered or modied in any way.
assist combustion. If a lower temperature is required, an external bypass should be installed to prevent condensation. e manufacturer’s
warranty does not cover damage done by condensation.
(b) to any expenses, including labor or material, incurred during removal or reinstallation of the Product or parts thereof.
(c) to damage as a result of selement, distortion, collapse, or cracking of any foundation area, beams or pipes surrounding the Product.
is limited warranty is conditional upon:
(a) shipment, to the Manufacturer, of that part of the Product thought to be defective. Goods can only be returned with prior wrien
approval from the Manufacturer. All returns must be freight prepaid.
(b) determination in the reasonable opinion of the Manufacturer that there exists a defect in material or workmanship.
Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired
or replaced part beyond the stated warranty period.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, AND
ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED
FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR
ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY
AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE
DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL
RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY EACH JURISDICTION.
43
Page 44
260 North Elm Street 7555 Tranmere Drive
Westfield, MA 01085 Mississauga, Ontario L5S 1L4 Canada
Phone: (413) 568-9571 Phone: (905) 670-5888
Fax: (413) 568-9613 Fax: (905) 670-5782
www.rbiwaterheaters.com
44
05/14 Copyright 2014 Mestek, Inc.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.