3.37 firmware on version 2.x control boards.
Current firmware is backwards compatible with
version 1.x boards, but some current features may
not be available. To replace firmware on an
existing boiler, contact the factory to obtain the
original firmware file or for assistance in applying
current firmware to an older version control board.
Also read and follow:
Futera III Boiler manual or
Futera Fusion Boiler manual or
Futera XLF Boiler manual
This manual is intended only for use by a qualified heating installer/technician. Read and follow this manual, all
supplements and related instructional information provided with the boiler. Install, start and service the boiler only
in the sequence and methods given in these instructions. Failure to do so can result in severe personal injury,
death or substantial property damage.
Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause
contamination of the burner, resulting in possible severe personal injury, death or substantial property damage.
The boiler can only be operated with a dust-free air supply. Follow the instruction manual procedures to duct air to
the boiler air intake. If the boiler has been contaminated by operation with contaminated air, follow the instruction
manual guidelines to clean, repair or replace the boiler if necessary.
Affix these instructions near to the boiler. Instruct the building owner to retain the instructions for future use by a
qualified service technician, and to follow all guidelines in the User’s Information Manual.
Copyright 2010 Mestek, Inc.
HeatNet Control REV 3.37-1
TABLE OF CONTENTS
TABLE OF CONTENTS .............................................................................................................................. 2
Version 2.x Control .................................................................................................................................. 30
Domestic Hot Water Methods ................................................................................................................. 31
DHW METHOD 1: DHW T
A
VAILABLE ON
DHW METHOD 1A: DHW H
DHW METHOD 1B: C
DHW METHOD 2: DHW H
A
VAILABLE ON BOTH
DHW METHOD 3: S
A
VAILABLE ON BOTH
DHW METHOD 4: DHW
A
VAILABLE ON BOTH
V2.X C
ANK SENSOR INPUT
ONTROLS
OMBO
V1.X
PACE HEATING WITH
V1.X
V1.X
ONLY .............................................................................................................................................. 31
Futera HeatNet Control Run Screen ....................................................................................................... 73
* Status Information ................................................................................................................................. 74
Status Screen Fault Display .................................................................................................................... 83
Line 4 Log Entries: .................................................................................................................................. 86
Information contained in this publication regarding device applications and the like
is provided only for your convenience and may be superseded by updates. It is your
responsibility to ensure that your application meets with your specifications.
RBIMAKES NO REPRESENTATIONS OR WARRANTIES OF ANY KIND
WHETHER EXPRESS OR IMPLIED, WRITTEN OR ORAL, STATUTORY OR
OTHERWISE, RELATED TO THE INFORMATION, INCLUDING BUT NOT
LIMITED TO ITS CONDITION, QUALITY, PERFORMANCE,
MERCHANTABILITY OR FITNESS FOR PURPOSE.
http://www.rbiwaterheaters.com/
The RBI name and logo, Mestek name and logo, Futera, HeatNet, and HNet name and logo are registered trademarks of Mestek, Incorporated in the
U.S.A. and other countries.
BACnet is a registered trademark of ASHRAE. LonWorks is a registered
trademark of Echelon Corporation.All trademarks mentioned herein are
property of their respective companies.
The Futera-Series boiler control is designed to provide the
Futera-Series of boilers with an integrated boiler
management system on every boiler. Designed for the AirFuel coupled Futera-Series boilers, the Futera-Series
HeatNet control provides for optimized heating efficiency
without the need for a “wall mount control”. Since the
Futera-Series modular control method is based on digital
communications, analog control signals are not required.
Although the use of analog control signals is still supported
(4-20mA control loops and 0-10vdc (20mA minimum)
control voltages), a higher level of control precision,
repeatability, and feedback is gained with digital
communications control.
With the Futera-Series, optimized heating efficiency is
accomplished by setting the Modulation Maximum (ModMax) setting to exploit the inverse efficiency curve. This
value can be adjusted so that as each boiler is added, it
operates at its maximum turndown. This allows the
maximum number of boilers to operate at their lowest
inputs, until all boilers are firing. Once all boilers are firing,
full range modulation control is allowed. An outdoor reset
function is also provided to assist in the optimized heating
efficiency of the Futera- Series boilers.
The Futera-Series boiler with the Futera-Series H-Net
control, can be operated in multiple ways:
1. As a stand-alone boiler.
2. A boiler in a Boiler Network using the HeatNet®
(H-Net®) protocol.
3. A member boiler to a boiler management system with
multiple input control methods.
The primary purpose of the control is to maintain the boiler
water temperature at the supply or the header sensor using a
target setpoint. While performing this task, the control also
monitors dedicated external limits in a limit string and
provides an orderly shutdown and fault indication in the
event of a tripped limit. The monitored limits include a
HIGH LIMIT AQUASTAT, LOW WATER CUTOFF,
GAS PRESSURE, FLOW, IGNITION CONTROL fault,
GAS VALVE alarm, VARIABLE FREQUENCY DRIVE
alarm, and other optional or user selectable limits.
The HIGH LIMIT circuit is independent of
the control and shuts down the ignition
control and the boiler if the control board or
other component of the boiler was to
malfunction. The control will continue to
function and report the fault, but its ability to
control the boiler will end.
HeatNet Control REV 3.37-1
Each Futera-Series boiler employing this control can
function as either a master or a member. This allows one
boiler (Master) to be in control of target temperature. The
other boilers (Members) only respond to the commands
issued by the Master. If using an external control, all boilers
can be setup as members. The following will define the
roles of master and member.
Master
A boiler becomes a master when a temperature sensor is
connected to the J10 “SYS/DHW HEADER” terminals. The
sensor is auto-detected.
The master senses and controls the common system
header/loop water temperature using a system setpoint. It
uses any boilers it finds (over the H-Net communications
cable) to accomplish this. It can also monitor the Outside
Air (OA) temperature to provide outdoor reset functionality.
Only one master is allowed in a system.
When operating as a master, the boiler provides a control
method using a PID algorithm to regulate water
temperature. This algorithm allows a single boiler (Master),
or multiple (Master + Member) boilers.
Figure 1 Heat band
BOILERS
UPPER HEAT
BAND LIMIT
SETPOINT
LOWER HEAT
BAND LIMIT
WATER
TEMPERATURE
The control algorithm is based upon a Heat Band, at the
center of which is the setpoint. While below the Heat Band,
boilers are staged on and modulated up until the Heat Band
is entered. Once in the Heat Band, modulation is used to
maintain setpoint. Boilers are shut down only when the top
of the Heat Band is breached. Timers are also used to
prevent short cycling.
While staging the boilers on, a modulation clamp
ADVANCED SETUP: MODULAR BOILER SET:
MOD MAX-LAST FIRE is used to hold the boilers at a
lower fire rate until the last boiler is fired. Once the last
boiler fires, the modulation clamp is removed and all boilers
are allowed to fire above this clamped percentage up to
100%. This “boiler efficiency” clamp is defaulted to 70%
and thus limits all of the boilers individual outputs to 70%
until the last boiler fires. All running boilers modulate up
and down together, always at the same modulation rate. As
a general rule, this percentage should be no lower than twice
the minimum turndown to minimize short cycling.
STAGED
OFF
Boilers Staged
ON
Time
Page 4
Features & Specifications
HeatNet Control REV 3.37-1
When additional boilers are needed to achieve setpoint in
the system, the Master boiler employs an ADAPTIVE
MODULATION algorithm to prevent over firing of the
system. The Master communicates over the H-Net to view
the exact status of each Member boiler. When a new boiler
is added, the Master boiler adjusts the system modulation
rate lower to compensate for the BTUs that will be
introduced by the newly added boiler. This adjustment
occurs when the newly added Member boiler enters its ON
CALL state (default setting). This can be changed to PILOT
when the new boiler is called using the menu:
ADVANCED SETUP:ADAPTIVE MOD:DROP
DOWN. Once the Main Valve (on the newly added boiler)
is opened, and the DELAY RELEASE timer equals zero,
the PID algorithm is allowed to control the system
modulation. Setting the DELAY RELEASE timer will
allow some “soak” time of the newly added boiler before
releasing modulation control to the PID.
The ADAPTIVE MOD menus are disabled
on a Member boiler, but are still visible.
Member
If a “SYS/DHW HEADER” sensor is not connected to J10,
a boiler always defaults to the role of Member.
In a stand-alone installation the Member typically receives
its command signals internally and operates based upon the
outlet water temperature input and the established settings in
the menu (Local Set-point) to start/stop the burner, and/or to
modulate the firing rate. If the operating limit is exceeded,
or if an interlock trips, the boiler is shut down. As in a
multi-boiler system, a stand-alone Member boiler is also
capable of receiving inputs from an external control system.
When using the H-Net network cable in a Master/Member
system, the system setpoint is sent from the Master as a
digital signal, along with the modulation value to control
firing rate. It also receives its command to start or stop over
the H-Net cable. Also, the SYSTEM CLOCK only needs to
be set on the MASTER. The Master will then set the time
on all member boilers.
If not using the H-Net protocol (cable), an external control
can send a 4-20ma signal along with a 4-20ma enable signal
to control the firing rate or setpoint. The boiler may also be
treated as a 2-stage boiler or an ON-OFF boiler using the
dedicated T-inputs.
The Member boiler can operate as part of a multi-boiler
system or as a stand-alone unit.
In a multi-boiler system the Member typically receives its
command signals from a designated Master-boiler. It is also
capable of receiving inputs from an external control system.
The boiler responds to these signals, to start/stop the burner,
and/or to modulate the firing rate. The outlet water
temperature is also monitored. If the outlet temperature
approaches the operating limit temperature setpoint
(adjustable), the boilers firing rate is limited and its
modulation value is reduced to minimize short-cycling. If
the operating limit is exceeded, or if an interlock trips, the
boiler is shut down. When connected with a network cable,
in a Master/Member role, the Members' status is
interrogated by the Master boiler.
Page 5
Features & Specifications
Features Overview
Hardware Version 1.x Control
(Identified by circuit board color: BLUE)
1. Five levels of external control inputs, including
modulation and staging that provide application
flexibility.
2. Digital Communications Control (analog 4-20ma and 0-
10vdc control supported, but not required).
a. Boiler to Boiler : HeatNet (H-Net)
b. Building Management System (MODBUS,
Optional BACnet or LonWorks) to Boiler
3. Distributed control using the HeatNet (H-Net) protocol
for up to 16 boilers. Eliminates the need for “wall
mounted” controls.
4. Analog Control 4-20ma and 0-10vdc (20mA minimum
current) signals supported.
5. System/Boiler operating status text display
6. Interlock, Event, and System logging with a time
stamp.
7. Advanced PID algorithm optimized for the Futera-
Series boilers.
8. (4) Dedicated temperature sensor inputs for: Outside
Air Temperature, Supply (Boiler Outlet) Temperature,
Return (Boiler Inlet) Temperature, and Header
(Common System Supply) Temperature.
9. Automatically detects the optional temperature sensors
on power up.
10. Menu driven calibration and setup menus with a bright
(Adj.) 4 line Vacuum Fluorescent Display.
11. (8) Dedicated 24vac interlock monitors, and 8 dedicated
120vac system monitors used for diagnostics and
providing feedback of faults and system status.
12. Multiple circulator pump control modes.
13. Combustion Air Damper control with proof time,
support for a common combustion air damper.
14. USB/RS485 network plug-in to allow firmware updates
or custom configurations.
15. Optional BACnet or LonWorks interface.
16. Alarm Relay dry contacts, and Audible Alarm.
17. Runtime hours, and Cycles(based on Main Valve
Open).
18. Outdoor Air Reset with programmable setpoint and
ratio.
HeatNet Control REV 3.37-1
19. Time of Day clock to provide up to (4) night setback
temperatures.
20. Failsafe mode when a Building Management System is
controlling setpoint. If communications is lost, the
boiler/system automatically transfers to local boiler
setpoint control.
21. Rotation Methods(Lead-Lag): True Rotation (based on
boiler runtime)is default. First On First Off (FOFO),
and Last On First Off (LOFO) is an optional
programmable setting.
22. Programmable password protection to secure the
programmable settings.
23. Heat exchanger delta T limiting feature. If the
temperature across the heat exchanger is greater than
40F, a menu selection can set to one of (2) modes. (1.)
The input rate is reduced to half of the called for rate.
(2.) The boiler will shut down, but when the Delta
temperature across the heat exchanger drops by 10 °F
the boiler will restart.
24. Low inlet temperature warning if return water
temperature drops below 130°F.
25. Remote 4-20mA setpoint control using a mapped
setpoint range to the 4-20mA control signal.
26. Freeze Protection allowing automatic starting of
boiler(s) using (2) Failsafe modes.
27. Adaptive Modulation. When additional boilers are
called, the Master adjusts all boilers fire rates to
compensate.
28. Mixed boiler types in a system.
Hardware Version 2.x Control
Additional Features
(Identified by circuit board color: GREEN)
1. Support for Domestic Hot Water (DHW) using a 10k
Sensor or a dry contact input from a tank thermostat.
2. Domestic Hot Water relay for use with a pump or
valve.
3. Separate power for a pilot blower (12 VDC @ 1amp –
J3 connector).
4. On-board power and socket for Protocessor
BACnet/LonWorks module.
5. HI/LO relay control option from connector J4
6. Resettable Fused interlock power circuit.
7. Additional terminal connector for H-Net shielded cable.
8. Backwards compatible to Version 1.x hardware.
9. Communications board integrated with the main board
from version 1.x control.
10. Base Loading of (1) boiler.
Page 6
Features & Specifications
HeatNet Control REV 3.37-1
Specifications
Control Microprocessor based PID modulating control ( NOT a safety limit )
Environment -40 °F to 140 °F, <90% RH non-condensing
refer to Refer to the 2008 ASHRAE Handbook, CH12 or later revision.
A basic multi boiler system typically uses boilers of the
same size and type. With HeatNet, this includes (1) Master
and (1-15) Member boilers. The boilers are connected
together using an H-Net communications cable effectively
creating (1) boiler. This allows the system heating BTUs to
be evenly distributed amongst all of the boilers. (See: Figure
43, Typical Single Boiler System, page 46).
Figure 2 Basic multiple boiler system
A basic multi boiler system can be configured using the
boiler menus to create custom systems/features. These
features are best described in the section: Default Settings
& Menu Item Description, page 52. Along with these
menu items are hardware support for many
auxiliary functions.
Once the system has been properly setup (all default menu
values used and H-Net addresses assigned), the system is
enabled by placing the REMOTE/LOCAL switch to the
LOCAL position on the Master boiler. All Member boilers
must have their respective switches in the REMOTE
position. When the Master boiler’s Heat Demand input
(LOCAL switch) closes, the system becomes operational
and will fire as many boilers as it needs to maintain the
header water temperature’s setpoint.
When a boiler is to be fired in a multi boiler system (header
water temperature is below the heating band), the Master
checks the HeatNet boilers it has available. Then the Master
checks if a Lead Boiler is to be used (LEAD BOILER > 0).
The Master boiler then looks at which type of firing rotation
it has selected: LOFO, FOFO, TRUE (runtime), or MIXED.
In our example we will use the TRUE (runtime) rotation
since it is the default.
The Master now checks all of the runtimes to determine
which boiler has the least runtime based on the MIN
HeatNet Control REV 3.37-1
RUNTIME setting in ADVANCED SETUP:FIRING
MODE:. The MIN RUNTIME setting is the minimum
runtime interval in hours that is used to compare boiler to
boiler runtimes.
Once the boiler to fire has been determined, the Master
sends the command over the H-Net cable to fire that boiler
and resets the ADD BOILER delay timer to prepare for the
next boiler to fire. If the header water temperature is still
below the heating band and the ADD BOILER delay timer
has expired to zero, the process is repeated until the header
water temperature enters the heating band.
When a boiler receives a command to fire it:
1. The system pump relay is enabled and the H-Net
control displays 'Flow Wait' until the flow-switch closes
between J11A, 1 & 2 within the programmed time (10240 seconds).
2. All elements in the interlock string, terminated between
J11A and J11B, must be closed before the sequence is
allowed to continue.
3. If all interlocks are closed relay K5 is enabled to
command the combustion-air damper open (If used).
The H-Net control displays 'Damp: Wait' until the
damper endswitch to closes.
4. Relay K6 is enabled energizing the local pump (if
used). The H-Net control commences its 'Flow-Wait'
timer (adjustable 10–240 sec.). The flow switch contact
is interrogated on terminals J11-B 5 and 6.
5. With all the interlocks closed the boiler start relay K1 is
enabled and energizes terminal 6 on the ignition
control.
6. The ignition control begins its cycle and provides an
output signal from terminal 4 to the H-Net control. The
H-Net control responds and provides an output signal to
the VFD which sets the blower to the programmed prepurge speed.
7. After air-flow is established the ignition control waits
for the air switch to close. When the air switch closes it
provides an input to terminal 7 and pre-purge timing
commences. The H-Net display indicates 'Pre Purge'.
8. When purge is complete the ignition control energizes
the pilot gas valve from terminal 8, and the spark
generator from terminal 10, beginning a 10-second pilot
flame establishing period (PFEP). The H-Net control
responds and provides an output signal to the VFD
which sets the blower to the programmed ignition
speed. The H-Net display indicates 'Pilot'.
9. At the end of the PFEP the spark generator is de-
energized. If the pilot flame is detected, by the UV
scanner, the ignition control energizes the main gas
valve from terminal 9. The H-Net display indicates
'Run'.
10. If main-flame is detected the H-Net control holds the
burner at the low-fire rate for the MODULATION
DELAY time period. After this timer expires, the PID
allows the boiler to modulate and places the boiler into
the running state.
Page 9
HeatNet Control REV 3.37-1
As boilers are added to the system settings in the
ADVANCED SETUP:ADAPTIVE MOD:DROP DOWN
menu determines when the modulation rate drops down to
compensate for the newly added BTUs. For the drop down
to be active one boiler needs to be running when a new
boiler is added (see: Introduction: The Futera-SERIES H-Net Control: Master).
If all boilers are firing, the modulation rate is released to go
to 100%. If all boilers are not firing, the modulation is
limited to the MOD-MAX clamp value. The MOD-MAX
clamp is used to keep the boilers running as efficiently as
possible. The following Mixed Boiler System Operation: Selecting Mixed Boilers section outlines this with examples.
Once the header water temperature is in the heating band,
only the modulation rate is used to achieve the target
setpoint. The system will maintain the setpoint until the load
demand increases or decreases.
As the load decreases, the header water temperature will
start approaching the top of the band. The PID now lowers
the modulation rate to the boilers, attempting to keep the
temperature within the heating band. If the system is
delivering too many BTUs, the water temperature will cross
the top of the heating band.
Setting all (example) condensing boilers to the highest
Priority of 1, and then setting all (example) non-condensing
boilers to a Priority of 2, will create (2) sets of boilers, one
condensing and the other non-condensing. Once this is
done, the Priority 1 set of condensing boilers will have a
firing order that has a higher Priority and is independent of
the other non-condensing set with the lower priority. The
boiler set with the highest Priority can then be fired based
on a conditional settings menu. The lower Priority set will
follow.
Mixed Boiler System Operation
Starting Boilers:
When a boiler is to be fired (water temp is below the heating
band), the Master checks the HeatNet boilers it has
available. The Master boiler then looks at which boilers are
returning Priority firing status (set on a boiler in:
(ADVANCED SETUP:SYSTEM:BOILER
TYPE:PRIORITY : 1). If the Start condition for the
Priority 1set is met (ADVANCED SETUP:FIRING MODE:
MODE: MIXED:SET FIRST (example), the Master or
Member boiler that is configured as PRIORITY 1, with the
lowest runtime, will be fired FIRST (example).
When the header water temperature first exceeds the top of
the heating band, the boilers are again checked for the one
with the most runtime. The selected boiler will turn off
immediately and a shed boiler delay timer will be loaded
with the delay time. This time will need to expire before the
next boiler will be stopped, but only if the header water
temperature remains above the heating band. This timer is
used to allow the header water temperature to return back
into the band when a boiler is stopped. When a boiler is
stopped there is a fixed rate of BTUs (Min Fire) that will be
removed (PID discontinuity to modulate from Min Fire to 0
BTUs on a boiler). The timer allows for this loss of BTUs.
This cycle will continue until the call for heat is satisfied or
the Warm Weather Shutdown feature is enabled.
Mixed Boiler Types Using
Priority Sets
Using the Basic Multi Boiler System Operation, a MIXED
boiler Priority method may be added to control condensing,
non-condensing, base load, or other boiler SETs in a system
together. These sets compose a system which provides for
optimal performance and economy. Having dedicated sets
of boilers gives the system engineer a tool to create many
different boiler systems.
A boiler set can be constructed by simply setting the firing
Priority on each boiler (to be in a set) at the same priority.
As long as the start condition for Priority 1 is met, all
boilers in the PRIORITY 1 set will fire based on runtime.
Once all boilers in the PRIORITY 1 set have fired, the
PRIORITY 2 set of boilers will fire based on runtime.
If the Start condition changes and/or is not met (such as
with: OA T or RET temp), the PRIORITY 2 set of boilers
will fire first/next based on runtime. This has the effect of
flipping the Priority of the sets.
Stopping Boilers:
When a boiler is to be stopped (water temp is above the
heating band), the Master checks the HeatNet boilers it has
available. The Master boiler then looks at which boilers are
returning Priority firing status (set on a boiler in:
(ADVANCED SETUP:FIRING MODE: MODE:
MIXED:SET LAST(example) If the Stop condition for
Priority 1 is met, the Master or Member boiler that is
configured as PRIORITY 1 with the highest runtime will be
stopped LAST (example). As long as the stop condition and
SHED DELAY time are met, all remaining PRIORITY 1 set
of boilers will stop based on runtime. If the Stop condition
changes and/or is not met (such as with: OA T or RET
temp), the PRIORITY 2 set of boilers will stop first/next
based on their highest runtime.
A boiler’s firing Priority can be designated as such in:
ADVANCED SETUP:SYSTEM:BOILER TYPE:FIRING
PRIORITY : 1 menu on each boiler. A Priority of ‘1’ is
the highest priority, a ‘2 the lowest (default is always 2).
Page 10
SETUP & OPERATION
PRIORITY 2
Futera III boilers (non-condensing)
>
S E T : O A T < 1 5 ° F
Figure 3 Mixed Boilers: Condensing/Non-Condensing
PRIORITY 1
Fusion boilers (condensing)
HeatNet Control REV 3.37-1
FIRING MODE
(master boiler only)
BOILER TYPE
(all boilers in set)
menu
menu
>MODE MIXE D
MIN RUNT IM E: 10HRs
MIN OFF T IM E:0s
PREDICT ST ART:YES
>FIRIN G P RIORITY :1
B TU I N 50 0,000
C ON DENSING YES
MASS LOW
In the example Mixed Boilers: Condensing/NonCondensing, condensing boilers and non-condensing boilers
are used, but other combinations may also be used. Another
example could use (2) small boilers and set them to
Priority 1 and then use (3) larger boilers and set them to
Priority 2. Using these Priority settings (with the conditions
menu), the small boilers can run first during the shoulder
months (Spring and Fall) and the larger boilers can fire last
during the colder Winter season (base loading set).
Before the MIXED method can be used, the firing mode on
the Master boiler must be set to MIXED. ADVANCED SETUP:FIRING MODE: MODE: MIXED. Pressing the
SELECT key when the cursor is pointing to MIXED will
enter the conditions menu. The START and STOP
conditions for starting and stopping the Priority boiler set
may be configured here. Temperatures are adjustable.
BOILER TYPE
(all boilers in set)
menu
FIRING PR IORITY :2
BTU IN 1250, 00 0
CONDE NS ING NO
MASS LOW
menu. All conditional settings apply to the Priority 1 boiler
set. When the conditional settings do not apply to the
Priority 1 set, the conditional settings will apply to the
Priority 2 boiler set.
Start/Stop Priority Conditions
The following is an example using mixed
condensing and non condensing boilers:
FIRE FIRST
Condensing boilers may be configured to fire first (set to
PRIORITY 1) when:
1. The Return water temperature is below 140F and
condensing occurs. (The Master’s return water sensor
would need to be moved to the header return.)
S T A R T P R I O R I T Y 1
> S E T : F I R S T
S T O P P R I O R I T Y 1
Once the conditions menu has been entered, the firing order
and stop order of the Priority 1 boiler set can be selected
based on up to (3) conditions in the conditional settings
2. The Outside Air Temperature is above a setpoint
determined by the system configuration. This setpoint
ensures that the more efficient condensing boilers run
first during shoulder months (Spring and Fall) when
minimal heating is required. Below this setpoint, larger
boilers should be brought on first to “base load” the
system.
3. Greater efficiency is required.
Page 11
S E T :
L A S T
HeatNet Control REV 3.37-1
STOP FIRST
Condensing boilers may be configured to stop first (set to
PRIORITY 1) when:
The Return water temperature is above 140F and
condensing is minimized, thus leaving the larger lower cost
boilers running to carry the load.
1. The Outside Air Temperature is below an adjustable
setpoint determined by the system configuration. This
setpoint ensures that the larger non-condensing boilers
run during the coldest months when maximum heating
is required. Above this setpoint smaller condensing
boilers should be brought on first to run the system as
efficiently as possible.
2. Maximum heating is required
START PRIORITY 1 SET
Selections (always the lowest runtime first):
The condensing boiler set (Priority 1) has a
higher Priority to fire when one of these
conditions is met. Values are adjustable.
FIRST: The condensing boilers (Priority 1) are always
started FIRST
OA T > 15F: The condensing boilers (Priority 1) are
started when the OA temperature is greater than the Mixed
Boiler Outdoor Air Temperature setting.
RET < 140F: The condensing boilers (Priority 1) are
started when the Return water temperature is less than the
Mixed Boiler Return temperature setting (This may not
applicable in most configurations since the local return
temperature on the Master is used to provide a difference
temperature across the heat exchanger. However, the return
temperature sensor may be moved on the Master to provide
system return temp if the difference temp is not required).
STOP PRIORITY 1 SET
Selections (always the highest runtime first):
The condensing boiler set (Priority 1) has a
higher Priority to stop when one of these
conditions are met. Values are adjustable.
LAST: The condensing boilers (Priority 1) are always
stopped LAST.
OA T < 15F: The condensing boilers (Priority 1) are
stopped first when the OA temperature is less than Mixed
Boiler Outdoor Air Temperature.
RET > 140F: The condensing boilers (Priority 1) are
stopped first when the Return water temperature is greater
than the Mixed Boiler Return temperature. (This may not
applicable in most configurations since the local return
temperature on the Master is used to provide a difference
temperature across the heat exchanger. However, the return
temperature sensor may be moved on the Master to provide
system return temp if the difference temp is not required)
Start/stop settings
Any combination of Start Conditions and Stop Conditions
can be used to optimize the mixing of condensing
(Priority 1) and non-condensing boilers (Priority 2) for best
performance/economy.
The default settings for the start and stop conditions of the
condensing set are:
S T A R T P R I O R I T Y 1
> S E T : F I R S T
S T O P P R I O R I T Y 1
The default start setting always starts the condensing boilers
(Priority 1 example) first, except for the lead boiler setting.
The lead boiler will always start first if enabled, unless
there is a boiler already running (this includes a Member
boiler in LOCAL). The default stop condition setting always
stops the condensing boilers (Priority 1) last.
If prolonging the life of the heat exchanger(s) on noncondensing boilers is very important, consider starting the
condensing boilers (Fusion series) when the return water
temperature is below 140F.
The return water temperature sensor would
need to be moved from the Master’s return
inlet to the system return. The EXCHGR
DELTA may need to be adjusted in
SETUP:AUX FUNCTIONS:HEAT
EXCHANGER to prevent the Master from
going to ½ input when a high DELTA T is
reached.
This method would lead to the non-condensing boilers
carrying the load when the system temperature stabilizes
above 140F, since non-condensing boilers will start first
with the Return water temperature is > 140F. The
condensing boilers can then be stopped first when the RET
water temperature is above the 140F. Remember, any
combination of the Start and Stop conditions may be applied
for best performance and economy in the system.
Base load boilers can also be mixed in the same way as
condensing and non-condensing boilers. The base load
boiler(s) can be prioritized in one set (example, Priority 2)
and non-base load boilers (Priority 1) . The non-base load
boilers can then be set to fire first and once they are all
firing, the base load boiler would fire.
Page 12
SETUP & OPERATION
System
Effective
MOD
Priority
1
Priority
2
HeatNet Control REV 3.37-1
To minimize the cycling of a large base load boiler, consider
using the stop condition. Change it to the OA T < 15F
(Outside Air Temperature) condition. This setting may be
used to stop the Priority 1 boiler set when the OA T drops
below the OA T setpoint, thus leaving the large base loaded
boiler on and shutting off the condensing boilers first. This
is also true when using the OA T setting to start the
Priority 1 boiler set when the OA T is above the start
setpoint. To use temperatures as start and stop conditions,
the system design temperatures must be known.
Selecting Mixed Boilers
There are a few factors to consider when choosing which
type of boilers to use in a mixed system. These factors need
to be considered when boilers are added or shed. When
BTUs are introduced into the system by adding boilers, the
amount of introduced BTUs should be smooth (linear). If
these factors are not considered, discontinuity in BTUs may
occur when boilers are added and as a result, short cycling
will occur.
1. Turndown: This is the ratio of minimum fire rate to
maximum fire rate: Example: a 20% minimum
modulation = 5:1 turndown (100%mod / 20% mod). A
(1) million BTU boiler = 200,000 BTUs minimum
input.
The Futera III Mixed Boiler System (examples) is
advantageous in providing low BTU input for light loads
and high BTUs for heavy loads. The effective system
turndown minimizes short cycling when light loads are
present by assigning smaller boilers to Priority 1, running
them first, and then stopping them last.
In order to achieve the high effective
turndown, smaller boilers are required
(plumbing considerations need to be
considered here due to differing flow/volume
characteristics through the large and small
boilers).
Example Systems:
Figure 4 Non-Mixed Boiler System
MMBTU
10.0 20:1 70%
5.0 20:1 70%
2.5 20:1 70%
Turndown
MAX
MB/MW 4:1
2000, 2000, 2000,
2000, 2000
1000, 1000, 1000,
1000, 1000
500, 500, 500, 500,
500
2. MOD MAX CLAMP: This value determines the
maximum modulation % at which the boilers will fire
to until all available boilers are firing.
3. Total System BTUs.
4. Desired Effective Turndown. This is the lowest
firing rate of the system relative to the maximum firing
rate of the system. The larger the value, the lower the
BTUs that can be delivered to a light load.
5. Piping.
Mixed System Type 1:
High System Turndown
The following examples are of mixed boiler systems with
high effective system turndown and fault tolerance built in.
When boiler types are the same, the system turndown is
limited to the boiler’s min input and fault tolerance is
always present. When the system has mixed boiler types,
consideration needs to be taken on what types can be mixed
properly to achieve a high system turndown and provide
some fault tolerance.
Fault tolerance allows for one boiler in the Priority 1 system
to fail and any boiler(s) in the Priority 2 system to fail and
still provide near linear (continuity) BTU response when
adding boilers. This is illustrated in the following examples
using the Boiler System Response graphs.
With the traditional Non-Mixed boiler system, the effective
turndown increases by the turndown ratio for every boiler
added. The min fire rate is equal to the minimum BTUs that
can be delivered to the system.
Number of boilers * Turndown Ratio = Effective System
Turndown: 5 * 4:1 = 20:1.
Figure 5 Mixed Boiler System
System
MMBTU
4.5 24:1 46% 750, 750
4.75 32:1 60% 500, 500
6.5 26:1 45% 1000, 1000
6.0 48:1 55%
Effective
Turndown
MOD
MAX
MB/MW
4:1
500, 500,
500
MB/MW
4:1
1000, 1000,
1000
1250, 1250,
1250
1500, 1500,
1500
1500, 1500,
1500
With the mixed boiler system, a lower minimum fire
rate/BTU can be delivered to the system by using small
boilers with larger boilers. This works in much the same
way as base loading.
Page 13
MB/MW
Mod Max
HeatNet Control REV 3.37-1
Figure 6 Futera Fusion & III Boiler Btu Chart (MBH)
CB/CW
Max Input 500 750 1000 1250 1500 1750 2000
Min Input
4:1
Mod Max
80%
70%
Mod Max
60%
Mod Max
50%
500 750 1000 1250 1500 1750 2000
125 188 250 312 375 437 500
400 600 800 1000 1200 1400 1600
350 525 700 875 1.05 1220 1400
300 450 600 750 900 1050 1200
250 375 500 625 750 875 1000
When selecting the Priority 1 boiler(s) for a high effective
system turndown, the BTU Min Input is selected first. (See:
Futera Fusion & III Boiler Btu Chart). Next, the MODMAX value of this Priority 1 boiler needs to be greater than:
Mod MAX % =
(Priority 1 ‘s Min Input + Priority 2 ‘s Min Input)
Max Input of the Priority 1 boiler
The reason for this is keep the continuity of BTUs linear
without a BTU bump (discontinuity) when boilers are added
or shed. This is illustrated in the Boiler System Response 2
graph.
If redundancy is not required, the min inputs of the
Priority 1 boilers may be summed to lower the Mod Max %
value so smaller Priority 1 boilers can be used. The sum of
the min inputs would then need to be divided by the sum of
the Max Input of the Priority 1 boilers. The effect of this
would create a higher turndown. See: EXCEPTION NOTES:
EXCEPTION NOTES:
1. Mixing more than two different size/type boilers
becomes more complex than the scope of this manual
and is not recommended.
2. If using more than one Priority 1 boiler and the
calculated value is <
Priority 1Min * 2
Priority 1 Max Input
Use this result PLUS note 3 value as the
ModMax%.
3. Always add a few % (3-5%) to the calculated MOD
MAX % value to allow a guard band (tolerance).
4. If boilers are of different sizes, try to use larger Priority
2 boilers.
If the calculated Mod MAX % value is greater
than 99%, the combination cannot be used
since short cycling will occur.
Once the Priority 1 and Priority 2 boilers are selected, they
can be multiplied in each Priority set to achieve the desired
system design BTUs. If the # of boilers becomes a large
number, a Priority 1 boiler with a higher Min Input may
need to be selected.
While considering the MOD-MAX value, the lower the
MOD-MAX the greater the combustion efficiency since it
effectively limits the input rate. The Typical Efficiency of
Non-Condensing Boilers chart can help illustrate how the
MOD-MAX value can affect the efficiency by limiting the
input until all boilers have fired. Non-condensing boiler
efficiency is relatively flat compared with condensing as
illustrated in the Typical Efficiency of Condensing Boiler
graph.
In the Mixed Boiler System table line 2 example, (2)
MB/MW 500s are set as Priority 1 and MB/MW 1250s set
as Priority 2. With a MOD MAX of 60%, each 500 can run
to 300M (600M total) before a 1250 is called ON (Add
Delay timer). Once both 500s are running and the 1250 is
called on, all (3) boilers will drop to a total of the 600M
BTUs: The sum of the 500, 500, and 1250 would equal
about 27% modulation: (.27* 500M) + (.27* 500M) + (.27*
1.25MM) or: 135M +135M + 337M = 607M and operate at
higher combus tion efficiencies (non condensing boilers
have minimal effect individually, but can have an effect if
many are used).
If CB/CW Fusion boilers are substituted for the MB/MW
Futera III boilers, the efficiency is greatly increased due to
the condensing mode of these boilers. When using CB/CW
Fusion boilers, during the first 2850 MBTH of load, the
combustion efficiency is maximized by running the CB/CW
Fusion boilers from low to middle input rates. See: Typical Efficiency of Condensing Boiler graph.
Figure 9 Boiler System Response 1
(2) MB/MW 500s, (3) MB/MW 1250s
1.00
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.10
0.00
01,000,0002,000,0003,000,0004,000,000
When running non condensing boilers at low
input rates, the risk of condensing should be
considered.
The Boiler System Response 1 chart illustrates how each
boiler (in the example) is brought on and fires to 60%, drops
to a lower fire rate and then adds the next boiler (vertical
dashed lines). Once all boilers are firing, the modulation is
released allowing all boilers to fire to 100%.
Now, if (1) MB/MW 500 (one of the MB/MW 500s was
brought offline) were used with (3) MB/MW 1250s and the
Mod-Max is set to 60%, the MB/MW 500 would fire to 300
MBTUs and wait for the MB/MW 1250 (Boiler System Response 2 graph). Now, the minimum input rate would be
312M (MB/MW 1250) + the 125M (MB/MW 500) (already
running, but dropped to low fire when the MB/MW 1250
fired), the total being 437M. With a 60% MOD-MAX
clamp, there would be 137 MBTUS more than needed and
added to the system when the MB/MW 1250 fired.
The PID algorithm would then compensate for the
discontinuity (bump) in BTUs and the MB/MW 1250 could
shut off (short cycle).
This discontinuity is observed in the graph below, (Boiler System Response 2) where the jump from the MB/MW 500
@60% to the firing of the MB/MW 1250 is apparent.
Figure 10 Boiler System Response 2
(1) MB/MW 500, (3) MB/MW 1250, 60% ModMax
Blr 1+2 (1750 MBTU)
1.00
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.10
0.00
01,000,0002,000,0003,000,0004,000,000
Blr 1+2+3 (3000 MBTU)
To correct this would require the MB/MW 500 to set the
MOD-MAX to roughly 90% (Boiler System Response 3: not
as efficient as it could be when using CB/CW Fusion
boilers) in order to have a linear BTU transfer when the
MB/MW 1250 is added (fired).
Page 15
Priority
2
5,000,000
I
n
p
u
t
,
%
System Load, Btu/Hr
Blr 1+2+3 (4250 MBTU)
5,000,000
I
n
p
u
t
,
%
System Load, Btu/Hr
Blr 1+2+3 (3000 MBTU)
Blr 1+2+3+4 (5000 MBTU)
Blr 1+2+3+4+5 (7000 MBTU)
HeatNet Control REV 3.37-1
Figure 11 Boiler System Response 3
(1) MB/MW 500, (3) MB/MW 1250, 90% ModMax
Blr 1+2 (1750 MBTU)
1.00
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.10
0.00
01 ,000,0002,000,0003,000,0004,000,000
Blr 1+2+3 (3000 MBTU)
An MB/MW 500 running with a MB/MW 1250 may not be
an optimal choice unless (2) MB/MW 500s are used in the
Priority 1 set or (3) MB/MW 500s and one is allowed to be
taken offline.
A system employing this redundancy where (1) is allowed
to be taken offline is listed in the MIXED BOILER SYSTEM
chart. This system uses (3) MB/MW 500s and (3) MB/MW
1500s. Two of the MB/MW 500s are treated as one when
adding the min inputs of the Priority 1 set.
Figure 12 Boiler System Response 4
(2) MB/MW 500s, (3) MB/MW 2000s
system, it is important to note any discontinuities in BTUs if
a Priority 1 boiler fails when multiple Priority 1 boilers are
used.
Mixed System Type 2:
Condensing / Non-Condensing
This mixed system may also have mixed boilers with
differing sizes as outlined in the Mixed System Type 1: High System Turndown section. The reason for creating a mixed
system is primarily to control the system cost.
Figure 13 Mixed Boiler System
System
MMBTU
4.5 24:1 60% 750, 750
4.75 32:1 60% 500, 500
6.5 26:1 65% 1000, 1000
6.0 48:1 65% 500, 500, 500
The Mixed Boiler System table show some examples of
mixed systems using different sizes along with Fusion
condensing (Priority 1) and Futera III non condensing
(Priority 2) boilers.
Effective
Turndown
MOD
MAX
Priority 1
CB/CW 4:1
MB/MW
4:1
1000, 1000,
1000
1250, 1250,
1250
1500, 1500,
1500
1500, 1500,
1500
1.00
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.10
0.00
01,000,0002,000,0003,000,0004,000,000
The Boiler System Response 4 graph illustrates another
system where 80% is used as the MOD-MAX clamp. With
this example, when using all non condensing boilers, the
system can maximize the use of the smaller boilers before
calling the larger ones.
In summary, the system should be tuned using the boiler
selection charts and the MOD-MAX value. Since selecting
the Priority 1 boiler is integral to the fault tolerance of the
Using the boiler charts and the examples used in: Mixed System Type 1: High System Turndown, a mixed boiler
system can be designed. The Priority 1 boilers should be
setup so as to keep the non-condensing boilers from seeing
return water temperatures of less than 140F to ensure a long
heat exchanger life.
Futera III/ Fusion Boiler BTU Chart
In the Mixed Boiler System table line 2 example, (2)
CB/CW 500s are set as Priority 1 and (3) MB/MW 1250s
set as Priority 2. With a MOD MAX of 60%, each 500 can
run to 300M (600M total) before a 1250 is called ON (Add
Delay timer). Once both 500s are running and the 1250 is
called on and running, all (3) boilers will drop to a total of
the 600M BTUs: The sum of the 500, 500, and 1250 would
equal about 27% modulation: (.27* 500M) + (.27* 500M) +
(.27* 1.25MM) or: 135M +135M + 337M = 607M and
operate at higher combustion efficiencies: 27% is roughly
between the top two lines on the Typical Efficiency of
Condensing Boilers chart.
Page 16
SETUP & OPERATION
MB/MW
Max
5,000,000
I
n
p
u
t
,
%
System Load, Btu/Hr
Blr 1+2+3 (2250 MBTU)
Blr 1+2+3+4 (3500 MBTU)
Blr 1+2+3+4+5 (4750 MBTU)
PRIORITY 2
Futera III boilers (non-condensing)
>
HeatNet Control REV 3.37-1
The Boiler System Response 5 chart illustrates how each
boiler (in the example) is brought on and fires to 60%, drops
to a lower fire rate and then adds the next boiler (vertical
dashed lines). Once all boilers are firing, the modulation is
released allowing all boilers to fire to 100%.
Figure 14 Boiler System Response 5
(2) CB/CW 500s, (3) MB/MW 1250s
1.00
0.90
0.80
0.70
0.60
0.50
0.40
0.30
0.20
0.10
0.00
01,000,0002,000,0003,000,0004,000,000
So, for the first 600 MBTH of load, the combustion
efficiency is maximized by running the (2) fusion boilers
from low to middle input rates. Running the (2) fusion
boilers first also has the added effect of minimizing the
return water temperatures of <140F from reaching the non
condensing boilers.
Figure 15 Futera Fusion & III Boiler Btu Chart (MBH)
CB/CW
500 750 1000 1250 1500 1750 2000
Max Input 500 750 1000 1250 1500 1750 2000
Min Input
4:1
Mod Max
80%
Mod
70%
Mod Max
60%
Mod Max
50%
125 188 250 312 375 437 500
400 600 800 1000 1200 1400 1600
350 525 700 875 1.05 1220 1400
300 450 600 750 900 1050 1200
250 375 500 625 750 875 1000
In summary, the system should be tuned using the boiler
selection charts and the MOD-MAX value so that boilers
are brought on and fired in their respective efficiency curve
while maintaining continuity in BTUs. Since selecting the
Priority 1 boiler is integral to the fault/offline tolerance of
the system, it is important to note any discontinuities in
BTUs if a Priority 1 boiler goes offline when multiple
Priority 1 boilers are used.
>MODE MI XE D
MIN RUNT IM E: 1 0H Rs
MIN OFF T IM E:0s
PREDICT ST AR T:YES
>FIRING PRIOR IT Y : 1
B TU IN 50 0, 00 0
CON DE NS ING YE S
MASS LOW
BOILER TYPE
(all boilers in set)
menu
FIRING PR IO RITY :2
BTU IN 1250, 00 0
CONDE NS IN G NO
MASS L OW
Page 17
>BOILER TY PE
LOAD FIRM WARE
OPTION: B ASE LOAD
>BASE LOAD BOILERS: 1
START>MO D 95
DELAY TIM E 10m ins
Master
FIII/Fusion
Baseload
>BOILER TY PE
LOAD FIRM WARE
OPTION: B ASE LOAD
>BASE LOAD BOILERS:1
START>MOD 95
DELAY TIME 10mins
Master
Baseload
Dominator
HeatNet Control REV 3.37-1
Base Loading, Relay Control
(Version 2.x control)
The control has the ability to control (1) base load boiler
using the K8 Relay contacts on J4 pins 2 & 6. In order to
connect to this plug, (2) wires with pins are required and
inserted in J4. Base Loading via relay requires these (2)
flying leads (loose wires available from the factory) to be
inserted into J4, pins 2 & 6. These (2) wires then make up
the Normally Open contacts. This feature also requires a rev
2.x control board and can be used on Master or Member
boilers. It is not applicable in version 1.x control boards (no
relay). The solid state relay K8, with contact connections on
J4.2 & J4.6 has a rating of: 0.1 to 1 Amp.
If the base load boiler is of the modulating type, a 4-20mA
signal is also provided on J4 pins 1 and 5. Jumper shunt J18
will then need to be set to 4-20mA position. Two additional
wires (available from the factory) will need to be added to
the J4 pins at 1 & 5. Pin 1 is the + output of the 4-20mA
transmitter, and pin 5 is the – output. This modulating
control signal is used to modulate the base load boiler along
with the HeatNet boilers in parallel. The ADAPTIVE MOD
does not function in lowering the modulation rate when the
base load boiler is added. The PID will adapt to the newly
fired base load boiler and lower its modulation rate when
the increase in water temperature is observed.
Figure 17 Base loading with Futera II boiler
FII
Figure 18 Base loading with Dominator boiler
FIII/Fusion
BASE LOADING
(master boiler only)
menu
STOP FIRST
SYSTEM
()master boiler only
Enable the base load feature by setting:
ADVANCED SETUP:SYSTEM:OPTION to BASE LOAD.
This setting the OPTION Relay to be used as control for a
Base Load Boiler.
1. The ADVANCED SETUP:BASE LOAD BOILERS:
menu
BASE LOAD BOILERS: to 1. Currently allows (1)
base load boiler.
BASE LOADING
(master boiler only)
SYSTEM
()master boiler only
menu
Page 18
menu
STOP FIRS T
2. The START & STOP qualifier condition to the method
discussed below.
3. The DELAY TIME to the amount of time required after
the start qualifier condition has been met to start the
boiler.
If a MINIMUM OFF time of the Base Load boiler is
needed, the Base Load boiler will share the MIN OFF TIME of the boiler controlling it. If the base load boiler was
running and shuts off, the MIN OFF TIME will need to
expire before the boiler can start again. Once this time
expires, the DELAY TIME also needs to expire to start the
boiler. This will help in minimizing short cycle conditions
and can be set at: ADVANCED SETUP:FIRING MODE: MODE:MIN OFF TIME.
Control Methods
HeatNet Control REV 3.37-1
Preferred:
A modulating base load boiler that can accept a 4-20mA
control signal is preferred or a non-modulating base load
boiler that is sized correctly to the H-Net boilers. A 0–135
ohm input for the base load boiler will need a converter
from 4-20mA to 0–135 ohm. Consider the Futera II or the
Dominator series for the Base Load role.
http://www.rbiwaterheaters.com/
If the base load boiler is not of the modulating type,
stopping the Base Load boiler will require that the size of
the Base Load boiler in BTUs is known relative to the
HeatNet boilers. Boiler selection is ideally; having more
total BTUs in the HeatNet boilers than total BTUs of the
Base Load boiler. This will prevent short cycling. Example:
(4) 2 million BTU HeatNet boilers = 8 million BTUs and
(1) 6 million BTU Base Load boiler.
When all (4) HeatNet boilers are running @ 95%, the Base
Load boiler is called on (demand is approx. 8 million
BTUs). As the Base load boiler comes on it introduces 6
million BTUs and the HeatNet boilers modulate down to
25% for a total output of 2 million BTUs and running at
high efficiency. The HeatNet boilers can now modulate to
the load from 1.6 million BTUs (20% mod) to another 8
million BTUs.
Not Preferred:
Example of having a larger Base Load boiler that is not of
the modulating type: If there is a 6 Million BTU Base Load
boiler running with (3) 2 million BTU HeatNet boilers, a
short cycling situation will arise when the (3) 2 million BTU
boilers are running @ 95% and the Base Load boiler is
called on. At this point there is a need for approximately 6
million BTUs. The (3) smaller boilers will then modulate
down to low fire. At this point, the (3) smaller boilers need
to shut off or the Base load boiler needs to shut off. There is
no overlap. A selection for stopping the boiler now needs to
be determined. Setting the Stop qualifier; Modulation to
40% or a low fire rate will shut the Base Load boiler off and
allow the (3) smaller boilers to modulate up again (short
cycle of the Base Load boiler; Use the Delay Timer and Min
OFF timer). The Stop qualifier; OA T > xxF may also be
used if the system design temperature is known. Then let the
Base Load boiler cycle off its limits, whether a 2 stage,
Hi/Lo, or modulating boiler. The default setting is for the
Base Load boiler to stop first once the water temperature
exceeds the top of the heating band.
Figure 19
Base loading relay
Page 19
HeatNet Control REV 3.37-1
Setting up base loading
The base load boiler is controlled using a set of contacts to
enable it (location J4). Enabling/Disabling this relay contact
can be done using any combination of (3) qualifiers to start
the boiler and (4) to stop the boiler. These qualifiers are:
1. Modulation %:
a. START menu item: The relay contact will close
when the MOD % from the Master boiler exceeds
this value. ADVANCE SETUP:BASE LOADING:
START>MOD
b.
STOP menu item
when the MOD % from the Master boiler falls
below this value.
LOADING: STOP<MOD
If the START>MOD value is set to a value
higher than the ADVANCED SETUP:MOD-MAX: all boilers will be firing before this
modulation rate is reached. This will ensure
that all available boilers are firing before the
base load boiler relay is enabled.
c. Setting the : STOP<MOD to a % value slightly
above the min fire rate % of the system will ensure
that the base load boiler will stop before the first
condensing boiler stops. This is due to the
Modulation rate being close to the min modulation
rate before the water temperature exceeds the top
of the heating band.
2. Outside Air Temperature:
a. START menu item: The relay contact will close
to enable the boiler when the OA T read from the
Outside Air Temperature sensor (if Equipped) falls
below this temperature. ADVANCE SETUP:BASE
LOADING: START< OA T
b. STOP menu item: The relay contact will open to
disable the boiler when the OA T read from the
Outside Air Temperature sensor (if equipped) rises
above this value. ADVANCE SETUP:BASE
LOADING: STOP> OA T
: The relay contact will open
ADVANCE SETUP:BASE
3. Return Water Temperature
a.
4.
START menu item
close to enable the boiler when the RET read
from the Return Water Temperature sensor (if
Equipped) falls below this temperature.
ADVANCE SETUP:BASE LOADING: START>
RET
b.
STOP menu item
to disable the boiler when the RET
temperature read from the Return Water
Temperature sensor (if Equipped) rises above
this temperature.
LOADING: STOP< RET
:
FIRST
a.
STOP menu item
to disable the boiler when the temperature
exceeds the heating band. This gives the
result of stopping the Base Load boiler First.
Default setting.
: The relay contact will
: The relay contact will open
ADVANCE SETUP:BASE
: The relay contact will open
Delay time
The DELAY TIME is also included to hold off starting the
boiler until the delay time is met. Once the start condition
qualifier term is met, the DELAY TIME will start counting
down. When the time expires, the base load relay contacts
will close. ADVANCE SETUP:BASE LOADING:DELAY TIME. It is adjustable in a range of: 0 to 60 minutes.
Base Load Failsafe
If there are no boilers available to fire (offline or faulted)
and there are no boilers in local override, and there is a call
for heat, The J4 Base Load relay will close. If a boiler
becomes available and needs to fire, the Base Load boiler
will remain firing until the temperature exceeds the band.
This is provided to keep the system from entering a no heat
situation.
Page 20
If the OA T qualifier is used as the Start and
Stop qualifier, ensure that there is at least a
few degrees difference for hysteresis.
Control Methods
Heating Control Methods
An overview of the (5) methods for controlling the Futera
series boiler are presented here. They are outlined in more
detail at the end of this section. See Figure 33, page 36,
through Figure 39, page 42.
Heating Method 1
The first method is to use the Futera Series boiler in its
stand-alone modulating method. This method uses a PID
algorithm to maintain a setpoint and is enabled using the
HEAT DEMAND input. Closing a relay contact or switch
across the HEAT DEMAND input will cause the Master
boiler to control all member boilers using H-Net.
A member boiler may also be controlled by the HEAT
DEMAND input (LOCAL mode). The member boiler will
then ignore commands from the Master and maintain its
LOCAL SETPOINT at the supply sensor.
Heating Method 2
The second method is to view the Futera boiler as two
separate boilers or as a HIGH/LOW boiler using T1 & T2.
Heating Method 3
The third method is to allow a remote 4-20 ma or 0-10 VDC
signal to control the firing rate (modulation) of the boiler
using the 4-20ma input, along with the 4-20ma REMOTE
ENABLE input.
Heating Method 4
HeatNet Control REV 3.37-1
Short cycling may occur when a firing rate is
sent to a member boiler that would cause the
supply temperature to rise high enough to trip
the operating limit (low flow rate). After the
supply temperature falls, the boiler would
restart and the process may continue. A
member boiler would use its supply (outlet)
sensor to protect itself from short cycling by
limiting the firing rate coming from the
Master. This occurs in the event that the
member’s supply temperature increases above
the (OPERATE LIMIT- OPERATE LIMIT
BAND).
Operating Limit
When the master boiler or an external control input is used
to control a member boiler (i.e. AA, T1-T2, 4-20ma, HNet), a software operating limit on the member boiler will
be used to limit the maximum output of the member boiler.
This operating limit can be adjusted in the
SETUP:SETPOINTS:OPERATING LIMIT.
There is also an associated operating limit band that must be
set in conjunction with the operating limit to help prevent
this LIMIT from being reached. Its purpose, is to limit the
output of the boiler as it approaches the operating limit. If
the band is set to 10 degrees, then for every degree that it
approaches the operating limit, the maximum output will be
lessened by 10%. With a band of 20 degrees, for every
degree that it approaches the band, the maximum output will
be lessened by 5%. You can think of this operating limit as
a smart aquastat which prevents the High Limit from
tripping. This method minimizes boiler short cycling when
using external inputs. The minimum setting is 1 degree and
effectively turns the limit band OFF. The default setting is
20F.
The fourth method turns the boiler ON and OFF @ 100%
modulation using the AA terminal.
Heating Method 5
The fifth method uses an RS485 digital communications
cable with the MODBUS protocol. The boiler is controlled
by writing and reading registers using MODBUS
commands. A bridge module may also be used to convert
BACnet or LonWorks protocols to MODBUS.
Input Priorities
The Futera-Series control inputs areprioritized so that
multiple levels of external control can be employed at the
same time. This means that if we are firing the boiler with a
low Priority input and a higher Priority input is called for,
the boiler will now fire at the higher Priority input. When
the high Priority input is removed, the boiler will revert
back to the lower Priority input that is still being called.
Priority 1
The AA terminal has absolute control, and if used, will
always fire the boiler at 100% output, regardless of any
other input. The 4-20mA input may be raised to this
Priority using ADVANCED SETUP: 4-20mA INPUT:PRIORITY.
Page 21
HeatNet Control REV 3.37-1
Priority 2
The HEAT DEMAND input is the next, and provides the
means to operate the boiler in LOCAL MODE when an
external control is not present, has failed, or needs to be
enabled or disabled. A member can override the H-Net
commands using this input.
Priority 3
If a HeatNet (H-Net) Network cable is connected between
boilers, and one is configured as a MASTER (requires
HEADER sensor), then the MEMBER boilers will be
controlled over the network by the MASTER.
Priority 4
The 4-20ma/0-10VDC input in tandem with the 4-20ma
REMOTE ENABLE input is next. Any signal over 4.02ma
or 2.01VDC will start and operate the boiler if the
REMOTE ENABLE is closed.
Priority 5
The lowest Priority is using the boiler as (2) stages
HIGH/LOW. These are the T1 and T2 inputs.
Figure 20
Heat demand input
Master boiler
The MASTER boiler controls the system using a PID
algorithm. Once the boiler is started, a PID algorithm is
used to produce a modulation percentage value from 0100%. This percentage is converted to a PWM, (P)ulse
(W)idth (M)odulation signal by each boiler. The
temperature of the water is maintained by sending this
PWM signal to the Variable Frequency Drive, which in turn
controls the blower motor. Since the main fuel valve is airfuel coupled to the blower, the speed of the blower provides
the firing rate.
Each of these control methods will now be explained in
more detail:
Heating Method 1
HEAT DEMAND
Closing a relay contact, switch, or jumper across the HEAT
DEMAND input will enable this method. This method
allows operation as a setpoint control. As a setpoint control,
the Master (defined by having a common system supply
header sensor), on the H-Net network can command the
boiler fire rate of all Member boilers. The Master can call as
many boilers that it has available (boilers are auto-detected
over the H-Net cable by the Master) to meet its SYSTEM SETPOINT. The H-Net cable must be connected and will
cause the amber light on the communications board to flash.
The amber light indicates an H-Net master is broadcasting
control information and a system heartbeat.
The AA terminal, the FAILSAFE mode active, 4-20ma at
PRIORITY:HIGHEST, and the HEAT DEMAND input
(LOCAL) on a Member, are the only inputs that will
override the H-Net control.
Member boiler(s)
A Member (lacking a common system supply header
sensor) boiler may also be controlled by the HEAT
DEMAND input (LOCAL mode). The member boiler will
then ignore commands from the Master and maintain its
own LOCAL SETPOINT at its supply sensor. This can be
viewed as a manual override on a member boiler. Be sure to
observe the use of the proper use of a Common System
Damper (See: AUXILIARY FUNCTION OPTIONS
section) and any system pumps or system common
interlocks.
Features of the HEAT DEMAND input include:
1. The control is designed to predict when to start and
stop the boiler and keep the setpoint in, or as close to
the control band as possible. If PREDICTIVE START
is enabled, the boiler may start when it is in the band
and not below it. This will help to maintain a more
accurate temperature relative to the setpoint. See also:
ADVANCED SETUP:FIRING MODE:PRDICTIVE
START: to disable this feature.
2. The control can also use the Outdoor Reset feature.
This feature allows the setpoint to be changed
automatically based on the outside air temperature. If
this feature is used, the control input: OR OVR
(OUTDOOR RESET OVERRIDE), can be used to
override the Outdoor Reset feature and run from the
local setpoint. A contact closure on the ‘AA’ input can
also override this method.
Page 22
3. Firmware Version 2.0 added a 4-20ma setpoint control
function that works in conjunction with this mode. This
Control Methods
HeatNet Control REV 3.37-1
function translates a 4-20ma control signal to a setpoint
mapped between 50F and 220F. These (2) temperatures
are adjustable to provide a setpoint range. The
minimum start current is also adjustable between 3.71
and 5ma. The setpoint control feature is used in
conjunction with the REMOTE ENABLE input on
J12A. This feature is enabled in the SETPOINTS menu
as:
SETPT SOURCE 4-20ma
4. Firmware version 2.2 added support for a common
system damper, Heat Exchanger support, and starting
the Master first for common venting. For an overview
of each of the menu settings see: DEFAULT SETTINGS section.
Heating Method 2
STAGE Control T1-T2
The boiler can also be operated in 2 separate stages using
the inputs T1 and T2 inputs. Its intended use is with an
external stage controller with no analog or modulation
outputs.
Heating Method 3
4-20ma Control
Placing a current source between the + and – 4-20ma inputs
will allow remote control of the boilers firing rate. An
adjustable starting mA current signal here will start and then
fire the boiler at the minimum fire rate. See: ADVANCED SETUP:4-20mA INPUT.
See section OPTIONAL FEATURES Using the 4-20ma
input for extensive detail.
A 20ma signal will fire the boiler at the maximum firing
rate. The input current signal is viewed as a percentage to
the boiler from 0 to 100% (0-20mA). This means that a
20% (4mA) input signal is required to start the boiler, but
since the boiler is classified as having example:4:1 turn
down ratio, the boiler can only be fired as low as 25% of
output. Any signal between 20% and 25 %, will fire the
boiler at the minimum fire rate. If the MINIMUM setting of
the boiler is set above the example: 4:1 turndown of 25%
(such as 33%), a control signal change between 25% and
33% will not change the boilers firing rate. Once the control
signal rises above the MINIMUM fire rate, the control
signal will then affect control of the boilers fire rate.
Closing only one of these contacts tells the boiler to operate
at MINIMUM FIRE.
1. Closing the other contact will fire the boiler at
MAXIMUM output (the same rate as closing the AA
input).
Figure 21
Stage control input
The AA terminal, the HEAT DEMAND, and the H-Net
NETWORK are the only inputs that will override the 420ma input.
Heating Method 4
AA Input
HIGH FIRE input Control: The AA input will fire the boiler
at HIGH fire (maximum output of the boiler). No other
inputs can override this input.
Figure 22
AA — High fire input
The maximum output of the boiler is based on
the MAX VFD setting in the calibration mode
and not the nameplate rating.
The AA, HEAT DEMAND (LOCAL) input, the H-Net, the
4-20ma input will all override the stage control inputs.
Page 23
HeatNet Control REV 3.37-1
Heating Method 5
MODBUS communications
The fifth method uses an RS485 digital communications
cable with the MODBUS protocol to control the boiler
using the H-Net network. The Boiler or Boiler network will
run as in Method 1, but instead of the HEAT DEMAND
input, a software form of the HEAT DEMAND input is
used (40001: Boiler/System Enable/Disable). See:
MODBUS COMMUNICATIONS section.
Figure 23
MODBUS connections — version 1.x board
Protocessor option
An optional BACnet or LonWorks bridge module can be
used to connect the MODBUS network to a BACnet or
LonWorks network.
Figure 25
Protocessor bridge module option
Figure 24
The System Setpoint Timer also needs to be loaded
periodically to allow the H-Net system to fallback to
Method 1 in the event communications is lost from the
Building Management System (BMS). The MODBUS
protocol allows writing and reading registers using
MODBUS commands.
MODBUS connections — version 2.x board
This method allows enabling and disabling the boiler or HNet system, changing setpoints, reading boiler(s) status, or
temperatures remotely using digital commands. See the
section:
Page 24
Optional Features
Using the 4-20ma input
The 4-20ma input is designed to operate per the ISA-50.1
standard. It will support Type 2, Type 3, and Type 4
Transmitter/Receiver circuits.
The Type 2 and Type 3 circuit may use the supplied +24VDC
and 24VDC RET connections (J10B) to power a remote
transmitter. The –ma terminal will need to have a jumper
connected to the adjacent 24VDC RET terminal to reference
the signal ground.
With the type 4 configuration, multiple boilers (up to 5), may
be connected in series using the –ma +ma –ma +ma scheme
(no jumper to 24VDC RET). This allows one 4-20ma
transmitter to control multiple boilers. A free-floating 250
ohm resistor is viewed by the BMS (or external control’s) 420ma transmitter across the + and –4-20ma terminals with
this method.
Figure 26
4–20ma connections
(OPTIONAL)
HeatNet Control REV 3.37-1
The 4-20 ma input uses a 250 ohm sense resistor to convert
the current to a voltage from 1 to 5 volts DC for the control to
use. For this reason, a 1-5 VDC control voltage may also be
used across the 4-20mA +/- input, but it still needs to supply
the necessary current, i.e. 20mA. This resistor is located on
the bottom side of the control board. When a 4.02 ma signal is
sensed, the boiler will initiate a start sequence and fire the
boiler at its minimum setting if the REMOTE ENABLE input
is closed. This is typically 25% of the boilers output (4:1
turndown).
If jumper shunt JP3 is set to the PWM/0-10 position, the 420mA input will accept a 0-10 VDC signal. The operating
range will be from 2-10 VDC or twice what was previously
stated for the 1-5 VDC functionality. To convert a 0-10VDC signal to mA, divide by 500 (ohms).
NOTE: Due to the inability of control voltage methods (1-5,
2-10 VDC) to reject noise, the use of the 4-20mA control
current is recommended. The control voltage methods may be
less expensive, but are the least stable. If using a 0-10VDC
control signal, a source current of 20mA is required.
If using a remote panel with a relay and a 4-20 ma transmitter
for operation, connect the 4-20ma transmitter output from the
remote panel to the member boilers using the floating 250
ohm method (type 4). The relay contacts on the remote panel
will then be connected to the associated 4-20ma REMOTE
ENABLE inputs on the associated boiler(s).
Figure 27
4–20ma enable connection
The minimum setting of the boiler is calibrated
so that the minimum PWM signal to control
the Blower motor is 20%. The VFD to blower
motor operates with a control signal from 20%
- 80% Pulse Width Modulation. This PWM
signal to the VFD can be measured using a
multimeter. It is a 0–10volt square wave signal
at 110 Hertz. A 20% modulation signal will
read 2.0 VDC, and an 80% modulation signal
will read 8.0 VDC on an RMS multimeter. See
Setpoint Control functionality can be implemented remotely
using the 4-20mA input. This function translates a 4 to 20ma
control signal to a setpoint mapped from 50F to 220F. The
feature is enabled in the SETPOINTS menu as: SETPT
SOURCE 4-20ma.
ADVANCED SETUP:4-20ma INPUT. Also, when
selecting; SETUP:SETPOINTS:SETPOINT SOURCE and
selecting 4-20ma, the 4-20ma INPUT menu will be
automatically entered.
You may now select the current at which the boiler will start.
It is adjustable from 3.7ma to 5ma. Hysteresis of .1ma is
always in effect. So, if the starting ma = 4.10ma the boiler
will start when the control current applied achieves this value
of 4.10ma. The boiler must drop .1ma below this to turn OFF,
Figure 44, page 47.
Page 25
in this example 4.00ma. This hysteresis value is not
adjustable.
HeatNet Control REV 3.37-1
Circulator Pump Options
When using the 4-20ma setpoint control, a band may now be
set at which the 4-20ma signal will operate over. The lower
setpoint is defined as 4ma SETPOINT and the upper setpoint
is defined as 20ma SETPOINT. The 4ma SETPOINT is
linked to the BOILER START x.xxma where this starting
current is the lower setpoint. So, if we set the 4ma
SETPOINT to 130F and the 20ma SETPOINT at 180F we
will have established the band. Once a starting control current
of BOILER START 4.1mA is applied, and the 4-20
REMOTE ENABLE INPUT is closed, the boiler will start and
the setpoint will be set to 130F. If a control current of 10ma is
applied the boiler will track on a linear slope towards the
20ma SETPOINT settling at a SETPOINT of ~149F. As the
current increases to 20ma, the SETPOINT will indicate 180F.
The Default setting is 4ma SETPOINT: 50F, and 20ma
SETPOINT 220F for backwards compatibility with the older
version. NOTE: anytime a new firmware version is uploaded
to the control, these values return these defaults.
Anytime a new firmware version is uploaded to
the control, these values return to these
defaults.
If using the direct modulation mode by applying a 4-20ma
current, only the BOILER START x.xx setting applies.
There are provisions for a system pump and a local pump.
This is to allow for primary/secondary loop configurations.
The system circulator pump is implemented using the K4
RELAY and normally open contacts at J13 BOILER
2/OTHER or marked SYSTEM PUMP depending on the
revision control board.
The pumps require motor contactors to isolate
the on-board relay contacts. The on-board
relays should never be used to energize pumps
directly.
Figure 28
Pump connections
Firmware Version 3.0 adds the ability to set the 4-20 mA
input to HIGH PRIORITY. This can be set in menu:
ADVANCED SETUP:4-20mA INPUT. This allows a
member boiler to be taken offline and directly modulated by
an external control. If the Master is using it for heating and
the 4-20mA is set to HIGH PRIORITY, an external control
can now output a 4-20mA signal which will take over the
boiler’s fire rate. This is typically used for DHW control.
The system circulator pump is supported by (2) modes and a
special feature.
1. The first mode will allow the circulator pump to remain
on, unless the control’s outside high air temperature
setting has been met when using OUTDOOR AIR
RESET.
2. The second mode will allow the circulator pump to be
turned on whenever there is a call for heat (any control
input). This mode will stop the circulator pump when the
call for heat is lost and the pump post purge time has
been satisfied.
The summer pump jog is a special feature that can be selected
when the system is in summer shutdown (OUTDOOR
RESET). The jog allows the system circulator pump to run for
the pump purge time once a week. It can be set to any day of
the week and will occur at 12:01 AM.
The system flow proving switch is implemented using
SPARE 3/System Water Flow on J11A. If a flow switch is
connected to the WTR FLW interlock, the HeatNet control
will wait up to 240 seconds to prove flow. This time is
adjustable under SETUP:PUMP OPTIONS. The default
flow proving time is 10 seconds. It can be increased to allow
Page 26
Optional Features
slower valves to open before flow is established. If flow is
interrupted after it has been established, an error will be
displayed and the boiler will cycle OFF. As long as there is a
call for heat, every 10 minutes the circulator pump will try to
re-establish flow and start the boiler again.
The local circulator pump is supported by (3) modes and (2)
features.
1. The first mode allows the circulator pump to remain on,
unless the control’s outside high air temperature setting
has been met when using Warm Weather Shutdown.
HeatNet Control REV 3.37-1
Auxiliary Function Options
Relay K5 and the terminal J13 DAMPER is used to control a
combustion air damper. The Spare 1 input on J10B or J12B is
used to detect the dry contact proof switch from the damper.
The J12B is the preferred connection, J10B is used for
backwards compatibility. A proof time of up to 4 minutes can
be set before the boiler can start or an alarm condition will
occur. The Combustion Damper can be setup in the
SETUP:AUX FUNCTIONS menu.
2. The second mode will allow the circulator pump to be
turned on whenever there is a call for heat (any control
input). This mode will stop the circulator pump when the
call for heat is lost and the pump post purge time has
been satisfied.
3. The third mode works much the same as mode 2, but it
allows the inlet sensor (RETURN) to be used with the
outlet sensor (SUPPLY) to keep the pump on until a delta
(difference) temperature is met. A return temperature
sensor is required for this mode, because the delta
temperature (SUPPLY – RETURN) measured is across
the boiler. In this mode, the post purge time is also used.
After the delta temp has been met, the post purge time
needs to expire before the pump is turned off. This mode
works much the same as mode 2.
PUMP/VALVE OPTION: This is a special feature of the
local circulator pump to prevent deadheading water flow
when all boilers are off. When this feature is enabled, the
master boiler will enable its local circulator pump/valve when
NO boilers are running. If boilers are running in LOCAL
override and not controlled by H-NET, but are visible to HNET, the pump(s) on these boilers are presumed ON. In this
situation, the master will not enable its circulator pump/valve
unless it is running.
Another feature of the PUMP/VALVE OPTION is to control
a local (primary) pump using a Variable Frequency Drive.
This feature may be required when a secondary system pump
is also variable speed. To enable this feature: SETUP:PUMP
OPTIONS:LOCAL PUMP PUMP/VALVE
OPTION:LOCAL PUMP VFD: ON. Setting this Option to
ON will map the control signal on J4 pins 1+ and 5- to the
modulation rate. (2) wires need to be run from J4.1+ and J4.5to the VFD’s input connection. Ensure that the J18 shunt
jumper on the control board is in position PWM/0-10.
The Master boiler controls the system damper, so in the event
this damper fails to open, the system will not start. If the
Master boiler’s system damper fails, then no call for heat will
be made to the member boiler(s).
Each member boiler can control its own damper and is
independent of the Master boiler when a call for heat is made
to the member. This allows for separate dampers for each
member boiler. They can be wired to J12B terminals 7 and 8.
If a common system damper is used (controlled by the Master
boiler), each individual boiler must prove that the combustion
air damper is open when it is placed in LOCAL. This may be
done using J12B terminal 7 on all boilers wired to the
damper’s prove switch. Terminal 7 is the sense input and
terminal 8 is 24 VAC. Connecting a wire to terminal 8 is not
recommended.
See Figure 45, Common system damper wiring, Page 48.
A separate/independent 24 VAC source is
recommended to be used for the damper prove
switch when a common system damper is used.
If you use terminal 8 to supply power from the
Maste,r and the Master is powered OFF, no
boiler will be allowed to fire due to the loss of
power through the prove switch. A backup
boiler will also need to have the damper relay
contacts wired in parallel with the Master for
when the Master is powered OFF.
A second wire on the Master J12B terminal 7 is then
connected. The other end of this wire is then run to the first
Member boiler J12B terminal 7. If another member boiler is
present, a second wire can be connected to the first member
boiler J12B terminal 7 and the other end connected to the
other boiler J12 terminal 7. This method can be continued if
additional boilers are present. This input must be selected in
the SETUP:AUX FUNCTIONS:COMBUST AIR DAMPER menu.
Outdoor Reset
The Outdoor reset feature allows the water setpoint
temperature to change dynamically with the outside air
Page 27
HeatNet Control REV 3.37-1
temperature. It also provides an adjustable temperature that
shuts the boiler/boiler system down when the outside
temperature rises above it. Firmware version 2.3 and up
separates the Warm Weather Shutdown from the Outdoor
Reset.
Figure 29
Water Temp
Outdoor reset curve, typical
WATER TEMPERATURE SETPOINT
190
180
170
160
150
140
130
1070
Outside Temp
With the WWS SETPOINT set to 72F and WARM
WEATHER SD set to ON, the boiler/system will enter
summer shutdown when the Outside Air temperature rises
above 72F. While in this state, the OR OVR input on J12A
can be used to bring the boiler/system on to maintain the
water setpoint at the LOCAL or SYSTEM SETPOINT value.
During WWS operation, the System pump will not be enabled
just the Local pump unless the SETUP:SYSTEM
PUMP:OVR ENAB IN WWS is set to ON. This is the System
Pump Priority mode. When SETUP:SYSTEM PUMP:OVR
ENAB IN WWS is set to OFF, the system pump will not
come on while in WWS with the OR OVR override input
closed.
Sensors
The H-Net control supports a standard 10K thermistor (Type
ACI/10K-CP). These sensors can be calibrated to the control
by entering the sensor menu and placing a precision 10k
resistor on an input.
Immersion sensors must have wells.
The above chart shows how the water temperature setpoint
changes with the Outside air temperature. The four values of
180, 10 and 140, 70 are the default values:
WATER TEMP
LOW OA TEMP
WATER TEMP
HIGH OA TEMP
WWS Setpoint 72°F
WARM WEATHER SD=ON
180°F
10°F
140°F
70°F
Water temp @
outside air temp
Water temp @
outside air temp
Outside air temperature
where Warm Weather
Shutdown occurs
If set to ON here
The chart depicts what the water temperature setpoint will
equal with a corresponding outside air temperature. At an
outside temperature of 10F and below, the water temperature
setpoint will be limited to 180F. With an outdoor temperature
of 70F and above, the water temperature will be limited to
140F. The water temperature setpoint will track along the
charts plotted line with corresponding outside temperatures.
The OR OVR (Outdoor Reset Override) input on J12A can be
used to override this Outside Air Setpoint and maintain the
water setpoint at the LOCAL or SYSTEM SETPOINT value
when a contact is closed across this input. This can be used as
a Domestic Hot Water demand input.
Another function of the OUTDOOR RESET is the
Winter/Summer mode ( (W)arm (W)eather (S)hutdown).
Security
A password can be used to lock out control and setup features.
It can be enabled, but is shipped in the disabled state.
Diagnostics
The H-Net control can display and identify faults in a
meaningful way. If an interlock trips, it will be indicated in
the main screen display, along with an audible alarm
(mounted on control board) and a set of relay contacts will
close. A record of this, with a time stamp, will also be entered
into the log as an aide in the diagnosis of the event. The log
can be downloaded and a histogram used to display the data.
If using Modbus, BACnet, or LonWorks, software flag bits in
registers are available.
Open and shorted sensors are checked continuously, so that in
the event of a sensor failure, the system shuts down and the
alarm relay is closed.
If a pump fails (flow switch required), or the flow switch
fails, the boiler will cycle the start condition every 10 minutes
in an attempt get the boiler restarted.
If the damper fails to open and never closes its proof switch, a
retry algorithm will attempt a retry. Every 10 minutes the
damper relay will cycle and try to open the damper again.
Page 28
Optional Features
HeatNet Control REV 3.37-1
If the H-Net control closes the last interlock string connected
to the ignition control and the ignition control never closes its
Blower Relay, the H-Net control will wait 2 minutes. The HNet control will then retry for the duration of the local pump
post purge time and then retry the ignition sequence. During
this time “retry strt” will be displayed in the status screen.
After (5) attempts the H-Net control will lock out and display
call service.
Communications
The H-Net control has the ability to communicate using the
MODBUS protocol with a building management system.
Most registers and functions are available for MODBUS
access. Access is allowed using the RS485 MODBUS PORT
connecter on the communication board. Version 2.x Control
has these connections integrated on the main board.
An optional BACNet or LonWorks bridge module can be
used to connect the MODBUS network to a BACnet or
LonWorks network. See Method 5 control.
The following are types of Failsafe conditions.
1. Building Management System Failure
If a BMS system is controlling the setpoint and enabling
the boiler system, a timer is provided to allow operation
of the system in the event that communications are lost
with the BMS system. The HeatNet boiler system will
run locally if communications is lost and this timer
expires due to the lack of being updated.
The system setpoint timer and system setpoint work in
tandem to externally control (i.e. a BMS - building
management system) the operating setpoint. The setpoint
(countdown) timer should be loaded with a timeout value
(in seconds) prior to writing the system setpoint. When
the timer reaches zero, the control assumes that the BMS
is no longer operating and the local setpoint (saved on the
control) is reloaded. If the setpoint timer is not written, a
default timeout value of 60 seconds is assumed. The
timer is automatically reloaded with the default value
when a setpoint is written.
The BMS mode is always on and no menu item
is available.
Failsafe Modes
FAILSAFE MODES have been added to help protect systems
from loss of heat conditions. When using one of these modes
ensure that you connect any DAMPER control, or system
pump control to safely allow operation with the assumption
that the MASTER boiler or BMS system is DOWN.
FAILSAFE REQUIREMENTS:
1. Since the Member boiler that will be assigned the
Failsafe duty will always turn the system pump ON, this
boiler should not be used for DHW heating. If the Master
controls the system pump, then the Failsafe Member
boiler would need to control the system pump in parallel
with the Master boiler. Wire the System Pump contacts in
parallel with the Master.
2. If the combustion air damper is used as a common system
damper, the Failsafe boiler should be wired to control the
damper in parallel with the Master boiler.
3. The Failsafe boiler must have the LOCAL SETPOINT
set to the same setpoint temperature as the Master
boiler’s SYSTEM SETPOINT.
2. HeatNet Communications Lost
SETUP:AUX FUNCTIONS:FAILSAFE MODES:HNET COMM LOST:
This mode allows a member boiler to run in LOCAL if
the communications link via the H-NET cable is lost.
This includes the MASTER boiler losing its Control
board, Communications board, or the power on the
MASTER is switched OFF. When this MODE is set to
ON, and if the member boiler loses it’s link (heartbeat
packet over the H-NET cable) to the MASTER Boiler,
this MEMBER will fire to the LOCAL setpoint.
The heartbeat packet over the H-NET cable
needs to be lost for 10 minutes.
This MEMBER boiler will continue to run at the LOCAL
setpoint until H-NET communications from the
MASTER boiler is re-established.
Ensure that this Member boiler’s Damper and System
pump control are configured correctly with the
assumption that the Master is not powered. Also ensure
that any other System settings related to outside air
temperature sensing and system interlocks are set to
provide safe operation.
Be aware that the boiler may start without a call-for-heat in
the FAILSAFE MODES. FAILSAFE MODES can be
accessed through the:
SETUP:AUX FUNCTIONS:FAILSAFE MODES.
Page 29
3. Low Temperature Protection
LOW TEMP: OFF, SUPPLY, HEADER, DHW,
or RETURN
This mode may be used by the MASTER or MEMBER
boiler and can be used as a type of freeze protection. In
this mode you may select which Sensor you wish to
monitor, or you may opt to turn this mode OFF. If you
select a sensor, you may then associate it with a
temperature at which the boiler will turn ON. Once the
temperature at this sensor falls below the LOW TEMP
temperature the boiler will start and fire to its LOCAL
setpoint. Once the Boiler reaches it’s setpoint it will turn
OFF.
4. Using the Base Load Relay (Version 2.x)
If there are no boilers available to fire (offline or faulted)
and there are no boilers in local override, and there is a
call for heat, The J4 Base Load relay will close. If a
boiler becomes available and needs to fire, the Base Load
boiler will remain firing until the temperature exceeds the
band. This is provided to keep the system from entering a
no heat situation.
HeatNet Control REV 3.37-1
Version 2.x Control
The second generation HeatNet control incorporates some
new and additional features. The firmware automatically
detects the presence of the version 2.x control. These features
include:
1. Support for Domestic Hot Water using a temperature
sensor or a dry contact from a tank thermostat. Also, a
separate relay contact for a DHW pump or Valve is
provided.
2. On-Board HeatNet and Modbus connections. Also, added
a second terminal connector for daisy chaining the H-Net
connections when using shielded wire.
3. Added a low fire hold switch for ease in calibrating.
4. Added a ‘U’ shaped socket system for mounting the
Protocessor module. No other wiring connectors are
required when connecting BACnet & LonWorks, other
than the BACnet or LonWorks network cable.
5. Support for the Futera III XLF with 12 VDC, 1 amp
power control for the Pilot assembly.
6. Interlock string is now fused with a resettable fuse
onboard (F4).
Page 30
Optional Features
JPS1
HeatNet Control REV 3.37-1
Domestic Hot Water Methods
The Version 2.x control supports Domestic Hot Water control
using (4) methods. When using the Domestic Hot Water
methods, the wire jumper, JPS1 on each control board
providing Domestic Hot Water, must be cut to limit the
boiler’s maximum output temperature of 200F. Refer to
Figure 42 for control input and output locations.
Figure 30
Jumper JPS1
This method works with (2) settings. A target tank water
setpoint (DHW SETPOINT) and a start/add boiler
temperature setting (DHW DIFF). Boilers are started as long
as the tank’s water temperature is below the (DHW
SETPOINT – DHW DIFF). The first boiler is started
immediately. The next boiler(s) is started after the ADD
BOILER DELAY time expires. Boilers are not added when
the temperature is above the (DHW SETPOINT – DHW
DIFF) and below the DHW SETPOINT. Once the DHW
SETPOINT is reached all boilers shut off. This limits the tank
temperature to the setpoint + post purge time of the DHW
pump.
Setting up this method is done via the menus in:
SETUP:DOMESTIC HOT WATER.
1. Connect a 10k thermistor from the DHW tank’s
sensor well to J10B terminals 1 & 2 on the DHW
MASTER, or stand alone boiler. Wire any pump
or valve from the DHW Pump relay (normally
open) contact to control flow of the heating water
into the tank’s coil.
2. Next, enter the DOMESTIC HOT WATER menu.
When prompted for DHW BOILER?, enter NO.
We will enter YES when we are finished entering
all parameters
The following Domestic Hot Water setup information will
include a walkthrough using the menus.
DHW METHOD 1: DHW Tank Sensor
Input
Available on V2.X Controls ONLY
DHW METHOD 1a: DHW Heating ONLY using a
Single Boiler or a DHW MASTER and Member
boiler(s) employing H-Net
This method utilizes a 10k thermistor connected to the DHW
Sensor input of a DHW MASTER, or a stand alone boiler,
and a DHW tank WITHOUT a HEADER sensor. It requires a
DHW setpoint and other parameters to be set. This method is
used when the water temperature in the tank needs to be no
greater than the setpoint, with little overshoot of temperature.
One of its limitations is that it may short cycle. It functions
much in the same way a tank thermostat works.
3. Change the DHW SETPOINT to the desired
target temperature of the water in the tank. Once
the control determines there is a call for DHW,
the DHW SETPOINT is loaded and the Master
boiler will target this new setpoint.
4. Now, change the DHW DIFF to the desired
differential. This setting corresponds to the
minimum water temperature required in the tank.
DHW heating will be initiated when the DHW
tank’s water temperature is below the DHW SETPOINT – DHW DIFF.
5. How long the temperature of the tank stays below
the (DHW SETPOINT – DHW DIFF) is used to
determine when boilers are started along with the
ADD BOILER DELAY.
6. Scroll down to USE SENSOR? Press the
SELECT key and select YES, then press the
SELECT key again. This will allow the boiler to
control the tank temperature using its sensor.
7. Press the DOWN arrow key again to position the
cursor beside the menu item DHW PRIORITY?.
Setting this value to YES will turn OFF the
system pump when the DHW mode is active.
Setting this value to NO leaves the system pump
on.
8. Press the DOWN arrow again and the menu item
POST PURGE should appear. This is the time
that the DHW pump relay remains energized after
the DHW SETPOINT has been satisfied. Once
Page 31
HeatNet Control REV 3.37-1
the tank has reached setpoint all boilers will shut
off. Using the POST PURGE time to dump the
boiler’s heat into the tank may heat the tank
above the setpoint temperature. Care should be
taken here.
9. Press the DOWN arrow again and the menu item:
DHWMASTER?, will be displayed. If this item is
set to YES, once the DHW MASTER receives a
HEAT DEMAND signal, it will call other boilers
it has available using H-Net. Setting to NO,
requires no Heat Demand signal, and will only
enable the single boiler when the DHW Tank
Temperature drops below (DHW SETPOINT –
DHW DIFF).
NOTE: DHW MASTER? YES is to be only be
used WITHOUT a Header Sensor.
10. Finally, go to DHW BOILER?. Select YES. If
JPS1 has not been cut, a message will appear
instructing to do so. Once this is done, the stand
alone boiler will control the temperature in the
tank, or the DHW Master will control the
temperature in the tank using as many boilers as
it has available on H-Net.
NOTE: DHW BOILER? Does not need to be
set to YES on MEMBER boilers, only the DHW
MASTER or on a stand alone boiler providing
DHW.
NOTE: JPS1 MUST be cut on all boilers
providing DHW.
DHW METHOD 1b: Combo DHW and Space
Heating using a MASTER Boiler and Member
boiler(s) employing H-Net
This method utilizes a 10k thermistor connected to the DHW
Sensor input of a MASTER boiler, a DHW tank AND a
HEADER sensor. This Method works the same as DHW
METHOD 1a, but also has the ability to provide space
heating.
Setting up the DHW portion of this method is done via the
menus in: SETUP:DOMESTIC HOT WATER. For
information on setting up the space heating portion of the
method Refer to Heat Demand Control Method 1 located in
the CONTROL METHODS section on page 22.
1. Connect a 10k thermistor from the DHW tank’s
sensor well to J10B terminals 1 & 2 on the
MASTER, and connect a Header Sensor to the
SYSTEM HEADER input. Wire any pump or
valve from the DHW Pump relay (normally open)
contact to control flow of the heating water into
the tank’s coil.
2. Next, enter the DOMESTIC HOT WATER menu.
When prompted for DHW BOILER?, enter NO.
We will enter YES when we are finished entering
all parameters
3. Change the DHW SETPOINT to the desired
target temperature of the water in the tank. Once
the control determines there is a call for DHW,
the DHW SETPOINT is loaded and the Master
boiler will target this new setpoint.
4. Now, change the DHW DIFF to the desired
differential. This setting corresponds to the
minimum water temperature required in the tank.
DHW heating will be initiated when the DHW
tank’s water temperature is below the DHW SETPOINT – DHW DIFF.
5. Since the same the ADD BOILER DELAY time
is used for space heating and DHW, how long
the temperature of the tank stays below the
(DHW SETPOINT – DHW DIFF) has to be
considered when setting the ADD BOILER DELAY.
6. Scroll down to USE SENSOR? Press the
SELECT key and select YES, then press the
SELECT key again. This will allow the boiler to
control the tank temperature using its sensor.
7. Press the DOWN arrow key again to position the
cursor beside the menu item DHW PRIORITY?.
Setting this value to YES will turn OFF the
system pump when the DHW mode is active.
Setting this value to NO leaves the system pump
on.
8. Press the DOWN arrow again and the menu item
POST PURGE should appear. This is the time
that the DHW pump relay remains energized after
the DHW SETPOINT has been satisfied. If there
is no HEAT DEMAND signal, once the tank has
reached setpoint all boilers will shut off, and the
post purge time will begin. If there is a HEAT
DEMAND Signal when the tank has reached
setpoint, the boilers will continue running to
provide space heating, and the DHW pump relay
will be de-energized immediately. Using the
POST PURGE time to dump the boiler’s heat into
the tank may heat the tank above the setpoint
temperature. Care should be taken here.
9. Press the DOWN arrow again and the menu item:
DHWMASTER?, will be displayed. Set it to NO
for this DHW Method.
NOTE: This DHW Method requires no Heat
Demand signal to control the temperature in the
tank. As soon as the DHW Tank Temperature
drops below (DHW SETPOINT – DHW DIFF) a
boiler will be enabled.
Page 32
Optional Features
HeatNet Control REV 3.37-1
NOTE: DHW MASTER? YES is only to be
used WITHOUT a Header Sensor. When both a
Header Sensor and a DHW Tank Sensor are
installed, because it has a HEADER Sensor, the
Boiler will recognize itself as a MASTER.
When DHW BOILER? is also set to YES, the
MASTER will automatically call on other boilers
when the DHW Tank Temperature drops below
(DHW SETPOINT – DHW DIFF) even when no
Heat Demand signal is present. However, the
MASTER will only enable boilers for space
heating in response to a Heat Demand signal.
10. Finally, go to DHW BOILER?. Select YES. If
JPS1 has not been cut, a message will appear
instructing to do so. Once this is done, the
MASTER boiler will control the temperature in
the tank using as many boilers as it has available
on H-Net.
NOTE: DHW BOILER? Does not need to be
set to YES on MEMBER boilers, only the
MASTER boiler.
NOTE: JPS1 MUST be cut on all boilers
providing DHW.
DHW METHOD 2: DHW Header
Sensor Input
the tank setpoint is set to 140F and the heat band
is set to 10F, then the tank temperature will rise
to 145F before the first boiler turns off (setpoint
=140F +/-heat band/2). With (2) boilers running,
the SHED BOILER DELAY time could add to
the tank temperature. So, to ensure that all boilers
are shut off at the upper point of the heat band,
set the SHED BOILER DELAY time to 0. This
will effectively turn off all boilers at the upper
heat band point of: (example) 145F.
Now, there is one more thing to consider, the
pump’s post purge time. Dumping the heat from
all boilers (that were running) using a pump post
purge cycle will have an effect on the tank’s
water temperature. Consider this when
establishing the local pump’s POST PURGE TIME.
3. Connect the Local Pump relay contact on J13 to
enable the DHW pump. Set its post purge time to
dump the boiler’s heat into the tank when the
boiler shuts off. Be aware that this may heat the
tank above the setpoint’s upper heat band
temperature.
4. Enable the system by placing the
LOCAL/REMOTE switch on the Master to the
LOCAL position.
Available on both V1.X and V2.X Controls
1. This method will control a tank temperature when
the tank temperature setpoint needs to be
maintained for extended periods with minimal
cycling. Multiple boilers can be used via the HNet, as this method employs the same PID
algorithm as for space heating. For this method, a
tank temperature band needs to be tolerated.
JPS1 MUST be cut on all boilers providing DHW
to ensure the maximum output temperature of all
boiler is limited for DHW operation.
2. Use the Heat Demand Control Method 1
located in the CONTROL METHODS section on
page 22. Instead of placing the Header sensor in
the Header pipe, place it in a well in the tank.
The temperature at which boilers are staged ON,
and then OFF is controlled by the
SETUP:BOILERS:HEAT BAND differential.
This can be understood by referring to the
INTRODUCTION section on the MASTER in
the beginning of this manual.
This differential has the added effect of heating
the tank above the tank’s setpoint temperature. If
DHW METHOD 3: Space Heating
with DHW Override
Available on both V1.X and V2.X Controls
This method is for controlling DHW utilizing a tank
thermostat connected to a Master or Member boiler.
This method can be used instead of the 10k thermistor
sensor. When the thermostat contact closes across the
input OA OVR (J12A .7 & .8), the control will sense
this closure and enter the DHW heating mode.
In this mode, the boiler will fire to 100% and be
regulated by the OPERATE LIM setting located in
SETUP:SETPOINTS. The OP LIM BAND can be
used to keep the boiler from short cycling too much
by limiting the firing rate as it approaches the
OPERATE LIM.
1. Wire the dry contact from the thermostat on the
tank to the input on J12A terminal 7 & 8. Also, at
this time wire any pump or valve from the DHW
Pump relay (normally open) contact (J13
Page 33
HeatNet Control REV 3.37-1
terminals 9, 10) to control flow of the heating
water into the tank’s coil.
2. Enter the DOMESTIC HOT WATER MENU.
When prompted for DHW BOILER?, enter NO.
We will enter YES when we are finished entering
all parameters
Follow the same steps as used to program the 10k
thermistor sensor method, but when asked to
USE SENSOR?, select NO.
Set the DHW MASTER to NO. A thermostat
can only control (1) boiler. H-Net is not available
with a thermostat on the tank.
Go to the DHW BOILER?, enter and select
YES. The Master or Member will now control
the temperature in the tank.
DHW METHOD 4: DHW using Direct
Control
Available on both V1.X and V2.X Controls
Firmware Version 3.0 adds the ability to set the 4-20 mA
input to HIGH PRIORITY. This can be set in menu:
ADVANCED SETUP:4-20mA INPUT. This allows a
member boiler to be taken offline and directly modulated by
an external control.
If the Master is using it for heating and the 4-20mA is
set to HIGH PRIORITY, an external control can now
output a 4-20mA signal which will take over the
boiler’s fire rate and override all other heating
demand inputs. This is typically used for DHW
control.
Page 34
REV 3.37-1 Futera III • XLF • Fusion — HeatNet Control manual HN-IOM-2 / 3382-0331
Wiring Connections
Figure 31
Power connections —
Version 1.X control factory wiring (blue pc board)
Figure 32
Power connections —
Version 2.X control factory wiring (green pc board)
Page 35
HeatNet Control REV 3.37-1
Figure 33
Heating Method 1 H-Net, Master/member —
Version 1.x control (blue pc board)
Page 36
Wiring Connections
HeatNet Control REV 3.37-1
Figure 34
Heating Method 1 H-Net, Master/member —
Version 2.x control (green pc board)
Page 37
HeatNet Control REV 3.37-1
Figure 35
Heating Methods 2 and 4: AA-High Fire and High/Low, master or member boiler
(Version 1 board = blue; version 2 board = green)
Page 38
Wiring Connections
HeatNet Control REV 3.37-1
Figure 36
Heating Method 3 4–20 ma —
Version 1.x control (blue pc board)
24VDC
Modulation Control
Input
4-20ma/0-10vdc -
4-20ma/0-10vdc +
24VDC Return
Jumper in this
position for
4-20ma
Closing Contact here
enables the 4–20 ma
control input.
This Method allows direct modulation of the boiler based on a 4-20 mA control
signal. A control capable of transmitting a 4-20mA/0-10 VDC control signal for the
purpose of modulating a boiler and to control a common system temperature must
be used with this method.
NOTE: If using a 0-10 VDC signal multiply any references to current in the
manual by .5. Example: 5ma * .5 = 2.5 VDC
Temperature sensors (Top board, version 1 = blue / Bottom board, version 2 = green)
Page 45
HeatNet Control REV 3.37-1
Figure 43
OUTDOOR
SENSOR
North Away
From Exhaust
#1
Typical Single Boiler System (version 2, green pc board, shown)
LOCAL PUMP
ENABLE #8
FLOW PROVE
#10
RETURN
SENSOR
#3
BOILER
COMBUSTION
AIR DAMPER
ENABLE #7
PROVE #11
HEADER SENSOR
(Determines Master Boiler) #4
SYSTEM PUMP
ENABLE #14
FLOW PROVE #9
SUPPLY
SENSOR
#2
DHW RETURN
DHW SUPPLY
DHW TANK
AQUASTAT
#13
DHW TANK
SENSOR #5*
DHW TANK
DHW PUMP
ENABLE #12
#9
High Limit
IGN Control
Connections
#8#14 #7
#10
#12
Heat Demand*
#2#1
#3
#4
#5
#13
*Note: When using DHW
MASTER? YES, a Heat
Demand signal must be used
to activate the system.
#11
Page 46
Wiring Connections
HeatNet Control REV 3.37-1
Figure 44
Using a 4–20ma signal for direct modulation
Page 47
HeatNet Control REV 3.37-1
Figure 45
Common system damper wiring
Connection if Member
boiler is running as
Failsafe
MEMBER BOILER 2
MEMBER BOILER 1
DAMPER
Prove Switch
DAMPER
Enable
MASTER BOILER
NOTE:
Combustion Air Damper is enabled
on all Boilers for use.
SETUP MENU:AUX FUNCTIONS
24 VAC
24 VAC Ret
Ensure that the
DAMPER 24 VAC
Transformer
Mains
Page 48
DAMPER
Connect to 24 VAC
Return on each Boiler
Wiring Connections
HeatNet Control REV 3.37-1
Figure 46
Failsafe common system pump wiring
120 VAC Return
DPST
Relay
Add additional relays/
contacts for more
boilers
MEMBER BOILER 1
System Flow
Prove Switch
120VAC
System Pump Voltage Return
120 Return
System Pump
System Pump
Contactor
MASTER BOILER
120VAC
System Pump Voltage Feed
Ph2
Ph3
Page 49
Calibration
A detailed startup and walkthrough of the calibration and HNet setup is provided in the Programming Examples
manual.
The calibration of the Futera-Series
boiler should only be performed by a
licensed technician.
To enter the calibration menus, place the S2 switch on the
main control board to the CAL position.
Be sure to set this switch back to NORM when the
calibration is complete, otherwise no external control inputs
will work (except T1-T2), the display will always indicate
CALIBRATE and some of the runtime temperatures will
not be displayed.
The MIN VFD setting, the MAX VFD setting, and the
Ignition setting can be adjusted in the calibration displays.
The values can be changed while running ONLY IN MINIMUM FIRE (any, but only one of the T inputs closed).
Prior to ignition, the values may be changed, but the blower
will not operate.
HeatNet Control REV 3.37-1
Press the arrow keys until MIN VFD is shown in the
display, along with the minimum percentage value at which
the boiler is to run at min fire. While in Standby (no call for
heat on inputs), the minimum percent may be preset. To set
the minimum rate while running, any (1), and only (1) of the
(T) inputs must be closed in order to set the boiler to
MINIMUM fire. Press the SELECT key for approximately
1 second. The Percentage value will start flashing,
indicating that it can be adjusted. Adjust the Minimum value
to the desired setting using the arrow keys. The Minimum
setting is clamped to its lowest rated setting and cannot be
adjusted below this. Once you are done with this setting,
press the SELECT key until the value stops flashing. The
new setting is now saved.
Press the Arrow key to select the IGNITION percent. The
Blower speed will be set here to provide the rate for
ignition. While in Standby (no call for heat on inputs), the
Ignition percent may be preset, before firing the boiler. To
set the ignition rate while running, any (1), and only (1) of
the T inputs must be closed Pressing the SELECT key here
will cause the IGNITION setting to flash and the boiler will
ramp to the ignition setting. Adjust it using the arrow keys
and then press the SELECT key until the value stops
flashing. The new setting is now saved.
If a version 2.0 control board is used, a Low
Fire Hold switch is located near the
Calibration switch.
Page 50
Log Entry
Log Entry
The Futera-Series H-Net control contains a log that records
the major activity (events) in the operation of the boiler.
This activity includes interlock faults, boiler starting and
stopping events, power cycles, misc. faults, and types of
calls-for-heat (control inputs). Setting the time clock to an
accurate time and date is very useful when events are
recorded, since the control will time stamp each snapshot. If
the system is configured to run with HeatNet, then only the
Master boilers SYSTEM TIME needs to be entered. The
Master will then set the time on all Member boilers.
The log is primarily used as a troubleshooting and
diagnostic tool, but may be used as a performance tool to
view run time cycles.
HeatNet Control REV 3.37-1
Valve, Pilot Valve, Blower, and the Ignition alarm). The #
of boilers that are displayed is limited to 7 if the boiler is the
MASTER. If boilers #8 and up need to be viewed, the
Boiler Control Pro software will need to be used. The Last
2 characters on the fourth line indicate the heating mode the
control is in. The modes are:
NC = No Call for Heat
HD = Heat Demand (MASTER and Local modulation
control using PID control, MASTER and
MEMBER)
RM = Remote Modulation from 4-20ma input
HF = High Fire from ALL T-inputs closed or the AA
input
1T = Low Fire from any 1 T-input closed (Low Fire or
High Fire)
An event in time of the boiler’s state is presented via
multiple screens. Each screen event can be stepped through
using the arrow keys.
The top line displays the time and date the event occurred.
In the top right corner, the event # is displayed so that easy
indexing can be done using the arrow keys. The second line
displays the Water temperature of the boiler’s output
(supply) and the Setpoint temperature. The third line
displays the Outside Air temperature, and the Modulation
PWM signal sent to the Variable Frequency drive (20%
=min, 80% =Max). The bottom line is used to record the
control state of the boiler.
The control state is defined as the Boiler(s) that is running,
the Circulator Pump state, and the ignition condition (Main
Figure 47
Log entry display
Time
2T = Mid Fire from any 2 T-inputs closed (Low fire or
High Fire )
OP = Option input Active
HT = H-Net Control using the Heat-Link
communications cable
The bottom line is also used to indicate an interlock or limit
that has tripped. It may also indicate a sensor that has failed.
When this occurs, the normal bottom line in the display is
not visible, and the sensor fault is displayed.
For details on messages that appear on the fourth line: See
Appendix B.
Stamp
Event
number
Water Setpoint
: 0 5 : 4 2 P
3
H2O1 2 7 °F
Outside Air
Temperature
OA
Boiler 1 On
Boiler 2 On
Boiler 3 On
D = DHW Pump
6 5 °F
- - - - - -
1
Boiler 7
P = Circulator Pump
S = System Pump
(Ver 2.x control)
M = Main Valve open
P = Pilot Valve open
1 0 / 1 4
SET
MOD%
P
M
PB
1 3
1 4 0 °F
5 7
HHD
H= Honeywell Alarm
B = Blower ON
Modulation PWM %
NC = No Call for Heat
HD = Heat Demand
RM = Remote Mod 4-20ma
HF,1T, 2T, 3T = T-inputs Fire Rates
HT = H-NET Control
Page 51
DEFAULT
BOILERS
SETPOINTS
OUTDOOR AIR RESET
PUMP OPTIONS
Default Settings & Menu Item Descriptions — SETUP
HeatNet Control REV 3.37-1
MENU
# OF BOILERS 1 (1-16)
LEAD BOILER # 0 (0-16)
LEAD BOILER # 0 (0-16)
HEAT BAND
HNT M (M-16)
LOCAL SETPT
OPERATE LIMIT
LOCAL SETPT
OP LIM BAND
SETPT SOURCE AUTO
VALUE
30 °F (2 -50°F)
160 °F (40-220 °F)
215 °F (45-230 °F)
160 °F (40-220 °F)
20 °F (1-50°F)
RANGE DESCRIPTION
AUTO
4-20mA
If operating as a member.
# of first boiler to run, determines the fire order in rotation. A
# of first boiler to run, determines the fire order in rotation. A 0
disables the Lead Boiler function. Firing Mode determines lead.
Differential temp around setpoint used to stage boiler(s) OFF/ON
This line displays the boilers auto detected by H-Net. While M is the
Master boiler the numbers are the H-Net address of each boiler from
2–16.
Local setpoint used to maintain temperature of SETPT SOURCE
When running as a member, boiler shuts off when supply
temperature reached.
Boiler restarts at lower temp of OP LIM BAND or 10F whichever is
lower
Local setpoint used to maintain temperature of SETPT SOURCE
Limits external input % when in (OP LIM - OP LIM BAND)
AUTO = Local/ System/ WWS Setpoint is used
4-20mA input is mapped to a setpoint.
OA RESET OFF
WARM WEATHER SD NO
WWS SETPOINT
SET OA SETPOINTS
WATER TEMP
At
HIGH OA TEMP
WATER TEMP
At
LOW OA TEMP
SYSTEM PUMP
POST PRGE TIME 2 minutes (2-60min)
ALWAYS ENABLED OFF ON/OFF
SUMMER PUMP JOG OFF
OVR ENAB IN WWS OFF ON/OFF
68 °F (40 – 100 °F)
140 °F (60 – 150 °F)
10 °F (-35 – 40 °F)
ON/OFF
MON-SUN
Outdoor reset ratio (boiler water temp/outside air temp).
If set to YES, the boiler /system shuts down when the
temperature exceeds the WWS SETPOINT.
Temperature at which boiler shuts down, operation is below this.
If boiler is running using either OA RESET or WWS and the OA
OVR input is closed the OA RESET slope is overridden and runs at
local setpoint until OA OVR input opens.
Boiler water temp setpoint when OA temp is at HIGH
OATEMP These four setpoints determine the OA reset slope.
Header/Supply setpoint when OA Temp is at LOW OA TEMP
Time in minutes to keep system circ. pump on after boiler stops
ON = Pump never shuts off.
Used with Outdoor Reset, Jogs pump for POST PRGE time when
system is in summer shutdown. Jog once a week @12:00 AM.
Priority mode for the system pump while in Warm Weather
hutdown. ON: The system pump is allowed to run in WWS when
the OR OVR override input is closed. When set to OFF, the system
pump will not come on while in WWS with the OR OVR override
input closed.
Page 52
Default Settings & Menu Item Descriptions
20mA signal from J4 pins 1 & 5 that is
NIGHT SETBACK
OPTIONS
LOG/RUNTIME
LOCAL PUMP
DELTA TEMP ENAB OFF
DELTA TEMP 10 °F
POST PRGE TIME 2 minutes (1-60min)
ALWAYS ENABLED OFF
PUMP/VALVE OPTIONS
MASTER PUMP/VALVE
REMAINS ON: OFF ON/OFF
LOCAL PUMP VFD OFF ON/OFF
FLOW PROVE 10s 10-240 sec
(2 - 50°F)
ON: Use Delta temperature to shut pump off when temperature
across boiler is less than DELTA TEMP setting.
Time in minutes to keep local circ. pump on after boiler stops
Pump never shuts off.
ON: The master boiler will keep its pump/valve on when no boilers
are running. Prevents deadheading the system flow.
ON: Outputs a 0-10VDC or 4proportional to the fire rate of the boiler. Connect to a
VFDcontrolling a Local pump.
This is an adjustable flow proving time to allow slower valves to
open before proving flow.
HeatNet Control REV 3.37-1
SETBACK ENTRY 1 (1 – 4)
ENTRY IS OFF
SETBACK
START DAY MON
TIME 12:00AM
END DAY MON
TIME 12:00AM
TEMP SCALE
KEY CLICK ON
SKIP PASSWORD ON
BRIGHTNESS 50% (25, 50,75,100)
RUN HOURS
DATA LOG ENTRY
SIZE
BOILER CYCLES
20 °F (0 – 50 °F)
°
F
(F or C)
Four setbacks to adjust setpoint during a time period
Enable or disable the use of this setback
Temporarily subtracts this temp from the setpoint
Day of the week to begin setback or a day range
Time to begin setback
Day of the week to end the setback or a day range
Time of the day to end the setback
Fahrenheit scale is default
Beeps when a key is pressed
Disables the Password
Four levels of display brightness, lower for longer life of the display
Displays runtime hours. Total time the main valve has been open.
Displays the current entry in the data log
Displays the current size of the log in entries
Displays completed boiler cycles. Incremented when the main valve
turns OFF after it has been ON. Does not include attempts to light.
Page 53
COMBUST AIR
DAMPER
IN USE? YES
INPUT: J10B DAMPER
PROOF TIME 2:00 (0 – 4min)
ALARM SILENCE
ALARM SILENCE IN
USE?
INPUT = J10B SPARE 2
FAILSAFE MODES
RUN IN LOCAL IF:
H-NET COMM LOST
LOW TEMP OFF
TEMP < 40F
LINKED/COMMON
YES
OFF
40 °F 35-200 °F
AUX FUNCTIONS
INDEPENDENT
HeatNet Control REV 3.37-1
The LINKED/COMMON setting allows one common damper to be
used and controlled by the Master Boiler. All Member boilers must
have their damper prove inputs wired as per Figure 45, Common
system damper wiring, page 48. Also see Section: Optional Features: Auxilliary Function Options INDEPENDENT: Individual
dampers are in controlled by their respective boiler.
If set to YES, then OUTPUT RELAY K5 can be used to control a
combustion air damper. The Master can control a common system
damper or an individual damper. Members control their respective
damper independent of the Master. Relay K5 is used to enable the
combustion air damper. See Figure 45, Common system damper
wiring, page 48. Needs to Prove the damper is open.
There are (2) inputs that may be used for the Combustion Air
Damper. The first is located at J10B terminals 1 and 2 (legacy
compatibility). The second input is located at J12B terminals 7 and 8.
This is the proving time in minutes for the combustion air damper
prove switch. It is sensed at SPARE 1 on J10B or J12B Pin 7. If
J10B is used (legacy), Sensor #5 must be set to ON/OFF in the
sensors menu in order to detect the prove switch being made. If the
damper faults, a retry will occur every 10 minutes in attempt to open
the damper.
If Using J12B in a common damper configuration, wiring is done
beginning with the Master boiler. J12B Pins 7,8 are connected to the
prove switch of the combustion damper. Pin 8 is supplying 24 VAC
and pin 7 is the sense input. A second wire is connected to J12B pin
7 of the Master and the other end connected to the first member
boilers J12B pin 7. If another member boiler is present, connect
another wire to the J12B Pin 7 terminal of the first member and the
other end to the second member boiler J12B pin 7. Continue this
method for each additional boiler.
This menu allows the configuration of the Alarm Silence switch. It
can be disabled so that the Alarm Silence switch can not silence the
alarm until the alarm is cleared; ALARM SILENCE = NO. The
default value is to enable the ALARM SILENCE switch.
This setting allows the Alarm Switch to be looked at using another
input. This input should not be changed, but allows for custom
configurations to resolve conflicts.
If this entry is set to ON and the Member boiler does not see any
communications coming from the Master boiler, this boiler will run
in LOCAL. The boiler will continue to run in LOCAL until
communications is re-established or this entry is set to OFF.
This entry may be set to one of the temperature sensors: SUPPLY,
HEADER, RETURN, or turned OFF (default). If this entry is set to a
sensor and the temperature falls below TEMP, the boiler will
automatically start and run the water temperature up to the LOCAL
Setpoint and then shut OFF.
This is the temperature that the selected sensor must fall below for
the boiler to start.
Page 54
Default Settings & Menu Item Descriptions
DEFAULT
DOMESTIC HOT WATER
SY
STEM CLOCK
HeatNet Control REV 3.37-1
MENU
HEAT EXCHANGER
ALARM TYPE: WARNING
EXCHR DELTA T
LIM-> HALF RATE YES
DHW BOILER? NO
DHW SETPOINT
DHW DIFF
USE SENSOR? NO
DHW PRIORITY NO
POST PURGE 120s 0-600 secs
DHW MASTER? NO
VALUE
40 °F
160 °F 40F – 200 °F
5 °F 1F- 30 °F
RANGE DESCRIPTION
per Boiler
This setting determines the way in which the control reacts when the
differential temperature across the heat exchanger exceeds the
specified maximum differential temperature. The default alarm
condition is a WARNING. The WARNING state will allow the
boiler to keep functioning and display a warning message and a
timestamp in the status screen when the maximum differential
temperature is exceeded. If FAULT is selected, the boiler will shut
down and act as if an interlock has tripped. After the Delta T has
dropped by 10F the boiler will restart if the demand is still present.
This is the maximum differential temperature the heat exchanger can
see before the ALARM TYPE is applied. This value can not be
changed and is defined for each boiler size.
Limit to Half Rate: When set to YES, and the maximum differential
temperature (delta T) has been exceeded, the fire rate called for is cut
in half. In other words: if we are calling for 80% modulation and
have exceeded the delta T, the boiler will only fire at 40%. The delta
T needs to drop 10F below the maximum delta T to reset this limit.
The message “ ½ INPUT” will be displayed on a member boiler and
a Master Boiler will display the Modulation % for the system even
though it is running at ½ of this rate. This method helps protect the
heat exchanger from damage due to excessive delta T’s. If this
Master boiler is running
(Version 2.x control)
Setting this value to YES enables the Boiler/System for DHW
operation. DHW settings are only looked at if set to YES.
Setpoint that the boiler/system will target when a call for DHW.
DHW SETPOINT – DHW DIFF : if DHW water temperature is less
than this temperature, the Boiler/System will enter DHW Heating
mode. Once the DHW SETPOINT is reached, DHW mode is exited.
If this entry is set to YES, the DHW 10k Sensor is looked to for
controlling DHW water temperature. If set to NO, A thermostat is
used.
If the DHW PRIORITY is set to YES, then when there is a call for
DHW, the system pump shuts off. If NO, the system pump stays on.
This is the time that the DHW relay remains on after the DHW call
ends.
This parameter can only be used if USE SENSOR? is set to YES,
and there is NO Header sensor Present..
If set to YES, this boiler becomes the DHW Master Boiler and will
use HeatNet to control member boilers based on the DHW Sensor,
DHW SETPOINT, and DHW DIFF. If set to NO, only this boiler
will run in DHW mode.
TIME
DAY OF WEEK
MONTH
YEAR
PRESS SEL TO SAVE
DAY
This time needs to be entered at first turn-on and in the event that
power has been lost for more than 3 days. The time is only required
for an accurate log entry time-stamp and fault time stamp.
The SEL key must be pressed after all time values have been entered
to save all time values at once.
Page 55
MODULAR BOILER SET
adjustments will help produce smooth temperature control when each
HeatNet Control REV 3.37-1
Default Settings & Menu Item Descriptions — ADVANCED SETUP
DISTRIBUTED CTRL
CONTROL H-Net
H-Net MASTER YES
H-NET ADDRESS 255 (2 –16)
MODBUS ADDRESS 1 (1 – 247)
ADD BOILER DELAY 10mins (0 – 15min)
SHED BOILER DELAY 2mins (0-15min)
MODULATE DELAY
TIME
MOD MAX – LAST FIRE
10 secs (0 – 60min)
70% (25 – 100%)
Displays method of operation: HeatNet (H-Net)
Auto detected, based on the HEADER sensor.
If the HEADER sensor is present and is set to TYPEZ, the FuteraSeries control is run as a H-Net MASTER (YES).
If the HEADER sensor is not TYPEZ, H-Net MASTER = NO.
The local address is the address of a member device. This is
normally in the range of 2 through 16. But if the Futera-Series
control is a MASTER, then the default address is 255. The H-NET
ADDRESS # is synonymous with boiler #.
The MODBUS address is for communicating with Laptop, PC, or
other MODBUS capable device. It is the 2nd communication port
reserved for host control.
This is the delay time in 30sec intervals, before starting a new boiler.
Boiler #1 is started immediately after a call for heat. If a second
boiler needs to start, the ADD BOILER DELAY will need to expire
before starting.
This is the delay time in 30 second intervals, before stopping a
boiler. A boiler is stopped immediately when the top of the heat band
is exceeded. If a second boiler needs to stop, the SHEDBOILER
DELAY will need to expire before stopping.
This is the time the boiler remains in min-fire before it relinquishes
control to the modulation % signal.
This value represents the maximum % of input on the boilers if all
the available boilers are not firing. Once all boilers are firing, this
clamp is removed and all boilers are allowed to modulate up to
100%. When this value is limiting the input an ‘*’ is displayed and
the “INPUT CLAMP” message is displayed in the STATUS screen.
This value is derived by: multiplying twice the minimum fire rate of
the boiler with the least turndown (2* turndown(20% 5:1, 25% 4:1,
33% 3:1)). In mixed boiler size configurations, more than (2) boilers
in a system, or when “bumps” in the temperature occur as boilers are
added and subtracted, this value may need adjustment. The
Page 56
boiler is started and stopped. This method ensures that, once a new
boiler starts to fire, and holds its fire rate at the minimum setting, it
does not add its BTU output to a boiler already firing at 100%. The
boilers can not be fired starting @ 0%, but start at a minimum
(example: 20%) and introduce a minimum amount of BTUs into the
system. Section: SETUP & OPERATION
Default Settings & Menu Item Descriptions
ion MODE is set to ADAPTIVE on the Master boiler, the
er waits the DELAY RELEASE time before allowing the PID to
FIRING MODE
Master boiler. Boilers with the least runtime are fired first and boilers
MOD MODE ADAPTIVE
DROP DOWN ON CALL
DELAY RELEASE 0s
MODE TRUE
MIN RUNTIME 10 (1-255)
MIN OFF TIME 0 (0-10m)
PREDICT START: YES YES/NO
ADAPTIVE MOD
If MODulat
Master lowers the system modulation rate of all currently running
boilers before a newly started boiler enters the Main Valve state.
Upon entering the Main Valve state of a newly fired boiler, the
Mast
resume modulation control. With MOD MODE set to ORIG KN,
The Master boiler keeps firing at the current modulation rate when a
new boiler is added and lets the PID adjust modulation rate
accordingly.
If drop down is set to ON PILOT and MOD MODE = ADAPTIVE,
and when a newly added boiler starts, the system waits until it enters
its PILOT state before bring the system modulation down. This
allows for the system to prepare for the new energy that is to be
introduced. If DROP DOWN is set to immediately, the system
modulation is lowered as soon as the newly added boiler is called.
Once the Main Valve opens on the newly added boiler and the MOD
MODE = ADAPTIVE the Master waits this amount of time before
releasing the PID to control modulation. This allows for the newly
added boiler to accumulate some soak time.
LOFO: Boilers are fired Last On, First Off starting with Lead Boiler
FOFO: Boilers are fired First On, First Off
TRUE: Boilers are fired based on the runtime they report back to the
with the most runtime are stopped first.
MIXED: Different types of boilers can be mixed in a system and
fired based on (2) Priority sets. Boilers are started and stopped with
in the Priority sets based on their runtime hours.
When the firing rotation is based on runtime, this value represents
the interval in hours of runtime before rotation occurs. Boiler to
Boiler.
This is the time in minutes that the boiler must remain OFF before it
can be fired again.
YES: Predicts the boiler restart point in the heating band while the
temperature of the boiler is drifting down through the band. The
purpose of this is to ensure the temperature remains in the
temperature band. It also minimizes temperature swings when
the boiler is stopped and started at low inputs.
HeatNet Control REV 3.37-1
Page 57
SENSORS
4–20mA INPUT
HeatNet Control REV 3.37-1
BASE LOAD BOILERS
BASE LOAD BOILERS:
START >MOD
START>MOD 100% (20–100)
START<OA T (40–140)
START>RET (60–150F)
STOP FIRST
STOP<MOD 20% (20–100) 20% (20–100)
STOP>OA T (40–100F)
STOP<RET (60–150F)
DELAY TIME 0 (0–60 minutes)
SENSOR #
TYPE
CALIBRATE
0 0-1
(START>MOD,
START<OA T,
START>RET)
STOP<MOD,
START>OA T,
START>RET)
Sensors can only be changed when there is no call for heat. The boiler must be in STANDBY.
(FIRST,
(Version 2.x control)
This setting works in conjunction with the ADVANCED SETUP:
SYSTEM:OPTION setting BASE LOAD. Currently only (1) base
load boiler is supported using relay K8 on the Version 2.x control.
Used in Conjunction with DELAY TIME.
The base load relay K8 will close when the Modulation is >%.
The base load relay K8 will close when the OA temp is > T
The base load relay K8 will close when the Return temp is > T.
The base load relay K8 will open when the Modulation is <%.
The base load relay K8 will open when the OA temp is > T.
The base load relay K8 will open when the Return temp is < T.
This setting allows a wait time before firing the base load boiler once
the start condition is met.
The first (4) sensor #’s are reserved as: OUTSIDE AIR, water
SUPPLY outlet, water RETURN inlet, and system HEADER
temperature. If the HEADER sensor is used (TYPEZ), that boiler
performs the tasks of the MASTER boiler. If the HEADER sensor is
set to NONE, its function is the MEMBER. The remaining (2)
sensors perform as user selections and provide functions such as:
Combustion Air Proving.
There are (4) sensor types:
NONE = do not use this sensor
TYPEZ = 10k thermistor
ON/OFF = 5 volts supplied out to detect a contact/switch closure.
Placing a precision 10k (TYPEZ) precision resistor across the sensor
input selected allows calibration of the sensor input.
Page 58
4mA SETPOINT
20mA SETPOINT
BOILER START 4.11mA 3.71-5.0mA
PRIORITY NORMAL
50 °F 50-220 °F
220 °F 50-220 °F
When using 4-20mA setpoint control in SETPOINTS:SETPOINT
SOURCE. This is the temperature when a 4ma signal is applied and
is tied to the BOILER START mA. The Setpoint will then be
mapped from 4mA –20mA and example default of: 50-220F
This is the setpoint temperature when a 20mA signal is applied.
This is the current value which will start the boiler. There is a .1mA
hysteresis value. So if the Boiler starts at 4.11mA it shuts off a
4.01mA.
If the Priority is set to NORMAL, the boiler responds to its HEAT
DEMAND inputs in the Priority that is outlined in the Control
Methods section. If the PRIORITY is set to HIGHEST, The 4-20ma
input responds at the highest Priority level (same as the AA input).
This method may be used by an external control to override the
HeatNet control and fire the boiler using this external control
(external control override). This allows for complex DHW control
systems.
Default Settings & Menu Item Descriptions
COMMUNICATIONS
Net control. If set to “NO”, MODBUS always has control and on a
LOAD DEFAULTS
SYSTEM
the h
AAAAAA
PASSWORD
Provides a limited access for security, though restoring system
defaults will reset the password to the value “AAAAAA”
HeatNet Control REV 3.37-1
1200, 2400,
BAUD 19200
DATA FORMAT 8E1
SETPOINT TIMER YES
FACTORY CAL?
FACTORY RESET? NO
BOILER TYPE
FIRING PRIORITY: 2 1 or 2
BTU IN 2000,000
CONDENSING YES
MASS
LOAD FIRMWARE NO
OPTION: NO OPTION
4800, 9600,
19200, 38400
8E1, 8N1,
8N2, 8O1
NO OPTION
DUAL FUEL
BASE LOAD
This is the Baud rate for serial communication from the MODBUS
port. Selectable from 1200, 2400, 4800, 9600, 19200, 38400.
If set to ‘YES”, the setpoint timer is enabled and requires a periodic
update of its value to keep from timing out and retuning control to
Hloss of MODBUS communications, H-Net does not assume control.
Selecting YES will load just the factory calibration values: MIN
VFD, MAX VFD and IGN VFD.
Selecting YES will load all factory defaults except the Calibration
values, HeatNet, and Modbus addresses.
There are (2) Priority settings used by the MIXED boiler rotation
algorithm. Priority 2 is the default and lowest priority. Priority 1 is
This is the BTU input rating of the boiler. This value is not used with
this version and is displayed only for reference.
This defines a boiler as condensing or non-condensing. This value is
not used with this version and is displayed only for reference and
future applications.
This defines the mass of the boiler. This value is not used with this
version and is displayed only for reference and future applications.
Answering YES deletes the existing Firmware and allows a firmware
update.
When set to DUAL FUEL, input T3/ RESERVED, OPTION input is
used to control the DUAL FUEL OPTION relay via K8 contacts on
J4.2 &.6. When set to NO OPTION the input T3/RESERVED,
OPTION relay K8 on J4.2 &.6 is inactive.
When set to BASE LOAD, the Option Relay K8 on J4.2 &.6 is used
as an enable contact for a base load boiler. The J4.1 &.5 0-10vdc/420mA output is used to modulate the base load relay if it is of the
modulating type.
Page 59
Figure 48
Address
Name
Raw Data Type
Scale
Description
Valid Values/Ra
nge
HeatNet Control REV 3.37-1
MODBUS Communications
The Futera-Series control can be controlled using Modbus commands to Enable/Disable the boiler/system. A connection to the
Console Modbus Port on the Communications board is required. The Master Boiler assumes the role of MEMBER, RTU, 192Kb,
8 bits, Even Parity, 1 stop bit, when connected to a BMS (Building Management System).
The Member Boilers should not be connected to a BMS system other than to view Read Only addresses. Refer to
http://www.rbiwaterheaters.com/ website for greater detail on communicating with Modbus, BACnet, or LonWorks protocols.
MODBUS Input/Output Variables (Read/Write)
40001 HeatDemand 1 bit unsigned ---
40002 SetpointTimer 16 bit unsigned ---
40003 Setpoint 8 bit unsigned 1.0
40004 OAResetEnable 1 bit unsigned ---
40005 OARSetpoint 8 bit unsigned 1.0
40006 OARHighWaterTemp 8 bit unsigned 1.0
40007 OARHighAirTemp 8 bit unsigned 1.0
40008 OARLowWaterTemp 8 bit unsigned 1.0
40009 OARLowAirTemp 8 bit signed 1.0
40010 SetMonth 8 bit unsigned ---
40011 SetDay 8 bit unsigned ---
40012 SetYear 8 bit unsigned ---
40013 SetHour 8 bit unsigned ---
Heat Demand/Request. Setting the state
member of this variable will put the boiler
in heating mode.
System Setpoint Timer
The system setpoint timer and system
setpoint work in tandem to externally
control (i.e. a BMS - building management
system) the operating setpoint. The
setpoint (countdown) timer should be
loaded with a timeout value (in seconds)
prior to writing the system setpoint. When
the timer reaches zero, the control assumes
that the BMS is no longer operating and the
local setpoint (saved on the control) is
reloaded. This is a failsafe feature used to
help safeguard the system in case of BMS
failure. If the setpoint timer is not written,
a default timeout value of 60 seconds is
assumed.
System Setpoint (see SetpointTimer)
Enables/Disables outdoor air reset mode.
Outdoor air reset setpoint. Temperature at
which boiler shuts down.
Boiler water temperature setpoint when
outdoor air temperature is at the high
outdoor air temperature setpoint
(OARHiAirTemp).
High outdoor air temperature setpoint.
Header/Supply temperature setpoint when
outdoor air temperature is at the low
outdoor air temperature setpoint
(OARLoAirTemp).
Low outdoor air temperature setpoint.
Set real time clock – month (see SetClock)
Set real time clock – day (see SetClock)
Set real time clock – year (see SetClock)
Set real time clock – hour (see SetClock)
0 = no heat demand
1 = heat demand
0 – 65535 seconds
40 - 220 °F
0 = disabled
1 = enabled
40 – 100 °F
60 – 150 °F
50 – 90 °F
70 – 220 °F
-35 – 40 °F
0 (January) - 11
(December)
1 – 31
0 – 99
0 – 23
Page 60
MODBUS Communications
Figure 48
Address
Name
Raw Data Type
Scale
Description
Valid Values/Ra
nge
Figure 49
Raw Data
MODBUS Input/Output Variables (Read/Write)
HeatNet Control REV 3.37-1
40014 SetMinute 8 bit unsigned ---
40015 SetSecond 8 bit unsigned ---
40016 SetWeekday 8 bit unsigned ---
40017 SetClock 1 bit unsigned ---
Set real time clock – minute (see SetClock)
Set real time clock – second (see SetClock)
Set real time clock – weekday (see SetClock)
Set (write) the real time clock.
Do Not Write more than once per minute
To write the real time clock, the system
variables (SetMonth, SetMonth, SetDay,
SetYear, SetHour, SetMinute, SetSecond,
SetWeekday) must first be loaded with the
correct date and time. Then, a 1 must be
written to the state portion of this system
variable to write the new date and time to
the system clock.
0 – 59
0 – 59
1 (Monday) - 7
(Sunday)
0 = no action
1 = set/write the clock
MODBUS Input Variables (Read Only)
Address
30001 BoilersOn 8 bit unsigned ---
30002 Modulation 8 bit unsigned 0.01 Current system modulation level. 0 – 100 %
30003 HeaderTemp 16 bit signed 0.01 Header / System temperature. 32 – 250 °F
30004 SupplyTemp 16 bit signed 0.01 Supply temperature. 32 – 250 °F
30005 ReturnTemp 16 bit signed 0.01 Return temperature. 32 – 250 °F
30006 OutsideTemp 16 bit signed 0.01 Outside air temperature. -40 – 250 °F
30007 Spare1 16 bit signed --- Raw A/D value from spare 1 input. -32768 to 32767
30008 Spare2 16 bit signed --- Raw A/D value from spare 2 input. -32768 to 32767
30009 Month 8 bit unsigned --- Real time clock month.
30010 Day 8 bit unsigned --- Real time clock day. 1 – 31
30011 Year 8 bit unsigned --- Real time clock year. 0 – 99
30012 Hour 8 bit unsigned --- Real time clock hour. 0 – 23
30013 Minute 8 bit unsigned --- Real time clock minute. 0 – 59
30014 Second 8 bit unsigned --- Real time clock second. 0 – 59
30015 Weekday 8 bit unsigned --- Real time clock weekday. 1 (Monday) – 7 (Sunday)
30016 Boiler01Status1
30017 Boiler01Status2
30018 Boiler02Status1
30019 Boiler02Status2
30020 Boiler03Status1
30021 Boiler03Status2
30022 Boiler04Status1
30023 Boiler04Status2
Name
Type
16 bit unsigned ---
Scale
Description Valid Values/Range
The number of boilers currently
running.
Boiler (1 – 16) status flags. These bits
indicate the state of the 24VAC
interlocks, ignition circuit, and various
other conditions. See the values
column for a list of conditions.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
0 – 16
0 (January) - 11
(December)
See the “BoilerStatus1” and
“BoilerStatus2” Tables
below.
Page 61
Figure 49
Raw Data
MODBUS Input Variables (Read Only)
HeatNet Control REV 3.37-1
Address
30024 Boiler05Status1
30025 Boiler05Status2
30026 Boiler06Status1
30027 Boiler06Status2
30028 Boiler07Status1
30029 Boiler07Status2
30030 Boiler08Status1
30031 Boiler08Status2
30032 Boiler09Status1
30033 Boiler09Status2
30034 Boiler10Status1
30035 Boiler10Status2
30036 Boiler11Status1
30037 Boiler11Status2
30038 Boiler12Status1
30039 Boiler12Status2
30040 Boiler13Status1
30041 Boiler13Status2
30042 Boiler14Status1
30043 Boiler14Status2
30044 Boiler15Status1
30045 Boiler15Status2
30046 Boiler16Status1
30047 Boiler16Status2
30048 Boiler01RuntimeHigh16
30049 Boiler01RuntimeLow16
30050 Boiler02RuntimeHigh16
30051 Boiler02RuntimeLow16
30052 Boiler03RuntimeHigh16
30053 Boiler03RuntimeLow16
30054 Boiler04RuntimeHigh16
30055 Boiler04RuntimeLow16
30056 Boiler05RuntimeHigh16
30057 Boiler05RuntimeLow16
30058 Boiler06RuntimeHigh16
30059 Boiler06RuntimeLow16
30060 Boiler07RuntimeHigh16
30061 Boiler07RuntimeLow16
30062 Boiler08RuntimeHigh16
30063 Boiler08RuntimeLow16
Name
Type
16 bit unsigned ---
Scale
Description Valid Values/Range
Boiler (1 – 16) Runtime seconds High
(Upper) and Low (Lower) 16 bit
counters. To get the actual runtime for
any given boiler (##), the high and low
16 bit counters must be combined
(concatenated) into a single 32 bit
counter as:
Boiler##RuntimeHigh16:Boiler##Runti
meLow16
Example
Boiler01Runtime =
(Boiler01RuntimeHigh16 * 65536) +
Boiler01RuntimeLow16
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
0 – 4294967295 seconds
Page 62
MODBUS Communications
Figure 49
Raw Data
MODBUS Input Variables (Read Only)
HeatNet Control REV 3.37-1
Address
30064 Boiler09RuntimeHigh16
30065 Boiler09RuntimeLow16
30066 Boiler10RuntimeHigh16
30067 Boiler10RuntimeLow16
30068 Boiler11RuntimeHigh16
30069 Boiler11RuntimeLow16
30070 Boiler12RuntimeHigh16
30071 Boiler12RuntimeLow16
30072 Boiler13RuntimeHigh16
30073 Boiler13RuntimeLow16
30074 Boiler14RuntimeHigh16
30075 Boiler14RuntimeLow16
30076 Boiler15RuntimeHigh16
30077 Boiler15RuntimeLow16
30078 Boiler16RuntimeHigh16
30079 Boiler16RuntimeLow16
30080 Boiler01Status3
30081 Boiler02Status3
30082 Boiler03Status3
30083 Boiler04Status3
30084 Boiler05Status3
30085 Boiler06Status3
30086 Boiler07Status3
30087 Boiler08Status3
30088 Boiler09Status3
30089 Boiler10Status3
30090 Boiler11Status3
30091 Boiler12Status3
30092 Boiler13Status3
30093 Boiler14Status3
30094 Boiler15Status3
30095 Boiler16Status3
30096 Boiler01SupplyTemp
30097 Boiler02SupplyTemp
30098 Boiler03SupplyTemp
30099 Boiler04SupplyTemp
30100 Boiler05SupplyTemp
30101 Boiler06SupplyTemp
30102 Boiler07SupplyTemp
Name
----- The following registers are available starting in firmware version 2.0 -----
Type
16 bit unsigned ---
16 bit signed 0.01
Scale
Description Valid Values/Range
Boiler (1 – 16) stage control input
flags. These bits indicate the state of
the stage control inputs. See the
values column for a list of conditions.
Boiler (1 – 16) supply temperature (if
available). See BoilerStatus2 to
determine if the sensor is present.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
See the “BoilerStatus3”
Table below.
32 – 250 °F
Page 63
Figure 49
Raw Data
Low (Lower) 16 bit counters. To get the
MODBUS Input Variables (Read Only)
HeatNet Control REV 3.37-1
Address
30103 Boiler08SupplyTemp
30104 Boiler09SupplyTemp
30105 Boiler10SupplyTemp
30106 Boiler11SupplyTemp
30107 Boiler12SupplyTemp
30108 Boiler13SupplyTemp
30109 Boiler14SupplyTemp
30110 Boiler15SupplyTemp
30111 Boiler16SupplyTemp
30112 Boiler01ReturnTemp
30113 Boiler02ReturnTemp
30114 Boiler03ReturnTemp
30115 Boiler04ReturnTemp
30116 Boiler05ReturnTemp
30117 Boiler06ReturnTemp
30118 Boiler07ReturnTemp
30119 Boiler08ReturnTemp
30120 Boiler09ReturnTemp
30121 Boiler10ReturnTemp
30122 Boiler11ReturnTemp
30123 Boiler12ReturnTemp
30124 Boiler13ReturnTemp
30125 Boiler14ReturnTemp
30126 Boiler15ReturnTemp
30127 Boiler16ReturnTemp
30128 Boiler01CyclesHigh16
30129 Boiler01CyclesLow16
30130 Boiler02CyclesHigh16
30131 Boiler02CyclesLow16
30132 Boiler03CyclesHigh16
30133 Boiler03CyclesLow16
30134 Boiler04CyclesHigh16
30135 Boiler04CyclesLow16
30136 Boiler05CyclesHigh16
30137 Boiler05CyclesLow16
30138 Boiler06CyclesHigh16
30139 Boiler06CyclesLow16
30140 Boiler07CyclesHigh16
30141 Boiler07CyclesLow16
30142 Boiler08CyclesHigh16
Name
Type
16 bit signed 0.01
16 bit unsigned ---
Scale
Description Valid Values/Range
Boiler (1 – 16) return temperature (if
available). See BoilerStatus2 to
determine if the sensor is present.
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
Boiler (1 – 16) Cycles High (Upper) and
actual cycle count for any given boiler
(##), the high and low 16 bit counters
must be combined (concatenated) into
a single 32 bit counter as:
Boiler##CyclesHigh16:Boiler##CyclesL
ow16
Example
Boiler01Cycles =
(Boiler01CyclesHigh16 * 65536) +
Boiler01CyclesLow16
Boiler01 = Master
Boiler02 = Member01
…
Boiler16 = Member15
32 – 250 °F
0 – 4294967295
Page 64
MODBUS Communications
Figure 49
Raw Data
Bit Description
Valid Va
lues/Range
MODBUS Input Variables (Read Only)
HeatNet Control REV 3.37-1
Address
30143 Boiler08CyclesLow16
30144 Boiler09CyclesHigh16
30145 Boiler09CyclesLow16
30146 Boiler10CyclesHigh16
30147 Boiler10CyclesLow16
30148 Boiler11CyclesHigh16
30149 Boiler11CyclesLow16
30150 Boiler12CyclesHigh16
30151 Boiler12CyclesLow16
30152 Boiler13CyclesHigh16
30153 Boiler13CyclesLow16
30154 Boiler14CyclesHigh16
30155 Boiler14CyclesLow16
30156 Boiler15CyclesHigh16
30157 Boiler15CyclesLow16
30158 Boiler16CyclesHigh16
30159 Boiler16CyclesLow16
Name
Type
Scale
Description Valid Values/Range
Figure 50 MODBUS — BoilerStatus Flags
0 Pilot Valve 0 = closed, 1 = open
1 Blower Running 0 = off, 1 = running
2 Ignition Alarm 0 = ok, 1 = alarm
3 Valve Alarm 0 = ok, 1 = alarm
4 High Limit 0 = ok, 1 = tripped
5 Air Prove Switch 0 = open, 1 = closed
6 RESERVED (FACTORY)
7 Software Operator 0 = off, 1 = on
8 Header Sensor not Detected 0 = detected, 1 = not detected
9 Supply Sensor not Detected 0 = detected, 1 = not detected
10 Return Sensor not Detected 0 = detected, 1 = not detected
11 Outside Sensor not Detected 0 = detected, 1 = not detected
12 System Pump 0 = off, 1 = on
13 Combustion Air Damper 0 = off, 1 = on
14 Master Boiler 0 = member, 1 = master
15 Boiler Detected (at this address) 0 = not detected, 1 = detected
This BoilerStatus3 Heat Demand Flag is Heat Demand input. On member boilers, this indicates a “Local Override”.
Page 67
HeatNet Control REV 3.37-1
Troubleshooting
This section is included as an aide to help troubleshoot
problems with the setup and operation of the boiler. See
Appendix A for additional fault messages.
Situation:
Nothing happens when the power switch is turned
on.
1. Check For 120/240 VAC on the Service connector J1.
Verify the line power is connected as per wiring
diagram. The Power switch light (ON - Position) should
illuminate if this is wired correctly. If the light does not
illuminate on the power switch, ensure that J7 is
connected to the main board and the power switch.
2. If the Ignition Control is active, but the front panel
display is inactive check:
a. Cable and cable polarity from the control board to
the display.
b. J14 on control board. 120vac is routed from here to
the transformer. The transformer returns 24vac to
power the control.
is set to NONE the controller will not recognize the
closed circuit. Set the Sensor #5 to ON/OFF.
3. If you are not using the combustion air damper then it
needs to be disabled in the AUX FUNCTIONS menu.
Situation:
The display is displaying random characters or the
control keeps resetting.
There may exist a grounding problem with the controller or
one of the boilers, pumps, contactors or other devices
connected to it. If all grounding is correct, there may be an
issue with radiated or induced electrical noise (interference).
This may be caused by, arcing across a contactor's contacts
when starting a pump motor, or a large electrical load. It
may also be caused by, the ignition transformer being
improperly grounded, or the spark gap set incorrectly.
1. Attempt to identify the noise source:
2. What is the boiler/controller trying to do at the time of
the failure?
3. Is the boiler on the same circuit as the noise source?
(the boiler should have isolated power.)
4. Are shielded sensor wires used? (Ensure the shields are
grounded only at the boiler control end.)
c. Check for 120vac on the primary of the
transformer and 24vac on the secondary. If one of
the 24vac interlocks has been shorted to ground or
the 24vac output is low, the transformer may be
damaged or a 24vac circuit may be miss-wired.
The H-Net control is equipped with resettable
fuses on the power input circuit. Wiring
power incorrectly to the unit will cause these
fuses to open. Once the incorrect wiring is
corrected, the fuses should reset themselves in
less than 5 minutes.
Situation:
You get the error message for the Combustion Air
Damper.
1. The prove switch for the combustion air damper is not
closing. Check to make sure the dampers are being
controlled by the output relay. Also check to make sure
the prove switch is wired and working properly.
2. If (1.) has been done and you are using SPARE 1 and
you continue to get the error message, check the sensor
TYPE specified for sensor #5 in the sensors menu. If it
5. Are any sensors or sensor wires located near a
transmitting antenna? (Move sensor)
Situation:
There are no heating boilers on.
1. Check the settings for WWS SETPOINT, WARM
WEATHER SHUTDOWN; if the outdoor air
temperature is above the WWS SETPOINT and
WARM WEATHER SHUTDOWN is set to YES, the
circulator pump relay will be locked out and the heating
boilers will not fire.
2. If the water temperature is within the heating band
around the setpoint, boilers will not come on. The water
temperature must fall below the lower band limit to
begin firing boilers.
Page 68
Troubleshooting
HeatNet Control REV 3.37-1
Situation:
Unable to change the # of Boilers in the BOILERS
menu.
1. In H-Net method, the Futera-Series control auto-detects
the boilers in the system and adjusts the # of boilers
accordingly.
2. Using H-NET, if the # of Boilers is not being adjusted
properly to the actual amount of boilers in the system,
check each boiler. There can only be (1) master boiler,
but there can be up to 15 member boilers. Currently, a
total of 16 boilers in a system.
Situation:
The boilers menu only indicates 1 boiler, but there
are member boilers connected and the amber light
blinks on all of the boilers communication’s jacks.
1. Ensure that the latest version of firmware is installed on
all boilers. All boilers in a system must have the same
firmware revision.
2. Ensure the proper termination is set on the Master and
the last Member boiler.
Situation:
You get the error message – WATER FLOW
SWITCH or WAITING FOR FLOW.
1. If the control does not sense a closed circuit at input
connection, WTR FLW. Check to make sure the circuit
for the circulator pump is correct, that the pump is
being energized, and that the flow prove switch is
working properly.
2. If there is no flow prove switch, check to make sure that
a jumper wire has been hooked up to J11B, WTR FLW
interlock.
Situation:
H-Net boilers are detected but then lost and then
detected again etc...
b. There may be (2) or more MASTER boilers.
Ensure that only one header sensor is present and
connected to the SYS/DHW input. There should be
no wires or sensors connected to the SYS/DHW
input if the boiler is operating as a member. This
input is auto detected and defines the boiler as a
MASTER.
c. Ensure the cable to connect the H-Net is of a
shielded or twisted pair type. Shielding of the cable
is required.
d. Minimize the electrical interference by routing the
communications cable away from electrical noise
sources, such as: Motors, ignition controls,
contactors etc…
Situation:
Only the MASTER boiler Fires, but the system has
many boilers and is using H-Net.
1. In order for the MASTER boiler to act as a MASTER,
the header sensor must be set to TYPEZ, and there must
be a header sensor present. At power-up, the header
sensor is auto detected. If the temperature of the header
sensor at power-up is greater than –25 °F and less than
240 °F it is considered a valid sensor. The boiler will
default to the MEMBER mode if the temperature is not
in this range and can only be run locally or by external
inputs.
a. If the LOAD FACTORY DEFAULTS has been
used to restore all the default settings, the header
sensor has been set to NONE. This needs to be set
as stated in 1, and the header sensor will need to be
replaced or the temperature brought into a valid
range. A power cycle of the boiler will detect the
sensor if it is in the range as stated in 1.).
b. The H-Net needs a communications cable daisy-
chained between boilers. Ensure that a good
connection is made on the communications board
and that the lights on the dual RJ45 jack flash
(roughly twice a second). The MASTER is the only
one that should flash with no communications
cables plugged in.
1. The H-Net communications cable may be receiving
interference from the blower, ignition, or other form of
radiated electrical noise. Termination of the jumpers
may not be correct or there is more than one master.
a. Ensure that the termination jumpers are set on the
MASTER boiler and only the LAST MEMBER
boiler. All of the other member boilers should have
their termination jumpers in the non-terminated
position.
Situation:
I am in CALIBRATE and I cannot fire the boiler to
adjust it.
1. Only one, but any one of the T1-T2 inputs can be used
to start the boiler. All other inputs are disabled. This
method prevents an external control or Building
Management System from trying to control the boiler
while it is offline and being calibrated. If the boiler is
Page 69
HeatNet Control REV 3.37-1
being used as a staged boiler controlled by an external
control, the staged inputs need to be disconnected
before CALIBRATION, since more than one of the T
inputs may be closed by the external control.
Situation:
You have forgotten the password.
2. As a last resort, you can turn the controller off, then
depress and hold the ESC key while turning it back on.
This will load the default password “AAAAAA”.
Situation:
Firmware update program starts to load, but then
stops, or does not load at all.
1. Check that the termination shunts J3 and J6 are not in
the termination setting. If they are, remove them
temporarily while updating. Restore them for proper
communication with a building management system.
2. Ensure that the USB driver for your PC/Laptop
computer is properly installed.
3. Disconnect BMS or Protocessor Module if connected.
Situation:
All HeatNet Boilers fire at the same time.
1. This is usually caused by the HeatNet addresses on the
Member boilers not being set. If the address on each
boiler is not set, then all boilers will have address = 2
by default. When the Master boiler calls to fire boiler
#2, all boilers with address #2 will fire. Set each
Member boiler to a unique address from 2-16.
2. Check the ADD Boiler delay time to ensure it is at a
reasonable value. A setting of 0 will start all the
boilers at the same time.
Situation:
The boiler is showing that it is running at 45% and
there is no fire in the sight glass.
1. The Boiler always shows it’s called for firing
modulation %. This is not an indication of what the
boiler is actually firing at. If the ignition control fails to
receive a call to fire (last interlock closed on terminal 6
of the ignition control) the display will indicate the
called for %. Check if the ignition control is in standby,
if so then the HeatNet control has closed the Start
contact on J5..10 (Limits) and is waiting for the Blower
relay to close on the ignition control which is monitored
on J5.3 of the HeatNet control.
Situation:
I can hear the blower ramping up and down and
the firing rate is changing, but the display
indicates it is running at the same modulation rate.
1. The Boiler always shows it’s called for firing
modulation %. This is not an indication of what the
boiler is actually firing at. In this case, the boiler is
trying to meet the called for modulation % which is
displayed, but is unable to do so. The boiler protects
itself by looking at it’s supply water temperature and
the temperature is probably in the Operating Limit
Band. While in the operating limit band, the HeatNet
control limits the input of the boiler. The boiler tries to
deliver the most input it can in an attempt to meet the
called for modulation % without tripping the operating
limit.
2. If the boiler is constantly varying in blower speed and
in the operating limit band there may be not enough
flow through the boiler or the Operating
Limit/Operating Limit Band may be improperly set.
The Operating Limit/Operating Limit Band should not
overlap the heating band. This may occur when a
building management system is controlling the setpoint
and is setting the setpoint in the operating limit band.
3. Example: Setpoint set to 180F (by Building
Management) and the Operating Limit is set to 200F
with a 20F Operating Limit Band. When the boiler is
trying to deliver 180F to the load it’s supply
temperature would be a minimum of 180F. The
beginning of the Operating Limit Band (looks at supply
temp) would be 200F-20F = 180F. Now, when the
Master is trying to maintain setpoint at 180F, the boiler
is trying to reduce input beginning at 180F at its supply
sensor and as a result, fighting the setpoint. The
Operating Limit band needs to be reduced in this case,
while taking into account the Heat Band differential.
Situation:
The Master boiler sees all of the Member boilers in
the system, but does not fire any of the Members.
1. If the Master modulates to 100% without firing a
Member boiler and the Member boilers are seen by the
Master (in menu SETUP:BOILERS), then the Member
boilers are sending back offline status to the Master.
a. The Member boilers may have an alarm or error
condition which would be indicated by a blinking
boiler # in the Boilers Firing screen.
b. Ensure the HeatNet is set up properly: Amber
lights blink on HeatNet Jacks. Only one Master
boiler.
Page 70
Troubleshooting
HeatNet Control REV 3.37-1
c. If the Member boiler is in Local Mode then it also
would not be called and report unavailable to the
Master.
d. If the Local flow switch for the Local pump is
wired to the System flow switch input this would
also create an offline condition. The Member needs
to detect system flow or have a jumper across that
sensor input in order for the Member boiler to
report available status. The Local flow prove
switch must be wired to the Water Flow interlock
sensor input.
Situation:
We are trying to use a 0-10VDC control signal, but
when we send it 10 VDC only 7 VDC is measured at
terminal
J10B 6 & 7.
1. The HeatNet control was designed to use a 4-20mA
control input. If a 0-10 VDC control signal is to be
used, it must supply at least 20mA. O-10 VDC control
signals are not recommended due to line loss and the
ability of the control signal to reject noise. So, if using a
0-10 VDC control signal it must be able to supply the
20mA.
Situation:
We are using a BACnet or LonWorks bridge. We
can talk to the bridge, but all of the data is zero (0)
or invalid.
This condition usually indicates that the bridge is not
communicating with the HeatNet control. When operating
properly, the bridge continuously reads data from the boiler
on the Modbus port into an internal buffer. When a BACnet
or LonWorks read request is received, the buffered values
are placed in a BACnet or LonWorks packet and sent. If the
bridge has never been able to successfully read data from
the control, all data points will have their default value
which is typically zero. In this situation, the control will also
not respond to write commands; for instance changing the
setpoint.
1. The control’s MODBUS ADDRESS must be set to one
(1). This is set in the ADVANCED SETUP->DISTRIBUTED CONTROL menu. On older
(legacy) firmware this setting was also called the
CONSOLE ADDRESS.
the ADVANCED SETUP->COMMUNICATIONS
menu.
3. Check the termination on the BMS/Modbus port. If the
control is the first or last device on the Modbus RTU
network, it should be terminated. For the short cable
runs (for instance when using a BACnet or LonWorks
bridge on a Revision 1.x board), the termination should
be in, but usually doesn’t matter.
4. Check the wiring. The Modbus RTU (RS485)
connections on the HeatNet control are A(+), B(-), and
G (ground). Some systems use opposite polarity; A(-),
B(+). Always use the polarity to determine the proper
connections. A ground wire must always be used
and a shielded twisted wire is STRONGLY
suggested.
5. The HeatNet LonWorks and BACnet bridges plug
directly into Revision 2.x+ boards. Legacy boards
(Revision 1.x) required a ProtoCarrier to provide power
and the RS485 signal conversion to the bridge. The
RS845 signal conversion chips are easily damaged by
electrical noise, ground loops, and large differences in
ground potential between devices on the network. This
is a common problem faced by all RS485 devices, not
just the HeatNet control. To help eliminate grounding
problems, nylon standoffs are required to isolate the
bridge from the boiler chassis. The ProtoCarrier should
also be powered from the 24VDC output on the
HeatNet control to help eliminate electrical noise (VFD
and spark pickup, power spikes, etc.) on the power
supply lines. Please download complete HeatNet
bridge installation instructions from the product web
site.
a. When the ProtoCarrier is functional, the small
green surface mount TX and RX LEDs near the 6pin connector (power and communications) should
be flashing regularly.
b. If the TX LED flashes very briefly about once per
minute, the ProtoCarrier has most likely been
damaged, please contact Tech Services.
c. If either LED is always on, the ProtoCarrier has
most likely been damaged, please contact Tech
Services.
2. The control’ BAUD (rate) must be set to 19200 and the
DATA FORMAT must be set to 8E1 (8 data bits, even
parity, 1 stop bit). On older (legacy) versions of
firmware, the DATA FORMAT was called PARITY
which must be set to EVEN. These settings are set in
Page 71
Situation:
We are using a Building Management System
(BMS) to control the boilers. We can write the
setpoints, but they keep changing back to their
“default” values after approximately 60 seconds.
1. When using a BMS, the setpoint values work in
conjunction with the SETPOINT TIMER. The
SETPOINT TIMER is a failsafe feature used to help
detect that a BMS is no longer working or
communicating with the control. The time must be
regularly loaded with a predetermined number of
seconds (1 – 65535). Every second this value will
decremented. If it reaches zero, the local (permanently
saved) values for the setpoints will be loaded. The
concept is that periodically (or every time a setpoint is
written), the BMS must write this value. If the value
reaches zero (0), the HeatNet control assumes that the
BMS in no longer functional and “safe” operational
values for the setpoints will be restored. As an
example, if it is decided that the BMS will write the
HeatNet Control REV 3.37-1
control every 5 minutes, you may decide to write 600
seconds (10 minutes) to the setpoint timer. If after 10
minutes (5 minutes longer than the normal write
interval) the BMS has not written the timer, the saved
setpoint values will be restored.
2. As a convenience, the SETPOINT TIMER is
automatically loaded with 60 seconds (if it has fallen
below 60) each time the setpoint is written. If you
decide to take advantage of this convenience, you
would need to write the setpoint periodically at less
than 1 minute intervals.
3. Newer firmware versions allow the SETPOINT
TIMER failsafe feature to be disabled by writing a zero
(0) to the timer. The feature will automatically revert
back to the enabled state whenever the control is reset
or power cycled. The SETPOINT TIMER failsafe
feature can permanently disabled (or enabled) in
firmware versions 3.35 or greater. This setting can be
changed in the ADVANCED SETUP->COMMUNICATIONS menu.
Page 72
Operation
Futera HeatNet Control Run Screen
MASTER:SYSTEM SET
Hold theBACK
button down
for 5 seconds
to enter the
SETUP menus
MEMBER: LOCAL SET
RUN %100
RUN %100
RUN %100SUPPLY
SYSTEM SET
SYSTEM SET
158°F
HEADER
142°F
162°F
CALIBRATE
HeatNet Control REV 3.37-1
Press the UPor Down Arrow
Keys to navigate the display screen
The SETPOINT can be
adjusted by pressing and
holding the SELECT button
until the SETPOINT flashes.
Then use the UP and DOWN
buttons to change the value.
Prssing the SELECT button
saves the value.
RUN %100
OUTSIDE
50°F
RUN %100
RETURN
90°F
RUN %100*STATUS
START 0
STOP0
RUN %100
RUN %100
BLRS FIRING
1_2______
_________
DELTA TEMP
25°F25°F
RUN %100
DHW TEMP
RUN %100
RUN %100
RUN %100
RUN %100
RUN %100
RUN %100
MINIMUM
CALIBRATE
25%
IGNITION
CALIBRATE
30%
MAX OUTPUT
CALIBRATE
90%
DELTA TEMP
CALIBRATE
DHW TEMP
157°F
RUN %100
DHW SETPT
RUN %100
160°F
157°F
DHW SETPT
160°F
Page 73
HeatNet Control REV 3.37-1
* Status Information
Whenever an * is displayed on the RUN screen it indicates that there is more information available about the current running
conditions. This information can be viewed by going to the *STATUS screen as shown on the previous page. For more
information on the parameters discussed here please see the Default Settings & Menu Item Descriptions — SETUP, starting on
page 52.
Status information screens
This screen indicates that the boiler’s SUPPLY
Temperature has gone above the OPERATOR
LIMIT. This will mainly be seen on member
boilers to show why they are not available to fire.
This screen indicates that the boiler’s SUPPLY
temperature has risen inside the OPERATOR LIMIT
BAND.
This screen indicates the boiler’s input is being
limited by the MOD-MAX value to optimize system
efficiency. This will only be seen on a MASTER
boiler.
Page 74
Operation
Status information screens
This screen indicates the control is attempting to reinitiate the ignition control because the ignition
control did not begin PRE-PURGE. For more
information see CALL SERVICE LOG entry.
This screen indicates that the boiler’s has received a
heat demand, but it’s MINIMUM OFF time has not
expired.
HeatNet Control REV 3.37-1
This Screen indicates that the boiler’s input is
temporarily being limited to optimize the boiler’s
efficiency.
This screen indicates that the boiler is running in
LOCAL MODE because it has lost H-NET
communications with the MASTER, and the failsafe
mode has been activated.
This screen indicates that the boiler is running In
LOCAL MODE because the LOW TEMPERATURE
failsafe mode has been activated. This particular
screen shows that the SUPPLY sensor was used,
HEADER, or RETURN sensors can also be used for
this failsafe mode.
Page 75
Futera HeatNet Control Menu Tree — Version 3.37
HeatNet Control REV 3.37-1
Page 76
Operation
HeatNet Control REV 3.37-1
Futera HeatNet Control Advanced Menu Tree — Version 3.37
Page 77
2 3 4
° ° °
Worksheet
SETUP MENU
BOILERS
# of BOILERS
LEAD STAGE
HEAT BAND °
SETPOINTS
LOCAL SETPOINT °
OPERATE LIMIT °
OP LIM BAND °
SETPOINT SOURCE
OUTDOOR AIR RESET °
OA RESET
WARM WEATHER SD
WWS SETPOINT °
SET OA SETPOINTS
WATER TEMP °
@
HIGH OA TEMP °
WATER TEMP °
@
LOW OA TEMP °
PUMP OPTIONS
SYSTEM PUMP
POST PURGE TIME
ALWAYS ENABLED
SUMMER PUMP JOG
LOCAL PUMP
DELTA TEMP ENAB
DELTA TEMP °
POST PRGE TIME s
ALWAYS ENABLED
PUMP/VALVE OPTION
REMAINS ON:
LOCAL PUMP VFD
FLOW PROVE
NIGHT SETBACK
SETBACK ENTRY 1
ENTRY IS
SETBACK °
SETBACK TIME
START DAY
HeatNet Control REV 3.37-1
Page 78
Worksheet
TIME
END DAY
TIME
OPTIONS
TEMP SCALE °
KEY CLICK
SKIP PASSWORD
BRIGHTNESS %
LOG/ RUNTIME
RUN HOURS
DATA LOG ENTRY
SIZE
BOILER CYCLES
AUX FUNCTIONS
COMBUST AIR DAMPER
TYPE:
IN USE?
INPUT:
PROOF TIME
ALARM SILENCE SWITCH
IN USE
INPUT:
FAILSAFE MODES
H-NET COMM LOST
LOW TEMP:
TEMP <
HEAT EXCHANGER
EXCHGR DELTA T 40F
LIM-> HALF RATE
DHW SETPOINT
DHW DIFF
USE SENSOR?
DHW PRIORITY?
POST PURGE
DHW MASTER?
SYSTEM CLOCK
HeatNet Control REV 3.37-1
Page 79
ADVANCED SETUP
DISTRIBUTED CTRL
CONTROL
H-Net MASTER
H-NET ADDRESS
MODBUS ADDRESS
MODULAR BOILER SET
ADD BOILER DELAY
SHED BOILER DELAY
MODULATE DELAY TIME
MOD MAX – LAST FIRE
ADAPTIVE MOD
MOD MODE:
DROP DOWN
DELAY RELEASE
FIRING MODE
MODE
MIXED
START PRIORITY 1
SET:
STOP PRIORITY 1
SET:
MIN RUNTIME
MIN OFF TIME
PREDICT START
BASE LOADING
BASE LOAD BOILERS:
START > MOD
STOP
DELAY TIME
SENSORS
SENSOR #
TYPE
4-20mA INPUT
4mA SETPOINT
20mA SETPOINT
BOILER START
PRIORITY
PASSWORD
COMMUNICATIONS
BAUD
DATA FORMAT
SETPOINT TIMER
HeatNet Control REV 3.37-1
%
OUTDSIDE SUPPLY R E T U R N H E A D E R DHW 6 7 8
Page 80
Worksheet
HeatNet Control REV 3.37-1
SYSTEM
BOILER TYPE
LOAD FIRMWARE
OPTION:
CALIBRATION SETTINGS
MIN VFD
IGN VFD
MAX VFD
Version:
Page 81
Thermistor Resistance/Temperature Table
HeatNet Control REV 3.37-1
Temp °C Temp °F
-40 -40 336,450 60 140 2,488
-35 -31 242,660 65 149 2,083
-30 -22 176,960 70 158 1,752
-25 -13 130,410 75 167 1,479
-20 -4 97,072 80 176 1,255
-15 5 72,951 85 185 1,070
-10 14 55,326 90 194 915.4
-5 23 43,326 95 203 786.6
0 32 32,650 100 212 678.6
5 41 25,391 105 221 587.6
10 50 19,899 110 230 510.6
Resistance
Temp °C Temp °F
Resistance
15 59 15,711 115 239 445.2
20 68 12,492 120 248 389.6
25 77 10,000 125 257 341.9
30 86 8,057 130 266 301.0
35 95 6,531 135 275 265.8
40 104 5,326 140 284 235.4
45 113 4,368 145 293 209.0
50 122 3,602 150 302 186.1
55 131 2,986
Page 82
Appendix A
SYSTEM SET
SYSTEM SET
SYSTEM SET
FAULT
SYSTEM SET
FAULT
SYSTEM SET
FAULT
SYSTEM SET
Status Screen Fault Display
There are numerous interlock switches and software
limits that are detected. Each of these, when tripped will
produce a display message, an audible beeping, and an
alarm relay closure. The fault is displayed first, then after
a second, the time the fault occurred is displayed. This
cycle will keep occurring until the fault is cleared.
These faults and interlocks are:
HIGH LIMIT:
When the high limit aquastat trips the following message
is displayed:
FAULT
HIGH LIMIT
HeatNet Control REV 3.37-1
LOW WATER CUTOFF:
If there is a low water condition reported by the low water
cutoff switch this fault is displayed. Check that there is water
flow and water in the boiler. There is a reset switch located on
the LWCO box. The interlock connection is located on J5B,
LWCO.
LOW WATER CUTOFF
160°F
VAR FREQ DRIVE:
The variable frequency drive, which controls the blower, if
supported, reports this fault in the event of over current or
other conditions that would cause it to shut down. If this is the
case, check the fault indicators on the VFD. The interlock is
located on J5B, VFD.
FAULT
10/27 9:16
The high limit interlock breaks power to the ignition
control (shutting it off) and effectively removes any
chance of the gas valve receiving power. The HeatNet
series control will remain powered to display the fault,
latch the alarm relay/audible beeper, and to access the log.
The interlock is located on J5, HIGH LIMIT. Ensure
power is present on the input to the High Limit Control.
SPARE 4:
This is a reserved interlock input that is user defined. The
interlock is located on J5B, SPARE 4.
USER INTERLOCK
160°F
VAR FREQ DRIVE
160°F
GAS PRESSURE:
The gas pressure switches (high pressure and low pressure) are
connected in series, so if either trip, a fault will be reported
here. A reset switch is located on the gas pressure switches.
The interlock is located on J15B, GAS PR.
FAULT
GAS PRESSURE
SYSTEM WATER FLOW:
Once the HeatNet series boiler receives a call for heat, it
closes the system circulator pump relay. It then waits 10
seconds or more (adjustable) to prove flow. If there is no flow,
the flow switch alarm will be set. Every 10 seconds the
circulator pump relay will cycle ON for 10 seconds and then
OFF for 10 seconds to try and establish flow. The interlock
connection is located on J5B, SYSTEM WTR FLOW.
Page 83
FAULT
SYSTEM SET
FAULT
SYSTEM SET
FAULT
SYSTEM SET
FAULT
SYSTEM SET
FAULT
SYSTEM SET
FAULT
SYSTEM SET
RUN %54
SYSTEM SET
RUN %54
SYSTEM SET
SYSTEM FLOW SWITCH
WTR FLW LOCAL:
160°F
HeatNet Control REV 3.37-1
OPEN ******* SENSOR :
If the open sensor fault is displayed, the sensor in the position
reported was originally detected, but has since opened. The
boiler will shut down on any OPEN sensor except the
OUSTSIDE AIR sensor.
Once the HeatNet series boiler receives a call for heat, it
closes the LOCAL PUMP/VALVE relay. It then waits 10
seconds or more (adjustable) to prove flow. If there is no
flow, the flow switch alarm will be set. Every 10 seconds
the circulator pump relay will cycle ON for 10 seconds
and then OFF for 10 seconds to try and establish flow.
The interlock connection is located on J5B, WTR FLW.
WATER FLOW SWITCH
160°F
IGNITION CTRL ALARM:
The ignition control alarm is displayed if the ignition
control detects a fault. This could be a flame failure, air
proving switch, or other fault associated with the ignition
control. When this fault occurs, you will need to refer to
the ignition control for the reason.
IGNITON CTRL ALARM
160°F
OPEN OUTSIDE SENSOR
160°F
SHORTED ******* SENSOR:
If the shorted sensor fault is displayed, the sensor in the
position reported was originally detected, but has since
shorted. The boiler will shut down on any SHORTED sensor
except the OUSTSIDE AIR sensor.
SHORTED OUTSIDE SENSOR
160°F
DELTA TEMPERATURE WARNING:
If the temperature difference across the boiler measured from
RETURN water to SUPPLY water exceeds 40F this message
will be displayed. This can be set to an alarm condition in the
AUX FUNCTIONS menu. High delta temperatures can result
in damage to the boiler.
COMBUST AIR DAMPER:
If the combustion air damper has been selected for use
(AUX FUNCTIONS), and the proof switch does not
make, this fault will be displayed.
COMBUSTION AIR DAMPER
160°F
When the master boiler receives a call for heat and needs
to start a boiler, the DAMPER relay closes on J13. If the
combustion air damper does not prove within the proof
time specified in the combustion air damper menu, the
boiler will not start and then display the fault. A
combustion damper fault on a boiler can only be cleared
by power cycling.
Page 84
DELTA TEMP > 40 °F
160°F
RETURN TEMPERATURE WARNING:
If the RETURN water temperature is less than 130F
(condensing) this message will be displayed. Return
temperatures less than 130F with the boiler running can cause
condensation of the flue gases. Condensation of flue gases will
damage the heat exchanger. Low return temperatures for an
extended period of time can result in damage to the boiler.
RETURN TEMP < 130F
160°F
Appendix A
FAULT
SYSTEM SET
FAULT
SYSTEM SET
HeatNet Control REV 3.37-1
AIR SWITCH:
If the IGNITION control closes its blower relay, the
control does not see the PILOT relay close within (2)
minutes, and the AIR PRESSURE switch is made, this
message will be displayed. This alarm protects the boiler
from freeze ups being caused by a blower bringing in cold
outside air with no fire.
AIR SWITCH(BLOWER)
160°F
CALL SERVICE:
If the H-Net control closes the last interlock string entering the
ignition control and the ignition control never closes its
Blower Relay, the H-Net control will wait 2 minutes. The HNet control will then retry for the duration of the local pump
post purge time and then retry the ignition sequence. During
this time “retry strt” will be displayed in the status screen.
After (5) attempts the H-Net control will lock out and display
call service.
CALL SERVICE
160°F
Page 85
Line 4 Log Entries:
The following table lists the messages on line # 4 of the log’s display.
HeatNet Control REV 3.37-1
Line # 4 Message Description
SETBACK IS ACTIVE
SETBACK EXPIRED
NO LOCAL FLOW
NO SYSTEM FLOW
COMBUSTION AIR FAIL
SYSTEM RESET -- ----
O: stack overflow,
U: Stack Underflow ( both are software faults)
R: Reset Instruction ( Firmware or Default load),
W: Watchdog ( Firmware code ran erroneous code and
rebooted),
P: Power-ON (Power switch toggled),
B: Brown-out ( Microcontroller saw a voltage less than 4.5
VDC)
OUTDOOR RESET
If any of the (4) temperature setbacks are active these log entries will be
displayed in the log.
If the test for flow fails these log entries will be displayed. The flow proving
switches are wired to J11A and J11B.
If the combustion air damper is used and does not prove across J10B
DAMPER or J12B DAMPER, this message is displayed.
When the control is reset, this log entry captures the reason the reset occurred.
This log entry indicates that Warm Weather Shutdown is in effect.
Page 86
Appendix B
Line # 4 Message Description
HIGH DELTA TEMP
LOW RETURN TEMP
SHUTDOWN UV TEST
HIGH LIMIT EXCEEDED
IGNITION CTRL ALARM
IRI Alarm
DOMESTIC HOT WATER
LOW WATER CUTOFF
VAR FREQ DRIVE
GAS PRESSURE
SPARE 4
OP LIMIT MECH
This log entry occurs when the temperature across the heat exchanger has
been greater than 40 degrees °F.
If the return temperature is less than 130 degrees °F condensing may be
occurring.
After 24 hours of continuous runtime the ignition control module needs to
check it’s UV detection circuit. An orderly shutdown and then a restart will
occur. This log entry indicates that this has taken place. This is not a fault.
If the mechanical aguastat trips due to it’s high temperature setting having
been exceeded, this log entry will occur.
The ignition control module has faulted while performing an ignition
sequence, or while monitoring flame during normal operation.
If the gas valve proving circuit ( if equipped) detects a gas pressure problem.
Indicates a call for DHW heating by either the DHW sensor or an external
thermostat.
These log entry faults are result of the interlocks connected to the 24VAC
interlock inputs: J11A and J11B.
Low Water Cutoff = Low water condition in boiler
Var Freq Drive = The blowers Variable Frequency Drive has a problem
Spare 4 = User installed interlock,
Op Lim Mech = An external operator (aquastat).
If the H-Net control closes the last interlock string entering the ignition
control and the ignition control never closes its Blower Relay, the H-Net
control will wait 2 minutes. The H-Net control will then retry for the duration
of the local pump post purge time and then retry the ignition sequence. During
this time “retry strt” will be displayed in the status screen. After (5) attempts
the H-Net control will lock out and display call service. The Log will report
the retries.
The is the firmware Operating Limit as defined in
SETUP:SETPOINTS:OPERATE LIM. When the Supply temperature exceeds
this value, this event is logged.
If one of the 10k thermistor sensors was detected to be open or not connected,
this fault will be logged.
If one of the 10k thermistor sensors was detected to be shorted this fault will
be logged.
If a call is made to the ignition control to start and the HeatNet control detects
a blower start, but no Pilot within two minutes, the boiler locks out. This log
entry indicates that the blower was ON with no flame in the boiler. Freeze up
protection.
These log entries indicate that HeatNet has either discovered a boiler or lost a
boiler using it’s auto detection algorithm.
If the Fail Safe modes are active, these log entries indicate that they became
active for some reason and the boiler had entered Fail Safe mode.
The Base load Boiler Relay K8 is Active if ON
Inactive if OFF
If the H-Net control closes the last interlock string connected to the ignition
control and the ignition control never closes its Blower Relay, the H-Net
control will wait 2 minutes. The H-Net control will then retry for the duration
of the local pump post purge time and then retry the ignition sequence. During
this time “retry strt” will be displayed in the status screen. After (5) attempts
the H-Net control will lock out and display call service.
HeatNet Control REV 3.37-1
Page 88
RBI
260 N Elm Street
Westfield, MA 01085
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.