is manual is intended only for use by a qualied heating installer/technician. Read and follow this manual, all supplements
and related instructional information provided with the boiler. Install, start and service the boiler only in the sequence and
methods given in these instructions. Failure to do so can result in severe personal injury, death or substantial property damage.
Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause contamination
of the burner, resulting in possible severe personal injury, death or substantial property damage. e boiler can only be operated with
a dust-free air supply. Follow the instruction manual procedures to duct air to the boiler air intake. If the boiler has been contaminated
by operation with contaminated air, follow the instr uction manual guidelines to clean, repair or replace the boi ler if necessary.
Ax these instructions near to the boiler. Instruct the building owner to retain the instructions for future use by a qualied
service technician, and to follow all guidelines in the User’s Information Manual.
)
Copyright 201 Mestek, Inc.
Information contained in this publication regarding device applications and
the like is provided only for your convenience and may be superseded by
updates. It is your responsibility to ensure that your application meets with
your specifications.
RBI MAKES NO REPRESENTATIONS OR WARRANTIES OF ANY KIND
WHETHER EXPRESS OR IMPLIED, WRITTEN OR ORAL, STATUTORY
OR OTHERWISE, RELATED TO THE INFORMATION, INCLUDING BUT
NOT LIMITED TO ITS CONDITION, QUALITY, PERFORMANCE,
MERCHANTABILITY OR FITNESS FOR PURPOSE.
http://www.rbiwaterheaters.com/
The RBI name and logo, Mestek name and logo, FlexCore CK -
Series, HeatNet, and H-Net name and logo are registered
trademarks of Mestek, Incorporated in the U.S.A. and other
countries.
BACnet is a registered trademark of ASHRAE. LonWorks is a
registered trademark of Echelon Corporation.All trademarks
mentioned herein are property of their respective companies.
THE FLEXCORE CK-SERIES V3HEATNET CONTROL .........................................................................................................................6
Features & Specifications ................................................................................................................... 8
STANDARD FEATURES OVERVIEW .....................................................................................................................................................8
PART NUMBER .............................................................................................................................................................................. 11
BASIC MULTI BOILER SYSTEM OPERATION ....................................................................................................................................... 12
MIXED BOILER TYPES USING PRIORITY SETS ................................................................................................................................... 13
MIXED BOILER SYSTEM OPERATION ................................................................................................................................................ 14
MIXED SYSTEM TYPE 1:HIGH SYSTEM TURNDOWN ......................................................................................................................... 17
MIXED SYSTEM TYPE 2:CONDENSING/NON-CONDENSING ................................................................................................................. 20
Heating Control Methods ................................................................................................................... 24
DHWMETHOD 3:DHWHEATING ONLY, USING A HEADER SENSOR INPUT .......................................................................................... 40
DHWMETHOD 4A:SPACE HEATING WITH DHWOVERRIDE OF SETPOINT ON MASTER, USING AN AQUASTAT ......................................... 43
DHWMETHOD 4B:SPACE HEATING WITH DHWOVERRIDE OF SETPOINT ON MASTER, USING A DHW10KTANK SENSOR ..................... 46
DHWMETHOD 5A:LOCAL DHWTANK HEATING USING A 10K TANK SENSOR. ..................................................................................... 49
DHWMETHOD 5B:LOCAL DHWTANK HEATING USING A THERMOSTAT &HYBRID SENSOR. ................................................................ 53
DHWMETHOD6:DHW USING DIRECT CONTROL ......................................................................................................................... 55
BASE LOADING,RELAY CONTROL ................................................................................................................................................... 56
Using the 4-20 mA input (OPTIONAL) ............................................................................................... 59
GENERAL MESSAGES: ................................................................................................................................................................... 88
Type II Thermistor Resistance/Temperature Table ........................................................................ 134
Page 5
FEATURES & SPECIFICATIONS HeatNet Control V3
SETPOINT
UPPER HEAT
BAND LIMIT
LOWER HEAT
BAND LIMIT
Boilers Staged
ON
BOILERS
STAGED
OFF
Time
WATER
TEMPERATURE
target setpoint. This function is displayed in the Home
Introduction
Screen. While performing this task, the control also
monitors dedicated external limits in a limit string and
provides an orderly shutdown and fault indication in the
The FlexCore CK-Series V3 HeatNet
Control
The FlexCore CK -Series boiler control is designed to
provide the FlexCore CK -Series of boilers with an
integrated boiler management system on every boiler.
Designed for the Air-Fuel coupled FlexCore CK -Series
boilers, the FlexCore CK -Series HeatNet control provides
for optimized heating efficiency without the need for a “wall
mount control”. Since the FlexCore CK -Series modular
control method is based on digital communications, analog
control signals are not required. Although the use of analog
control signals is still supported (4-20 mA control loops and
0-10vdc control voltages), a higher level of control
precision, repeatability, and feedback is gained with digital
communications control.
With the FlexCore CK -Series, optimized heating efficiency
is accomplished by setting the Modulation Maximum (ModMax) setting to exploit the inverse efficiency curve. This
value can be adjusted so that as each boiler is added, it
operates at its maximum turndown. This allows the
maximum number of boilers to operate at their lowest
inputs, until all boilers are firing. Once all boilers are firing,
full range modulation control is allowed. An outdoor reset
function is also provided to assist in the optimized heating
event of a tripped limit. The monitored limits include a
HIGH LIMIT AQUASTAT, LOW WATER CUTOFF,
GAS PRESSURE, FLOW, IGNITION CONTROL fault,
GAS VALVE alarm, VARIABLE FREQUENCY DRIVE
alarm, and other optional or user selectable limits.
The HIGH LIMIT circuit is independent of
the control and shuts down the ignition
control and the boiler if the control board or
other component of the boiler was to
malfunction. The control will continue to
function and report the fault, but its ability to
control the boiler will end.
Each FlexCore CK-Series boiler employing this control can
function as either a Master or a member. This allows one
boiler (Master) to be in control of target temperature. The
other boilers (Members) only respond to the commands
issued by the Master. If using an external control, all boilers
can be setup as members. The following will define the
roles of Master and member.
Master
A boiler becomes a Master when a temperature sensor is
connected to the J10 “SYSTEM HEADER” terminals. The
sensor is auto-detected.
efficiency of the FlexCore CK -Series boilers.
The Master senses and controls the common system
The FlexCore CK -Series boiler with the FlexCore CK Series H-Net control, can be operated in multiple ways:
1. As a stand-alone boiler.
2. A boiler in a Boiler Network using the HeatNet®
header/loop water temperature using a system setpoint. It
uses any boilers it finds (over the H-Net communications
cable) to accomplish this. It can also monitor the Outside
Air (OA) temperature to provide outdoor reset functionality.
Only one Master is allowed in a system.
(H-Net®) protocol.
3. A member boiler to a boiler management system with
multiple input control methods.
When operating as a Master, the boiler provides a control
method using a PID algorithm to regulate water
temperature. This algorithm allows for a single boiler
(Master), or multiple (Master + Member) boilers.
Home Screen
The primary purpose of the control is to maintain the boiler
water temperature at the supply or the header sensor using a
Page 6
Heat band
The control algorithm is based upon a Heat Band, at the
center of which is the setpoint. While below the Heat Band,
boilers are staged on and modulated up until the Heat Band
is entered. Once in the Heat Band, modulation is used to
Features and Specifications HeatNet Control V3
maintain setpoint. Boilers are shut down only when the top
of the Heat Band is breached. Timers are also used to
prevent short cycling.
While staging the boilers on, a modulation clamp is used to
hold the boilers at a lower fire rate until the last boiler is
fired. Once the last boiler fires the modulation clamp is
removed, and all boilers are allowed to fire above this
clamped percentage up to 100%. This “boiler efficiency”
clamp is defaulted to 70% and thus limits all of the boilers
individual outputs to 70% until the last boiler fires. All
running boilers modulate up and down together, always at
the same modulation rate. As a general rule, this percentage
should be no lower than twice the minimum turndown to
minimize short cycling.
ADAPTIVE MOD: DROP DOWN. Once the Main Valve
(on the newly added boiler) is opened, and the DELAY RELEASE timer equals zero, the PID algorithm is allowed
to control the system modulation. Setting the DELAY
RELEASE timer will allow some “soak” time of the newly
added boiler before releasing modulation control to the PID.
The ADAPTIVE MOD menus are disabled
on a Member boiler, but are still visible.
Member
If a “SYS/DHW HEADER” sensor is not connected to J10,
a boiler always defaults to the role of Member.
The Member boiler can operate as part of a multi-boiler
system or as a stand-alone unit.
In a multi-boiler system the Member typically receives its
command signals from a designated Master-boiler. It is also
capable of receiving inputs from an external control system.
The boiler responds to these signals, to start/stop the burner,
and/or to modulate the firing rate. The outlet water
temperature is also monitored. If the outlet temperature
approaches the operating limit temperature setpoint
(adjustable), the boilers firing rate is limited and its
modulation value is reduced to minimize short-cycling. If
the operating limit is exceeded, or if an interlock trips, the
boiler is shut down. When connected with a network cable,
in a Master/Member role, the Members' status is
interrogated by the Master boiler.
When additional boilers are needed to achieve setpoint in
the system, the Master boiler employs an ADAPTIVE
MODULATION algorithm to prevent over firing of the
system. The Master communicates over the H-Net to view
the exact status of each Member boiler. When a new boiler
is added, the Master boiler adjusts the system modulation
rate lower to compensate for the BTUs that will be
introduced by the newly added boiler. This adjustment
occurs when the newly added Member boiler enters its ON
CALL state (default setting). This can be changed to PILOT
when the new boiler is called using the menu:
In a stand-alone installation the Member typically receives
its command signals internally and operates based upon the
outlet water temperature input and the established settings in
the menu (Local Set-point) to start/stop the burner, and/or to
modulate the firing rate. If the operating limit is exceeded,
or if an interlock trips, the boiler is shut down. As in a
multi-boiler system, a stand-alone Member boiler is also
capable of receiving inputs from an external control system.
When using the H-Net network cable in a Master/Member
system, the system setpoint is sent from the Master as a
digital signal, along with the modulation value to control
firing rate. It also receives its command to start or stop over
the H-Net cable. Also, the SYSTEM CLOCK only needs to
be set on the MASTER. The Master will then set the time
on all member boilers.
If not using the H-Net protocol (cable), an external control
can send a 4-20 mA signal along with a 4-20 mA enable
signal to control the firing rate or setpoint. The boiler may
also be treated as a 2-stage boiler or an ON-OFF boiler
using the dedicated T-inputs.
Page 7
FEATURES & SPECIFICATIONS HeatNet Control V3
Features & Specifications
Hardware Version 3.x Control
Features
(Identified by circuit board color: BLACK)
1. Support for (2) Circulator pumps. Two rotation modes
are provided: Based on system runtime or system pump
runtime hours. Pump failure switchover/retry mode.
2. Warm weather shutdown, (2) pump jog and local pump
jog to keep pumps from seizing.
3. The Modbus, BACnet or LonWorks communications
port can be accessed concurrently with the USB port
(HeatNet Control Pro). The BACnet, LonWorks, or
Modbus connections do not need to be disabled to use
the USB ports.
4. The DHW pump and the Local Pump relay connections
now provide a normally closed contact. This allows for
the use of a power open/power close valve.
5. Support for 5ma 0-10v control signals using third party
controls.
6. Support for (2) display types: Vacuum Florescent and
Color LCD using the same 20 pin ribbon cable.
7. System Return sensor input.
8. Enhanced bootloader and firmware storage. One
firmware storage location for user updates. One
firmware program that always remains resident so that a
factory program can be restored. Primary loading is
with a flashdrive.
17. Dual PID controls. One for space heating and one for
DHW heating. Allows for simultaneous DHW/Space
heating.
Standard Features Overview
1. Five levels of external control inputs, including
modulation and staging that provide application
flexibility.
2. Digital Communications Control (analog 4-20 mA and
0-10vdc control supported, but not required).
a. Boiler to Boiler : HeatNet (H-Net)
b. Building Management System (MODBUS,
Optional BACnet or LonWorks) to Boiler
3. Distributed control using the HeatNet (H-Net) protocol
for up to 16 boilers. Eliminates the need for “wall
mounted” controls.
4. Analog Control 4-20 mA and 0-10vdc (5mA minimum
current) signals supported.
5. System/Boiler operating status text display
6. Interlock, Event, and System logging with a time
stamp.
7. Advanced PID algorithm optimized for the FlexCore
CK -Series boilers.
8. (4) Dedicated temperature sensor inputs for: Outside
Air Temperature, Supply (Boiler Outlet) Temperature,
Return (Boiler Inlet) Temperature, and Header
(Common System Supply) Temperature.
9. Automatically detects the optional temperature sensors
on power up.
10. Menu driven calibration and setup menus with a bright
(Adj.) 4 line Vacuum Fluorescent Display.
9. Support for High Efficiency Ametek blowers.
10. 32 bit Microcontroller operating @ 64 MHz with
5-stage pipeline, and prefetch cache.
11. (3) Stage control relay outputs for TBD applications.
12. Backwards compatible with existing HeatNet versions
1.x and 2.x controls and applications.
13. Support for 135 Ohm control actuators.
14. 1k Platinum Stack sensor
15. Flow meter input or BMS GPM input/control
16. On-board HeatNet Online network module.
Page 8
11. (8) Dedicated 24vac interlock monitors, and 8 dedicated
120vac system monitors used for diagnostics and
providing feedback of faults and system status.
12. Multiple circulator pump control modes.
13. Combustion Air Damper control with proof time,
support for a common combustion air damper.
14. USB/RS485 network plug-in to allow firmware updates
or custom configurations.
15. Optional BACnet or LonWorks interface.
16. Alarm Relay dry contacts, and Audible Alarm.
17. Runtime hours, and Cycles (based on Main Valve
Open).
18. Outdoor Air Reset with programmable setpoint and
ratio.
19. Time of Day clock to provide up to (4) night setback
temperatures.
FEATURES & SPECIFICATIONS HeatNet Control V3
20. Failsafe mode when a Building Management System is
controlling setpoint. If communications is lost, the
boiler/system automatically transfers to local boiler
setpoint control.
21. Rotation Methods (Lead-Lag): True Rotation (based on
boiler runtime) is default. First On First Off (FOFO),
Last On First Off (LOFO) and MIXED are optional.
22. Programmable password protection to secure the
programmable settings.
23. Remote 4-20 mA setpoint control using a mapped
setpoint range to the 4-20 mA control signal.
24. Freeze Protection allowing automatic starting of
boiler(s) using (2) Failsafe modes.
25. Adaptive Modulation. When additional boilers are
called, the Master adjusts all boilers fire rates to
compensate.
26. Mixed boiler types in a system.
27. Support for Domestic Hot Water (DHW) using a 10k
Sensor or a dry contact input from a tank thermostat.
28. Domestic Hot Water relay for use with a pump or
valve.
FlexCore Multi Heat Exchangers
1. Multiple HeatNet controls serving each heat exchanger.
2. Direct wiring for Heat Exchanger - HeatNet to HeatNet
handshaking.
3. New Minibus for digital communication between
internal HeatNet boards.
4. Personality profiles for each FlexCore model.
29. On-board power and socket for Protocessor
BACnet/LonWorks module.
30. HI/LO relay control option from connector J4
31. Resettable Fused interlock power circuit.
32. Additional terminal connector for H-Net shielded cable.
33. Backwards compatible to Version 1.x hardware.
34. Communications board integrated with the main board
from version 1.x control.
35. Base Loading of (1) boiler.
36. Delayed Blower Power staging. Used to minimize
inrush currents by powering the blower 7 seconds after
main power.
37. Domestic Hot Water time out for maximum DHW
runtime.
38. Added the Local Minibus for inter-boiler
communication. Primarily FlexCore series.
Page 9
Specifications
Control Microprocessor based PID modulating control (NOT a safety limit)
Environment -40 °F to 140 °F, <90% RH non-condensing
please refer to the 2008 ASHRAE Handbook, CH12 or later
revision.
A basic multi boiler system typically uses boilers of the
same size and type. With HeatNet, this includes (1) Master
and (1-15) Member boilers. The boilers are connected
together using an H-Net communications cable effectively
creating (1) boiler. This allows the system heating BTUs to
be evenly distributed amongst all of the boilers.
The Version 1.6 HeatNet board requires Minibus
connections for FlexCore boilers with more than (1) heat
exchanger. The Minibus requires a serial data cable between
each HeatNet Control board. The first and last Heat
Exchanger must have the minibus terminated for the bus to
work properly. S1 would be placed in the ON position as
indicated below for the front and rear heat exchangers. The
jumper, JS1 must always be in the position indicated
(closest to S1). It is used for testing.
(LOCAL switch) closes, the system becomes operational
and will fire as many boilers as it needs to maintain the
header water temperature’s setpoint. See the DHW section
to fire using two setpoints.
When a boiler is to be fired in a multi boiler system (header
water temperature is below the heating band), the Master
checks the HeatNet boilers it has available. Then the Master
checks if a Lead Boiler is to be used (LEAD BOILER > 0).
The Master boiler then looks at which type of firing rotation
it has selected: LOFO, FOFO, TRUE (runtime), or MIXED.
In our example we will use the TRUE (runtime) rotation
since it is the default.
The Master now checks all of the runtimes to determine
which boiler has the least runtime based on the MIN
RUNTIME setting in SETTINGS: FIRING MODE: The
MIN RUNTIME setting is the minimum runtime interval in
hours that is used to compare boiler to boiler runtimes.
Once the boiler designated to fire has been determined, the
Master sends the command over the H-Net cable to fire that
boiler and resets the ADD BOILER delay timer to prepare
for the next boiler to fire. If the header water temperature is
still below the heating band and the ADD BOILER delay
timer has expired to zero, the process is repeated until the
header water temperature enters the heating band.
Basic multiple boiler system
A basic multi boiler system can be configured using the
boiler menus to create custom systems/features. These
features are best described in the section: Default Settings & Menu Item Description. Along with these menu items
are hardware support for many auxiliary functions.
Once the system has been properly setup (all default menu
values used and H-Net addresses assigned), the system is
enabled by placing the REMOTE/LOCAL switch to the
LOCAL position on the Master boiler. All Member boilers
must have their respective switches in the REMOTE
position. When the Master boiler’s Heat Demand input
When a boiler receives a command to fire:
NOTE: Runtime messages are displayed in the lower left
corner of the Home Screen. See Section Messages for
descriptions.
1. The system pump relay is enabled and the H-Net
control displays “Waiting for Flow” until the flowswitch closes between J11A, 1 & 2 within the
programmed time (10 seconds default).
2. All elements in the interlock string, terminated between
J11A and J11B, must be closed before the sequence is
allowed to continue.
3. If all interlocks are closed, relay K5 is enabled to
command the combustion-air damper open (if used).
The H-Net control displays “Waiting for Damper to Open” until the damper end switch closes.
4. Relay K6 is enabled energizing the local pump (if
used). The H-Net control commences its Waiting for
Page 12
SETUP & OPERATION HeatNet Control V3
Flow” timer (adjustable 10–240 sec.). The flow switch
contact is checked on terminals J11B, 5 &6.
5. With all the interlocks closed, the boiler start relay K1
is enabled and energizes terminal 6 on the ignition
control. This signal is present on J5 Boiler Start
Operator. The control now displays “Waiting for Start Sequence”
6. The ignition control begins its cycle and provides an
output signal from terminal 4 to the H-Net control J5 Blower. The H-Net control responds and provides an
output signal to the VFD which sets the blower to the
programmed pre-purge speed. If an Ametek blower is
used, a soft start speed is applied before the pre-purge
speed.
7. After air-flow is established the ignition control waits
for the air switch to close. When the air switch closes it
provides an input to terminal 7 and pre-purge timing
commences. The H-Net display indicates “Pre-Purge”.
8. When purge is complete the ignition control energizes
the pilot gas valve from terminal 8, and the spark
generator from terminal 10, beginning a 10-second Pilot
Flame Establishing Period (PFEP). The H-Net control
responds to J5 Pilot Valve and provides an output
signal to the VFD which sets the blower to the
programmed ignition speed. The H-Net display
indicates “Pilot”.
9. At the end of the PFEP the spark generator is de-
energized. If the pilot flame is detected, by the UV
scanner, the ignition control energizes the main gas
valve from terminal 9 to J5 Main Valve. The H-Net
display indicates “Running 0%” (0% indicates PID
modulation signal is not being calculated yet).
10. If main-flame is detected the H-Net control holds the
burner at the low-fire rate for the MODULATION
DELAY time period. After this timer expires, the PID
allows the boiler to modulate and places the boiler into
the running state.
As boilers are added to the system settings in the
SETTINGS: ADAPTIVE MODULATION MOD: DROP
DOWN menu determines when the modulation rate drops
down to compensate for the newly added BTUs. For the
drop down to be active, one boiler needs to be running when
a new boiler is added (see: Introduction: The FLEXCORE CK-SERIES H-Net Control: Master).
If all boilers are firing, the modulation rate is released to go
to 100%. If all boilers are not firing, the modulation is
limited to the MOD-MAX clamp value. The MOD-MAX
clamp is used to keep the boilers running as efficiently as
possible. The following Mixed Boiler System Operation: Selecting Mixed Boilers section outlines this with examples.
NOTE: If the boiler is running as a stand-alone boiler or
is direct modulated (including the AA input),
the MOD-MAX clamp will also be in effect for
the ADD BOILER DELAY time. This is to
minimize thermal shock to the boiler.
Once the header water temperature is in the heating band,
only the modulation rate is used to achieve the target
setpoint. The system will maintain the setpoint until the load
demand increases or decreases.
As the load decreases, the header water temperature will
start approaching the top of the band. The PID now lowers
the modulation rate to the boilers, attempting to keep the
temperature within the heating band. If the system is
delivering too many BTUs, the water temperature will cross
the top of the heating band.
When the header water temperature first exceeds the top of
the heating band, the boilers are again checked for the one
with the most runtime. The selected boiler will turn off
immediately and a shed boiler delay timer will be loaded
with the delay time. This time will need to expire before the
next boiler will be stopped, but only if the header water
temperature remains above the heating band. This timer is
used to allow the header water temperature to return back
into the band when a boiler is stopped. When a boiler is
stopped there is a fixed rate of BTUs (Min Fire) that will be
removed (PID discontinuity to modulate from Min Fire to 0
BTUs on a boiler). The timer allows for this loss of BTUs.
This cycle will continue until the call for heat is satisfied or
the Warm Weather Shutdown feature is enabled.
Mixed Boiler Types Using
Priority Sets
Using the Basic Multi Boiler System Operation, a MIXED
boiler Priority method may be added to control condensing,
non-condensing, base load, or other boiler SETs in a system
together. These sets compose a system which provides for
optimal performance and economy. Having dedicated sets
of boilers gives the system engineer a tool to create many
different boiler systems.
A boiler set can be constructed by simply setting the firing
Priority on each boiler (to be in a set) at the same priority.
Setting all (example) condensing boilers to the highest
Priority of 1, and then setting all (example) non-condensing
boilers to a Priority of 2, will create (2) sets of boilers, one
condensing and the other non-condensing. Once this is
done, the Priority 1 set of condensing boilers will have a
firing order that has a higher Priority and is independent of
the other non-condensing set with the lower priority. The
boiler set with the highest Priority can then be fired based
on a conditional settings menu. The lower Priority set will
follow.
Page 13
SETUP & OPERATION
Mixed Boiler System Operation
Starting Boilers:
When a boiler is to be fired (water temp is below the heating
band), the Master checks the HeatNet boilers it has
available. The Master boiler then looks at which boilers are
returning Priority firing status (set on a boiler in:
(SETTINGS: FIRING MODE: FIRING PRIORITY:
PRIORITY: 1). If the Start condition for the Priority 1 set is
met (SETTINGS: FIRING MODE: MIXED BOILERS
FIRST (example), the Master or Member boiler that is
configured as PRIORITY 1, with the lowest runtime, will be
fired FIRST (example).
As long as the start condition for Priority 1 is met, all
boilers in the PRIORITY 1 set will fire based on runtime.
Once all boilers in the PRIORITY 1 set have fired, the
PRIORITY 2 set of boilers will fire based on runtime.
If the Start condition changes and/or is not met (such as
with: OA T or RET temp), the PRIORITY 2 set of boilers
will fire first/next based on runtime. This has the effect of
flipping the Priority of the sets.
Stopping Boilers:
When a boiler is to be stopped (water temp is above the
heating band), the Master checks the HeatNet boilers it has
available. The Master boiler then looks at which boilers are
returning Priority firing status (set on a boiler in:
(SETTINGS:FIRING MODE: MIXED BOILERS
LAST(example) If the Stop condition for Priority 1 is met,
the Master or Member boiler that are configured as
PRIORITY 1 with the highest runtime will be stopped LAST
(example). As long as the stop condition and SHED
DELAY time are met, all the remaining PRIORITY 1 set of
boilers, will stop based on runtime. If the Stop condition
changes and/or is not met (such as with: OA T or RET
temp), the PRIORITY 2 set of boilers will stop first/next
based on their highest runtime.
A boiler’s firing Priority can be designated as such in:
SETTINGS: FIRING MODE: FIRING PRIORITY:
PRIORITY menu on each boiler. A Priority of ‘1’ is the highest priority, a ‘2’ the lowest (default is always 2).
Page 14
SETUP & OPERATION HeatNet Control V3
Mixed Boilers: Example: Condensing/Non-Condensing
Page 15
CONTROL METHODS HeatNet Control V3
In the example Mixed Boilers: Condensing/Non-Condensing, condensing boilers and non-condensing boilers
are used, but other combinations may also be used. Another
example could use (2) small boilers and set them to
Priority 1 and then use (3) larger boilers and set them to
Priority 2. Using these Priority settings (with the conditions
menu), the small boilers can run first during the shoulder
months (Spring and Fall) and the larger boilers can fire last
during the colder Winter season (base loading set).
Before the MIXED method can be used, the firing mode on
the Master boiler must be set to MIXED. SETTINGS: FIRING MODE: MIXED. Pressing the MIXED BOILERS
tab will enter the conditions menu. The START and STOP
conditions for starting and stopping the Priority boiler set
may be configured here. Temperatures are adjustable.
2. The Return water temperature is below 140F and
condensing occurs. (The Master’s system return water
would need to be used.)
3. The Outside Air Temperature is above a setpoint
determined by the system configuration. This setpoint
ensures that the more efficient condensing boilers run
first during shoulder months (Spring and Fall) when
minimal heating is required. Below this setpoint, larger
boilers should be brought on first to “base load” the
system.
4. Greater efficiency is required.
STOP FIRST
Condensing boilers may be configured to stop first (set to
PRIORITY 1) when:
The Return water temperature is above 140F and
condensing is minimized, thus leaving the larger lower cost
boilers running to carry the load.
1. The Outside Air Temperature is below an adjustable
setpoint determined by the system configuration. This
setpoint ensures that the larger non-condensing boilers
run during the coldest months when maximum heating
is required. Above this setpoint smaller condensing
boilers should be brought on first to run the system as
efficiently as possible.
Once the Mixed Boilers menu has been entered, the firing
order and stop order of the Priority 1 boiler set can be
selected based on up to (3) conditions in the conditional
settings menu. All conditional settings apply to the
Priority 1 boiler set. When the conditional settings do not
apply to the Priority 1 set, the conditional settings will apply
to the Priority 2 boiler set.
Note: If the firmware version for a HeatNet V2 board is at
least 3.47(or a version 3 board), the non-condensing boiler
may hold itself off from being added to the HeatNet
Master’s available to fire list. This would effectively keep
the non-condensing boiler from firing in a condensing
mode, but as a result, may not satisfy the system setpoint.
See: SETTINGS: HEAT EXCHANGER TEMP DISAB:
Start/Stop Priority Conditions
The following is an example using mixed
condensing and non-condensing boilers:
FIRE FIRST
Condensing boilers may be configured to fire first (set to
PRIORITY 1) when:
2. Maximum heating is required
START PRIORITY 1 SET
Selections (always the lowest runtime first):
The condensing boiler set (Priority 1) has a
higher Priority to fire when one of these
conditions is met. Values are adjustable.
FIRST: The condensing boilers (Priority 1) are always
started FIRST
OA T > 15F: The condensing boilers (Priority 1) are
started when the OA temperature is greater than the Mixed
Boiler Outdoor Air Temperature setting.
RET < 140F: The condensing boilers (Priority 1) are
started when the Return water temperature is less than the
Mixed Boiler Return temperature setting (This may not
applicable in most configurations since the local return
temperature on the Master is used to provide a difference
temperature across the heat exchanger. A System Return
sensor will be required. However, the return temperature
sensor may have been moved on the Master to provide
system return temperature on existing installations and is
still supported).
STOP PRIORITY 1 SET
Page 16
Selections (always the highest runtime first):
CONTROL METHODS HeatNet Control V3
The condensing boiler set (Priority 1) has a
higher Priority to stop when one of these
conditions are met. Values are adjustable.
LAST: The condensing boilers (Priority 1) are always
stopped LAST.
OA T < 15F: The condensing boilers (Priority 1) are
stopped first when the OA temperature is less than Mixed
Boiler Outdoor Air Temperature.
RET > 140F: The condensing boilers (Priority 1) are
stopped first when the Return water temperature is greater
than the Mixed Boiler Return temperature. (This may not be
applicable in most configurations since the local return
temperature on the Master is used to provide a delta
temperature across the heat exchanger). A System Return
sensor will be required. However, the return temperature
sensor may have been moved on the Master to provide
system return temperature on existing installations and is
still supported).
Start/stop settings
Any combination of Start Conditions and Stop Conditions
can be used to optimize the mixing of condensing
(Priority 1) and non-condensing boilers (Priority 2) for best
performance/economy.
The default start setting always starts the condensing boilers
(Priority 1 example) first, except for the lead boiler setting.
The lead boiler will always start first if enabled, unless
there is a boiler already running (this includes a Member
boiler in LOCAL). The default stop condition setting always
stops the condensing boilers (Priority 1) last.
If prolonging the life of the heat exchanger(s) on noncondensing boilers is very important, consider starting the
condensing boilers (Fusion-Series) when the return water
temperature is below 140F.
The return water temperature sensor would
need to be moved from the Master’s return
inlet to the system return. The EXCHGR
DELTA may need to be adjusted in SETUP:
AUX FUNCTIONS: HEAT EXCHANGER
to prevent the Master from going to ½ input
when a high DELTA T is reached.
This method would lead to the non-condensing boilers
carrying the load when the system temperature stabilizes
above 140F, since non-condensing boilers will start first
with the Return water temperature is > 140F. The
condensing boilers can then be stopped first when the RET
water temperature is above the 140F. Remember, any
combination of the Start and Stop conditions may be applied
for best performance and economy in the system. Also, noncondensing boilers may be set to go offline when a return
temperature is too low using the SETUP: AUX
FUNCTIONS: HET EXCHANGER: TEMP DISAB menu.
Base load boilers can also be mixed in the same way as
condensing and non-condensing boilers. The base load
boiler(s) can be prioritized in one set (example, Priority 2)
and non-base load boilers (Priority 1). The non-base load
boilers can then be set to fire first and once they are all
firing, the base load boiler would fire.
To minimize the cycling of a large base load boiler, consider
using the stop condition. Change it to the OA T < 15F
(Outside Air Temperature) condition. This setting may be
used to stop the Priority 1 boiler set when the OAT drops
below the OA T setpoint, thus leaving the large base loaded
boiler on and shutting off the condensing boilers first. This
is also true when using the OA T setting to start the
Priority 1 boiler set when the OA T is above the start
setpoint. To use temperatures as start and stop conditions,
the system design temperatures must be known.
Selecting Mixed Boilers
There are a few factors to consider when choosing which
type of boilers to use in a mixed system. These factors need
to be considered when boilers are added or shed. When
BTUs are introduced into the system by adding boilers, the
amount of introduced BTUs should be smooth (linear). If
these factors are not considered, discontinuity in BTUs may
occur when boilers are added and as a result, short cycling
will occur.
1. Turndown: This is the ratio of minimum fire rate to
maximum fire rate: Example: a 20% minimum
modulation = 5:1 turndown (100%mod / 20% mod). A
(1) million BTU boiler = 200,000 BTUs minimum in.
2. MOD MAX CLAMP: This value determines the
maximum modulation % at which the boilers will fire
to, until all available boilers are firing.
3. Total System BTUs.
4. Desired Effective Turndown. This is the lowest
firing rate of the system relative to the maximum firing
rate of the system. The larger the value, the lower the
BTUs that can be delivered to a light load.
5. Piping.
Mixed System Type 1:
High System Turndown
The following examples are of mixed boiler systems with
high effective system turndown and fault tolerance built in.
When boiler types are the same, the system turndown is
limited to the boiler’s min input and fault tolerance is
always present. When the system has mixed boiler types,
consideration needs to be taken on what types can be mixed
properly to achieve a high system turndown and provide
some fault tolerance.
Page 17
CONTROL METHODS HeatNet Control V3
System
MMBTU
Effective
Turndown
MOD
MAX
CK 5:1
24.0
20:1
70%
6000, 6000, 6000,
6000
12.0
20:1
70%
3000, 3000, 3000,
3000
6
20:1
70%
1500, 1500, 1500,
1500
System
MMBTU
Effective
Turndown
MOD
MAX
Priority 1
CK
5:1
Priority 2
CK
5:1
8.0
26:1
45%
1500, 1500
2500, 2500,
9.0
30:1
50%
1500, 1500
3000, 3000
9.5
30:1
50%
2500 2500
5000,5000
CK
Series
1500
2000
2500
3000
3500
4000
Max
Input
1500
2000
2500
3000
3500
4000
Min
Input
300
400
500
600
700
800
5:01
Mod
Max
1200
1600
2000
2400
2800
3200
80%
Mod
Max
1050
1400
1750
2100
2450
2800
70%
Mod
Max
900
1200
1500
1800
2100
2400
60%
Mod
Max
750
1000
1250
1500
1750
2000
50%
CK
Series
4500
5000
6000
7000
8000
9000
Max
Input
4500
5000
6000
7000
8000
9000
Min
Input
900
1000
1200
1400
1600
1800
5:1
Mod
Max
3600
4000
4800
5600
6400
7200
80%
Mod
Max
3150
3500
4200
4900
5600
6300
70%
Mod
Max
2700
3000
3600
4200
4800
5400
60%
Mod
Max
2250
2500
3000
3500
4000
4500
50%
Fault tolerance allows for one boiler in the Priority 1 system
to fail and any boiler(s) in the Priority 2 system to fail and
still provide near linear (continuity) BTU response when
adding boilers. This is illustrated in the following examples
using the Boiler System Response graphs.
The CK Series/Futera III/Fusion-Series Mixed Boiler
System (examples) is advantageous in providing low BTU
input for light loads and high BTUs for heavy loads. The
effective system turndown minimizes short cycling when
light loads are present by assigning smaller boilers to
Priority 1, running them first, and then stopping them last.
In order to achieve the high effective
turndown, smaller boilers are required
(plumbing considerations need to be
considered here due to differing flow/volume
characteristics through the large and small
boilers).
Example Systems:
Non-Mixed Boiler System Examples
CK Series 1500 – 4000 Modulation Parameters
CK Series 4500- 9000 Modulation Parameters
With the traditional Non-Mixed boiler system, the effective
turndown increases by the turndown ratio for every boiler
added. The min fire rate is equal to the minimum BTUs that
can be delivered to the system.
Number of boilers * Turndown Ratio = Effective System
Turndown: 5 * 5:1 = 25:1.
Mixed Boiler System Examples
With the mixed boiler system, a lower minimum fire
rate/BTU can be delivered to the system by using small
boilers with larger boilers. This works in much the same
way as base loading.
When selecting the Priority 1 boiler(s) for a high effective
system turndown, the BTU Min Input is selected first. (See:
CK/Futera III/Fusion Boiler Btu Chart). Next, the MODMAX value of this Priority 1 boiler needs to be greater than:
Mod MAX % =
(Priority 1‘s Min Input + Priority 2‘s Min Input)
Max Input of the Priority 1 boiler
Page 18
CONTROL METHODS HeatNet Control V3
The reason for this is to keep the continuity of BTUs linear
without a BTU bump (discontinuity) when boilers are added
or shed. The Mod Max % can be adjusted to the high side to
allow for tolerance (about 10%) as is indicated in the tables.
This is illustrated in the Boiler System Response 2 graph.
If redundancy is not required, the min inputs of the
Priority 1 boilers may be summed to lower the Mod Max %
value so smaller Priority 1 boilers can be used. The sum of
the min inputs would then need to be divided by the sum of
the Max Input of the Priority 1 boilers. The effect of this
would create a higher turndown. See: EXCEPTION NOTES:
Example: (2) CK 1500, (2) CK 2500
Redundancy: (300 + 500)/1500 = 53%
No Redundancy: (300 * 2) + 500) / (1500*2) =36%
In this example, if “Redundancy” is used, the variable “# of
Priority 1’s” is not used.
EXCEPTION NOTES:
Non-Condensing Boilers chart can help illustrate how the
MOD-MAX value can affect the efficiency by limiting the
input until all boilers have fired. Non-condensing boiler
efficiency is relatively flat compared with condensing as
illustrated in the Typical Efficiency of Condensing Boiler
graph.
Typical Efficiency of Non-Condensing Boilers
Typical efficiency of Flexcore boilers
1. Mixing more than two different size/type boilers
becomes more complex than the scope of this manual
and is not recommended.
2. If using more than one Priority 1 boiler and the
calculated value is <
Priority 1Min * 2
Priority 1 Max Input
Use this result PLUS note 3 value as the
ModMax %.
3. Always add a few % (3-5%) to the calculated MOD
MAX % value to allow a guard band (tolerance).
4. If boilers are of different sizes, try to use larger Priority
2 boilers.
If the calculated Mod MAX % value is greater
than 99%, the combination cannot be used
since short cycling will occur.
Once the Priority 1 and Priority 2 boilers are selected, they
can be multiplied in each Priority set to achieve the desired
system design BTUs. If the # of boilers becomes a large
number, a Priority 1 boiler with a higher Min Input may
need to be selected.
In the Mixed Boiler System table line 1 example, (2) CK
1500s are set as Priority 1 and (2) CK 2500 boilers are set
as Priority 2. With a MOD MAX of 50% (Redundancy),
each 1500 can run to 750M (1500M total) before a 2500 is
called ON (Add Delay timer). Once both 1500s are running
and the 2500 is called on, all (3) boilers will drop to a sum
of 1500M BTUs: Taking this1500M value and dividing by
total M BTUS of the (3) boilers, 1500 +1500+1750 = 5500,
we get 27.27%. (.2727* 1500M) + (.2727* 1500M) +
(.2727* 2500M) or: 409M +409M + 681M = ~1500M and
operate at higher combustion efficiencies
While considering the MOD-MAX value, the lower the
MOD-MAX the greater the combustion efficiency since it
effectively limits the input rate. The Typical Efficiency of
Page 19
CONTROL METHODS HeatNet Control V3
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0
1,500,000
2,750,000
4,000,000
5,000,000
6,000,000
,%
System Load, Btu/Hr
Blr1 (750 MBTU)
Blr1+Blr2+Blr3 (2750 MBTU)
Blr1+Blr2+Blr3+Blr4 (4000 MBTU)
Blr1+Blr2 (1500 MBTU)
8,000,000
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0
2,000,000
3,250,000
5,000,000
7,000,000
9,000,000
Inpt%
System Load, Btu/Hr
Blr 1+2 (2000 MBTU)
Blr 1+2+3 (9000 MBTU)
Blr 1+2+3 (3250 MBTU)
Blr 1 (750 MBTU)
750,000
Boiler System Response 1
(2) CK 1500s, (2) CK 2500’s
When running non condensing boilers at low
input rates, the risk of condensing should be
considered.
The Boiler System Response 1 chart illustrates how each
boiler (in the example) is brought on and fires to 50%, drops
to a lower fire rate and then adds the next boiler (vertical
dashed lines). Once all boilers are firing, the modulation is
released allowing all boilers to fire to 100%.
Now, if (1) CK 1500 (one of the CK 1500s was taken
offline) were used with (2) CK 2500’s and the Mod-Max is
set to 50%, the CK 1500 would fire to 750 MBTUs and wait
for the CK2500 (Boiler System Response 2 graph). Now, the
minimum input rate would be 500M (CK 2500) + the 300M
(CK 1500) (already running, but dropped to low fire, but it
needs to go to 18.75%, when the CK 2500 starts), the total
being 800M. The turndown limits the boiler to running at a
minimum of 20%. With a 50% MOD-MAX clamp, there
would be 50 MBTUS more than needed that would be
added to the system when the CK 2500 fired.
The PID algorithm would then compensate for the
discontinuity (bump) in BTUs and the CK2500 would short
cycle. To compensate for this, the Mod Max percent would
need to be increased by 3%, but should be increased by at
least 5% to 55% to allow tolerance. 10% is a better
tolerance choice if room is available. This allows the load to
fluctuate without causing short cycles.
1500 * .55 = 825 MBTUS.
This new Mod-Max value will allow the sum of the low fire
BTUs of both boilers to fire at; 300 + 500 = 800 MBTUs
with room of 25 MBTUs, and prevent the short cycle
condition.
Boiler System Response 2
(1) CK 1500, (3) CK 2500, 50% Mod-Max
While a CK 1500 running with a CK 2500 is an acceptable
solution, it may not be an optimal choice unless (2) CK
1500s are used in the Priority 1 set and one is allowed to be
taken offline (for Redundancy).
A system employing this redundancy where (1) is allowed
to be taken offline is listed in the MIXED BOILER SYSTEM
chart. This system uses (2) CK 1500s and (2) CK 2500s.
Two of the CK 1500s are treated as one when adding the
min inputs of the Priority 1 set.
In summary, the system should be tuned using the boiler
selection charts and the MOD-MAX value. Since selecting
the Priority 1 boiler is integral to the fault tolerance of the
system, it is important to note any discontinuities in BTUs if
a Priority 1 boiler fails when multiple Priority 1 boilers are
used.
Mixed System Type 2:
Condensing/Non-Condensing
In the following examples, condensing boilers will be used
with non-condensing mass boilers. The reason for creating a
mixed system is primarily to control the system cost.
Note: In a mixed condensing/non-condensing system,
boilers with differing sizes, as outlined in the Mixed System
Type 1: High System Turndown section may also be used.
Page 20
CONTROL METHODS HeatNet Control V3
Local Pump
Local Pump
MASTER
Condensing
MEMBER 1
Condensing
HNETHNET
Header Sensor
System Return Sensor
HNET
Local Pump
Local Pump
System Pump
MEMBER 2
Non-
Condensing
MEMBER 3
Non-
Condensing
Priority 1 SetPriority 2 Set
M
Combustion Air Damper
Outdoor Air Sensor
Outdoor Air
Sensor
System
MMBTU
Effective
Turndown
MOD
MAX
Priority 1
CK 5:1
Priority 2
MB/MW
7.5
25:1
55%
1500,
1500
4:1
1500, 1500,
1500
10.5
35:1
60%
1500,
1500
5:1
2500, 2500,
2500
18
30:1
55%
3000,
3000
5:1
4000, 4000,
4000
24
26:1
55%
4500,4500
5:1
5000, 5000,
5000
MB/MW
CB/CW
500
750
1000
1250
1500
1750
2000
Max
Input
500
750
1000
1250
1500
1750
2000
Min
Input
4:1
125
188
250
312
375
437
500
Mod
Max
80%
400
600
800
1000
1200
1400
1600
Mod
Max
70%
350
525
700
875
1.05
1220
1400
Mod
Max
60%
300
450
600
750
900
1050
1200
Mod
Max
50%
250
375
500
625
750
875
1000
MB/MW
2500
3000
3500
4000
5000
Max Input
2500
3000
3500
4000
5000
Min
5:1
500
600
700
800
1000
Mod Max
80%
2000
2400
2800
3200
4000
Mod Max
70%
1750
2100
2450
2800
3500
Mod Max
60%
300
450
600
750
900
Mod Max
50%
1250
1500
1750
2000
2500
Mixed Condensing/Non-Condensing Boiler
System
Note: The example drawings in this section are simplified.
They are meant to illustrate connections to the HeatNet V3
control. Only major components are illustrated. The system
engineer must ensure additional safeties, piping,
maintenance valves, and components meet code
requirements and safe operation.
Futera III/Fusion/ Boiler Btu Chart (MBH)
Futera XLF Boilers
Mixed Boiler System Examples
For the examples, the RBI FIII/Fusion series water heaters
will be used. These boilers are non-Condensing, fully
modulating, low mass, and HeatNet compatible.
If CB/CW Fusion boilers are substituted for the MB/MW
Futera III boilers, the efficiency is greatly increased due to
the condensing mode of these boilers. When using CB/CW
Fusion boilers, at lower firing rates, the combustion
efficiency is maximized by running the CB/CW Fusion
boilers from low to middle input rates. See: Typical Efficiency of Condensing Boiler graph.
The Mixed Boiler System table show some examples of
mixed systems using different sizes along with Fusion
condensing (Priority 1) and Futera III non condensing
(Priority 2) boilers.
Page 21
CONTROL METHODS HeatNet Control V3
Using the boiler charts and the examples used in: Mixed System Type 1: High System Turndown, a mixed boiler
system can be designed. The Priority 1 boilers should be
setup so as to keep the non-condensing boilers from seeing
return water temperatures of less than 140F to ensure a long
heat exchanger life.
Normally, the Priority 1 boilers (Condensing) will be set to
fire first. Once all the Priority 1 boilers are firing, the next
boiler to fire (after the ADD BOILER timer expires) would
be the Priority 2 (non-condensing). If the return water
temperature has not come up to ~140F, the non-condensing
boilers could fire in a condensing mode. The ADD BOILER
delay timer would have to be set to a long enough period to
ensure this does not happen. Even then, the load may be too
great.
When running with a remote BMS setpoint, care must be
taken that an Outside Air reset setpoint (or other setpoint)
sent by the BMS is not set too low. If the BMS system is
controlling the setpoint close to the condensing temperature,
the return water temperature may never rise sufficiently to
keep boilers out of a condensing mode. HeatNet online is a
good way to monitor this scenario if suspected.
The following note will explain an alternative way (not
depending on the ADD BOILER DELAY) to keep noncondensing boilers from firing in a condensing mode.
HeatNet Master’s request as” unavailable”. As soon as
the return temperature reaches 140F, the boiler will
respond to the Master’s request that it is available to fire.
If the Master boiler is a version 2 board, the Master will
always transmit its Local Return temperature to all
boilers. If the Master is set to Priority 1 and all other
non-condensing boilers are set to Priority 2, the Master
should always remain on if there is a call for heat. This
requires that the Priority 1 boiler be set up to start first
and stop last. Using this method should always send a
valid return temperature to the Member boilers. This
method can also be used with a version 3 board, but a
system return sensor is preferred.
When this condition is in effect, the STATUS * screen will
indicate “blr offline”. While the boiler is in this “not
available” state, it can still be fired locally and failsafe is
still available.
SETUP: AUX FUNCTIONS: HEAT
EXCHANGER: SEND RETURN:
OFF The Master sends its return
temperature to all boilers
RETURN The Master sends its return
temperature to all boilers
NOTE:
If the firmware version for a HeatNet V2 board is at least
3.47(or a version 3 board), the non-condensing boiler
may hold itself off from being added to the HeatNet
Master’s available to fire list. This would effectively keep
the non-condensing boiler from firing in a condensing
mode, but as a result, may not satisfy the system setpoint.
In order to use this feature, the version 2 board would
need to monitor the system or local return temperature.
This can be done locally by setting SETUP: AUX
FUNCTIONS: HEAT EXCHANGER: TEMP DISAB:
RETURN if the there is no pump/valve limiting flow
continuously through the boiler. If there is a pump/valve
limiting the flow through the boiler, the SETUP: AUX
FUNCTIONS: HEAT EXCHANGER: TEMP DISAB: SYS
RET needs to be set. Then the Master boiler needs to set
SETUP: AUX FUNTIONS: HEAT EXCHANGER: SEND
RETURN: to which of its return temperatures it would
send to all boilers. These include the Local Return
temperature or the System Return temperature.
The Member’s menu “SETUP: AUX FUNCTIONS: HEAT
EXCHANGER: TEMP DISAB:” if set to RETURN or SYS
RET, will force the boiler to become unavailable to
HeatNet when the SETUP: AUX FUNCTIONS: HEAT
EXCHANGER: TEMP< 140F. This value is adjustable to
135F if a forced air fan is used. When the SYS RET or
RETURN temperature is <140F the boiler responds to a
SYS RET The Master sends the system
return temperature to all
boilers
SETUP: AUX FUNCTIONS: HEAT EXCHANGER:
LOW TEMP:
OFF No check is made to the return
temperature – boiler remains
online
RETURN Uses the boilers own return
sensor (No pump /valve
present)
SYS RETURN Uses the System Return temp
received from the Master Boiler
(its Local or System Return).
SETUP: AUX FUNCTIONS: HEAT EXCHANGER:
TEMP < 140F
This is the adjustable threshold temperature below
which the boiler will take itself offline.
(1) Degree F of hysteresis is provided so as to not
toggle offline<-to->online at the threshold temp.
Page 22
CONTROL METHODS HeatNet Control V3
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0
3,300,000
4,800,000
6,000,000
8,000,000
10,500,000
System Load, Btu/Hr
Blr 1+2+3 (3300 MBTU)
Blr 1+2+3+4 (4800 MBTU)
Blr 1+2+3+4+5 (10500 MBTU)
900,000
Blr 1 (900 MBTU)
Blr 1+2 (1800 MBTU)
Since the FIII boiler is non-condensing, the efficiency vs.
input is relatively flat. The MOD MAX value will not have
the same impact if the FIII non-condensing boilers were
placed in the Priority 1 set.
In a mixed condensing/non-condensing boiler system
example: (2) CK 1500s are set as Priority 1 and (3)
MB/MW 2500s are set as Priority 2. With a MOD MAX of
60%, each CK 1500 can run to 900M (1800M total) before a
MB/MW 2500 is called ON (Add Delay timer). Once both
CK 1500s are running and the CK 2500 is called on, all (3)
boilers will drop to a total of the 1800M BTUs. Taking this
1800M value and dividing by total M BTUS of the (3)
boilers The sum of the CK 1500, CK 1500, and CK 2500
would equal about 32.7% modulation: (.327* 1500M) +
(.327* 1500M) + (.327* 2500M) or: 490.5M +490.5M +
817.5M =~ 1800M and operate at higher combustion
efficiencies: 32.7% is roughly between the top two lines on
the Typical Efficiency of Condensing Boilers chart.
The 5:1 turndown of the boilers can allow the Mod Max
clamp to go lower, but return water temperatures need to be
taken into account to ensure the Priority 2 boilers don’t
enter a condensing state. Each system is different and
adjustments to the Mod Max value can be adjusted to
achieve the greatest efficiency.
So, for the first 1800 MBTU of load, the combustion
efficiency is maximized by running the (2) CK Series
boilers from low to middle input rates. Running the (2) CK
1500 boilers first, also has the added effect of minimizing
the return water temperatures of <140F from reaching the
non-condensing boilers.
In summary, the system should be tuned using the boiler
selection charts and the MOD-MAX value so that boilers
are brought on and fired in their respective efficiency curve
while maintaining continuity in BTUs. Since selecting the
Priority 1 boiler is integral to the fault/offline tolerance of
the system, it is important to note any discontinuities in
BTUs if a Priority 1 boiler goes offline when multiple
Priority 1 boilers are used.
The Boiler System Response 5 chart illustrates how each
boiler (in the example) is brought on and fires to 60%, drops
to a lower fire rate and then adds the next boiler (vertical
dashed lines). Once all boilers are firing, the modulation is
released allowing all boilers to fire to 100%.
Boiler System Response 5
(2) CK 1500s, (3) MB/MW 2500s
Page 23
CONTROL METHODS HeatNet Control V3
MASTER
System Header Sensor
System Return
Sensor
Local Pump
System Pump
Expansion Tank
Backflow
Prevention
Pressure
Reducing
Ball Valve
System Pump
Supply Header Se nsor
HeatNet
Outdoor Air Sensor
MIN 3X PIPE DIAME TERS
MAX 10X PIPE DIAME TERS
BETWEEN CENTERS
WM
Water Meter
System Supply
System Return Sensor
Heating Control Methods
An overview of the (5) methods for controlling the FlexCore
CK -Series boiler are presented here. They are outlined in
more detail at the end of this section.
Heating Method 1
The first method is to use the FlexCore CK -Series boiler in
its stand-alone modulating method. This method uses a PID
algorithm to maintain a setpoint and is enabled using the
HEAT DEMAND input. Closing a relay contact or switch
across the HEAT DEMAND input will cause the Master
boiler to control all member boilers using H-Net.
A member boiler may also be controlled by the HEAT
DEMAND input (LOCAL mode). The member boiler will
then ignore commands from the Master and maintain its
LOCAL SETPOINT at the supply sensor.
Basic Single Boiler
Heating Method 3
The third method is to allow a remote 4-20 mA or 0-10
VDC signal to control the firing rate (modulation) of the
boiler using the 4-20 mA input, along with the 4-20 mA
REMOTE ENABLE input.
Heating Method 4
The fourth method turns the boiler ON and OFF @ 100%
modulation using the AA terminal.
Heating Method 5
The fifth method uses an RS485 digital communications
cable with the MODBUS protocol. The boiler is controlled
by writing and reading registers using MODBUS
commands. A bridge module may also be used to convert
BACnet or LonWorks protocols to MODBUS.
Short cycling may occur when a firing rate is
sent to a member boiler that would cause the
supply temperature to raise high enough to
trip the operating limit (low flow rate). After
the supply temperature falls, the boiler would
restart and the process may continue. A
member boiler would use its supply (outlet)
sensor to protect itself from short cycling by
limiting the firing rate coming from the
Master. This occurs in the event that the
member’s supply temperature increases above
the (OPERATE LIMIT- OPERATE LIMIT
BAND).
Note: The example drawings in this section are simplified.
They are meant to illustrate connections to the HeatNet V3
control. Only major components are illustrated. The system
engineer must ensure additional safeties, piping,
maintenance valves, and components meet code
requirements and safe operation.
Heating Method 2
The second method is to view the FlexCore CK -Series
boiler as two separate boilers or as a HIGH/LOW boiler
using T1 & T2.
Page 24
Operating Limit
When the Master boiler or an external control input is used
to control a member boiler (i.e. AA, T1-T2, 4-20 mA, HNet), a software operating limit on the member boiler will
be used to limit the maximum output of the member boiler.
This operating limit can be adjusted in the SETTINGS: SETPOINTS: OPERATE LIMIT.
There is also an associated operating limit band that must be
set in conjunction with the operating limit to help prevent
this LIMIT from being reached. Its purpose, is to limit the
output of the boiler as it approaches the operating limit. If
the band is set to 10 degrees, then for every degree that it
approaches the operating limit, the maximum output will be
lessened by 10%. With a band of 20 degrees, for every
degree that it approaches the band, the maximum output will
be lessened by 5%. You can think of this operating limit as
a smart Aquastat which prevents the High Limit from
tripping. This method minimizes boiler short cycling when
using external inputs. The minimum setting is 1 degree and
effectively turns the limit band OFF. The default setting is
20F.
CONTROL METHODS HeatNet Control V3
MEMBER: Close to run at Local setpoint.
MASTER: Close to control all boilers and
run at System setpoint.
Local Pump
Local Pump
MASTER
MEMBER
1
HNETHNET
Space Heating
Loop
Header Sensor
MEMBER
2
MEMBER
3
System Return Sensor
HNET
Local Pump
Local Pump
System Pump
Input Priorities
The FlexCore CK-Series control inputs areprioritized so
that multiple levels of external control can be employed at
the same time. This means that if we are firing the boiler
with a low Priority input and a higher Priority input is called
for, the boiler will now fire at the higher Priority input.
When the high Priority input is removed, the boiler will
revert back to the lower Priority input that is still called.
Priority 1
The AA terminal has absolute control, and if used, will
always fire the boiler at 100% output, regardless of any
other input. The 4-20 mA input may be raised to this
Priority using SETTINGS: 4-20 mA INPUT: PRIORITY.
Priority 2
The HEAT DEMAND input is the next, and provides the
means to operate the boiler in LOCAL MODE when an
external control is not present, has failed, or needs to be
enabled or disabled. A member can override the H-Net
commands using this input.
Priority 3
If a HeatNet (H-Net) Network cable is connected between
boilers, and one is configured as a MASTER (requires
HEADER sensor), then the MEMBER boilers will be
controlled over the network by the MASTER.
The AA terminal, the FAILSAFE mode active, 4-20 mA at
PRIORITY: HIGHEST, and the HEAT DEMAND input
(LOCAL) on a Member, are the only inputs that will
override the H-Net control.
Heat demand input
Master boiler
The MASTER boiler controls the system using a PID
algorithm. Once the boiler is started, a PID algorithm is
used to produce a modulation percentage value from 0100%. This percentage is converted to a PWM, (P)ulse
(W)idth (M)odulation signal by each boiler. The
temperature of the water is maintained by sending this
PWM signal to the Variable Frequency Drive, which in turn
controls the blower motor. Since the main fuel valve is airfuel coupled to the blower, the speed of the blower provides
the firing rate.
Member boiler(s)
Priority 4
The 4-20 mA/0-10VDC input in tandem with the 4-20 mA
REMOTE ENABLE input is next. Any signal over 4.02 mA
or 2.01VDC will start and operate the boiler if the
REMOTE ENABLE is closed.
Priority 5
The lowest Priority is using the boiler as (2) stages
HIGH/LOW. These are the T1 and T2 inputs.
Each of these control methods will now be explained in
more detail:
Heating Method 1
HEAT DEMAND
Closing a relay contact, switch, or jumper across the HEAT
DEMAND input will enable this method. This method
allows operation as a setpoint control. As a setpoint control,
the Master (defined by having a common system supply
header sensor), on the H-Net network can command the
boiler fire rate of all Member boilers. The Master can call as
many boilers that it has available (boilers are auto-detected
over the H-Net cable by the Master) to meet its SYSTEM SETPOINT. The H-Net cable must be connected and will
cause the amber light on the communications board to flash.
The amber light indicates an H-Net Master is broadcasting
control information and a system heartbeat.
A Member (lacking a common system supply header
sensor) boiler may also be controlled by the HEAT
DEMAND input (LOCAL mode). The member boiler will
then ignore commands from the Master and maintain its
own LOCAL SETPOINT at its supply sensor. This can be
viewed as a manual override on a member boiler. Be sure to
observe the proper use of a Common System Damper (See:
AUXILIARY FUNCTION OPTIONS section) and any
system pumps or system common interlocks.
HeatNet Boilers Configured as Reverse Return
Page 25
CONTROL METHODS HeatNet Control V3
Method 2
Stage Control Inputs:
T1 & T2
Features of the HEAT DEMAND input include:
1. The control is designed to predict when to start and
stop the boiler and keep the setpoint in, or as close to
the control band as possible. If PREDICTIVE START
is enabled, the boiler may start when it is in the band
and not below it. This will help to maintain a more
accurate temperature relative to the setpoint. See also:
SETTINGS: FIRING MODE: PREDICTIVE START:
to disable this feature.
2. The control can also use the Outdoor Reset feature.
This feature allows the setpoint to be changed
automatically based on the outside air temperature. If
this feature is used, the control input: OR OVR
(OUTDOOR RESET OVERRIDE), can be used to
override the Outdoor Reset feature and run from the
local setpoint. A contact closure on the ‘AA’ input can
also override this method.
3. The 4-20 mA setpoint control function works in
conjunction with this mode. This function translates a
4-20 mA control signal to a setpoint mapped between
50F and 220F. These (2) temperatures are adjustable to
provide a setpoint range. The minimum start current is
also adjustable between 3.71 and 5 mA. The setpoint
control feature is used in conjunction with the
REMOTE ENABLE input on J12A. This feature is
enabled in the SETPOINTS menu as:
SETPT SOURCE 4-20 mA
Stage control input
The maximum output of the boiler is based on
the MAX VFD setting in the calibration mode
and not the nameplate rating.
The AA, HEAT DEMAND (LOCAL) input, the H-Net, the
4-20 mA input will all override the stage control inputs.
Heating Method 3
4-20 mA Control
4. There is also support for a common system damper,
Heat Exchanger support, and starting the Master first
for common venting. For an overview of each of the
menu settings see: DEFAULT SETTINGS section.
Heating Method 2
STAGE Control T1-T2
The boiler can also be operated in 2 separate stages using
the inputs T1 and T2 inputs. Its intended use is with an
external stage controller with no analog or modulation
outputs.
Closing only one of these contacts tells the boiler to operate
at MINIMUM FIRE.
Closing the other contact will fire the boiler at MAXIMUM
output (the same rate as closing the AA input).
Placing a current source between the + and – 4-20 mA
inputs will allow remote control of the boilers firing rate.
An adjustable starting mA current signal here will start and
then fire the boiler at the minimum fire rate. See:
SETTINGS: 4-20 mA INPUT: CHANNEL MODE.
See section OPTIONAL FEATURES Using the 4-20 mA
input for extensive detail.
A 20 mA signal will fire the boiler at the maximum firing
rate. The input current signal is viewed as a percentage to
the boiler from 0 to 100% (0-20 mA). This means that a
20% (4mA) input signal is required to start the boiler, but
since the boiler is classified as having example: 4:1 turn
down ratio, the boiler can only be fired as low as 25% of
output. Any signal between 20% and 25 %, will fire the
boiler at the minimum fire rate. If the MINIMUM setting of
the boiler is set above the example: 4:1 turndown of 25%
(such as 33%), a control signal change between 25% and
33% will not change the boilers firing rate. Once the control
signal rises above the MINIMUM fire rate, the control
signal will then affect control of the boilers fire rate.
The AA terminal, the HEAT DEMAND, and the H-Net
NETWORK are the only inputs that will override the 4-20
mA input.
Page 26
CONTROL METHODS HeatNet Control V3
Modbus Using
RJ45 Cat 5 cable
Modbus Using
shielded 3 wire.
Building
Management
Method 4: Close this AA contact
to run the boiler at High Fire.
Heating Method 4 AA Input
HIGH FIRE input Control: The AA input will fire the boiler
at HIGH fire (maximum output of the boiler). No other
inputs can override this input.
AA — High fire input
Heating Method 5
MODBUS communications
The System Setpoint Timer also needs to be loaded
periodically to allow the H-Net system to fallback to
Method 1 in the event communications is lost from the
Building Management System (BMS).
This feature can be turned off in SETTINGS:
COMMUNICATIONS: SETPOINT TIMER: OFF. If the
setpoint timer feature is set to ON, the SETTINGS:
COMMUNICATIONS: SETPOINT TIMER may be set to a
time that allows any write to a MODBUS register to reset
the setpoint timer as long as it occurs within that time. This
will reset the setpoint timer without writing the setpoint
timer register. So, periodically writing the setpoint register
will automatically reset the setpoint timer as long as the
write occurs within that time window.
Protocessor option
An optional BACnet or LonWorks bridge module can be
used to connect the MODBUS network to a BACnet or
LonWorks network.
Protocessor bridge module option
The fifth method uses an RS485 digital communications
cable with the MODBUS protocol to control the boiler
using the H-Net network. The Boiler or Boiler network will
run as in Method 1, but instead of the HEAT DEMAND
input, a software form of the HEAT DEMAND input is
used (40001: Boiler/System Enable/Disable). See:
MODBUS COMMUNICATIONS section.
MODBUS connections
This method allows enabling and disabling the boiler or HNet system, changing setpoints, reading boiler(s) status, or
temperatures remotely using digital commands. See the
section: MODBUS Communications.
Page 27
CONTROL METHODS HeatNet Control V3
Domestic Hot Water Methods
Domestic Hot Water control is supported using (6) methods.
When using the Domestic Hot Water methods, the wire
jumper, JPS1 on each control board providing Domestic Hot
Water, must be cut to limit the boiler’s maximum output
temperature to 200F. Refer to Figure 41 for control input
and Figure 49 for output locations.
Jumper JPS1
AUTO: will handle normal heating only applications. It
may also be used when individual boilers have tanks
connected and are controlled with the DHW BOILER?
set to LOCAL.
DHW: is for DHW applications without space heating.
Combination: Will allow combination Space and DHW
heating control of boilers by the Master.
The OR OVR input now functions in many of the
methods as a DHW Heat Demand input (except DHW
Heating Only method), but still retains the original OR OVR
functionality in AUTO, if the DHW menus are not used
(BOILER MODE? OFF). If the DISABLE TO CHANGE
message appears, remember to remove the any call for heat
including the OR OVR input.
When the MASTER TYPE is set to Combination the
MODULAR BOILER menu will contain (2) separate menu
tabs for controlling the ADD BOILER DELAY, SHED
BOILER DELAY, MODULATE DELAY, and the MOD
MAX for the SPACE HEATING and DHW HEATING.
This allows the independent control of boilers by the Master
for each of the (2) PIDs.
Note: Most of these methods use a separate PID control
for the DHW. This means that the Master boiler can be
used to individually control its own DHW tank and
provide space heating functionality at the same time.
A MASTER TYPE is required when using DHW. Its
setting is located under the DISTRIBUTED CONTROL
menu. Any time its setting is changed, a power cycle is required. The menu choices are:
Page 28
CONTROL METHODS HeatNet Control V3
MASTER
MEMBER 2
MEMBER 3
HNETHNET
Tank Sensor
DHW Sensor
Ball Valve
Expansion T ank
Pressure
Reducing
Cold Wate r
Makeup
Backflow
Prevention
Local Pump
Local Pump
Domestic
Supply
Domestic
Supply
WM
Water Met er
HeatNet
HeatNet
Local Pump
HeatNet
DHW Method 1: DHW Heating ONLY using a DHW MASTER and Member Boiler(s) Employing H-Net
Example DHW Only, Reverse Return Piping – Method 1.
DHW METHOD 1: DHW Heating ONLY using a DHW MASTER, Multiple Non-Condensing Boilers
A DHW Setpoint is maintained in the DHW tank based on the Master’s DHW Sensor. The system pump is enabled when the
boiler’s Heat Demand input is closed. Boilers are staged to meet the DHW Setpoint in the tank based on their runtime, and each
boiler will enable its local pump when it is running. The Master modulates the boilers to maintain the setpoint in the tank.
The cold water make up is piped into the supply piping to reduce the possibility of condensing in the boilers.
Page 29
CONTROL METHODS HeatNet Control V3
Master (DHW Only)
Settings
DHW Use Sensor
HeatNet Address
Master Type
Combustion Air Damper
Yes
Automatic
DHW Only
Off
Inputs
Local/Remote
DHW Sensor
JPS1 Jumper must be cut to service DHW
Local
Yes - Tank
Outputs
Local Pump On
When Boiler Running
Member 2
Settings
HeatNet Address
Combustion Air Damper
2
Off
Inputs
Local/Remote
JPS1 Jumper must be cut to service DHW
Remote
Outputs
Local Pump On
When Boiler Running
Member 3
Settings
HeatNet Address
Combustion Air Damper
3
Off
Inputs
Local/Remote
JPS1 Jumper must be cut to service DHW
Remote
Outputs
Local Pump On
When Boiler Running
DHW Method 1Quick StartSettings
DHW METHOD 1: DHW Heating ONLY Using a DHW MASTER and Member Boiler(s)
Note: The example drawings in this section are simplified. They are meant to illustrate connections to the HeatNet V3 control.
Only major components are illustrated.
The system engineer must ensure additional safeties, piping, maintenance valves, and components meet code requirements and
safe operation.
Page 30
Loading...
+ 106 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.