RBI CB500, CB750, CB1000, CB1250, CB1500 Installation And Operation Instructions Manual

...
FTF-I0M-HN-4
82-0312
Finned copper tube Gas boilers (CB), & Water heaters (CW) & Pool heaters (CP)
Boiler manual
Installation and operation instructions
Also read and follow:
HeatNet control manual
instructional information provided with the boiler. Install, start and service the boiler only in the sequence and methods given in these instructions. Failure to do so can result in severe personal injury, death or substantial property damage.
Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause contamination
of the burner, resulting in possible severe personal injury, death or substantial property damage.  e boiler can only be operated with a dust-free air supply. Follow the instruction manual procedures to duct air to the boiler air intake. If the boiler has been contaminated by operation with contaminated air, follow the instruction manual guidelines to clean, repair or replace the boiler if necessary.
A x these instructions near to the boiler. Instruct the building owner to retain the instructions for future use by a quali ed service
technician, and to follow all guidelines in the User’s Information Manual.
10/12 Copyright 2012 Mestek, Inc.
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
F
If the information in this manual is not followed
exactly, a  re or explosion may result causing property, personal injury or loss of life.
Do not store or use gasoline or other  ammable vapors and liquids in the vicinity of this or any other applianc
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch. Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the  re department.
Installation and service must be performed by a quali ed installer, service agency or the gas supplier.
Assurez-vous de bien suivre les instructions données
dans ce e notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides in ammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
BEFORE YOU START . . . . . . . . . . . . . . . . . . . . 2
RATINGS & CAPACITIES . . . . . . . . . . . . . . . . . . 3
BOILER/WATER HEATER LOCATION . . . . . . . . . . . . 3
COMBUSTION AIR & VENTILATION. . . . . . . . . . . . . 3
GENERAL VENTING GUIDELINES. . . . . . . . . . . . . . 5
OUTDOOR VENTING. . . . . . . . . . . . . . . . . . . . .10
GENERAL PIPING REQUIREMENTS . . . . . . . . . . . . 11
HEATING SYSTEM PIPING . . . . . . . . . . . . . . . . .12
DOMESTIC WATER SUPPLY PIPING . . . . . . . . . . . .16
GAS SUPPLY PIPING . . . . . . . . . . . . . . . . . . . .20
ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . 21
GENERAL OPERATION . . . . . . . . . . . . . . . . . . . 22
OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . 24
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . .25
CHECKING & ADJUSTMENTS. . . . . . . . . . . . . . . .26
HEATNET FIELD WIRING . . . . . . . . . . . . . . . . . .28
CONTROL DESCRIPTION . . . . . . . . . . . . . . . . . .28
DIAGNOSTIC . . . . . . . . . . . . . . . . . . . . . . . . . 31
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . .33
TROUBLE-SHOOTING . . . . . . . . . . . . . . . . . . . .33
REPAIR PARTS. . . . . . . . . . . . . . . . . . . . . . . . 34
START-UP SHEET . . . . . . . . . . . . . . . . . . . . . .40
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . 43
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournisseur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien quali é ou par le fournisseur de gaz.
Failure to properly vent this unit can cause excessive
amounts of carbon monoxide resulting in severe personal injury or death!
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRES­SURE OF 160 PSI, 1103 kPa WATER.
2
BEFORE YOU START
 is manual covers the application, installation, operation and
maintenance of a Futera Series  nned copper heating boiler/water heater/pool heater.
To obtain the safe, dependable, e cient operation and long life
for which this heating boiler/water heater was designed, these instructions must be read, understood and followed.
 e Futera Series  nned copper heating boiler/water heaters have
been design certi ed by CSA for use with natural and propane gas under the latest revision of ANSI-Z21.10.3/CSA 4.3, Gas Water
Heaters, ANSI-Z21.13/CSA 4.9, Gas-Fired Low Pressure Steam
and Hot Water Boilers ANSI-Z21.56/CSA 4.7 Gas Fired Pool Heaters and CAN1-3.1, Industrial and Commercial Gas Fired Packaged Boilers. Each unit has been constructed and hydrostatically
tested for a maximum working pressure of 160 psi, 1103 kPa in
accordance with Section IV of the A.S.M.E. Boiler and Pressure Vessel Code.
All aspects of the boiler/water heater installation must conform to
the requirements of the authority having jurisdiction, or, in the
absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision. Where required by the authority
having jurisdiction, the installation must conform to the Standard
for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
Finned copper tube gas boilers & water heaters – Boiler Manual
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
In Canada, the installation must be in accordance with the requirements of CSA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
If installed in the Commonwealth of Massachuse s, you MUST FOLLOW the additional instructions contained in RBI’s instruction sheet MACODE-3. Which is located in the back of this manual.
 e owner should maintain a record of all service work performed
with the date and a description of the work done. Include the name of the service organization for future reference.
Direct all questions to your RBI distributor or contact the RBI Customer Service Department at: 260 North Elm Street, West eld, MA 01085 for US or 7555 Tranmere Drive, Mississauga ONT L5S
1L4 for Canada. Always include the model and serial numbers from
the rating plate of the boiler/water heater in question.
RATINGS & CAPACITIES
Before undertaking the installation of the Futera Series boiler/water heater check the rating plate to ensure that the unit has been sized properly for the job.  e “Net AHRI Ratings” specify the equivalent amount of direct copper radiation that the unit can supply under normal conditions. Also ensure that the unit has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1.  is boiler/water heater is suitable for indoor and outdoor installations. Locate the boiler/water heater in an area that provides good access to the unit. Servicing may require the removal of jacket panels. Allow the minimum clearances between adjacent construction and the boiler/water heater as listed in Table 1.
Service clearances are not mandatory, but are recom-
mended to ensure ease of service should it be required.
Table 1
Clearance to Combustibles
To p 6 153 30 762
Back 6 153 24 610 Left Side 6 153 24 610 Right Side 6 153 24 610 Front 6 153 30 762
in mm in mm
Service
Clearance
2. An optimum site will be level, central to the piping system, close to a chimney or outside wall and have adequate fresh air for combustion. Ensure that the boiler/water heater is level from front to back and from side to side. Use metal shims to level the boiler/water heater. Electrical and electronic components must also be protected from exposure to water during operation and maintenance. DO NOT install this boiler/water heater in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
3. Ensure that the  oor is structurally sound and will support the weight of the boiler/water heater.
 e Futera may be installed directly on combustible
 ooring, but never on carpeting.
4. Locate the boiler/water heater in an area that will prevent water damage to adjacent construction should a leak occur or during routine maintenance. If such a location doesn’t exist, a suitable drain pan that’s adequately drained must be installed under the unit.
5. DO NOT place this boiler/water heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure, see “GENE L VENTING GUIDELINES”.
6. NEVER place this boiler/water heater in a location that would subject it to temperatures at or near freezing, see the
“FREEZE PROTECTION” section on page 11.
Never store combustible materials, gasoline or any
product containing  ammable vapors or liquids in the vicinity of the boiler/water heater. Failure to
comply with this warning can result in an explosion or  re causing extensive property damage, severe
personal injury or death!
COMBUSTION AIR & VENTILATION
 is boiler/water heater must be supplied with
combustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and all applicable local building
codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. Failure to provide adequate combustion air for this boiler/ water heater can result in excessive levels of carbon monoxide which can result in severe personal injury
or death!
To operate properly and safely this boiler/water heater requires
a continuous supply of air for combustion. NEVER store objects on or around the boiler/water heater!
3
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
F
Combustion air contaminated with  uorocarbons
or other halogenated compounds such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber.  ese acids will cause premature failure of the boiler/water heater voiding the warranty!
If the boiler/water heater is operated while the building
is under construction it MUST be protected from wood, concrete, sheet rock and other types of dust. Failure to properly protect the unit from construction dust will damage the unit voiding the warranty!
Buildings will require the installation of a fresh air duct or other means of providing make-up air if the intake air option isn’t used. Any building utilizing other gas burning appliances, a  replace, wood stove or any type of exhaust fan must be checked for adequate combustion air when all of these devices are in operation at one time. Sizing of an outside air duct must be done to meet the requirements of all such devices.
Never operate the Futera in an environment subjected
to a negative pressure unless it is Direct Vented. Failure to comply with this warning can result in excessive levels of carbon monoxide causing severe personal injury or death!
Where directly communicating with the outdoors or communi-
cating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in
2
/4000 Btu/hr, 550 mm2/kW
of the total input rating of all of the equipment in the enclosure.
Where communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1 in
2
2000 Btu/hr, 1100 mm2/kW of the total input rating of all of
the equipment in the enclosure.
When ducts are used, they must have the same cross-sectional area
as the free area of the opening to which they connect.
When calculating the free area necessary to meet the make-up
air requirements of the enclosure, consideration must be given to the blockage e ects of louvers, grills and screens. Screens must have a minimum mesh size of 1/4 in, 6.4 mm. If the free area through a louver or grill is not known, ducts should be sized per
Table 2.
Canadian installations must comply with CSA B149.1 when
air supply is provided by natural air  ow from the outdoors for natural dra , partial fan-assisted, fan-assisted, or power dra -
assisted burners, there shall be a permanent air supply opening(s) having a cross-sectional area of not less than 1 in
2
per 7,000
Btuh (310 mm2 per kW) up to and including 1 million Btuh,
plus 1 in2 per 14,000 Btuh (155 mm2 per kW) in excess of
1 million Btuh.
/
All Air From Inside The Building
If the Futera is to be located in a con ned space, the minimum clearances listed in Table 1 must be maintained between it and any combustible construction. When installed in a con ned space without the intake air option, Figures 5 and 6, two permanent openings communicating with an additional room(s) are required.
 e combined volume of these spaces must have su cient volume
to meet the criteria for an uncon ned space.  e total air requirements of all gas utilization equipment,  replaces, wood stoves or any type of exhaust fan must be considered when making this determination. Each opening must have a minimum free area of
1 in2/1000 Btu/hr, 2200 mm2/kW based on the total input rating
of ALL gas utilization equipment in the con ned area. Each opening must be no less than 100 in2, 64,516 mm2 in size.  e upper opening must be within 12 in, 305 mm of, but not less than 3 in,
76 mm from, the top of the enclosure.  e bo om opening must
be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bo om of the enclosure.
All Air From Outside The Building
When installed in a con ned space without utilizing the intake
air option two permanent openings communicating directly with,
or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present.  e upper opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure.  e bo om opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bo om of the enclosure.
Table 2 Make-up Air Louver Sizing
Required Cross Sectional Area
2
75% Free Area
Metal Louvers
2
in
cm
1/4 in 6.4 mm
Input
(MBH)
500 125 806 167 1077 500 3226
750 187 1206 250 1613 750 4839 1000 250 1613 333 2148 1000 6452 1250 313 2019 416 2684 1250 8065 1500 375 2419 500 3226 1500 9677 1750 437 2819 583 3761 1750 11,290 1999 500 3226 667 4303 2000 12,900
Wire Screen
2
cm
in
2
25% Free Area
Wooden Louvers
in
2
cm
2
Intake Air Option – General Guidelines
 is con guration provides combustion air directly to the boiler/ water heater’s air intake adapter using a dedicated pipe when using
the direct vent option. Combustion air can be drawn in horizontally through the same outside wall which terminates the exhaust gases or vertically through the roof, see Figures 1, 2, 3 & 4.
Common intake air systems may be used provided
the common duct is sized properly. An intake combustion air damper should be installed if the common vent option is used in the intake air pipe of each heater. Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
4
Finned copper tube gas boilers & water heaters – Boiler Manual
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
Single wall galvanized smoke pipe, single wall aluminum pipe,  exible aluminum pipe, PVC or CPVC pipe can be used for the intake air pipe. It must be sized per Table 3.
Table 3 Intake Air Pipe Sizing (Up to 60 ft)
Model
Size
500 8 203
750 8 203 1000 8 203 1250 10 254 1500 10 254 1750 12 305 2000 12 305
Note: Max horizontal/vertical intake pipe 60 ft equivalent.
in mm
All joints in metal intake air systems must be secured using corro-
sion resistant fasteners and sealed using a suitable Silicone caulk. If PVC or CPVC is used, the joints must be cleaned with a suitable solvent and connected using a solvent based PVC cement.  e
combustion air system MUST be supported by the building structure not the boiler/water heater.
A combustion air damper interlocked with the unit
should be installed in the intake air pipe when the in ltration of subfreezing air could occur, otherwise the unit could freeze up voiding the warranty!
All vent systems must be fully supported by the building structure
and not by the boiler/water heater. Appropriate thimbles and  re­stops must be used where required.
Common vent systems must be properly engineered
and sized, please contact the factory.
A UL listed stainless steel vent system must be used
unless this unit is   ed with an RBI supplied non metallic vent kit. Failure to comply with this warning
can cause excessive levels of carbon monoxide resulting
in severe illness and death!!
For instructions utilizing the non-metallic vent option,
see Addendum (FTF-PVCVO) for PVC and (FTF-
PPVO) for Polypropylene.
VENT SYSTEM OPTIONS
 e  ue products in the vent system may be cooled below their
dew point and form condensate in the  ue.  e materials used for
a Category IV vent must be resistant to any corrosive damage from  ue gas condensate.  e  ue from a Category IV vent system must have a condensate drain with provisions to properly collect
and dispose of any condensate that may occur in the venting system.
 e Futera Fusion may be vented the following ways:
Intake Air Option – Vertical Guidelines
 e maximum equivalent length for the vertical intake air pipe is
60  , 18.3 m. Each 90° elbow and the intake air terminal are equal to 10 linear  , 3.0 m of pipe, see Table 3.
An approved, nonrestrictive intake air terminal must be used.  e
intake air terminal must terminate as shown in Figure 3.  e penetration point in the roof must be properly  ashed and sealed.
Intake Air Option – Horizontal Guidelines
 e maximum equivalent length for the horizontal intake air pipe
is 60  , 18.3 m. Each 90° elbow and the intake air terminal are equal to 10 linear  , 3.0 m of pipe. If horizontal runs exceed 5  , 1.5 m they must be supported at 3  , 0.9 m intervals with overhead hangers.  e certi ed intake air terminal from RBI must be used, see Figures 1, 2 and 4.
GENERAL VENTING GUIDELINES
 e vent installation must be in accordance with Part
7, Venting of Equipment, of the National Fuel Gas
Code, ANSI Z223.1/NFPA 54-latest revision or appli­cable provisions of the local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death!
1) Direct Vent, Positive Pressure, Category IV uses a vent system certi ed to UL 1738 for installations in the United States, ULC S636 for installations in Canada. Combustion air is piped from the outdoors to the blower inlet.
2) Side Wall Vent, Positive Pressure, Category IV uses a vent system certi ed to UL 1738 for installations in the United States, ULC S636 for installations in Canada. Combus­tion air is obtained from the space in which the unit is installed.
3) Vertical Vent, Positive Pressure, Category IV uses a vent system certi ed to UL 1738 for installations in the United States, ULC S636 for installations in Canada. Combustion air is obtained from the outdoors or the space in which the unit is installed.
4) Vertical Vent, Negative Pressure, Category II (common venting) requires negative pressure in vent (natural dra ). Requires a metal chimney system approved for Category II venting.  is method is required if common venting multiple Fusion boilers.
All venting and combustion air material supplied by
installer. All venting materials must be approved for the application. Consult the vent manufacturer’s product literature.
 e maximum equivalent length for the  ue outlet vent
system for Category IV conditions is 60  , 18.3 m.
Use Table 4 for the equivalent lengths per   ing. Table 4 - “Category IV Equivalent Length per Fi ing” chart is meant as a guideline for preliminary sizing. If vent
length approaches 75% of maximum length listed an engineered vent system calculation must be performed, consult factory.
5
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
F
Table 4 Category IV Equivalent Length Per Fitting
Model/Outlet
Diameter
Standard Tee 1.25 25 ft 25 ft 30 ft 30 ft 35 ft 40 ft 40 ft Boot Tee 0.65 15 ft 15 ft 15 ft 15 ft 15 ft 20 ft 20 ft Cap - Low Res (UL) 0.50 10 ft 10 ft 10 ft 10 ft 10 ft 15 ft 15 ft 45° w/Bird Screen 0.40 10 ft 10 ft 10 ft 10 ft 10 ft 10 ft 10 ft Elbow - 90° 0.38 10 ft 10 ft 10 ft 10 ft 10 ft 15 ft 15 ft Elbow - 45° 0.15 5 ft 5 ft 5 ft 5 ft 5 ft 5 ft 40 ft
*Equivalent lengths based on listed K-factors and (5x) pipe diameters straight length between  ttings.
*K
CB5007"CB7507"CB10007"CB12508"CB15008"CB1750
Must consult factory when venting single or multiple unit(s)
over 60 equivalent feet. Mechanical system may be required.
Equivalent Feet of Straight Pipe
10"
CB2000
10"
Horizontal Direct Vent Systems Figures 1 & 2
 e vent materials used in horizontal vent systems must be certi ed
to UL 1738 for installations in the United States, ULC S636 for installations in Canada.  e certi ed vent terminal from RBI must also be used.
If any part of a single wall metal vent system passes through an
unheated space, it must be insulated with insulation rated for 400°F,
204°C. Structural penetrations must be made using approved  re-
stops. For best results, horizontal vent systems should be as short and straight as possible.
 e vent system must be both gas tight and watertight. All seams
and joints in metal pipes must be joined and sealed in accordance
with the vent system manufacturer’s instructions.
When horizontal vent runs exceed 5  , 1.5 m they must be supported
at 3  , 0.9 m intervals with overhead hangers.  e vent system must be pitched down, toward the vent terminal, 1/4 in/ , 20 mm/m. If any part of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400°F, 204°C.
Horizontal vent systems shall terminate at least 4  , 1.2 m below, 4  , 1.2 m horizontally from or 1  , 0.30 m above any door, window
or gravity air inlet into any building. It must not terminate less than
4  , 1.2 m horizontally from, and in no case above or below, unless
a 4  , 1.2 m horizontal distance is maintained, from electric meters, gas meters, regulators and relief equipment and not less than 7  ,
2.1 m above adjacent public walkway.  e bo om of the vent terminal(s) shall be located at least 5  , 1.5 m above the air intake terminal(s) unless there is a minimum 5  , 1.5 m horizontal separation between them. Avoid terminal locations likely to be a ected by winds, snowdri s, people and pets. Protect building materials and vegetation from degradation caused by the  ue gases.
DIRECT VENT, POSITIVE PRESSURE, CATEGORY IV
In this con guration the boiler/water heater blower is used to push the  ue products to the outdoors while drawing combustion air from the outdoors.  e Intake Air Option instructions under the
“COMBUSTION AIR & VENTILATION” section must be
followed!  e vent system must be sized per Table 5.
Table 5 Category IV
Model
Size
500 7 178
750 7 178 1000 7 178 1250 8 203 1500 8 203 1750 10 254
2000 10 254
Pipe Diameter (Min.)
(Up to 60 ft)
in mm
6
Vertical Direct Vent Systems – Figure 3
If any part of a single wall metal vent system passes through an unheated
space, it must be insulated with insulation rated for 400°F, 204°C. Structural penetrations must be made using approved  re-stops.
An approved, nonrestrictive vent terminal must be used.  e top
of a vertical vent system must extend at least 51/2  , 1.7 m above the roof surface and maximum snow line that it passes through,
4  , 1.2 m above the intake air terminal, see Figure 3.
In addition the vent system must conform to the dimensions shown
in Figure 3.  e penetration point in the roof must be properly  ashed and sealed.
 e vent system must be gas tight. All seams and joints in metal
pipes must be joined and sealed in accordance with the vent system manufacturer’s instructions.
Combination Direct Vent Systems – Figure 4
 e boiler/water heater can be vented vertically with the intake
air piped horizontally through an outside wall. Follow the instruc­tions in the Intake Air Option – Horizontal Guidelines on page
5. Also follow the general instructions in the “COMBUSTION AIR & VENTILATION” and “GENE L VENTING GUIDE LINES” sections.
Finned copper tube gas boilers & water heaters – Boiler Manual
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
Figure 1 Horizontal Air Intake and Venting for a Single Direct Vent System
16 FT 4.9 m
1.5 FT 0.5 m
1/4 IN. PER FOOT
20 mm/m
When running horizontal combustion air and venting for single or multiple units, exhaust and combustion air terminals must be installed on the same plane (outside wall) in order to prevent pressure di erences due to prevailing winds. In cold climates, double-wall or insulated inlet pipe recommended to prevent condensation.
Figure 2 Horizontal Air Intake and Venting for Multiple Direct Vent Systems
MBH
500 TO 1000
1001 TO 2000
2001 TO 4000
4001 & LARGER
kW 146 TO 293 293 TO 586
586 TO 1172
1172 & LARGER
FT m
5 1.5 10 3.1 15 4.6 20 6.1
5 FT 1.5 m
1.5 FT 0.5 m
1000 BTU’S
2 IN. 5.0 cm
7
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
F
10 FT 3.1 m
4 FT
1.2 m
5 FT
1.5 m
1.5 FT
0.5 m
5 1/2 FT
1.7 m
Figure 3 Vertical Air Intake and Venting for a Direct Vent System
Locate exhaust terminal downwind to reduce  ue gas recirculation.
Figure 4 Horizontal Air Intake and Venting for Multiple Direct Vent Systems
3 FT. 1 m
1.5 FT. .5 m
10 FT. 3.1 m
8
Finned copper tube gas boilers & water heaters – Boiler Manual
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
SIDE WALL VENT, POSITIVE PRESSURE, CATEGORY IV – Figure 5
In this con guration the boiler/water heater blower is used to push the  ue products horizontally to the outdoors, see Figure 5.  e air for combustion is taken from the space in which the unit is installed.  e applicable instructions under the “COMBUSTION AIR & VENTILATION” section must be followed!  e vent guidelines under the Horizontal Direct Vent Systems section must also be followed.
Figure 5 Side Wall Venting
1/4 IN. PER F00T
20 mm/m
Figure 6 Vertical Venting with a Metal Chimney System
10 FT. 3.1 m
1.5 FT 0.5 m
VERTICAL VENT, POSITIVE PRESSURE,
CATEGORY IV – Figure 6
(Vent pipe equivalent length up to 60  , 18.3 m maximum)
Masonry chimneys, when used, must be lined with a metal liner certi ed for Category IV venting.
A through inspection of the masonry chimney must be performed
to ensure that the chimney is clean, properly constructed lined, and sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and dra problems.
VERTICAL CHIMNEY VENTING NEGATIVE
PRESSURE — CATEGORY II
Category II venting is required for multiple Fusion
boilers connected to a common vent. Common vent systems cannot be pressurized.
 e Fusion is listed as a CategoryII appliance when vented vertically
into a listed metal chimney system.  e chimney must provide a
negative pressure not greater than 0.10inch, 2.5 mm WC at the
boiler/water heater  ue collar with the unit running.
When using a listed metal chimney system the chimney
system manufacturer’s instructions must be followed.
Masonry chimneys, when used, must be lined with a metal liner certi ed for Category IV venting.
(Common Venting)
9
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
F
g
 e vent piping must be large enough to safely vent the combined output of all of the appliances connected to the system.
If an appliance using any type of a mechanical dra
system operating under positive pressure is connected to a chimney  ue, never connect any other appliances to this  ue. Doing so can result in excessive levels of carbon monoxide which can cause severe personal injury or death!
CATEGORY II CHIMNEY INSPECTION
& SIZING
Masonry chimneys, when used, must be lined with a
metal liner certi ed for Category IV venting.
A thorough inspection of the masonry chimney must be performed
to ensure that the chimney is clean, properly constructed, lined and sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and dra problems.
Table6 lists the minimum riser sizes required for the Fusion boiler/
water heater.
Vent Connections
Locate the boiler/water heater as close to the chimney as possible. Use the shortest, straightest vent connector possible for the instal-
lation. If horizontal runs exceed 5  , 1.5 m they must be supported at 3  , 0.9 m intervals with overhead hangers.
 e vent connector should be sloped up toward the chimney at a
minimum rate of 1/4 in/ , 21 mm/m. On masonry chimneys the connector must terminate  ush with the inside of the chimney  ue.
Always provide a minimum clearance of 6 in, 152 mm between
single wall vent pipe and any combustible materials.
Failure to maintain minimum clearances between vent
connectors and any combustible material can result in a  re causing extensive property damage, severe personal injury or death!
Exit cones are favorable when used to increase
the velocity of the  ue gas exiting the stack and, may also help, in cold climates, to reduce ice build­up. Exit cone terminations must be supplied by others, installed per manufacturer’s instructions, and meet local and federal code.
eneric exit cone
Table 6 Equivalent Breeching & Chimney Size, Negative Pressure
Model
Size
500 7 178
750 7 178 1000 8 203 1250 8 203 1500 8 203 1750 10 254
2000 10 254
Note: These sizes are based on a 20 ft, 6.1 m chimney height.
Pipe Diameter
in mm
CATEGORY II VENT CONNECTIONS
Locate the boiler/water heater as close to the chimney as possible. Use the shortest, straightest vent connector possi ble for the installation. If horizontal runs exceed 5  , 1.5 m they must be supported at 3  ,
0.9 m intervals with overhead hangers.
 e boiler vent connectors should be sloped up toward the breeching
at a minimum rate of 1/4 in per  , 21mm per m.
Always provide a minimum clearance of 6 in, 152 mm
single wall vent pipe and any combustible materials.
Failure to maintain minimum clearances between vent connectors and any combustible material can result in a  re causing extensive property damage, severe personal injury or death!
between
OUTDOOR VENTING
When installed outdoors the Futera Fusion must be   ed with the
factory supplied outdoor hood, air intake adapter with  lter and exhaust terminal, see Figure 7. Multiple units must be spaced per
Figure 8.
 e boiler/heater must be at least 2  , .62 m from any door, window
or gravity air inlet into any building and at least 3  , 1 m from any overhang unless local codes dictate di erently.
Avoid locations where wind de ection o of adjacent walls,
buildings or shrubbery might cause a downdra .  e unit(s) should be located at least 3  , 1 m from structures. Outdoor installations are not recommended in areas where the danger of snow blockage exists.
Do not place the boiler/water heater in a location that
would subject it to runo from adjacent buildings or damage may occur voiding the warranty!
Outdoor Installations
 e Futera Boiler is certi ed for outside installations in temperate climates only.
1.  e condensate traps located under the secondary heat exchanger and the vent pipe must be wrapped with heat tape to ensure the traps never drop below 32°F.
2.  e vent pipe must be insulated to prevent freezing of condensate in the pipe.
3.  e boiler and system must be  lled with an ethylene glycol/ water antifreeze mixture not to exceed 50% glycol by volume.
4. All water piping exposed to low temperatures must be insulated.
10
Finned copper tube gas boilers & water heaters – Boiler Manual
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
A
Figure 7 Outdoor Venting
Figure 8 Multiple Outdoor Units
2 FT
(0.62 M)
GENERAL PIPING REQUIREMENTS
Improper piping of this boiler/water heater will void
the manufacturer’s warranty and can cause boiler failure resulting in  ooding and extensive property
damage! Excessive water hardness causing scaling in the copper heat exchanger tubes is NOT covered under the manufacturer’s warranty, see Table 8. Excessive pi ing and erosion of the internal surface of the copper heat exchanger tubes is NOT covered under the manufacturer’s warranty if the result of high water  ow rates.
Shut o valves and unions should be installed at the
inlet and outlet connections of the boiler/hot water
heater to provide for isolation of the unit should
servicing be necessary.
Freeze Protection
Installations in areas where the danger of freezing exists are not recommended unless proper freeze protection is provided.  e following precautions MUST be observed:
A continuous  ow of water through the unit MUST be maintained!
1.  e pump responsible for  ow through the boiler/water heater
must run continuously!
2. An ethylene glycol/water mixture suitable for the minimum temperature that the unit will be exposed to must be used.
 e pump must be capable of producing a minimum of 15%
more  ow and overcoming a 20% increase in head loss. Domestic water systems must be isolated from the water heater by the use of a heat exchanger or other approved method.
3. If the unit must be shut o for any reason the electric, gas and water supplies MUST be shut o and the unit and its pump completely drained.
3 FT
(1 M)
RIOM-60 REV.
Improper outdoor installation of this unit can cause
boiler failure voiding the manufacturer’s warranty!
Condensate Piping
 e condensate trap provided with the boiler must be a ached to
the bo om pan and piped to a suitable  oor drain or condensate pump. If a condensate neutralization device is installed, it must be positioned prior to boiler room drain. Condensate  ll trap must be maintained with  uid.
Relief Valve
Pipe the discharge of the pressure relief valve as shown in Figure 9.
Never install any type of valve between the boiler/
water heater and the relief valve or an explosion causing
extensive property damage, severe personal injury or death may occur!
11
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
F
Flow Switch
 e  ow switch supplied with the boiler/water heater must be
wired to the terminal strip in the control panel to prevent the boiler from  ring unless there’s adequate water  ow through the unit.  e  ow switch must be installed in the supply piping adjacent to the boiler outlet connection.
Failure to properly install the  ow switch may result
in damage to the boiler/water heater heat exchanger voiding the warranty!
HEATING SYSTEM PIPING
General Piping Requirements
All heating system piping must be installed by a quali ed technician
in accordance with the latest revision of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV, and ANSI/ASME CSD-1, Standard for Controls and Safety Devices for Automatically Fired Boilers. All applicable local codes and ordinances must also be followed. A minimum clearance of 1 in, 25 mm must be maintained between heating system pipes and all combustible construction.
All heating system piping must be supported by suitable hangers
not the boiler.  e thermal expansion of the system must be considered when supporting the system. A minimum system pressure of 12 psig, 82.7 kPa must be maintained.
Bleed Air From Boiler
Open the water heater piping bleed valves one at a time, to purge the air trapped in the primary and secondary heat exchangers. Refer to piping drawings (Figures 9, 10 & 11) for bleed locations.
Heating Boiler Piping Connections
 e supply and return connections should be sized to suit the system,
see Table 7.
Table 7 Supply & Return Pipe Sizing
Model Size Supply Size Return Size
500 thru 1000 2” NPT 2” NPT
1250 thru 2000 2 1/2” NPT 2 1/2” NPT
Pump Requirements
 is low mass boiler requires a continuous minimum water  ow
for proper operation.  e boiler pump is sized to overcome the head loss of the boiler and the near piping in order to achieve the required temperature rise.  e temperature rise across the boiler must never exceed 35°F, 19.4°C.  e adjustable pump delay turns the pump on each time the burner  res and runs the pump for 20 to 600 seconds a er the call for heat is satis ed.
 e maximum allowable primary heat exchanger
temperature rise is 35°F, 19.4°C.
 e maximum allowable  ow rate through a Futera Fusion boiler
is 97 GPM, 6.1 L/s on 500 through 1000 models and 136 GPM,
8.6 L/s for 1250 through 2000 models.  e Cupro-Nickel heat exchanger allows for 108 GPM, 6.8 L/s on 500 through 1000 models and 151 GPM, 9.5 L/s on 1250 through 2000 models.
Factory Supplied - On Board - Circulating Pump
 e factory installed - on board - pump is sized to work the total
boiler head loss plus an additional (30  ) of pipe and (6 elbows)
- (min pipe diameter of inlet/outlet boiler water connections - see Table 7). Please consult factory for systems outside these parameters.
Low Water Cuto
If a boiler is installed above any radiation elements it must be   ed with a low water cuto device.
Refer to the wiring diagram supplied with the boiler/water heater
for proper wiring connections.
Expansion Tank & Air Separator
An expansion tank or other means to control thermal expansion
must be installed in the heating system. An expansion tank must be installed close to the boiler on the suction side of the pump. An air scoop and automatic air vent must also be installed to eliminate air trapped in the system.
Primary/Secondary Piping
Figure 10 shows a typical primar y/secondary piping system. Boilers
connected to heating systems using zone valves, zone pumps, or systems that have excessive  ow rates must be isolated from these systems to protect the boiler.
Multiple Boiler Systems
Systems using multiple boilers can also be installed using a primary/ secondary manifold system, Figure 11.
Piping For Use With Cooling Units
 e boiler, when used in connection with a refrigeration system,
must be installed so the chilled medium is piped in parallel with the boiler. Appropriate valves must be used to prevent the chilled
water from entering the boiler.
When a boiler is connected to a heating coil that may be exposed
to refrigerated air from an air handling device, the piping system must be equipped with  ow-control valves or some other automatic means of preventing gravity circulation of the boiler water during the cooling cycle.
12
Finned copper tube gas boilers & water heaters – Boiler Manual
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
Figure 9 Futera Fusion Secondary Bypass Piping
Discharge Pipe: Do not restrict  ow. Pipe size equal to valve outlet.
Pump
Valve
Balance Valve
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
Discharge so as to avoid exposure of persons to hot liquid or vapor and to allow complete drainage of relief valve and piping.
NOTES:
1. Fill condensate drain trap with water or approved anti-freeze solution prior to start-up.
2. Air purging valve may be located on pump or  ange.
Item
Number Description
1
2
3
4
5
6
7
8
3-Way Valve
Air Purging Valves
Flow Switch
Circulator
Pressure Relief Valve
T & P Gauge
Primary Heat Exchanger Drain Valves
Condensate Drain Trap
Thermometer
Aquastat Union
Automatic
Air Vent
Temperature &
Pressure
Relief Valve
Vacuum
Relief Valve
Drain Valve
(Typ.)
3-Way
Mixing Valve
13
Fi
nned copper tube gas boilers & water heaters – Boiler Manua
l
F
F
Figure 10 Typical Primary/Secondary, Low Temperature Piping System (See Notes)
H-16 REV C
NOTES:
1. Boiler circuit piping must be sized large enough to handle maximum  ow through unit.
2. Boiler and pump purging required. Air must be purged from 3-way valve after the boiler is  lled. Use purge valves provided. Purge valve may be located on pump  ange. On multiple boiler installations the  ow switch may fail due to trapped air. See manual for procedure.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. For HeatNet operation, a sensor is required and installation at a minimum of 12" from the primary tee.
Notice: These drawings show suggested piping con guration, valving and are diagrammatic. Check with local codes and ordinances for speci c requirements.
H-16 REV C
14
Loading...
+ 30 hidden pages