RBI 8800 series, 8900 series Installation And Operation Instructions Manual

Page 1
Finned Copper Gas Boilers (HB) &
CI0M-12
82-0252
Water Heaters (HW)
Boiler Manual
Installation and Operation Instructions
is manual is intended only for use by a qualied heating installer/technician. Read and follow this manual, all supplements and related
instructional information provided with the boiler. Install, start and service the boiler only in the sequence and methods given in these instructions. Failure to do so can result in severe personal injury, death or substantial property damage.
Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause contamination
of the burner, resulting in possible severe personal injury, death or substantial property damage. e boiler can only be operated with a dust-free air supply. Follow the instruction manual procedures to duct air to the boiler air intake. If the boiler has been contaminated by operation with contaminated air, follow the instruction manual guidelines to clean, repair or replace the boiler if necessary.
Ax these instructions near to the boiler. Instruct the building owner to retain the instructions for future use by a qualied service
technician, and to follow all guidelines in the User’s Information Manual.
03/16 Copyright 2014 Mestek, Inc.
Page 2
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 2
If the information in this manual is not followed
exactly, a re or explosion may result causing property, personal injury or loss of life.
Do not store or use gasoline or other ammable vapors and liquids in the vicinity of this or any other appliance
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch. Do not use any phone in your building.
• Immediately call your gas supplier from a phone outside of the building. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a quali­ed installer, service agency or the gas supplier.
A ssurez -vous de bien suiv re les instr uctions données
dans cee notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommoge matériel, toute blessure ou la mort
Ne pas entreposer ni utiliser d’essence ou ni d’autres vapeurs ou liquides inammables à proximité de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gas depuis un voisin. Suivez les intructions du fournis­seur.
• Si vous ne purvez rejoindre le fournisseur, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien qualié ou par le fournisseur de gaz.
CONTENTS
Before You Start ................................................page 2
Ratings & Capacities ......................................... page 3
Boiler/Water Heater Location ............................page 3
Combustion Air & Ventilation ............................. page 4
Chimney & Vent Pipe Connections ....................page 8
Common Vent Systems .....................................page 9
General Piping Requirements .........................page 10
Heating System Piping .................................... page 10
Domestic Water Supply Piping ........................ page 15
Gas Supply Piping ........................................... page 19
Electrical Wiring ............................................... page 20
General Operation ........................................... page 20
Operating Instructions .....................................page 21
Checking & Adjustments .................................. page 22
Control Description .......................................... page 24
Maintenance .................................................... page 25
Trouble-Shooting ............................................. page 27
Repair Parts, 8900 ...........................................page 29
Repair Parts, 8800 ...........................................page 38
BEFORE YOU START
This manual covers the application, installation, operation
and maintenance of a Series 8800 and 8900 nned
copper heating boiler/water heater/(pool heater - Canada Only).
To obtain the safe, dependable, efcient operation and
long life for which this heating boiler/water heater was designed, these instructions must be read, understood and followed.
Failure to properly vent this unit can cause excessive
amounts of carbon monoxide resulting in severe personal injury or death!
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRES­SURE OF 160 PSI, 1103 kPa WATER.
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER.
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE PURPOSES.
The Series 8800 and 8900 finned copper heating
boiler/water heaters have been design certied by CSA
for use with natural and propane gas under the latest revision of ANSI-Z21.10.3/CSA 4.3, Gas Water Heaters, ANSI-Z21.13/CSA 4.9, Gas-Fired Low Pressure Steam and Hot Water Boilers ANSI-Z21.56/CSA 4.7 Gas Fired Pool Heaters (Canada Only) and CAN1-3.1, Industrial and Commercial Gas Fired Packaged Boilers. Each unit has been constructed and hydrostatically tested for a maximum working pressure of 160 psi, 1103 kPa in accordance with Section IV of the A.S.M.E. Boiler and Pressure Vessel Code.
Page 3
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 3
All aspects of the boiler/water heater installation must conform to the requirements of the authority having jurisdiction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the requirements of CAN/CGA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
If installed in the Commonwealth of Massachusetts, you MUST FOLLOW the additional instructions contained in RBI's instruction sheet MACODE-3. If you do not have a copy, call your RBI distributor or contact the RBI Customer Service Department.
The owner should maintain a record of all service work performed with the date and a description of the work done. Include the name of the service organization for future reference.
Direct all questions to your RBI distributor or contact the RBI Customer Service Department, 260 North Elm Street,
Westeld, MA 01085 for U.S. or 7555 Tranmere Drive,
Mississauga ONT L5S 1L4 for Canada. Always include the model and serial numbers from the rating plate of the boiler/water heater in question.
RATINGS & CAPACITIES
Before undertaking the installation of the Series 8800 and 8900 boiler/water heater check the rating plate to ensure that the unit has been sized properly for the job. The “Net Ratings” specify the equivalent amount of direct copper radiation that the unit can supply under normal conditions. Also ensure that the unit has been set up for the type of gas available at the installation site. Other important considerations are the availability of an adequate electrical supply, fresh air for combustion and a suitable chimney or vent system.
BOILER/WATER HEATER LOCATION
1. Locate the boiler/water heater in an area that provides good access to the unit. Servicing may require the removal of jacket panels. minimum clearances between adjacent construction and the boiler/water heater as listed in Table 1 or 1A.
NOTE: Service clearances are not mandatory, but are recommended to ensure ease of service should it be required.
Table 1 (8800) Clearance to Service Combustibles Clearance in mm in mm
Top 24 610 18 457 Back 24 610 18 457 Left Side 24 610 24 610 Right Side 24 610 24 610 Front 48 1220 48 1220 Flue 6 152 6 152
Table 1A (8900) Clearance to Service Combustibles Clearance in mm in mm
Top 24 610 18 457 Back 18 457 18 457 Left Side 18 457 18 457 Right Side 18 457 18 457 Front 48 1220 36 914 Flue 6 152 6 152
2. An optimum site will be level, central to the piping system, close to a chimney and have adequate fresh air for combustion. Ensure that the boiler/water heater is level from front to back and from side to side. Use metal shims to level the boiler/water heater. Electrical and electronic components must also be protected from exposure to water during operation and maintenance. DO NOT install this boiler/water heater in a location that would subject any of the gas ignition components to direct contact with water or excessive moisture during operation or servicing.
Allow the
Page 4
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 4
3. Ensure that the oor is structurally sound and will
support the weight of the boiler/water heater.
NOTE: Never install a Series 8800 or 8900 boiler/
water heater on a concrete oor that contains wires,
cables, water pipes or hoses. This boiler/water
heater is designed for noncombustible oors only!
Never install this boiler/water heater on combustible materials or carpeting even if a non-combustible
foundation material is placed over them!
4. Locate the boiler/water heater in an area that will prevent water damage to adjacent construction should a leak occur or during routine maintenance.
If such a location doesn’t exist, a suitable drain pan that’s adequately drained must be installed under
the unit. The combustion air to the unit.
5.
DO NOT place this boiler/water heater in a location that would restrict the introduction of combustion air into the unit or subject it to a negative pressure, see “GENERAL VENTING GUIDELINES”.
6. NEVER place this boiler/water heater in a location that would subject it to temperatures at or near freezing.
WARNING: Never store combustible materials,
gasoline or any product containing ammable vapors
or liquids in the vicinity of the boiler/water heater. Failure to comply with this warning can result in an
explosion or re causing extensive property damage, severe personal injury or death!
pan must not restrict the flow of
COMBUSTION AIR & VENTILATION
WARNING: This boiler/water heater must be supplied with combustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54 and all applicable local building codes. Canadian installations must comply with CAN/ CGA B149.1 or .2 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. Failure to provide adequate combustion air for this boiler/water heater can result in excessive levels of carbon monoxide which can result in severe personal injury or
death!
To operate properly and safely this boiler/water heater requires a continuous supply of air for combustion. NEVER store objects on or around the boiler/water heater!
CAUTION: Combustion air contaminated with
uorocarbons or other halogenated compounds
such as cleaning solvents and refrigerants will result in the formation of acids in the combustion chamber. These acids will cause premature failure
of the boiler/water heater voiding the warranty!
CAUTION: If the boiler/water heater is operated while the building is under construction it MUST be protected from wood, concrete, sheet rock and other types of dust. Failure to properly protect the unit from construction dust will damage the unit
voiding the warranty!
All Air From Inside The Building
If the boiler/water heater is to be located in a conned
space minimum clearances listed in Table 1 or 1A must be maintained between the boiler/water heater and any
combustible construction. When installed in a conned
space, Figures 1, 2, 3, 4 and 5, two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have
sufcient volume to meet the criteria for an unconned
space. The total air requirements of all gas utilization equipment, fireplaces, wood stoves or any type of exhaust fan must be considered when making this determination. Each opening must have a minimum free area of 1 in2/1000 Btu/hr, 2200 mm2/kW based on the total input rating of ALL gas utilization equipment in the conned area. Each opening must be no less than
100 in2, 64,516 mm2 in size. The upper opening must
be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure. The bottom
opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bottom of the enclosure.
All Air From Outside The Building
When installed in a conned space two permanent
openings communicating directly with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure. The bottom opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bottom of the enclosure.
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in2/4000 Btu/hr, 550 mm2/kW of the total input rating of all of the equipment in the enclosure.
Page 5
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 5
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in2/2000 Btu/hr, 1100 mm2/kW of the total input rating of all of the equipment in the enclosure. When ducts are used, they must have the same cross­sectional area as the free area of the opening to which they connect.
Canadian installations must comply with CSA B149.1 when air supply is provided by natural air ow from the outdoors for natural draft, partial fan-assisted, fan­assisted, or power draft-assisted burners, there shall be a permanent air supply opening(s) having a cross­sectional area of not less than 1 in2 per 7,000 Btuh (310 mm2 per kW) up to and including 1 million Btuh, plus 1 in2 per 14,000 Btuh (155 mm2 per kW) in excess of 1 million Btuh.
When calculating the free area necessary to meet the make-up air requirements of the enclosure, consideration must be given to the blockage effects of louvers, grills and screens. Screens must have a minimum mesh size of 1/4 in, 6.4 mm. If the free area through a louver or grill is not known, ducts should be sized per Table 2.
Table 2 - Make-up Air Louver Sizing
Required Cross Sectional Area
Input 1/4 in 6.4 mm (MBH) Wire Screen Metal Louvers Wooden Louvers in2 cm
75% Free Area 25% Free Area
2
in
2
cm
2
in
2
cm
2
420 105 677 140 903 420 2710 530 133 858 177 1142 530 3419 630 158 1019 210 1355 630 4064 735 184 1187 245 1581 735 4742 840 210 1355 280 1806 840 5419 950 238 1535 317 2032 950 6129 1050 263 1697 350 2258 1050 6774 1160 290 1871 387 2497 1160 7484 1260 315 2032 420 2710 1260 8129 1370 343 2213 457 2948 1370 8839 1470 368 2374 490 3161 1470 9484 1580 395 2548 527 3400 1580 10,194 1685 421 2716 562 3626 1685 10,871 1790 448 2890 597 3852 1790 11,548 1900 475 3065 633 4084 1900 12,258 2000 500 3226 667 4303 2000 12,903 2400 600 3871 800 5161 2400 15,483 2800 700 4516 933 6019 2800 18,064 3200 800 5161 1067 6884 3200 20,645 3600 900 5806 1200 7742 3600 23,226 4000 1000 6452 1333 8600 4000 25,806
Figure 1 - Vertical Venting Using A Metal Chimney And Inside Air (8900/8800 Series)
2 FT .6 m
10 FT 3.4 m
3 FT 1 m
3 FT 1 m
5 FT 1.52 m
RIOM-40
Page 6
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 6
Figure 2 - Vertical Venting Using A Masonary Chimney And Inside Air (8900/8800 Series)
10 FT 3.1 m
3 FT 1 m
3 FT 1 m
5 FT 1.52 m
Figure 3 - Dual Flue Outlets And Inside Air (8900/8800 Series)
2 FT .6 m
10 FT 3.4 m
3 FT 1 m
10 FT 3.4 m
5 FT 1.5 m
RIOM-41
RIOM-42
Page 7
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 7
Figure 4 - Common Vents and Inside Air (8900/8800 Series)
10FT 3.1m
3FT 1m
5FT 1.52 m
3FT 1m
Figure 5 - Common Vents and Inside Air (8800/8900 Series) Dual Flue
10 FT
3.1 m
3 FT
1 m
RIOM-43
3 FT
1 m
5 FT
1.52 m
Figure 6 - Horizontal Venting And Inside Air (8900/8800 Series)
BUILDING OVERHANG
4FT 1.2 M MAX.
PITCH PIPE DOWN TOWARDS TERMINAL CAP 1/4IN. PERFOOT 20MM/M OF RUN TO
3FT .9 m
1.5FT 0.5m MINIMUM DISTANCE FROM
EXHAUST TO MAXIMUM SNOW LINE.
ALLOW FOR CONDENSATE DRAINAGE
3FT 1 m
5FT 1.52 m
RIOM-44
RIOM-45
Page 8
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 8
CHIMNEY & VENT PIPE CONNECTIONS
WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision or applicable provisions of the local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can
result in severe personal injury or death!
Chimney Inspection & Sizing
A thorough inspection of the masonry chimney must be performed to ensure that the chimney is clean, properly constructed, lined and sized. Exterior masonry chimneys should not be used unless properly lined to prevent condensation and draft problems. Table 3 and 4 lists
the equivalent breeching and ue sizes required for the
boiler/water heater. Uninsulated single-wall vent pipe shall not be used outdoors for regions where the design temperature is below 32°F, 0°C.
When more than one appliance is connected to the
same chimney ue, the ue must be large enough to
safely vent the combined output of all the appliances.
WARNING: If an appliance using any type of a mechanical draft system operating under positive pressure is connected to a chimney
ue, never connect any other appliances to this ue. Doing so can result in the accumulation of
carbon monoxide which can cause severe
personal injury or death!
Vent Connections
Always use a type B or single wall galvanized metal vent
pipe the same diameter as the draft diverter ue collar.
Use the shortest, straightest vent system possible for the installation. If horizontal runs exceed 6 ft, 1.8 m they must be supported at 6 ft, 1.8 m intervals with overhead hangers. The vent system should be sloped up toward the chimney at a minimum rate of 1/4 in/ft, 20 mm/m
and terminate ush with the inside of the chimney ue.
Fasten each connection with at least 3 corrosion resistant sheet metal screws.
Table 3 - Equivalent Breeching & Chimney Size
Model Size Model Size Size in mm Size in mm 420 10 254 1580 18 457 530 10 254 1685 18 457 630 12 305 1790 20 508 735 14 356 1900 20 508 840 14 356 2000 22 559 950 14 356 2400 24 610 1050 16 406 2800 26 660 1160 16 406 3200 28 711 1260 16 406 3600 30 762 1370 18 457 4000 30 762 1470 18 457
Note: These sizes are based on a 20 ft, 6.1m chimney height.
Table 4 - Equivalent Breeching & Chimney Size Dual Flue
Model Size Model Size Size in mm Size in mm 840 10 254 1790 16 406 950 10 254 1900 16 406 1050 12 305 2000 14 356 1160 12 305 2400 16 406 1260 12 305 2800 18 457 1370 14 355 3200 20 508 1470 14 355 3600 22 559 1580 14 355 4000 22 559 1685 14 355
Note: Minimum vertical rise off top dual ue units: 3 ft, 1 m (sizes 840-3200), 5 ft, 1.5 m (sizes 3600-4000).
Always provide a minimum clearance of 6 in, 152 mm between type C vent pipe and any combustible materials. Type B1 vent may be used, clearance between it and any combustible material must be as listed.
To determine the appropriate power venter for the boiler/ water heater, see Table 5, Power Venter Sizes. Follow
the power venter manufacturer’s installation instructions.
Table 5 - Power Venter Sizes 8900 Power Venter Max. Pipe Length Model Size FT m
420-530 HS-2 100 31 630 HS-3 100 31 735-1160 HS-4 100 31 1260-1900 HS-5 100 31 Models 2000-4000 - Consult Tjernlund
WARNING: Never modify or alter any part of the
boiler’s draft diverter. This includes the removal or alteration of any bafes. Never install a vent
pipe of a diameter different than that of the
boiler draft hood ue collar. Failure to comply
with this warning can result in severe personal injury or death.
WARNING: Failure to maintain minimum clearances between vent connectors and any
combustible material can result in a re causing
extensive property damage, severe personal
injury or death!
Page 9
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 9
COMMON VENT SYSTEMS
If an existing boiler/water heater is removed from a common venting system, the common venting system may then be too large for the proper venting of the remaining appliances connected to it. At the time of removal of an existing boiler/water heater, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Au moment du retrait d’une chaudière existante, les
mesures suivantes doivent être prises pour chaque
appareil toujours raccordé au système d’évacuation commun et qui fonctionne alors que d’autres appareils toujours raccordés au système d’évacuation ne fonction­nent pas: système d’évacuation
a) Seal any unused openings in the common venting
system.
Sceller toutes les ouvertures non utilisées du sys-
tème d’évacuation.
b) Visually inspect the venting system for proper size
and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other
deciencies which could cause an unsafe condition.
Inspecter de façon visuelle le système d’évacu-ation
pour déterminer la grosser et l’inclinaison horizontale qui conviennent et s’assurer que le système est exempt d’obstruction, d’étranglement
de fruite, de corrosion et autres défaillances qui pourraient présenter des risques.
c) Insofar as is practical, close all building doors and
windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhaust, so they will operate at maximum speed. Do not operate a summer exhaust fan for a
boiler installation. Close replace dampers.
Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l’espace où les appareils toujours raccordés du système d’évacuation sont installés et
les autres espaces du bâtiment. Mettre en marche les sécheuses, tous les appareils non raccordés au
système d’évacuation commun et tous les ventilateurs d’extraction comme les hottes de cuisinère et les ventilateurs des salles de bain. S’assurer que ces ventilateurs fonctionnent à la
vitesse maximale. Ne pas faire fonctionner les
ventilateurs d’été. Fermer les registres des
cheminées.
d) Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.
Mettre l’appareil inspecté en marche. Suivre les
instructions d’allumage. Régler le thermostat de façon que l’appareil fonctionne de façon continue.
e) Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the ame
of a match or candle, or smoke from a cigarette, cigar or pipe.
Faire fonctionner le brûleur principal pendant 5 min
ensuite, déterminer si le coupe-tirage déborde à l'ouverture de décharge. Utiliser la amme d'une
allunette ou d'une chandelle ou la fumée d'une cigarette, d'un cigare ou d'une pipe.
f) After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
Une fois qu’il a été d éterminé, selon la métode
indiquée ci-dessus, que chaque appareil raccordé
au système d’évacuation est mis à l’air libre de façor
adéquate. Remettre les portes et les fenêtres, les ventilateurs, les registres de cheminées et les
appareils au gaz à leur position originale.
g) Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and or CAN/CGA-B149 Installation Codes.
Tout mauvais fonctionnement du systéme d'évacu-
tion commun devrait étré corrigé de façor que l'installation soit conforme au National Fue Gas Code, ANSI Z223.1/NFPA 54 et (ou) aux codes d'installation CSA-B149. Si la grosseur d'une
section du système d'évacuation doit étré modiée, le système devrait étré modié pour respecter les
valeurs minimales des tableaux pertinents de l'appendice F du National Fuel Gas Code, ANSI Z223.1/NFPA 54 et (ou) des codes d'installation CSA-B149.
Page 10
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 10
GENERAL PIPING REQUIREMENTS
CAUTION: Improper piping of this boiler/water heater
will void the manufacturer’s warranty and can cause
boiler failure resulting in flooding and extensive
property damage! Excessive water hardness causing
lime build-up in the copper heat exchanger tubes is
NOT covered under the manufacturer’s warranty.
Excessive pitting and erosion of the internal surface of the copper heat exchanger tubes is NOT covered
under the manufacturer’s warranty if the result of high water ow rates, see Table 7. Return water
temperatures below 110°F, 43°C will result in heat exchanger damage from excessive
condensation voiding the manufacturer’s warranty,
see Primary/Secondary Piping Figure 8.
NOTE: Shut off valves and unions should be installed at the inlet and outlet connections of the boiler/hot water heater to provide for isolation of the unit should servicing be necessary.
Relief Valve
Pipe the discharge of the pressure relief valve to prevent scalding in the event of a discharge, see Figure 7. The discharge piping must be sized the same as the pressure relief valve outlet and installed to allow complete drainage of both the relief valve and the discharge piping.
Figure 7
1" (25mm) CLEARANCE MUST BE MAINTAINED BETWEEN HOT WATER PIPING AND COMBUSTIBLE CONSTRUCTION.
CAUTION: Failure to properly install the ow switch
may result in damage to the boiler/water heater heat
exchanger voiding the warranty!
HEATING SYSTEM PIPING
General Piping Requirements
All heating system piping must be installed by a qualied
technician in accordance with the latest revision of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV, and ANSI/ASME CSD-1, Standard for Controls and Safety Devices for Automatically Fired Boilers. All applicable local codes and ordinances must also be followed. A minimum clearance of 1 in, 25 mm must be maintained between heating system pipes and all combustible construction. All heating system piping must be supported by suitable hangers not the boiler.
The thermal expansion of the system must be considered when supporting the system. A minimum system pressure of 12 psig, 82.7 kPa must be maintained.
Heating Boiler Piping Connections
The supply and return connections should be sized to suit the system, see Table 6.
Table 6 - Supply & Return Pipe Sizing
Model Supply Return 8900 21/2" NPT 21/2" NPT 8800 3" Victaulic 3" Victaulic *Models 420-950 may have 21/2" x 2" reducing tting installed.
DISCHARGE PIPE SIZE TO EQUAL VALVE OUTLET.
OUTLET
INLET
RIOM-46
DO NOT RESTRICT FLOW.
DISCHARGE SO AS TO AVOID EXPOSURE OF PERSONS TO HOT LIQUID OR VAPOR AND ALLOW COMPLETE DRAINAGE 0F RELIEF VALVE AND PIPING
.
WARNING: Never install any type of valve between the boiler/water heater and the relief valve or an explosion causing extensive property damage, severe personal injury or
death may occur!
Flow Switch
The ow switch supplied with the boiler/water heater
must be wired to the terminal strip in the junction box
to prevent the boiler from ring unless there’s adequate water ow through the unit. The ow switch must be
installed in the supply piping adjacent to the boiler outlet connection.
Pump Requirements
This low mass boiler requires a continuous minimum
water ow for proper operation. The system pump must
be sized to overcome the head loss of the boiler and the heating system in order to achieve the required temperature rise. Table 7 provides the heat exchanger pressure drop and temperature rise figures. The temperature rise across the boiler must never exceed 35°F, 19.4°C. The pump delay turns the pump on each
time the burners re and runs the pump for up to 10 minutes after the call for heat is satised.
CAUTION: A temperature rise outside of the range
listed in Table 7 indicates that the ow rate through
the heat exchanger is incorrect which will damage
the heat exchanger voiding the warranty!
The maximum allowable ow rate through an 8900
boiler with copper heat exchanger is 92 GPM,
5.8 L/s.
The maximum allowable ow rate through an 8800
boiler with copper heat exchanger is 185 GPM,
11.7 L/s.
Page 11
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 11
Table 7 - Temperature Rise Table — 2 Pass Headers
20°F
Press
Flow
Model
420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900 2000 2400 2800 3200 3600 4000
*Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupro-nickel heat exchanger should be considered.
GPM Ft
34.0
42.9
51.0
59.5
68.0
77.0
85.1
94.0*
164.0
196.8*
Rate
— — — — — — —
— — — —
Drop
0.4
0.7
1.1
1.6
2.4
3.3
4.4
5.8 — — — — — — —
4.1
6.8 — — — —
11.1°C
Press
Flow
Drop
Rate
L/s kPa
1.1
2.1
2.0
2.7
3.2
3.2
4.8
3.8
7.0
4.3
9.8
4.9
12.9
5.4
17.0
5.9
12.0
10.3
20.0
12.4
25°F
Flow Rate
GPM Ft
34.3
40.8
47.6
54.4
61.6
68.0
75.2
81.6
88.8
95.3* — — — —
131.2
157.4
183.7 — — —
Press
Drop
0.4
0.7
1.1
1.6
2.2
2.9
3.8
4.8
6.1
7.4 — — — —
2.7
4.5
6.9 — — —
13.9°C
Press
Flow Rate
Drop
L/s kPa
1.3
2.2
2.1
2.6
3.2
3.0
4.6
3.4
6.5
3.9
8.6
4.3
11.2
4.7
14.2
5.2
17.9
5.6
21.8
6.0
8.0
8.3
13.2
9.9
20.3
11.6
30°F
Flow Rate
GPM Ft
— —
34.0
39.7
45.4
51.3
56.7
62.6
68.0
74.0
79.4
85.3
91.0
96.7* —
109.3
131.2
153.1
174.9
196.8* —
Press
Drop
— —
0.5
0.8
1.1
1.6
2.1
2.7
3.4
4.3
5.3
6.5
7.7
9.2 —
1.9
3.2
4.9
7.2
10.0 —
16.7°C
Press
Flow
Drop
Rate
L/s kPa
2.1
1.5
2.5
2.3
2.9
3.3
3.2
4.6
3.6
6.1
4.0
8.0
4.3
10.1
4.7
12.8
5.0
15.6
5.4
19.0
5.7
22.8
6.1
27.0
6.9
5.7
8.3
9.4
9.7
14.5
11.0
21.1
12.4
29.3
35°F
Flow Rate
GPM Ft
— — —
34.0
38.9
44.0
48.6
53.7
58.3
63.4
68.0
73.1
78.0
82.9
87.9
93.7
112.5
131.2
149.9
168.7
187.4*
Press
Drop
— — —
0.6
0.8
1.2
1.6
2.0
2.6
3.3
4.0
4.8
5.8
6.9
8.1
1.4
2.4
3.7
5.4
7.5
10.1
19.4°C
Press
Flow
Drop
Rate
L/s kPa
2.1
1.7
2.5
2.5
2.8
3.5
3.1
4.6
3.4
6.0
3.7
7.6
4.0
9.6
4.3
11.7
4.6
14.3
4.9
17.1
5.2
20.3
5.5
23.9
5.9
4.3
7.1
7.1
8.3
10.9
9.5
15.8
10.6
22.0
11.8
29.6
Page 12
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 12
Low Water Cutoff
If a boiler is installed above any radiation elements it
must be tted with a low water cutoff device.
Refer to the wiring diagram supplied with the boiler/ water heater for proper wiring connections.
Expansion Tank
An expansion tank or other means to control thermal expansion must be installed in the heating system. An expansion tank must be installed close to the boiler on the suction side of the pump.
Primary/Secondary Piping
Boilers connected to heating systems using zone valves, zone pumps, or systems that have excessive ow rates or return water temperatures less than 110°F, 43°C must be isolated from these systems to protect the boiler.
Variable Water Flows
Figure 8 shows a typical primary/secondary piping system. A dedicated pump is used to maintain a
constant water ow through the boiler. This secondary
pump is sized to overcome the head loss of the boiler
and secondary piping system while supplying the ow
rate required to maintain the desired temperature rise across the boiler. The primary pump is sized to provide
the required ow to the heating system. The secondary
piping connections to the primary system piping must not be more than 6 pipe diameters apart to ensure zero pressure drop in the primary system, see Figure 8.
Low Return Water Temperatures
To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary/secondary piping system with a bypass and bypass valve must be installed, see Figure 9 and 10. The bypass and bypass valve must be sized the same as the secondary piping. A balancing valve must also be installed in the supply side of the secondary piping downstream of the bypass. The balancing valve should be adjusted to divert some of the heated discharge water into the return water until the required inlet water temperature is achieved. The primary and secondary pumps should be sized to
provide the required ow through each system. The
secondary piping connections to the primary system piping must not be more than 6 pipe diameters apart to ensure zero pressure drop in the primary system, see Figure 9 and 10.
Multiple Boiler Systems
Systems using multiple boilers can also be installed using a primary/secondary manifold system, Figure 11.
Piping For Use With Cooling Units
The boiler, when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler. Appropriate valves must be used to prevent the chilled water from entering the boiler.
When a boiler is connected to a heating coil that may be exposed to refrigerated air from an air handling
device, the piping system must be equipped with ow-
control valves or some other automatic means of preventing gravity circulation of the boiler water during the cooling cycle.
Page 13
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 13
Figure 8 - Typical Primary/Secondary Piping System
(See Notes)
NOTES:
1. Boiler circuit piping must be sized large enough to handle maximum ow through unit.
2. Boiler pump sized to boiler design ow requirements.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
Notice: These drawings show suggested piping conguration and valving. Check with local codes and ordinances for specic requirements.
H-1 Rev 4
Pump
Gate Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve
Ball Valve
Motorized Valve
Solenoid
Operated Valve
Self-Operated
Valv e
Figure 9 - Low Temperature Piping
(See Notes and Adjustment Procedures)
H-3 Rev 6
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
Thermometer
Aquastat Union
Pressure Switch
Gas Pressure
Regulator
Automatic
Air Vent
Backflow­Prevention
Device
3-Way Valve
NOTES:
1. Boiler circuit piping must be sized large enough to
handle maximum ow through unit.
2. Boiler pump sized to boiler design ow requirements.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
Notice: These drawings show suggested piping
conguration and valving. Check with local codes and ordinances for specic
requirements.
Adjustment Procedure
To Maintain Inlet Temperature
Above Dew Point
T1-Temp-Min=110°F For Atmospheric
T1-Temp-Min=125°F Sealed Combusion
1. Turn heater on and open valves A & B.
2. After steady-state operation, if T1 is less than Temp-Min slowly close valve B until T1 climbs to desired operating temperature above Temp-Min.
3. If T1 is greater than desired operating temperature, slowly close valve A to adjust to lower desired temperature above Temp-Min.
4. Check after system operating temperature has stabilized. Make
nal adjustments.
5. Follow same adjustment procedure for sealed combustion.
Expansion
Tank
Page 14
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 14
Tank
Figure 10 - Low Temperature Piping with Thermostatic Valve
(See notes and adjustment procedures)
Pump
Gate Valve
Globe Valve
H-18 Rev 3
Figure 11 - Multiple Boiler Piping
(See Notes)
NOTES:
1. For pump selection consult factory.
2. Boiler pump sized to boiler and thermostatic 3-way valve design
ow requirements.
3. Boiler circuit piping must be sized large enough to handle maximum
ow through unit.
4. All boilers furnished with factory mounted outlet water temperature gauge.
5. Boiler pump purging required. Use terminals supplied.
6. Valve is precalibrated for 140°F return temperature.
Notice: These drawings show
suggested piping conguration and
valving. Check with local codes and
ordinances for specic requirements.
Angle Valve
Bufferfly Valve
Balance Valve
Ball Valve
Motorized Valve
Solenoid
Operated Valve
Self-Operated
Valv e
Pressure
Reducing Valve
Check Valve
Pressure
Relief Valve
Flow Switch
Thermometer
NOTES:
1. Boiler circuit piping must be large enough to handle
maximum ow through unit.
2. Boiler pump sized to boiler design ow requirements.
3. All boilers furnished with factory mounted outlet water temperature gauge.
4. Boiler pump purging required. Use terminals supplied.
5. Secondary loop pipe diameter must be sized large enough to
handle maximum ow through all units.
Notice: These drawings show suggested piping conguration and valving. Check with local codes and ordinances for specic requirements.
H-15 Rev 5
Aquastat Union
Pressure Switch
Gas Pressure
Regulator
Automatic
Air Vent
Backflow­Prevention
Device
3-Way Valve
Expansion
Page 15
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 15
DOMESTIC WATER SUPPLY PIPING
CAUTION: Proper controls must be used to prevent water supplied for domestic use from exceeding 130°F, 54 °C or a scald injury will occur! When higher water temperatures are required for appliances such as a dishwasher, a mixing valve or some other tempering means must be installed. Households with small children may require water temperatures less than 120°F, 49 °C. Local codes
must be complied with!
General Piping Requirements
Ensure that the water heater is equipped with bronze headers. Piping and components connected to the water heater must be suitable for use with potable water. The water heater must not be connected to any heating system piping or components previously used with a non-potable water heating appliance. Toxic chemicals, such as those used for boiler treatment, are not to be introduced into any potable water used for space heating. If a hot water storage tank is used in the system it must be equipped with a temperature and pressure relief valve that complies with ANSI Z21.22 or CAN-4.4 and CAN-4.6.
NOTE: The storage tank must be located as close to the water heater as possible to prevent excessive
head loss which will reduce ow.
Water Chemistry
The required temperature rise across the water heater is based on water having a hardness between 8 and 18 grains per gallon with a level of dissolved solids not exceeding 350 ppm. Water having a hardness less than 8 grains can cause excessive corrosion of the heat exchanger. Water that has a hardness greater than 18 grains per gallon and/or a level of dissolved solids exceeding 350 ppm will require a recalculation of the pump size and temperature rise.
A cupro-nickel heat exchanger may also be required. The manufacturer should be consulted when these water conditions are encountered. See Table 8.
CAUTION: through a water heater with copper heat exchanger on an 8900 is 92 GPM, 5.8 L/s. The cupro-nickel heat exchanger allows for 100 GPM, 6.3 L/s.
The maximum allowable flow rate through a water heater with copper heat exchanger on an 8800 is 185 GPM, 11.7 L/s. The cupro-nickel heat exchanger allows for 200 GPM, 12.6 L/s. See Table 7.
RBI water heaters are designed to run scale free. Due to the extreme variables of water conditions world wide it is necessary to consider pH values and water hardness in relationship to scaling. It is crucial to consider these two variables when making heat exchanger and pump selections. If local water conditions are extreme, follow the guidelines in the Heat Exchanger Selection Table (Table 8) and the Pumping Performance Table (Table 9). Scale free operation can be achieved by using water with a hardness between 8 and 18 and by maintaining the pH between 5 and 9. Follow the conditions listed under NORMAL in the table. In some areas of the country additional precautions must be observed due to unusual characteristics of the local water supply. Call the nearest RBI representative for details.
To properly size the pump a grain hardness and pH test must be taken at the installation site before the order is placed. Proper pump sizing will improve heater performance and help ensure heater longevity.
Expansion Tank
An expansion tank or other means to control thermal expansion must be installed in the water heating system
if back ow prevention devices are installed.
The maximum allowable flow rate
Page 16
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 16
Pump Requirements
This low-mass water heater requires a continuous mini­mum water flow for proper operation. The factory recommended circulating pump has been sized to overcome the head loss of the water heater plus a 30 foot piping loop under normal water conditions. Table 9 provides the heat exchanger pressure drop chart and temperature rise table. The temperature rise across
the water heater must never exceed 35°F, 19.4°C.
Cold Water Supply
The cold water supply must be piped to the water
heater’s outlet piping between the water heater and the
hot water storage tank. This will prevent untempered water from entering the water heater, see the temperature rise control section below. A typical water heating system is shown in Figure 12 and 13.
Temperature Rise Control
Water returned to the water heater inlet must not be less than 110°F, 43°C or excessive condensation of the products of combustion will damage the water heater voiding the warranty. The method outlined below can be employed to prevent this condition from occurring. A balancing valve should be installed on the outlet side
of the water heater for purposes of adjusting the ow
rate through the heat exchanger. Thermometers are
installed on both the inlet and outlet of the water heater for determining the temperature rise through the unit.
The proper velocity through the water heater must
be maintained in accordance with Table 9 for efcient
operation and long life. If the temperature rise through the water heater is lower than recommended the water velocity is too high. Premature erosion of the heat exchanger will occur. Conversely, if the temperature rise
is higher than recommended in Table 9 the ow rate is
too low. Scaling and softening of the heat exchanger will occur.
Thermostatic Mixing Valve
- Water Above 140°F, 60°C
Water can be stored at temperatures above 140°F, 60°C provided that a thermo-statically controlled mixing valve is used to temper the hot water to an acceptable
temperature before it’s supplied for domestic use.
The mixing valve MUST be set to prevent a scald injury from occurring, see the caution against scalding.
Storage of water for domestic use above 140°F, 60°C will provide an increased quantity of tempered water and help prevent growth of water born bacteria.
Table 8 - 8800 and 8900 Heat Exchanger Selection Graph
Page 17
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 17
Table 9 - 8900 Pumping Performance Requirement Table
Table 10 - 8800 Pumping Performance Requirement Table
Page 18
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 18
Pressure Switch
e
Temperatu
Figure 12 - Typical Water Heating Piping (HW Models Only)
(See Notes)
Pump
3
8
2
1
4
7
Not all RBI stock storage tanks
incorporate this tapping: See Note 1.
Attention:
Figure 13 - Multiple Water Heating Piping (HW Models Only)
(See Notes)
4
3
6
8
D-1 Rev 6
Valve
Globe Valve
Angle Valve
Bufferfly Valve
Balance Valve
Ball Valve
Motorized Valv
Solenoid
Operated Valve
Self-Operated
Valve
Pressure
Reducing Valve
Check Valve
Pressure
4
Relief Valve
1
7
2
NOTES:
1. Optional cold water make up and recirculation line location.
2. When using intermittent pump and pump delay, locate remote aquastat well in lower 1/3 of tank. Install aquastat with heat sensing compound.
3. Thermal expansion tank may be required, check local codes.
4. When using optional factory mounted pump, max pipe length 30’ total, 6-90° elbows, full pipe size.
5. CAUTION: TEST WATER HARDNESS AND pH AT JOB SITE.
The pH and water hardness must be measured before selecting heat exchanger and pump. Consult the Heat Exchanger Graph and
Pumping Performance Table before making selection.
6. Common piping must be sized for maximum combined heater ow.
7. Hot water tanks should be equipped with a combination temperature & pressure relief valve.
8. MA Code requires an 1/8” hole in check valve to compensate for thermal expansion.
Notice: These drawings show suggested piping conguration and valving.
Check with local codes and ordinances for specic requirements.
Flow Switch
Thermometer
7
2
D-4 Rev 6
Attention:
Not all RBI stock storage tanks
incorporate this tapping: See Note 1.
Aquastat Union
Gas Pressure
Regulator
Automatic
Air Vent
re &
Pressure
Relief Valve
Vacuum
Relief Valve
Drain Valve
(Typ.)
Page 19
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 19
GAS SUPPLY PIPING
WARNING: Check the boiler/water heater rating plate to make sure that the boiler/water heater
is for the type of gas that will be used. If it isn’t,
do not connect the boiler/water heater to the gas supply. Gas supply piping must be in accordance with the National Fuel Code, ANSI Z223.1-latest revision or applicable provisions of the local building codes. Canadian installations must comply with CAN/CGA B149.1 or .2 Installation Code. Failure to comply with this warning can result in extensive property
damage, severe personal injury or death!
The Series 8800 and 8900 come from the factory ready to be piped to the gas supply. If for any reason the boiler/water heater is not for the type of gas available at the installation site, call the nearest RBI representative to resolve the problem.
NOTE: A minimum gas supply presssure of 6 in, 152 mm W.C. natural or 11 in, 279 mm W.C. propane
and maximum 14 in, 356 mm W.C. natural or propane, must be available at the safety shutoff valve inlet with the unit(s) operating.
Table 11 - Gas Pipe Capacity
A ground joint union should be installed between the boiler gas controls and the supply piping. Each of these items are needed to ensure long life and ease of servicing. Always use a pipe sealant that is suitable for use with LP gas.
Table 12 - Equivalent Pipe Length Chart
Nominal Iron Pipe Size, (in)
1" 1 1/4" 1 1/2"
2" 2 1/2"
3"
4"
Notes: 1. For ow through branch.
2. For ow at full open.
Type of pipe tting
90°
Elbow
Tee
Equivalent of pipe length (ft)
5.2
2.6
6.9
3.5
8.0
4.0
10.3
5.2
12.3
6.2
15.3
7.7
15.3
7.7
Gate
Valve
0.6
0.8
0.9
1.2
1.4
1.8
1.8
2
1
Gas
Cock
1.5
1.9
2.3
3.0
3.7
4.5
4.5
2
CAUTION: Always use a square jawed wrench on the gas valve body when making gas connections to it. Never over-tighten the piping entering the gas
valve body or gas valve failure may result!
Figure 14 - Gas Supply Piping
Table 11 should be used to ensure that the gas supply piping is sized properly. If more than one appliance is supplied by the same supply pipe, the piping must be sized based on the maximum possible demand. Do not
neglect the pressure drop due to pipe ttings. Table 11
should be used in conjunction with Table 12 to ensure that the gas supply piping has the capacity to meet the demand.
Figure 14 depicts the proper way to connect the boiler/ water heater to the gas supply piping. The manual shut­off valve MUST be installed in the supply piping. It should be installed 5 ft, 1.5 m above the oor where required by local codes. Provide a sediment trap at the bottom of the vertical section of the gas supply pipe upstream of the gas controls.
Maximum pipe capacity in ft3/hr based on 0.60 specic gravity gas at a pressure of 0.5 psig or less and a 0.3" W.C. pressure drop.
Nominal Iron Pipe Size, (in)
1" 1 1/4" 1 1/2"
2" 2 1/2"
3"
4"
Note: Multiply the gas volume by 0.62 for propane ow capacity in ft3/hr. Multiply the propane ow capacity by 2500 Btu/ft3 to determine the propane Btu/hr
capacity for a given pipe size and length.
10
520 1050 1600 3050 4800 8500 17,500
20
350 730 1100 2100 3300 5900 12,000
Pipe length in feet
30
40
50
Maximum gas volume of pipe, (ft
285
245
215
590
500
440
890
760
670
1650
1450
1270
2700
2300
2000
4700
4100
3600
9700
8300
7400
60
195
400 610 1150 1850 3250 6800
80
3
/hr)
170
350 530 990 1600 2800 5800
100
150 305 460 870 1400 2500 5100
150
120 250 380 710 1130 2000 4100
RIOM-47
When applicable, provisions for vent, bleed and gas relief lines must be made in accordance with the latest revision of ANSI Z223.1/NFPA 54.
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler. All gas connections MUST be leak tested before putting the boiler into operation.
WARNING: Never use an open ame to test for
gas leaks. Always use an approved leak detection method. Failure to comply with this warning can cause extensive property damage,
severe personal injury or death!
Page 20
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 20
Whenever the gas supply piping is pressure tested the boiler/water heater gas controls must be protected. If the test pressure is equal to, or less than 1/2 psig,
3.5 kPa isolate the boiler/water heater by closing it’s
manual shut off valve, see Figure 14. If the test pressure is greater than, or equal to 1/2 psig, 3.5 kPa, disconnect the boiler/water heater and its individual shut-off valve.
ELECTRICAL WIRING
Electrical Power Connections
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation! Verify proper operation after servicing!
ATTENTION. Au moment de l’entretien des commandes, étiquetez tous les ls avant de les
débrancher. Des erreurs de câblage peuvent entraîner un fonctionnement inadéquat et
dangereux. S’assurer que l’appareil fonctionne adéquatement une fois l’entretirn terminé.
The electrical connections to this boiler/water heater must be made in accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI /NFPA-70. Installation should also conform with CSA C22.1 Canadian Electrical Code Part I if installed in Canada.
GENERAL OPERATION
WARNING: Before proceeding read and fully understand the instructions contained in this manual. Do not attempt to operate this boiler/ water heater if it has not been installed in accordance with the guidelines set forth in this manual. Failure to comply with this warning can result in extensive property damage, severe
personal injury or death!
Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the
appliance. Do not interrupt water ow through the boiler/
water heater.
En cas de surchauffe ou si l’alimentation en gaz ne s’arrête pas, fermez manuellement le robinet d’arrêt de l’admission de gaz.
Hydronic Heating Boilers
Open the make-up water valve and slowly ll the boiler
and all of the radiation with water. Ensure that all bleed and drain valves are closed.
Adjust the make-up water pressure regulator so a minimum 12 psig, 82.7kPa system pressure is maintained at the highest point in the system piping. If a make-up water pump is used adjust it to maintain a minimum 12 psig, 82.7 kPa system pressure.
Install a separate 120 volt 15 amp circuit for the boiler/ water heater. A shut-off switch should be located at the boiler/water heater. The boiler/water heater must be grounded in accordance with the authority having jurisdiction, or if none, the latest revision of the National Electrical Code, ANSI/NFPA-70.
Line voltage eld wiring of any controls or other devices
must conform to the temperature limitation of type T wire at 95°F, 35°C above room temperature. Use copper conductors with a minimum size of #14 awg.
Refer to the wiring diagram supplied with the boiler/ water heater for proper wiring connections.
Open the system bleed and drain valves, one at a time, to purge the air trapped in the heating system piping.
With the boiler off, run the system pump for at least 30 minutes and bleed the system piping using the bleed valves. If strainers are used in the system piping, the make-up water valve should be closed and the strainers checked and cleaned.
The system expansion tank should be checked to ensure that the correct water level in the tank is maintained. The tank should be less than half full of water with the system full and adjusted to the correct operating pressure.
Start the boiler as described in the “OPERATING INSTRUCTIONS” section. Run the boiler for at least an hour. The system pump(s) and all radiation units must be operated during this time. Ensure that the make-up water valve is open.
Page 21
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 21
Shut the boiler off and open the bleed valves to purge the air trapped in the heating system piping. Close the make-up water valve and check and clean the strainers and make-up water pressure reducing valve.
Open the make-up water valve and adjust the system pressure if necessary. The system should be checked and bled after three days of operation.
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
POUR VOTRE SÉCURITÉ LISEZ AVANT DE METTRE EN MARCHE
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light the pilot by hand.
Cet appareil est muni d’un dispositif d’allumage qui
allume automatiquement la veilleuse. Ne tentez pas
d’allumer la veilleuse manuellement.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the
oor because some gas is heavier than air and will settle on the oor.
DANGER: Propane gas may not always be detected by smell. Propane gas is heavier than air and can collect in low areas.
Propane gas can ignite or explode if an ignition source is present and result in death, serious
injury and property damage!
FOR YOUR SAFETY
• Have only qualied licensed professionals install,
service and maintain this appliance and your gas system in accordance with all applicable codes.
• Install a nationally listed combustible gas detector(s) in your home.
• If you suspect a leak:
1. Have everyone leave the building immediately.
2. Do not attempt to light any appliance.
3. Do not touch any electrical or electronic switches in the building.
4. Do not use any phone in the building.
5. Call your gas supplier from a phone outside of the building.
6. If you cannot reach your gas supplier call the re
department.
AVANT DE FAIRE FONCTIONNER, reniez tout autour de l’appareil pour déceler une odeur de gaz. Reniez près du plancher, car certains gaz sont plus lourds que l’air et peuvent s’accumuler au niveau du sol.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareil.
• Ne touchez à aucun interrupteur; ne pas vous servir
des téléphones se trouvant dans le bâtiment.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suives les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur, appelez le service de incendies.
C. Do not use this appliance if any part has been under
water. Immediately call a qualied service technician
to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
N’utilisez pas cet appareil s’il a été plongé dans
l’eau, même partiellement. Faites inspecter l’appareil par un tecnicien qualifié et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
CAUTION: To prevent being burned, stand clear of the boiler during ignition and do not touch any hot
metal parts!
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above. If, at
any time, the appliance will not operate properly, follow the instructions “TO TURN OFF GAS TO APPLIANCE.”
2. Set the operating control or thermostat to off or its
lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to light the pilot by hand.
5. Close the manual main and pilot gas shut-off valves.
6. Wait ve (5) minutes to clear out any gas. Then
smell for gas, including near the oor. If you smell
gas, STOP! Follow “B” in the safety information
above. If you don’t smell gas go to next step.
7. Connect a manometer having a minimum capacity of
20 in, 508 mm W.C. to the outlet pressure port of the gas valve. Make sure that the gas supply piping has been purged of air and that all gas joints up to the gas valve have been thoroughly checked for leaks.
8. Open the manual pilot valve.
9. Turn on all electric power to the boiler.
10. Set the operating control or thermostat to the
desired setting.
11. The pilot(s) should automatically light. Do not try to
light the pilot(s) by hand!
12. With the pilot(s) lit, open the main gas shut-off valve.
13. The burners should light
with proper boiler operation.
14. The pilot and manifold pressures should match
those listed in Table 13. To adjust the manifold gas pressure see the instructions in the section.
“CHECKING AND ADJUSTMENTS”
Gas Pressure Adjustment
Page 22
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 22
Required Gas Pressure
Provide gas supply pressure at inlet to boiler gas train as follows: LP Nat
Minimum (in W.C.) 11 6 Maximum (in W.C.) 14 14
Measure pressure when the boiler is ring at full rate.
Low gas pressure could indicate undersized gas line or
insufcient gas supply.
"Static and operating gas pressure required at the gas valve inlet is between 6" W.C. and 14" W.C. for natural gas and 11" W.C. and 14" W.C. for propane. If the gas pressure is above this limit, a lock-up style regulator suitable for dead end service such as an Equimeter or Fisher must be installed to prevent increase (creep) of gas pressure when the units are not operating. This pressure regulator (supplied by others) may be installed at the service entrance to each unit or a "master" regulator sized to handle multiple units may be utilized. Consult local gas utility or regulator
manufacturer for recommendations to meet specic job
site requirements."
Table 13 - Pilot & Manifold Settings
inches W.C. mm W.C. Natural 3.5 (± .2) 89 (± 5) Propane 10 (± .2) 254 (± 5)
Instructions De Mise En Marche
1. ARRÊTEZ! Lisez les instructions de sécurité sur la portion supérieure de cette étiquette.
2. Réglez le thermostat à la température la plus basse.
3. Coupez l’alimentation électrique de l’appareil.
4. Cet appareil est muni d’un dispositif d’allumage qui
allume automatiquement la veilleuse. Ne tentez pas
d’allumer la veilleuse manuellement.
5.
Fermer la vanne manuelle d’arrêt d’alimintation de gaz.
6. Attendre cinq (5) minutes pour laisser échapper tout
le gaz. Reniez tout autour de l’appareil, y compris près du plancher, pour déceler une odeur de gaz. Si
vous sentez une odeur de gaz, ARRÊTEZ! Passez
à l’étape B des instructions de sécurité sur la portion supérieure de cette étiquette. S’il n’y a pas d’odeur de gaz, passez à l’étape suivante.
7.
Ouver la vanne manuelle d’arrêt d’alimintation de gaz.
8. Mettez l’appareil sous tension.
9. Réglez le thermostat à la température désirée.
10. Si l’appareil ne se met pas en marche, suivez les instructions intitulées «Comment couper l’admission de gaz de l’appareil» et appelez un technicien qualié ou le fournisseur de gaz.
To Turn Off Gas To Appliance
1. Set the operating control or thermostat to its lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Close the manual main and pilot gas shut-off valves.
COUPER L’ADMISSION DE GAZ DE L’APAREIL
1. Réglez le thermostat à la température la plus basse.
2. Coupez l’alimentation électrique de l’appareil s’il faut procéder à l’entretien.
3.
Fermer la vanne manuelle d’arrêt d’alimintation de gaz.
CHECKING & ADJUSTMENTS
1. With the burners in operation, close the manual shutoff valve in the gas supply line. As soon as the
main burner ames go out, open the manual shutoff
valve. A normal ignition sequence should take place. If the burners fail to light, the system will make one more ignition attempt. If the burners have not lit after the last ignition try, the gas valve will close and the system will go into lock out on CSD-1 units or continuous retry. DO NOT attempt to reset the system until the ignition system has been inspected and the problem resolved. The pilot and manifold pressures should match those listed in Table 13.
2. With the burners in operation, interrupt the power to the control circuit by lowering the operating control or thermostat. The main burners should go out. Reset the operating control or thermostat, a normal ignition sequence should follow.
3. To test the ignition safety shutoff device, close the manual shutoff valve in the gas supply line. Within
5 seconds of main burner ame extinction, the main
gas valve solenoid should close with an audible noise.
4. A sparking noise should be heard while the ignition module tries to relight the pilot. After 15 seconds the module should lockout and the trial for ignition end. After 5 minutes a second trial for ignition should occur. Open the manual shutoff valve in the gas supply line and reset the ignition control system. A normal ignition sequence should take place.
Page 23
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 23
Pilot Adjustment
The pilot burner ame should envelope 3/8" to 1/2" of the ame sensing probe, Figure 15. To adjust the pilot
the following steps must be taken:
1. Remove the pilot gas pressure regulator cap.
2. Turn the pressure regulator adjustment screw clock-
wise to increase the ame and counterclockwise to
decrease it.
3. Replace the pressure regulator adjustment screw cap.
Figure 15 - Pilot Flame Adjustment
Gas Pressure Adjustment
CAUTION: The maximum inlet gas pressure listed on the rating plate must not be exceeded or damage to the boiler/water heater may occur voiding the
warranty!
The minimum supply pressure listed on the rating plate is for input adjustment.
NATURAL GAS: Optimum results are obtained when the boiler/water heater is operated with the manifold pressure(s) set per Table 13. The manifold pressure should not vary outside this range. The gas valve pressure regulator has been preset at the factory. If adjustment is necessary the following steps must be followed:
1. Attach a 20 in, 508 mm W.C. manometer to the tap on the manifold.
2. Remove the regulator adjustment screw cap from the gas regulator. On systems that do not use a separate gas regulator, remove the adjustment screw cap from the gas valve body on the valve closest to the gas supply piping.
3. Rotate the regulator adjustment screw clockwise to increase the manifold pressure, counterclockwise to decrease it.
4. Replace the regulator adjustment screw cap and manifold pressure tap plug.
PROPANE GAS: Optimum results are obtained when the boiler/water heater is operated with the manifold pressure(s) set per Table 10. If the manifold pressure is off by more than 5% adjust it according to steps 1 through 4 above.
Input Rate, Natural Gas
Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 2000 ft., 610 m. At elevations above 2000 ft, 610 m input ratings should be reduced by 4% for each additional 1000 ft, 305 m.
Check the input rate as follows:
1. Turn off all other gas appliances that use the same gas meter as the boiler/water heater.
2. Call your gas supplier and ask for the heating value of the gas.
3. Start the boiler/water heater and let it run for 15 minutes.
4. Using the gas meter and a stopwatch, clock the time that it takes to burn 10 ft3, 0.28m3 of gas and divide this time by 10.
5. Insert the heating value and the time, in seconds, into the formula below.
6. Input = (heating value, Btu/hr)(3600)/(time, seconds)
7. If the computed rate deviates by more than 5% from the rated input value of the unit adjust the manifold pressure accordingly. DO NOT adjust the manifold pressure by more than 5%. If a proper rate cannot be maintained without adjusting the manifold pressure beyond the 5% limit, the main burner
orices must be replaced. If the input rate is too low, go to the next larger size of main burner orices. If
the input rate is too high, go to the next smaller size.
CAUTION: Never increase the input to the boiler/ water heater above that for which it is rated. Doing
so can cause premature failure of the unit!
CAUTION: Never force the regulator adjustment screw beyond the stop limits or damage to the
regulator will occur!
Page 24
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 24
CONTROL DESCRIPTION
Boiler Thermostat
If a thermostat is to be used to control the boiler always follow the instructions included with the thermostat.
Proper location of the thermostat will ensure efcient
trouble-free operation of the boiler. Mount the thermostat
to an inside wall at a height approximately ve feet above the oor.
Avoid placing the thermostat in areas that will not provide an accurate measurement of the room temperature. Locating the thermostat behind a door, in an alcove, close to a source of thermal radiation or in a drafty area will cause poor or sporadic heating.
For a thermostat that employs an adjustable heat anticipator, adjust the anticipator to match the current measured in the thermostat circuit. An increased anticipator setting may be necessary if the unit cycles frequently. If the room temperature over-shoots the thermostat setting, reduce the anticipator setting.
Operating Control
The preferred control setting for potable hot water is 130°F, 54°C. The operating control should be set to the lowest setting that will satisfy the consumer's needs.
High Limit (Aquastat)
The high limit is located in the top control area of the boiler/water heater. A remote capillary bulb is run to a well on the outlet side of the supply header. The high limit can be reset by depressing the black rubber plug in the front top jacket panel.
The water heater high limit should be set a minimum of 20°F, 11°C higher than the operating control. Refer to the HOT WATER SUPPLY section for the proper supply water temperature.
Flow Switch
A ow switch is provided in the water outlet piping to
prevent the boiler/water heater from firing without
adequate water ow through the heat exchanger.
Low Water Cutoff
If the boiler is to be installed above radiation or if required by other codes or regulations, install a low water cutoff in appropriate piping. Wire the switch and any external controls in series to the "Interlock" contacts in the junction box (see the attached Connection Diagrams for details). Ensure that the low water cutoff device(s) will function properly.
WARNING: Setting the thermostat or operation control too high can result in scalding resulting
in severe personal injury!
Page 25
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 25
MAINTENANCE
WARNING: Disconnect electrical power and close the manual gas shut off valve before performing maintenance or severe personal
injury may result!
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, exposure to hazardous materials or loss of life. Installation
and service must be performed by a qualied
installer, service agency or the gas supplier who must read and follow the supplied instructions before installing, servicing or removing this boiler. This boiler contains crystalline silica materials that have been identified as carcinogenic or possibly carcinogenic to humans when inhaled.
AVERTISSMENT: Une instqallation, un réglage, une réparation ou un entretien non comforme aux normes peut entraîner des dommages matériels, des blessures,exposition à des
matiéres dangereuses ou la mort. L’installation et l’entretien doivent être effectués par un installateur ou un service d’entretien qualié ou
le foumisseur de gaz qui doivent avoir lu les
instructions foumies avant de faire l’installation, l’entretien ou l’enlèvement de la chaudière et les respecter, Cette chaudière contient des matériaux qui ont été identiés comme étant cancérogènes ou pouvant l’être.
CAUTION: Servicing, inspection and adjustment must be done by a trained technician in accordance with all applicable local and national codes. Improper servicing or adjustment can damage the
boiler/water heater!
WARNING: The ceramic combustion chamber contains crystalline silica. Wear a tightly tted dust mask when removing the burners or heat exchanger to prevent inhalation of airborne fibers. Crystalline silica fibers have been identified as carcinogenic, or possibly carcinogenic when inhaled.
The boiler/water heater should be cleaned and inspected once a year and before each heating season. Make sure that the burner and ignition components are free from dust, soot, dirt, corrosion or other deposits that would
impair the boiler/water heater’s performance. Refer to
page 29 (8900) or page 38 (8800) for component
identication.
Combustion Chamber Inspection
1. Remove the left or right lower jacket end panel, item 5 or 24 (8900) or item 5 or 24 (8800).
2. Remove the upper end refractory brackets and carefully remove the end refractory panel.
3. Inspect the combustion chamber, heat exchanger and burner tray components for sign of corrosion and/or deterioration.
4. Clean or replace components as required.
CAUTION: Improper burner servicing can result in premature burner failure voiding the warranty.
Burner Drawer & Burner Removal
1. Close the manual shutoff valves in the gas supply lines and turn off electrical power to the boiler/water heater.
2. Disconnect the gas train from the gas supply piping at the ground joint union, Figure 14.
3. Remove the ame roll-out shield, 8900 only.
4. Remove the two bolts that attach the burner drawer to the base frame.
5. Disconnect the pilot tubing from the solenoid valve and the ignition lead from the ignition control.
6. Pull the burner drawer out until the burners are fully exposed.
7. Inspect each burner for damage or signs of deterioration. Use a brush or compressed air to remove any debris from the burner ports.
8. DO NOT install damaged or badly corroded burners, replace them.
9. Install the burners making sure that they are properly seated in the burner drawer.
10. Replace the burner drawer and ame roll out shield,
8900 only, following the removal steps in reverse order.
Heat Exchanger Inspection & Cleaning
1. Close the shut off valves in the inlet and outlet piping. Relieve the system pressure from the boiler by carefully lifting the relief valve or opening the drain valve.
2. Disconnect the boiler/water heater from the system piping.
3. Remove the left and right headers and mounting studs.
4. Remove the left & right upper and left & right lower jacket end panels, items 5 & 24 (8900) or items 5 & 24 (8800).
5. Remove the left & right front corner trim panels,
8900.
6. Remove the ue collector front panel.
7. Remove the upper front refractory channel assembly and front refractory panels.
8. Slide the heat exchanger out and thoroughly inspect it.
Page 26
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 26
NORMAL
(HARD FLAME)
LIFTING
(TOO MUCH AIR)
YELLOW TIPPING
(MARGINAL)
YELLOW FLAME
(TOO LITTLE AIR)
9. The outside surfaces of the copper tubes should be free of any soot deposits. A slight black smudge is normal with some types of gases. Black soot indicates poor combustion. Green deposits indicate condensation due to low return water temperatures. In either case the heat exchanger must be cleaned thoroughly with water and the problem resolved before the boiler/water heater is returned to service.
10. Replace the cleaned heat exchanger and other components in the reverse order of their removal.
11. The torque values for the bolts that secure the removable headers are 17-20 ft lbs. Once bolts have been started and secured the tightening sequence is as follows:
1) Middle Top
2) Middle Bottom
3) Right Top
4) Left Bottom
5) Left Top
6) Right Bottom
Heat Exchanger Replacement
1. Sagging or distorted heat exchanger tubes are an
indication of low water ow through the system.
2. A damaged heat exchanger must be replaced and the condition that caused the damage resolved before the boiler/water heater is returned to service.
4. The relief valve should not weep or discharge water at normal system pressure. If it does contact
a qualied service technician to have it inspected.
NEVER try to clean or repair the relief valve! If the valve fails to operate properly, have it replaced!
5. The aquastat high limit controls the maximum water temperature in the boiler and should be 20°F, 11°C above set point temperature. If the water temperature reaches the set temperature before the demand for heat has been met, the aquastat high limit should shut the boiler off. The water temperature should never exceed the maximum set point of 240°F, 116 °C. The aquastat high limit cannot be repaired. If it fails to function properly, replace it.
6. Visually check the pilot and main burner ames to
ensure proper operation, see Figures 15 & 16.
WARNING: A yellow, oating ame indicates a lack of combustion air. A lifting ame indicates
too much combustion air. Do not operate the boiler/water heater until the problem is solved
or severe personal injury or death may occur!
Figure 16 - Main Burner Flames
Vent System
Thoroughly inspect the vent system for any signs of blockage, corrosion or leakage. Immediately replace any unsound vent system piping.
Controls
Use the “GENERAL OPERATION” and “CHECKING AND ADJUSTMENTS” sections of this manual for reference.
1. Check the thermostat or operating controls for
2. A oat type low water cutoff device must be ushed
3. The ow switch contacts must be open when water
proper operation.
out per the manufacturers’ instructions. The probe
on a probe low water cut off must be removed, cleaned and inspected at least once a year. Ensure that the low water cutoff operate properly. If not, replace them.
ow is not present.
RIOM-49
Page 27
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 27
TROUBLE-SHOOTING FLOW CHART FOR HONEYWELL OR UTC IGNITION MODULE (24V CONTROL SYSTEM)
Proper line voltage L1 to L2 on heater
terminal strip
24V on secondary
terminals of heater
transformer
24V across 24V and 24V
(GND) terminals of
ignition module
On application of 24V,
control produces audible
spark at pilot
Pilot
Ignites
Adjust the pilot gas
pressure using the
pilot regulator. Pilot
ignition problems
can be caused by high or low pilot
pressure.
Pilot ignites
Check for tripped breaker or open safety
/ limit switch in supply voltage circuit.
Check for broken or loose
connection to transformer, if none
replace transformer.
Check for open limit in this 24V circuit operating control, high limit, flow switch, LWCO, high / low gas pressure switches,
remote operating controls, etc.
Check for loose or broken ignition lead. Check for shorted pilot electrode.
If pilot and ignition lead test good replace module.
During pilot ignition period (audible spark present) check
for 24V between PV and MV/PV terminals of module.
24V at pilot gas
valve leads
A tripped manual reset
high limit may
indicate insufficient
water flow.
Check for loose or
broken wire between
pilot valve and
PV-MV/PV terminals.
Replace module.
Main Flame
Ignites
Manifold pressure in proper
range (3.5”-4.2” N.G.,
10”-11” L.P.). If no pressure on
manifold, during main flame trial for ignition period, check for pressure at tappings of each
main valve. Replace valve
that shows no pressure at
downstream tapping while
powered with pressure at
upstream tapping.
With pilot lit: 24V between the MV and MV/PV terminals of
the module
24V at terminals of
all valves in main
gas train
Pilot valve opens.
Confirm that gas is
present at pilot valve
inlet.
Insure pilot line and
pilot orifice are clear
and that the pilot is
undamaged. The pilot
ignites.
Check for loose or
broken wire between
MV-MV/PV terminals.
Replace pilot solenoid
valve.
Replace the pilot
assembly.
Replace
module.
main valves and
Page 28
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 28
Trouble-Shooting
PROBLEM POSSIBLE CAUSES CORRECTIVE ACTION
Boiler Pounds or Knocks Low or no water flow Ensure that pump is operating properly - look for voltage through
ow switch.
Ensure that all system valves are open.
Ensure that all air has been bled from the system.
Ensure that maximum temperature rise of 35°F, 19°C has not been exceeded.
Low or no system pressure Ensure that water makeup valve is open and functioning.
Heat exchanger blocked Remove return header and inspect the heat exchanger tubes.
Relief Valve Leaks System pressure too high Ensure relief valve is properly sized for the system - never exceed 160 psi.
Expansion tank is waterlogged Ensure expansion tank is properly sized for the system.
Expansion tank is isolated Ensure valve between expansion tank and system is open.
Sooting of Heat Exchanger Return water temperature to low Adjust balancing valves for a minimum return water temperature of 110°F, 43 °C.
Inadequate combustion air Ensure that the make up air supply is adequate per NFPA 54/ANSI Z223.
Ensure that the vent system is sized properly, is not blocked or restricted and that there is adequate draft present in the breeching.
Rated input has been exceeded Ensure that the input rate is correct. Incorrect fuel type Ensure that the fuel type supplied
matches the rating plate.
Page 29
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 29
PARTS LIST (MODELS 420-1900)
36
33
Page 30
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 30
SERVICE AND REPLACEMENT PARTS LIST (MODELS 420-1900)
8900
Ref # Name of Part
6 Inlet/Outlet Header, Cast Iron 01-0001S 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Inlet/Outlet Header, Bronze 01-0003.1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Inlet/Outlet Header, Cast Iron (Mod) 01-0001M 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Inlet/Outlet Header, Bronze (Mod) 01-0003M 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
7 Return Header, Cast Iron 01-0002S 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Return Header, Bronze 01-0004.1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
8 O Ring (pkg of 20) 21-2010 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS
NS Burner Shield 03-0092 1
03-0093 1
03-0094 1
03-0095 1
03-0096 1
03-0097 1
03-0098 1
03-0099 1
03-0100 1
03-0101 1
03-0102 1
03-0103 1
03-0104 1
03-0105 1
03-0106 1
13, 13a Burner Tube 10-0277 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
Burner Tube w/Bracket 70-0635 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Burner Spacers 03-0309 1
03-0310 1
03-0311 1
03-0312 1
03-0313 1
03-0314 1
03-0315 1
03-0316 1
03-0317 1
03-0318 1
03-0319 1
03-0320 1
03-0321 1
03-0322 1
03-0323 1
Stud, Inlet/Outlet & Return Headers ASME
Nut, Inlet/Outlet & Return Headers ASME
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
57-0223 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
57-0492 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
8900 Model Size with Item Quantities Below
Page 31
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 31
8900
Ref # Name of Part
15 Firing Valve, 1" 11-0456 1 1 1 1 1/2* 1/2* 2* 2* 2* 2* 2* 2* 2*
Firing Valve, 1-1/4" 11-0457 1 1 1 1 1 1 1 2* 2*
Firing Valve, 1-1/2" 11-0458 1 1
16 Main Gas Valve, V83042 11-0084 2*
Main Gas Valve, V8944B, 1" 11-0171 1 1 1 1 1 1/2* 2* 2* 2* 2* 2* 2* 2*
Main Gas Valve, V8944B, 1-1/4" 11-0172 1 1 1 1 1 1 1 2* 2*
Main Gas Valve, V8944B, 1-1/2" 11-0173 1 1
17 “A” Valve, 1" 11-0465 1 1 1 1 1 1
“A” Valve, 1-1/4" 11-0466 1 1 1 1 1 1 1
“A” Valve, 1-1/2" 11-0467 1 1
NS Bracket Refractory Upper End 03-0306 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
NS Bracket Refractory Lower End 03-0307 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
18 End Refractory Panel, Left & Right 05-0001 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
19 Center Refractory Panel 05-0002 2
05-0003 2
05-0004 2 2 2 2 4 4 4 4 4 4
20 Corner Refractory Panel 05-0005 4
05-0006 4
05-0007 4
05-0008 4
05-0009 4
05-0010 4
05-0011 2
05-0012 4
05-0013 4
05-0014 4
05-0015 6
05-0016 6
05-0017 6
18, 19, Tile Kit 70-0226K 1
20 70-0227K 1
70-0228K 1
70-0229K 1
70-0230K 1
70-0231K 1
70-0232K 1
70-0233K 1
70-0234K 1
70-0235K 1
70-0236K 1
70-0237K 1
70-0238K 1
70-0239K 1
70-0240K 1
8900 Model Size with Item Quantities Below
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
Page 32
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 32
8900
Ref # Name of Part
NS Bracket Refractory Front/Rear 03-0308 2 2 3 3 3 4 4 5 5 5 6 6 6 7 7
NS Upper Front Refractory Channel 70-0177 1
70-0178 1
70-0179 1
70-0180 1
70-0181 1
70-0182 1
70-0183 1
70-0184 1
70-0185 1
70-0186 1
70-0187 1
70-0188 1
70-0189 1
70-0190 1
70-0191 1
NS Upper Rear Refractory Channel 70-0162 1
70-0163 1
70-0164 1
70-0165 1
70-0166 1
70-0167 1
70-0168 1
70-0169 1
70-0170 1
70-0171 1
70-0172 1
70-0173 1
70-0174 1
70-0175 1
70-0176 1
29
Burner Drawer Side Rail Assy, Left & Right
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
70-0362 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
8900 Model Size with Item Quantities Below
Page 33
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 33
8900
Ref # Name of Part
NS Heat Exchanger Assembly (Copper) 70-0072 1
Cast Iron Headers 70-0073 1
70-0074 1
70-0075 1
70-0076 1
70-0077 1
70-0078 1
70-0079 1
70-0080 1
70-0081 1
70-0082 1
70-0083 1
70-0084 1
70-0085 1
70-0086 1
Heat Exchanger Assembly (Cupronickel) 70-0087 1
Cast Iron Headers 70-0088 1
70-0089 1
70-0090 1
70-0091 1
70-0092 1
70-0093 1
70-0094 1
70-0095 1
70-0096 1
70-0097 1
70-0098 1
70-0099 1
70-0100 1
70-0101 1
Individual copper/cupronickel tubes* available for eld repair *model and serial number required
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
8900 Model Size with Item Quantities Below
Page 34
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 34
8900
Ref # Name of Part
Tube Expansion Tool 30-0761 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Heat Exchanger Assembly (Copper) 70-0102 1
Bronze Headers 70-0103 1
70-0104 1
70-0105 1
70-0106 1
70-0107 1
70-0108 1
70-0109 1
70-0110 1
70-0111 1
70-0112 1
70-0113 1
70-0114 1
70-0115 1
70-0116 1
Heat Exchanger Assembly (Cupronickel) 70-0117 1
Bronze Headers 70-0118 1
70-0119 1
70-0120 1
70-0121 1
70-0122 1
70-0123 1
70-0124 1
70-0125 1
70-0126 1
70-0127 1
70-0128 1
70-0129 1
70-0130 1
70-0131 1
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
8900 Model Size with Item Quantities Below
Page 35
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 35
8900
Ref # Name of Part
30 Tube Bundle (Copper) 70-0132 1
70-0133 1
70-0134 1
70-0135 1
70-0136 1
70-0137 1
70-0138 1
70-0139 1
70-0140 1
70-0141 1
70-0142 1
70-0143 1
70-0144 1
70-0145 1
70-0146 1
30 Tube Bundle (Cupronickel) 70-0147 1
70-0148 1
70-0149 1
70-0150 1
70-0151 1
70-0152 1
70-0153 1
70-0154 1
70-0155 1
70-0156 1
70-0157 1
70-0158 1
70-0159 1
70-0160 1
70-0161 1
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
8900 Model Size with Item Quantities Below
Page 36
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 36
8900
Ref # Name of Part
NS Heat Exchanger “V” Bafes 03-0244 7
03-0245 7
03-0246 7
03-0247 7
03-0248 7
03-0249 7
03-0250 14
03-0251 14
03-0252 14
03-0253 14
03-0254 14
03-0255 14
03-0256 14
03-0257 14
03-0258 14
NS Heat Exchanger Edge Bafes 03-0259 2
03-0260 2
03-0261 2 4
03-0262 2 4
03-0263 2 4
03-0264 2
03-0265 4
03-0266 4
03-0267 4
03-0269 4
03-0271 4
03-0273 4
31 Safety Valve, V88A, 1" 11-0156 1 1 1 1 1 1
Safety Valve, V88A, 1-1/4" 11-0157 1 1 1 1 1 1 1
Safety Valve, V88A, 1-1/2" 11-0158 1 1
32 Ignitor, PSE-NA29 70-9013 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Ignitor, PSE-NA185 70-9014 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Ignitor, PSE-NA29, LP 70-0631 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Ignitor, PSE-NA185, LP 70-0632 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
33 Solenoid Valve w/Regulator, NG, 24V 11-0373 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Solenoid Valve w/Regulator, LP, 24V 11-0375 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
35 Manual Pilot “B” Valve 11-0031 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
36 Ignition Module, S8610M 16-0054 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Ignition Module, UTC 1003 (CSD-1 Only) 16-0058 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Alarm Board, (CSD-1) 16-0023 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS BTC 4 Stage 14-0307 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Spark Generator 16-0036 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Ignition Cable Assembly 120V 16-0201 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
37 Transformer, 50VA 15-0007 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
8900 Model Size with Item Quantities Below
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
Page 37
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 37
8900
Ref # Name of Part
NS Rocker Switch 48-0001 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Relay, 24V AC 15-0113 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Pump Contactor 1PH 15-0118 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Pump Contactor 3PH 15-0111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS
NS
38 High Limit, L4008E, (HB) 14-0112 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
High Limit, L4008E, (HW) 14-0105 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
39 High Limit Well, 3/8 x 3 3/16 13-0105 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
40 Operator, L4008A,(HB), On/Off 14-0102 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Operator, L6008A, (HW) 14-0106 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Operator, L6008G, (2 stage) 14-0107 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Operator, T6031A, (pool heaters) 14-0003 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
41 Orice, #29, NG 10-0016 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Orice, #47, LP 10-0009 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
NS Pressure Relief Valve 50# 13-0040 1 1 1 1
Pressure Relief Valve 50# 30-0360 1 1 1
Pressure Relief Valve 50# 30-0374 1 1 1 1 1
Pressure Relief Valve 50# 30-0379 1 1 1
NS Pressure Relief Valve 125# 30-0364 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Tridicator 13-0308 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Thermometer 13-0302 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
42 Thermometer Well, 3/8 x 2 5/8 13-0103 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Thermometer w/well 13-0320 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Flow Switch 14-0203 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Flow Switch (Potter) 14-0201 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Rating Plate 82-0054 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
NS Vent Termination Hood 6" 09-0112 1 1
Vent Termination Hood 8" 09-0113 1 1 1 1 1 1
Vent Termination Hood 10" 09-0115 1 1 1 1 1 1 1
*4 Stage Only
Low Gas Pressure Switch (Manual Reset)
High Gas Pressure Switch (Manual Reset)
Part # 420 530 630 735 840 950 1050 1160 1260 1370 1470 1580 1685 1790 1900
11-0410 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
11-0411 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
8900 Model Size with Item Quantities Below
Page 38
21a
21
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 38
PARTS LIST (MODELS 2000-4000)
19
18
22
25
7
36
33
42
39
3086
Page 39
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 39
SERVICE AND REPLACEMENT PARTS LIST (MODELS 2000-4000)
8800
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
6 Inlet/Outlet Header, Bronze 01-0012.1 1 1 1 1 1 1
7 Return Header, Bronze 01-0013.1 1 1 1 1 1 1
8 O Ring (pkg of 20) 21-2010 2 2 2 2 2 2
NS Stud, Inlet/Outlet & Return Headers ASME 57-0223 24 24 24 24 24 24
Nut, Inlet/Outlet & Return Headers ASME 57-0492 24 24 24 24 24 24
NS Heat Exchanger “V” Bafe 03-1147 15
03-1148 30
03-1149 30
03-1150 30
03-1151 30
03-1152 30
NS Heat Exchanger Edge Bafe 03-1181 2
03-1182 4
03-1183 4
03-1184 4
8800 Model Size with Item Quantities Below
03-1185 4
03-1186 4
NS Heat Shield 70-1733 2
70-1734 2
70-1735 2
70-1736 1 1
70-1737 1 1
70-1738 1 1
13, 13a Burner Tube, Aluminized Steel 10-0256 19 23 27 30 34 38
Burner Tube, Aluminized w/ Bracket 70-1851 1 1 1 2 2 2
Burner Tube, Stainless Steel 10-0258 19 23 27 30 34 38
Burner Tube, Stainless w/ Bracket 70-1852 1 1 1 2 2 2
16 Main Gas Valve, V8944B, 1-1/4" 11-0172 2* 2* 2* 2/2*
Main Gas Valve, V8944B, 1-1/2" 11-0173 1 2/2* 2/2*
Main Gas Valve, V8944B, 2" 11-0174 1 1
NS Safety Valve, V88A, 1-1/2" 11-0158 1
Safety Valve, V88A, 2" 11-0159 1* 1/1* 2/2* 2/2* 2/2* 2/2*
17 “A” Valve, 1-1/2" 11-0467 1
“A” Valve, 2" 11-0454 1* 1/1* 1/1* 1/1* 1/1* 1/1*
18 End Refractory Panel, Left & Right 05-0050 2 2 2 2 2 2
19, 20 Center Refractory Panel 853413 8 8 10 12 12 14
Page 40
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 40
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
18, 19, Tile Kit 70-1739K 1
20 70-1740K 1
70-1741K 1
70-1742K 1
70-1743K 1
70-1744K 1
NS Bracket Refractory Front/Rear 03-0308 3 3 4 4 5 5
NS Upper Front/Rear Refractory Support 03-1155 2
03-1156 2
03-1157 2
03-1158 2
03-1159 2
03-1160 2
NS Upper Right/Left Refractory Support 03-1161 2 2 2 2 2 2
NS Tube Bundle (Copper) 70-1696 1
8800
8800 Model Size with Item Quantities Below
70-1697 1
70-1698 1
70-1699 1
70-1700 1
70-1701 1
Tube Bundle (Cupronickel) 70-1702 1
70-1703 1
70-1704 1
70-1705 1
70-1706 1
70-1707 1
30 Heat Exchanger (Copper) 70-1684 1
70-1685 1
70-1686 1
70-1687 1
70-1688 1
70-1689 1
Individual copper/cupronickel tubes* available for eld repair *model and serial number required
Page 41
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 41
8800
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
Tube Expansion Tool 30-0761 1 1 1 1 1 1
Heat Exchanger (Cupronickel) 70-1690 1
70-1691 1
70-1692 1
70-1693 1
70-1694 1
70-1695 1
NS 3" Gruvlok Coupling 53-0100 2 2 2 2 2 2
3" x 4" Gruvlok Nipple 53-0300 2 2 2 2 2 2
3" x 4" Gruvlok Nipple, Brass 53-0600 2 2 2 2 2 2
32 Ignitor, PSE-NA29 70-9013 1 1 1 1 1 1
Ignitor, PSE-NA185 70-9014 1 1 1 1 1 1
Ignitor, PSE-NA29, LP 70-0631 1 1 1 1 1 1
Ignitor, PSE-NA185, LP 70-0632 1 1 1 1 1 1
33 Solenoid Valve w/Regulator, NG, 24V 11-0373 1 1 1 1 1 1
8800 Model Size with Item Quantities Below
Solenoid Valve w/Regulator, LP, 24V 11-0375 1 1 1 1 1 1
35 Manual Pilot “B” Valve 11-0031 1/2* 1/2* 1/2* 2/2* 2/2* 2/2*
NS Spark Generator 16-0036 1 1 1 1 1 1
36 Ignition Module, S8610M 16-0054 1 1 1 1 1 1
Ignition Module, UTC 1003 (CSD-1 Only) 16-0058 1 1 1 1 1 1
BTC Staging Control, 4 Stage 14-0307 1 1 1 1 1 1
NS Alarm Board (CSD-1) 16-0023 1 1 1 1 1 1
37 Transformer, 50 VA 15-0007 1 1 1 1 1 1
Transformer, 75 VA 15-0008 1 1 1 1 1 1
NS Rocker Switch (illuminated) 48-0001 1 1 1 1 1 1
NS Relay, 24V AC 15-0113 1 1 1 1 1 1
NS Relay, 120V AC 15-0114 1 1 1 1 1 1
NS Pump Contactor 1PH 15-0118 1 1 1 1 1 1
Pump Contactor 3PH 15-0111 1 1 1 1 1 1
NS Low Gas Pressure Switch (Manual Reset) 11-0410 1 1 1 1 1 1
NS High Gas Pressure Switch (Manual Reset) 11-0411 1 1 1 1 1 1
38 High Limit, L4008E, (HB) 14-0112 1 1 1 1 1 1
High Limit, L4008E, (HW) 14-0105 1 1 1 1 1 1
39 High Limit Well, 3/8 x 13/16 13-0105 1 1 1 1 1 1
40 Operator, L4008A, (HB), On/Off 14-0102 1 1 1 1 1 1
Operator, L6008A, (HW), On/Off 14-0106 1 1 1 1 1 1
Operator, L6008G, 2 stage 14-0107 1 1 1 1 1 1
Operator, T6031A (pool heater) 14-0003 1 1 1 1 1 1
Page 42
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONSPage 42
8800
Ref # Name Of Part Part # 2000 2400 2800 3200 3600 4000
41 Orice, #17, NG 10-0014 20 24 28 32 36 40
Orice, #34, LP 10-0021 20 24 28 32 36 40
NS Pressure Relief Valve 50# 30-0379 1
Pressure Relief Valve 50# 13-0002 1
Pressure Relief Valve 50# 30-0382 1 1 1
Pressure Relief Valve 50# 30-0384 1
Pressure Relief Valve 125# 30-0364 1 1
Pressure Relief Valve 125# 13-0009 1
Pressure Relief Valve 125# 13-0003 1 1
Pressure Relief Valve 125# 13-0053 1
NS Tridicator 13-0305 1 1 1 1 1 1
NS Thermometer (HB) 13-0302 1 1 1 1 1 1
Thermometer (HW) 13-0302 2 2 2 2 2 2
42 Thermometer Well, 3/8 x 2 5/8 13-0103 1 1 1 1 1 1
NS Flow Switch 14-0203 1 1 1 1 1 1
8800 Model Size with Item Quantities Below
NS Flow Switch (Potter) 14-0201 1 1 1 1 1 1
NS Rating Plate 82-0054 1 1 1 1 1 1
*4 Stage Only
Page 43
NOTICE!
Commonwealth of Massachusetts
Installation Requirements
MACODE-3
In the Commonwealth of Massachuses, the
installation must be performed by a licensed plumber or gas er.
1. For all side wall horizontally vented gas fueled equipment installed in every dwelling , building or structure used in whole or in part for residential purposes, including those owned or operated by the commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above nished grade, in the area of the venting, including but not limited to decks and porches, the following requirements shall be satised:
d. INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gaser shall observe that a hard wired carbon monoxide detector with an alarm and baery back-up is installed on the oor level where the gas equipment is to be installed. In addition, the installing plumber or gas er shall observe that a baery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualied licensed professionals for the installation of hard wired carbon monoxide detectors.
i. In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an aic, the hard wired carbon monoxide detector with alarm and baery back-up may be installed on the next adjacent oor level.
ii. In the event that the requirements of this subdivision
can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a baery operated carbon monoxide detector with an alarm shall be installed.
e. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
f. SIGNAGE. A metal or plastic identication plate shall be
permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. e sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLE AR OF ALL OBSTRUCTIONS”.
g. INSPECTION. e state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4. Improper venting can result in excessive levels of
carbon monoxide which can cause severe personal injury or death!
2. Exemptions — e following equipment is exempt from 248CMR 5.08(2)(a) 1 through 4:
a. e equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
b. Product Approved side wall horizontally vented gas fueled
equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
3. MANUFACTURER REQUIREMENTS — GAS EQUIPMENT VENTING SYSTEM PROVIDED.
a When the manufacturer of Product Approved side wall
horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
i. Detailed instructions for the installation of the venting
system design or the venting system components; and
ii. A complete parts list for the venting system design
or venting system.
4. MANUFACTURER REQUIREMENTS — GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
a When the manufacturer of a Product Approved side wall
horizontally vented gas fueled equipment does not provide the parts for venting the ue gases, but identies “special venting systems”, the following requirements shall be satised by the manufacturer:
i. e referenced “special venting system” instructions
shall be included with the appliance or equipment installation instructions; and
ii. e “special venting systems” shall be Product
Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
5. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
Improper venting can result in excessive levels of
carbon monoxide which can cause severe personal injury or death!
Page 44
LIMITED WARRANTY
Boilers/Water Heaters
Industrial, Commercial and Other Non-Residential Use
The “Manufacturer” warrants to the original owner at the original installation site that the heat exchanger of the Industrial, Commercial, and other Non-Residential Use Boiler (the “Product”) will be free from defects in material or workmanship for ten (10) years from the date of installation. Additional twenty one (21) year thermal shock warranty on heat exchanger. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective. All other RBI supplied Boiler/Water Heater parts are warranted against defects in material and workmanship for one (1) year from date of installation or 18 months from date of shipment from RBI.
The “Manufacturer” warrants to the original owner at the original installation site that the heat exchanger of the Industrial, Commercial, and other Non-Residential Use Water Heater (the “Product”) will be free from defects in material
or workmanship for ve (5) years from the date of installation. Additional twenty one (21) year thermal warranty on heat
exchanger. If upon examination by the Manufacturer the Product is shown to have a defect in material or workmanship during the warranty period, the Manufacturer will repair or replace, at its option, that part of the Product which is shown to be defective. All other RBI supplied Boiler/Water Heater parts are warranted against defects in material and
workmanship for one (1) year from date of installation or 18 months from date of shipment from RBI.
This limited warranty does not apply: (a) if the Product has been subjected to misuse or neglect, has been accidentally or intentionally damaged, has
not been installed, maintained or operated in accordance with the furnished written instructions, or has been
altered or modied in any way.
These include but not limited to:
• Excessive water hardness causing a lime build-up in the heat exchanger tubes is not a fault of the equipment and is not covered under the manufacturer’s warranty.
• Excessive pitting and erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer’s warranty. (See Installation Instructions for proper pump performance.)
• Chemical corrosion, no corrosive chemical (freon, dry cleaning chemicals, degreasing liquids, chlorine or any chemicals that produce hydrochloric acid) can be present in the boiler room as it rapidly destroys the heating equipment and voids the warranty.
• All copper n boilers should not operate with a return water temperature less than 110°F, 43°C atmospheric combustion, 125°F, 52°C fan assist combustion. If a lower temperature is required, an external bypass should be
installed to prevent condensation. The manufacturer’s warranty does not cover damage done by condensation.
(b) to any expenses, including labor or material, incurred during removal or reinstallation of the Product or
parts thereof.
(c) to damage as a result of settlement, distortion, collapse, or cracking of any foundation area, beams or pipes
surrounding the Product.
(d) to any workmanship of any installer of the Product; or to Products installed outside the continental United
States or Canada.
This limited warranty is conditional upon: (a) shipment, to the Manufacturer, of that part of the Product thought to be defective. Goods can only be returned
with prior written approval from the Manufacturer. All returns must be freight prepaid.
(b) determination in the reasonable opinion of the Manufacturer that there exists a defect in material or workmanship.
Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period.
THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EITHER EXPRESS OR IMPLIED, AND ALL SUCH OTHER WARRANTIES, INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY. IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL, SPECIAL, OR INCIDENTAL DAMAGES OF ANY NATURE WHATSOEVER, OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE. THIS LIMITED WARRANTY GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY EACH JURISDICTION.
260 North Elm Street 7555 Tranmere Drive Westeld, MA 01085 Mississauga, Ontario L5S 1L4 Canada Phone: (413) 568-9571 Phone: (905) 670-5888 Fax: (413) 568-9613 Fax: (905) 670-5782
Loading...