Raytec SPARTAN Series, SPZ SPARTAN, SPX SPARTAN, BL24-EM, BL24-STD Installation Manual

SPX/SPZ
SPARTAN
Bulkhead Range - Installation Guide
Zone 1 variant CML 13ATEX3007 & IEC Ex CML14.0001 Zone 2 variant CML 17ATEX4231 & IEC Ex CML17.0135
This installation guide provides instructions for installing the White-Light SPARTAN series of explosion protected oodlights.
Overview
1 Safety Instructions
2 Installation
3 Maintenance
4 Technical Specication
5 Declaration of Conformity
Important information
The SPARTAN series of explosion protected bulkheads are specialist devices, certied for use in specic operating environments.
The units must be installed in accordance with these instructions, must be correctly certied for the specic operating environment and must be installed by suitably qualied personnel.
If you have any queries about the installation or the certication of the unit – please contact Raytec for immediate assistance and advice.
940-M-00069 Rev A
1. Safety instructions
1. Read this leaet carefully before commencing to install the SPARTAN Bulkhead unit and retain it for future use. Installation can only be carried out by suitably qualied personnel.
2. Check the certication nameplate attached to the luminaire to ensure that the
hazardous zone, mains supply, ambient temperature present and ‘T’ rating are suitable
for the environment the unit is being installed in.
3. If the SPARTAN unit is to be installed in areas of high vibration, please consult with Raytec.
4. The SPARTAN unit housing is constructed from marine grade aluminium and toughened glass. The end user must ensure that these materials are suitable for the environment the SPARTAN unit will be installed in; Zone 1 or Zone 2 Hazardous areas.
5. Check certication nameplate on side of bulkhead to ascertain type of threaded cable entry on the luminaire. Select suitably certied ATEX/IEC Ex cable glands and stopper
plugs, these must be parallel thread, have a minimum of 5 full thread engagement and
be of a medium/ne tolerance to ISO965-1 and ISO965-3. The cable entry devices
selected must maintain the IP rating of the luminaire
6. The incoming mains cable should not exceed a temperature rise of 24°C above the ambient conditions; select suitable cable.
Isolate mains before
removing cover
2 www.raytecled.com UK / Europe Tel: +44 (0) 1670 520055
!
Install in a well ventilated area
1.5m
Do not continually
stare at lamp
Americas Tel: +1 613 270 9990
2. Installation
Mounting SPARTAN Unit
1. To meet the requirements of certication a MINIMUM of 2 xing points must be used, the xing points must be suitable for the conditions of use.
220
182
3
Americas Tel: +1 613 270 9990
302
288
204
240
220
168
70
20
121
104
17
3www.raytecled.comUK / Europe Tel: +44 (0) 1670 520055
Spartan Bulkhead 24 Floodlight Standard/Emergency Variant
Typical wiring diagram - Standard Variants
Typical wiring diagram - Emergency Variants
D
2. The unit may have been supplied with an integrated photocell. Care should be taken
when positioning the unit to ensure the sensor is not shielded, is not pointing directly
at another light source and is monitoring the general, prevailing light conditions.
3. The SPARTAN Bulkhead is supplied as standard with the mounting brackets tted as
shown on the above diagram, other mounting methods/brackets available – please contact Raytec.
GREEN
EARTH TO SCREW
PSU
GREEN
EARTH TO SCREW
PSU
WHITE
WHITE/RED
Wire the Mains cable into the terminal block. Provision has been made for this and identied as the E (Earth), L1 (Live switched), L2 (Live permanent) and N (Neutral) terminals. There
are two pairs of contacts for each of these to facilitate a mains cable that can be looped in
and out of the unit. The L2 terminals on a standard unit are not electrically connected but
allows them to be used on the same circuits as emergency bulkheads.
4. Installer should earth the unit separately – an internal and external earth point are
provided as standard
BROWN BLUE
TO LED's
N E L1 L2
BLACK
BLACK
RED
FUSE
RED
WHITE
WHITE/RED
BATTERY
TO LED's
GREY BROWN BLUE
N E L1 L2
REMOVE LINK IF 4-CORE CABLE USE
5. Connect wires to mains supply.
6. If the unit is opened for any reason, disconnect mains – On emergency luminaires
there may be more than one mains supply
7. All SPARTAN oodlights have terminal blocks suitable for looping 4mm2 cable,
only one cable should be connected to each terminal block connection
4 www.raytecled.com UK / Europe Tel: +44 (0) 1670 520055
Americas Tel: +1 613 270 9990