Raytec SPARTAN Series, SPZ SPARTAN, SPX SPARTAN, BL24-EM, BL24-STD Installation Manual

SPX/SPZ
SPARTAN
Bulkhead Range - Installation Guide
Zone 1 variant CML 13ATEX3007 & IEC Ex CML14.0001 Zone 2 variant CML 17ATEX4231 & IEC Ex CML17.0135
This installation guide provides instructions for installing the White-Light SPARTAN series of explosion protected oodlights.
Overview
1 Safety Instructions
2 Installation
3 Maintenance
4 Technical Specication
5 Declaration of Conformity
Important information
The SPARTAN series of explosion protected bulkheads are specialist devices, certied for use in specic operating environments.
The units must be installed in accordance with these instructions, must be correctly certied for the specic operating environment and must be installed by suitably qualied personnel.
If you have any queries about the installation or the certication of the unit – please contact Raytec for immediate assistance and advice.
940-M-00069 Rev A
1. Safety instructions
1. Read this leaet carefully before commencing to install the SPARTAN Bulkhead unit and retain it for future use. Installation can only be carried out by suitably qualied personnel.
2. Check the certication nameplate attached to the luminaire to ensure that the
hazardous zone, mains supply, ambient temperature present and ‘T’ rating are suitable
for the environment the unit is being installed in.
3. If the SPARTAN unit is to be installed in areas of high vibration, please consult with Raytec.
4. The SPARTAN unit housing is constructed from marine grade aluminium and toughened glass. The end user must ensure that these materials are suitable for the environment the SPARTAN unit will be installed in; Zone 1 or Zone 2 Hazardous areas.
5. Check certication nameplate on side of bulkhead to ascertain type of threaded cable entry on the luminaire. Select suitably certied ATEX/IEC Ex cable glands and stopper
plugs, these must be parallel thread, have a minimum of 5 full thread engagement and
be of a medium/ne tolerance to ISO965-1 and ISO965-3. The cable entry devices
selected must maintain the IP rating of the luminaire
6. The incoming mains cable should not exceed a temperature rise of 24°C above the ambient conditions; select suitable cable.
Isolate mains before
removing cover
2 www.raytecled.com UK / Europe Tel: +44 (0) 1670 520055
!
Install in a well ventilated area
1.5m
Do not continually
stare at lamp
Americas Tel: +1 613 270 9990
2. Installation
Mounting SPARTAN Unit
1. To meet the requirements of certication a MINIMUM of 2 xing points must be used, the xing points must be suitable for the conditions of use.
220
182
3
Americas Tel: +1 613 270 9990
302
288
204
240
220
168
70
20
121
104
17
3www.raytecled.comUK / Europe Tel: +44 (0) 1670 520055
Spartan Bulkhead 24 Floodlight Standard/Emergency Variant
Typical wiring diagram - Standard Variants
Typical wiring diagram - Emergency Variants
D
2. The unit may have been supplied with an integrated photocell. Care should be taken
when positioning the unit to ensure the sensor is not shielded, is not pointing directly
at another light source and is monitoring the general, prevailing light conditions.
3. The SPARTAN Bulkhead is supplied as standard with the mounting brackets tted as
shown on the above diagram, other mounting methods/brackets available – please contact Raytec.
GREEN
EARTH TO SCREW
PSU
GREEN
EARTH TO SCREW
PSU
WHITE
WHITE/RED
Wire the Mains cable into the terminal block. Provision has been made for this and identied as the E (Earth), L1 (Live switched), L2 (Live permanent) and N (Neutral) terminals. There
are two pairs of contacts for each of these to facilitate a mains cable that can be looped in
and out of the unit. The L2 terminals on a standard unit are not electrically connected but
allows them to be used on the same circuits as emergency bulkheads.
4. Installer should earth the unit separately – an internal and external earth point are
provided as standard
BROWN BLUE
TO LED's
N E L1 L2
BLACK
BLACK
RED
FUSE
RED
WHITE
WHITE/RED
BATTERY
TO LED's
GREY BROWN BLUE
N E L1 L2
REMOVE LINK IF 4-CORE CABLE USE
5. Connect wires to mains supply.
6. If the unit is opened for any reason, disconnect mains – On emergency luminaires
there may be more than one mains supply
7. All SPARTAN oodlights have terminal blocks suitable for looping 4mm2 cable,
only one cable should be connected to each terminal block connection
4 www.raytecled.com UK / Europe Tel: +44 (0) 1670 520055
Americas Tel: +1 613 270 9990
8. The battery fuse located within the Bulkhead housing on emergency variants is
disconnected after nal manufacturing testing. When installing the bulkhead the battery fuse will need to be reconnected and the unit charged for 24 hours and then discharged (repeated 3 times) to bring the battery up to peak capacity. (Unless an ‘EMX’ intelligent emergency variant – see notes below)
9. If a 4 core cable is used on emergency luminaires – L1, L2, N and E the link cable
at the front of the terminal block between L1 and L2 should be removed
10. During emergency operation the light output and duration will be determined by the
variant purchased
Spartan Intelligent Emergency Operation Guide
Operation
The light tting will carry out the following function automatically after installation:
Commissioning Cycle
Function test
Self-test
A tri-colour LED indicator displays the light tting status. The indication colours are shown in table 1.
a. Commissioning Cycle
Starts automatically 24 hours after installation.
3 charge/discharge cycles to maintain battery’s full capacity.
Battery is charged for 24 hours before each discharge cycle.
No need for manual commissioning
b. Function Test
Carried out every 7 days.
Checks the function of the battery, lamp and power supply.
Lasts for few minutes only.
Americas Tel: +1 613 270 9990
5www.raytecled.comUK / Europe Tel: +44 (0) 1670 520055
c. Self-test
Carried out at a random time every 3 month.
Checks the battery’s capacity and lamp’s condition.
Performs self-recovery for the battery if not at peak capacity.
Is carried out at 100% load
Discharges only 2/3 of the battery’s capacity.
LED indication
LED Indication Condition
Blinking amber Commissioning
Static Amber
Blinking Red
No light Emergency mode activated
Static Green Battery charged and PSU OK
Function Test
Self-test
Battery defective/Fuse blown
PSU error
Battery not at peak capacity
Light engine failure
Notes
The luminaire will switch off momentarily (<0.5sec) during the transition between a
test and normal operation.
If a test was interrupted by a mains failure, the test will be halted, and the unit will
enter emergency mode. Once the mains supply is back, the unit will allow 24 hours to recharge the battery before continuing the tests.
The self-test is carried out at a random time to eliminate the possibility of having more
than one unit undergoing the test at the same time.
6 www.raytecled.com UK / Europe Tel: +44 (0) 1670 520055
Americas Tel: +1 613 270 9990
3. Maintenance
1. It is essential that all SPARTAN Bulkhead units are maintained in accordance with
the requirements of the EN60079-17standard: (Electrical apparatus for explosive gas atmospheres – other than mines).
2. IMPORTANT. No modications are permitted to the unit, all spare parts must be
purchased from the manufacturer, unauthorized modications or spare parts will invalidate certication and make the equipment dangerous.
3. Isolate the SPARTAN Bulkhead from the mains supply and allow to cool before
carrying out any maintenance work.
For Emergency variants, battery must be isolated/ connected when a hazardous environment is NOT present prior to carrying out any maintenance work.
4. In the unlikely event of a number of LED’s failing, the light engine assembly must be replaced. This is achieved by loosening front cover bolts, disconnecting the white LED cables to power supply, remove four M6 bolts from rear of light engine and pull the light engine assembly clear. Re tting a light engine is a reversal of the above procedure.
5. The unit has one independent power supply, in the event that the power supply needs to be replaced the cables to the LED and mains terminal block will need to
be disconnected, the four M6 bolts released, then the power supply can then be
removed. Fitting a new power supply is a reversal of the above procedure.
6. Disposal of packaging, SPARTAN unit and old LED assemblies should be carried out in accordance with national regulations.
PROTECTION/CERTIFICATION
CML13ATEX3007 or IEC Ex CML14.0001 II 2 GD Ex e mb op is IIC T4 Gb
o
C to +55oC (standard variants)
Ta -52
II 2 GD Ex e mb op is IIC T4 Gb
o
C to +46oC (emergency variants)
Ta -20
Ex tb IIIC T98°C Db IP66 & IP67 Ta = -52°C to +55°C
110V-254V AC/155V-355V DC or 18-48V AC/18-69V DC
CML17ATEX4231 or IEC Ex CML17.0135 II 3 GD Ex ec mc op is IIC T4 Gc
o
C to +55oC or
Ta -50
Ex tb IIIC T98°C Dc IP66 & IP67 Ta = -50°C to +55°C
110V-254V AC/155V-355V DC or 18-48V AC/18-69V DC
o
Emergency variants restricted to -20
Americas Tel: +1 613 270 9990
C
7www.raytecled.comUK / Europe Tel: +44 (0) 1670 520055
4. Technical Specication
BL24-STD BL24-EM
Input Voltage 110-254V AC/DC
Input Current (230Vac, full load) 0.15A 0.2A
Consumption 33W 35W
Power Factor (230Vac, full load) >0.97
Mains Frequency 50/60Hz
Inrush Current (I
Total Harmonic Distortion (230Vac, full load) <10%
ATEX and IECEx Rating See below
Inrush Current Typical Curve
Ipeak
@50%) 20A, ∆t < 300µs
peak
IP Rating IP66/67
Weight (std) 5Kg 6Kg
Dimensions See previous pages for line diagrams
Twidth
8 www.raytecled.com UK / Europe Tel: +44 (0) 1670 520055
Americas Tel: +1 613 270 9990
Max number of ttings allowed per MCB
(Based on 230V)
MCB Type Rating BL24 - STD BL24 - EM
B 10A 11 10
B 16A 17 15
B 20A 25 22
B 25A 35 32
C 10A 24 20
C 16A 34 28
C 20A 49 44
C 25A 58 55
Americas Tel: +1 613 270 9990
9www.raytecled.comUK / Europe Tel: +44 (0) 1670 520055
Declaration Of Conformity With The Atex Directive 2014/34/EU
Raytec Ltd. declares under our sole responsibility that the product(s) listed below conform with the relevant provisions of directive 2014/34/EU of 20
Manufacturer Raytec Ltd
Description
of Equipment
Notied Bodies Sira Certication Services (0518)
Certicate
numbers
Equipment
Marking
Unit 15, Wansbeck Business Park Rotary Parkway Ashington Northumberland
NE63 8QW United Kingdom
Spartan range of bulkhead luminaires – standard and
emergency
Unit 6 Hawarden Industrial Park Hawarden Deeside CH5 3US
Zone 1 - CML13ATEX3007 or IEC Ex CML14.0001 Zone 2 - CML17ATEX4231 or IEC Ex CML17.0135
II 2 GD Ex e mb op is IIC T4 Gb
o
C to +55oC (standard variants)
Ta -52
II 2 GD Ex e mb op is IIC T4 Gb
o
C to +46oC (emergency variants)
Ta -20
Ex tb IIIC T98°C Db IP66 & IP67 Ta = -52°C to +55°C
110V-254V AC/155V-355V DC or 18-48V AC/18-69V DC
II 3 GD Ex ec mc op is IIC T4 Gc
o
C to +55oC
Ta -50
Ex tb IIIC T98°C Dc IP66 & IP67 Ta = -50°C to +55°C
110V-254V AC/155V-355V DC or 18-48V AC/18-69V DC
th
April 2016
*Emergency variants restricted to -20°C
10 www.raytecled.com UK / Europe Tel: +44 (0) 1670 520055
Americas Tel: +1 613 270 9990
Compliance with the Essential Health and Safety Requirements has been assessed by
reference to the following standards -
IEC 60079-0 : 2012 IEC 60079-7 : 2015 IEC 60079-1 : 2014
IEC 60079-18 : 2015 IEC 60079-25 : 2015 IEC 60079-31 : 2014
And also 2014/35/EU - Low Voltage Directive, 2014/30/EU - EMC Directive
Signed
Name Barry Thompson Position Director of Hazardous Area Division
Dated
Serial number
Americas Tel: +1 613 270 9990
11www.raytecled.comUK / Europe Tel: +44 (0) 1670 520055
UK / Europe T: +44 (0) 01670 520055 hazsales@raytecled.com
Americas T: +1 613 270 9990 ushazsales@raytecled.com
www.raytecled.com
Loading...