Raypak RSIT30, RSIT50, RSIT65, RSIT80, RSIT115 Installation & Operating Instructions Manual

...
Page 1
INSTALLATION & OPERATING
Stainless Steel Indirect Fired Storage Water Heater
Model RSIT30-
RSIT115
WARNING: If these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas sup­ plier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the heater or in a safe place for future ref­erence.
CATALOG NO. 3400.59 Effective: 06-01-17 Replaces: New P/N 241673 Rev. 1
Page 2
Rev. 1 Changes to: New Additions: New Deletions: None
2
Page 3
CONTENTS
INTRODUCTION ...............................4
SAFETY WARNINGS ........................4
Scalding ......................................................5
Single Wall Heat Exchanger........................6
Freeze Protection........................................6
SPECIFICATION PERFORMANCE
DATA ................................................7
Installation ...................................................8
Component Location ...................................8
Boiler and Circulator Sizing.........................8
Temperature & Pressure Relief Valve .........8
Plumbing .....................................................8
Controls .....................................................11
START UP ......................................13
Purging the System...................................13
Flushing the System..................................13
Checking Circulator...................................13
Set the Thermostat to the Desired
Temperature. .............................................13
Verify the Boiler Functionality....................13
Check the Water Temperature ..................13
MAINTENANCE &
TROUBLESHOOTING .....................14
PARTS ............................................15
WARRANTY....................................16
3
Page 4
INTRODUCTION
The Raypak indirect water heater uses heat from a boiler to heat domestic water. The heat is transferred to the water by a coil heat exchanger inside of the tank. The indirect storage tank stores the energy from the boiler for use later. With the excellent thermal insulation in the Raypak water heater, the boiler turns on and off less often. To maintain energy efficiency the stainless steel tank is fully insulated with 2 inches of rigid foam. The Raypak in­direct water heater is an efficient means of heating water.
This indirect water heater has all stainless steel construction. The stainless steel tank is fully welded, pickled and passivated. The stainless steel resists corrosion assuring a long service life.
SAFETY WARNINGS
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause serious injury or property damage. Refer to this manual. For assistance or additional information, consult a qualified installer or service agency.
CAUTION: The recommended water temperature
for normal residential use is 120°F. The control temperature setting does not always reflect the outlet water temperature, which could occasionally exceed 120°F. The variation in outlet temperature could be based on factors including but not limited to usage patterns and type of installation. Test your water at the tap nearest to the indirect water heater.
WARNING: Hotter water increases the risk of scald
injury. Before adjusting the water temperature setting, read this instruction manual. Temperatures at which injury occurs vary with the person’s age and the length of exposure.
The slower reaction time of children, elderly, and physically or mentally-challenged persons increases the scalding hazard to them. It is recommended that lower water temperatures be used where these exposure hazards exist. Such households may require a temperature setting less than 120°F to prevent accidental contact with hot water.
To lower water temperature, use point-of-use temperature limiting devices.
warranty does not apply to units that have been improp­erly installed or operated. (Refer to the warranty at the back of this manual.) Installation and service must be performed by a qualified installer, or service agency. If, after reviewing this manual, you still have questions which this manual does not answer, please contact your local Raypak representative or visit our website at
www.raypak.com. Keep this manual with the water
heater after installation.
Local plumbing and electrical codes must be followed in the installation of this indirect water heater. In the ab­sence of a local code, use the UNIFORM PLUMBING CODE and the NFPA Code. Local codes may super­sede instructions in this installation manual.
Thank you for purchasing a Raypak® product. We hope you will be satisfied with the high quality and durability of our equipment.
Product Receipt
On receipt of your unit it is suggested that you visually check for external damage to the shipping carton. If the carton is damaged, make a note to that effect on the Bill of Lading when signing for the shipment. Next, remove the water heater from the carton. Report any damage to the carrier immediately.
On occasion, items are shipped loose. Be sure that you receive the correct number of packages as indicated on the Bill of Lading.
BEFORE INSTALLATION
Raypak strongly recommends that this manual be re­viewed thoroughly before installing your Indirect Fired Storage Water Heater. Please review the General Safety information before installing the unit. Factory
Claims for shortages and damages must be filed with the carrier by consignee. Permission to return goods must be received from the factory prior to shipping. Goods returned to the factory without an authorized Re­turned Goods Receipt number will not be accepted. All returned goods are subject to a restocking charge.
4
Page 5
When ordering parts, you must specify the model and
Water temperature over 125°F can cause instant se ve re burns or death from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
See instruction manual before set­ting temperature at water heater.
Feel water before bathing or show­ering.
Temperature limiting valves are available, see manual.
serial number of the water heater. When ordering under warranty conditions, you must also specify the date of installation.
Purchased parts are subject to replacement only under the manufacturer’s warranty. Debits for defective re­placement parts will not be accepted. Parts will be re­placed in kind only per Raypak’s standard warranties.
Water Temp Time to Produce Serious Burn
120°F More than 5 minutes
125°F 1-1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
Scalding
Water Temperature Setting
DANGER: Safety and energy conservation are
factors to be considered when selecting the water temperature setting of a water heater’s temperature control. Water temperatures above 125°F can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined on the label pictured below. This label is also located on the water heater.
145°F Less than 3 seconds
150°F About 1-1/2 seconds
155°F About 1 second
Table courtesy of The Shriners Burn Institute.
Table A: Time To Produce Serious Burn
CAUTION: The recommended water temperature
setting for normal residential use is 120°F (49°C).
Time/Temperature Relation­ships in Scalds
The chart shown above may be used as a guide in de­termining the proper water temperature for your home.
DANGER: Households with small children, disabled, or elderly persons may require a 120°F or lower control (thermostat) setting to prevent contact with HOT water.
Maximum water temperatures occur just after the boiler has shut off. To find the water temperature being deliv­ered, turn on a hot water faucet, place a thermometer in the water stream and read the temperature.
NOTICE: Mixing valves are available for reducing point-of-use water temperature by mixing hot and cold water in branch water lines. Contact a licensed plumber or the local plumbing authority for further information.
DANGER: Hotter water increases the potential for Hot Water SCALDS.
5
Page 6
Single-Wall Heat Exchanger
Freeze Protection
This Indirect fired water heater uses a single-wall heat exchanger. In order for this water heater to meet the re-
uirements of the Uniform Plumbing Code, the following
q requirements must be met.
1. The boiler water pressure must be limited to 30 PSI.
An approved 30 PSI relief valve must be installed in the boiler loop.
2. The boiler heat transfer medium must be either
potable water or use fluid additives that have a tox­icity rating of Class 1.
3. Bear a label on the system with the Wording “Cau-
tion” followed by:
a. The heat transfer medium must be water or
other nontoxic fluid having a toxic rating of Class 1 as listed in clinical Toxicology of Com­mercial Products, 5th ed.
b. The pressure of the heat-transfer medium must
be limited to a maximum of thirty (30) psig (207kPa) by an approved safety or relief valve.
The water heater and water lines must be protected from exposure to freezing temperatures. Freezing tem-
eratures can cause damage to this indirect water
p heater. The unit should be located indoors.
If the water heater is to remain idle for an extended pe­riod of time, the power and water to the boiler system should be turned off to conserve energy and prevent a build-up of dangerous hydrogen gas.
The water heater and piping should be drained if they might be subjected to freezing temperatures.
After a long shut-down period, the water heater’s oper­ation and controls should be checked by qualified serv­ice personnel. Make certain the water heater is completely filled again before placing it in operation.
6
Page 7
SPECIFICATION & PERFORMANCE DATA
øA
20º 20º
B
WATER OUTLET
T
HERMOSTAT
WELL
W
ATER INLET
C
E
F
D
BOILER INLET
BOILER OUTLET
T
&P RELIEF VALVE
- Max working pressure 150 PSIG
- Max potable water temperature 150ºF
- Max boiler temperature 210ºF
Fig. 1: Dimensions
Tank
Model
RSIT30 48 (21.8) 270 (123) 3/4 NPT 1 NPT 20.1” (510) 39.6” (1006) 2.2” (56) 30.9” (785) 9.4” (239) 22” (559)
RSIT40 60 (27.3) 390 (177) 3/4 NPT 1 NPT 21.8” (554) 46.9” (1141) 2” (51) 37” (940) 10.2” (259) 23.6” (599)
RSIT50 76 (34.5) 545 (248) 3/4 NPT 1 NPT 21.8” (554) 62.7” (1593) 2” (51) 52.8” (1341) 10.2” (259) 26.3” (668)
RSIT65 85 (38.6) 620 (282) 3/4 NPT 1 NPT 21.8” (554) 70.2” (1783) 2” (51) 60.3” (1532) 10.2” (259) 26.3” (668)
RSIT80 106 (48.2) 760 (345) 1 NPT 1 NPT 23.8” (605) 69.9” (1775) 1.9” (48) 60.5” (1537) 9.9” (251) 33.3” (846)
RSIT115 150 (68.2) 1100 (500) 1-1/2 NPT 1 NPT 28.9” (734) 65.8” (1671) 2.4” (61) 53” (1346) 11.5” (292) 31.9” (810)
Weight
Empty
(lb) / (kg)
Tank
Weight
Full
(lb) / (kg)
Water
Inlet/
Outlet
Heat
Exchanger
Coil
Connections
Tank Dia.
(IN.) / (mm)
A
Tank Height
(IN.) / (mm)
B
Water
Inlet
Height
(IN.) / (mm)
C
Water
Outlet/ T&P Height (IN.) / (mm)
D
Boiler Outlet
Height
(IN.) / (mm)
E
Table B: Dimensions
Heat
Source
Water
Volume
(gal) / (L)
First Hour
Rating
(gal/hr) /
(L/hr)
Model
Potable
Water
Volume
(gal) / (L)
RSIT30 25.7 (97) 0.8 (3.0) 172 (651) 149 (564) 1.4 (0.8) 96 (328) 27 (8.2) 6.9 (0.64) 14.0 (53) 8.4 (2.6)
RSIT40 38.6 (146) 1.0 (3.8) 207 (783) 172 (651) 0.9 (0.5) 108 (369) 31 (9.4) 8.0 (0.74) 14.0 (53) 9.4 (2.9)
RSIT50 55.0 (208) 1.3 (4.9) 261 (988) 208 (787) 0.7 (0.4) 133 (454) 39 (11.9) 10.0 (0.93) 14.0 (53) 5.0 (1.5)
RSIT65 62.9 (238) 1.3 (4.9) 270 (1022) 209 (791) 0.6 (0.3 135 (461) 39 (11.9) 10.0 (0.93) 14.0 (53) 5.0 (1.5)
RSIT80 76.5 (290) 1.6 (6) 348 (1317) 276 (1045) 0.6 (0.3) 177 (604) 47 (14.3) 14.6 (1.4) 14.0 (53) 4.5 (1.4)
RSIT115 111.3 (421) 2.5 (9.5) 412 (1559) 309 (1170) 0.5 (0.3) 199 (679) 55 (16.8) 17.1 (1.6) 14.0 (53) 7.0 (2.1)
Continuous
Draw
Rating
(gal/hr) /
(L/hr)
Standby
Loss
(ºF/hr) /
(ºC/hr)
Minimum
Boiler
Ouptut
(BTUH) /
(kw)
Coil
Length
(ft) / (m)
Heating Surface
Area
(Sq. ft) /
2
(m
)
Heating
Coil
Flow
(GPM) /
(L/min)
Table C: Performance Data
Note: Rating Data based on 180ºF boiler output water, potable water inlet 58ºF and outlet 135ºF. Other operating conditions are possible.
7
Boiler Inlet/ Thermostat
Height
(IN.) / (mm)
F
Coil
Pressure
Drop at
Flow
(ft wc) /
(m wc)
Page 8
Installation
Plumbing
Component Location
or best results, the indirect water heater should be in
F a central location close to the boiler. This will minimize heat loss in the boiler piping and reduce wait times for hot water at the point of use. The indirect water heater must be protected from freezing temperatures.
Anode Rods
The use of anode rods is not required for this unit. The all-stainless steel construction of this tanks minimizes corrosion.
Boiler and Circulator Sizing
The ratings published in this manual for your Raypak indirect water heater can be obtained through proper selection of boiler output and circulator capacity. See the performance data in Table C.
To determine the appropriate circulator for your system, follow these three steps:
A tempering valve may be required by local jurisdiction to protect the user from scalding. Raypak recommends the use of a tempering valve with this indirect water
eater. The tempering valve limits the water tempera-
h ture at the point of use.
If local municipal codes require a backflow preventer, an expansion tank will be required. The expansion tank will prevent pressure build-up inside of the indirect water heater and associated piping. The expansion tank must be installed in the domestic water piping close to the tank. No shutoff valve is allowed between the expansion tank and the indirect water heater.
All water connections made to this heater should be sealed with thread tape or pipe dope. It is important to use two pipe wrenches when tightening connections to this tank. One wrench should be used to support the tank fitting from rotating; the other wrench will be used to rotate and tighten the plumbing fitting. It is recom­mended to use shutoff valves on this tank for servicing. The shutoff valves should not isolate the relief valve or expansion tank from the indirect water heater. The inlet of the heater should be piped with a drain connection for servicing the heater.
1. Calculate the pressure drop of all straight pipe and
fittings on the supply and return at the desired flow rate.
2. Add the pressure drop from Step 1 to the pressure
drop through the indirect water heater coil (see Table C for friction loss) to obtain a total pressure drop.
3. Select a circulator pump that will provide adequate
flow at the total pressure drop. A pump performance curve should accompany every circulator pump.
Temperature & Pressure Relief Valve
This water heater requires a temperature and pressure relief valve. The T&P relief valve is supplied by the in­staller. This relief valve is required for safe operation of the unit to protect from excessive temperatures and pressures. A discharge pipe should be installed to the relief valve. This discharge piping should terminate in a safe location. This discharge piping must comply with local and national plumbing codes. The piping must be rated for 120ºF and 150 PSI.
Several piping diagrams are shown below depicting var­ious installation variations. Use these diagrams (Figs. 3 & 4) to help piping the indirect water heater.
This unit is not supplied with a separate drain fitting. It is recomended that one be added to the inlet piping. Fig­ure 2 depicts the drain valve installation.
Cold Water Supply
Fig. 2: Drain Valve Installation
8
Page 9
P
RV
XPAK FT BOILER
BALL VALVE
S
YSTEM
PUMP
(S3) SYSTEM SENSOR
BALL VALVE
C
HECK
VALVE
T
&P
G
AUGE
UNION
INLET
OUTLET
UNION
UNION
MIXING
VALVE
P
RV
B
ALL
VALVE
BALL
VALVE
PRESSURE
REDUCING VALVE
BOILER
PUMP
EXPANSION TANK
DHW
PUMP
D
RAIN
AIR S
EPARATOR
PRESSURE GAUGE
BALL VALVE
UNION
BALL
VALVE
DRAIN
TO
BOILER
C
OLD
I
NLET
HOT
O
UTLET
FROM
SYSTEM
12” MAX APART
MIX
OUTLET
MAKE UP
WATER
T
O
SYSTEM
C
OLD
I
NLET
(S5) IND
TANK
SENSOR
FROM
BOILER
INDIRECT
F
IRED
STORAGE
W
ATER
HEATER
D
RAIN
DRAIN
Figure 3 depicts connecting the indirect water heater to the system loop. This diagram also shows the optional anti-scalding mixing valve (may be required in some ju­risdictions). The boiler shown in this diagram is the XPak FT. Other boilers may be used instead.
Fig. 3: VERSA MODE 2
9
Page 10
PRV
X
PAK FT
B
OILER
SYSTEM
P
UMP
(
S3)
S
YSTEM
S
ENSOR
B
ALL
V
ALVE
T&P GAUGE
UNION
INLET
OUTLET
U
NION
UNION
MIXING
VALVE
BALL VALVE
PRV
BALL
V
ALVE
(S6) IND SUPPLY
SENSOR
B
O
I
L
E
R
P
UM
P
EXPANSION TANK
D
HW
P
UMP
DRAIN
CHECK VALVE
PRESSURE GAUGE
BALL VALVE
UNION
BALL
VALVE
DRAIN
TO
BOILER
COLD INLET
H
OT
O
UTLET
F
ROM
SYSTEM
1
2” MAX APART
MIX
OUTLET
MAKE UP
W
ATER
TO
S
YSTEM
COLD INLET
(S5) IND
TANK
SENSOR
FROM
BOILER
I
NDIRECT
F
IRED
STORAGE
WATER
HEATER
DRAIN
DRAIN
Fig. 4: VERSA MODE 3
Figure 4 depicts connecting the indirect water heater di­rectly to the boiler loop. Other boilers may be used in­stead.
10
Page 11
BACK OF AQUASTAT
C
LAMP
CLAMP SCREWS
WIRE TERMINALS
TEMPERATURE DIAL
CLAMP
CROSS SECTIONAL VIEW
INSERT BULB AS SHOWN
TANK WALL
Controls
A Control system is required for this indirect water heater to function correctly. Some possible control schemes are explained below. The particular control
cheme will depend upon the specific installation.
s
This indirect water heater can be connected to any Ray­pak boiler that is equipped with a VERSA control. The VERSA control is pre-configured to handle an indirect storage water heater. The VERSA control can also be configured to give priority to the domestic hot water or to space heating. To connect the unit to a VERSA­equipped boiler, read the VERSA IC Installation & Op­erating Manual, Cat. 5000.72.
For the VERSA system to function properly, a 10K Ohm thermistor needs to be installed into the tank aquastat location, per Fig. 5.
Fig. 5: 10K Ohm Thermistor Installation
The indirect water heater can be controlled by an aqua­stat. The aquastat measures the domestic water tem­perature inside the tank. When more heat is required, the aquastat will turn on the pump to circulate boiler water through the indirect water heater.
To install the aquastat into the heater, see Fig. 6.
Fig. 6: Aquastat Well
11
Page 12
FIELD
INSTALLED
24VAC
igure 7 is a controls diagram for a boiler that is always
F on, maintaining hot water in the boiler loop. The aquas-
at turns on a circulator to induce boiler water flow
t through the indirect water heater.
Fig. 7: Boiler Maintaining 180ºF
Figure 8 depicts wiring the indirect water heater to a cold-start boiler system using a Honeywell RS845. In this type of system, the boiler does not run unless there is a call for heat in one of the zones of the system. When connecting to a cold-start boiler, always remember that in principle an indirect water heater operates as another heating zone. The difference is that when the indirect water heater calls for heat, the indirect water heater cir­culator must start rather than opening a zone valve; the system circulator stays off, and the boiler must light to reach Operating Temperature.
Fig. 8: Cold-Start Boiler
12
Page 13
START UP
Relief Valve
new combination temperature and pressure (T&P) re-
A lief valve, complying with the Standard for Relief Valves and Automatic Gas Shut-Off Devices for Hot Water Sup­ply Systems, ANSI Z21.22, is supplied by the installer. It must be installed in the opening provided and marked for the purpose on the water heater. No valve of any type should be installed between the relief valve and the tank. Local codes shall govern the installation of relief valves.
The pressure rating of the relief valve must not exceed 150 PSI, or the maximum working pressure of the water heater as marked on the rating plate.
The BTUH rating of the relief valve must equal or ex­ceed the BTUH input of the water heater as marked on its rating plate.
Position the outlet of the relief valve above a suitable open drain to eliminate potential water damage. Piping used must be of a type approved for hot water distribu­tion.
The discharge line must be no smaller than the outlet of the valve and must pitch downward from the valve to allow complete gravity drainage of the relief valve and discharge line.
The end of the discharge line should not be threaded or concealed, and must be protected from freezing. No valve of any type, restriction, or reducer coupling may be installed in the discharge line.
Checking Circulator
Check that the circulator or zone valve operates when there is a call for heat. When a call for heat is initiated, water should begin to flow through the indirect water heater’s coil.
Set the Thermostat to the Desired Temperature
For normal water heating installations, Raypak recom­mends an operating temperature of 120ºF or 49ºC. Other temperatures may be required by the particular installation. To minimize burns and scalding, Raypak recommends that the water temperature be verified at the point of use (see Verify the Water Temperature below).
For VERSA-equipped Raypak boilers, the indirect water heater’s setpoint is controlled by the boiler and the 10k Ohm thermistor installed in the water heater’s ther­mal well. To adjust the water heater setpoint, please refer to the equipped boiler, read the VERSA IC Instal­lation & Operating Manual, Cat. 5000.72.
For installations with an aquastat control, the tempera­ture is adjusted at the aquastat control located on the tank thermowell. To adjust the setpoint temp, rotate the dial on the aquastat to the desired setpoint.
Verify the Boiler Functionality
Purging the System
Purge the system of air and check for leaks at all of the connections.
Flushing the System
Flush the system completely. It is important to clear any debris and residues from inside the piping and tank be­fore the water heater will be put to use by the customer. To flush the system, open one of the hot water valves at the point of use after the water heater. Allow enough water to flow through the tank to change the water vol­ume at least two times.
When a call for heat is initiated, the boiler should come on and begin heating. The boiler should also shut off when the tank has reached its setpoint. If the boiler does not heat, please check that water circulator is function­ing and that the wiring is correct.
Verify the Water Temperature
Raypak recommends that the water temp be verified at the point of use. First, let the indirect water heater come to temperature. The water heater has reached its set­point when the boiler heating water has stopped flowing through the heat exchanger. To verify the water temp, open the shutoff valve at the point of use. Let the water run for several minutes until the temperature has stabi­lized. Measure this stabilized water temperature.
13
Page 14
MAINTENANCE & TROUBLESHOOTING
The Raypak indirect storage water heater requires little maintenance. Below is a list of maintenance tasks that should be performed annually.
Visually check for leaks in the system. This includes the domestic water piping, boiler piping, relief valve, and• the handhole cover at the top of the tank.
Have the boiler inspected according to its manufacturer’s operation manual.
Lift the lever on the relief valve to verify that the valve functions.
Periodically open the indirect water heater relief valve to verify its functionality.
Problem Cause Solution
Refer to boiler installation manual.
No potable hot water
Water too hot
Insufficient hot water
T&P valve discharges
Boiler not operating.
Zone valve not opening. Replace zone valve.
Circulator pump not working.
Tank thermostat.
Scale build-up.
Thermostat set too high. Adjust thermostat.
Tempering valve malfunction. Refer to tempering valve instructions.
Thermostat set too low. Adjust thermostat. Undersized boiler, no priority to
domestic hot water.
Demand higher than indirect water heater capacity.
Insufficient circulator flow.
Tank temperature too high.
Pressure too high.
Check boiler circuit breaker.
Check boiler thermostat setting.
Check power supply.
Replace circulator.
Thermostat set too low.
Check thermostat wiring. Check coil for scale build up. Descale if
necessary.
Replace boiler or rewire for priority.
Determine peak usage, and check tank sizing chart.
Install mixing valve, and raise tank tem­perature.
Check for restrictions in piping.
Check circulator sizing.
Lower tank aquastat setting.
Faulty aquastat.
Check incoming water pressure. Closed loop systems require an expan-
sion tank.
Table D: Troubleshooting
14
Page 15
2-M
1-M
3-M
PARTS
Below is a list of the replacement parts for the Stainless Steel Indirect Water Heater.
PL diagram showing replacement parts:
I
15
Page 16
!"#$#%&'!()**)+%,!
-./!*012034!5607 89:;;!56::9!#8<7/:=6!(06:/!>:06:/;!08<!56./0?:!%083;!
@&+&*)"!
Raypak Inc. (Raypak) warrants this indirect water heater to be free from defects in materials and workmanship, under normal use and service, for the appropriate a
pplicable Warranty periods. At its option, Raypak will repair or replace a malfunctioning indirect water heater in accordance with the terms of this Limited Warranty, if it fails in normal use and service during the appropriate applicable Warranty periods. The replacement indirect water heater must be supplied by Raypak. The replacement indirect water heater unit, will be warranted only for the unexpired portion of the original unit’s appropriate applicable Warranty period.!
&
--&A%#B&!')%&!
The effective Date of warranty coverage (or the beginning of the applicable Warranty periods) is the date of installation of the water heater if properly documented. Otherwise, it is the date of manufacture of the water heater plus ninety (90) days.
)CC"#A)D"&!()**)+%,!C&*#E'5!
T
he applicable Warranty periods will vary depending on the ownership and/or use (or water heating application) of the unit as follows: LIFETIME RESIDENTIAL LIMITED WARRANTY COVERAGE – as long as the indirect water heater is installed in a single family dwelling owned by its original owner/end user, Raypak will furnish a replacement unit (if the tank leaks) provided the unit has not been moved from the original installation site or been rendered inoperable by an event listed in the Warranty exclusions section of this Limited Warranty. This warranty coverage applies only to the original indirect water heater purchased and installed at each site. It does not apply to any in-warranty replacement indirect water heater. The owner/end user must be able to p
rovide proof that he or she purchased the indirect unit in order to qualify for Lifetime Residential Limited Warranty coverage.
1
0 YEAR RESIDENTIAL LIMITED WARRANTY COVERAGE – if the indirect water heater is installed in a single family dwelling owned by persons other than the original owner/end user, the applicable Warranty periods are ten (10) years from the effective Date for the tank provided the unit has not been moved from the original installation site or rendered inoperable by an event listed in the Warranty exclusions section of this Limited Warranty. This warranty coverage applies only to the original indirect water heater purchased and installed at each site. It does not apply to any in-warranty replacement indirect water heater.
5 YEAR COMMERCIAL LIMITED WARRANTY COVERAGE – if the indirect water heater is installed in a multiple family dwelling or any other type of commercial business, the applicable Warranty periods are five (5) years from the effective Date for the tank provided the unit has not been moved from the original installation site or rendered inoperable by an event listed in the Warranty exclusions section of this Limited Warranty. This warranty coverage applies only to the original indirect water heater purchased and installed at each site. It does not apply to any in-warranty replacement indirect water heater.
()**)+%,!&FA"G5# E+5!
This Limited Warranty will not cover: a) Service trips to the installation site to teach you how to install, use, or maintain this indirect water heater or to bring the indirect water heater’s installation into compliance with local building codes and regulations. b) Damages, malfunctions, or failures resulting from failure to install the indirect water heater in accordance with applicable building codes/ordinances or good plumbing and electrical trade practices. c) Damages, malfunctions, or failures resulting from improper installation or failure to operate and/or maintain the indirect water heater in accordance with the manufacturer’s instructions provided. d) Performance problems caused by improper sizing of the boiler and/or the indirect water heater. e) Chloride content >250ppm, maximum water temperature in excess of 90°C/194°F. f) Problems associated with the chemistry of the water being heated (for example: rotten egg smell or inappropriate use of water softening equipment); g) Damages, malfunctions, or failures caused by using the indirect water heater to perform functions it was not designed to perform, abuse, accident, fire, flood, freeze, lightning, acts of God, and the like. h) Tank failures (leaks) caused by operating the indirect water heater in a corrosive or contaminated atmosphere. i) Damages, malfunctions, or failures caused by operating the indirect water heater with an empty, or partially empty, tank. j) Damages, malfunctions, or failures caused by operating the indirect water heater at water temperatures exceeding the maximum setting of the operating, or high limit, control. k) Tank failures caused by operating the indirect water heater when it is not supplied with potable water, free to circulate at all times. l) Damages, malfunctions, or failures caused by subjecting the tank to pressures greater than those shown on the rating label. m) Damages, malfunctions, or failures resulting from the use of any attachment, including any energy saving device, not authorized by Raypak. n) Indirect units installed outside the fifty states (and the District of Columbia) of the United States of America and its territories and the Dominion of Canada. o) Indirect units moved from the original installation location. p) Indirect water heaters that have had their rating labels altered or removed. An indirect water heater should not be operated if the rating label is removed.
")DE*H!$)%&*#)"5H!5>#CC#+@H!)+'!C*EA&55# +@!AE5%5!
This Limited Warranty does not cover any labor expenses for service, repairs, reinstallation, permits, or removal and disposal of a leaking indirect water heater or a defective component part of an indirect water heater. All such expenses are the owner’s responsibility. This Limited Warranty does not cover any reinstallation material costs for pipe, valves, fittings, or any other materials and/or services required to repair or replace a malfunctioning indirect water heater or defective component part of an indirect water heater. All such expenses are the owner’s responsibility. Raypak will pay the transportation costs for an “in-warranty” replacement indirect water heater, to a convenient delivery point (selected by Raypak) near the place the original indirect water heater was purchased; such as a local Raypak water heater Distributor. The owner of the indirect water heater will be responsible for any local freight charges, including the cost of returning an indirect water heater, replaced “in-warranty” to a convenient location (selected by Raypak); such as a local Raypak water heater Distributor. Raypak does not authorize, recommend, or receive any benefit from any warranty claims processing or similar fees charged by others to process warranty claims for any Raypak indirect water heater. Raypak will not reimburse any party for these, or any other, fees not specifically covered in this Limited Warranty document.
16
Page 17
>E(!%E!ED%)#+!()**)+%,!A")#$!)55#5%)+A&!
Any claim for warranty assistance must be made promptly. Raypak reserves the right to deny any warranty claim filed more than ninety (90) days after an incident covered by this Limited Warranty occurs. First, determine if your indirect water heater is “in-warranty” (that is, within the applicable Warranty periods that a
pply). You can determine your unit’s warranty status by obtaining the complete model number, the complete serial number, and the date of original installation a
nd accessing the “Warranty Verification” functionality on the Raypak website (www.Raypak.com) or contacting Raypak Warranty personnel (telephone number (805) 278-5300). To establish Lifetime Residential Limited Warranty coverage you must be able to provide proof that you purchased the indirect unit that is the subject of your warranty claim. If your indirect water heater is “in-warranty”, refer to the installation and operation manual provided with it or contact the Raypak Technical Service Department (telephone number (805) 278-5300) to obtain the technical assistance you need to repair or replace your defective indirect unit. You may also use the plumber of your choice or select a plumber, or mechanical contractor, from your local Yellow pages to assist you – at your expense. Be prepared to provide the plumber, mechanical contractor, or Raypak Technical Service person you call with the complete model number, the complete serial n
umber, and the date of original installation or the date of the owner’s purchase of the defective indirect water heater in addition to an explanation of your indirect water heater problem. If an exact replacement unit is not available, Raypak will provide you with the current model of your indirect water heater. If government regulations or industry certification or similar standards require the replacement indirect water heater, or replacement component part, to have features not found in the malfunctioning indirect water heater, you will be charged for the difference in price represented by those required features. If you pay the price difference for those required features and/or to upgrade the size and/or other features available on a replacement new indirect water heater, you will also receive a complete new Limited Warranty (with the full applicable Warranty periods the original unit entitled you to) for the replacement indirect water heater. Raypak reserves the right to inspect, or require the return of, each indirect water heater or defective component part replaced under the terms and conditions of this L
imited Warranty. Each “in-warranty” indirect water heater replaced under this Limited Warranty must be made available to Raypak (with the original rating label and all the component parts intact) in exchange for the replacement indirect water heater. Warranty compensation is subject to validation of “in-warranty” coverage by Raypak.
Warranty claims personnel
• To obtain warranty compensation for an “in-warranty” indirect water heater replacement, you must provide Raypak with: (at Raypak’s option) either the indirect water heater replaced “in-warranty” (with the original rating label and all the component parts intact) or the complete original rating label (photocopies are not acceptable) removed from the indirect water heater replaced “in-warranty”; the complete model number and the complete serial number of the indirect water heater that replaced the original indirect water heater; and, the date the originally installed indirect water heater failed. The owner may also be required to provide proof he/she is the original owner/end user of the indirect water heater being replaced or the date of installation of the original indirect water heater to establish its “in-warranty” status.
• Warranty claim documentation should be mailed promptly to Raypak Inc., 2151 Eastman Ave, Oxnard, CA 93030.
EXCLUSIVE WARRANTY• LIMITATION OF LIABILITY
This Limited Warranty is the only Warranty given by Raypak Inc. (Raypak) for this indirect water heater. No one is authorized to make any other warranties on behalf of Raypak. ANY IMPLIED WARRANTIES, INCLUDING MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE, SHALL NOT EXTEND BEYOND THE APPLICABLE WARRANTY PERIODS SPECIFIED PREVIOUSLY. RAYPAK’S SOLE LIABILITY, WITH RESPECT TO ANY DEFECT, SHALL BE AS SET FORTH IN THIS LIMITED WARRANTY AND ANY CLAIMS FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES (INCLUDING DAMAGE FROM WATER LEAKAGE) ARE EXCLUDED. Some states do not allow limitations on how long an implied warranty lasts, or for the exclusion of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Limited Warranty gives you specific legal rights, and you may also have other rights, which vary from state to state. We suggest you immediately complete the information below and retain this certificate of Limited Warranty in the event warranty service is required. Reasonable proof of original purchase and current ownership or the original date of installation of your indirect water heater (whichever is applicable) may be required to establish its “in-warranty” status. Otherwise, the effective Date of the Limited Warranty will be the date of manufacture plus ninety (90) days.
'E!+E%!*&%G*+!%>#5!'EAG$&+%!%E!*),C)I!
"##$!%&!'%&(!)*+,!'-&#,!(#-&#,!*,!.+/%0#//!,#1*,2/!
0345!67!*895:;.<=>95==!?6@3A>69B!CCCCCCCCCCCCCCCCCCCCCCCCCC CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC!
'3A5:!(53A5: !%9=A3DD3A>69!?6@3A>69!-EE:5==B!CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC!
'F5:5!AF>=!'3A5:!(53A5:!>=!>9=A3DD5EB!CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC!
23A5!'3A5:!(53A5:!83=!>9=A3DD5EB!CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC!
0345!67!,3G H3I!,5A3>D5:B!CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC CCCCCCCC!
-EE:5==!67!,5A3>D5:B!CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC!
&5D5HF695!0<4J5:!67!,3GH3I!,5A3>D5:B!CCCCCCCC CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC!
164HD5A5!K6E5D!0<4J5:!67!'3A5:!(53A5:B!CCCCC CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC!
164HD5A5!/5 :>3D!0<4J5:!67!'3A 5:!(53A5:B!CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC!
17
Page 18
18
Page 19
19
Page 20
www.raypak.com
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468
Litho in U.S.A.
20
Loading...