Raypak Raytherm 4001, Raytherm 2100 User Manual

Job: Engineer: Contractor: Prepared By: Date:
Versatile
Suitable for use with hydronic heating boilers and hot water heaters
Permits sidewall venting Allows use of smaller diameter vent pipe
Efficient
Maintains thermal efficiency of 82% on all appliance sizes
Power Vent
For Raytherm
®
Models 2100-4001
Features
Induced draft Plenum sized for appliance capacity Pre-wired and shipped loose for field mounting Air flow proving switch, mounted and wired Fan motor relay, mounted and wired Heavy-duty galvanized steel cabinet Polytuf powder coat finish Indoor construction Easy installation Limited one-year warranty Shipped loose for field mounting
Catalog No.: 1000.96B Effective: 11-15-07 Replaces: 10-15-01
Power Vent
For Raytherm 2100 - 4001 Model
Raytherm
Model
2100 2100 20 60 16-7/8 22-3/8 33-1/2 17-1/4 7-11/16 14 115 7.2 1/2 1900 2500 2499 20 60 16-7/8 22-3/8 33-1/2 21-3/4 12-3/16 14 115 7.2 1/2 1900 3001 3000 20 60 24-1/4 27-3/8 44-3/4 23-5/8 10-1/8 16 115 10.7 3/4 3400 3500 3500 20 60 24-1/4 27-3/8 44-3/4 29-1/4 15-3/4 16 115 10.7 3/4 3400 4001 4000 20 60 24-1/4 27-3/8 44-3/4 34-7/8 21-3/8 18 115 10.7 3/4 3400
MBTU
Max. Runt (ft.) Dimensions Electrical Ratings
Vert. Horiz. A B C E F K Volts Amps HP
Max. CFM
@ 70°F
Notes: 1. Vent pipe sizes are based on standard horizontal discharge with maximum sixty feet of horizontal length with
no elbows, 300°F nominal flue temperature, and sea-level operation. (Allow 10 ft. equivalent length adjustment for each 90° elbow.) For installation under other conditions, please consult the factory.
2. Left discharge is standard.
3. Vent pipe must meet Category III appliance venting requirements.
4. Follow installation instructions provided by power vent manufacturer.
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725 www.raypak.com
Catalog No.: 1000.96B Effective: 11-15-07 Replaces: 10-15-01