Raypak B-21, B-23, B-26, B-27 User Manual

4 (1)
Raypak B-21, B-23, B-26, B-27 User Manual

Job:

 

 

 

 

 

TempTracker

 

 

 

 

 

Engineer:

 

2- and 4-Stage Controllers

Contractor:

 

For Hi Delta® and Raytherm®

Prepared By:

 

Date:

Boilers & Water Heaters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TempTracker is designed to sequence multiple boilers up to four total stages, whether it’s one to four on/off boilers, two two-stage boilers, or one boiler with up to four stages. It is available factory-mounted or loose on Hi Delta boilers, and loose on Raytherm boilers. This control can be used for space heating and hot water supply with six application-specific modes to meet various applications, including outdoor reset for heating systems. It monitors and displays inlet and outlet temperatures on all applications as well as monitors outdoor temperature when an outdoor reset mode is utilized.

Features

1-4 boilers/stages

Selectable P or PID logic

LCD display

NEMA 1 enclosure

Boiler-in and boiler-out water sensors

System water sensor

Outdoor air sensor (Models B-27 and B-23)

Alarm ready (pilot duty)

24 VAC, 60 Hz, 3 VA Supply Power

Relay Ratings

Stage 1: 5A @ 120 VAC Stages 2 to 4: 3A @ 120 VAC

Programmable Functions

6 programming modes

Adjustable outdoor reset

Min. system water temperature (70 °F)

Max. system water temperature o Heating – 220 °F

o DHW – 190 °F

Temperature differential (2 to 42 °F)

Boiler target (70 to 220 °F)

Outdoor cutoff (35 to 85 °F)

Boiler mass (low, med, high)

Stage-on delay (P mode) (10 sec. to 8 min.)

System pump-off delay (0 to 20 min.)

Temperature measurement (°F or °C)

Model Information

B-26

2-stage setpoint

B-27

2-stage outdoor reset

B-21

4-stage setpoint

B-23

4-stage outdoor reset

Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725 www.raypak.com

Catalog No.: 5100.30A

Effective: 2-1-08

Replaces: 8-1-07