WARNING: If these instructions are not followed exactly, a fire or explosion may
result causing property damage, personal injury or death
.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and
liquids or other combustible materials in the vicinity of this or any other appliance. To
do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or
the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for
future reference.
Models 399B–2339B
Types H & WH
L
W
2
Rev. 2 reflects the following: Changes to: Paragraph one of the Stacking section on page 9; Table G on page 16; Table H
on page 18; Fig. 19 on page 22; Fig. 20–22 on page 23; Fig. 24 on page 24; the Wiring Diagrams on pages 39 and 40. Theaddition of: A wiring diagram note on page 38.
WARNINGS4
BEFORE INSTALLATION5
Product Receipt5
Model Identification5
Ratings and Certifications5
Installations at Elevation5
Component Locations6
General Information7
GENERAL SAFETY8
Time/Temperature Relationships in
Scalds8
INSTALLATION9
Installation Codes9
Equipment Base9
Stacking9
Clearances11
Combustion and Ventilation Air12
Conventional Combustion Air Supply12
Water Piping14
Hydronic Heating16
Gas Supply18
Electrical Power Connections21
Field Wiring Connection22
Venting25
Changing the Flue Outlet27
Venting Installation Tips27
Venting Configurations28
Outdoor Installation32
Controls32
Heater Sequence of Operation33
Wiring Diagrams39
START-UP41
Pre Start-up41
Start-Up42
OPERATION45
Lighting Instructions45
To Turn Off Gas To Appliance45
Indicates the presence of immediate hazards which will cause severe
personal injury, death or substantial property damage if ignored.
WARNING:
Indicates the presence of hazards or unsafe practices which could cause
severe personal injury, death or substantial property damage if ignored.
CAUTION:
Indicates the presence of hazards or unsafe practices which could cause
minor personal injury or product or property damage if ignored.
NOTE:
Indicates special instructions on installation, operation, or maintenance which
are important but not related to personal injury hazards.
DANGER: Make sure the gas on which the heater
will operate is the same type as that specified on the
heater rating plate.
WARNING: Should overheating occur or the gas
supply valve fail to shut, do not turn off or disconnect
the electrical supply to the heater. Instead, shut off
the gas supply at a location external to the heater.
WARNING: Do not use this heater if any part has
been under water. Immediately call a qualified
service technician to inspect the heater and to
replace any part of the control system and any gas
control which has been under water.
WARNING: To minimize the possibility of improper
operation, serious personal injury, fire, or damage to
the heater:
•Always keep the area around the heater free of
combustible materials, gasoline, and other
flammable liquids and vapors.
•Heater should never be covered or have any
blockage to the flow of fresh air to the heater.
WARNING - CALIFORNIA PROPOSITION
65: This product contains chemicals known to the
State of California to cause cancer, birth defects or
other reproductive harm.
WARNING: Risk of electrical shock. More than one
disconnect switch may be required to deenergize the
equipment before servicing.
CAUTION: Operation of this heater in lowtemperature systems requires special piping.
Harmful internal condensation will occur if the inlet
water temperature does not exceed 105°F. Warranty
claims will be denied when condensation occurs.
CAUTION: If this heater is to be installed above
radiation level, it must be provided with a low water
cut-off device at the time of heater installation.
CAUTION: If this heater is to be installed in a
negative or positive pressure equipment room, there
are special installation requirements. Consult factory
for details.
WARNINGS
Pay Attention to These Terms
4
WARNING: This unit contains refractory ceramic
fiber (RCF) insulation in the combustion chamber.
RCF, as manufactured, does not contain respirable
crystalline silica. However, following sustained
exposure to very high temperatures (>2192F), the
RCF can transform into crystalline silica
(cristabolite). The International Agency for Research
on Cancer (IARC) has classified the inhalation of
crystalline silica (cristabolite) as carcinogenic to
humans.
When removing the burners or heat exchangers,
take precautions to avoid creating airborne dust and
avoid inhaling airborne fibers. When cleaning spills,
use wet sweeping or High Efficiency Particulate Air
(HEPA) filtered vacuum to minimize airborne dust.
Use feasible engineering controls such as local
exhaust ventilation or dust collecting systems to
minimize airborne dust. Wear appropriate personal
protective equipment including gloves, safety
glasses with side shields, and appropriate NIOSH
certified respiratory protection, to avoid inhalation of
airborne dust and airborne fiber particles.
BEFORE INSTALLATION
Raypak strongly recommends that this manual be reviewed thoroughly before installing your Delta Limited
heater. Please review the General Safety information
before installing the heater. Factory warranty does not
apply to heaters that have been improperly installed or
operated. (Refer to the warranty at the back of this
manual.) Installation and service must be performed
by a qualified installer, service agency or gas supplier.
If, after reviewing this manual, you still have questions
which this manual does not answer, please contact the
manufacturer or your local Raypak representative.
Thank you for purchasing a Raypak product. We hope
you will be satisfied with the high quality and durability
of our equipment.
Product Receipt
On receipt of your heater it is suggested that you visually check for external damage to the shipping crate. If
the crate is damaged, make a note to that effect on the
Bill of Lading when signing for the shipment. Remove
the heater from the shipping packaging. Report any
damage to the carrier immediately.
On occasion, items are shipped loose. Be sure that
you receive the correct number of packages as indicated on the Bill of Lading.
Claims for shortages and damages must be filed with
the carrier by consignee. Permission to return goods
must be received from the factory prior to shipping.
Goods returned to the factory without an authorized
Returned Goods Receipt number will not be accepted.
All returned goods are subject to a restocking charge.
When ordering parts, you must specify the model and
serial number of the heater. When ordering under warranty conditions, you must also specify the date of
installation.
Purchased parts are subject to replacement only
under the manufacturer’s warranty. Debits for defective replacement parts will not be accepted and will be
replaced in kind only per Raypak’s standard warranties.
Model Identification
The model identification number and heater serial
number are found on the heater rating plate located on
the lower right outside jacket of the heater. The model
number will have the form H8 1259B or similar
depending on the heater size and configuration. The
letter(s) in the first group of characters identifies the
application (H = Hydronic Heating, WH = Domestic
Hot Water (DHW)). The number which fol-lows identifies the firing mode (1 or 4 = on-off, 3 = 2-stage, 8 =
3-stage and 9 = 4-stage). The second group of characters identifies the size of the heater (four numbers
representing the approximate MBTUH input), and,
where applicable, a letter, indicating the manufacturing
series.
Ratings and Certifications
Standards:
•ANSI Z21.13 · CSA 4.9 - latest edition, Gas-Fired
Hot Water Boilers
•ANSI Z21.10.3 · CSA 4.3 - latest edition Gas
Water Heaters
All Raypak heaters are National Board Approved, and
design-certified and tested by the Canadian Standards
Association (CSA) for the U.S. and Canada. Each
heater is constructed in accordance with Section IV of
the American Society of Mechanical Engineers
(ASME) Heater Pressure Vessel Code and bears the
ASME stamp. The heater also complies with the latest
edition of ASHRAE 90.1 Standard.
Installations at Elevation
Rated inputs are suitable for up to 5,000 ft elevation
without de-rating. Consult the factory for installations
at altitudes over 5,000 ft above sea level.
WARNING: Altering any Raypak pressure vessel
by installing replacement heat exchangers, tube
bundle headers, or any ASME parts not
manufactured and/or approved by Raypak will
instantly void the ASME and CSA ratings of the
vessel and any Raypak warranty on the vessel.
Altering the ASME or CSA ratings of the vessel also
violates national, state, and local approval codes.
To meet commercial hot water use needs, the high
limit safety control on this water heater is adjustable up
to 210°F. However, water temperatures over 125°F
can cause instant severe burns or death from scalds.
When supplying general purpose hot water, the recommended initial setting for the temperature control is
125°F.
Safety and energy conservation are factors to be considered when setting the water temperature on the
thermostat. The most energy-efficient operation will
result when the temperature setting is the lowest that
satisfies the needs of the application.
Water temperature over 125°F can cause instant
severe burns or death from scalds. Children, disabled
and elderly are at highest risk of being scalded.
•Feel water before bathing or showering.
•Temperature limiting valves are available.
Maximum water temperatures occur just after the
heater’s burner has shut off. To determine the water
temperature being delivered, turn on a hot water
faucet and place a thermometer in the hot water
stream and read the thermometer.
NOTE: When this water heater is supplying general
purpose hot water for use by individuals, a
thermostatically controlled mixing valve for reducing
point of use water temperature is recommended to
reduce the risk of scald injury. Contact a licensed
plumber or the local plumbing authority for further
information.
Time/Temperature
Relationships in Scalds
The following chart details the relationship of water
temperature and time with regard to scald injury and
may be used as a guide in determining the safest
water temperature for your applications.
Table C: Time to Produce Serious Burn
8
Water temperature over 125°F can
cause instant severe burns or death
from scalds.
Children, disabled, and elderly are
at highest risk of being scalded.
See instruction manual before setting temperature at water heater.
Feel water before bathing or showering.
Temperature limiting valves are
available, see manual.
Water
Temp.
120°FMore than 5 minutes
125°F1-1/2 to 2 minutes
130°FAbout 30 seconds
135°FAbout 10 seconds
140°FLess than 5 seconds
145°FLess than 3 seconds
150°FAbout 1-1/2 seconds
155°FAbout 1 second
Table courtesy of The Shriners Burn Institute
Time to Produce Serious
Burn
INSTALLATION
INSTALLATION
Installation Codes
Installations must follow these codes:
•Local, state, provincial, and national codes, laws,
regulations and ordinances
•Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1,
when required (CSD-1)
•For Canada only: CAN/CGA B149 Installation
Code (B149) and CSA C22.1 C.E.C. Part 1
(C22.1)
The temperature of the water in the heater can be regulated by using the temperature controller. To comply
with safety regulations, the temperature controller is
set at the lowest setting when shipped from the factory.
To adjust the water temperature, insert a small straight
screwdriver into the adjustment screw on the front of
temperature controller and turn the wheel to the
desired setting (See Fig. 4.).
CAUTION: Hotter water increases the risk of scalding! There is a hot water scald potential if the
thermostat is set too high.
Fig. 4: Temperature Control
Equipment Base
The heater should be mounted on a level, structurally
sound surface. The heater is approved for installation
on a combustible surface but must NEVER be
installed on carpeting. Gas-fueled equipment installed
in enclosed parking garages must be located at least
18 in. above the floor.
Stacking
Delta Limited units can be stacked two units high with
an optional stacking rack. A stacking kit is available
from Raypak for this type of installation.
CAUTION: The heaters should be located in an
area where water leakage will not result in damage
to the area adjacent to the appliances or to the
structure. When such locations cannot be avoided, it
is recommended that a suitable catch pan,
adequately drained, be installed under the
appliance. The pan must not restrict air flow.
Fig. 5: Typical Stacked Installation
9
REQUIRES OPTIONAL VENT TEE.
REQUIRES OPTIONAL VENT TEE IF VENTED OUT BACK
OF HEATER.
Fig. 6: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
Table D: Vent/Air Inlet Termination Clearances
10
U.S. Installations
Clearance above grade, veranda, porch,
A
deck, or balcony
Clearance to window or door that may be
B
opened
4 ft (1.2m) below or to side
1 ft (30 cm)1 ft (30 cm)
of opening; 1 foot (30 cm)
above opening
1
Canadian Installations
3 ft (91 cm)
2
CClearance to permanently closed window**
Vertical clearance to ventilated soffit located
above the terminal within a horizontal dis-
D
tance of 2 ft (61cm) from the centerline of the
5 ft (1.5m)*
terminal
EClearance to unventilated soffit**
FClearance to outside corner**
GClearance to inside corner6 ft (1.83m)*
Clearance to each side of center line ex-
H
tended above meter/regulator assembly
*
3 ft (91 cm) within a height
15 ft above the me-
ter/regulator assembly
IClearance to service regulator vent outlet*6 ft (1.83m)
Clearance to non-mechanical air supply inlet
to building or the combustion air inlet to any
J
other appliance
KClearance to mechanical air supply inlet
Clearance above paved sidewalk or paved
L
driveway located on public property
Clearance under veranda, porch, deck or
M
balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
2
In accordance with the current CAN/CGA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that serves
both dwellings
TT Permitted only if veranda, porc h, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and
underside of ver anda, porch, deck or balcony is greater than 1 ft (30cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
above opening
3 ft (91 cm) above if within
10 ft (3m) horizontally
7 ft (2.13m)
*12 in. (30 cm) TT
3 ft (91 cm)
6 ft (1.83m)
7 ft (2.13m) t
In addition, the heater shall be installed such that the
gas ignition system components are protected from
water (dripping, spraying, rain, etc.) during appliance
operation or service (circulator replacement, control
replacement, etc.).
Clearances
Indoor Installations
Table E: Clearances – Indoor Installations
Fig. 7: Minimum Clearances from Combustible
Surfaces – Indoor Installations
When installed according to the listed minimum clearances from combustible construction, these heaters
can still be serviced without removing permanent
structural construction around the heater. However, for
ease of servicing, we recommend a clearance of at
least 24 in. in front, and at least 12 in. on the water
connection side. This will allow the heater to be serviced in its installed location without movement or
removal of the heater.
Service clearances less than the minimums may
require removal of the heater to service either the heat
exchanger or the burner tray. In either case, the heater
must be installed in a manner that will enable the
heater to be serviced without removing any structure
around the heater.
Outdoor Installations
These heaters are design-certified for outdoor installation. Heaters must not be installed under an overhang
that is less than 3 ft from the top of the heater. Three
sides must be open in the area under the overhang.
Roof water drainage must be diverted away from
heaters installed under overhangs.
Table F: Clearances – Outdoor Installations
These clearances are required when the outdoor
vent cap is used. If installing the heater outdoors
with a vent stack, the indoor clearances may be
utilized.
The combustion air intake hood MUST be used for
outdoor installations. The hood is shipped loose and
installed on the side of the heater over the filter box at
the jobsite.
* DO NOT install on carpeting.
11
Heater
Side
Minimum Clearance
from Combustible
Surfaces
Floor*0”0”
Rear1”24”
Water Side12”24”
Other Side1”24”
Top1”1”
FrontOpen24”
Vent2”2”
Recommended
Service
Clearance
Heater
Side
Min. Clearance
from Combustible
Surfaces
Recommended
Service
Clearance
TOP VIEW
FRONT VIEW
Venting not shown for clarity. Heater must be vented
per instructions in this manual
Front Open 24”
Rear 12” 24”
Water Side 36” 36”
Other Side 36” 36”
Top Unobstructed 36”
Vent N/A N/A
three or four sheet metal screws (not supplied) equally distributed around the circumference of the duct. All
ducting should be self-supported. The filter housing is
not designed to support the air duct.
Conventional Combustion Air
Supply
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO per-
manent openings communicating directly with an
additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for a
room large in comparison (NFGC). The total input of all
gas utilization equipment installed in the combined
CAUTION:This type of installation is
recommended if damaging airborne contaminants
are or will be present in the heater area. See the
Appendix regarding air contamination.
Fig. 8: Minimum Clearances from Combustible
Surfaces – Outdoor Installations
Combustion and Ventilation Air
Indoor Units
The heater must be supplied with sufficient quantities
of non-contaminated air to support proper combustion
and equipment ventilation. Combustion air can be supplied via conventional means where combustion air is
drawn from the area immediately surrounding the
heater, or via direct vent, where combustion air is
drawn directly from outside. All installations must comply with the requirements of the NFGC (U.S.) and
B149 (Canada), and all local codes.
Reversing Air Filter
Follow these instructions to change the air duct connection from the left-hand side (standard) to the
right-hand side:
1. Remove the four screws and the dust cover from
the right-hand side of the heater.
2. Remove the four screws and the air filter bracket
from the left-hand side of the heater.
3. Reverse the components and reattach in the new
location, making sure that the air filter locking
bracket is on the bottom. (The air filter locking
bracket is reversible.)
Direct-Ducted Combustion Air
In certain applications it may be desirable to duct the
combustion air directly to the heater. This should be
done with PVC, CPVC or single-wall galvanized ducting. The duct will attach directly to the collar on the air
filter housing located on the side of the heater. The
ducting is attached to the air filter housing collar using
CAUTION:Combustion air must not be
contaminated by corrosive chemical fumes which
can damage the heater and void the warranty. (See
the Appendix.)
NOTE: It is recommended that the intake vent be
insulated to minimize sweating.
NOTE: Use of the heater in construction areas
where fine particulate matter, such as concrete or
dry-wall dust, is present may result in damage to the
heater that is not covered by the warranty. If
operated in a construction environment, a clean
source of combustion air must be provided directly to
the heater.
12
space shall be considered in making this determination. Each opening shall have a minimum free area of
1 in.
2
per 1,000 BTUH (2,225 mm2per kW) of the total
input rating of all gas utilization equipment in the confined space, but not less than 100 in.
2
(645 cm2). One
opening shall commence within 12 in. (305 mm) of the
top, and one opening shall commence within 12 in.
(305 mm) of the bottom of the enclosure. The minimum dimension of air openings shall be not less than
3 in. (76 mm) in any direction.
All Air from Outdoors
The confined space shall communicate with the outdoors in accordance with one of the methods below.
The minimum dimension of air openings shall not be
less than 3 in. (76 mm) in any direction. Where ducts
are used, they shall be of the same cross-sectional
area as the net free area of the openings to which they
connect.
1. Two permanent openings, one commencing
within 12 in. (305 mm) of the top, and one commencing within 12 in. (305 mm) of the bottom of
the enclosure, shall be provided. The openings
shall communicate directly, or by ducts, with the
outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
a. Where directly communicating with the out-
doors or where communicating to the
outdoors through vertical ducts, each opening
shall have a minimum free area of 1 in.
2
per
4,000 BTUH (550 mm2per kW) of total input
rating of all equipment in the enclosure.
b. Where communicating with the outdoors
through horizontal ducts, each opening shall
have a minimum free area of 1 in.
2
per 2,000
BTUH (1,100 mm2per kW) of total input rating of all equipment in the enclosure.
2. One permanent opening, commencing within 12
in. (305 mm) of the top of the enclosure, shall be
permitted where the equipment has clearances of
at least 1 in. (25 mm) from the sides and back and
6 in. (152 mm) from the front of the appliance. The
opening shall directly communicate with the outdoors or shall communicate through a vertical or
horizontal duct to the outdoors or spaces that
freely communicate with the outdoors, and shall
have a minimum free area of:
a. 1 in.
2
per 3,000 BTUH (740 mm2per kW) of
the total input rating of all equipment located in
the enclosure, and
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use one permanent opening
method if the equipment room is under negative
pressure conditions or the equipment is common
vented with other gas-fired appliances.
1. Ventilation of the space occupied by the heater
shall be provided by an opening(s) for ventilation
air at the highest practical point communicating
with the outdoors. The total cross-sectional area of
such an opening(s) shall be at least 10% of the
area required in 2. and 3. (below), but in no case
shall the cross-sectional area be less than 10 in.
2
(65 cm2).
2. For heaters using a barometric damper in the vent
system there shall be a permanent air supply
opening(s) having a cross section area of not less
than 1 in.
2
per 7,000 BTUH (320 mm2per kW) up
to and including 1 million BTUH, plus 1 in.
2
per
14,000 BTUH (160 mm
2
per kW) in excess of 1
million BTUH. This opening(s) shall be either
located at or ducted to a point not more than 18 in.
(450 mm) nor less than 6 in. (152 mm) above the
floor level. The duct can also “goose neck” through
the roof. The duct is preferred to be straight down
and terminated 18 in. (450 mm) from the floor, but
not near piping. This air supply opening requirement shall be in addition to the air opening for
ventilation air required in 1. (above).
3. For heaters not using a barometric damper in the
vent system, and when air supply is provided by
natural air flow from outdoors for a power burner
and there is no draft regulator, drafthood or similar
flue gas dilution device installed in the same
space, in addition to the opening for ventilation air
required in 1., there shall be a permanent air supply opening(s) having a total cross-sectional area
CAUTION: All combustion air must be drawn from
the air outside of the building; the mechanical equipment room must communicate directly with the
outdoors.
Canadian Installations
WARNING: Care must be taken to ensure that the
equipment room is not under negative pressure
conditions or that the equipment is not commonvented with other gas-fired appliances.
13
5. Remove all plumbing fittings to the header. This
will include both inlet and outlet water pipe unions
and the pressure relief valve and drain piping.
6. Remove limits, control bulbs and/or thermocouples.
7. Remove the six (or 8) flange nuts and the in/out
header from the left-hand side.
8. Remove the six (or 8) flange nuts and the return
header from the right-hand side.
9. Remove the header stud bolts from each tube
sheet.
10. Reverse the headers and stud bolts to the new
location.
11. Install NEW red beveled O-rings flush against both
tube sheets with the bevel facing outward.
12. Push the header firmly against the O-rings. Install
and tighten the flange nuts onto the stud bolts until
finger tight.
13. Slowly tighten the flange nuts, starting from the
center nut (number 1) in Fig. 9 and working sequentially around the header as indicated. Torque
all nuts to 25 ft/lb. DO NOT OVER-TIGHTEN.
14. Re-route the capillary(s), wiring etc. to the new
location, adding thermal paste and shim to the
capillary well.
Relief Valve Piping
WARNING: Pressure relief valve discharge piping
must be piped near the floor and close to a drain to
eliminate the potential of severe burns. Do not pipe
to any area where freezing could occur. Refer to
local codes.
Hydrostatic Test
Unlike many types of heaters, this heater does not require hydrostatic testing prior to being placed in
operation. The heat exchanger has already been factory-tested and is rated for 160 psi operating pressure.
However, Raypak does recommend hydrostatic testing of the piping connections to the heater and the rest
of the system prior to operation. This is particularly
true for hydronic systems using expensive glycolbased anti-freeze. Raypak recommends conducting
of not less than 1 in.2for each 30,000 BTUH mm
2
per kW) of total rated input of the burner(s), and
the location of the opening(s) shall not interfere
with the intended purpose of the opening(s) for
ventilation air referred to in (1). This opening(s)
can be ducted to a point not more than 18 in. (450
mm) nor less than 6 in. (152 mm) above the floor
level. The duct can also “goose neck” through the
roof. The duct is preferred to be straight down 18
in. (450 mm) from the floor, but not near piping.
4. Refer to B149 Installation code for additional information.
Water Piping
General
The heater should be located so that any water leaks
will not cause damage to the adjacent area or structures.
Reversing Water Connections
Follow these instructions to change the water connections from the left-hand side (standard) to the
right-hand side.
1. Disconnect all electrical power from the heater (if
applicable).
2. Label all electrical connections and conduit lines.
This may include the flow switch, low water cut-off
probe and/or pump.
3. Disconnect or isolate the main gas pipe from the
heater (if applicable).
4. Remove both in/out and return header access
panels by removing all sheet metal screws.
CAUTION: This heater requires forced water
circulation when the burner is operating. See Table
G and Table H for minimum and maximum flow rates
and water pump selection. The pump must be
interlocked with the heater to prevent heater
operation without water circulation.
NOTE: Minimum pipe size for in/out connections is
2
1
⁄2 in (2 in. for 399B–899B). Verify proper flow rates
and ΔT as instructed in this manual.
14
Fig. 9: Torque Sequence
the hydrostatic test before connecting gas piping or
electrical supply.
Leaks must be repaired at once to prevent damage to
the heater. NEVER use petroleum-based stop-leak
compounds.
To perform hydrostatic test:
1. Connect fill water supply. With bleed valve open,
fill heater with water. When water flows from bleed
valve, shut off water. Close bleed valve. Carefully
fill the rest of the system, making sure to eliminate
any entrapped air by using high-point vents. Close
feed valve. Test at standard operating pressure for
at least 24 hours.
2. Make sure constant gauge pressure has been
maintained throughout test.
3. Check for leaks. Repair if found.
Cold Water Operation
A heater operated with an inlet temperature of less
than 105ºF (41ºC) must have a manual bypass or an
approved low-temperature operation system to prevent problems with condensation. A manual bypass,
shown in Fig. 15, must be piped into the system at the
time of installation. This piping is like a primary/secondary boiler installation with a bypass acting
as the secondary boiler piping. Raypak strongly recommends that thermometer(s) be placed into the
heater piping next to the in/out header to facilitate temperature adjustment. Inlet water temperatures below
105ºF (41ºC) can excessively cool the products of
combustion, resulting in condensation on the heat
exchanger and in the flue.
CAUTION: Damaging internal condensation may
occur if the heater inlet water temperature does not
exceed 105ºF (41ºC) within 7 minutes of start-up.
Failure to exceed 105ºF (41ºC) within 7 minutes may
result in the premature failure of the hot surface igniter, remote flame sensor, burners and heat exchanger.
It can cause operational problems, bad combustion,
sooting, flue gas spillage and reduced service life of
the vent system. The bypass allows part of the heater
discharge water to be mixed with the cooler heater
return water to increase the heater inlet temperature
above 105ºF (41ºC). This precautionary measure
should prevent the products of combustion from condensing in most installations. Warranty claims will be
denied when condensation occurs.
Cold water operation issues are applicable to both
cold water start and cold water run applications. Cold
water operation for 7 minutes or less on start-up is
acceptable. Where cold water starts will last longer
than 7 minutes or where cold water operation is continuous, provisions must be made to mix higher
temperature outlet water with the colder inlet water
and thereby raise the inlet temperature to at least
105ºF (41ºC) within the 7-minute time limit.
Cold Water Starts
Frequent (more than once a week) cold water starts,
wherein the inlet water temperature remains below
105ºF (41ºC) for more than 7 minutes, must have cold
water start protection. Known protection methods consist of mixing heated outlet water with the inlet water
with a bypass to raise the inlet to 105ºF (41ºC) or higher. Once the system is heated up and has return water
temperatures of 105ºF (41ºC) or higher, the mixing of
outlet water with inlet water is no longer needed and
the bypass can be shut off. If the bypass is not shut off
Models 399B–899B
Models 989B–2339B
15
Cold Water Run
Cold water run differs from cold water start in that the
system water entering the heater remains below 105ºF
(41ºC) continuously. Typically, this is the case in swimming pool heating and water source heat pump
applications as well as some others. If the system
water is kept in a narrow temperature range, a permanent manual bypass can be employed and manually
adjusted to achieve an inlet temperature of 105ºF
(41ºC) or higher. An injector pump arrangement may
also be utilized to keep the heater loop at or above
105ºF (41ºC). An injector pump approach has the
added value of being able to adjust to changes in the
system water coming back to the heater take-off.
Table G: Heater Rates of Flow and Pressure Drops
Notes: 1. Basis for minimum flow: Models 399–899, 20 gpm or 40°F ΔT. Models 989–2339, 30 gpm or 40°F ΔT.
Basis for maximum flow: Models 399–899, 90 gpm. Models 989–2339, 132 gpm.
2. Flow switch will not operate if flow is less than 20 gpm.
as the system heats up, the outlet temperature may
continue to climb and actuate the high limit, thereby
shutting down the heater. Thus an automatic valve
system, such as a three-way proportional valve or a
modulating two-way valve to control the bypass,
should be utilized.
Temperature & Pressure Gauge
The temperature and pressure gauge is factorymounted in the in/out header.
Hydronic Heating
Pump Selection
In order to ensure proper performance of your heater
system, you must install a correctly sized pump. Raypak recommends using a 20°F ΔT as design ΔT. (ΔT is
the temperature difference between the inlet and outlet water when the heater is firing at full rate). If a ΔT
of larger than 20°F is necessary, see Table G and
Table H for flow rate requirements.
Raypak recommends that a feedwater regulator be installed and set at 12 psi minimum pressure at the
highest point of the system. Install a check valve or
back flow device upstream of the regulator, with a
manual shut-off valve as required by local codes.
Piping
All high points should be vented. Purge valves and a
bypass valve should be installed. A heater installed
above radiation level must be provided with a low water cut-off device (sales order option F-10). The heater,
when used in connection with a refrigeration system,
must be installed so that the chilled medium is piped in
parallel with the heater with appropriate valves to prevent the chilled medium from entering the heater.
The piping system of a hot water heater connected to
heating coils located in air handling units where they
may be exposed to circulating refrigerated air, must be
equipped with flow control valves or other automatic
means to prevent gravity circulation of the heater
water during the cooling cycle. It is highly recommended that the piping be insulated.
Air-Separation/Expansion Tank
All heaters should be equipped with a properly sized
expansion tank and air separator fitting as shown in
Fig. 10.
Three-Way Valves
Valves designed to blend water temperatures or
reduce water circulation through the heater should not
be used. Raypak heaters are high-recovery, low-mass
Fig. 10: Air-Separation/Expansion Tank
heaters which are not subject to thermal shock.
Raypak offers a full line of electronic sequencers that
produce direct reset of heater water temperature.
(Refer to the Controls section of the Raypak Catalog.)
Domestic Hot Water
When designing the water piping system for domestic
hot water applications, water hardness should be considered. Table H indicates the suggested flow rates for
soft, medium and hard water. Water hardness is expressed in grains per gallon.
Fig. 11: Single Heater - Low-Temperature (Heat Pump)
Application with Primary/Secondary Piping
Fig. 12: Dual Heaters (Reverse/Return)
with Primary/Secondary Piping
17
*
18
Potable Water and Space Heating
1. All piping materials and components connected to
the water heater for the space heating application
shall be suitable for use with potable water.
2. Toxic chemicals, such as used for boiler treatment,
shall not be introduced into the potable water used
for space heating.
3. If the heater will be used to supply potable water,
it shall not be connected to any heating system or
components previously used with a non-potable
water heating appliance.
4. When the system requires water for space heating
at temperatures higher than 140°F, a means such
as a mixing valve shall be installed to temper the
water in order to reduce scald hazard potential.
CAUTION: When this heater is used for both
potable water and space heating, observe the
following to ensure proper operation.
Fig. 13: Single Domestic Hot Water Heater and Storage
Tank
Table H: Domestic Water Heater Flow Rate Requirements
ΔT = Temperature rise, °F.
ΔP = Pressure drop through heat exchanger, ft.
SHL = System head loss, ft. (System head loss based on heater and tank placed no more than 5 ft apart and equivalent length pipe/fittings as follows: 2 in. tube = 25 ft; 2 1/2 in. tube = 80 ft.
gpm = Gallons per minute, flow rate.)
MTS = Minimum tubing size.
*Must utilize optional cupro-nickel tubes.
**With Hard Water (16-25 grains per gallon), the operating control must be set no higher than 130F for scale free operation. For operating temperatures above 130F, a water softener must be utilized.
Model
No.
Soft (0–4 grains per gallon)Medium (5–15 grains per gallon)Hard* (16–25** grains per gallon)
Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve located outside the heater jacket. It is recommended
that a union be installed in the gas supply piping adjacent to the heater for servicing. A pounds-to-inches
DANGER: Make sure the gas on which the heater
will operate is the same type as specified on the
heater’s rating plate.
19
Gas Supply Connection
The heater must be isolated from the gas supply piping system by closing the manual shut-off valve during
any pressure testing of the gas supply piping system
at test pressures equal to or less than 1/2 psi (3.45
kPa). Relieve test pressure in the gas supply line prior
to reconnecting the heater and its manual shut-off
valve to the gas supply line. FAILURE TO FOLLOW
THIS PROCEDURE MAY DAMAGE THE GAS
VALVES. Over pressurized gas valves are not cov-
ered by warranty. The heater and its gas connections
shall be leak-tested before placing the appliance in
operation. Use soapy water for leak test. DO NOT use
an open flame.
CAUTION: The heater must be disconnected from
the gas supply during any pressure testing of the gas
supply system at test pressures in excess of 1/2 psi
(3.45 kPa).
Fig. 14: Gas Supply Connection
CAUTION: Do not use Teflon tape on gas line pipe
thread. A pipe compound rated for use with natural
and propane gases is recommended. Apply
sparingly only on male pipe ends, leaving the two
end threads bare.
Table I: Maximum Equivalent Pipe Length
Natural gas – 1,000 BTU per ft3, .60 specific gravity at 0.5 in. WC pressure drop
Propane gas – 2,500 BTU per ft
3
, 1.53 specific gravity at 0.6 in. WC pressure drop
Model
No.
3/4”1”1-1/4”1-1/2”2”2-1/2”3”4”
NPNPNPNPNPNPNPNP
399B152560100260250
499B65150130360500
649B4510095250340
749B358075180260600
899B204545110150360400
989B120300300
1259B75180170325560
1529B50120125250400
1799B40100100225340
1999B308075175260
2069B308075175260
2339B205555135160400600
regulator must be installed to reduce the gas supply
pressure to a maximum of 10.5 in. WC for natural gas
and 13.0 in. WC for propane gas. The regulator should
be placed a minimum distance of 10 times the pipe
diameter up-stream of the heater gas controls. Refer
to Table I for maximum pipe lengths.
9. Install a coupling, nipple, union and sediment trap
onto the right-hand end of the main gas line and
then install the gas line, making sure that a manual shut-off valve has been installed within 10 ft of
the heater.
10. Replace the left and right front panels on the
heater.
Gas Supply Pressure
A minimum of 5.0 in. WC and a maximum of 10.5 in.
WC upstream gas pressure is required under load and
no-load conditions for natural gas. A minimum of 11.0
in. WC and a maximum of 13.0 in. WC is required for
propane gas. The gas pressure regulator(s) supplied
on the heater is for low-pressure service. If upstream
pressure exceeds 14.0 in. WC, an intermediate gas
Fig. 15: Gas Valves
CAUTION: Support gas supply piping with
hangers, not by the heater or its accessories. Make
sure the gas piping is protected from physical
damage and freezing, where required.
Reversing Gas Supply Connection
Reversing the standard fuel connection from the lefthand to the right-hand side is a simple field operation.
1. Disconnect all electrical power from the heater (if
applicable).
2. Disconnect the main gas pipe from the heater (if
applicable).
3. Remove the left and right front panels from the
heater.
4. Locate the main gas line that traverses across the
heater above the manifold risers.
5. Remove the pipe cap from the right-hand end of
the main gas line.
6. Reinstall the pipe cap on the left-hand end of the
main gas line.
7. Remove plastic cap from the right-hand side panel
and reinstall into the standard main gas opening
located on the left-hand side of the heater.
8. Remove the rubber grommet from the left-handside panel and reinstall into the standard main gas
opening, located on the right-hand side of the
heater.
pressure regulator, of the lockup type, must be
installed.
When connecting additional gas utilization equipment
to the gas piping system, the existing piping must be
checked to determine if it has adequate capacity for
the combined load.
The gas valve pressure regulator(s) on the heater are
nominally preset at 3.5 in. WC for natural gas, and
10.5 in. WC for propane gas. The pressure at the gas
valve outlet tap, measured with a manometer, while in
operation should be 3.5 ± 0.1 in. WC for natural gas
and 10.5 in. ± 0.1 in. WC for propane gas. If an adjustment is needed, remove the adjustment screw cover
and turn the adjustment screw clockwise to increase
pressure or counter-clockwise to lower pressure.
Models 399B–2339B
Models 989B–2339B
20
Adjustment
Electrical Power Connections
Installations must follow these codes:
•National Electrical Code and any other national,
state, provincial or local codes or regulations having jurisdiction.
•Safety wiring must be NEC Class 1.
•Heater must be electrically grounded as required
by the NEC.
•In Canada, CSA C22. 1 C.E.C. Part 1.
The heater is wired for 120 VAC, <12 amps. The voltage is indicated on the tie-in leads. Consult the wiring
diagram shipped with the heater in the instruction
packet. The remote tank control stat, thermostat, or
electronic heater control (as applicable) may be connected to the stage selector terminal (See wiring
diagram). 24 VAC is supplied to this connection
through the heater transformer. DO NOT attach anyvoltage to the stage selector terminals. Before
starting the heater check to ensure proper voltage to
the heater and pump.
Install a separate disconnect means for each load.
Use appropriately sized wire as defined by NEC, CSA
and/or local code. All primary wiring should be 125% of
minimum rating.
If any of the original wire as supplied with the heater
must be replaced, it must be replaced with 105°C wire
or its equivalent.
Field-Connected Controllers
It is strongly recommended that all individually-powered control modules and the heater should be
supplied from the same power source.
Check the Power Source
NOTE: Field-supplied isolation relays should be
installed when field-connected controllers are
mounted more than 50 equivalent feet (18 Ga) from
heater.
WARNING: Using a multi-meter, check the
following voltages at the terminal block inside the
unit. Make sure proper polarity is followed and house
ground is proven. (See Fig. 18.)
Fig. 16: Wiring Connections
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX
AB = 108 VAC Minimum, 132 VAC MAX
BC = <1 VAC Maximum
If the heater does not have a factory-wired stage controller, it is factory-wired in an on-off configuration with
other stage terminals jumpered.
To field-connect a stage controller, remove factoryinstalled jumpers and wire stage controller as shown in
Fig. 19–22.
Making the Electrical Connections
Refer to Fig. 16–22.
1. Verify that circuit breaker is properly sized by
referring to heater rating plate. A dedicated circuit
breaker should be provided.
2. Turn off all power to the heater. Verify that power
has been turned off by testing with a multi-meter
Fig. 17: Multi-meter
21
BLACK
CIRCUIT
BREAKER
WHITE
GREEN
GROUND
AB C
prior to working with any electrical connections or
components.
3. Observe proper wire colors while making electrical connections. Many electronic controls are
polarity sensitive. Components damaged by
improper electrical installation are not covered by
warranty.
4. Provide overload protection and a disconnect
means for equipment serviceability as required by
local and state code.
5. Install heater controls, thermostats, or building
management systems in accordance with the
applicable manufacturers’ instructions.
6. Conduit should not be used as the earth ground.
Field Wiring Connection
22
NOTE: A grounding electrode conductor shall be
used to connect the equipment grounding
conductors, the equipment enclosures, and the
grounded service conductor to the grounding
electrode.
Fig. 18: Wiring Location
DANGER: SHOCK HAZARD
Make sure electrical power to the heater is disconnected to avoid potential serious injury or damage to
components.
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper
operation after servicing.
Fig. 19: On-Off Wiring Connections
23
Fig. 20: 2-Stage Wiring Connections
Fig. 21: 3-Stage Wiring Connections
Fig. 22: 4-Stage Wiring Connection
Consult the wiring diagram shipped with the heater in
the instruction packet or at the end of this section. The
stage-selector terminals are for the remote tank control through the heater’s 24 VAC transformer. DO NOT
attach any voltage to the stage-selector terminals.
Before starting the heater, check to ensure proper voltage to the heater and pump.
24
Fig. 23: 2-Stage Tankstat
Fig. 24: Single-Stage Tankstat
Installer action is required to electrically enable your
heater to operate after making the power connections.
You must make a closed contact connection on Stage
1 connector of the Central Point Wiring (CPW) board
for temperature control connections. This will be done
based on the controller option selected with your
heater order.
1. For Closed-Loop Water-Source Heat Pump applications with fixed bypass, your heater should be
configured to operate in an on-off firing mode. This
means that you will connect a single-pole control
to stage one of the CPW board. Then jumper the
remaining firing stages. For example, if your
heater is a Model 1529B, you will jumper stages
two, three and four. Then your heater will either be
on at full fire, or it will be off.
2. For 2-stage controller connections, connect each
stage of the control to the corresponding stage of
the CPW board in the heater, i.e., stage 1 of the
heater to stage 1 of the control; stage 2 of the
heater to stage 2 of the control, as shown in Fig.
22 and Fig. 25. Set the operating control to the
set-point at which you want the heater to maintain.
Ensure that the sensing bulb of the control is at the
point in the system that will best maintain the temperature you want. For example, when you are
heating a tank of water, you want the operating
control sensor bulb in the tank.
NOTE: If any of the original wire supplied with the
heater must be replaced, it must be replaced with
similar sized 105°C wire or its equivalent.
3. For single-stage controller connections, attach the
stage 1 connections on heater 1 to the tankstat per
Fig. 26.
Heater must be electrically grounded in accordance
with the NEC, and CSA C22.1 C.E.C. Part 1 in
Canada.
2-STAGE
TANKSTAT
SINGLE
STAGE
TANKSTAT
STAGE 1
CONNECTION
STAGE 1
CONNECTION
ATTACH STAGE 1 CONNECTIONS ON HEATER
TO STAGE 1 CONNECTION ON TANKSTAT.
ATTACH STAGE 2 CONNECTIONS OR
STAGE 1 CONNECTION OF HEATER 2
TO STAGE 2 CONNECTIONON TANKSTAT
AS SHOWN IN THE DIAGRAM.
STAGE 2 CONNECTION OR
STAGE 1 CONNECTION
OF HEATER 2
ATTACH STAGE 1 CONNECTIONS
ON HEATER TO THE SINGLE STAGE
TANKSTAT AS SHOWN IN THE DIAGRAM ABOVE.
25
Venting
General
Flue Exhaust Tee
An optional Flue Exhaust Tee is available to facilitate
horizontal venting. Any reference to horizontal venting
that exits the back of the heater requires this tee. Refer
to Table J for the appropriate kit for your model.
CAUTION: Proper installation of flue venting is critical for the safe and efficient operation of the heater.
Table J: Flue Exhaust Tee Kits
ModelDiameterOrder Number
399B–499B6”011839
649B, 749B,
899B
8”011840
989B10”011841
1259B, 1529B12”011842
1799B, 1999B,
2069B
14”011843
2339B16”011844
Category IV – A heater which operates with a positive
vent pressure and with a vent gas temperature that
may cause excessive condensate production in the
vent.
See Table K for appliance category requirements.
Support of Vent Stack
The weight of the vent stack or chimney must not rest
on the heater vent connection. Support must be provided in compliance with applicable codes. The vent
should also be installed to maintain proper clearances
from combustible materials.
Barometric Damper
A barometric damper may be required when vent
heights exceed 25 feet or when the draft is greater
than -0.08 in. WC. In these installations, a barometric
damper (single or double acting) is recommended.
The damper should be installed NO CLOSER than 18
in. from the discharge of the unit and no closer than 18
in. from a combustible ceiling. The damper can be
installed in horizontal or vertical runs of vent pipe as
necessary. Installation in a bull-head tee is acceptable
as shown in the NFGC.
The weights on the damper should be adjusted per the
damper manufacturer’s instructions for proper operation.
Appliance Categories
Heaters are divided into four categories based on the
pressure produced in the exhaust and the likelihood of
condensate production in the vent.
Category I – A heater which operates with a non-positive vent static pressure and with a vent gas
temperature that avoids excessive condensate production in the vent.
Category II – A heater which operates with a non-positive vent static pressure and with a vent gas
temperature that may cause excessive condensate
production in the vent.
Category III – A heater which operates with a positive
vent pressure and with a vent gas temperature that
avoids excessive condensate production in the vent.
NOTE: For additional information on appliance
categorization, see appropriate ANSI Z21 Standard
and the NFGC (U.S.), or B149 (Canada), or
applicable provisions of local building codes.
CAUTION: When condensate traps are installed,
condensate must be routed to an appropriate
container for neutralization before disposal, as
required by local codes.
WARNING: Contact the manufacturer of the vent
material if there is any question about the appliance
categorization and suitability of a vent material for
application on a Category III or IV vent system.
Using improper venting materials can result in
personal injury, death or property damage.
NOTE: During winter months check the vent cap
and make sure no blockage occurs from build-up of
snow or ice.
8. Locate and guard vent termination to prevent accidental contact by people or pets.
9. DO NOT terminate vent in window well, stairwell,
alcove, courtyard or other recessed area.
10. DO NOT terminate above any door, window, or
gravity air intake. Condensate can freeze, causing
ice formations.
11. Locate or guard vent to prevent condensate from
damaging exterior finishes. Use a rust-resistant
sheet metal backing plate against brick or masonry surfaces.
12. DO NOT extend exposed vent pipe outside of
building. Condensate could freeze and block vent
pipe.
U.S. Installations
Refer to the latest edition of the National Fuel Gas
Code.
Vent termination requirements are as follows:
1. Vent must terminate at least 4 ft below, 4 ft horizontally from or 1 ft above any door, window or
gravity air inlet to the building.
2. The vent must not be less than 7 ft above grade
when located adjacent to public walkways.
3. Terminate vent at least 3 ft above any forced air
inlet located within 10 ft.
4. Vent must terminate at least 4 ft horizontally, and
in no case above or below unless 4 ft horizontal
distance is maintained, from electric meters, gas
meters, regulators, and relief equipment.
Use insulated vent pipe spacers where the vent passes through combustible roofs and walls.
Vent Terminal Location
1. Condensate can freeze on the vent cap. Frozen
condensate on the vent cap can result in a blocked
flue condition.
2. Give special attention to the location of the vent
termination to avoid possibility of property damage or personal injury.
3. Gases may form a white vapor plume in winter.
The plume could obstruct a window view if the termination is installed near windows.
4. Prevailing winds, in combination with below-freezing temperatures, can cause freezing of
condensate and water/ice build-up on buildings,
plants or roofs.
5. The bottom of the vent terminal and the air intake
shall be located at least 12 in. above grade, including normal snow line.
6. Un-insulated single-wall metal vent pipe shall not
be used outdoors in cold climates for venting gasfired equipment.
7. Through-the-wall vents for Category II and IV
appliances and non-categorized condensing appliances shall not terminate over public walkways or
over an area where condensate or vapor could
create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or
other equipment. Where local experience indicates that condensate is a problem with Category
I and III appliances, this provision shall also apply.
Table K: Venting Category Requirements
26
Combustion
Air Supply
Exhaust
Configuration
Heater Venting
Category
Certified
Materials
Combustion Air
Inlet Material
Vertical Natural
From Inside Building
From Outside Building
Draft Venting
Horizontal Through-
the-Wall Venting
Vertical Natural
Draft Venting
Horizontal Through-
the-Wall Venting
I “B” Vent
III
I “B” Vent
III
Stainless Steel
(Gas Tight)
Galvanized Steel
Stainless Steel
(Gas Tight)
PVC
ABS
CPVC
Canadian Installations
Refer to latest edition of B149 Installation code.
A vent shall not terminate:
1. Directly above a paved sidewalk or driveway
which is located between two single-family dwellings and serves both dwellings.
2. Less than 7 ft (2.13 m) above a paved sidewalk or
paved driveway located on public property.
3. Within 6 ft (1.8 m) of a mechanical air supply inlet
to any building.
4. Above a meter/regulator assembly within 3 ft (915
mm) horizontally of the vertical centre-line of the
regulator.
5. Within 6 ft (1.8 m) of any gas service regulator
vent outlet.
6. Less than 1 ft (305 mm) above grade level.
7. Within the 3 ft (915 mm) of a window or door which
can be opened in any building, any non-mechanical air supply inlet to any building or the
combustion air inlet of any other appliance.
8. Underneath a verandah, porch or deck, unless the
verandah, porch or deck is fully open on a minimum of two sides beneath the floor, and the
distance between the top of the vent termination
and the underside of the verandah, porch or deck
is greater than 1 ft (305 mm).
5. Terminate vent at least 6 ft away from adjacent
walls.
6. DO NOT terminate vent closer than 5 ft below roof
overhang.
7. The vent terminal requires a 12 in. vent terminal
clearance from the wall.
8. Terminate vent at least 1 ft above grade, including
normal snow line.
9. Multiple sidewall vent installations require a 4 ft
clearance between the ends of vent caps located
on the same horizontal plane.
Changing the Flue Outlet
Follow these instructions to change the flue connection from the standard top location to the rear of the
heater (with optional flue exhaust tee).
1. Disconnect all electrical power from the heater (if
applicable).
2. Disconnect or isolate the main gas pipe from the
heater (if applicable).
3. Remove the screws, gasket and dustcover from
the rear of the heater.
4. Remove the screws, stainless steel flue cover and
gasket from the branch side of the tee located in
the flue box at the rear of the heater.
5. Remove the screws, retaining ring and rain gasket
from top of heater.
6. Remove the screws, flue collar and gasket from
the run side of the tee located in the flue box on
top of the heater.
7. Reverse the components and reattach in the new
location.
8. Make sure that the stainless steel cover, now located on the run side of the tee, is sealed to avoid
any flue gas spillage.
Venting Installation Tips
Support piping:
•horizontal runs - at least every 5 ft
•vertical runs - use braces
•under or near elbows
CAUTION: The silicone vent gaskets must be properly reinstalled to prevent flue gas leakage. Replace
any torn or worn vent gaskets.
WARNING: Examine the venting system at least
once a year. Check all joints and vent pipe
connections for tightness, corrosion or deterioration.
27
Venting Configurations
For heaters connected to gas vents or chimneys, vent
installations shall be in accordance with the NFGC
(U.S.), or B149 (Canada), or applicable provisions of
local building codes.
Natural Draft Vertical Venting
(Category I)
Installation
Natural draft venting uses the natural buoyancy of the
heated flue products to create a thermal driving head
that expels the exhaust gases from the flue. The negative draft must be within the range of -.01 to -.08 in.
WC as measured 12 in. above the appliance flue outlet to ensure proper operation. Vent material must be
listed by a nationally recognized test agency.
28
Termination
The vent terminal should be vertical and should terminate outside the building at least 2 ft above the highest
point of the roof that is within 10 ft. The vent cap
should have a minimum clearance of 4 ft horizontally
from and in no case above or below (unless a 4 ft horizontal distance is maintained) electric meters, gas
meters, regulators and relief equipment. The distance
of the vent terminal from adjacent public walkways,
adjacent buildings, open windows and building openings must be consistent with the NFGC (U.S.) or B149
(Canada). Gas vents supported only by flashing and
extended above the roof more than 5 ft should be securely guyed or braced to withstand snow and wind
loads.
Common Venting System
Manifolds that connect more than one heater to a common chimney must be sized to handle the combined
CAUTION: A listed vent cap terminal, adequately
sized, must be used to evacuate the flue products
from the heaters.
The maximum and minimum venting length for Category I appliances shall be determined per the NFGC
(U.S.) or B149 (Canada).
The diameter of vent flue pipe should be sized according to the NFGC (U.S.) and B149 (Canada). The
minimum flue pipe diameter for conventional negative
draft venting using double-wall Type B vent is: 6 in. for
Models 399B and 499B, 8 in. for Models 649B, 749B
and 899B, 10 in. for Model 989B, 12 in. for Models
1259B and 1529B, 14 in. for Models 1799B, 1999B
and 2069B, and 16 in. for 2339B.
The connection from the appliance vent to the stack
must be as direct as possible and shall be the same diameter as, or larger than, the vent outlet. The
horizontal breaching of a vent must have an upward
slope of not less than 1/4 inch per linear foot from the
heater to the vent terminal. The horizontal portions of
the vent shall also be supported for the design and
weight of the material employed to maintain clearances and to prevent physical damage or separation
of joints.
NOTE: A vent adapter (field-supplied) must be used
to connect Type B vent to the unit.
Fig. 25: Natural Draft Vertical Venting
(Category I)
29
Table L: Category I Vertical Venting
* Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
When vertical height exceeds 25 ft, consult factory prior to installation.
** Subtract 10 ft per elbow. Max. 3 elbows.
Maximum combustion air duct length terminated at 100 equivalent ft.
load. Consult available guides for proper sizing of the
manifold and the chimney. At no time should the area
of the common vent be less than the area of the
largest heater exhaust outlet.
Common venting systems may be too large once an
existing unit is removed. At the time of removal of an
existing appliance, the following steps must be fol-lowed with each appliance remaining connected to the
common venting system placed in operation, while the
other appliances remaining connected to the common
venting system are not in operation.
WARNING: Vent connectors serving appliances
vented by natural draft shall not be connected into
any portion of mechanical draft systems operating
under a positive pressure.
CAUTION: Vent connectors for natural draft
venting systems must be Type B or better.
1. Seal any unused opening in the common venting
system.
2. Visually inspect the venting system for proper size
and horizontal pitch and verify there is no blockage, restriction, leakage, corrosion or other unsafe
condition.
3. Insofar as is practical, close all building doors and
windows and all doors between the space in which
the appliances remaining connected to the common venting system are located and other spaces
of the building. Turn on clothes dryers and any appliance not connected to the common vent
system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, at maximum
Model
No.
Certified
Venting
Material
Vent
Size
Vertical Venting
Height*
Combustion
Air
Intake Pipe
Material
Air Inlet Max. Length**
Min.Max.6”8”10”12”
399B
Category I
(Type B
Equivalent)
6”
5’25’
Galvanized
Steel,
PVC, ABS,
CPVC
100’
499B75’
100’
649B
8”40’749B
899B
989B10”
75’100’1259B
12”
1529B
1799B
14”
40’75’
1999B
2069B
2339B16”
speed. Do not operate summer exhaust fan. Close
fireplace dampers.
4. Place in operation the appliances being inspected.
Follow the manufacturer’s instructions for lighting
each appliance. Adjust thermostat so appliance
will operate continuously.
5. Check the pressure at a pressure tap located 12
in. above the bottom joint of the first vertical vent
pipe. Pressure should be anywhere between -0.01
and -0.08 in. WC.
6. After it has been determined that each appliance
remaining connected to the common venting system properly vents when tested as outlined above,
return doors, windows, exhaust fans, fireplace
dampers and other gas burning appliances to their
previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
conforms with the NFGC (U.S.) or B149 (Canada).
When re-sizing any portion of the common venting
system, the common venting system should be resized to approach the minimum size as
determined using the appropriate tables in the
NFGC (U.S.) or B149 (Canada).
The total length of the horizontal through-the-wall flue
system should not exceed 70 equivalent ft in length. If
horizontal run exceeds 70 equivalent ft, an appropriately sized extractor must be used. Each elbow used
is equal to 10 ft of straight pipe. This will allow installation in one of the four following arrangements:
•70’ of straight flue pipe
•60’ of straight flue pipe and one elbow
•50’ of straight flue pipe and two elbows
•40’ of straight pipe and three elbows
The vent cap is not considered in the overall length of
the venting system.
These installations utilize the heater-mounted blower
to vent the combustion products to the outdoors.
Combustion air is taken from inside the room and the
vent is installed horizontally through the wall to the outdoors. Adequate combustion and ventilation air must
be supplied to the equipment room in accordance with
the NFGC (U.S.) or B149 (Canada).
30
*
Table M: Category III Horizontal and Direct Venting
*Subtract 10 ft per elbow. Max. 3 elbows.
Maximum combustion air duct length terminated at 100 equivalent ft.
WARNING: No substitutions of flue pipe or vent
cap material are allowed. Such substitutions would
jeopardize the safety and health of inhabitants.
Model
No.
Certified
Venting
Material
Vent
Size
Maximum
Equivalent
Vent Length*
Combustion
Air
Intake Pipe
Material
Air Inlet Max. Length*
6”8”10”12”
399B
Category III
6”
70’Room Air
40’ Ducted
Combustion Air
Galvanized
Steel,
PVC, ABS,
CPVC
100’
499B75’
100’
649B
8”
40’
749B
899B30’80’
989B10”
75’100’1259B
12”
1529B
1799B
14”
40’75’
1999B
2069B
2339B16”
The vent must be installed to prevent flue gas leakage.
Care must be taken during assembly to ensure that all
joints are sealed properly and are airtight. The vent
must be installed to prevent the potential accumulation
of condensate in the vent pipes. It is required that:
1. The vent must be installed with a slight downward
slope of not more than 1/4 inch per foot of horizontal run to the vent terminal.
2. The vent must be insulated through the length of
the horizontal run.
For installations in extremely cold climate, it is required that:
1. The vent must be installed with a slight upward
slope of not more than 1/4 inch per foot of horizontal run to the vent terminal. In this case, an
approved condensate trap must be installed per
applicable codes.
2. The vent must be insulated through the length of
the horizontal run.
Termination
The flue direct vent cap MUST be mounted on the exterior of the building. The direct vent cap cannot be
installed in a well or below grade. The direct vent cap
must be installed at least 1 ft above ground level and
above normal snow levels. The Raypak-approved
stainless steel flue direct vent cap must be used (sales
order option D-15).
Use only the special gas vent pipes listed for use with
Category III gas burning heaters, such as the AL29-4C
stainless steel vents offered by Heat Fab Inc. (800772-0739), Protech System, Inc. (800-766-3473),
Z-Flex (800-654-5600) or American Metal Products
(800-423-4270). Pipe joints must be positively sealed.
Follow the vent manufacturer’s installation instructions
carefully.
31
Freeze Protection
When installing this heater in an outdoor location that
is susceptible to freezing, sales order option B-22
must be ordered. The B-22 option energizes the
heater pump at a preset temperature drop to circulate
water and reduces the possibility of freezing and damaging the heat exchanger or headers.
Controls
NOTE: Condensate can freeze on the vent cap.
Frozen condensate on the vent cap can result in a
blocked flue condition.
NOTE: The vent cap, flow switch cover and air
intake hood must be furnished by the heater
manufacturer in accordance with its listing (sales
order option D-11).
WARNING: Installation, adjustment and service of
heater controls, including timing of various operating
functions, must be performed by a qualified installer,
service agency or the gas supplier. Failure to do so
may result in control damage, heater malfunction,
property damage, personal injury, or death.
WARNING: Turn off the power to the heater before
installation, adjustment or service of the CPW board
or any heater controls. Failure to do so may result in
board damage, heater malfunction, property
damage, personal injury, or death.
CAUTION: This appliance has provisions to be
connected to more than one supply source. To
reduce the risk of electric shock, disconnect all such
connections before servicing.
CAUTION: Risk of electric shock: More than one
disconnect switch may be required to de-energize
the equipment before servicing.
1.Outdoor models must be installed outdoors and
must use the outdoor vent cap, flow switch cover
and air intake hood available from the manufacturer (sales order option D-11).
2.Periodically check venting system. The heater’s
venting areas must never be obstructed in any
way and minimum clearances must be observed
to prevent restriction of combustion and ventilation
air. Keep area clear and free of combustible and
flammable materials.
3.Do not locate adjacent to any window, door walkway, or gravity air intake. The vent must be
located a minimum of 4 ft horizontally from such
areas.
4.Install above grade level and above normal snow
levels.
5.Vent terminal must be at least 3 ft above any
forced air inlet located within 10 ft.
6.Adjacent brick or masonry surfaces must be protected with a rust-resistant sheet metal plate.
Outdoor Installation
Outdoor models are self-venting when installed with
the optional factory-supplied outdoor vent kit and require no additional vent piping. A special vent cap, flow
switch cover and air intake hood are provided in accordance with CSA requirements, which must be installed
directly on the heater. Correct clearances can be
found earlier in this section.
Care must be taken when locating the heater outdoors, because the flue gases discharged from the
vent cap can condense as they leave the cap.
Improper location can result in damage to adjacent
structures or building finish. For maximum efficiency
and safety, the following precautions must be
observed:
32
33
Fig. 27: Status LED Indicator Decal
Heater Sequence of Operation
Models 399B–899B
1. The black (hot) wire lead goes directly to the main
power switch. This black toggle switch is located
at the middle front of the control compartment.
2. When the main power switch is placed in the “ON”
position, 120 VAC is applied to the 120 VAC terminal block on the circuit board and the 120/24 VAC
transformer is powered.
3. 120 VAC is waiting at the N.O. contacts of the
pump delay relay.
4. Terminals L1 and F1 of the ignition module are
powered with 120VAC.
5. 120 VAC power is also applied to the control
power connector on the circuit board.
6. 120 VAC power is waiting at relay contacts K-3 to
energize the heater blower.
7. The 120/24 VAC transformer outputs 24 VAC.
8. 24 VAC is sent to power terminal L1 of the low
water cut-off board (optional).
9. 24 VAC is applied to the red LED safety shutdown
light on the front of the unit.
10. 24 VAC is applied to the alarm circuit (optional). If
the E-5 sales option (Alarm) is included a 5 second time delay relay will not allow the alarm to
sound unless the circuit stays energized for more
than 5 seconds.
11. Power is output from terminal J5-24V of the CPW
board to all of the safeties. All safeties are verified
to ensure that it is safe to operate the heater. The
safety components wired into the diagnostic board
are: Manual reset high limit, low water cut-off
(optional), blocked vent switch, low gas pressure
switch (optional), and high gas pressure switch
(optional).
12. Once all safeties have been verified to be closed a
24 VAC signal is sent to pin P3-16 of J-5 on the
CPW board.
13. 24 VAC power now leaves pin P3-16 of J-5 on the
CPW board and is sent to the auto-reset high limit
(optional). If closed the power now goes to terminal P1-4 of J-5 on the CPW board.
14. Power is applied to terminal 24V of the pump
delay relay to energize the timing circuit .
15. Relay K-1 (N.C.) will now be energized, and opens
the N.C. contacts to disable the alarm (optional)
and turn off the red safety shutdown light.
16. Pin P1-4 on the diagnostic board will now output a
24 VAC signal to pin 1 of the “standby switch”.
17. The “standby switch” (rocker switch) located at the
lower left front of the control compartment is now
Table N: Status LED Indicators
External Lights
LightColorIndication
Power OnGreen
24 VAC
switched on
Call For HeatAmber
Thermostat is
closed
Burner FiringBlue
Burner(s) are
firing
Service Req’dRed
Service
required
34
powered. If the switch is “ON” and there is no call
for heat (CFH), the heater is in standby mode.
18. After the standby switch is placed into the “ON”
position, a 24 VAC signal is sent to the green
power light on the front of the unit and the
“enable/disable” connection (normally jumpered).
19. 24 VAC switched power is applied to the 24VAC
terminal on the ignition module.
20. When the “enable/disable” contacts are closed,
the 24 VAC signal travels to pin 1 of the stage 1
connection and waits for a CFH.
21. When a CFH occurs, a 24 VAC signal is sent from
J-5 CFH on the CPW board to the amber CFH light
on the front of the unit.
22. Power is now sent to terminal TRIG of the pump
delay relay to energize it and close the contacts.
23. The heater pump is energized.
24. Upon sufficient flow from the heater pump, the
flow switch contact will close.
25. A 24 VAC signal is then sent to the “TH” terminal
located on the ignition module.
26. Once the 24 VAC “TH” signal is received, a 120
VAC signal is sent from F2 on the ignition module
to the 120 VAC pilot duty terminals, located at J-14
on the circuit board.
27. The 120 VAC signal continues to the coil of relay
K-3 (N.O.).
28. The 120 VAC signal continues to the 120 VAC
safety terminals located at J-13 on the circuit
board.
29. When the coil on relay K-3 (N.O.) is powered, the
relay contacts (K-3) close and energize the blower(s) from the J-8 connections on the CPW board.
30. After proper air pressure is received in the air
plenum, the air pressure switch(s) will close.
31. Power is applied to the optional equipment interlock connection (normally jumpered).
32. The 24 VAC signal is then sent to the 24 VAC safety connector.
33. 24 VAC is now sent to the pressure switch (P
Switch) terminal on the ignition module.
34. Once the pressure switch signal is received at the
ignition module, the hot surface igniter is energized by a 120 VAC signal from S-1 on the ignition
module. (The hot surface igniter must draw
greater than 3.2 amps while being energized or
the ignition module red LED will flash 4 times and
ignition lockout will occur after three tries).
35. Once the ignition module determines that the hot
surface igniter is operating properly, a 24 VAC signal is output from terminal “valve” of the module.
36. A 24 VAC signal is sent to gas valve 1.
37. The blue LED on the front of the unit is now illuminated.
38. The coil of relay K-2 (N.O.) is now energized with
the (K-2) contacts closing downstream of the
stage 2 and upstream of the stage 3 connections.
39. The gas coming through the burners should ignite
from the heat of the hot surface igniter and the
flame should carry over from one burner to the
other burners of stage 1. The remote sensor is
now trying to sense the flame. If the flame is not
sensed within 4 seconds, the ignition module will
shut down the gas valve and retry the hot surface
igniter. During ignition retry the heater must perform a 15-second pre-purge and an approximately
30-second igniter warm-up before opening gas
valve 1 again. The standard ignition module will
attempt ignition a maximum of three times prior to
ignition lockout.
40. After gas valve 1 opens and flame rectification is
received, time delay relay 1 (TD-1) is powered and
starts a 5-second countdown.
41. After the 5 second countdown from TD-1, 24 VAC
is waiting at pin 3 of the stage 2 connection on the
CPW board.
42. After closure of the stage 2 contacts Gas valve 2
in energized.
43. After a 5 second countdown from TD-2, 24 VAC is
waiting at pin 5 of the stage 3 connection on the
CPW board.
44. After closure of the stage 3 contacts Gas valve 2
is energized.
35
45. The Heater is now operating at full fire.
Models 989B–2339B
1. The black (hot) wire lead goes directly to the main
power switch. This black toggle switch is located
at the middle front of the control compartment.
2. When the main power switch is placed in the “ON”
position, 120 VAC is applied to the 120 VAC terminal block on the circuit board and the 120/24 VAC
transformer is powered.
3. 120 VAC is waiting at the N.O. contacts of the
pump delay relay.
4. Terminals L1 and F1 of the ignition module 1 are
powered with 120VAC.
5. 120 VAC power is also applied to the control
power connector on the circuit board.
6. Terminals L1 and F1 of the ignition module 2 are
powered with 120VAC (1529B-2349B only).
7. 120 VAC power is waiting at relay contacts K-4 to
energize the heater blowers.
8. The 120/24 VAC transformer outputs 24 VAC.
9. 24 VAC is sent to power terminal L1 of the low
water cut-off board (optional).
10. 24 VAC is applied to the red LED safety shutdown
light on the front of the unit.
11. 24 VAC is applied to the alarm circuit (optional). If
the E-5 sales option (Alarm) is included a 5 second time delay relay will not allow the alarm to
sound unless the circuit stays energized for more
than 5 seconds.
12. Power is output from terminal J5-24V of the CPW
board to all of the safeties. All safeties are verified
to ensure that it is safe to operate the heater. The
safety components wired into the diagnostic board
are: Manual reset high limit, low water cut-off
(optional), blocked vent switch, low gas pressure
switch, and high gas pressure switch(s) (optional).
13. Once all safeties have been verified to be closed a
24 VAC signal is sent to pin P3-16 of J-5 on the
CPW board.
14. 24 VAC power now leaves pin P3-16 of J-5 on the
CPW board and is sent to the auto-reset high limit
(optional). If closed the power now goes to terminal P1-4 of J-5 on the CPW board.
15. Power is applied to terminal 24V of the pump
delay relay to energize the timing circuit.
16. Relay K-1 (N.C.) will now be energized, and opens
the N.C. contacts to disable the alarm (optional)
and turn off the red safety shutdown light.
17. Terminal J4-24 on the CPW board will now output
a 24 VAC signal to pin 1 of the “standby switch”.
18. The “standby switch” (rocker switch) located at the
lower left front of the control compartment is now
powered. If the switch is “ON” and there is no call
for heat (CFH), the heater is in standby mode.
19. The “standby switch” (rocker switch) located at the
lower left front of the control compartment is now
powered. If the switch is “ON” and there is no call
for heat (CFH), the heater is in standby mode.
20. Power is applied to the coil of K-3. (If an ignition
lockout occurs, ignition module 1 closes contacts
allowing the 24VAC from K-3 to go to ground and
closes the contacts to allow the unit to fire at stage
3.)
21. After the standby switch is placed into the “ON”
position, a 24 VAC signal is sent to the
“enable/disable” connection (normally jumpered).
22. 24 VAC switched power is applied to the 24VAC
terminals on ignition modules 1 and 2.
23. When the “enable/disable” contacts are closed,
the 24 VAC signal travels to pin 1 of the stage 1
connection and waits for a CFH.
24. Power is now sent to terminal TRIG of the pump
delay relay to energize it.
25. The heater pump is energized.
26. Upon sufficient flow from the heater pump, the
flow switch contact will close.
27. A 24 VAC signal is now sent to the “TH” terminal
located on ignition module 1 and to the N.O. contacts of K-2 and K-3.
28. Once the 24 VAC “TH” signal is received, a 120
VAC signal is sent from F2 on ignition module 1 to
36
the 120 VAC pilot duty terminals, located at J-14
on the circuit board.
29. The 120 VAC signal continues to the coil of relay
K-4 (N.O.).
30. The 120 VAC signal continues to the 120 VAC
safety terminals located at J-13 on the circuit
board.
31. When the coil on relay K-4 (N.O.) is powered, the
relay contacts (K-4) close and energize the blowers from the J-8 connections on the CPW board.
32. After proper air pressure is received in the air
plenum, the air pressure switches will close.
33. Power is applied to the optional equipment interlock connection (normally jumpered).
34. The 24 VAC signal is then sent to the 24 VAC safety connector.
35. 24 VAC is now sent to the pressure switch (P
Switch) terminal on the ignition modules.
36. Once the pressure switch signals are received at
both ignition modules, hot surface igniter 1 is energized by a 120 VAC signal from S-1 on ignition
module 1. (The hot surface igniter must draw
greater than 3.2 amps while being energized or
ignition lockout will occur after three tries.)
37. Once ignition module 1 determines that hot surface igniter 1 has heated up and operating
properly, a 24 VAC signal is output from terminal
“valve” on module 1.
38. 24 VAC signal is sent to gas valve 1.
39. The blue LED on the front of the unit is now illuminated.
40. The coil of relay K-2 (N.O.) is now energized with
the (K-2) contacts closing downstream of the
stage 2 connections and upstream of the stage 3
connections.
41. The gas coming through the burners should ignite
from the heat of hot surface igniter 1 and the flame
should carry over from one burner to the other
burners of stage 1. The remote sensor is now trying to sense the flame. If the flame is not sensed
within 4 seconds, the ignition module will shut
down the gas valve and retry the hot surface igniter. During ignition retry the heater must perform a
15-second pre-purge and an approximately 30second igniter warm-up before opening gas valve
1 again. The standard ignition module will attempt
ignition a maximum of three times prior to ignition
lockout.
42. After gas valve 1 opens and flame rectification is
received, time delay relay 1 (TD-1) is powered and
starts a 5-second countdown.
43. After the 5 second countdown from TD-1, the contacts close time delay relay 2 receives 24 VAC.
44. After 5 seconds gas valve 1a is now energized
allowing the remainder of stage 1 to fire.
45. After the 5-second countdown from TD-2 the internal contacts close allowing 24 VAC to sit at pin 3
of the stage 2 connection on the CPW board.
46. The temperature controller closes the stage 2 contacts and gas valve 2 in energized.
47. The temperature controller closes the stage 3 contacts at J-3 on the CPW board.
48. 24 VAC signal is received at gas valve 3 (Model
1259B only).
Models 1529B–2339B Only
49. Power is applied to the “TH” terminal of ignition
module 2.
50. Once the “TH” signal is received at ignition module
2, hot surface igniter 2 is energized by a 120 VAC
signal from S-1 on ignition module 2. (The hot surface igniter must draw greater than 3.2 amps while
being energized or ignition lockout will occur after
three tries.)
51. Once the ignition module determines that the hot
surface igniter has heated up and operating properly, a 24 VAC signal is output from pin “valve” on
the module.
52. 24 VAC signal is received at gas valve 3.
53. The coil of relay K-5 (N.O.) is now energized with
the (K-5) contacts closing downstream of the
stage 4 connections.
54. Remote flame sensor 2 is trying to rectify flame.
55. Power is now applied to time delay relay 3 and the
contacts of TD-3 located upstream of the stage 4
37
The optional single-try ignition module will lock out
after failing to light one time. To reset it, press and
release the small, recessed black push button located
inside of the cut-out on the lower right-hand corner of
the ignition module case (see Fig. 28). Turning off the
power to the heater WILL NOT reset the ignition module.
High Limit (Manual Reset)
The heater is equipped with a manual reset high limit
temperature device. Push the reset button and adjust
the setting to 40 - 50°F above desired operating temperature.
Flow Switch
This dual-purpose control, mounted and wired in
series with the main gas valve, shuts off heater in case
of pump failure or low water flow.
Operating Control
The heater may be equipped with different types of
operating controls. Consult the individual control data
Fig. 29: High Limit (Manual Reset)
Fig. 30: Flow Switch
Ignition Module
When additional heat is needed, the combustion air
blower starts to purge air from the combustion chamber for about 15 seconds. On proof-of-air flow, the airproving switch closes and the igniter is energized. To
ensure safe operation, the gas valve cannot open until
the igniter is verified. The main burner is automatically
lit when the device is powered and pre-purged. The
heater performs its own safety check and opens the
main valve only after the igniter is proven to be capable of ignition.
Fig. 28: Ignition Module
Table O: Ignition Module Diagnostic LED Codes
connection close after 5 seconds.
56. The stage 4 temperature controller contacts close.
57. Power is sent to gas valve 4.
58. The heater is now operating at full fire.
The standard ignition module will attempt to light three
times before locking out. To reset it, turn off power to
the heater, wait 30 seconds and re-apply power.
Reset button
on 1-try
module
Code
Condition
On
Off
1 Flash
2 Flashes
3 FlashesIgnition lockout
4 FlashesLow igniter current
5 Flashes
6 Flashes
flashing normal on start-up
Low 24 VAC, check control
System OK;
No faults present
Possible control fault;
Check power
Low air pressure, brief
Flame in combustion
chamber; No call for heat
supply voltage
Internal fault;
Replace module
Fig. 31: Operating Control
Low Water Cut-Off (Optional)
The low water cut-off automatically shuts down the
burner whenever water level drops below the level of
the sensing probe. A 5-second time delay prevents
premature lockout due to temporary conditions such
as power fluctuations or air pockets.
Fig. 32: Low Water Cut-Off
High and Low Gas Pressure Switches
The low gas pressure switch (standard on models
989B–2339B, optional on models 399B–899B) connection mounts upstream of the gas valve to ensure
that sufficient gas pressure is present for proper regulator performance. The low gas pressure switch
automatically shuts down the heater if gas supply
drops below the factory setting of 5.0 in. WC for natural gas, and 10.0 in. WC for propane gas.
The high gas pressure switch (optional) connection
mounts down-stream of the stage-1 gas valve. If the
gas pressure regulator fails, the high gas pressure
sheets supplied with your heater paperwork. See the
General Safety Section for safety precautions concerning domestic hot water applications.
Fig. 33: High/Low Gas Pressure Switch
Fig. 34: Fan-Proving Switch
Fig. 35: Blocked Vent Switch
switch automatically shuts down the burner. The high
gas pressure switch automatically shuts down the
heater if gas manifold pressure rises above the recommended setting of 5.0 in. WC for natural gas, and 11.5
in. WC for propane gas.
38
NOTE: Some jurisdictions may require two high gas
pressure switches on models 1529B–2339B due to
two ignition modules.
NOTE: The wiring diagrams in this manual show all
standard options. Refer to the large wiring diagram
provided with your heater for options installed on
your specific unit(s).
Wiring Diagram - Models 399B–1259B
39
Wiring Diagram - Models 1529B–2339B
40
START-UP
Pre Start-up
Filling System (Heating Boilers)
Fill system with water. Purge all air from the system.
Lower system pressure. Open valves for normal system operation, and fill system through feed pressure.
Manually open air vent on the compression tank until
water appears, then close vent.
Air Purge (Domestic Hot Water
Heaters)
Purge all air from system before lighting heater. This
can be normally accomplished by opening a downstream valve.
Venting System Inspection
1. Check all vent pipe connections and flue pipe material.
2. Make sure vent terminations are installed per code
and are clear of all debris or blockage.
For Your Safety
This appliance has a hot surface igniter. It is equipped
with an ignition device which automatically lights the
burners. Do not try to light the burners by hand.
BEFORE OPERATING, smell all around the appliance
area for gas. Be sure to smell near the floor because
some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any
telephone in your building.
•Immediately call your gas supplier from a neighbor’s telephone. Follow the gas supplier’s
instructions.
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
•If you cannot reach your gas supplier, call the fire
department.
•Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not turn
by hand, do not try to repair it, call a qualified service technician. Forced or attempted repair may
result in a fire or explosion.
•Do not use this appliance if any part has been
under water, immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
which has been under water.
•Check around unit for debris and remove combustible products, i.e. gasoline, etc.
Pre Start-up Check
1. Verify heater is filled with water.
2. Check system piping for leaks. If found, repair
immediately.
3. Vent air from system. Air in system can interfere
with water circulation.
With multi-meter at incoming power, check voltage
between:
Hot - Common (≈120 VAC)
Hot - Ground (≈120 VAC)
Common - Ground (< 1 VAC)
Attach Manometers to Measure Pressures
1. Turn off main gas valve.
2. Attach 24” scale manometer to the first main gas
shut-off valve pressure tapping.
3. Attach (1) 12” scale manometer to the outlet side
of the second main gas shut-off valve pressure
tapping.
4. Attach (1) 12” scale manometer near the fan-proving switch. Pull black cap from air pressure switch
tee and connect the manometer. NOTE: Retain
caps for reinstallation later.
Check Gas Supply Pressure
1. Slowly turn on main gas shut-off valve.
2. Read the gas supply pressure from the manometer; minimum supply pressure for natural gas is 5.0
in. WC, recommended supply is 7.0 in. WC, minimum supply pressure for propane gas is 11.0 in.
WC (dynamic readings, all stages firing).
3. If the pressure is > 14.0 in. WC, turn off the valve.
4. Check if the service regulator is installed and/or
adjust the service regulator.
WARNING: Do not turn on gas at this time.
WARNING: If Common - Ground is > 1 VAC,
STOP: Contact electrician to correct ground failure.
Failure to do this may burn out 120V-24V
transformer, or may cause other safety control
damage or failure.
Start-Up
Blower Adjustment
1. Turn off power.
2. Unplug cap at pressure switches and connect manometer(s) to the tee.
3. Close all manual firing valves.
4. Turn power on.
5. Check manometers attached to fan pressure
switch. The reading should be 1.4 ± 0.1 in. WC for
propane gas and natural gas. If not, adjust the air
shutter on the blowers to attain the correct value.
6. Turn power off.
7. Reconnect this cap.
Main Burner Adjustment
1. Turn off unit.
2. Open manual firing valves.
3. Turn on the unit, wait 15 seconds, and the igniter
should glow. Look into sight glass located at each
end of the heater to check igniter operation. Gas
valves should open in 45-60 seconds.
4. If burner does not light on first trial. It will retry, up
to three times.
5. Main burner ignition: Check manifold gas pressure
at gas valve outlet pressure tap. This should read
3.5 ± 0.1 in. WC for natural gas and 10.5 ± 0.1 in.
WC for propane gas.
6. If the pressure reading differs by more than ± 0.1
in. WC, remove screw cover from the gas pressure regulator and adjust main burner manifold
pressure. Replace the screw cover. Repeat steps
2 to 5 on other valves as necessary.
CAUTION: Special manifold and air settings may
be required. Verify rating plate and blower housing.
42
Safety Inspection
1. Check all thermostats and high limit settings.
2. During the following safety checks leave manometers hooked up, check and record.
3. If other gas-fired appliances in the room are on the
same gas main, check all pressures on the Delta
Limited with all other equipment running.
4. Check thermostats for ON-OFF operation.
5. Check high limits for ON-OFF operation.
6. While in operation, check flow switch operation.
7. Check the low gas pressure switch. (For proper
adjustment, use the attached manometers, if
available, to set pressure. The scales on the
switch are approximate only.) Low gas pressure
switch must be set at 5.0 in. WC for natural gas
and 10.0 in. WC for propane gas.
8. Make sure that the high gas pressure switch (optional) is set to 1.0 in. WC above manifold
pressure.
Follow-Up
Safety checks must be recorded as performed.
Turn heater on. After main burner ignition:
1. Check manometer for proper reading.
2. Cycle heater several times and re-check readings.
3. Remove all manometers and replace caps and
screws.
4. Replace all gas pressure caps.
5. Check for gas leaks one more time.
Pilot Turn-Down Test
The Delta Limited heaters, depending on their size,
have two to five burner sections. Each burner section
is supplied gas by two gas valves incorporated into a
single valve body. A maximum of three burner sections
may be controlled by a single hot surface ignition system. The middle of the three burner sections is ignited
directly with a hot surface ignition system.
The burner section that is ignited directly by the hot
surface ignition system serves as a supervised pilot to
light the burner sections on either side of it. The burner sections on either side of the supervised section
(pilot) are electrically interlocked with the supervised
ignition system so as they are not energized unless
flame is proven on the center section which is acting
as a pilot to light the right and left-hand sections.
The pilot turn-down test is conducted as follows:
1. Turn off manual valves on non-supervised burner
sections.
2. Turn on electrical power and adjust thermostat to
call for heat.
3. Wait for completion of ignition sequence to light
burner section being utilized as a pilot for those
turned off in step 1 above.
4. Gradually reduce manifold pressure (flame) on
supervised burner section by slowly closing manual gas valve. Watch for shut-down due to loss of
supervised flame signal as pressure is being reduced. Flame signal should be lost before
manifold pressure goes below 2.0 in. WC for natural gas and 6.0 in. WC for propane gas.
Leak Test Procedure: Dual-Seat Gas
Valves
Proper leak testing requires three pressure test points
in the gas train.
Test point A is upstream of the automatic gas valve. On
the first automatic valve, this is a bleedle valve. On the
other valves, this is a plugged port. The bleedle valve
on the first valve may be used for all the other valves
as well.
Test point B is a bleedle valve located between the two
automatic gas valve seats.
Test point C is located downstream of both automatic
gas valve seats and upstream of the manual valve. On
the manual valve, this is a bleedle valve. Identical
readings will be found at the plugged port labeled as
Alternate C.
Refer to Fig. 36. The numbers on the diagram refer to
the steps below:
These tests are to be conducted with the electrical
power to the heater turned off.
43
1. Manually close the downstream leak test valve.
2. Open test point A and connect a manometer to it.
Verify that there is gas pressure and that it is within the proper range (NOTE: must not exceed 14.0
in. WC).
3. Open test point B and connect a rubber tube to it.
Connect the other end of the tube to a manometer
and look for a build-up of pressure. Increasing
pressure indicates a leaking gas valve.
4. Next, close the upstream manual gas valve and
remove the manometer from test point A and from
test point B. Connect a rubber tube from test point
A to test point B and open the upstream manual
gas valve. Make sure that test points A & B have
been opened so as to allow gas to flow. This will
bring pressure to the second valve seat.
5. Open test point C and connect a second rubber
tube to it. Connect the other end of the tube to a
manometer and look for a build-up of pressure. Increasing pressure indicates a leaking gas valve.
6. Remove rubber tube and manometers. Close
each test point valve as the tubes are removed.
7. Connect a manometer to each test point (one at a
time) and look for a build-up of pressure. If a buildup of pressure is detected, check each test point
valve to see if it is tightly closed. If leak persists,
replace test point valve(s).
8. After no leakage has been verified at all valve
seats and test valves, open downstream leak tests
valve and restore electrical power to heater.
Fig. 36: Leak Test
This completes leak testing for a single Delta Limited
manifold riser. Repeat steps 1-8 for each riser.
Post Start-Up Check
Check off steps as completed:
1. Verify that the heater and heat distribution units or
storage tank are filled with water.
2. Confirm that the automatic air vent (if used) was
opened two full turns during the venting procedure.
3. Verify that air has been purged from the system.
4. Verify that air has been purged from the gas piping, and that the piping has been checked for
leaks.
5. Confirm that the proper start-up procedures were
followed.
6. Inspect burner to verify flame.
7. Test safety controls: If heater is equipped with a
low water cut-off or additional safety controls, test
for operation as outlined by manufacturer. Burner
should be operating and should go off when controls are tested. When safety devices are restored,
burners should re-ignite after pre-purge time
delay.
8. Test limit control: While burner is operating, move
indicator on high limit control below actual water
temperature. Burner should go off while blower
and circulator continue to operate. Raise setting
on limit control above water temperature and burner should re-ignite after pre-purge time delay.
9. Test ignition system safety device:
a. Turn on manual gas valve. Turn power on.
b. Set thermostat to call for heat.
c. When the heater is in operation, pull cap off of
tee in air switch hose. The burner should go
off immediately.
d. Wait 5 minutes.
e. Reattach cap on tee. Burner should re-ignite
after pre-purge time delay.
44
10. To restart system, follow lighting instructions in the
Operation section.
11. Check to see that the high limit control is set
above the design temperature requirements of the
system.
For multiple zones: Check to make sure the flow is
adjusted as required in each zone.
12. Check that the heater is cycled with the thermostat. Raise to the highest setting and verify that the
heater goes through the normal start-up cycle. Reduce to the lowest setting and verify that the
heater goes off.
13. Observe several operating cycles for proper operation.
14. Set the room thermostat or tankstat to desired
temperature.
15. Review all instructions shipped with this heater
with owner or maintenance person, return to envelope and give to owner or place the instructions
inside front panel on heater.
OPERATION
Lighting Instructions
1. Before lighting, make sure you have read all of the
safety information in this manual.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the appliance.
4. This appliance is equipped with an ignition device
which automatically lights the burner. Do not try to
light the burner by hand.
5. Remove upper front panel.
6. Turn on main manual gas valve.
7. Wait 5 minutes to clear out any gas. Then smell for
gas, especially near the floor. If you then smell
gas, STOP! Follow the steps in the safety information on the front cover of this manual. If you do not
smell gas, go to next step.
8. Turn on all electrical power to the appliance.
9. Set thermostat to desired setting. The appliance
will operate. The igniter will glow after the prepurge time delay (15 seconds). After igniter
reaches temperature (45 seconds) the main valve
will open. System will try for ignition three times. If
flame is not sensed, lockout will commence.
10. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance,” and call your
service technician or gas supplier.
11. Replace access panel.
12. If heater fails to start, verify the following:
a. There are no loose connections or that the
service switch is off.
b. High temperature limit switch is set above wa-
ter temperature.
c. Thermostat is set above room temperature.
d. Gas is on at the meter and the heater.
e. Incoming gas pressure to the gas valve is
NOT less than 5.0 in. WC for natural gas, 11.0
in. WC for propane gas.
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electrical power to the appliance if service is to be performed.
3. Remove upper front panels.
4. Turn off main manual gas valve.
5. Replace access panel.
45
TROUBLESHOOTING
jump
r
p
(
)
g
y
p
y
r
46
Does the power switch
provide power to the
Step 1
Step 2
Step 3
control panel?
YES
YES
Is there a call for heat?
YES
Do the combustion air
blowers come on?
Is enable/disable
NO
er intact (J1)?
NO
NO
NO
Reattach
Unit is in standby mode.
Is there 120VAC at J8
Connecto
on the CPW board?
YES
Check the switch
and/or line voltage
Replace ignition module
Check all safety limit
devices and voltage from
the transformer to J10 on
CPW board.
NO
NO
Does F2 on ignition module
have 120VAC?
YES
Step 4
Step 5
Step 6
YES
Is 24VAC at PS on
ignition module? Is
connecting plug
secure?
Does igniterprove?
YES
Is the flame
sensor signal to
the ignition
module greater
than 4 uA DC?
YES
Is 24VAC at present at TH (J3 & J12 on CPW
board and orange wire on ignition module)?
NO
YES
NO
Check Amp draw during
heat-up for 3.2 Amps or
reater.
NO
Is air pressure switch(s) and
J2 of CPW board (N.O.)
owered?
NO
Does air pressure switch(s)
have correct pressure?
1.4” W.C.
NO
YES
NO
Replace HSI
Are the gas valve
settings correct?
YES
NO
Check flow switch, all
connectors on CPW board
and controller.
Is there continuity from the
fan relay to fan(s)?
YES
YES
Replace air
ressure switch
Is air switch
bouncing?
NO
NO
YES
Check the fan relay. Is there
120VAC at K3 relay?
YES
Replace fan rela
Replace fan
Correct the air settings or
you may have to clean
burners, heat exchanger
and/or air filter.
YES
Readjust to 3.5” W.C.
gas.
Is the unit running?
NO
NO
Step 7
Is the unit running?
NO
Call our Technical Service Department
1-800-947-2975 Outside California
1-800-627-2975 Inside California
YES
Is static and dynamic inlet
manifold gas pressure correct?
Is downdraft present?
NO
The unit is oka
YES
Clean or replace flame senso
Replace gas valve
MAINTENANCE
Suggested Minimum
Maintenance Schedule
Regular service by a qualified service agency and
maintenance must be performed to ensure maximum
operating efficiency.
Maintenance as outlined below may be performed by
the owner.
Daily
1. Check that the area where the heater is installed
is free from combustible materials, gasoline, and
other flammable vapors and liquids.
2. Check for and remove any obstruction to the flow
of combustion or ventilation air to heater.
Monthly
1. Check for piping leaks around circulators, mixing
valves, relief valves, and other fittings. If found,
repair at once. DO NOT use petroleum-based
stop-leak compounds.
2. Visually inspect burner flame.
3. Visually inspect venting system for proper function, deterioration or leakage.
4. Check air vents for leakage.
Yearly (Beginning Of Each Heating
Season)
Schedule annual service call by qualified service
agency.
1. Visually check top of vent for soot. Call service
person to clean. Some sediment at bottom of vent
is normal.
2. Visually inspect venting system for proper function, deterioration or leakage.
3. Check that area is free from combustible materials, gasoline, and other flammable vapors and
liquids.
4. Check for and remove any obstruction to the flow
of combustion or ventilation air to heater.
5. Follow pre-start-up check in the Start-up section.
6. Visually inspect burner flame. It should be light
blue. Remove and visually inspect hot surface igniter and sensor for damage, cracking or debris
build-up.
7. Check operation of safety devices. Refer to manufacturers’ instructions.
8. Follow oil-lubricating instructions on circulator if
required. Over-oiling will damage circulator.
Water-lubricated circulators do not need oiling.
9. To avoid potential of severe burn, DO NOT REST
HANDS ON OR GRASP PIPES. Use a light touch;
return piping will heat up quickly.
10. Check blower and blower motor.
11. Check for piping leaks around circulators, relief
valves and other fittings. Repair, if found. DO NOT
use petroleum-based stop-leak.
12. Clean air filter.
Periodically
1. Check relief valve. Refer to manufacturer’s instructions on valve.
2. Test low water cut-off, if used. Refer to manufacturer’s instructions.
3. Clean screen and air filter in intake.
Preventive Maintenance
Schedule
The following is required procedure in CSD-1 states
and good practice for all Delta Limited installations.
Daily
1. Check gauges, monitors and indicators.
2. Check instrument and equipment settings. (See
“Post Start-Up Check” on page 44.)
3. Check burner flame. (Should see light blue flame).
47
Weekly
For low-pressure heaters, test low-water cut-off
device. (With at least one stage of the appliance on,
depress the low water cut-off test button, appliance
should shut-off and ignition fault light should come on.
Depress reset button to reset).
Monthly
1. Check flue, vent, stack, or outlet dampers.
2. Test fan air pressure. (See “Blower Adjustment” on
page 42.)
3. Test high and low gas pressure interlocks (if
equipped). (See “Safety Inspection” on page 43.)
Semi-Annually
1. Recalibrate all indicating and recording gauges.
2. Check flame failure detection system components.
(See “Pilot Turn-Down Test Procedure,” page 43.)
3. Check firing rate control by checking the manifold
pressure. (See “Main Burner Adjustment” on page
42.)
4. Check piping and wiring of all interlocks and shutoff valves.
Annually
1. Test flame failure detection system and pilot turndown. (See “Pilot Turn-Down Test Procedure,”
page 43.)
2. Test high limit and operating temperature. (See
“Post Start-Up Check,” page 44.)
3. Check flame sensors.
4. Conduct a combustion test at full fire. Carbon dioxide should be 7.5 to 8.5% at full fire for natural
gas, and between 9.2 to 9.8% for propane gas
(Carbon monoxide should be < 150 ppm).
5. Check coils for 60 cycle hum or buzz. Check for
leaks at all valve fittings using a soapy water solution. Test other operating parts of all safety shut-off
and control valves and increase or decrease settings (depending on the type of control) until the
safety circuit opens. Reset to original setting after
each device is tested.
6. Perform leakage test on gas valves. (See Fig. 36.)
7. Test air switch in accordance with manufacturer’s
instructions. (Turn panel switch to the “On” position until blower is proven, then turn the switch to
“Off”.
8. Inspect and clean burners as necessary.
As Required
1. Recondition or replace low water cut-off device (if
equipped).
2. Check drip leg and gas strainers.
3. Perform flame failure detection and pilot turndown tests.
4. Check igniter. (Resistance reading should be 4270 ohms at ambient temperature.)
5. Check flame signal strength. (Flame signal should
be greater than 1 microamp).
6. Test safety/safety relief valves in accordance with
ASME Heater and Pressure Vessel Code Sections
VI and VII.
48
APPENDIX
Inside Air Contamination
All heaters experience some condensation during
start-up. The condensate from flue gas is acidic.
Combustion air can be contaminated by certain vapors
in the air which raise the acidity of the condensate.
Higher acidity levels attack many materials including
stainless steel, which is commonly used in high efficiency systems. The heater can be supplied with
corrosion-resistant, non-metallic intake air vent material. You may, however, choose to use outside
combustion air for one or more of these reasons:
1. Installation is in an area containing contaminants
listed below which will induce acidic condensation.
2. You want to reduce infiltration into your building
through openings around windows and doors.
3. You are using AL29-4C stainless steel vent pipe,
which is more corrosion-resistant than standard
metallic vent pipe. In extremely contaminated areas, this may also experience deterioration.
Products causing contaminated combustion air:
•spray cans containing chloro/fluorocarbons
•permanent wave solutions
•chlorinated waxes/cleaners
•chlorine-based swimming pool chemicals
•calcium chloride used for thawing
•sodium chloride used for water softening
•refrigerant leaks
•paint or varnish removers
•hydrochloric acid/muriatic acid
•cements and glues
•antistatic fabric softeners used in clothes dryers
•chloride-type bleaches, detergents, and cleaning
solvents found in household laundry rooms
•adhesives used to fasten building products
•similar products
Areas where contaminated combustion air commonly
exists:
•dry cleaning/laundry areas
•metal fabrication plants
•beauty shops
•refrigeration repair shops
•photo processing plants
•auto body shops
•plastic manufacturing plants
•furniture refinishing areas and establishments
•new building construction
•remodeling areas
•open pit skimmers
Check for areas and products listed above before installing heater. If found, remove products permanently.
49
LIMITED PARTS WARRANTY
DELTA LIMITED – TYPES H AND WH
MODELS 399B–2339B
SCOPE
Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heater whic h are actually manufactured by Raypak will be free
from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this Wa rranty. Labor
charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this Warranty but a re the
owner’s responsibility.
HEAT EXCHANGER WARRANTY
Domestic Hot Water
Five (5) years fr om date of heater installation. Includes copper heat exchanger with bronze and cast iron waterways.
Ten (10) years fr om date of heater installation. Includes only cupro-nickel heat exchanger with bronze or cast iron waterways.
Space Heating (Closed Loop System)
Ten (10) years fr om date of heater installation. Includes both cupro-nickel and copper heat exchanger with bronze or cast iron waterways.
Thermal Shock Warranty
Twenty (20) years from date of heater installation against “Thermal Shock” (excluded, however, if caused by heater operation at large
changes exceeding 150°F between the water temperature at intake and heater temperature, or operating at heater temperatures exc eeding 230°F).
ANY OTHER PART MANUFACTURED BY RAYPAK
One (1) year warranty from date of heater installation, or eighteen (18) months from date of factory shipment based on Raypak’s records,
whichever comes first.
SATISFACTORY PROOF OF INSTALLATION DATE, SUCH AS INSTALLER INVOICE, IS REQUIRED. TH IS WARRANTY WILL BE
VOID IF THE HEATER RATING PLATE IS ALTERED OR REMOVED.
ADDITIONAL WARRANTY EXCLUSIONS
This warranty does not cover failures or malfunctions resulting from:
1. Failure to properly install, operat e or maintain the heater in accordance wit h our printed instructions provided;
2. Abuse, alteration, accident, fire, flood and the like;
3. Sediment or lime build-up, freezing, or other conditions causing inadequate water c irculation;
4. High velocity flow exceeding heater design rates;
5. Failure of connected systems devices, s uch as pump or controller;
6. Use of non-factory authorized accessories or other components in conjunction with the heater system;
7. Failing to eliminate air from, or replenish water in, the connected water system;
8. Chemic al contamination of combustion air or use of chemical additives to water.
PARTS REPLACEMENT
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if requested,
with transportation charges prepaid, and all applicable warranty conditions found satisfied. The replacement part will be warra nted for
only the unexpired portion of the or iginal warranty. Raypak makes no warranty whatsoever on parts not manufactur ed by it, but R aypak
will apply any such warranty as may be provided to it by the parts manufacturer.
TO MAKE WARRANTY CLAIM
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and descriptio n of the problem. The installer must then notify his Raypak distributor for instructions regarding the claim. If either is not available, co ntact Service
Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnar d, CA 93030 or call (805) 278- 5300. In all cases proper authorization must fir st be
received from Raypak before replacement of any part.
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY
This is the only warranty given by Raypak. No one is author ized to make any other warranties on Raypak’s behalf. THIS WARRA NTY IN
LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. RAYPAK’S SOLE LIABILITY AND THE SOLE REMEDY AGAINST
RAYPAK WITH RESPECT TO DEFECTIVE PARTS SHALL BE AS PROV IDED IN THIS WARRANTY. IT IS AGREED THAT RAYPAK
SHALL HAVE NO LIABILITY, WHETHER UNDER THIS WARRANTY, OR IN CONTRACT, TORT, NEGLIGENCE OR OTHERWISE,
FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGE, INCLUDING DAMAGE FROM WATER LEAKAGE. Some states
do not allow limitations on how long an implied warranty lasts, or for the exclusion of incident al or consequential damages. So the abov e
limitation or exclusion may not apply to you.
This Limited Warranty gives you specific legal rights. You may als o have other rights w hich may vary from state to state. We su ggest that
you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of the effective
date of the warranty (dat e of installation) must be presented, otherwis e, the effective date will be based on the rate of manuf acture plus
thirty (30) days.
This start-up checklist is to be completely filled out by the service technician starting up the Raypak Boiler or Heater
for the first time. All information may be used for warranty purposes and to ensure that the installation is correct.
Additionally this form will be used to record all equipment operation functions and required settings.
GAS SUPPLY DATA CLEARANCES
Regulator Model & Size _________ / ______CFH Front Clearance _______________In.
Gas Line Size (in room) ________________In. NPT Right Side Clearance _______________In.
Length of Gas Line ________________Eq Ft Left Side Clearance _______________In.
Low Gas Pressure Setting ________________In. WC Rear Clearance _______________In.
High Gas Pressure Setting ________________In. WC Overhead Clearance _______________In.
Gas Shut-Off Valve Type ________________
( Ball, Lube cock)
Sediment Trap ________________Y/N Voltage Supply (VAC) No Load______ Load_____
Port _______Std______Full Voltage -24 VAC _______________VAC
Voltage Com to Ground _______________VAC
VISUAL INSPECTION OF COMPONENTS
Verify inspection was done and condition of components are in
good working order with a “yes”
Wiring Harness _________________ Y/N Operating Control Setting _______________deg F
Burner/s (flame) _________________ Y/N
Refractory (visual) _________________ Y/N Sketch plumbing on reverse side
Remote flame sense _________________ Y/N
Covers in place for outdoor _________________ Y/N Flow Rate in GPM or Delta T _______________If Avail
VENTING
Vent Size: _____________ Stack Height:_______ Low Water Cutoff _______________Test
Category: _________ sketch vent on reverse side ***
Vent Material: __________________ Plumbing Size _______________
Vent Termination Type: __________________ Pump Size: _________
Combustion Air Openings: Low __________ in2 Impeller trim____________ Pump Model___________
Ventilation air High __________ in2 Louvers __________________ Screens________________
Pump Economaster setting _______________Minutes
EMISSIONS SETTINGS AND TEST INFORMATION
(AT FULL FIRE)
Blower Pressure Setting _________________In. WC See manual or card tag
Supply Gas Pressure
Verify stable pressure static &
Pilot Gas Pressure _________________In. WC See manual or card tag
Manifold Gas Pressure _________________In. WC See manual or card tag
The following measurements must be obtained with a Combustion Analyzer.
NOX _________________PPM Less than 20 PPM (If required by Certifying Agency)
Free Oxygen _________________% See manual
CO _________________PPM Less than 150 PPM
CO2 _________________% See manual
Model Number: ______________________________ Serial Number: _______________________________
*** Note: draw venting with details, such as extractors,
barometric dampers, blast dampers or draft inducers
_________________In. WC
dynamic condition
ELECTRICAL
Hot Surface Igniter
Auto High Limit Setting
Manual Reset High Limit Setting
_______________Ohms
_______________deg F
_______________deg F
WATER SUPPLY
Measure flow rate at full fire
Number of Tanks and Size Qty____ _______Gallons
(boiler) Pump HP: ______
Nominal Factory Recommended Settings
See manual or card tag
Site Altitude Above Sea Level __________________Ft.
Job Name _______________________________________________________________________________________