Raypak 399B, 499B, 649B, 749B, 899B Installation & Operating Instructions Manual

...
INSTALLATION & OPERATING
INSTRUCTIONS
CATALOG NO. 1000.60A Effective: 01-06-09 Replaces: 09-28-07 P/N 241330 Rev. 2
WARNING: If these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or death
.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for future reference.
Models 399B–2339B
Types H & WH
L
W
2
Rev. 2 reflects the following: Changes to: Paragraph one of the Stacking section on page 9; Table G on page 16; Table H on page 18; Fig. 19 on page 22; Fig. 20–22 on page 23; Fig. 24 on page 24; the Wiring Diagrams on pages 39 and 40. The addition of: A wiring diagram note on page 38.
WARNINGS 4 BEFORE INSTALLATION 5
Product Receipt 5 Model Identification 5 Ratings and Certifications 5 Installations at Elevation 5 Component Locations 6 General Information 7
GENERAL SAFETY 8
Time/Temperature Relationships in Scalds 8
INSTALLATION 9
Installation Codes 9 Equipment Base 9 Stacking 9 Clearances 11 Combustion and Ventilation Air 12 Conventional Combustion Air Supply 12 Water Piping 14 Hydronic Heating 16 Gas Supply 18 Electrical Power Connections 21 Field Wiring Connection 22 Venting 25 Changing the Flue Outlet 27 Venting Installation Tips 27 Venting Configurations 28 Outdoor Installation 32 Controls 32 Heater Sequence of Operation 33 Wiring Diagrams 39
START-UP 41
Pre Start-up 41 Start-Up 42
OPERATION 45
Lighting Instructions 45 To Turn Off Gas To Appliance 45
TROUBLESHOOTING 46 MAINTENANCE 47
Suggested Minimum Maintenance Schedule 47 Preventative Maintenance Schedule 47
APPENDIX 49
Inside Air Contamination 49
WARRANTY 50 START-UP CHECKLIST 51
CONTENTS
3
DANGER:
Indicates the presence of immediate hazards which will cause severe personal injury, death or substantial property damage if ignored.
WARNING:
Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored.
CAUTION:
Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored.
NOTE:
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
DANGER: Make sure the gas on which the heater will operate is the same type as that specified on the heater rating plate.
WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or disconnect the electrical supply to the heater. Instead, shut off the gas supply at a location external to the heater.
WARNING: Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
WARNING: To minimize the possibility of improper operation, serious personal injury, fire, or damage to the heater:
Always keep the area around the heater free of combustible materials, gasoline, and other flammable liquids and vapors.
Heater should never be covered or have any blockage to the flow of fresh air to the heater.
WARNING - CALIFORNIA PROPOSITION 65: This product contains chemicals known to the
State of California to cause cancer, birth defects or other reproductive harm.
WARNING: Risk of electrical shock. More than one disconnect switch may be required to deenergize the equipment before servicing.
CAUTION: Operation of this heater in low­temperature systems requires special piping. Harmful internal condensation will occur if the inlet water temperature does not exceed 105°F. Warranty claims will be denied when condensation occurs.
CAUTION: If this heater is to be installed above radiation level, it must be provided with a low water cut-off device at the time of heater installation.
CAUTION: If this heater is to be installed in a negative or positive pressure equipment room, there are special installation requirements. Consult factory for details.
WARNINGS
Pay Attention to These Terms
4
WARNING: This unit contains refractory ceramic fiber (RCF) insulation in the combustion chamber. RCF, as manufactured, does not contain respirable crystalline silica. However, following sustained exposure to very high temperatures (>2192F), the RCF can transform into crystalline silica (cristabolite). The International Agency for Research on Cancer (IARC) has classified the inhalation of crystalline silica (cristabolite) as carcinogenic to humans.
When removing the burners or heat exchangers, take precautions to avoid creating airborne dust and avoid inhaling airborne fibers. When cleaning spills, use wet sweeping or High Efficiency Particulate Air (HEPA) filtered vacuum to minimize airborne dust. Use feasible engineering controls such as local exhaust ventilation or dust collecting systems to minimize airborne dust. Wear appropriate personal protective equipment including gloves, safety glasses with side shields, and appropriate NIOSH certified respiratory protection, to avoid inhalation of airborne dust and airborne fiber particles.
BEFORE INSTALLATION
Raypak strongly recommends that this manual be re­viewed thoroughly before installing your Delta Limited heater. Please review the General Safety information before installing the heater. Factory warranty does not apply to heaters that have been improperly installed or operated. (Refer to the warranty at the back of this manual.) Installation and service must be performed by a qualified installer, service agency or gas supplier. If, after reviewing this manual, you still have questions which this manual does not answer, please contact the manufacturer or your local Raypak representative.
Thank you for purchasing a Raypak product. We hope you will be satisfied with the high quality and durability of our equipment.
Product Receipt
On receipt of your heater it is suggested that you visu­ally check for external damage to the shipping crate. If the crate is damaged, make a note to that effect on the Bill of Lading when signing for the shipment. Remove the heater from the shipping packaging. Report any damage to the carrier immediately.
On occasion, items are shipped loose. Be sure that you receive the correct number of packages as indi­cated on the Bill of Lading.
Claims for shortages and damages must be filed with the carrier by consignee. Permission to return goods must be received from the factory prior to shipping. Goods returned to the factory without an authorized Returned Goods Receipt number will not be accepted. All returned goods are subject to a restocking charge.
When ordering parts, you must specify the model and serial number of the heater. When ordering under war­ranty conditions, you must also specify the date of installation.
Purchased parts are subject to replacement only under the manufacturer’s warranty. Debits for defec­tive replacement parts will not be accepted and will be replaced in kind only per Raypak’s standard war­ranties.
Model Identification
The model identification number and heater serial number are found on the heater rating plate located on the lower right outside jacket of the heater. The model
number will have the form H8 1259B or similar depending on the heater size and configuration. The letter(s) in the first group of characters identifies the application (H = Hydronic Heating, WH = Domestic Hot Water (DHW)). The number which fol-lows identi­fies the firing mode (1 or 4 = on-off, 3 = 2-stage, 8 = 3-stage and 9 = 4-stage). The second group of char­acters identifies the size of the heater (four numbers representing the approximate MBTUH input), and, where applicable, a letter, indicating the manufacturing series.
Ratings and Certifications
Standards:
ANSI Z21.13 · CSA 4.9 - latest edition, Gas-Fired Hot Water Boilers
CAN 3.1 - latest edition, Industrial and Commercial Gas-Fired Package Boilers
ANSI Z21.10.3 · CSA 4.3 - latest edition Gas Water Heaters
All Raypak heaters are National Board Approved, and design-certified and tested by the Canadian Standards Association (CSA) for the U.S. and Canada. Each heater is constructed in accordance with Section IV of the American Society of Mechanical Engineers (ASME) Heater Pressure Vessel Code and bears the ASME stamp. The heater also complies with the latest edition of ASHRAE 90.1 Standard.
Installations at Elevation
Rated inputs are suitable for up to 5,000 ft elevation without de-rating. Consult the factory for installations at altitudes over 5,000 ft above sea level.
WARNING: Altering any Raypak pressure vessel by installing replacement heat exchangers, tube bundle headers, or any ASME parts not manufactured and/or approved by Raypak will instantly void the ASME and CSA ratings of the vessel and any Raypak warranty on the vessel. Altering the ASME or CSA ratings of the vessel also violates national, state, and local approval codes.
5
Component Locations
Fig. 1: Component Locations – Back
Fig. 2: Component Locations – Left Side
Panels removed for clarity
Fig. 3: Component Locations – Front
6
OPTIONAL FLUE CONNECTION
General Information
Table A: Basic Data
Table B: Manifold Data
Model
No.
Quantity of Vent Size (in.)
Burners Gas Valves Blowers Flue Intake
399B 8 1 1 6 6
499B 10 2 1 6 6
649B 13 2 1 8 6
749B 15 2 1 8 6
899B 18 3 1 8 6
989B 11 2 2 10 10
1259B 14 3 2 12 10
1529B 17 4 2 12 10
1799B 20 4 2 14 10
1999B 23 5 3 14 10
2069B 23 5 3 14 10
2339B 26 5 3 16 10
Model
No.
Burners per Valve Stages % Fire at Stage
1 1A 2 3 4 1 2 3 4 1 2 3 4
399B 8 1 100
499B 5 5 1 1, 2 50 100
649B 7 6 1 1, 2 54 100
749B 8 7 1 1, 2 53 100
899B 6 6 6 1, 2 1, 2, 3 66 100
989B 6 5 1 1, 2 54 100
1259B 5 3 6 1 1, 2 1, 2, 3 36 57 100
1529B 6 4 4 3 1 1, 2 1, 2, 3 1, 2, 3, 4 35 59 82 100
1799B 6 4 5 5 1 1, 2 1, 2, 3 1, 2, 3, 4 30 50 75 100
1999B 4 5 5 5 4 1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 39 61 83 100
2069B 4 5 5 5 4 1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 39 61 83 100
2339B 5 6 5 5 5 1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 42 62 81 100
7
GENERAL SAFETY
To meet commercial hot water use needs, the high limit safety control on this water heater is adjustable up to 210°F. However, water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water, the rec­ommended initial setting for the temperature control is 125°F.
Safety and energy conservation are factors to be con­sidered when setting the water temperature on the thermostat. The most energy-efficient operation will result when the temperature setting is the lowest that satisfies the needs of the application.
Water temperature over 125°F can cause instant severe burns or death from scalds. Children, disabled and elderly are at highest risk of being scalded.
Feel water before bathing or showering.
Temperature limiting valves are available.
Maximum water temperatures occur just after the heater’s burner has shut off. To determine the water temperature being delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.
NOTE: When this water heater is supplying general purpose hot water for use by individuals, a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.
Time/Temperature Relationships in Scalds
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
Table C: Time to Produce Serious Burn
8
Water temperature over 125°F can cause instant severe burns or death from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
See instruction manual before set­ting temperature at water heater.
Feel water before bathing or show­ering.
Temperature limiting valves are available, see manual.
Water
Temp.
120°F More than 5 minutes
125°F 1-1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1-1/2 seconds
155°F About 1 second
Table courtesy of The Shriners Burn Institute
Time to Produce Serious
Burn
INSTALLATION
INSTALLATION
Installation Codes
Installations must follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances
National Fuel Gas Code, ANSI Z223.1/NFPA 54 – latest edition (NFGC)
National Electrical Code, ANSI/NFPA 70 - latest edition (NEC)
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required (CSD-1)
For Canada only: CAN/CGA B149 Installation Code (B149) and CSA C22.1 C.E.C. Part 1 (C22.1)
The temperature of the water in the heater can be reg­ulated by using the temperature controller. To comply with safety regulations, the temperature controller is set at the lowest setting when shipped from the facto­ry.
To adjust the water temperature, insert a small straight screwdriver into the adjustment screw on the front of temperature controller and turn the wheel to the desired setting (See Fig. 4.).
CAUTION: Hotter water increases the risk of scald­ing! There is a hot water scald potential if the thermostat is set too high.
Fig. 4: Temperature Control
Equipment Base
The heater should be mounted on a level, structurally sound surface. The heater is approved for installation on a combustible surface but must NEVER be installed on carpeting. Gas-fueled equipment installed in enclosed parking garages must be located at least 18 in. above the floor.
Stacking
Delta Limited units can be stacked two units high with an optional stacking rack. A stacking kit is available from Raypak for this type of installation.
CAUTION: The heaters should be located in an area where water leakage will not result in damage to the area adjacent to the appliances or to the structure. When such locations cannot be avoided, it is recommended that a suitable catch pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.
Fig. 5: Typical Stacked Installation
9
REQUIRES OPTIONAL VENT TEE.
REQUIRES OPTIONAL VENT TEE IF VENTED OUT BACK OF HEATER.
Fig. 6: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
Table D: Vent/Air Inlet Termination Clearances
10
U.S. Installations
Clearance above grade, veranda, porch,
A
deck, or balcony
Clearance to window or door that may be
B
opened
4 ft (1.2m) below or to side
1 ft (30 cm) 1 ft (30 cm)
of opening; 1 foot (30 cm)
above opening
1
Canadian Installations
3 ft (91 cm)
2
C Clearance to permanently closed window **
Vertical clearance to ventilated soffit located above the terminal within a horizontal dis-
D
tance of 2 ft (61cm) from the centerline of the
5 ft (1.5m) *
terminal
E Clearance to unventilated soffit **
F Clearance to outside corner **
G Clearance to inside corner 6 ft (1.83m) *
Clearance to each side of center line ex-
H
tended above meter/regulator assembly
*
3 ft (91 cm) within a height
15 ft above the me-
ter/regulator assembly
I Clearance to service regulator vent outlet * 6 ft (1.83m)
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any
J
other appliance
K Clearance to mechanical air supply inlet
Clearance above paved sidewalk or paved
L
driveway located on public property
Clearance under veranda, porch, deck or
M
balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code
2
In accordance with the current CAN/CGA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that serves
both dwellings
TT Permitted only if veranda, porc h, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of terminal and
underside of ver anda, porch, deck or balcony is greater than 1 ft (30cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
above opening
3 ft (91 cm) above if within
10 ft (3m) horizontally
7 ft (2.13m)
* 12 in. (30 cm) TT
3 ft (91 cm)
6 ft (1.83m)
7 ft (2.13m) t
In addition, the heater shall be installed such that the gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation or service (circulator replacement, control replacement, etc.).
Clearances
Indoor Installations
Table E: Clearances – Indoor Installations
Fig. 7: Minimum Clearances from Combustible
Surfaces – Indoor Installations
When installed according to the listed minimum clear­ances from combustible construction, these heaters can still be serviced without removing permanent structural construction around the heater. However, for ease of servicing, we recommend a clearance of at least 24 in. in front, and at least 12 in. on the water connection side. This will allow the heater to be serv­iced in its installed location without movement or removal of the heater.
Service clearances less than the minimums may require removal of the heater to service either the heat exchanger or the burner tray. In either case, the heater must be installed in a manner that will enable the heater to be serviced without removing any structure around the heater.
Outdoor Installations
These heaters are design-certified for outdoor installa­tion. Heaters must not be installed under an overhang that is less than 3 ft from the top of the heater. Three sides must be open in the area under the overhang. Roof water drainage must be diverted away from heaters installed under overhangs.
Table F: Clearances – Outdoor Installations
These clearances are required when the outdoor vent cap is used. If installing the heater outdoors with a vent stack, the indoor clearances may be utilized.
The combustion air intake hood MUST be used for outdoor installations. The hood is shipped loose and installed on the side of the heater over the filter box at the jobsite.
* DO NOT install on carpeting.
11
Heater
Side
Minimum Clearance
from Combustible
Surfaces
Floor* 0” 0”
Rear 1” 24”
Water Side 12” 24”
Other Side 1” 24”
Top 1” 1”
Front Open 24”
Vent 2” 2”
Recommended
Service
Clearance
Heater
Side
Min. Clearance
from Combustible
Surfaces
Recommended
Service
Clearance
TOP VIEW
FRONT VIEW
Venting not shown for clarity. Heater must be vented
per instructions in this manual
Front Open 24”
Rear 12” 24”
Water Side 36” 36”
Other Side 36” 36”
Top Unobstructed 36”
Vent N/A N/A
three or four sheet metal screws (not supplied) equal­ly distributed around the circumference of the duct. All ducting should be self-supported. The filter housing is not designed to support the air duct.
Conventional Combustion Air Supply
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO per- manent openings communicating directly with an additional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for a room large in comparison (NFGC). The total input of all gas utilization equipment installed in the combined
CAUTION: This type of installation is recommended if damaging airborne contaminants are or will be present in the heater area. See the Appendix regarding air contamination.
Fig. 8: Minimum Clearances from Combustible
Surfaces – Outdoor Installations
Combustion and Ventilation Air
Indoor Units
The heater must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be sup­plied via conventional means where combustion air is drawn from the area immediately surrounding the heater, or via direct vent, where combustion air is drawn directly from outside. All installations must com­ply with the requirements of the NFGC (U.S.) and B149 (Canada), and all local codes.
Reversing Air Filter
Follow these instructions to change the air duct con­nection from the left-hand side (standard) to the right-hand side:
1. Remove the four screws and the dust cover from the right-hand side of the heater.
2. Remove the four screws and the air filter bracket from the left-hand side of the heater.
3. Reverse the components and reattach in the new location, making sure that the air filter locking bracket is on the bottom. (The air filter locking bracket is reversible.)
Direct-Ducted Combustion Air
In certain applications it may be desirable to duct the combustion air directly to the heater. This should be done with PVC, CPVC or single-wall galvanized duct­ing. The duct will attach directly to the collar on the air filter housing located on the side of the heater. The ducting is attached to the air filter housing collar using
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty. (See the Appendix.)
NOTE: It is recommended that the intake vent be insulated to minimize sweating.
NOTE: Use of the heater in construction areas where fine particulate matter, such as concrete or dry-wall dust, is present may result in damage to the heater that is not covered by the warranty. If operated in a construction environment, a clean source of combustion air must be provided directly to the heater.
12
space shall be considered in making this determina­tion. Each opening shall have a minimum free area of 1 in.
2
per 1,000 BTUH (2,225 mm2per kW) of the total input rating of all gas utilization equipment in the con­fined space, but not less than 100 in.
2
(645 cm2). One opening shall commence within 12 in. (305 mm) of the top, and one opening shall commence within 12 in. (305 mm) of the bottom of the enclosure. The mini­mum dimension of air openings shall be not less than 3 in. (76 mm) in any direction.
All Air from Outdoors
The confined space shall communicate with the out­doors in accordance with one of the methods below. The minimum dimension of air openings shall not be less than 3 in. (76 mm) in any direction. Where ducts are used, they shall be of the same cross-sectional area as the net free area of the openings to which they connect.
1. Two permanent openings, one commencing
within 12 in. (305 mm) of the top, and one com­mencing within 12 in. (305 mm) of the bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely com­municate with the outdoors.
a. Where directly communicating with the out-
doors or where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in.
2
per 4,000 BTUH (550 mm2per kW) of total input rating of all equipment in the enclosure.
b. Where communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 in.
2
per 2,000 BTUH (1,100 mm2per kW) of total input rat­ing of all equipment in the enclosure.
2. One permanent opening, commencing within 12 in. (305 mm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (152 mm) from the front of the appliance. The opening shall directly communicate with the out­doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors, and shall have a minimum free area of:
a. 1 in.
2
per 3,000 BTUH (740 mm2per kW) of the total input rating of all equipment located in the enclosure, and
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use one permanent opening method if the equipment room is under negative pressure conditions or the equipment is common vented with other gas-fired appliances.
1. Ventilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with the outdoors. The total cross-sectional area of such an opening(s) shall be at least 10% of the area required in 2. and 3. (below), but in no case shall the cross-sectional area be less than 10 in.
2
(65 cm2).
2. For heaters using a barometric damper in the vent system there shall be a permanent air supply opening(s) having a cross section area of not less than 1 in.
2
per 7,000 BTUH (320 mm2per kW) up
to and including 1 million BTUH, plus 1 in.
2
per
14,000 BTUH (160 mm
2
per kW) in excess of 1 million BTUH. This opening(s) shall be either located at or ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down and terminated 18 in. (450 mm) from the floor, but not near piping. This air supply opening require­ment shall be in addition to the air opening for ventilation air required in 1. (above).
3. For heaters not using a barometric damper in the vent system, and when air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, drafthood or similar flue gas dilution device installed in the same space, in addition to the opening for ventilation air required in 1., there shall be a permanent air sup­ply opening(s) having a total cross-sectional area
CAUTION: All combustion air must be drawn from the air outside of the building; the mechanical equip­ment room must communicate directly with the outdoors.
Canadian Installations
WARNING: Care must be taken to ensure that the
equipment room is not under negative pressure conditions or that the equipment is not common­vented with other gas-fired appliances.
13
5. Remove all plumbing fittings to the header. This will include both inlet and outlet water pipe unions and the pressure relief valve and drain piping.
6. Remove limits, control bulbs and/or thermocou­ples.
7. Remove the six (or 8) flange nuts and the in/out header from the left-hand side.
8. Remove the six (or 8) flange nuts and the return header from the right-hand side.
9. Remove the header stud bolts from each tube sheet.
10. Reverse the headers and stud bolts to the new location.
11. Install NEW red beveled O-rings flush against both tube sheets with the bevel facing outward.
12. Push the header firmly against the O-rings. Install and tighten the flange nuts onto the stud bolts until finger tight.
13. Slowly tighten the flange nuts, starting from the center nut (number 1) in Fig. 9 and working se­quentially around the header as indicated. Torque all nuts to 25 ft/lb. DO NOT OVER-TIGHTEN.
14. Re-route the capillary(s), wiring etc. to the new location, adding thermal paste and shim to the
capillary well.
Relief Valve Piping
WARNING: Pressure relief valve discharge piping
must be piped near the floor and close to a drain to eliminate the potential of severe burns. Do not pipe to any area where freezing could occur. Refer to local codes.
Hydrostatic Test
Unlike many types of heaters, this heater does not re­quire hydrostatic testing prior to being placed in operation. The heat exchanger has already been fac­tory-tested and is rated for 160 psi operating pressure. However, Raypak does recommend hydrostatic test­ing of the piping connections to the heater and the rest of the system prior to operation. This is particularly true for hydronic systems using expensive glycol­based anti-freeze. Raypak recommends conducting
of not less than 1 in.2for each 30,000 BTUH mm
2
per kW) of total rated input of the burner(s), and the location of the opening(s) shall not interfere with the intended purpose of the opening(s) for ventilation air referred to in (1). This opening(s) can be ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down 18 in. (450 mm) from the floor, but not near piping.
4. Refer to B149 Installation code for additional infor­mation.
Water Piping
General
The heater should be located so that any water leaks will not cause damage to the adjacent area or struc­tures.
Reversing Water Connections
Follow these instructions to change the water connec­tions from the left-hand side (standard) to the right-hand side.
1. Disconnect all electrical power from the heater (if applicable).
2. Label all electrical connections and conduit lines. This may include the flow switch, low water cut-off probe and/or pump.
3. Disconnect or isolate the main gas pipe from the heater (if applicable).
4. Remove both in/out and return header access panels by removing all sheet metal screws.
CAUTION: This heater requires forced water circulation when the burner is operating. See Table G and Table H for minimum and maximum flow rates and water pump selection. The pump must be interlocked with the heater to prevent heater operation without water circulation.
NOTE: Minimum pipe size for in/out connections is 2
1
2 in (2 in. for 399B–899B). Verify proper flow rates
and ΔT as instructed in this manual.
14
Fig. 9: Torque Sequence
the hydrostatic test before connecting gas piping or electrical supply.
Leaks must be repaired at once to prevent damage to the heater. NEVER use petroleum-based stop-leak compounds.
To perform hydrostatic test:
1. Connect fill water supply. With bleed valve open, fill heater with water. When water flows from bleed valve, shut off water. Close bleed valve. Carefully fill the rest of the system, making sure to eliminate any entrapped air by using high-point vents. Close feed valve. Test at standard operating pressure for at least 24 hours.
2. Make sure constant gauge pressure has been maintained throughout test.
3. Check for leaks. Repair if found.
Cold Water Operation
A heater operated with an inlet temperature of less than 105ºF (41ºC) must have a manual bypass or an approved low-temperature operation system to pre­vent problems with condensation. A manual bypass, shown in Fig. 15, must be piped into the system at the time of installation. This piping is like a pri­mary/secondary boiler installation with a bypass acting as the secondary boiler piping. Raypak strongly rec­ommends that thermometer(s) be placed into the heater piping next to the in/out header to facilitate tem­perature adjustment. Inlet water temperatures below 105ºF (41ºC) can excessively cool the products of combustion, resulting in condensation on the heat exchanger and in the flue.
CAUTION: Damaging internal condensation may occur if the heater inlet water temperature does not exceed 105ºF (41ºC) within 7 minutes of start-up.
Failure to exceed 105ºF (41ºC) within 7 minutes may result in the premature failure of the hot surface ignit­er, remote flame sensor, burners and heat exchanger. It can cause operational problems, bad combustion, sooting, flue gas spillage and reduced service life of the vent system. The bypass allows part of the heater discharge water to be mixed with the cooler heater return water to increase the heater inlet temperature above 105ºF (41ºC). This precautionary measure should prevent the products of combustion from con­densing in most installations. Warranty claims will be
denied when condensation occurs.
Cold water operation issues are applicable to both cold water start and cold water run applications. Cold water operation for 7 minutes or less on start-up is acceptable. Where cold water starts will last longer than 7 minutes or where cold water operation is con­tinuous, provisions must be made to mix higher temperature outlet water with the colder inlet water and thereby raise the inlet temperature to at least 105ºF (41ºC) within the 7-minute time limit.
Cold Water Starts
Frequent (more than once a week) cold water starts, wherein the inlet water temperature remains below 105ºF (41ºC) for more than 7 minutes, must have cold water start protection. Known protection methods con­sist of mixing heated outlet water with the inlet water with a bypass to raise the inlet to 105ºF (41ºC) or high­er. Once the system is heated up and has return water temperatures of 105ºF (41ºC) or higher, the mixing of outlet water with inlet water is no longer needed and the bypass can be shut off. If the bypass is not shut off
Models 399B–899B
Models 989B–2339B
15
Cold Water Run
Cold water run differs from cold water start in that the system water entering the heater remains below 105ºF (41ºC) continuously. Typically, this is the case in swim­ming pool heating and water source heat pump applications as well as some others. If the system water is kept in a narrow temperature range, a perma­nent manual bypass can be employed and manually adjusted to achieve an inlet temperature of 105ºF (41ºC) or higher. An injector pump arrangement may also be utilized to keep the heater loop at or above 105ºF (41ºC). An injector pump approach has the added value of being able to adjust to changes in the system water coming back to the heater take-off.
Table G: Heater Rates of Flow and Pressure Drops
Notes: 1. Basis for minimum flow: Models 399–899, 20 gpm or 40°F ΔT. Models 989–2339, 30 gpm or 40°F ΔT.
Basis for maximum flow: Models 399–899, 90 gpm. Models 989–2339, 132 gpm.
2. Flow switch will not operate if flow is less than 20 gpm.
as the system heats up, the outlet temperature may continue to climb and actuate the high limit, thereby shutting down the heater. Thus an automatic valve system, such as a three-way proportional valve or a modulating two-way valve to control the bypass, should be utilized.
Temperature & Pressure Gauge
The temperature and pressure gauge is factory­mounted in the in/out header.
Hydronic Heating
Pump Selection
In order to ensure proper performance of your heater system, you must install a correctly sized pump. Ray­pak recommends using a 20°F ΔT as design ΔT. (ΔT is the temperature difference between the inlet and out­let water when the heater is firing at full rate). If a ΔT of larger than 20°F is necessary, see Table G and Table H for flow rate requirements.
Model
No.
10°F ΔT 20°F ΔT 30°F ΔT Min. Flow Max. Flow
gpm ΔP (ft) gpm ΔP (ft) gpm ΔP (ft) gpm ΔP (ft) ΔT gpm ΔP (ft) ΔT
399B 67 5.5 34 1.4 22 0.6 20 0.5 34 90 10.0 7
499B 84 9.1 42 2.3 28 1.1 21 0.6 40 90 10.4 9
649B 55 4.1 36 1.8 27 1.1 40 90 10.8 12
749B 63 5.7 42 2.6 32 1.5 40 90 11.3 14
899B 76 8.3 50 3.8 38 2.2 40 90 11.7 17
989B 83 5.2 55 2.3 42 1.3 40 132 13.1 13
1259B 106 9.6 71 4.3 53 2.4 40 132 14.8 16
1529B 129 15.7 86 7.1 64 4.0 40 132 16.5 19
1799B 101 10.7 76 6.0 40 132 18.3 23
1999B 112 13.8 84 7.9 40 132 19.0 25
2069B 116 14.8 87 8.5 40 132 19.0 26
2339B 132 21.4 98 12.1 40 132 21.4 30
16
Pressure Drop in Feet of Head Feedwater Regulator
Raypak recommends that a feedwater regulator be in­stalled and set at 12 psi minimum pressure at the highest point of the system. Install a check valve or back flow device upstream of the regulator, with a manual shut-off valve as required by local codes.
Piping
All high points should be vented. Purge valves and a bypass valve should be installed. A heater installed above radiation level must be provided with a low wa­ter cut-off device (sales order option F-10). The heater, when used in connection with a refrigeration system, must be installed so that the chilled medium is piped in parallel with the heater with appropriate valves to pre­vent the chilled medium from entering the heater.
The piping system of a hot water heater connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the heater water during the cooling cycle. It is highly recommend­ed that the piping be insulated.
Air-Separation/Expansion Tank
All heaters should be equipped with a properly sized expansion tank and air separator fitting as shown in Fig. 10.
Three-Way Valves
Valves designed to blend water temperatures or reduce water circulation through the heater should not be used. Raypak heaters are high-recovery, low-mass
Fig. 10: Air-Separation/Expansion Tank
heaters which are not subject to thermal shock. Raypak offers a full line of electronic sequencers that produce direct reset of heater water temperature.
(Refer to the Controls section of the Raypak Catalog.)
Domestic Hot Water
When designing the water piping system for domestic hot water applications, water hardness should be con­sidered. Table H indicates the suggested flow rates for soft, medium and hard water. Water hardness is ex­pressed in grains per gallon.
Fig. 11: Single Heater - Low-Temperature (Heat Pump)
Application with Primary/Secondary Piping
Fig. 12: Dual Heaters (Reverse/Return)
with Primary/Secondary Piping
17
*
18
Potable Water and Space Heating
1. All piping materials and components connected to the water heater for the space heating application shall be suitable for use with potable water.
2. Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used for space heating.
3. If the heater will be used to supply potable water, it shall not be connected to any heating system or components previously used with a non-potable water heating appliance.
4. When the system requires water for space heating at temperatures higher than 140°F, a means such as a mixing valve shall be installed to temper the water in order to reduce scald hazard potential.
CAUTION: When this heater is used for both potable water and space heating, observe the following to ensure proper operation.
Fig. 13: Single Domestic Hot Water Heater and Storage
Tank
Table H: Domestic Water Heater Flow Rate Requirements
ΔT = Temperature rise, °F. ΔP = Pressure drop through heat exchanger, ft. SHL = System head loss, ft. (System head loss based on heater and tank placed no more than 5 ft apart and equivalent length pipe/fittings as fol­lows: 2 in. tube = 25 ft; 2 1/2 in. tube = 80 ft. gpm = Gallons per minute, flow rate.) MTS = Minimum tubing size. *Must utilize optional cupro-nickel tubes. **With Hard Water (16-25 grains per gallon), the operating control must be set no higher than 130F for scale free operation. For operating temper­atures above 130F, a water softener must be utilized.
Model
No.
Soft (0–4 grains per gallon) Medium (5–15 grains per gallon) Hard* (16–25** grains per gallon)
ΔT gpm ΔP MTS SHL ΔT gpm ΔP MTS SHL ΔT gpm ΔP MTS SHL
399B 17 40 2.0 2 4.4 13 52 3.4 2 7.2 8 90 10.0 2 20.5
499B 21 40 2.1 2 4.5 16 52 3.5 2 7.4 9 90 10.4 2 20.9
649B 28 40 2.2 2 4.6 20 55 4.1 2 8.4 12 90 10.8 2 21.3
749B 30 42 2.6 2 5.2 20 63 5.7 2 11.1 14 90 11.3 2 21.8
899B 30 51 3.9 2 7.6 20 76 8.4 2 16.1 17 90 11.7 2 22.2
989B 28 60 2.7 2 1/2 4.6 20 83 5.2 2 1/2 8.6 13 132 13.1 2 1/2 21.0
1259B 30 72 4.4 2 1/2 7.0 20 106 9.6 2 1/2 14.8 16 132 14.8 2 1/2 22.7
1529B 30 86 7.1 2 1/2 10.7 20 132 16.5 2 1/2 24.4 20 132 16.5 2 1/2 24.4
1799B 30 101 10.7 2 1/2 15.5 23 132 18.3 2 1/2 26.1 23 132 18.3 2 1/2 26.1
1999B 30 112 13.9 2 1/2 19.7 26 132 19.0 2 1/2 26.9 26 132 19.0 2 1/2 26.9
2069B 30 116 14.8 2 1/2 21.0 27 132 19.0 2 1/2 26.9 27 132 19.0 2 1/2 26.9
2339B 30 132 21.4 2 1/2 29.3 30 132 21.4 2 1/2 29.3 30 132 21.4 2 1/2 29.3
Gas Supply
Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve lo­cated outside the heater jacket. It is recommended that a union be installed in the gas supply piping adja­cent to the heater for servicing. A pounds-to-inches
DANGER: Make sure the gas on which the heater will operate is the same type as specified on the heater’s rating plate.
19
Gas Supply Connection
The heater must be isolated from the gas supply pip­ing system by closing the manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa). Relieve test pressure in the gas supply line prior to reconnecting the heater and its manual shut-off valve to the gas supply line. FAILURE TO FOLLOW
THIS PROCEDURE MAY DAMAGE THE GAS VALVES. Over pressurized gas valves are not cov-
ered by warranty. The heater and its gas connections shall be leak-tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use an open flame.
CAUTION: The heater must be disconnected from the gas supply during any pressure testing of the gas supply system at test pressures in excess of 1/2 psi (3.45 kPa).
Fig. 14: Gas Supply Connection
CAUTION: Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with natural and propane gases is recommended. Apply sparingly only on male pipe ends, leaving the two end threads bare.
Table I: Maximum Equivalent Pipe Length
Natural gas – 1,000 BTU per ft3, .60 specific gravity at 0.5 in. WC pressure drop Propane gas – 2,500 BTU per ft
3
, 1.53 specific gravity at 0.6 in. WC pressure drop
Model
No.
3/4” 1” 1-1/4” 1-1/2” 2” 2-1/2” 3” 4”
N P N P N P N P N P N P N P N P
399B 15 25 60 100 260 250
499B 65 150 130 360 500
649B 45 100 95 250 340
749B 35 80 75 180 260 600
899B 20 45 45 110 150 360 400
989B 120 300 300
1259B 75 180 170 325 560
1529B 50 120 125 250 400
1799B 40 100 100 225 340
1999B 30 80 75 175 260
2069B 30 80 75 175 260
2339B 20 55 55 135 160 400 600
regulator must be installed to reduce the gas supply pressure to a maximum of 10.5 in. WC for natural gas and 13.0 in. WC for propane gas. The regulator should be placed a minimum distance of 10 times the pipe diameter up-stream of the heater gas controls. Refer to Table I for maximum pipe lengths.
9. Install a coupling, nipple, union and sediment trap onto the right-hand end of the main gas line and then install the gas line, making sure that a manu­al shut-off valve has been installed within 10 ft of the heater.
10. Replace the left and right front panels on the heater.
Gas Supply Pressure
A minimum of 5.0 in. WC and a maximum of 10.5 in. WC upstream gas pressure is required under load and no-load conditions for natural gas. A minimum of 11.0 in. WC and a maximum of 13.0 in. WC is required for propane gas. The gas pressure regulator(s) supplied on the heater is for low-pressure service. If upstream pressure exceeds 14.0 in. WC, an intermediate gas
Fig. 15: Gas Valves
CAUTION: Support gas supply piping with hangers, not by the heater or its accessories. Make sure the gas piping is protected from physical damage and freezing, where required.
Reversing Gas Supply Connection
Reversing the standard fuel connection from the left­hand to the right-hand side is a simple field operation.
1. Disconnect all electrical power from the heater (if applicable).
2. Disconnect the main gas pipe from the heater (if applicable).
3. Remove the left and right front panels from the heater.
4. Locate the main gas line that traverses across the heater above the manifold risers.
5. Remove the pipe cap from the right-hand end of the main gas line.
6. Reinstall the pipe cap on the left-hand end of the main gas line.
7. Remove plastic cap from the right-hand side panel and reinstall into the standard main gas opening located on the left-hand side of the heater.
8. Remove the rubber grommet from the left-hand­side panel and reinstall into the standard main gas opening, located on the right-hand side of the heater.
pressure regulator, of the lockup type, must be installed.
When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to determine if it has adequate capacity for the combined load.
The gas valve pressure regulator(s) on the heater are nominally preset at 3.5 in. WC for natural gas, and
10.5 in. WC for propane gas. The pressure at the gas valve outlet tap, measured with a manometer, while in operation should be 3.5 ± 0.1 in. WC for natural gas and 10.5 in. ± 0.1 in. WC for propane gas. If an adjust­ment is needed, remove the adjustment screw cover and turn the adjustment screw clockwise to increase pressure or counter-clockwise to lower pressure.
Models 399B–2339B
Models 989B–2339B
20
Adjustment
Electrical Power Connections
Installations must follow these codes:
National Electrical Code and any other national, state, provincial or local codes or regulations hav­ing jurisdiction.
Safety wiring must be NEC Class 1.
Heater must be electrically grounded as required by the NEC.
In Canada, CSA C22. 1 C.E.C. Part 1.
The heater is wired for 120 VAC, <12 amps. The volt­age is indicated on the tie-in leads. Consult the wiring diagram shipped with the heater in the instruction packet. The remote tank control stat, thermostat, or electronic heater control (as applicable) may be con­nected to the stage selector terminal (See wiring diagram). 24 VAC is supplied to this connection through the heater transformer. DO NOT attach any voltage to the stage selector terminals. Before starting the heater check to ensure proper voltage to the heater and pump.
Install a separate disconnect means for each load. Use appropriately sized wire as defined by NEC, CSA and/or local code. All primary wiring should be 125% of minimum rating.
If any of the original wire as supplied with the heater must be replaced, it must be replaced with 105°C wire or its equivalent.
Field-Connected Controllers
It is strongly recommended that all individually-pow­ered control modules and the heater should be supplied from the same power source.
Check the Power Source
NOTE: Field-supplied isolation relays should be
installed when field-connected controllers are mounted more than 50 equivalent feet (18 Ga) from heater.
WARNING: Using a multi-meter, check the following voltages at the terminal block inside the unit. Make sure proper polarity is followed and house ground is proven. (See Fig. 18.)
Fig. 16: Wiring Connections
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX AB = 108 VAC Minimum, 132 VAC MAX BC = <1 VAC Maximum
If the heater does not have a factory-wired stage con­troller, it is factory-wired in an on-off configuration with other stage terminals jumpered.
To field-connect a stage controller, remove factory­installed jumpers and wire stage controller as shown in Fig. 19–22.
Making the Electrical Connections
Refer to Fig. 16–22.
1. Verify that circuit breaker is properly sized by referring to heater rating plate. A dedicated circuit breaker should be provided.
2. Turn off all power to the heater. Verify that power has been turned off by testing with a multi-meter
Fig. 17: Multi-meter
21
BLACK
CIRCUIT
BREAKER
WHITE
GREEN
GROUND
AB C
prior to working with any electrical connections or components.
3. Observe proper wire colors while making electri­cal connections. Many electronic controls are polarity sensitive. Components damaged by improper electrical installation are not covered by warranty.
4. Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.
5. Install heater controls, thermostats, or building management systems in accordance with the applicable manufacturers’ instructions.
6. Conduit should not be used as the earth ground.
Field Wiring Connection
22
NOTE: A grounding electrode conductor shall be used to connect the equipment grounding conductors, the equipment enclosures, and the grounded service conductor to the grounding electrode.
Fig. 18: Wiring Location
DANGER: SHOCK HAZARD
Make sure electrical power to the heater is discon­nected to avoid potential serious injury or damage to components.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause im­proper and dangerous operation. Verify proper operation after servicing.
Fig. 19: On-Off Wiring Connections
23
Fig. 20: 2-Stage Wiring Connections
Fig. 21: 3-Stage Wiring Connections
Fig. 22: 4-Stage Wiring Connection
Consult the wiring diagram shipped with the heater in the instruction packet or at the end of this section. The stage-selector terminals are for the remote tank con­trol through the heater’s 24 VAC transformer. DO NOT
attach any voltage to the stage-selector terminals.
Before starting the heater, check to ensure proper volt­age to the heater and pump.
24
Fig. 23: 2-Stage Tankstat
Fig. 24: Single-Stage Tankstat
Installer action is required to electrically enable your heater to operate after making the power connections. You must make a closed contact connection on Stage 1 connector of the Central Point Wiring (CPW) board for temperature control connections. This will be done based on the controller option selected with your heater order.
1. For Closed-Loop Water-Source Heat Pump appli­cations with fixed bypass, your heater should be configured to operate in an on-off firing mode. This means that you will connect a single-pole control to stage one of the CPW board. Then jumper the remaining firing stages. For example, if your heater is a Model 1529B, you will jumper stages two, three and four. Then your heater will either be on at full fire, or it will be off.
2. For 2-stage controller connections, connect each stage of the control to the corresponding stage of the CPW board in the heater, i.e., stage 1 of the heater to stage 1 of the control; stage 2 of the heater to stage 2 of the control, as shown in Fig. 22 and Fig. 25. Set the operating control to the set-point at which you want the heater to maintain. Ensure that the sensing bulb of the control is at the point in the system that will best maintain the tem­perature you want. For example, when you are heating a tank of water, you want the operating control sensor bulb in the tank.
NOTE: If any of the original wire supplied with the heater must be replaced, it must be replaced with similar sized 105°C wire or its equivalent.
3. For single-stage controller connections, attach the stage 1 connections on heater 1 to the tankstat per Fig. 26.
Heater must be electrically grounded in accordance with the NEC, and CSA C22.1 C.E.C. Part 1 in Canada.
2-STAGE
TANKSTAT
SINGLE
STAGE
TANKSTAT
STAGE 1
CONNECTION
STAGE 1
CONNECTION
ATTACH STAGE 1 CONNECTIONS ON HEATER
TO STAGE 1 CONNECTION ON TANKSTAT.
ATTACH STAGE 2 CONNECTIONS OR
STAGE 1 CONNECTION OF HEATER 2
TO STAGE 2 CONNECTIONON TANKSTAT
AS SHOWN IN THE DIAGRAM.
STAGE 2 CONNECTION OR
STAGE 1 CONNECTION
OF HEATER 2
ATTACH STAGE 1 CONNECTIONS
ON HEATER TO THE SINGLE STAGE
TANKSTAT AS SHOWN IN THE DIAGRAM ABOVE.
25
Venting
General
Flue Exhaust Tee
An optional Flue Exhaust Tee is available to facilitate horizontal venting. Any reference to horizontal venting that exits the back of the heater requires this tee. Refer to Table J for the appropriate kit for your model.
CAUTION: Proper installation of flue venting is criti­cal for the safe and efficient operation of the heater.
Table J: Flue Exhaust Tee Kits
Model Diameter Order Number
399B–499B 6” 011839
649B, 749B,
899B
8” 011840
989B 10” 011841
1259B, 1529B 12” 011842
1799B, 1999B,
2069B
14” 011843
2339B 16” 011844
Category IV – A heater which operates with a positive vent pressure and with a vent gas temperature that may cause excessive condensate production in the vent.
See Table K for appliance category requirements.
Support of Vent Stack
The weight of the vent stack or chimney must not rest on the heater vent connection. Support must be pro­vided in compliance with applicable codes. The vent should also be installed to maintain proper clearances from combustible materials.
Barometric Damper
A barometric damper may be required when vent heights exceed 25 feet or when the draft is greater than -0.08 in. WC. In these installations, a barometric damper (single or double acting) is recommended.
The damper should be installed NO CLOSER than 18 in. from the discharge of the unit and no closer than 18 in. from a combustible ceiling. The damper can be installed in horizontal or vertical runs of vent pipe as necessary. Installation in a bull-head tee is acceptable as shown in the NFGC.
The weights on the damper should be adjusted per the damper manufacturer’s instructions for proper opera­tion.
Appliance Categories
Heaters are divided into four categories based on the pressure produced in the exhaust and the likelihood of condensate production in the vent.
Category I – A heater which operates with a non-pos­itive vent static pressure and with a vent gas temperature that avoids excessive condensate pro­duction in the vent.
Category II – A heater which operates with a non-pos­itive vent static pressure and with a vent gas temperature that may cause excessive condensate production in the vent.
Category III – A heater which operates with a positive vent pressure and with a vent gas temperature that avoids excessive condensate production in the vent.
NOTE: For additional information on appliance categorization, see appropriate ANSI Z21 Standard and the NFGC (U.S.), or B149 (Canada), or applicable provisions of local building codes.
CAUTION: When condensate traps are installed, condensate must be routed to an appropriate container for neutralization before disposal, as required by local codes.
WARNING: Contact the manufacturer of the vent material if there is any question about the appliance categorization and suitability of a vent material for application on a Category III or IV vent system. Using improper venting materials can result in personal injury, death or property damage.
NOTE: During winter months check the vent cap and make sure no blockage occurs from build-up of snow or ice.
8. Locate and guard vent termination to prevent acci­dental contact by people or pets.
9. DO NOT terminate vent in window well, stairwell, alcove, courtyard or other recessed area.
10. DO NOT terminate above any door, window, or gravity air intake. Condensate can freeze, causing ice formations.
11. Locate or guard vent to prevent condensate from damaging exterior finishes. Use a rust-resistant sheet metal backing plate against brick or mason­ry surfaces.
12. DO NOT extend exposed vent pipe outside of building. Condensate could freeze and block vent pipe.
U.S. Installations
Refer to the latest edition of the National Fuel Gas Code.
Vent termination requirements are as follows:
1. Vent must terminate at least 4 ft below, 4 ft hori­zontally from or 1 ft above any door, window or gravity air inlet to the building.
2. The vent must not be less than 7 ft above grade when located adjacent to public walkways.
3. Terminate vent at least 3 ft above any forced air inlet located within 10 ft.
4. Vent must terminate at least 4 ft horizontally, and in no case above or below unless 4 ft horizontal distance is maintained, from electric meters, gas meters, regulators, and relief equipment.
Use insulated vent pipe spacers where the vent pass­es through combustible roofs and walls.
Vent Terminal Location
1. Condensate can freeze on the vent cap. Frozen condensate on the vent cap can result in a blocked flue condition.
2. Give special attention to the location of the vent termination to avoid possibility of property dam­age or personal injury.
3. Gases may form a white vapor plume in winter. The plume could obstruct a window view if the ter­mination is installed near windows.
4. Prevailing winds, in combination with below-freez­ing temperatures, can cause freezing of condensate and water/ice build-up on buildings, plants or roofs.
5. The bottom of the vent terminal and the air intake shall be located at least 12 in. above grade, includ­ing normal snow line.
6. Un-insulated single-wall metal vent pipe shall not be used outdoors in cold climates for venting gas­fired equipment.
7. Through-the-wall vents for Category II and IV appliances and non-categorized condensing appli­ances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimen­tal to the operation of regulators, relief valves, or other equipment. Where local experience indi­cates that condensate is a problem with Category I and III appliances, this provision shall also apply.
Table K: Venting Category Requirements
26
Combustion
Air Supply
Exhaust
Configuration
Heater Venting
Category
Certified
Materials
Combustion Air
Inlet Material
Vertical Natural
From Inside Building
From Outside Building
Draft Venting
Horizontal Through-
the-Wall Venting
Vertical Natural
Draft Venting
Horizontal Through-
the-Wall Venting
I “B” Vent
III
I “B” Vent
III
Stainless Steel
(Gas Tight)
Galvanized Steel
Stainless Steel
(Gas Tight)
PVC ABS
CPVC
Canadian Installations
Refer to latest edition of B149 Installation code.
A vent shall not terminate:
1. Directly above a paved sidewalk or driveway which is located between two single-family dwell­ings and serves both dwellings.
2. Less than 7 ft (2.13 m) above a paved sidewalk or paved driveway located on public property.
3. Within 6 ft (1.8 m) of a mechanical air supply inlet to any building.
4. Above a meter/regulator assembly within 3 ft (915 mm) horizontally of the vertical centre-line of the regulator.
5. Within 6 ft (1.8 m) of any gas service regulator vent outlet.
6. Less than 1 ft (305 mm) above grade level.
7. Within the 3 ft (915 mm) of a window or door which can be opened in any building, any non-mechani­cal air supply inlet to any building or the combustion air inlet of any other appliance.
8. Underneath a verandah, porch or deck, unless the verandah, porch or deck is fully open on a mini­mum of two sides beneath the floor, and the distance between the top of the vent termination and the underside of the verandah, porch or deck is greater than 1 ft (305 mm).
5. Terminate vent at least 6 ft away from adjacent walls.
6. DO NOT terminate vent closer than 5 ft below roof overhang.
7. The vent terminal requires a 12 in. vent terminal clearance from the wall.
8. Terminate vent at least 1 ft above grade, including normal snow line.
9. Multiple sidewall vent installations require a 4 ft clearance between the ends of vent caps located on the same horizontal plane.
Changing the Flue Outlet
Follow these instructions to change the flue connec­tion from the standard top location to the rear of the heater (with optional flue exhaust tee).
1. Disconnect all electrical power from the heater (if applicable).
2. Disconnect or isolate the main gas pipe from the heater (if applicable).
3. Remove the screws, gasket and dustcover from the rear of the heater.
4. Remove the screws, stainless steel flue cover and gasket from the branch side of the tee located in the flue box at the rear of the heater.
5. Remove the screws, retaining ring and rain gasket from top of heater.
6. Remove the screws, flue collar and gasket from the run side of the tee located in the flue box on top of the heater.
7. Reverse the components and reattach in the new location.
8. Make sure that the stainless steel cover, now lo­cated on the run side of the tee, is sealed to avoid any flue gas spillage.
Venting Installation Tips
Support piping:
horizontal runs - at least every 5 ft
vertical runs - use braces
under or near elbows
CAUTION: The silicone vent gaskets must be prop­erly reinstalled to prevent flue gas leakage. Replace any torn or worn vent gaskets.
WARNING: Examine the venting system at least once a year. Check all joints and vent pipe connections for tightness, corrosion or deterioration.
27
Venting Configurations
For heaters connected to gas vents or chimneys, vent installations shall be in accordance with the NFGC (U.S.), or B149 (Canada), or applicable provisions of local building codes.
Natural Draft Vertical Venting (Category I)
Installation
Natural draft venting uses the natural buoyancy of the heated flue products to create a thermal driving head that expels the exhaust gases from the flue. The nega­tive draft must be within the range of -.01 to -.08 in. WC as measured 12 in. above the appliance flue out­let to ensure proper operation. Vent material must be listed by a nationally recognized test agency.
28
Termination
The vent terminal should be vertical and should termi­nate outside the building at least 2 ft above the highest point of the roof that is within 10 ft. The vent cap should have a minimum clearance of 4 ft horizontally from and in no case above or below (unless a 4 ft hori­zontal distance is maintained) electric meters, gas meters, regulators and relief equipment. The distance of the vent terminal from adjacent public walkways, adjacent buildings, open windows and building open­ings must be consistent with the NFGC (U.S.) or B149 (Canada). Gas vents supported only by flashing and extended above the roof more than 5 ft should be se­curely guyed or braced to withstand snow and wind loads.
Common Venting System
Manifolds that connect more than one heater to a com­mon chimney must be sized to handle the combined
CAUTION: A listed vent cap terminal, adequately sized, must be used to evacuate the flue products from the heaters.
The maximum and minimum venting length for Cate­gory I appliances shall be determined per the NFGC (U.S.) or B149 (Canada).
The diameter of vent flue pipe should be sized accord­ing to the NFGC (U.S.) and B149 (Canada). The minimum flue pipe diameter for conventional negative draft venting using double-wall Type B vent is: 6 in. for Models 399B and 499B, 8 in. for Models 649B, 749B and 899B, 10 in. for Model 989B, 12 in. for Models 1259B and 1529B, 14 in. for Models 1799B, 1999B and 2069B, and 16 in. for 2339B.
The connection from the appliance vent to the stack must be as direct as possible and shall be the same di­ameter as, or larger than, the vent outlet. The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch per linear foot from the heater to the vent terminal. The horizontal portions of the vent shall also be supported for the design and weight of the material employed to maintain clear­ances and to prevent physical damage or separation of joints.
NOTE: A vent adapter (field-supplied) must be used to connect Type B vent to the unit.
Fig. 25: Natural Draft Vertical Venting
(Category I)
29
Table L: Category I Vertical Venting
* Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details. When vertical height exceeds 25 ft, consult factory prior to installation. ** Subtract 10 ft per elbow. Max. 3 elbows. Maximum combustion air duct length terminated at 100 equivalent ft.
load. Consult available guides for proper sizing of the manifold and the chimney. At no time should the area of the common vent be less than the area of the largest heater exhaust outlet.
Common venting systems may be too large once an existing unit is removed. At the time of removal of an existing appliance, the following steps must be fol- lowed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
WARNING: Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft systems operating under a positive pressure.
CAUTION: Vent connectors for natural draft venting systems must be Type B or better.
1. Seal any unused opening in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and verify there is no block­age, restriction, leakage, corrosion or other unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the com­mon venting system are located and other spaces of the building. Turn on clothes dryers and any ap­pliance not connected to the common vent system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, at maximum
Model
No.
Certified
Venting
Material
Vent Size
Vertical Venting
Height*
Combustion
Air
Intake Pipe
Material
Air Inlet Max. Length**
Min. Max. 6” 8” 10” 12”
399B
Category I
(Type B
Equivalent)
6”
5’ 25’
Galvanized
Steel,
PVC, ABS,
CPVC
100’
499B 75’
100’
649B
8” 40’749B
899B
989B 10”
75’ 100’1259B
12”
1529B
1799B
14”
40’ 75’
1999B
2069B
2339B 16”
speed. Do not operate summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliances being inspected. Follow the manufacturer’s instructions for lighting each appliance. Adjust thermostat so appliance will operate continuously.
5. Check the pressure at a pressure tap located 12 in. above the bottom joint of the first vertical vent pipe. Pressure should be anywhere between -0.01 and -0.08 in. WC.
6. After it has been determined that each appliance remaining connected to the common venting sys­tem properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and other gas burning appliances to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so that the installation conforms with the NFGC (U.S.) or B149 (Canada). When re-sizing any portion of the common venting system, the common venting system should be re­sized to approach the minimum size as determined using the appropriate tables in the NFGC (U.S.) or B149 (Canada).
Fig. 26: Horizontal Through-the-Wall Venting (Category III)
*Requires optional vent tee.
The total length of the horizontal through-the-wall flue system should not exceed 70 equivalent ft in length. If horizontal run exceeds 70 equivalent ft, an appropri­ately sized extractor must be used. Each elbow used is equal to 10 ft of straight pipe. This will allow installa­tion in one of the four following arrangements:
70’ of straight flue pipe
60’ of straight flue pipe and one elbow
50’ of straight flue pipe and two elbows
40’ of straight pipe and three elbows
The vent cap is not considered in the overall length of the venting system.
Horizontal Through-the-Wall Venting (Category III)
Installation
These installations utilize the heater-mounted blower to vent the combustion products to the outdoors. Combustion air is taken from inside the room and the vent is installed horizontally through the wall to the out­doors. Adequate combustion and ventilation air must be supplied to the equipment room in accordance with the NFGC (U.S.) or B149 (Canada).
30
*
Table M: Category III Horizontal and Direct Venting
*Subtract 10 ft per elbow. Max. 3 elbows. Maximum combustion air duct length terminated at 100 equivalent ft.
WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.
Model
No.
Certified
Venting
Material
Vent Size
Maximum
Equivalent
Vent Length*
Combustion
Air
Intake Pipe
Material
Air Inlet Max. Length*
6” 8” 10” 12”
399B
Category III
6”
70’Room Air
40’ Ducted
Combustion Air
Galvanized
Steel,
PVC, ABS,
CPVC
100’
499B 75’
100’
649B
8”
40’
749B
899B 30’ 80’
989B 10”
75’ 100’1259B
12”
1529B
1799B
14”
40’ 75’
1999B
2069B
2339B 16”
The vent must be installed to prevent flue gas leakage. Care must be taken during assembly to ensure that all joints are sealed properly and are airtight. The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is required that:
1. The vent must be installed with a slight downward slope of not more than 1/4 inch per foot of hori­zontal run to the vent terminal.
2. The vent must be insulated through the length of the horizontal run.
For installations in extremely cold climate, it is re­quired that:
1. The vent must be installed with a slight upward slope of not more than 1/4 inch per foot of hori­zontal run to the vent terminal. In this case, an approved condensate trap must be installed per applicable codes.
2. The vent must be insulated through the length of the horizontal run.
Termination
The flue direct vent cap MUST be mounted on the ex­terior of the building. The direct vent cap cannot be installed in a well or below grade. The direct vent cap must be installed at least 1 ft above ground level and above normal snow levels. The Raypak-approved stainless steel flue direct vent cap must be used (sales order option D-15).
Use only the special gas vent pipes listed for use with Category III gas burning heaters, such as the AL29-4C stainless steel vents offered by Heat Fab Inc. (800­772-0739), Protech System, Inc. (800-766-3473), Z-Flex (800-654-5600) or American Metal Products (800-423-4270). Pipe joints must be positively sealed. Follow the vent manufacturer’s installation instructions carefully.
31
Freeze Protection
When installing this heater in an outdoor location that is susceptible to freezing, sales order option B-22 must be ordered. The B-22 option energizes the heater pump at a preset temperature drop to circulate water and reduces the possibility of freezing and dam­aging the heat exchanger or headers.
Controls
NOTE: Condensate can freeze on the vent cap.
Frozen condensate on the vent cap can result in a blocked flue condition.
NOTE: The vent cap, flow switch cover and air intake hood must be furnished by the heater manufacturer in accordance with its listing (sales order option D-11).
WARNING: Installation, adjustment and service of heater controls, including timing of various operating functions, must be performed by a qualified installer, service agency or the gas supplier. Failure to do so may result in control damage, heater malfunction, property damage, personal injury, or death.
WARNING: Turn off the power to the heater before installation, adjustment or service of the CPW board or any heater controls. Failure to do so may result in board damage, heater malfunction, property damage, personal injury, or death.
CAUTION: This appliance has provisions to be connected to more than one supply source. To reduce the risk of electric shock, disconnect all such connections before servicing.
CAUTION: Risk of electric shock: More than one disconnect switch may be required to de-energize the equipment before servicing.
1. Outdoor models must be installed outdoors and must use the outdoor vent cap, flow switch cover and air intake hood available from the manufac­turer (sales order option D-11).
2. Periodically check venting system. The heater’s venting areas must never be obstructed in any way and minimum clearances must be observed to prevent restriction of combustion and ventilation air. Keep area clear and free of combustible and flammable materials.
3. Do not locate adjacent to any window, door walk­way, or gravity air intake. The vent must be located a minimum of 4 ft horizontally from such areas.
4. Install above grade level and above normal snow levels.
5. Vent terminal must be at least 3 ft above any forced air inlet located within 10 ft.
6. Adjacent brick or masonry surfaces must be pro­tected with a rust-resistant sheet metal plate.
Outdoor Installation
Outdoor models are self-venting when installed with the optional factory-supplied outdoor vent kit and re­quire no additional vent piping. A special vent cap, flow switch cover and air intake hood are provided in accor­dance with CSA requirements, which must be installed directly on the heater. Correct clearances can be found earlier in this section.
Care must be taken when locating the heater out­doors, because the flue gases discharged from the vent cap can condense as they leave the cap. Improper location can result in damage to adjacent structures or building finish. For maximum efficiency and safety, the following precautions must be observed:
32
33
Fig. 27: Status LED Indicator Decal
Heater Sequence of Operation
Models 399B–899B
1. The black (hot) wire lead goes directly to the main power switch. This black toggle switch is located at the middle front of the control compartment.
2. When the main power switch is placed in the “ON” position, 120 VAC is applied to the 120 VAC termi­nal block on the circuit board and the 120/24 VAC transformer is powered.
3. 120 VAC is waiting at the N.O. contacts of the pump delay relay.
4. Terminals L1 and F1 of the ignition module are powered with 120VAC.
5. 120 VAC power is also applied to the control power connector on the circuit board.
6. 120 VAC power is waiting at relay contacts K-3 to energize the heater blower.
7. The 120/24 VAC transformer outputs 24 VAC.
8. 24 VAC is sent to power terminal L1 of the low water cut-off board (optional).
9. 24 VAC is applied to the red LED safety shutdown light on the front of the unit.
10. 24 VAC is applied to the alarm circuit (optional). If the E-5 sales option (Alarm) is included a 5 sec­ond time delay relay will not allow the alarm to sound unless the circuit stays energized for more than 5 seconds.
11. Power is output from terminal J5-24V of the CPW board to all of the safeties. All safeties are verified to ensure that it is safe to operate the heater. The safety components wired into the diagnostic board are: Manual reset high limit, low water cut-off (optional), blocked vent switch, low gas pressure switch (optional), and high gas pressure switch (optional).
12. Once all safeties have been verified to be closed a 24 VAC signal is sent to pin P3-16 of J-5 on the CPW board.
13. 24 VAC power now leaves pin P3-16 of J-5 on the CPW board and is sent to the auto-reset high limit (optional). If closed the power now goes to termi­nal P1-4 of J-5 on the CPW board.
14. Power is applied to terminal 24V of the pump delay relay to energize the timing circuit .
15. Relay K-1 (N.C.) will now be energized, and opens the N.C. contacts to disable the alarm (optional) and turn off the red safety shutdown light.
16. Pin P1-4 on the diagnostic board will now output a 24 VAC signal to pin 1 of the “standby switch”.
17. The “standby switch” (rocker switch) located at the lower left front of the control compartment is now
Table N: Status LED Indicators
External Lights
Light Color Indication
Power On Green
24 VAC
switched on
Call For Heat Amber
Thermostat is
closed
Burner Firing Blue
Burner(s) are
firing
Service Req’d Red
Service
required
34
powered. If the switch is “ON” and there is no call for heat (CFH), the heater is in standby mode.
18. After the standby switch is placed into the “ON” position, a 24 VAC signal is sent to the green power light on the front of the unit and the “enable/disable” connection (normally jumpered).
19. 24 VAC switched power is applied to the 24VAC terminal on the ignition module.
20. When the “enable/disable” contacts are closed, the 24 VAC signal travels to pin 1 of the stage 1 connection and waits for a CFH.
21. When a CFH occurs, a 24 VAC signal is sent from J-5 CFH on the CPW board to the amber CFH light on the front of the unit.
22. Power is now sent to terminal TRIG of the pump delay relay to energize it and close the contacts.
23. The heater pump is energized.
24. Upon sufficient flow from the heater pump, the flow switch contact will close.
25. A 24 VAC signal is then sent to the “TH” terminal located on the ignition module.
26. Once the 24 VAC “TH” signal is received, a 120 VAC signal is sent from F2 on the ignition module to the 120 VAC pilot duty terminals, located at J-14 on the circuit board.
27. The 120 VAC signal continues to the coil of relay K-3 (N.O.).
28. The 120 VAC signal continues to the 120 VAC safety terminals located at J-13 on the circuit board.
29. When the coil on relay K-3 (N.O.) is powered, the relay contacts (K-3) close and energize the blow­er(s) from the J-8 connections on the CPW board.
30. After proper air pressure is received in the air plenum, the air pressure switch(s) will close.
31. Power is applied to the optional equipment inter­lock connection (normally jumpered).
32. The 24 VAC signal is then sent to the 24 VAC safe­ty connector.
33. 24 VAC is now sent to the pressure switch (P Switch) terminal on the ignition module.
34. Once the pressure switch signal is received at the ignition module, the hot surface igniter is ener­gized by a 120 VAC signal from S-1 on the ignition module. (The hot surface igniter must draw greater than 3.2 amps while being energized or the ignition module red LED will flash 4 times and ignition lockout will occur after three tries).
35. Once the ignition module determines that the hot surface igniter is operating properly, a 24 VAC sig­nal is output from terminal “valve” of the module.
36. A 24 VAC signal is sent to gas valve 1.
37. The blue LED on the front of the unit is now illumi­nated.
38. The coil of relay K-2 (N.O.) is now energized with the (K-2) contacts closing downstream of the stage 2 and upstream of the stage 3 connections.
39. The gas coming through the burners should ignite from the heat of the hot surface igniter and the flame should carry over from one burner to the other burners of stage 1. The remote sensor is now trying to sense the flame. If the flame is not sensed within 4 seconds, the ignition module will shut down the gas valve and retry the hot surface igniter. During ignition retry the heater must per­form a 15-second pre-purge and an approximately 30-second igniter warm-up before opening gas valve 1 again. The standard ignition module will attempt ignition a maximum of three times prior to ignition lockout.
40. After gas valve 1 opens and flame rectification is received, time delay relay 1 (TD-1) is powered and starts a 5-second countdown.
41. After the 5 second countdown from TD-1, 24 VAC is waiting at pin 3 of the stage 2 connection on the CPW board.
42. After closure of the stage 2 contacts Gas valve 2 in energized.
43. After a 5 second countdown from TD-2, 24 VAC is waiting at pin 5 of the stage 3 connection on the CPW board.
44. After closure of the stage 3 contacts Gas valve 2 is energized.
35
45. The Heater is now operating at full fire.
Models 989B–2339B
1. The black (hot) wire lead goes directly to the main power switch. This black toggle switch is located at the middle front of the control compartment.
2. When the main power switch is placed in the “ON” position, 120 VAC is applied to the 120 VAC termi­nal block on the circuit board and the 120/24 VAC transformer is powered.
3. 120 VAC is waiting at the N.O. contacts of the pump delay relay.
4. Terminals L1 and F1 of the ignition module 1 are powered with 120VAC.
5. 120 VAC power is also applied to the control power connector on the circuit board.
6. Terminals L1 and F1 of the ignition module 2 are powered with 120VAC (1529B-2349B only).
7. 120 VAC power is waiting at relay contacts K-4 to energize the heater blowers.
8. The 120/24 VAC transformer outputs 24 VAC.
9. 24 VAC is sent to power terminal L1 of the low water cut-off board (optional).
10. 24 VAC is applied to the red LED safety shutdown light on the front of the unit.
11. 24 VAC is applied to the alarm circuit (optional). If the E-5 sales option (Alarm) is included a 5 sec­ond time delay relay will not allow the alarm to sound unless the circuit stays energized for more than 5 seconds.
12. Power is output from terminal J5-24V of the CPW board to all of the safeties. All safeties are verified to ensure that it is safe to operate the heater. The safety components wired into the diagnostic board are: Manual reset high limit, low water cut-off (optional), blocked vent switch, low gas pressure switch, and high gas pressure switch(s) (optional).
13. Once all safeties have been verified to be closed a 24 VAC signal is sent to pin P3-16 of J-5 on the CPW board.
14. 24 VAC power now leaves pin P3-16 of J-5 on the CPW board and is sent to the auto-reset high limit (optional). If closed the power now goes to termi­nal P1-4 of J-5 on the CPW board.
15. Power is applied to terminal 24V of the pump delay relay to energize the timing circuit.
16. Relay K-1 (N.C.) will now be energized, and opens the N.C. contacts to disable the alarm (optional) and turn off the red safety shutdown light.
17. Terminal J4-24 on the CPW board will now output a 24 VAC signal to pin 1 of the “standby switch”.
18. The “standby switch” (rocker switch) located at the lower left front of the control compartment is now powered. If the switch is “ON” and there is no call for heat (CFH), the heater is in standby mode.
19. The “standby switch” (rocker switch) located at the lower left front of the control compartment is now powered. If the switch is “ON” and there is no call for heat (CFH), the heater is in standby mode.
20. Power is applied to the coil of K-3. (If an ignition lockout occurs, ignition module 1 closes contacts allowing the 24VAC from K-3 to go to ground and closes the contacts to allow the unit to fire at stage
3.)
21. After the standby switch is placed into the “ON” position, a 24 VAC signal is sent to the “enable/disable” connection (normally jumpered).
22. 24 VAC switched power is applied to the 24VAC terminals on ignition modules 1 and 2.
23. When the “enable/disable” contacts are closed, the 24 VAC signal travels to pin 1 of the stage 1 connection and waits for a CFH.
24. Power is now sent to terminal TRIG of the pump delay relay to energize it.
25. The heater pump is energized.
26. Upon sufficient flow from the heater pump, the flow switch contact will close.
27. A 24 VAC signal is now sent to the “TH” terminal located on ignition module 1 and to the N.O. con­tacts of K-2 and K-3.
28. Once the 24 VAC “TH” signal is received, a 120 VAC signal is sent from F2 on ignition module 1 to
36
the 120 VAC pilot duty terminals, located at J-14 on the circuit board.
29. The 120 VAC signal continues to the coil of relay K-4 (N.O.).
30. The 120 VAC signal continues to the 120 VAC safety terminals located at J-13 on the circuit board.
31. When the coil on relay K-4 (N.O.) is powered, the relay contacts (K-4) close and energize the blow­ers from the J-8 connections on the CPW board.
32. After proper air pressure is received in the air plenum, the air pressure switches will close.
33. Power is applied to the optional equipment inter­lock connection (normally jumpered).
34. The 24 VAC signal is then sent to the 24 VAC safe­ty connector.
35. 24 VAC is now sent to the pressure switch (P Switch) terminal on the ignition modules.
36. Once the pressure switch signals are received at both ignition modules, hot surface igniter 1 is ener­gized by a 120 VAC signal from S-1 on ignition module 1. (The hot surface igniter must draw greater than 3.2 amps while being energized or ignition lockout will occur after three tries.)
37. Once ignition module 1 determines that hot sur­face igniter 1 has heated up and operating properly, a 24 VAC signal is output from terminal “valve” on module 1.
38. 24 VAC signal is sent to gas valve 1.
39. The blue LED on the front of the unit is now illumi­nated.
40. The coil of relay K-2 (N.O.) is now energized with the (K-2) contacts closing downstream of the stage 2 connections and upstream of the stage 3 connections.
41. The gas coming through the burners should ignite from the heat of hot surface igniter 1 and the flame should carry over from one burner to the other burners of stage 1. The remote sensor is now try­ing to sense the flame. If the flame is not sensed within 4 seconds, the ignition module will shut down the gas valve and retry the hot surface ignit­er. During ignition retry the heater must perform a
15-second pre-purge and an approximately 30­second igniter warm-up before opening gas valve 1 again. The standard ignition module will attempt ignition a maximum of three times prior to ignition lockout.
42. After gas valve 1 opens and flame rectification is received, time delay relay 1 (TD-1) is powered and starts a 5-second countdown.
43. After the 5 second countdown from TD-1, the con­tacts close time delay relay 2 receives 24 VAC.
44. After 5 seconds gas valve 1a is now energized allowing the remainder of stage 1 to fire.
45. After the 5-second countdown from TD-2 the inter­nal contacts close allowing 24 VAC to sit at pin 3 of the stage 2 connection on the CPW board.
46. The temperature controller closes the stage 2 con­tacts and gas valve 2 in energized.
47. The temperature controller closes the stage 3 con­tacts at J-3 on the CPW board.
48. 24 VAC signal is received at gas valve 3 (Model 1259B only).
Models 1529B–2339B Only
49. Power is applied to the “TH” terminal of ignition module 2.
50. Once the “TH” signal is received at ignition module 2, hot surface igniter 2 is energized by a 120 VAC signal from S-1 on ignition module 2. (The hot sur­face igniter must draw greater than 3.2 amps while being energized or ignition lockout will occur after three tries.)
51. Once the ignition module determines that the hot surface igniter has heated up and operating prop­erly, a 24 VAC signal is output from pin “valve” on the module.
52. 24 VAC signal is received at gas valve 3.
53. The coil of relay K-5 (N.O.) is now energized with the (K-5) contacts closing downstream of the stage 4 connections.
54. Remote flame sensor 2 is trying to rectify flame.
55. Power is now applied to time delay relay 3 and the contacts of TD-3 located upstream of the stage 4
37
The optional single-try ignition module will lock out after failing to light one time. To reset it, press and release the small, recessed black push button located inside of the cut-out on the lower right-hand corner of the ignition module case (see Fig. 28). Turning off the power to the heater WILL NOT reset the ignition mod­ule.
High Limit (Manual Reset)
The heater is equipped with a manual reset high limit temperature device. Push the reset button and adjust the setting to 40 - 50°F above desired operating tem­perature.
Flow Switch
This dual-purpose control, mounted and wired in series with the main gas valve, shuts off heater in case of pump failure or low water flow.
Operating Control
The heater may be equipped with different types of operating controls. Consult the individual control data
Fig. 29: High Limit (Manual Reset)
Fig. 30: Flow Switch
Ignition Module
When additional heat is needed, the combustion air blower starts to purge air from the combustion cham­ber for about 15 seconds. On proof-of-air flow, the air­proving switch closes and the igniter is energized. To ensure safe operation, the gas valve cannot open until the igniter is verified. The main burner is automatically lit when the device is powered and pre-purged. The heater performs its own safety check and opens the main valve only after the igniter is proven to be capa­ble of ignition.
Fig. 28: Ignition Module
Table O: Ignition Module Diagnostic LED Codes
connection close after 5 seconds.
56. The stage 4 temperature controller contacts close.
57. Power is sent to gas valve 4.
58. The heater is now operating at full fire.
The standard ignition module will attempt to light three times before locking out. To reset it, turn off power to the heater, wait 30 seconds and re-apply power.
Reset button on 1-try module
Code
Condition
On
Off
1 Flash
2 Flashes
3 Flashes Ignition lockout
4 Flashes Low igniter current
5 Flashes
6 Flashes
flashing normal on start-up
Low 24 VAC, check control
System OK;
No faults present
Possible control fault;
Check power
Low air pressure, brief
Flame in combustion
chamber; No call for heat
supply voltage
Internal fault;
Replace module
Fig. 31: Operating Control
Low Water Cut-Off (Optional)
The low water cut-off automatically shuts down the burner whenever water level drops below the level of the sensing probe. A 5-second time delay prevents premature lockout due to temporary conditions such as power fluctuations or air pockets.
Fig. 32: Low Water Cut-Off
High and Low Gas Pressure Switches
The low gas pressure switch (standard on models 989B–2339B, optional on models 399B–899B) con­nection mounts upstream of the gas valve to ensure that sufficient gas pressure is present for proper regu­lator performance. The low gas pressure switch automatically shuts down the heater if gas supply drops below the factory setting of 5.0 in. WC for natu­ral gas, and 10.0 in. WC for propane gas.
The high gas pressure switch (optional) connection mounts down-stream of the stage-1 gas valve. If the gas pressure regulator fails, the high gas pressure
sheets supplied with your heater paperwork. See the General Safety Section for safety precautions con­cerning domestic hot water applications.
Fig. 33: High/Low Gas Pressure Switch
Fig. 34: Fan-Proving Switch
Fig. 35: Blocked Vent Switch
switch automatically shuts down the burner. The high gas pressure switch automatically shuts down the heater if gas manifold pressure rises above the recom­mended setting of 5.0 in. WC for natural gas, and 11.5 in. WC for propane gas.
38
NOTE: Some jurisdictions may require two high gas pressure switches on models 1529B–2339B due to two ignition modules.
NOTE: The wiring diagrams in this manual show all standard options. Refer to the large wiring diagram provided with your heater for options installed on your specific unit(s).
Wiring Diagram - Models 399B–1259B
39
Wiring Diagram - Models 1529B–2339B
40
START-UP
Pre Start-up
Filling System (Heating Boilers)
Fill system with water. Purge all air from the system. Lower system pressure. Open valves for normal sys­tem operation, and fill system through feed pressure. Manually open air vent on the compression tank until water appears, then close vent.
Air Purge (Domestic Hot Water Heaters)
Purge all air from system before lighting heater. This can be normally accomplished by opening a down­stream valve.
Venting System Inspection
1. Check all vent pipe connections and flue pipe ma­terial.
2. Make sure vent terminations are installed per code and are clear of all debris or blockage.
For Your Safety
This appliance has a hot surface igniter. It is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.
BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell near the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any telephone in your building.
Immediately call your gas supplier from a neigh­bor’s telephone. Follow the gas supplier’s instructions.
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
If you cannot reach your gas supplier, call the fire department.
Use only your hand to push in or turn the gas con­trol knob. Never use tools. If the knob will not turn by hand, do not try to repair it, call a qualified serv­ice technician. Forced or attempted repair may result in a fire or explosion.
Do not use this appliance if any part has been under water, immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
Check around unit for debris and remove com­bustible products, i.e. gasoline, etc.
Pre Start-up Check
1. Verify heater is filled with water.
2. Check system piping for leaks. If found, repair immediately.
3. Vent air from system. Air in system can interfere with water circulation.
4. Purge air from gas line up to heater.
Initial Start-up
Tools Needed
(1) 12-0-12, 24” scale U-tube manometer
(4) 6-0-6, 12” scale U-tube manometers (mini­mum)
(1) Screwdriver
(1) Multi-meter
(1) 3/16” Allen wrench
NOTE: Digital manometers are not recommended.
41
Preparation
Check Power Supply
With multi-meter at incoming power, check voltage between:
Hot - Common (≈120 VAC)
Hot - Ground (≈120 VAC)
Common - Ground (< 1 VAC)
Attach Manometers to Measure Pressures
1. Turn off main gas valve.
2. Attach 24” scale manometer to the first main gas shut-off valve pressure tapping.
3. Attach (1) 12” scale manometer to the outlet side of the second main gas shut-off valve pressure tapping.
4. Attach (1) 12” scale manometer near the fan-prov­ing switch. Pull black cap from air pressure switch tee and connect the manometer. NOTE: Retain caps for reinstallation later.
Check Gas Supply Pressure
1. Slowly turn on main gas shut-off valve.
2. Read the gas supply pressure from the manome­ter; minimum supply pressure for natural gas is 5.0 in. WC, recommended supply is 7.0 in. WC, mini­mum supply pressure for propane gas is 11.0 in. WC (dynamic readings, all stages firing).
3. If the pressure is > 14.0 in. WC, turn off the valve.
4. Check if the service regulator is installed and/or adjust the service regulator.
WARNING: Do not turn on gas at this time.
WARNING: If Common - Ground is > 1 VAC,
STOP: Contact electrician to correct ground failure. Failure to do this may burn out 120V-24V transformer, or may cause other safety control damage or failure.
Start-Up
Blower Adjustment
1. Turn off power.
2. Unplug cap at pressure switches and connect ma­nometer(s) to the tee.
3. Close all manual firing valves.
4. Turn power on.
5. Check manometers attached to fan pressure switch. The reading should be 1.4 ± 0.1 in. WC for propane gas and natural gas. If not, adjust the air shutter on the blowers to attain the correct value.
6. Turn power off.
7. Reconnect this cap.
Main Burner Adjustment
1. Turn off unit.
2. Open manual firing valves.
3. Turn on the unit, wait 15 seconds, and the igniter should glow. Look into sight glass located at each end of the heater to check igniter operation. Gas valves should open in 45-60 seconds.
4. If burner does not light on first trial. It will retry, up to three times.
5. Main burner ignition: Check manifold gas pressure at gas valve outlet pressure tap. This should read
3.5 ± 0.1 in. WC for natural gas and 10.5 ± 0.1 in. WC for propane gas.
6. If the pressure reading differs by more than ± 0.1 in. WC, remove screw cover from the gas pres­sure regulator and adjust main burner manifold pressure. Replace the screw cover. Repeat steps 2 to 5 on other valves as necessary.
CAUTION: Special manifold and air settings may be required. Verify rating plate and blower housing.
42
Safety Inspection
1. Check all thermostats and high limit settings.
2. During the following safety checks leave manome­ters hooked up, check and record.
3. If other gas-fired appliances in the room are on the same gas main, check all pressures on the Delta Limited with all other equipment running.
4. Check thermostats for ON-OFF operation.
5. Check high limits for ON-OFF operation.
6. While in operation, check flow switch operation.
7. Check the low gas pressure switch. (For proper adjustment, use the attached manometers, if available, to set pressure. The scales on the switch are approximate only.) Low gas pressure switch must be set at 5.0 in. WC for natural gas and 10.0 in. WC for propane gas.
8. Make sure that the high gas pressure switch (op­tional) is set to 1.0 in. WC above manifold pressure.
Follow-Up
Safety checks must be recorded as performed.
Turn heater on. After main burner ignition:
1. Check manometer for proper reading.
2. Cycle heater several times and re-check readings.
3. Remove all manometers and replace caps and screws.
4. Replace all gas pressure caps.
5. Check for gas leaks one more time.
Pilot Turn-Down Test
The Delta Limited heaters, depending on their size, have two to five burner sections. Each burner section is supplied gas by two gas valves incorporated into a single valve body. A maximum of three burner sections may be controlled by a single hot surface ignition sys­tem. The middle of the three burner sections is ignited directly with a hot surface ignition system.
The burner section that is ignited directly by the hot surface ignition system serves as a supervised pilot to light the burner sections on either side of it. The burn­er sections on either side of the supervised section (pilot) are electrically interlocked with the supervised ignition system so as they are not energized unless flame is proven on the center section which is acting as a pilot to light the right and left-hand sections.
The pilot turn-down test is conducted as follows:
1. Turn off manual valves on non-supervised burner sections.
2. Turn on electrical power and adjust thermostat to call for heat.
3. Wait for completion of ignition sequence to light burner section being utilized as a pilot for those turned off in step 1 above.
4. Gradually reduce manifold pressure (flame) on supervised burner section by slowly closing man­ual gas valve. Watch for shut-down due to loss of supervised flame signal as pressure is being re­duced. Flame signal should be lost before manifold pressure goes below 2.0 in. WC for nat­ural gas and 6.0 in. WC for propane gas.
Leak Test Procedure: Dual-Seat Gas Valves
Proper leak testing requires three pressure test points in the gas train.
Test point A is upstream of the automatic gas valve. On the first automatic valve, this is a bleedle valve. On the other valves, this is a plugged port. The bleedle valve on the first valve may be used for all the other valves as well.
Test point B is a bleedle valve located between the two automatic gas valve seats.
Test point C is located downstream of both automatic gas valve seats and upstream of the manual valve. On the manual valve, this is a bleedle valve. Identical readings will be found at the plugged port labeled as Alternate C.
Refer to Fig. 36. The numbers on the diagram refer to the steps below:
These tests are to be conducted with the electrical power to the heater turned off.
43
1. Manually close the downstream leak test valve.
2. Open test point A and connect a manometer to it. Verify that there is gas pressure and that it is with­in the proper range (NOTE: must not exceed 14.0 in. WC).
3. Open test point B and connect a rubber tube to it. Connect the other end of the tube to a manometer and look for a build-up of pressure. Increasing pressure indicates a leaking gas valve.
4. Next, close the upstream manual gas valve and remove the manometer from test point A and from test point B. Connect a rubber tube from test point A to test point B and open the upstream manual gas valve. Make sure that test points A & B have been opened so as to allow gas to flow. This will bring pressure to the second valve seat.
5. Open test point C and connect a second rubber tube to it. Connect the other end of the tube to a manometer and look for a build-up of pressure. In­creasing pressure indicates a leaking gas valve.
6. Remove rubber tube and manometers. Close each test point valve as the tubes are removed.
7. Connect a manometer to each test point (one at a time) and look for a build-up of pressure. If a build­up of pressure is detected, check each test point valve to see if it is tightly closed. If leak persists, replace test point valve(s).
8. After no leakage has been verified at all valve seats and test valves, open downstream leak tests valve and restore electrical power to heater.
Fig. 36: Leak Test
This completes leak testing for a single Delta Limited manifold riser. Repeat steps 1-8 for each riser.
Post Start-Up Check
Check off steps as completed:
1. Verify that the heater and heat distribution units or storage tank are filled with water.
2. Confirm that the automatic air vent (if used) was opened two full turns during the venting proce­dure.
3. Verify that air has been purged from the system.
4. Verify that air has been purged from the gas pip­ing, and that the piping has been checked for leaks.
5. Confirm that the proper start-up procedures were followed.
6. Inspect burner to verify flame.
7. Test safety controls: If heater is equipped with a low water cut-off or additional safety controls, test for operation as outlined by manufacturer. Burner should be operating and should go off when con­trols are tested. When safety devices are restored, burners should re-ignite after pre-purge time delay.
8. Test limit control: While burner is operating, move indicator on high limit control below actual water temperature. Burner should go off while blower and circulator continue to operate. Raise setting on limit control above water temperature and burn­er should re-ignite after pre-purge time delay.
9. Test ignition system safety device:
a. Turn on manual gas valve. Turn power on.
b. Set thermostat to call for heat.
c. When the heater is in operation, pull cap off of
tee in air switch hose. The burner should go off immediately.
d. Wait 5 minutes.
e. Reattach cap on tee. Burner should re-ignite
after pre-purge time delay.
44
10. To restart system, follow lighting instructions in the Operation section.
11. Check to see that the high limit control is set above the design temperature requirements of the system.
For multiple zones: Check to make sure the flow is adjusted as required in each zone.
12. Check that the heater is cycled with the thermo­stat. Raise to the highest setting and verify that the heater goes through the normal start-up cycle. Re­duce to the lowest setting and verify that the heater goes off.
13. Observe several operating cycles for proper oper­ation.
14. Set the room thermostat or tankstat to desired temperature.
15. Review all instructions shipped with this heater with owner or maintenance person, return to enve­lope and give to owner or place the instructions inside front panel on heater.
OPERATION
Lighting Instructions
1. Before lighting, make sure you have read all of the safety information in this manual.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
5. Remove upper front panel.
6. Turn on main manual gas valve.
7. Wait 5 minutes to clear out any gas. Then smell for gas, especially near the floor. If you then smell gas, STOP! Follow the steps in the safety informa­tion on the front cover of this manual. If you do not smell gas, go to next step.
8. Turn on all electrical power to the appliance.
9. Set thermostat to desired setting. The appliance will operate. The igniter will glow after the pre­purge time delay (15 seconds). After igniter reaches temperature (45 seconds) the main valve will open. System will try for ignition three times. If flame is not sensed, lockout will commence.
10. If the appliance will not operate, follow the instruc­tions “To Turn Off Gas To Appliance,” and call your service technician or gas supplier.
11. Replace access panel.
12. If heater fails to start, verify the following:
a. There are no loose connections or that the
service switch is off.
b. High temperature limit switch is set above wa-
ter temperature.
c. Thermostat is set above room temperature.
d. Gas is on at the meter and the heater.
e. Incoming gas pressure to the gas valve is
NOT less than 5.0 in. WC for natural gas, 11.0 in. WC for propane gas.
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electrical power to the appliance if serv­ice is to be performed.
3. Remove upper front panels.
4. Turn off main manual gas valve.
5. Replace access panel.
45
TROUBLESHOOTING
jump
r
p
(
)
g
y
p
y
r
46
Does the power switch
provide power to the
Step 1
Step 2
Step 3
control panel?
YES
YES
Is there a call for heat?
YES
Do the combustion air
blowers come on?
Is enable/disable
NO
er intact (J1)?
NO
NO
NO
Reattach
Unit is in standby mode.
Is there 120VAC at J8
Connecto
on the CPW board?
YES
Check the switch
and/or line voltage
Replace ignition module
Check all safety limit devices and voltage from the transformer to J10 on
CPW board.
NO
NO
Does F2 on ignition module
have 120VAC?
YES
Step 4
Step 5
Step 6
YES
Is 24VAC at PS on ignition module? Is
connecting plug
secure?
Does igniterprove?
YES
Is the flame
sensor signal to
the ignition module greater than 4 uA DC?
YES
Is 24VAC at present at TH (J3 & J12 on CPW
board and orange wire on ignition module)?
NO
YES
NO
Check Amp draw during heat-up for 3.2 Amps or
reater.
NO
Is air pressure switch(s) and
J2 of CPW board (N.O.)
owered?
NO
Does air pressure switch(s)
have correct pressure?
1.4” W.C.
NO
YES
NO
Replace HSI
Are the gas valve
settings correct?
YES
NO
Check flow switch, all
connectors on CPW board
and controller.
Is there continuity from the
fan relay to fan(s)?
YES
YES
Replace air
ressure switch
Is air switch
bouncing?
NO
NO
YES
Check the fan relay. Is there
120VAC at K3 relay?
YES
Replace fan rela
Replace fan
Correct the air settings or
you may have to clean
burners, heat exchanger
and/or air filter.
YES
Readjust to 3.5” W.C.
gas.
Is the unit running?
NO
NO
Step 7
Is the unit running?
NO
Call our Technical Service Department
1-800-947-2975 Outside California
1-800-627-2975 Inside California
YES
Is static and dynamic inlet
manifold gas pressure correct?
Is downdraft present?
NO
The unit is oka
YES
Clean or replace flame senso
Replace gas valve
MAINTENANCE
Suggested Minimum Maintenance Schedule
Regular service by a qualified service agency and maintenance must be performed to ensure maximum operating efficiency.
Maintenance as outlined below may be performed by the owner.
Daily
1. Check that the area where the heater is installed is free from combustible materials, gasoline, and other flammable vapors and liquids.
2. Check for and remove any obstruction to the flow of combustion or ventilation air to heater.
Monthly
1. Check for piping leaks around circulators, mixing valves, relief valves, and other fittings. If found, repair at once. DO NOT use petroleum-based stop-leak compounds.
2. Visually inspect burner flame.
3. Visually inspect venting system for proper func­tion, deterioration or leakage.
4. Check air vents for leakage.
Yearly (Beginning Of Each Heating Season)
Schedule annual service call by qualified service agency.
1. Visually check top of vent for soot. Call service person to clean. Some sediment at bottom of vent is normal.
2. Visually inspect venting system for proper func­tion, deterioration or leakage.
3. Check that area is free from combustible materi­als, gasoline, and other flammable vapors and liquids.
4. Check for and remove any obstruction to the flow of combustion or ventilation air to heater.
5. Follow pre-start-up check in the Start-up section.
6. Visually inspect burner flame. It should be light blue. Remove and visually inspect hot surface ig­niter and sensor for damage, cracking or debris build-up.
7. Check operation of safety devices. Refer to manu­facturers’ instructions.
8. Follow oil-lubricating instructions on circulator if required. Over-oiling will damage circulator. Water-lubricated circulators do not need oiling.
9. To avoid potential of severe burn, DO NOT REST HANDS ON OR GRASP PIPES. Use a light touch; return piping will heat up quickly.
10. Check blower and blower motor.
11. Check for piping leaks around circulators, relief valves and other fittings. Repair, if found. DO NOT use petroleum-based stop-leak.
12. Clean air filter.
Periodically
1. Check relief valve. Refer to manufacturer’s in­structions on valve.
2. Test low water cut-off, if used. Refer to manufac­turer’s instructions.
3. Clean screen and air filter in intake.
Preventive Maintenance Schedule
The following is required procedure in CSD-1 states and good practice for all Delta Limited installations.
Daily
1. Check gauges, monitors and indicators.
2. Check instrument and equipment settings. (See “Post Start-Up Check” on page 44.)
3. Check burner flame. (Should see light blue flame).
47
Weekly
For low-pressure heaters, test low-water cut-off device. (With at least one stage of the appliance on, depress the low water cut-off test button, appliance should shut-off and ignition fault light should come on. Depress reset button to reset).
Monthly
1. Check flue, vent, stack, or outlet dampers.
2. Test fan air pressure. (See “Blower Adjustment” on page 42.)
3. Test high and low gas pressure interlocks (if equipped). (See “Safety Inspection” on page 43.)
Semi-Annually
1. Recalibrate all indicating and recording gauges.
2. Check flame failure detection system components. (See “Pilot Turn-Down Test Procedure,” page 43.)
3. Check firing rate control by checking the manifold pressure. (See “Main Burner Adjustment” on page
42.)
4. Check piping and wiring of all interlocks and shut­off valves.
Annually
1. Test flame failure detection system and pilot turn­down. (See “Pilot Turn-Down Test Procedure,” page 43.)
2. Test high limit and operating temperature. (See “Post Start-Up Check,” page 44.)
3. Check flame sensors.
4. Conduct a combustion test at full fire. Carbon di­oxide should be 7.5 to 8.5% at full fire for natural gas, and between 9.2 to 9.8% for propane gas (Carbon monoxide should be < 150 ppm).
5. Check coils for 60 cycle hum or buzz. Check for leaks at all valve fittings using a soapy water solu­tion. Test other operating parts of all safety shut-off and control valves and increase or decrease set­tings (depending on the type of control) until the safety circuit opens. Reset to original setting after each device is tested.
6. Perform leakage test on gas valves. (See Fig. 36.)
7. Test air switch in accordance with manufacturer’s instructions. (Turn panel switch to the “On” posi­tion until blower is proven, then turn the switch to “Off”.
8. Inspect and clean burners as necessary.
As Required
1. Recondition or replace low water cut-off device (if equipped).
2. Check drip leg and gas strainers.
3. Perform flame failure detection and pilot turn­down tests.
4. Check igniter. (Resistance reading should be 42­70 ohms at ambient temperature.)
5. Check flame signal strength. (Flame signal should be greater than 1 microamp).
6. Test safety/safety relief valves in accordance with ASME Heater and Pressure Vessel Code Sections VI and VII.
48
APPENDIX
Inside Air Contamination
All heaters experience some condensation during start-up. The condensate from flue gas is acidic. Combustion air can be contaminated by certain vapors in the air which raise the acidity of the condensate. Higher acidity levels attack many materials including stainless steel, which is commonly used in high effi­ciency systems. The heater can be supplied with corrosion-resistant, non-metallic intake air vent materi­al. You may, however, choose to use outside combustion air for one or more of these reasons:
1. Installation is in an area containing contaminants listed below which will induce acidic condensation.
2. You want to reduce infiltration into your building through openings around windows and doors.
3. You are using AL29-4C stainless steel vent pipe, which is more corrosion-resistant than standard metallic vent pipe. In extremely contaminated ar­eas, this may also experience deterioration.
Products causing contaminated combustion air:
spray cans containing chloro/fluorocarbons
permanent wave solutions
chlorinated waxes/cleaners
chlorine-based swimming pool chemicals
calcium chloride used for thawing
sodium chloride used for water softening
refrigerant leaks
paint or varnish removers
hydrochloric acid/muriatic acid
cements and glues
antistatic fabric softeners used in clothes dryers
chloride-type bleaches, detergents, and cleaning solvents found in household laundry rooms
adhesives used to fasten building products
similar products
Areas where contaminated combustion air commonly exists:
dry cleaning/laundry areas
metal fabrication plants
beauty shops
refrigeration repair shops
photo processing plants
auto body shops
plastic manufacturing plants
furniture refinishing areas and establishments
new building construction
remodeling areas
open pit skimmers
Check for areas and products listed above before in­stalling heater. If found, remove products permanently.
49
LIMITED PARTS WARRANTY
DELTA LIMITED – TYPES H AND WH
MODELS 399B–2339B
SCOPE
Raypak, Inc. (“Raypak”) warrants to the original owner that all parts of this heater whic h are actually manufactured by Raypak will be free from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this Wa rranty. Labor charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this Warranty but a re the owner’s responsibility.
HEAT EXCHANGER WARRANTY
Domestic Hot Water Five (5) years fr om date of heater installation. Includes copper heat exchanger with bronze and cast iron waterways. Ten (10) years fr om date of heater installation. Includes only cupro-nickel heat exchanger with bronze or cast iron waterways. Space Heating (Closed Loop System) Ten (10) years fr om date of heater installation. Includes both cupro-nickel and copper heat exchanger with bronze or cast iron water­ways. Thermal Shock Warranty Twenty (20) years from date of heater installation against “Thermal Shock” (excluded, however, if caused by heater operation at large changes exceeding 150°F between the water temperature at intake and heater temperature, or operating at heater temperatures exc eed­ing 230°F).
ANY OTHER PART MANUFACTURED BY RAYPAK
One (1) year warranty from date of heater installation, or eighteen (18) months from date of factory shipment based on Raypak’s records, whichever comes first.
SATISFACTORY PROOF OF INSTALLATION DATE, SUCH AS INSTALLER INVOICE, IS REQUIRED. TH IS WARRANTY WILL BE VOID IF THE HEATER RATING PLATE IS ALTERED OR REMOVED.
ADDITIONAL WARRANTY EXCLUSIONS
This warranty does not cover failures or malfunctions resulting from:
1. Failure to properly install, operat e or maintain the heater in accordance wit h our printed instructions provided;
2. Abuse, alteration, accident, fire, flood and the like;
3. Sediment or lime build-up, freezing, or other conditions causing inadequate water c irculation;
4. High velocity flow exceeding heater design rates;
5. Failure of connected systems devices, s uch as pump or controller;
6. Use of non-factory authorized accessories or other components in conjunction with the heater system;
7. Failing to eliminate air from, or replenish water in, the connected water system;
8. Chemic al contamination of combustion air or use of chemical additives to water.
PARTS REPLACEMENT
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if requested, with transportation charges prepaid, and all applicable warranty conditions found satisfied. The replacement part will be warra nted for only the unexpired portion of the or iginal warranty. Raypak makes no warranty whatsoever on parts not manufactur ed by it, but R aypak will apply any such warranty as may be provided to it by the parts manufacturer.
TO MAKE WARRANTY CLAIM
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and descriptio n of the prob­lem. The installer must then notify his Raypak distributor for instructions regarding the claim. If either is not available, co ntact Service Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnar d, CA 93030 or call (805) 278- 5300. In all cases proper authorization must fir st be received from Raypak before replacement of any part.
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY
This is the only warranty given by Raypak. No one is author ized to make any other warranties on Raypak’s behalf. THIS WARRA NTY IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MER­CHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. RAYPAK’S SOLE LIABILITY AND THE SOLE REMEDY AGAINST RAYPAK WITH RESPECT TO DEFECTIVE PARTS SHALL BE AS PROV IDED IN THIS WARRANTY. IT IS AGREED THAT RAYPAK SHALL HAVE NO LIABILITY, WHETHER UNDER THIS WARRANTY, OR IN CONTRACT, TORT, NEGLIGENCE OR OTHERWISE, FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGE, INCLUDING DAMAGE FROM WATER LEAKAGE. Some states do not allow limitations on how long an implied warranty lasts, or for the exclusion of incident al or consequential damages. So the abov e limitation or exclusion may not apply to you.
This Limited Warranty gives you specific legal rights. You may als o have other rights w hich may vary from state to state. We su ggest that you complete the information below and retain this certificate in the event warranty service is needed. Reasonable proof of the effective date of the warranty (dat e of installation) must be presented, otherwis e, the effective date will be based on the rate of manuf acture plus thirty (30) days.
Original Owner Model Number
Mailing Address Serial Number
Date of Installation
City State Zip Code Installation Site
Daytime Telephone Number Contractor/Installer
RAYPAK, INC 2151 Eastman Avenue Oxnard, CA 93030-9786 (805) 278-5300 Fax (800) 872-9725 www.raypak.com
50
START-UP CHECKLIST FOR FAN-ASSISTED
51
RAYPAK PRODUCTS
This start-up checklist is to be completely filled out by the service technician starting up the Raypak Boiler or Heater for the first time. All information may be used for warranty purposes and to ensure that the installation is correct. Additionally this form will be used to record all equipment operation functions and required settings.
GAS SUPPLY DATA CLEARANCES
Regulator Model & Size _________ / ______CFH Front Clearance _______________In. Gas Line Size (in room) ________________In. NPT Right Side Clearance _______________In. Length of Gas Line ________________Eq Ft Left Side Clearance _______________In. Low Gas Pressure Setting ________________In. WC Rear Clearance _______________In. High Gas Pressure Setting ________________In. WC Overhead Clearance _______________In. Gas Shut-Off Valve Type ________________ ( Ball, Lube cock)
Sediment Trap ________________Y/N Voltage Supply (VAC) No Load______ Load_____ Port _______Std______Full Voltage -24 VAC _______________VAC Voltage Com to Ground _______________VAC
VISUAL INSPECTION OF COMPONENTS
Verify inspection was done and condition of components are in good working order with a “yes” Wiring Harness _________________ Y/N Operating Control Setting _______________deg F Burner/s (flame) _________________ Y/N Refractory (visual) _________________ Y/N Sketch plumbing on reverse side Remote flame sense _________________ Y/N
Covers in place for outdoor _________________ Y/N Flow Rate in GPM or Delta T _______________If Avail
VENTING
Vent Size: _____________ Stack Height:_______ Low Water Cutoff _______________Test Category: _________ sketch vent on reverse side *** Vent Material: __________________ Plumbing Size _______________ Vent Termination Type: __________________ Pump Size: _________ Combustion Air Openings: Low __________ in2 Impeller trim____________ Pump Model___________ Ventilation air High __________ in2 Louvers __________________ Screens________________
Pump Economaster setting _______________Minutes
EMISSIONS SETTINGS AND TEST INFORMATION
(AT FULL FIRE)
Blower Pressure Setting _________________In. WC See manual or card tag Supply Gas Pressure Verify stable pressure static & Pilot Gas Pressure _________________In. WC See manual or card tag Manifold Gas Pressure _________________In. WC See manual or card tag
The following measurements must be obtained with a Combustion Analyzer. NOX _________________PPM Less than 20 PPM (If required by Certifying Agency) Free Oxygen _________________% See manual CO _________________PPM Less than 150 PPM CO2 _________________% See manual
Model Number: ______________________________ Serial Number: _______________________________ *** Note: draw venting with details, such as extractors, barometric dampers, blast dampers or draft inducers
_________________In. WC dynamic condition
ELECTRICAL
Hot Surface Igniter Auto High Limit Setting Manual Reset High Limit Setting
_______________Ohms _______________deg F _______________deg F
WATER SUPPLY
Measure flow rate at full fire
Number of Tanks and Size Qty____ _______Gallons
(boiler) Pump HP: ______
Nominal Factory Recommended Settings
See manual or card tag
Site Altitude Above Sea Level __________________Ft.
Job Name _______________________________________________________________________________________
Address _________________________________________________________________________________________
Physical Location of Boiler: Indoors______; Outdoors______; Ground Level______; Roof______; Below Grade______
Mechanical Contractor / Installer _______________________________________________________________________
Date and Time of Start-up _____________Print Name and Signature of Start-up Technician_________________________
Information must be faxed to: (805) 278-5471 in order to ensure warranty consideration Attn: Service Manager
www.raypak.com
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (805) 278-5468
Litho in U.S.A.
Loading...