Raypak 992C, 1262C, 1532C, 2072C, 2342C Installation & Operating Instructions Manual

...
INSTALLATION & OPERATING
LLC
®
INSTRUCTIONS
Models 992C–2342C
Types H, WH & P
WARNING: If these instructions are not followed exactly, a fire or explosion may
result causing property damage, personal injury or death.
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas
supplier's instructions.
• If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
This manual should be maintained in legible condition and kept adjacent to the heater or in another safe place for future reference.
CATALOG NO. 1000.512A Effective: 06-15 -18 Replaces: 02-15-17 P/N 241664 Rev. 2
Revision 2 reflects the following changes:
Removed California Proposition 65 warning on page 4.
2
CONTENTS
WARNINGS 4 BEFORE INSTALLATION 5
Product Receipt 5 Model Identification 5 Ratings and Certifications 5 Installations at Elevation 5 Component Locations 6 General Information 7
GENERAL SAFETY 8
Time/Temperature Relationships in Scalds 8
INSTALLATION 9
Installation Codes 9 Equipment Base 9 Stacking 9 Clearances 11 Combustion and Ventilation Air 12 Conventional Combustion Air Supply 13 Water Piping 14 Hydronic Heating 17 Domestic Hot Water 20 Pool Heating 22 Gas Supply 25 Electrical Power Connections 26 Field Wiring Connection 28 Venting 32
Changing the Flue Outlet 34 Venting Installation Tips 34 Venting Configurations 35 Sequence of Operation 40 Controls 44 Wiring Diagrams 992C-1262C 54 Wiring Diagram 1532C-2342C 55
START-UP 56
Pre Start-up 56 Start-up 57
OPERATION 60
Lighting Instructions 60 To Turn Off Gas To Appliance 60
MAINTENANCE 61
Suggested Minimum Maintenance Schedule 61 Preventative Maintenance Schedule 61
APPENDIX 63
Inside Air Contamination 63
WARRANTIES 64
Type H and WH 64
Type P 65 Start-up Checklist 67 Important Instructions for the Commonwealth of Massachusetts 68
3
WARNINGS
Pay Attention to These Terms
ndicates the presence of immediate hazards which will cause severe person-
DANGER:
I al injury, death or substantial property damage if ignored.
WARNING:
CAUTION:
NOTE:
DANGER: Make sure the gas on which the heater
will operate is the same type as that specified on the heater rating plate.
WARNING: Should overheating occur or the gas supply valve fail to shut, do not turn off or disconnect the electrical supply to the heater. Instead, shut off the gas supply at a location external to the heater.
WARNING: To minimize the possibility of improper operation, serious personal injury, fire, or damage to the heater:
• Always keep the area around the heater free of combustible materials, gasoline, and other flammable liquids and vapors.
Heater should never be covered or have any blockage to the flow of fresh air to the heater.
WARNING: Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
WARNING: All venting types must be of the same material or product throughout the entire exhaust installation to ensure proper securing and sealing.
Indicates the presence of hazards or unsafe practices which could cause severe personal injury, death or substantial property damage if ignored.
Indicates the presence of hazards or unsafe practices which could cause minor personal injury or product or property damage if ignored.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
WARNING: Both natural gas and propane have an odorant added to aid in detecting a gas leak. Some people may not physically be able to smell or recognize this odorant. If you are unsure or unfamiliar with the smell of natural gas or propane, ask your local gas supplier. Other conditions, such as "odorant fade," which causes the odorant to diminish in intensity, can also hide, camouflage, or otherwise make detecting a gas leak by smell more difficult.
WARNING: UL recognized fuel gas detectors are recommended in all enclosed propane and natural gas applications wherein there is a potential for an explosive mixture of fuel gas to accumulate and their installation should be in accordance with the detector manufacturer's recommendations and/or local laws, rules, regulations, or customs.
WARNING: Risk of electrical shock. More than one disconnect switch may be required to deenergize the equipment before servicing.
CAUTION: Operation of this heater in low­temperature systems requires special piping. Harmful internal condensation will occur if the inlet water temperature does not exceed 105°F. Warranty claims will be denied when condensation occurs.
CAUTION: If this heater is to be installed above radiation level, it must be provided with a low water cut-off device at the time of heater installation.
CAUTION: If this heater is to be installed in a negative or positive pressure equipment room, there are special installation requirements. Consult factory for details.
4
BEFORE INSTALLATION
Raypak strongly recommends that this manual be re­viewed thoroughly before installing your Hi Delta heater. Please review the General Safety information before installing the heater. Factory warranty does not
pply to heaters that have been improperly installed or
a operated. (Refer to the warranty at the back of this manual.) Installation and service must be performed by a qualified installer, service agency or gas supplier. If, after reviewing this manual, you still have questions which this manual does not answer, please contact the manufacturer or your local Raypak representative.
Thank you for purchasing a Raypak product. We hope you will be satisfied with the high quality and durability of our equipment.
Product Receipt
On receipt of your heater it is suggested that you visu­ally check for external damage to the shipping crate. If the crate is damaged, make a note to that effect on the Bill of Lading when signing for the shipment. Remove the heater from the shipping packaging. Report any damage to the carrier immediately.
On occasion, items are shipped loose. Be sure that you receive the correct number of packages as indi­cated on the Bill of Lading.
Claims for shortages and damages must be filed with the carrier by consignee. Permission to return goods must be received from the factory prior to shipping. Goods returned to the factory without an authorized Returned Goods Receipt number will not be accepted. All returned goods are subject to a restocking charge.
When ordering parts, you must specify the model and serial number of the heater. When ordering under war­ranty conditions, you must also specify the date of installation.
Purchased parts are subject to replacement only under the manufacturer’s warranty. Debits for defec­tive replacement parts will not be accepted and will be replaced in kind only per Raypak’s standard war­ranties.
Model Identification
The model identification number and heater serial number are found on the heater rating plate located on the lower right outside jacket of the heater. The model
number will have the form H9-1262C or similar
epending on the heater size and configuration. The
d letter(s) in the first group of characters identifies the application (H = Hydronic Heating, WH = Domestic
®
Hot Water, P = Pool). The number which follows iden-
ifies the firing mode ( 3 = 2-stage, 8 = 3-stage and 9
t = 4-stage). The second group of characters identifies the size of the heater (four numbers representing the approximate MBTUH input), and, where applicable, a letter, indicating the manufacturing series.
Ratings and Certifications
Standards:
ANSI Z21.13 · CSA 4.9 - latest edition, Gas-Fired Hot Water Boilers
CAN1 3.1 - latest edition, Industrial and Commercial Gas-Fired Package Boilers
ANSI Z21.56 · CSA 4.7 - latest edition Gas-Fired Pool Heaters
ANSI Z21.10.3 · CSA 4.3 - latest edition Gas Water Heaters
CSA certified compliance with California AB1953 and Vermont Legislative Act 193 requirements.
All Raypak heaters are National Board registered, and design-certified and tested by the Canadian Standards Association (CSA) for the U.S. and Canada. Each heater is constructed in accordance with Section IV of the American Society of Mechanical Engineers (ASME) Heater Pressure Vessel Code and bears the ASME stamp. The heater also complies with the latest edition of ASHRAE 90.1 Standard.
WARNING: Altering any Raypak pressure vessel by installing replacement heat exchangers, tube bundle headers, or any ASME parts not manufactured and/or approved by Raypak will instantly void the ASME and CSA ratings of the vessel and any Raypak warranty on the vessel. Altering the ASME or CSA ratings of the vessel also violates national, state, and local approval codes.
Installations at Elevation
Rated inputs are suitable for up to 4,500 ft elevation without de-rating. Consult the factory for installations at altitudes over 4,500 ft above sea level. Orifices are not affected.
5
Component Locations
Fig. 1: Component Locations – Back
Fig. 2: Component Locations – Left Side
Panels removed for clarity
Fig. 3: Component Locations – Front
6
General Information
Model
No.
M
odel
No.
Burners
Quantity of Vent Size (in.)
Gas
Valves
Blowers Flue Intake
992C 11 2 + 1* 2 10 10
1262C 14 3 + 1* 2 12 10
1532C 17 4 2 12 10
1802C 20 4 2 14 10
2002C 23 5 3 14 10
2072C 23 5 3 14 10
2342C 26 5 3 16 10
*Hidden solenoid valve located inside of air plenum.
Table A: Basic Data
Burners per Valve Stages % Fire at Stages
1 1A 2 3 4 1 2 3 4 1 2 3 4
992C 6 3 2 1 1, 2 1, 2, 3 54 82 100
1262C 5 3 3 3 1 1, 2 1, 2, 3 1, 2, 3, 4 36 57 79 100
1532C 6 4 4 3 1 1, 2 1, 2, 3 1, 2, 3, 4 35 59 82 100
1802C 6 4 5 5 1 1, 2 1, 2, 3 1, 2, 3, 4 30 50 75 100
2002C 4 5 5 5 4 1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 39 61 83 100
2072C 4 5 5 5 4 1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 39 61 83 100
2342C 5 6 5 5 5 1, 1A 1, 1A, 2 1, 1A, 2, 3 1, 1A, 2, 3, 4 42 62 81 100
Table B: Manifold Data
7
GENERAL SAFETY
Water temperature over 125°F can c a us e i ns t a nt se v e re bu r n s o r d e a th from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
See instruction manual before set­ting temperature at water heater.
Feel water before bathing or show­ering.
Temperature limiting valves are available, see manual.
Water
Temp.
Time to Produce Serious
Burn
120°F More than 5 minutes
125°F 1-1/2 to 2 minutes
130°F About 30 seconds
135°F About 10 seconds
140°F Less than 5 seconds
145°F Less than 3 seconds
150°F About 1-1/2 seconds
155°F About 1 second
Table courtesy of The Shriners Burn Institute
To meet commercial hot water use needs, the high limit safety control on this water heater is adjustable up to 210°F. However, water temperatures over 125°F can cause instant severe burns or death from scalds. When supplying general purpose hot water, the rec­ommended initial setting for the temperature control is 125°F.
Safety and energy conservation are factors to be con­sidered when setting the water temperature on the thermostat. The most energy-efficient operation will result when the temperature setting is the lowest that satisfies the needs of the application.
Water temperature over 125°F can cause instant severe burns or death from scalds. Children, disabled and elderly are at highest risk of being scalded.
Feel water before bathing or showering.
Temperature limiting valves are available.
NOTE: When this water heater is supplying general purpose hot water for use by individuals, a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of scald injury. Contact a licensed plumber or the local plumbing authority for further information.
Maximum water temperatures occur just after the heater’s burner has shut off. To determine the water temperature being delivered, turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer.
Time/Temperature Relationships in Scalds
The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications.
Table C: Time to Produce Serious Burn
8
The temperature of the water in the heater can be reg­ulated by adjusting the setpoint, this process is fully
escribed in the manual in the “Controls” section (see
d page 47).
For accurate control of water temperature, the sensors must be properly installed according with the piping configuration, see “Applications & Modes” section for detailed information (see page 19).
CAUTION: Hotter water increases the risk of scald­ing! There is a hot water scald potential if the thermostat is set too high.
Temperature & Pressure Gauge
The temperature and pressure gauge is factory­mounted in the in/out header.
INSTALLATION
Stacking
Hi Delta units can be stacked two units high with an
ptional stacking rack. A stacking kit (sales order
o option X-1) is available from Raypak for this type of installation. For installations above grade, a reinforc­ing kit (sales order option X-2) may also be required.
CAUTION: The heaters should be located in an area where water leakage will not result in damage to the area adjacent to the appliances or to the structure. When such locations cannot be avoided, it is recommended that a suitable catch pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.
Installation Codes
Installations must follow these codes:
Local, state, provincial, and national codes, laws, regulations and ordinances
National Fuel Gas Code, ANSI Z223.1/NFPA 54 – latest edition (NFGC)
National Electrical Code, ANSI/NFPA 70 - latest edition (NEC)
Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1, when required (CSD-1)
For Canada only: CAN/CSA B149 Installation Code (B149) and CSA C22.1 C.E.C. Part 1 (C22.1)
Equipment Base
The heater should be mounted on a level, structurally sound surface. The heater is approved for installation on a combustible surface but must NEVER be installed on carpeting. Gas-fueled equipment installed in enclosed parking garages must be located at least 18 in. above the floor.
Fig. 4: Typical Stacked Installation
9
U.S. Installations
1
Canadian Installations
2
A
Clearance above grade, veranda, porch, deck, or balcony
1 ft (30 cm) 1 ft (30 cm)
B
Clearance to window or door that may be opened
4 ft (1.2m) below or to side
of opening; 1 foot (30 cm)
above opening
3 ft (91 cm)
C Clearance to permanently closed window * *
D
Vertical clearance to ventilated soffit located above the terminal within a horizontal dis­tance of 2 ft (61cm) from the centerline of the terminal
5 ft (1.5m) *
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner 6 ft (1.83m) *
H
Clearance to each side of center line ex­tended above meter/regulator assembly
*
3 ft (91 cm) within a height
15 ft above the me-
ter/regulator assembly
I Clearance to service regulator vent outlet * 6 ft (1.83m)
J
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
4 ft (1.2m) below or to side
of opening; 1 ft (30 cm)
above opening
3 ft (91 cm)
K Clearance to mechanical air supply inlet
3 ft (91 cm) above if within
10 ft (3m) horizontally
6 ft (1.83m)
L
Clearance above paved sidewalk or paved driveway located on public property
7 ft (2.13m)
7 ft (2.13m) t
M
Clearance under veranda, porch, deck or balcony
* 12 in. (30 cm) TT
1
In accordance with the current ANSI Z223.1/NFPA 54 N ational Fuel Gas Code
2
In accordance with the current CAN/CSA-B149 Installation Codes
t Vent terminal shall not terminate directly above sidewalk or paved driveway located between 2 single family dwellings that se rves
both dwellings
TT Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor and top of term inal and
underside of veranda, porch, deck or balcony is greater than 1 ft (30cm)
* Clearances in accordance with local installation codes and the requirements of the gas supplier
Fig. 5: Minimum Clearances from Vent/Air Inlet Terminations – Indoor and Outdoor Installations
Table D: Vent/Air Inlet Termination Clearances
10
In addition, the heater shall be installed such that the
Heater
Side
Minimum Clearance
from Combustible
Surfaces
Recommended
Service
Clearance
Floor* 0” 0”
Rear 1” 6”
Water Side 12” 24”
Other Side 1” 24”
Top 1” 6”
Front Open 24”
Vent 2” 2”
Heater
Side
Min. C learance
from C ombustible
Surfaces
Recommended
Service
Clearance
Front Open 24”
Rear 12” 6”
Water Side 36” 36”
Other Side 36” 36”
Top Unobstructed 36”
Vent N/A N/A
gas ignition system components are protected from water (dripping, spraying, rain, etc.) during appliance operation or service (circulator replacement, control replacement, etc.).
Clearances
Indoor Installations
* DO NOT install on carpeting.
Table E: Clearances – Indoor Installations
When installed according to the listed minimum clear­ances from combustible construction, these heaters can still be serviced without removing permanent structural construction around the heater. Combustible clearances can be reduced per the NFGC; see para­graph 10.2.3. However, for ease of servicing, we recommend a clearance of at least 24 in. in front, and at least 12 in. on the water connection side. This will allow the heater to be serviced in its installed location without movement or removal of the heater.
Service clearances less than the minimums may require removal of the heater to service either the heat exchanger or the burner tray. In either case, the heater must be installed in a manner that will enable the heater to be serviced without removing any structure around the heater.
Outdoor Installations
These heaters are design-certified for outdoor installa­tion. Heaters must not be installed under an overhang that is less than 3 ft from the top of the heater. Three sides must be open in the area under the overhang. Roof water drainage must be diverted away from heaters installed under overhangs.
Top View
Fig. 6: Minimum Clearances from Combustible
Surfaces – Indoor Installations
Front View
Table F: Clearances – Outdoor Installations
These clearances are required when the outdoor vent cap is used. If installing the heater outdoors with a vent stack, the indoor clearances may be utilized.
The combustion air intake hood MUST be used for outdoor installations. The hood is shipped loose and installed on the side of the heater over the filter box at the jobsite.
11
1. Remove the four screws and the dust cover from the right-hand side of the heater.
2. Remove the four screws and the air filter bracket from the left-hand side of the heater.
Front View
Side View
Fig. 7: Minimum Clearances from Combustible
Surfaces – Outdoor Installations
Combustion and Ventilation Air
NOTE: Use of the heater in construction areas
where fine particulate matter, such as concrete or dry-wall dust, is present may result in damage to the heater that is not covered by the warranty. If operated in a construction environment, a clean source of combustion air must be provided directly to the heater.
Indoor Units
The heater must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be sup­plied via conventional means where combustion air is drawn from the area immediately surrounding the heater, or via direct vent, where combustion air is drawn directly from outside. All installations must com­ply with the requirements of the NFGC (U.S.) and B149 (Canada), and all local codes.
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty. (See the Appendix.)
3. Reverse the components and reattach in the new location, making sure that the air filter locking bracket is on the bottom. (The air filter locking bracket is reversible.)
Direct Vent
If outside air is drawn through the intake pipe directly to the unit for combustion:
1. Install combustion air direct vent in accordance with Fig. 31 (horizontal) or Fig. 32 (vertical) of this manual (pages 33 and 34, respectively).
2. Ventilation of the space occupied by the heater(s) is recommended and can be provided by an open­ing(s) for ventilation air at within 12” of the ceiling or the highest practical point communicating with the outdoors. The total cross-sectional area should be at least 1 in.2of free area per 20,000 BTUH (111 mm2per kW) of total input rating of all equipment in the room when the opening is com­municating directly with the outdoors or through vertical duct(s). The total cross-sectional area should be at least 1 in.2of free area per 10,000 BTUH (222 mm2per kW) of total input rating of all equipment in the room when the opening is com­municating with the outdoors through horizontal duct(s). Damage to the equipment due to inade­quate ventilation of the space is not a warrantable failure.
NOTE: In cold climates, and to mitigate potential freeze-up, Raypak highly recommends the installa­tion of a motorized sealed damper to prevent the circulation of cold air through the heater during the non-operating hours.
Direct-Ducted Combustion Air
NOTE: It is recommended that the intake vent be
insulated to minimize sweating.
Reversing Air Filter
Follow these instructions to change the air duct con­nection from the left-hand side (standard) to the right-hand side:
In certain applications it may be desirable to duct the combustion air directly to the heater. This should be done with PVC, CPVC or single-wall galvanized duct­ing. The duct will attach directly to the collar on the air filter housing located on the side of the heater. The ducting is attached to the air filter housing collar using
12
three or four sheet metal screws (not supplied) equal­ly distributed around the circumference of the duct. All ducting should be self-supported. The filter housing is not designed to support the air duct.
CAUTION: Use TruSeal combustion air if damaging airborne contaminants are or will be present in the heater area. See the Appendix regarding air contamination.
TruSeal®Combustion Air
In certain applications it may be necessary to utilize the TruSeal option (sales order option D-21 or D-22) and duct the combustion air directly to the blower. Combustion air may be ducted directly to the heater by using PVC, CPVC or sealed single-wall galvanized ducting. The duct will attach directly to the air collar lo­cated on the side of the heater, using three or four sheet metal screws (not supplied) equally positioned around the circumference of the duct. The screws and duct connection point must be sealed with RTV (not supplied). An in-line intake air filter kit (sales order option D-17) must be installed in the combustion air duct. TruSeal is generally used when damaging con­taminants are present in the mechanical room.
TruSeal heater connection points are available as fol­lows:
992C to 1802C Left side – standard
Right side – optional
2002C to 2342C Right side only
space shall be considered in making this determina­tion. Each opening shall have a minimum free area of 1 in.2 per 1,000 BTUH (2,225 mm2per kW) of the total input rating of all gas utilization equipment in the con­fined space, but not less than 100 in.2(645 cm2). One opening shall commence within 12 in. (305 mm) of the top, and one opening shall commence within 12 in. (305 mm) of the bottom of the enclosure. The mini­mum dimension of air openings shall be not less than 3 in. (76 mm) in any direction.
All Air from Outdoors
The confined space shall communicate with the out­doors in accordance with one of the methods below. The minimum dimension of air openings shall not be less than 3 in. (76 mm) in any direction. Where ducts are used, they shall be of the same cross-sectional area as the net free area of the openings to which they connect.
1. Two permanent openings, one commencing within 12 in. (305 mm) of the top, and one com­mencing within 12 in. (305 mm) of the bottom of the enclosure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely com­municate with the outdoors.
a. Where directly communicating with the out-
doors or where communicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in. 4,000 BTUH (550 mm2per kW) of total input rating of all equipment in the enclosure.
2
per
CAUTION: This type of installation is recommended if damaging airborne contaminants are or will be present in the heater area. See the Appendix regarding air contamination.
Conventional Combustion Air Supply
U.S. Installations
All Air from Inside the Building
The confined space shall be provided with TWO per­manent openings communicating directly with an additional room(s) of sufficient volume so that the com­bined volume of all spaces meets the criteria for a room large in comparison (NFGC). The total input of all gas utilization equipment installed in the combined
b. Where communicating with the outdoors
through horizontal ducts, each opening shall have a minimum free area of 1 in.2per 2,000 BTUH (1,100 mm2per kW) of total input rat­ing of all equipment in the enclosure.
2. One permanent opening, commencing within 12 in. (305 mm) of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (152 mm) from the front of the appliance. The opening shall directly communicate with the out­doors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors, and shall have a minimum free area of:
a. 1 in.2per 3,000 BTUH (740 mm2per kW) of
the total input rating of all equipment located in the enclosure, and
13
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use one permanent opening method if the equipment room is under negative pressure conditions or the equipment is common
ented with other gas-fired appliances.
v
Canadian Installations
of not less than 1 in.2for each 30,000 BTUH mm per kW) of total rated input of the burner(s), and the location of the opening(s) shall not interfere with the intended purpose of the opening(s) for ventilation air referred to in (1). This opening(s) can be ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down 18 in. (450 mm) from the floor, but not near piping.
2
CAUTION: All combustion air must be drawn from the air outside of the building; the mechanical equip­ment room must communicate directly with the outdoors.
1. Ventilation of the space occupied by the heater shall be provided by an opening(s) for ventilation air at the highest practical point communicating with the outdoors. The total cross-sectional area of such an opening(s) shall be at least 10% of the area required in 2. and 3. (below), but in no case shall the cross-sectional area be less than 10 in. (65 cm2).
2. For heaters using a barometric damper in the vent system there shall be a permanent air supply opening(s) having a cross section area of not less than 1 in.2per 7,000 BTUH (320 mm2per kW) up to and including 1 million BTUH, plus 1 in.2per 14,000 BTUH (160 mm2per kW) in excess of 1 million BTUH. This opening(s) shall be either located at or ducted to a point not more than 18 in. (450 mm) nor less than 6 in. (152 mm) above the floor level. The duct can also “goose neck” through the roof. The duct is preferred to be straight down and terminated 18 in. (450 mm) from the floor, but not near piping. This air supply opening require­ment shall be in addition to the air opening for ventilation air required in 1. (above).
4. Refer to B149 Installation code for additional infor­mation.
Water Piping
General
The heater should be located so that any water leaks will not cause damage to the adjacent area or struc-
tures.
2
CAUTION: This heater requires forced water circulation when the burner is operating. See Table G and Table H for minimum and maximum flow rates and water pump selection. The pump must be interlocked with the heater to prevent heater operation without water circulation.
NOTE: Minimum pipe size for in/out connections is 2 1⁄2 NPT. Verify proper flow rates and ∆T as instruct- ed in this manual.
Reversing Water Connections
Follow these instructions to change the water connec­tions from the left-hand side (standard) to the right-hand side.
WARNING: Care must be taken to ensure that the equipment room is not under negative pressure conditions or that the equipment is not common­vented with other gas-fired appliances.
3. For heaters not using a barometric damper in the vent system, and when air supply is provided by natural air flow from outdoors for a power burner and there is no draft regulator, drafthood or similar flue gas dilution device installed in the same space, in addition to the opening for ventilation air required in 1., there shall be a permanent air sup­ply opening(s) having a total cross-sectional area
1. Disconnect all electrical power from the heater (if applicable).
2. Label all electrical connections and conduit lines. This may include the flow switch, low water cut-off probe and/or pump.
3. Disconnect or isolate the main gas pipe from the heater (if applicable).
4. Remove both in/out and return header access panels by removing all sheet metal screws.
14
5. Remove all plumbing fittings to the header. This will include both inlet and outlet water pipe unions and the pressure relief valve and drain piping.
6. Remove limits, control bulbs and/or thermocou­ples.
. Remove the eight flange nuts and the in/out head-
7
er from the left-hand side.
8. Remove the eight flange nuts and the return head­er from the right-hand side.
9. Reverse the headers to the new location.
10. Install NEW red beveled O-rings flush against both tube sheets with the bevel facing outward.
Hydrostatic Test
Unlike many types of heaters, this heater does not re­quire hydrostatic testing prior to being placed in operation. The heat exchanger has already been fac­tory-tested and is rated for 160 psi operating pressure. However, Raypak does recommend hydrostatic test-
ng of the piping connections to the heater and the rest
i of the system prior to operation. This is particularly true for hydronic systems using expensive glycol­based anti-freeze. Raypak recommends conducting the hydrostatic test before connecting gas piping or electrical supply.
Leaks must be repaired at once to prevent damage to the heater. NEVER use petroleum-based stop-leak compounds.
11. Push the header firmly against the O-rings. Install and tighten the flange nuts onto the stud bolts until finger tight.
12. Slowly tighten the flange nuts, starting from the center nut (number 1) in Fig. 8 and working se­quentially around the header as indicated. Torque all nuts to 25 ft/lb. DO NOT OVER-TIGHTEN.
13. Re-route the capillary(s), wiring etc. to the new location, adding thermal paste and shim to the capillary well.
To perform hydrostatic test:
1. Connect fill water supply. With bleed valve open, fill heater with water. When water flows from bleed valve, shut off water. Close bleed valve. Carefully fill the rest of the system, making sure to eliminate any entrapped air by using high-point vents. Close feed valve. Test at standard operating pressure for at least 24 hours.
2. Make sure constant gauge pressure has been maintained throughout test.
3. Check for leaks. Repair if found.
Cold Water Protection (CWP)
This heater must operate with a stable inlet tempera­ture of 105°F (41°C), long periods of operation with temperatures below 105°F (41°C) can excessively cool the products of combustion, resulting in collection of condensate in the heat exchanger, damaging the heat exchanger, combustion chamber, significantly reducing the life of the equipment. The following appli­cations are approved configurations supported by Raypak for CWP systems.
Fig. 8: Torque Sequence
Relief Valve Piping
WARNING: Pressure relief valve discharge piping
must be piped near the floor and close to a drain to eliminate the potential of severe burns. Do not pipe to any area where freezing could occur. Refer to local codes.
A bypass allows part of the heater discharge water to be mixed with the cooler water returning to the heater inlet, to increase the heater inlet temperature above 105°F (41°C). This precautionary measure should pre­vent the products of combustion from condensing in most installations.
15
AUTION: Damage due to internal condensation
C
may occur if the heater inlet water temperature does
ot exceed 105°F (41°C) within 7 minutes of start-
n up. Warranty claims will be denied for damage or failures caused by condensation.
models: MIX TYPE = VALVE
H
Heating Systems, where the inlet water temperature remains below 105°F (41°C) must
have cold water
protection. Known protection methods consist of mix-
ing heated outlet water with the inlet water using a bypass to raise the inlet to 105°F (41°C) or higher. Once the system is heated up and has return water temperatures of 105°F (41°C) or higher, the mixing of outlet water with inlet water is no longer needed and the bypass can be shut off. If the bypass is not shut off as the system heats up, the outlet temperature may continue to climb and trip the high limit, thereby shut­ting down the heater. Thus an automatic valve system, such as a three-way proportional valve to control the bypass, should be used. The integrated VERSA IC control system provides automatic functionality to con­trol a proportional 3-way valve to provide Cold Water Protection for Single or Cascade configurations. See Fig. 9.
models: MIX TYPE = PUMP
H
models include a second option for individual Cold
H Water Protection method (“PUMP”). MIX TYPE =
UMP uses a Variable Speed Pump as a CWP mech-
P anism recommended for those systems that require low-lead/non-ferrous plumbing. Applications that require a working setpoint over 150°F must use an H model with a storage tank. See Figs.10,11 and 12.
®
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 9: CWP-Hydronic Single-Boiler (BOIL 3-way)
Mode 1
Fig. 10: H - Hydronic - Single Boiler with CWP (VS
Pump - MIX TYPE = 2)
Fig. 11: Low Temp Process - Open Loop: H model,
Single with Storage Tank
16
Fig. 12: Low Temp Process - Open Loop: H model, Cascade with Storage Tank
Cold Water Protection: WH models
Direct DHW heating systems utilize a variable speed pump arrangement (MIX TYPE = PUMP) to keep the heater inlet at or above 105°F (41°C). The integrated VERSA IC control system provides functionality to control a single variable speed injection pump via an added inverter drive to provide Cold Water Protection to the system.
See Fig. 13 as an example of a single heater applica­tion. For more information regarding this function see VERSA IC manual, catalog 5000.72.
Hydronic Heating
System Design
Hot water heating systems all have unique levels of operating diversity. Raypak equipment design utilizes as little water mass as possible to ensure maximum operating efficiency. Primary / Secondary piping arrangement is the method recommended and the only method supported by Raypak for installation of Hi Delta equipment. Proper system design should always include system flow in excess of the connected boiler flow for proper operation (Boiler Flow + 15% = Min. System Flow). When appropriate, a Buffer/De­coupler Tank can be used where system flow may be reduced below the connected boiler flow. Failure to design for adequate system flow (i.e. bypasses, 3-way control valves, flow limiting balance devices, buffer tanks, etc.) will result in boiler short-cycling and poor system performance. Always contact your local Raypak representative for system design assistance to avoid these issues.
Pump Selection
Fig. 13: WH Direct DHW - Single Heater with CWP (VS
Pump - MIX TYPE = 2)
In order to ensure proper performance of your heater system, you must install a correctly sized pump. Ray­pak recommends using a 20°F ∆T as design ∆T. (∆T is the temperature difference between the inlet and outlet water when the heater is firing at full rate). If a ∆T of larger than 20°F is necessary, see Table G for flow rate requirements.
17
Model
o.
N
0ºF∆T
2
gpm ∆P (ft) gpm ∆P (ft) gpm ∆P (ft) gpm ∆P (ft) ∆T gpm ∆P (ft) ∆T
0ºF∆T
3
9ºF∆T
3
in. Flow
M
ax. Flow
M
992C 83 5.2 55 2.3 43 1.4 43 1.4 39 132 13.1 13
1262C 106 9.6 71 4.3 54 2.5 54 2.5 39 132 14.8 16
1532C 129 15.7 86 7.1 66 4.2 66 4.2 39 132 16.5 19
1802C N/A N/A 101 10.7 78 6.3 78 6.3 39 132 18.3 23
2002C N/A N/A 112 13.8 86 8.3 86 8.3 39 132 19.0 25
2072C N/A N/A 116 14.8 89 8.9 89 8.9 39 132 19.0 26
2342C N/A N/A 132 21.1 101 12.7 101 12.7 39 132 21.4 30
Notes: 1. Basis for minimum flow is 40°F ∆T. Basis for maximum flow is 132 GPM.
Feedwater Regulator
2. Rear-mounted pumps may provide higher flow rates on smaller models than the system requirements
Table G: Heater Rates of Flow and Pressure Drops
an external source such as the Temp Tracker MOD+ Hybrid sequencer (sales option B-36). Proper place-
Raypak recommends that a feedwater regulator be in­stalled and set at 12 psi minimum pressure at the highest point of the system. Install a check valve or back flow device upstream of the regulator, with a manual shut-off valve as required by local codes.
ment and method of installation are critical for proper operation of the system. (See Fig. 7) The sensor must be installed in a drywell in conjunction with heat con­ductive compound as shown in the following images. The drywell must be installed no more than 5 equiva­lent feet of pipe/tubing downstream of the de-coupler
Piping
and installed in such a way that ensures the sensor bulb is in the flow path.
All high points should be vented. Purge valves and a bypass valve should be installed. A heater installed above radiation level must be provided with a low wa­ter cut-off device (sales order option F-10). The heater, when used in connection with a refrigeration system,
CAUTION: Be careful when installing the drywell not to over-tighten the well as this can damage the well and may prevent the sensor from fitting property.
must be installed so that the chilled medium is piped in parallel with the heater with appropriate valves to pre-
Three-Way Valves
vent the chilled medium from entering the heater.
Valves designed to blend water temperatures or
The piping system of a hot water heater connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be
reduce water circulation through the heater should not be used. Raypak heaters are high-recovery, low-mass heaters which are not subject to thermal shock.
equipped with flow control valves or other automatic means to prevent gravity circulation of the heater water during the cooling cycle. It is highly recommend­ed that the piping be insulated.
Air-Separation/Expansion Tank
All heaters should be equipped with a properly sized expansion tank and air separator fitting as shown in Fig. 14.
System Sensor Installation
The System Sensor (S3) is required for all selectable mode unless the unit’s firing rate will be controlled by
Fig. 14: Air-Separation/Expansion Tank
18
PT
N
itting
F
hermal
T Paste
Fig. 15: System Sensor Installation
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 16: Single Heater - Space Heating Application
with Primary/Secondary Piping
Drywell
ystem
S Sensor (S3)
Fig. 17: MODE 1 - Single Boiler with
Primary/Secondary Piping
Mode 1 (Type H Units Only)
This mode selection is for hydronic heating systems with single or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air Reset (S4). The system temperature is controlled by the System sensor (S3). The Boiler Pump (P1) runs during any call for heat. The System Pump (P2) runs whenever the system is enabled for heating and the outdoor air temperature is lower than the warm weather shut down (WWSD) temperature setting (if utilized). The Boiler Pump is delayed “off” as user-defined in the BOILER menu and System Pump is delayed “off” as user-defined in the ADJUST menu.
Applications & Modes
The VERSA IC Control system is designed for a wide range of applications. The installer/design engineer should refer to the following Modes to determine which best fits the intended application and functionality for the unit being installed.
Type H models of Hi Delta have three modes available to them to address the various applications the units can be applied to. Type WH and P units will only have one configuration available to them.
For detailed information on the Versa IC control sys­tem, see Catalog 5000.72. This manual can be found in the document library at www.raypak.com
S1 - Outlet Sensor S2 – Inlet Sensor
Fig. 18: MODE 1 - Boiler Cascade with
Primary/Secondary Piping
NOTE: MODE 1 can also be used for process heat­ing applications in conjunction with a buffer/storage tank when operating temperatures above 150°F are
.
required. Care must be given to ensure water hard­ness is no more than 15 grains per gallon for scale free operation.
19
Fig. 19: MODE 2 - Single Boiler with Indirect
on System Loop
Mode 2 (Type H Units Only)
This mode selection is for hydronic heating systems with single or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air Reset (S4) with indirect DHW on the sys­tem loop (with or without priority). The system temperature is controlled by the System sensor (S3). The Indirect DHW sensor (S5) determines the indirect call/tank setpoint. The system temperature is boosted to Target Max when using the Indirect DHW sensor (S5) during an indirect call for heat. Priority mode tog­gles off the System Pump (P2) when an indirect call for heat is present. The Boiler Pump (P1) runs during any call for heat. The Indirect DHW Pump (P3) runs during an indirect call for heat with no “off” delay. The Boiler Pump (P1) is delayed “off” as user-defined in the BOILER menu and System Pump (P2) delay “off” as user-defined in the ADJUST menu. The System Pump (P2) runs whenever the system is enabled for heating and the outdoor air temperature is lower than the WWSD temperature setting (if utilized) unless an indi­rect call for heat is present with priority.
Mode 3 (Type H Units Only)
This mode selection is for hydronic heating systems with single or multiple boilers (Maximum 4 boilers) in primary/secondary piping configuration with or without Outdoor Air Reset (S4) with indirect DHW on the boiler
oop (with priority). The system temperature is con-
l trolled by the Supply sensor (S3) whenever the indirect call for heat is not active. The DHW Supply sensor (S5) determines the indirect call/tank setpoint. During an indirect call for heat the boiler firing rate is determined by the water temperature at the Indirect Supply sensor (S6) and the Target Max setting when using the Indirect DHW sensor (S5). The Boiler Pump (P1) runs during all heat calls regardless of priority. The Indirect DHW Pump (P3) runs during an indirect call for heat with no “off” delay. The Boiler Pump (P1) is delayed “off” as user-defined in the BOILER menu and System Pump (P2) delay “off” as user-defined in the ADJUST menu. The system pump (P2) runs whenever the system is enabled for heating and the outdoor air temperature is lower than the WWSD tem­perature setting (if utilized) unless an indirect call for heat is present.
NOTE: A Tank Aquastat can be used in lieu of the Indirect DHW Sensor (S5). See the Versa IC manual for additional details.
Fig. 20: MODE 3 - Single Boiler with Indirect
on Boiler Loop
*Maximum 4 times the pipe diameter or 12”, whichever is less.
Fig. 21: Dual Heaters (Reverse/Return)
with Primary/Secondary Piping
Domestic Hot Water
When designing the water piping system for domestic hot water applications, water hardness should be con­sidered. Table H indicates the suggested flow rates for soft, medium and hard water. Water hardness is ex­pressed in grains per gallon.
20
Fig. 22: Single Domestic Hot Water Heater and Storage
Tank
WH – Direct DHW Configuration
When the unit is ordered as a “WH” configuration the only application available to it is direct DHW with sin­gle or multiple heaters (Maximum 4 heaters). The tank temperature is controlled by the System sensor (S3). The Boiler Pump (P1) runs during any call for heat. The System Pump (P2) output is active whenever the system is enabled. The Boiler Pump is delayed “off” after the Tank Target temperature is achieved and as user defined in the BOILER menu.
Potable Water and Space Heating
CAUTION: When this heater is used for both
otable water and space heating, observe the
p following to ensure proper operation.
1. All piping materials and components connected to the water heater for the space heating application shall be suitable for use with potable water.
2. Toxic chemicals, such as used for boiler treatment, shall not be introduced into the potable water used for space heating.
3. If the heater will be used to supply potable water, it shall not be connected to any heating system or components previously used with a non-potable water heating appliance.
4. When the system requires water for space heating at temperatures higher than 140°F (60°C), a means such as a mixing valve shall be installed to temper the water in order to reduce scald hazard potential.
Automatic Chemical Feeders
Fig. 23: WH Units - Single Water Heater with Tank
H Units - Single Boiler with Process Tank
NOTE: WH units will operate to a maximum tank temperature of 150°F. For temperatures required above 150°F, an “H” model boiler must be used and great care must be given to ensure water hardness is no more than 15 grains per gallon for scale free operation. MODE 1 should be used and configured for setpoint operation for process heating applica­tions.
NOTE: If local codes require a vacuum relief valve, acquire one locally and install per valve manufacturer’s instructions.
All chemicals must be introduced and completely dilut­ed into the water before being circulated through the heater. High chemical concentrations will result when the pump is not running (e.g. overnight).
NOTE: High chemical concentrates from feeders that are out of adjustment will cause rapid corrosion to the heat exchanger. Such damage is not covered under the warranty.
NOTE: Failure of a heat exchanger due to lime scale build-up on the heating surface, low pH or other chemical imbalance is non-warrantable.
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty.
21
Model
No.
Soft* (3-4 grains per gallon) Medium (5-15 grains per gallon) Hard* (16+** grains per gallon)
T GPM P MTS SHL T GPM P MTS SHL T GPM P MTS SHL
992C 29 60 2.7 5.2 17 98 7.3 13.3 13 132 13.1 23.6
262C29
1
2
.4
½
7
4
2
.9
7
9
1
1511.3
1
½
1
9.4
2
6
1
3214.82½25.3
1
1532C 29 86 7.1 11.9 22 120 13.7 22.5 20 132 16.5 27.0
1802C 29 102 10.9 17.4 26 120 15.1 23.9 23 132 18.3 28.7
2002C 29 112 13.9 21.6 26 132 19.0 29.5 26 132 19.0 29.5
2072C 31 117 15.1 23.4 27 132 19.0 29.5 27 132 19.0 29.5
2342C 33 120 17.8 26.5 30 132 21.4 31.8 30 132 21.4 31.8
∆T = Temperature rise, °F ∆P = Pressure drop through heat exchanger, ft SHL = System head loss, ft. Includes 50 eq ft of tubing each way (total 100 eq ft). GPM = Gallons per minute, flow rate MTS = Minimum tubing size *Must utilize optional cupro-nickel tubes. **If over 25 grains per gallon, a water softener/treatment system must be utilized. Caution: For scale free operation with "Hard Water" (16-25 grains per gallon of total hardness), the operating control must NOT be set higher than 130 °F. For higher than 130 °F operation, a water softener/treatment system must be utilized.
Caution: Water softened below 3 grains per gallon is known to be aggressive and corrosive.
Table H: Domestic Water Heater Flow Rate Requirements
Pool Heating
CAUTION: Power to the heater should be
interlocked with the main system pump to make sure the heater does not fire without the main system
pool. This arrangement permits operation of the heater at a temperature range that has been optimized both to avoid forming condensation on the heat exchanger and to mitigate the formation of scale in the heat exchanger tubes.
pump in operation. Improper flow control can damage the heater. Uncontrolled flow (too high) or restricted flow (too low) can seriously damage the heater. Follow these instructions to make sure your heater is properly installed.
All Raypak pool heaters are certified to ANSI Z21.56, which is the nationally recognized standard for swim-
For a Pool heating application, always verify that the Hi Delta unit has been ordered as a pool heater. To avoid issues related to high temperatures not appropri­ate to a pool application.
NOTE: The recommended setting for the outlet thermostat is 110°F.
ming pools. Some heaters being sold in the marketplace for heating commercial swimming pools are often certified as hot water boilers or water heaters. Regardless of which standard they are certi­fied to, they are generally trimmed out either by the manufacturer or the installer with controls that are suit­able for maintaining normal swimming pool temperatures and water conditions.
The P-992C-2342C models are configured to accom­modate locating the outlet temperature controller in the pool system piping that supplies the heated water to the pool. This arrangement facilitates controlling or limiting the temperature of the water supplied to the pool. The heater must be plumbed in a primary/sec­ondary arrangement, wherein only a portion of the water flowing in the piping system is pulled off, heated, and then returned to the system. The water coming out of the heater is mixed with the filtered water in the main pipe and thus tempered before returning to the
The Hi Delta pool heater is offered with bypass options: manual H-Bypass, or automatic Cold Water Run (CWR) bypass made of CPVC. These arrange­ments both blend outlet water with the inlet water to increase the inlet water temperature, thereby reducing the likelihood of condensation forming on the heat exchanger. The pump also serves to circulate water through the heater from the main system piping.
To complete installation of the heater, the system sen­sor (S3) must be installed in the return water line, upstream of the heater. The supplied electronic oper­ating control is configured to operate as the poolstat. A separate sensor (S6) is shipped loose to be installed in the system piping downstream of the heater outlet.
WARNING: To ensure safe operation of the Hi Delta heater, all plumbing from the heater to the main loop must be CPVC, copper or brass.
22
Loading...
+ 50 hidden pages