SOURCE HEAT PUMP SYSTEM
• Ideal for Low-temperature Systems
• High Recovery, High Efficiency
• Thermal Shock Proof
• Outdoor / Indoor
• Lightweight
Why use Raypak for heat pump applications?
Water source heat pump applications utilize low system
return temperatures, and most boiler designs, such as cast
iron and smooth tube, can not operate with system temperatures below 140°F without condensing. When a boiler
condenses, soot is formed which builds up on the heat
exchanger and burners and reduces its thermal efficiency.
This results in a noticeable loss of performance, higher
service and maintenance costs, and shortened boiler life.
Raypak boilers use copper finned tubes that can operate
at temperatures as low as 105°F without condensing. Most
other boilers must operate above 140°F to avoid condensation. This means that a Raypak boiler can provide added
years of reliable service with less maintenance in a much
wider range of applications.
FAST RESPONSE
Raypak copper finned tube boilers are much smaller and
lighter than any other boiler design. The operating weight
can be up to 35 times lighter due to water content alone!
Typical water content in a 624 MBH boiler is:
Raypak 1.4 gallons
Smooth tube 50.0 gallons
Cast Iron 55.0 gallons
CLOSED LOOP WATER
THERMAL SHOCK PROOF
Another prime concern of low-temperature hydronic systems is thermal shock. Thermal shock takes place when
the system temperature undergoes a rapid temperature
change. Both cast iron and multi-row, smooth tube boilers
are not designed to withstand thermal shock, and thermal
shock damage is not covered under warranty. Raypak’s
single-row heat exchanger and floating return header design is guaranteed against thermal shock for 20 years from
the date of installation. (For complete warranty information see Catalog No. 1900.10.)
COMPLETE PRODUCT LINE
Raypak has three models of boilers for Heat Pump applications: the atmospheric; the sealed combustion Hi DeltaTM;
and, the sealed combustion, high efficiency Advanced
Design Boiler.
As you can see, a Raypak boiler has minimal water content thus requiring no pick-up load factors. A hydronic system with a responsive Raypak boiler will operate more efficiently and under better control at all times.
Catalog No. 2000.32 J Effective: 2-15-03 Replaces: 11-15-99
With over 50 years of industry experience and a proven
reputation for high quality, reliable products, Raypak is
truly your “Hot Water Management Expert!”
Closed Loop Water Source Heat Pump
Fig# 9267.1
To properly adjust boiler temperatures for this application:
MODELS
1. Select the proper size of boiler based on the BTU
requirement to meet the maximum boiler load of the
water loop system.
2. Use boiler Type H4 (on/off). For Hi Delta 502 and
larger, convert the stage firing to on/off by connecting
a single-stage aquastat to stage 1 and connecting
jumpers to stages 2 and up.
3. For the pipe connecting the boiler and the system
loop main, select a size that is at least equal to the
inlet/outlet header connections of the boiler.
4. Install recommended boiler pump (from chart).
5. Check that both isolation valves are open.
6. Adjust Balancing Valve A 1/2 open and Balancing
Valve B fully open.
7. Fire the boiler and adjust Balancing Valve A to obtain
a boiler inlet temperature approximately 50°F greater
183-403
514-624
724-824
926-1125
1178-1826
2100-4001
302-502
652-752
902-992
1262
1532-1802
2002-2342
RAYTHERM™
HI DELTA™
than the system loop return temperature. (Turning
Valve A in the open direction will raise the boiler inlet
temperature and closing Valve A will lower the boiler
inlet temperature.) Note: Boiler inlet should never
be less than 105°F.
8. If the boiler inlet temperature remains less than 50°F
higher than system loop return temperature and Valve
A is fully open, leave Valve A fully open and throttle
This chart provides a pump with sufficient head to work with approximately 50 equivalent feet of piping from the boiler, to the system, and
back to the boiler. For example, the boiler may be 5 feet from the main
system piping and have four elbows. (Assuming an elbow has 10 equiva-
lent feet, this would be 40 feet + 5 + 5 = 50 feet).
500-750
1000
Valve B until the boiler inlet temperature rises to be
50°F higher than system loop return temperature.
9. Main loop and boiler temperatures should be checked
regularly throughout the heating season to prevent
boiler condensation. If balancing valves are adjusted
at the coldest loop temperature (typically 50°F) and
the boiler inlet temperature adjusted to 105°F, then the
entire heating season should have proper boiler
operation. The boiler inlet temperature can be higher
than 105°F without boiler damage, but operating at less
than 105°F inlet can cause damage from condensation.
Raypak, Inc. reserves the right to make product changes or improvements at any time without notification.
RECOMMENDED PUMP
TACO (or equivalent)
0012-1/7 Hp
120-1/6 Hp
1600-1/4 Hp
1630-1/2 Hp
1632-3/4 Hp
1638-2 Hp
120-1/6 Hp
1600-1/4 Hp
1630-1/2 Hp
1632-3/4 Hp
1634-1 Hp
1634-1 Hp
ADB™
1600-1/4 Hp
1630-1/2 Hp
©RAYPAK, INC., 2151 Eastman Road, Oxnard, CA 93030 (805) 562-5300 Fax (800) 872-9725
RAYPAK CANADA LIMITED, 2805 Slough St., Mississauga, Ontario Canada L4T 1G2 (905) 677-7999 Fax (905) 677-8036
www.raypak.com
Litho in U.S.A.